Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
I/O solutions for the control cabinet
Interface
I/O solutions for the
I/O solutions for the control cabinet
TURCK is one of the world‘s leading interfaces) and RFID (radio frequency
groups of companies in the field of in identification), we offer effi cient solu
dustrial automation. With more than tions for manufacturing and process au
3.350 employees in 27 countries and tomation. State-of-the-art production fa
with sales partners in a further 60 coun cilities in Germany, Switzerland, the USA,
tries, we are always close to our custom Mexico and China enable o ur family-
ers worldwide. As specialists in sensor, owned enterprise to meet the require
fieldbus, connection and interface tech ments of the local markets q uickly and
nology, as well as HMI (human machine flexibly at any time.
The Program
2 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
The Company
pany
The Service
With almost 50 years of experience and tinuously improve the efficiency and
an extensive know-how, we can support productivity of your manufacturing p ro
you in every project phase with efficient cess or machine. The excellent quality of
services – from the initial analysis right our products, combined with the sup
through to the tailored solution and portive services of our specialists and a
commissioning of your application. The fast delivery service, ensures the high
prime objective of our activities is to con availability of your systems.
Regardless of whether you require soft www.turc k.com – offering 24/7 world
ware tools for programming, configu- wide access in nine different languages.
ra
tion or commissioning support, de Virtually all products and solutions can
tailed data sheets or CAD data in almost be accessed directly – clearly structured,
80 export formats, you will find the fully docu mented and free of charge,
right solution quickly in just a few clicks without any registration required.
at the TURCK product database at
The catalog offers a selection of flexible provide a brief description of the prod
I/O solutions for installation in the con uct group as well as a tabular o verview
trol cabinet. In addition to the IP20 I/O of the available products and functions.
systems BL20 and excom® the product The overview also provides p age refer
groups of IP20 I/O block modules and in ences on the detailed product informa
terface modules are introduced. A first tion, which are presented in the subse
overview offers the complete table of quent pages of the chapters. If you
contents. Detailed information on p rod already know the type code the type in
uct groups is provided in the relevant dex will guide you directly to the re
chapter. The first pages of these chapters quired product.
4 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
I/O solutions for the control cabinet
Table of Contents
Contents
BL20 – Modular I/O system in IP20 Short description and table of contents Page 6
Our strengths – Your advantages Page 8
System integration Page 10
Compact block I/O modules in IP20 Short description and table of contents Page 150
Our strengths – Your advantages Page 152
Type code Page 154
Interface technology
– Type code Page 300
– Interface modules series IM, IME, IMS, IMSP Page 302
Interface modules in IP67 housing Page 480
– Short description and table of contents Page 480
– Our strengths – Your advantages Page 482
– Type code Page 484
– Interface modules series IMC Page 486
Interface technology – Accessories Page 498
Open, modular, highly flexible: The BL20 der to supply the I/O modules. If the
universal bus terminal system makes it power supply for the modules is not s uf
possible to plan and implement tailored ficient (up to 74 modules depending on
I/O solutions for the IP20 area. The user gateway), the power supply can be re
can freely combine all I/O modules irre freshed with a bus refreshing module.
spective of the fieldbus and implement Gateways, which control the entire data
the required I/O channels to the precise exchange between the PLC and the I/O
number of bits: analog and digital signal modules, are used to connect to the
types, 1, 2, 4, 8, 16 or 32 channels, block fieldbus. Proven standards such as
or slice designs. PROFIBUS-DP, DeviceNet™, CANopen,
Technology modules with IO-Link, c oun Modbus RTU/ASCII, Modbus TCP, Ether
ter, PWM, SSI, RS232, RS485, RS422 o r Net/IP™, PROFINET and EtherCAT® can be
RFID interfaces for the T URCK identifica used here.
tion system are available to integ rate CODESYS programmable gateways are
more complex field devices. available for complex applications. The
The base modules are used to connect gateways handle local control tasks au
the sensors, actuators and field devices. tonomously and can be used for r emote
Variants are available with different pre-processing in order to relieve the
numbers of cage clamp or screwload on the higher-level controller.
terminals. FDT/DTM technology enables the user to
The power feeding modules enable the set the parameters for the BL20 system
provision of a new field supply. The use via a graphical user interface. Whether in
of these modules may be necessary for online or offline mode, commissioning o r
high power outputs; it also offers the testing, the FDT/DTM technology s impli
possibility of forming application-specif fies the planning of modules as well as
ic potential groups at any location in the the configuration and parametriz ation,
BL20 system. irrespective of the fieldbus used.
The BL20 gateways feature an integrated
power supply for the module bus in or
6 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Short Description/Table of Contents
system in IP20
Our Stren
Our Strengths – You
Our Strengths – Your Advantages
The BL20 I/O system features gateways col gateways automatically detect which
for the PROFIBUS-DP, DeviceNet™, C AN of the three Ethernet networks is being
open and Modbus RTU/ASCII fieldbuses, used. High-feature gateways for PROFI
as well as gateways for integration in in NET IRT and E therCAT®, as well as C
ODE
dustrial Ethernet networks. In addition, SYS programmable gateways for M od
multiprotocol solutions are a vailable that bus TCP and EtherNet/IP™ round off the
unite the three Ethernet p rotocols Ether program.
