Initial calculations
When new designs are created, but no operating The MTBF of the whole system would calculate as
experience is available, how do designers estimate the MTBF = 1 / (56,380 x 10-9) = 17,737 hours,
product’s reliability? They rely on statistical measures
of each of the components and subassemblies included or just over 2 years. Not particularly good, so a careful
in their design. Manufacturers of components and designer would take steps to improve that.
Key factors Option for record keeping
Several important factors affect the calculated MTBF The operating hours and failures can be tracked from
(and the actual fleet MTBF experience) once the product day one, when the first system began operating.
is released, including: Alternately, running averages of failures over periods
• total number of components of 12 or 24 months may be kept. Tracking lifetime
• the FIT rate of each component failures and operating hours is more accurate, because
• the quality of the components it includes early troubles experienced when a new
• how conservatively the components are used VFD is first released. Running totals are quite valid,
however. They reflect the most recent experience and
One would expect a VFD with fewer components,
likely include experience from corrections applied
each with excellent FIT rate, (designed and used well
to fleet problems. Additionally, running averages for
under their published ratings) to have a much higher
MTBF calculations can quickly show product changes,
MTBF than a VFD designed and constructed less
for better or worse. A true product improvement could
conservatively, with cheaper components.
raise the MTBF. Or, a bad batch of components from
a vendor that causes drive problems would lower
Fewer components calculated MTBF. When the bad parts are replaced, the
Lower FIT rates MTBF improvement results rise quickly.
Applied well below ratings High MTBF
After all the careful design work is done and the VFD’s
High component quality inherent design reliability has been calculated, it is
the fleet reliability that really matters. For this reason,
TMEIC’s policy is to publish only fleet reliability once a
After a product is released relatively few months of VFD field experience is gained.
A manufacturer may continue to use the calculated
Example. Here are some fleet MTBF calculations based
MTBF in their advertisements for part or all of the life
on recent TMEIC experience for one of its drives:
of the product. The manufacturer may apply a factor
of conservatism or optimism to this calculated number
based on their previous experience with similar designs. Item Raw Value Conservative Value
In the hypothetical VFD example on the previous page,
in which we calculated MTBF of just over 2 years, Days per Month 30 30
the manufacturer may look to its fleet experience Daily Operating
and double that to 4 years for their advertising. Later, Percent Time 100% 80%
predicted MTBF can be based on fleet experience. (Conservative factor)
Availability vs. Reliability Running Hours
720 576
It is important here to distinguish between availability Per Month
and inherent reliability. Some manufacturers have Fleet of Running Drives 620 620
added additional components (such as bypass switches Monthly Fleet Hours 446,400 (B) 357,120 (B)
to cut out failed power cells) so that their VFD can
continue to operate at a lower power level after one of 12-Month Average of
the cells fails to operate. In order to have this bypass Significant Events/ 2.58 (A) 2.58 (A)
system work, the detection system, the power switches, Month
and other related components all have to be functional. Drive Hours
172,800 (C) 138,240 (C)
Although some increased operating availability may be Between Failures
gained, it requires more components. It may even Hours/Year 8,760 8,760
cover up inherent unreliability issues. This is one reason
MTBF Years Between
why TMEIC chooses not to add such components 19.7 (D) 15.8 (D)
Significant Events
that will decrease reliability in order to gain possible
higher availability.
Fleet reliability In the above example, 446,400 monthly fleet hours
Another method of calculating MTBF uses carefully kept (B) / 2.58 failures per month (A) = 172,800 average
equipment failure records of the operating fleet of VFDs. hours per failure (C). Dividing by 8,760 hours per year
This method requires the accumulation of VFD fleet yields an MTBF of 19.7 years. A conservative factor of
operating hours. MTBF is calculated by dividing this 80% reduces this to 15.8 years (D). This factor takes
figure by the number of failures in the same period. into account that not all drives may be operating in a
particular month and that some events may not have
been reported. Using the more conservative 15.8 year
Operating Hours (D) value easily allows truthful advertising that states
MTBF = _______________________
“drive reliability is greater than 15 years.”
