Pipe Culvert Design Calculation Report

This document summarizes the design calculations for a pipe culvert. It calculates the maximum headwater height, checks for inlet and outlet control, calculates flow velocity, and verifies that the culvert size is sufficient to handle the design discharge of 2 cubic meters per second. Key results are that the maximum headwater height is 1.02 meters, the culvert is under inlet control with a headwater height of 0.88 meters, and the flow velocity is calculated to be 2.842 meters per second.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
416 views3 pages

Pipe Culvert Design Calculation Report

This document summarizes the design calculations for a pipe culvert. It calculates the maximum headwater height, checks for inlet and outlet control, calculates flow velocity, and verifies that the culvert size is sufficient to handle the design discharge of 2 cubic meters per second. Key results are that the maximum headwater height is 1.02 meters, the culvert is under inlet control with a headwater height of 0.88 meters, and the flow velocity is calculated to be 2.842 meters per second.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
  • Pipe Culvert Calculation Summary: Provides a summary of proposed pipe culvert design calculations including discharges and headwaters.
  • Outlet Control Check: Contains calculations for checking outlet control conditions and flow velocity assumptions.
  • Flow Calculation Details: Details specific flow calculations using Colebrook-White’s Chart for design assessment.

Project :

Design By : Date :
Checked By : Verified By :
REF CALCULATION : PIPE CULVERT NO.3 REMARK
CH 3560

Proposed culvert size , D Dia = 1.00 m


Number of culvert , N = 2.0
RSUD Design Discharge, Q = 2.00 m3/s
Culvert Length, L = 28.000 m
Track Level = 2.972 m
Culvert IL
Inlet = 0.982 m Culvert
Outlet = 0.842 m Gradient
Ls = 0.140 m 1 : 200
Gradient S = 0.005
Acceptable Upstream Flood Level = 2.000 m
Min. Track level Above Head water = 0.300 m
Estimated downstream tailwater level = 1.000 m

Maximum Headwater height, Hwi is the lesser of the below condition;

i.) maximum practical culvert height:

2.972 - 0.3 - 0.982 = 1.69 m

ii.) Acceptable upstream flood level:

2 - 0.982 = 1.02 m
HW,max

Therefore, Hwmax = 1.02 m 1.02 m

Check for Inlet Control, Hwi,

Design Chart On Chart 18.A2 : Use,


18.A2 D = 1.00
Q/N = 2/2
= 1
From Chart,
HWi/D = 0.88
HWi = 0.88 x D
HWi = 0.88 x 1

= 0.88 m

HWi < HW,max HWi


0.88 m
Therefore, Pipe Culvert Dia is Sufficient

1
Project :

Design By : Date :
Checked By : Verified By :
REF CALCULATION : PIPE CULVERT NO.3 REMARK

Check for Outlet Control

Tw = 1 - 0.842

= 0.16 < D

Design Chart
18 A7 hc = 0.52 < D

(hc + D)/2 = 0.76 > Tw

\ ho = (hc + D)/2 = 0.76

Calculate Hwo
Hwo = H + ho - Ls

Design Chart
18.A9 Where ,
H = 0.23
Ls = 0.140

18.A9 Hwo = 0.23 + 0.76 - 0.14

HWo = 0.85

HWo < HWi Hwmax = Hwo

\ HW = Hwi 0.85 m

HW = 0.88

Flow Velocity

A = (𝜋D^2)/4 Assume
full flow
= 0.79 m2

s = '1 : 200

= 0.005

Q = AV

= 1.57 m3/s

2
Project :

Design By : Date :
Checked By : Verified By :
REF CALCULATION : PIPE CULVERT NO.3 REMARK

Design Chart From Colebrook-White's Chart for k = 0.6mm


18.A12

Qf = 400 L/s Qf > Qact

= 0.4 m3/s

Vf = 2.9 m/s

Design Chart the culvert not flowing full


18.A5
Q/Qf = 3.927
= 0.8

From Chart 18. A.5

V/Vf = 0.98

V = 2.842

y/D = 0.74

y = 0.74

HW =

EMBARKMENT
IL=

CULVERT
IL=3
Ls=

L =42

1
Project    :
Design By :
Date :
Checked By :
Verified By :
REF
CALCULATION : PIPE CULVERT NO.3
REMARK
CH 3560
Proposed cul
2
Project    :
Design By :
Date :
Checked By :
Verified By :
REF
CALCULATION : PIPE CULVERT NO.3
REMARK
Check for Outlet Con
3
Project    :
Design By :
Date :
Checked By :
Verified By :
REF
CALCULATION : PIPE CULVERT NO.3
REMARK
Design Chart 