Net/IP™, Modbus TCP a nd PROFINET in
an I/O device: The E thernet multiproto
The large number of I/O modules avail of channels and output ratings. Device
able allows the user the possibility of in variants, such as for NAMUR signals or
tegrating virtually any required signal 230 VAC signals round off the range of
type in the BL20 system. The program in products. Besides the analog I/O mod
cludes digital and analog I/O modules ules for current or voltage signals, there
for standard I/O signals, relay modules, are also combination modules, g iving
as well as technology modules with IO- the possibility to choose between cur
Link, counter, PWM, SSI, RS232, RS485, rent, voltage and also Pt/Ni elements for
RS422 or RFID interfaces. The digital I/O each channel. Modules for thermocou
modules for 24 VDC are available as PNP ples or with HART® compatibility round
or NPN versions with different numbers off the range.
8 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Our Strengths – Your Advantages
ngths – Your A
ur Advantages
Besides the gateways and I/O modules in provided with push-in terminals instead
the standard housing, versions are also of screw or tension spring connection.
available in the ECO housing. The gate Unlike the standard I/O modules, the I/O
ways in the ECO housing have a particu modules in the ECO housing have the
larly slimline design, enabling the user to connection level already integrated. In
save space on the DIN rail. Unlike the this way a higher channel density can be
standard gateways, the ECO versions are achieved with the ECO I/O modules.
Special bus refreshing and power feed Power feeding modules are used for re-
ing modules are available for the system powering the field devices. This may be
and field supply. Above a specific num necessary when using several I/O mod
ber of I/O modules, the bus refreshing ules, espe cially output modules, if the
modules must be integrated in the BL20 field supply current exceeds 10 A. Power
system in order to refresh the internal feeding m odules are used for instance to
system power supply. This makes it pos create n ew potential groups in order to
sible to create extensive s tations with a implement the safety-related off switch
large number of I/O m
odules. Redundant ing of outputs or to implement the po
bus refreshing modules make it possible tential isolation of plant sections.
to create redundant supplied systems.
The use of BR-24VDC-RED modules e na and increases system availability accord
bles the user to turn the BL20 I/O s ystem ingly. Different potential groups can be
into a redundantly supplied system. In created in redundancy mode as well as
this way it is possible to redundantly in normal o peration, in order, for exam
supply both the I/O system itself as well ple, to implement the safety-related off
as the field devices connected to it. This switching of specific outputs.
considerably reduces the risk of failure
BL20 - Sy
BL20 - System integ
BL20 – System integration
easy
Remote signal processing
The programmable gateways can be programming user interface s upports all
programmed using the IEC 61131‑3 com IEC-61131‑3 programming languages:
pliant CODESYS vendor-neutral pro ▪▪ Instruction list (IL)
gramming software and can thus be ▪▪ Ladder diagram (LD)
formed into distributed control units. ▪▪ Function block diagram (FBD)
Possible applications include for e xam ▪▪ Structured text (ST)
ple the stand-alone control of an a pplica ▪▪ Sequential function chart (SFC)
tion or use in networks for the remote
pre-processing of signals. The g raphical
The global network variables function in of bidirectional data e xchange between
tegrated in CODESYS enables the simple CODESYS systems w ithout any addition
interconnection and communication of al programming. For example, several
several I/O stations. This makes it p
ossi decentralized systems can interact with
ble to network heterogeneous systems each other without the need for a high
quickly and simply. The use of s tandard er-level controller. Connection to CODE
transmission protocols such as TCP/IP SYS-3 c ontrollers is also straightforward.
and UDP/IP enables the implementation
10 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
BL20 – System integration
ystem integrat
gration
The BL20 system can be configured and cution of diagnostic functions, even
parametrized via a graphical user inter without a controller. This simplifies both
face based on FDT/DTM technology. For the testing of the application as well as
this TURCK provides special DTMs which commissioning in the field. Both the
can be incorporated in any FDT frame PACTware™ FDT/DTM frame application
application for its I/O systems and mod as well as the DTMs are available free of
ules. This enables the reading and set charge from the T URCK website at www.
ting of process data, and the simple exe turck.com
HART® communication
■ Analog input and output modules with
HART® communication
Gateway
■ The interface to the higher-level control
■ Gateways for PROFIBUS, CANopen,
DeviceNet™, Modbus RTU/ASCII,
Modbus TCP, EtherNet/IP™, PROFINET
and EtherCAT®
FDT/DTM
■ DTM for Remote I/O
■ Topology scan
■ Commissioning
■ Simulation and diagnostics
12 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
BL20 – System Overview
ystem overview
rview
RFID
■ 2-channel RFID modules
■ Integration of HF and UHF read/write
heads of the TURCK RFID System
BL ident®
The BL20 system features two power The voltage supply for the module bus The field supply is provided by the gate-
circuits: is integrated in the BL20 gateways. If the way. A power feeding module has to be
■ The internal module bus feeds the module bus is not sufficiently supplied used if the field supply of fieldbus nodes
module electronics and the gateway. (max. 1.5 A), a second refreshing modu- reaches 8/10 A (depending on the gate-
■ The field supply feeds all connected le has to be applied – see chapter Supply way) or a new potential group is required.
field devices. concept on the next page .
For details on the system and field supp-
NOTE: Bus refreshing modules can not ly, please refer to the technical data of the
Forming potential groups be used in combination with the ECO individual gateways.
gateway for PROFIBUS-DP.