Failures During Period
Basic ground rules • Factory assembly – Careful procedures are
Some basic ground rules and definitions have been followed in important areas, including meticulous
established for gathering such information. These power and control wiring, and properly torqued
include the following: fasteners for mechanical and electrical joints.
What are significant events? • Factory testing – These include extremes of the
In general, they are events that are the result of TMEIC intended operational, electrical, and mechanical
hardware or system failures that stop operation of the environment. Critical components such as the
drive. These include: microprocessor boards are thermally cycled for
• Events such as non-resettable trips that require several hours to ensure proper operation.
hardware replacement or repair, replacement of Other key reliability factors
blown fuses, and so forth. Other not-so-obvious factors can greatly affect the VFDs
• Events that result from failure or misoperation of in service reliability. These include, but are not limited
internal drive components supplied and included to, critical items such as the following:
by TMEIC, such as breakers, inductors, power • Experienced-based VFD application engineering.
supplies, and so forth.
• Selecting and matching the VFD to the required
What events are excluded from MTBF?
user or OEM environment, process loads, and
• Events that happen before commissioning is
electrical system.
complete (even during commissioning) are not
counted, but they are analyzed for improvement. • VFD installation guidance and commissioning
• Events occurring from a problem after a solution services ensure proper equipment setup and
has been identified (like firmware changes) while interconnection with user equipment and
the solution is being applied to the fleet. processes.
• Events that are the result of customer equipment • Regular preventive maintenance after equipment
or site conditions (wiring and cable or connections, is in service maximizes equipment life.
dust, over-temperature in control room, poor TMEIC Drive Fleet MTBF
maintenance, and so forth). December 2016 fleet records for TMEIC drives’ MTBF
• Events that, after individual engineering and/or are summarized below:
factory review, result in no failure being found
Fleet MTBF
(example – power module returned to factory TMEIC Family Notes
Years
and found OK – possibly was a loose or
contaminated fiber optic connector). Since 1st
TM-XL55, 75, 80, 85 44
shipment
• Events that result from normal wear – such as fans,
capacitor age, power supplies, and so forth, which Since 1st
TM-MV / MVG / MVG2 13
are past their recommended replacement period. shipment
Back to the beginning Since 1st
TM-MVe2 15
As we showed earlier, using fewer, higher-quality shipment
components applied at well below their published ratings 1-year rolling
Dura-Bilt5i MV 15
will produce superior results. Additionally, factory testing, average
factory assembly, and basic construction of the VFD Since 1st
equipment lends itself to reliable operation and practical TM30 / 50 / 70 / 70e2 22
shipment
service. Here are some examples of TMEIC practices.
• Stainless steel fittings and hardware are the rule Summary
for water-cooled drives. Plus, the insulated tubes We have discussed basic understandings of VFD
connecting to the power heatsinks are carefully reliability, including what it means, how it is calculated,
selected and tested to eliminate leaks, a prime and how good design and manufacturing maximize
source of unreliability in water-cooled VFDs. reliability. We have also shown how keeping accurate
records of fleet operating time and reported operational
• Dry, film-type capacitors are used instead of
problems allows the use of the actual fleet MTBF
electrolytic capacitors in multilevel drives
statistics. We have shown how this is the superior
(TMdrive-MVG2, MVe2) to eliminate problems
method to continuing the use of calculated MTBF after
with aging, high-maintenance, and shortened
the equipment is in service. All users would be well
equipment life.
advised to use fleet MTBF as their criteria in comparing
• Long-life variable-speed cooling fans (TM-MVe2) various medium voltage VFD offerings.
provide more than double the expected operating
lifetime versus traditional fixed-speed fans.
+1-540-283-2300 www.tmeic.com
2060 Cook Drive • Salem, VA 24153 USA
AE-041817
©2017 TMEIC Corporation. All Rights Reserved.