Bus-Refreshing modules as well as Pow-
er-feeding modules can be used for the
creation of potential groups. Modules
with 24 VDC and 120/230 VAC field sup-
ply cannot be used in the same potential
group. The use of digital input modules
for 120/230 VAC requires the creation of a System planning
separate potential group with the power
feeding module BL20-PF-120/230VAC-D. For the planning of many complex BL20
stations, different factors have to be con-
sidered. For example rated current con-
sumption of the modules, number of mo-
dules, parameters and data volume and
possible restrictions imposed by the hig-
her level fieldbus.
The I/O-ASSISTANT (PACTware™ and
BL20-DTM), which can be downloaded
from our website, checks all relevant pa-
rameters and simplifies project planning
considerably. The I/O-ASSISTANT is also
able to generate dimension drawings
and documentation of the stations. Rea-
ding and setting of I/Os is also possible
which proves very helpful for commissi-
oning. Furthermore, module parameters
can also be set.
14 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
BL20 – System and field supply
I MBmax = 1.5 A
I F1 I F2 I F1 IF1max = 10 A
IF2max = 10 A
Gateways in ECO-Design*
*NOTE: Bus-refreshing modules can not be used in combination with the ECO gateway for PROFIBUS-DP.
BL20 – S 3 T – S B B C B B – B optional
16 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Type code
de
Features
Pinning overview
Position Note Pinning assignment
Power supply
The USYS system supply feeds power to the gateway
and the I/O modules. GNDL – +
=
UL Field supply
The UL field supply feeds power to the sensors and
actuators.
GNDSYS – +
=
USYS System supply
PROFIBUS-DP 1 = shield
Fieldbus cable (example): 2 = n.c.
3 = RD (Bus B)
D9T451‑2M (ident no. 6915759) or 9 5 4 = n.c.
5 = GND
RSSW-D9T451‑2M (ident no. 6915779) 6 1 6 = 5 VDC
7 = n.c.
8 = GN (Bus A)
9 = n.c.
18 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Gateways
Technical data
Type BL20-GW-DPV1
Ident no. 6827234
System data
Fieldbus transmission rate 9.6 kbps … 12 Mbps
Fieldbus addressing 2 rotary switches
Fieldbus address range 1…99
Fieldbus connection technology 1 x female sub-D connector
Fieldbus termination external
Max. number of I/O modules 64
Service interface PS/2 socket
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 50.6 x 114.8 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL
Pinning overview
Position Note Pinning assignment
Power supply + –
UL =
Field supply
The USYS system supply feeds power to the gateway GNDL
+ –
and the I/O modules. USYS =
System supply
The UL field supply feeds power to the sensors and GNDSYS
actuators.
PROFIBUS-DP A
Fieldbus cable (example): B
D9T451‑2M (ident no. 6915759) or A
B
RSSW-451‑2M (ident no. 6914229) SHLD
SHLD
20 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Gateways
Technical data
Type BL20-E-GW-DP
Ident no. 6827250
System data
Fieldbus transmission rate 9.6 kbps … 12 Mbps
Fieldbus addressing via DIP switch
Fieldbus address range 1…126
Fieldbus connection technology Push-in terminals
Fieldbus termination via DIP switch
Max. number of I/O modules 48
Service interface PS/2 socket
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 33.5 x 129.5 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL
Features
Pinning overview
Position Note Pinning assignment
Power supply
The USYS system supply feeds power to the gateway
and the I/O modules. GNDL – +
=
UL Field supply
The UL field supply feeds power to the sensors and GNDSYS – +
=
actuators. USYS System supply
CANopen
Fieldbus cable (example): V+
CBC5‑572‑2M (ident no. 6606065) or CAN_H
shield
RKC5701‑5M (ident no. 6931035) CAN_L
V–
22 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Gateways
Technical data
Type BL20-GWBR-CANOPEN
Ident no. 6827167
System data
Fieldbus transmission rate 20 kbps … 1 Mbps
Fieldbus addressing 2 rotary switches
Fieldbus address range 1…99
Fieldbus connection technology open style connector
Fieldbus termination external
Max. number of I/O modules 74
Service interface PS/2 socket
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 50.6 x 114.8 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL,
1 x o pen style connector
Pinning overview
Position Note Pinning assignment
Power supply + –
UL =
Field supply
The USYS system supply feeds power to the gateway GNDL
+ –
and the I/O modules. USYS =
System supply
The UL field supply feeds power to the sensors and GNDSYS
actuators.
CANopen CAN_H
Fieldbus cable (example): CAN_L
CBC5‑572‑2M (ident no. 6606065) or CAN_H
CAN_L
RKC5701‑5M (ident no. 6931035) CANGND
CANGND
24 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Gateways
Technical data
Type BL20-E-GW-CO
Ident no. 6827252
System data
Fieldbus transmission rate 20 kbps … 1 Mbps
Fieldbus addressing via DIP switch
Fieldbus address range 1…63
Fieldbus connection technology Push-in terminals
Fieldbus termination via DIP switch
Max. number of I/O modules 62
Service interface PS/2 socket
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 33.5 x 129.5 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL
Features
Pinning overview
Position Note Pinning assignment
Power supply
The USYS system supply feeds power to the gateway
and the I/O modules. GNDL – +
=
UL Field supply
The UL field supply feeds power to the sensors and GNDSYS – +
=
actuators. USYS System supply
DeviceNet™
Fieldbus cable (example): V+
CBC5‑572‑2M (ident no. 6606065) or CAN_H
shield
RKC5701‑5M (ident no. 6931035) CAN_L
V–
26 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Gateways
Technical data
Type BL20-GWBR-DNET
Ident no. 6827168
System data
Fieldbus transmission rate 125 / 250 / 500 kbps
Fieldbus addressing 2 rotary switches
Fieldbus address range 0…63
Fieldbus connection technology open style connector
Fieldbus termination external
Max. number of I/O modules 74
Service interface PS/2 socket
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 50.6 x 114.8 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL,
1 x o pen style connector
Pinning overview
Position Note Pinning assignment
Power supply +
UL
The USYS system supply feeds power to the gateway GNDL Field supply
–
and the I/O modules. GNDL
The UL field supply feeds power to the sensors and
actuators.
DeviceNet™
Fieldbus cable (example): V+
CBC5‑572‑2M (ident no. 6606065) or CAN_H
shield
RKC5701‑5M (ident no. 6931035) CAN_L
V–
28 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Gateways
Technical data
Type BL20-E-GW-DN
Ident no. 6827301
System data
Fieldbus transmission rate 125…500 kbps
Fieldbus addressing via DIP switch
Fieldbus address range 0…63
Fieldbus connection technology open style connector
Fieldbus termination via DIP switch
Max. number of I/O modules 62
Service interface PS/2 socket
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 33.5 x 129.5 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL,
1 x o pen style connector
Pinning overview
Position Note Pinning assignment
Power supply + –
UL =
Field supply
The USYS system supply feeds power to the gateway GNDL
+ –
and the I/O modules. USYS =
System supply
The UL field supply feeds power to the sensors and GNDSYS
actuators.
Modbus RTU/ASCII Tx / A
Fieldbus cable for RS485 (example): Rx / B
RSC5701‑5M (ident no. 6931036) Tx / A
Rx / B
GND
Shield
30 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Gateways
Technical data
Type BL20-E-GW-RS-MB/ET
Ident no. 6827381
System data
Fieldbus transmission rate 9.6 kbps … 115.2 kbps
Fieldbus addressing via DIP switch, I/O-ASSISTANT
Fieldbus address range 1…31 (via DIP switch)1…247 (via
I/O-ASSISTANT)
Fieldbus connection technology Push-in terminals
Fieldbus termination via DIP switch
Max. number of I/O modules 32
Service interface Mini USB
Environmental conditions
Ambient temperature -25…+60 °C
Relative humidity ≤ 15 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+70 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 33.5 x 129.5 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL
Power supply + –
UL =
Field supply
The USYS system supply feeds power to the gateway GNDL
+ –
and the I/O modules. USYS =
System supply
The UL field supply feeds power to the sensors and GNDSYS
actuators.
32 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Multiprotocol gateways for Ethernet
Technical data
Type BL20-E-GW-EN Mechanical data
Ident no. 6827329 Protection class IP20
Dimensions 33.5 x 129.5 x 74.4 mm
System data
Fieldbus transmission rate 10/100 Mbps, Full/Half Duplex, Auto
Negotiation, Auto Crossing
Max. number of I/O modules 31
Connection technology Ethernet 2 x RJ45, female
Protocol detection automatic
Web server 192.168.1.254 (Default)
Service interface Ethernet
Modbus TCP
Addressing Static IP, BOOTP, DHCP
Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15,
FC16, FC23
Simultaneous connections 8
Input Data Size max. 1024 register
Input register start address 0 (0x0000 hex)
Output Data Size max. 1024 register
Output register start address 2048 (0x0800 hex)
EtherNet/IP™
Addressing acc. to EtherNet/IP™ specification
Device Level Ring (DLR) supported
Simultaneous CIP connections 8
PROFINET
Addressing DCP
Conformance Class B (RT)
MinCycleTime 1 ms
Diagnostics acc. to PROFINET alarm handling
Topology detection supported
Automatic addressing supported
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Pinning overview
Position Note Pinning assignment
PROFINET 1 = TX +
Fieldbus cable (example): 8 2 = TX –
ETH2 3 = RX +
RJ45S-RJ45S-441‑2M (ident no. 6932517) or 1 4 = n.c.
RJ45‑FKSDD-441‑0.5M/S2174 (ident no. 6914221) 8 5 = n.c.
ETH1 6 = RX –
1 7 = n.c.
8 = n.c.
Power supply + –
UL =
Field supply
The USYS system supply feeds power to the gateway GNDL
+ –
and the I/O modules. USYS =
System supply
The UL field supply feeds power to the sensors and GNDSYS
actuators.
34 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Gateways
Technical data
Type BL20-E-GW-PN
Ident no. 6827377
System data
Fieldbus transmission rate 10/100 Mbps, Full/Half Duplex, Auto
Negotiation, Auto Crossing
Max. number of I/O modules 72
Connection technology Ethernet 2 x RJ45, female
Service interface Mini USB
PROFINET
Addressing DCP
Conformance Class C (IRT)
MinCycleTime 1 ms
Diagnostics acc. to PROFINET alarm handling
Topology detection supported
Automatic addressing supported
Media Redundancy Protocol (MRP) supported
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 33.5 x 129.5 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL
Pinning overview
Position Note Pinning assignment
EtherCAT® 1 = TX +
Fieldbus cable (example): 8 2 = TX –
ETH2 3 = RX +
RJ45S-RJ45S-441‑2M (ident no. 6932517) or 1 EtherCAT OUT 4 = n.c.
RJ45‑FKSDD-441‑0.5M/S2174 (ident no. 6914221) 8 5 = n.c.
ETH1 6 = RX –
EtherCAT IN 7 = n.c.
1
8 = n.c.
Power supply + –
UL =
Field supply
The USYS system supply feeds power to the gateway GNDL
+ –
and the I/O modules. USYS =
System supply
The UL field supply feeds power to the sensors and GNDSYS
actuators.
36 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Gateways
Technical data
Type BL20-E-GW-EC
Ident no. 6827380
System data
Fieldbus transmission rate 10/100 Mbps, Full/Half Duplex, Auto
Negotiation, Auto Crossing
Max. number of I/O modules 72
Connection technology Ethernet 2 x RJ45, female
Service interface Mini USB
EtherCAT®
Address allocation automatic
MinCycleTime 250 µs
Diagnostics CoE Emergencies, DiagnosisHistory
CAN over EtherCAT acc. to modular device profile
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 33.5 x 129.5 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL
Pinning overview
Position Note Pinning assignment
Modbus TCP 1 = TX +
Fieldbus cable (example): 12345678 2 = TX –
3 = RX +
RJ45S-RJ45S-441‑2M (ident no. 6932517) or 4 = n.c.
RJ45‑FKSDD-441‑0.5M/S2174 (ident no. 6914221) 5 = n.c.
6 = RX –
7 = n.c.
8 = n.c.
Power supply
The USYS system supply feeds power to the gateway
and the I/O modules. GNDL – +
=
UL Field supply
The UL field supply feeds power to the sensors and GNDSYS – +
=
actuators. USYS System supply
38 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Gateways
Technical data
Type BL20-GW-EN
Ident no. 6827237
System data
Fieldbus transmission rate 10/100 Mbps, Full/Half Duplex, Auto
Negotiation, Auto Crossing
Fieldbus addressing Rotary switch, BOOTP, DHCP, IO-
ASSISTANT
Fieldbus connection technology RJ45 port
Max. number of I/O modules 74
Web server 192.168.1.254 (Default)
Service interface PS/2 socket
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 50.6 x 114.8 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL
Pinning overview
Position Note Pinning assignment
EtherNet/IP™ 1 = TX +
Fieldbus cable (example): 12345678 2 = TX –
3 = RX +
RJ45S-RJ45S-441‑2M (ident no. 6932517) or 4 = n.c.
RJ45‑FKSDD-441‑0.5M/S2174 (ident no. 6914221) 5 = n.c.
6 = RX –
7 = n.c.
8 = n.c.
Power supply
The USYS system supply feeds power to the gateway
and the I/O modules. GNDL – +
=
UL Field supply
The UL field supply feeds power to the sensors and GNDSYS – +
=
actuators. USYS System supply
40 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Gateways
Technical data
Type BL20-GW-EN-IP
Ident no. 6827247
System data
Fieldbus transmission rate 10/100 Mbps, Full/Half Duplex, Auto
Negotiation, Auto Crossing
Fieldbus addressing Rotary switch, BOOTP, DHCP, IO-
ASSISTANT
Fieldbus connection technology RJ45 port
Max. number of I/O modules 74
Web server 192.168.1.254 (Default)
Service interface PS/2 socket
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 50.6 x 114.8 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL
Pinning overview
Position Note Pinning assignment
Modbus TCP 1 = TX +
Fieldbus cable (example): 12345678 2 = TX –
3 = RX +
RJ45S-RJ45S-441‑2M (ident no. 6932517) or 4 = n.c.
RJ45‑FKSDD-441‑0.5M/S2174 (ident no. 6914221) 5 = n.c.
6 = RX –
7 = n.c.
8 = n.c.
Power supply
The USYS system supply feeds power to the gateway
and the I/O modules. GNDL – +
=
UL Field supply
The UL field supply feeds power to the sensors and GNDSYS – +
=
actuators. USYS System supply
42 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Programmable Gateways
Technical data
Type BL20-PG-EN
Ident no. 6827249
System data
Fieldbus transmission rate 10/100 Mbps, Full/Half Duplex, Auto
Negotiation, Auto Crossing
Fieldbus addressing Rotary switch, BOOTP, DHCP, IO-
ASSISTANT
Fieldbus connection technology RJ45 port
Max. number of I/O modules 74
Web server 192.168.1.254 (Default)
Service interface PS/2 socket
PLC data
Programming CODESYS V2.3
Released for CODESYS version V 2.3.9.35
Programming languages IEC 61131‑3 (IL, LD, FBD, SFC, ST)
Application tasks 1
Number of POUs 1024
Programming interface RS232 interface, Ethernet
Processor RISC, 32 bit
Cycle time < 1 ms for 1000 IL commands
(without I/O cycle)
Program memory 512 kByte
Data memory 512 kByte
Input data 4 kByte
Output data 4 kByte
Non-volatile memory 16 kByte
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 50.6 x 114.8 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL
Pinning overview
Position Note Pinning assignment
EtherNet/IP™ 1 = TX +
Fieldbus cable (example): 12345678 2 = TX –
3 = RX +
RJ45S-RJ45S-441‑2M (ident no. 6932517) or 4 = n.c.
RJ45‑FKSDD-441‑0.5M/S2174 (ident no. 6914221) 5 = n.c.
6 = RX –
7 = n.c.
8 = n.c.
Power supply
The USYS system supply feeds power to the gateway
and the I/O modules. GNDL – +
=
UL Field supply
The UL field supply feeds power to the sensors and GNDSYS – +
=
actuators. USYS System supply
44 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Programmable Gateways
Technical data
Type BL20-PG-EN-IP
Ident no. 6827248
System data
Fieldbus transmission rate 10/100 Mbps, Full/Half Duplex, Auto
Negotiation, Auto Crossing
Fieldbus addressing Rotary switch, BOOTP, DHCP, IO-
ASSISTANT
Fieldbus connection technology RJ45 port
Max. number of I/O modules 74
Web server 192.168.1.254 (Default)
Service interface PS/2 socket
PLC data
Programming CODESYS V2.3
Released for CODESYS version V 2.3.9.35
Programming languages IEC 61131‑3 (IL, LD, FBD, SFC, ST)
Application tasks 1
Number of POUs 1024
Programming interface RS232 interface, Ethernet
Processor RISC, 32 bit
Cycle time < 1 ms for 1000 IL commands
(without I/O cycle)
Program memory 512 kByte
Data memory 512 kByte
Input data 4 kByte
Output data 4 kByte
Non-volatile memory 16 kByte
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 50.6 x 114.8 x 74.4 mm
Accessories
Included in delivery 2 x end brackets BL20‑WEW-35/2‑SW,
1 x end plate BL20‑ABPL
BL20‑P4T-SBBC-B
6827042
Tension spring connection, C rail
128,9
BL20‑P4S-SBBC-B
6827043
Screw connection, C rail
12,6
46 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-BR-24VDC-D
Ident no. 6827006
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
6827050 – –
BL20‑S4S-SBBC
6827051
Screw connection - slot 2 next to the gateway
BL20‑P4T-SBBC-B – +
6827042
Tension spring connection - slot n+1 next to the + –
24 VDC 24 VDC
gateway System supply US 11 21 11 21
System supply US
128,9 – –
BL20‑S4T-SBBC
12 22 12 22
6827050
+ +
Tension spring connection - slot n+2 next to the 24 VDC
Field supply UL
24 VDC
Field supply UL
13 23 13 23
gateway
PE PE
12,6 BL20‑P4S-SBBC-B 14 24 14 24
further potential group(s) 6827043 …-B …SBBC
Screw connection - slot n+1 next to the gateway
BL20‑S4S-SBBC
6827051
Screw connection - slot n+2 next to the gateway
48 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-BR-24VDC-RED
Ident no. 6827366
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
BL20‑P3S-SBB
6827037
Screw connection
BL20‑P4T-SBBC
6827038
Tension spring connection, access to C rail
128,9
BL20‑P4S-SBBC
6827039
Screw connection, access to C rail
12,6
50 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-PF-24VDC-D
Ident no. 6827007
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
BL20‑P3S-SBB
6827037
Screw connection
BL20‑P4T-SBBC
6827038
Tension spring connection, access to C rail
128,9
BL20‑P4S-SBBC
6827039
Screw connection, access to C rail
12,6
52 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-PF-120/230VAC-D
Ident no. 6827008
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
BL20‑S3S-SBB
6827045
Screw connection
BL20‑S4T-SBBC
6827050
Tension spring connection, access to C rail
128,9
BL20‑S4S-SBBC
6827051
Screw connection, access to C rail
12,6
54 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2DI-120/230VAC-P
Ident no. 6827011
Inputs
Low level signal voltage 0…20 VAC
High level signal voltage 79…265 VAC
Frequency range 47.5…63 Hz
Low level signal current 0…1 mA
High level signal current 3…10 mA
Input delay < 20 ms
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
128,9
BL20‑S4S-SBBS
6827047
Screw connection
12,6
BL20‑S6T-SBBSBB
6827052
Tension spring connection
BL20‑S6S-SBBSBB
6827053
Screw connection
56 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-4DI-24VDC-P
Ident no. 6827012
Inputs
Input type pnp
Low level signal voltage -30…+5 V
High level signal voltage 15…30 V
Low level signal current 0…1.5 mA
High level signal current 2…10 mA
Input delay < 0.2 ms
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
128,9
BL20‑S4S-SBBS
6827047
Screw connection
12,6
BL20‑S6T-SBBSBB
6827052
Tension spring connection
BL20‑S6S-SBBSBB
6827053
Screw connection
58 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-4DI-24VDC-N
Ident no. 6827013
Inputs
Input type npn
Low level signal voltage > 13 V
High level signal voltage 0…5 V
Low level signal current 0…1.2 mA
High level signal current 1.3…6 mA
Input delay < 0.2 ms
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
12,6
60 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-4DI-NAMUR
Ident no. 6827212
Inputs
Input wire-break Switch on threshold: 0.08 mA
Switch off threshold: 0.12 mA
Input - short-circuit Switch on threshold: 6.2 mA
Switch o ff threshold: 5.9 mA
Input type NAMUR acc. to DIN EN 60947‑5‑6
No-load voltage 8.2…8.6 VDC
Input - status Switch on threshold: 1.74 mA
Switch off threshold: 1.45 mA
Input delay 0.25 or 2.5 ms
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
▪▪ Fieldbus-independent
▪▪ Electronics and connection techno
logy in one housing
▪▪ Connectivity: Push-in terminals
▪▪ Protection class IP20
▪▪ 8 digital inputs, 24 VDC, PNP
switching
Pinning overview
Position Note Pinning assignment
Digital inputs
62 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with integrated terminal level
Technical data
Type BL20-E-8DI-24VDC-P
Ident no. 6827227
Inputs
Input type pnp
Low level signal voltage -30…+5 V
High level signal voltage 11…30 V
Low level signal current -1…+1.5 mA
High level signal current 2…5 mA
Input delay < 0.2 ms
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 128.6 x 74.6 mm
▪▪ Fieldbus-independent
▪▪ Electronics and connection technolo‑
gy in one housing
▪▪ Connectivity: Push-in terminals
▪▪ Protection class IP20
▪▪ 16 digital inputs, 24 VDC, PNP
switching
Pinning overview
Position Note Pinning assignment
Digital inputs
64 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with integrated terminal level
Technical data
Type BL20-E-16DI-24VDC-P
Ident no. 6827231
Inputs
Input type pnp
Low level signal voltage -30…+5 V
High level signal voltage 11…30 V
Low level signal current -1…+1.5 mA
High level signal current 2…5 mA
Input delay < 0.3 ms
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 160 x 74.6 mm
BL20‑B4T-SBBC
6827056
Tension spring connection, access to C rail
BL20‑B4S-SBBC
6827057
Screw connection, access to C rail
66 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-16DI-24VDC-P
Ident no. 6827014
Inputs
Input type pnp
Low level signal voltage -30…+5 V
High level signal voltage 15…30 V
Low level signal current 0…1.5 mA
High level signal current 2…10 mA
Input delay < 0.2 ms
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 100.8 x 74.1 x 55.4 mm
BL20‑B6S-SBBSBB
6827067
Screw connection
68 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-32DI-24VDC-P
Ident no. 6827015
Inputs
Input type pnp
Low level signal voltage -30…+5 V
High level signal voltage 15…30 V
Low level signal current < 1.5 mA
High level signal current 2…10 mA
Input delay < 0.2 ms
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 100.8 x 74.1 x 55.4 mm
PE PE
13 23
BL20‑S4T-SBCS
6827063
S S
Tension spring connection, access to C rail
Bit 0 Bit 1
128,9
BL20‑S4S-SBCS 11 21
6827060 + +
Screw connection, access to C rail
12 22
PE PE
13 23
12,6
– –
14 24
70 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2DO-24VDC-0.5A-N
Ident no. 6827025
Outputs
Output voltage 24 VDC
Output current per channel 0.5 A
Output type npn
Load type resistive, inductive, lamp load
Load resistance, resistive > 48 Ω
Load resistance, inductive < 1.2 H
Lamp load < 12 W
Switching frequency, resistive < 100 Hz
Inductive switching frequency < 2 Hz
Switching frequency, lamp load < 10 Hz
Output delay 0.1 ms
Short-circuit protection yes
Simultaneity factor 1
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
BL20‑S4T-SBCS
6827063
Tension spring connection, access to C rail
128,9
BL20‑S4S-SBCS
6827060
Screw connection, access to C rail
12,6
72 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2DO-24VDC-2A-P
Ident no. 6827026
Outputs
Output voltage 24 VDC
Output current per channel 2A
Output type pnp
Load type resistive, inductive, lamp load
Load resistance, resistive > 12 Ω
Load resistance, inductive < 1.2 H
Lamp load < 6 W
Switching frequency, resistive < 5000 Hz
Switching frequency, lamp load < 10 Hz
Output delay 0.1 ms
Short-circuit protection yes
Simultaneity factor 1
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
12 22
PE PE
13 23
BL20‑S4T-SBCS
6827063
Tension spring connection, access to C rail S S
Bit 0 Bit 1
128,9
BL20‑S4S-SBCS 11 21
6827060 N N
Screw connection, access to C rail
12 22
PE PE
13 23
12,6
L L
14 24
74 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2DO-120/230VAC-0.5A
Ident no. 6827137
Outputs
Output voltage 120 / 230 VAC
Output current per channel 0.5 A
Load type resistive, inductive, lamp load
Load resistance, resistive > 48 Ω
Load resistance, inductive < 1.2 H
Output delay 0.1 ms
Short-circuit protection yes
Simultaneity factor 1
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
128,9
BL20‑S4S-SBBS
6827047
Screw connection
12,6
76 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2DO-R-CO
Ident no. 6827030
Outputs
Load type resistive, inductive, lamp load
Rated load voltage 230/30 VAC/DC
Simultaneity factor 1
Lifespan at 230 VAC, 5A 100000 switching cycles
Lifespan at 230 VAC, 0.5A 1000000 switching cycles
Output current with DC voltage (resistive) see load limit curve
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
128,9
BL20‑S4S-SBCS
6827060
Screw connection, access to C rail
12,6
BL20‑S6T-SBCSBC
6827064
Tension spring connection, access to C rail
BL20‑S6S-SBCSBC
6827066
Screw connection, access to C rail
78 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-4DO-24VDC-0.5A-P
Ident no. 6827023
Outputs
Output voltage 24 VDC
Output current per channel 0.5 A
Output type pnp
Load type resistive, inductive, lamp load
Load resistance, resistive > 48 Ω
Load resistance, inductive < 1.2 H
Lamp load < 6 W
Switching frequency, resistive < 5000 Hz
Inductive switching frequency < 2 Hz
Switching frequency, lamp load < 10 Hz
Output delay 0.25 ms
Short-circuit protection yes
Simultaneity factor 1
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
▪▪ Fieldbus-independent
▪▪ Electronics and connection technolo‑
gy in one housing
▪▪ Connectivity: Push-in terminals
▪▪ Protection class IP20
▪▪ 8 digital outputs, 24 VDC, max. 0.5 A,
PNP switching
Pinning overview
Position Note Pinning assignment
Digital outputs S
S 1
2 S
S 3
4 S
S 5
6 S
S 7
8
9
10
GND
80 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with integrated terminal level
Technical data
Type BL20-E-8DO-24VDC-0.5A-P
Ident no. 6827226
Outputs
Output voltage 24 VDC
Output current per channel 0.5 A
Output type pnp
Load type resistive, inductive, lamp load
Load resistance, resistive > 48 Ω
Lamp load < 6 W
Switching frequency, resistive < 100 Hz
Switching frequency, lamp load < 10 Hz
Output delay 0.3 ms
Short-circuit protection yes
Simultaneity factor 1
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 128.6 x 74.6 mm
▪▪ Fieldbus-independent
▪▪ Electronics and connection technolo‑
gy in one housing
▪▪ Connectivity: Push-in terminals
▪▪ Protection class IP20
▪▪ 16 digital outputs, 24 VDC, max. 0.5 A,
PNP switching
Pinning overview
Position Note Pinning assignment
Digital outputs
82 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with integrated terminal level
Technical data
Type BL20-E-16DO-24VDC-0.5A-P
Ident no. 6827230
Outputs
Output voltage 24 VDC
Output current per channel 0.5 A
Output type pnp
Load type resistive, inductive, lamp load
Load resistance, resistive > 48 Ω
Lamp load < 6 W
Switching frequency, resistive < 100 Hz
Switching frequency, lamp load < 10 Hz
Output delay 0.3 ms
Short-circuit protection yes
Simultaneity factor 0.5
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 160 x 74.6 mm
84 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-16DO-24VDC-0.5A-P
Ident no. 6827027
Outputs
Output voltage 24 VDC
Output current per channel 0.5 A
Output type pnp
Load type resistive, inductive, lamp load
Load resistance, resistive > 48 Ω
Load resistance, inductive < 1.2 H
Lamp load < 6 W
Switching frequency, resistive < 100 Hz
Output delay 0.1 ms
Short-circuit protection yes
Simultaneity factor 1
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 100.8 x 74.1 x 55.4 mm
6827219
86 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-32DO-24VDC-0.5A-P
Ident no. 6827220
Outputs
Output voltage 24 VDC
Output current per channel 0.5 A
Output type pnp
Load type resistive, inductive, lamp load
Load resistance, resistive > 48 Ω
Load resistance, inductive < 1.2 H
Lamp load < 6 W
Switching frequency, resistive < 100 Hz
Output delay 0.3 ms
Short-circuit protection yes
Simultaneity factor 1
Electrical isolation electronics to the field level
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 100.8 x 74.1 x 55.4 mm
12,6
3‑wire connection
88 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2AI-I(0/4…20MA)
Ident no. 6827021
Inputs
Input type 0/4…20 mA
Input resistance < 0.125 kΩ
Max. input current 50 mA
Electrical isolation electronics to the field level
Response characteristic
Resolution 16 Bit
Basic fault limit at 23 °C < 0.2 %
Repeatability 0.05 %
Temperature coefficient < 300 ppm / °C of full scale
Measuring principle Delta Sigma
Measured-value display 16 bit signed integer
12 bit full range left-justified
Cycle time ≤ 10 ms
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
12,6
90 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2AIH-I
Ident no. 6827331
Inputs
Input type 0/4…20 mA
Input resistance > 250 Ω
Max. input current 24 mA
Electrical isolation electronics to the field level
Response characteristic
Resolution 16 Bit
Basic fault limit at 23 °C < 0.1 %
Repeatability 0.1 %
Temperature coefficient < 150 ppm / °C of full scale
Measuring principle Delta Sigma
Measured-value display 16 Bit signed integer, NE43(PA),
extended
Cycle time ≤ 250 ms
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
12,6
3‑wire connection
92 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2AI-U(-10/0…+10VDC)
Ident no. 6827022
Inputs
Input type -10/0 …10 VDC
Input resistance < 98.5 kΩ
Max. input voltage 35 V continuous
Electrical isolation electronics to the field level
Response characteristic
Resolution 16 Bit
Basic fault limit at 23 °C < 0.2 %
Repeatability 0.05 %
Temperature coefficient < 150 ppm / °C of full scale
Measuring principle Delta Sigma
Measured-value display 16 bit signed integer
12 bit full range left-justified
Cycle time ≤ 10 ms
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
BL20‑S4T-SBBS
6827046
Tension spring connection
128,9
BL20‑S4S-SBBS
6827047
Screw connection
12,6
94 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2AI-PT/NI-2/3
Ident no. 6827017
Inputs
Input type Pt100, Pt200, Pt500, Pt1000, Ni100,
Ni1000
Electrical isolation electronics to the field level
Measuring current < 1 mA
Response characteristic
Resolution 16 Bit
Basic fault limit at 23 °C < 0.2 %
Repeatability 0.05 %
Temperature coefficient < 300 ppm / °C of full scale
Measured-value display 16 bit signed integer
12 bit full range left-justified
Cycle time ≤ 200 ms
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
12,6
96 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2AI-THERMO-PI
Ident no. 6827020
Inputs
Input type types B, E, J, K, N, R, S, T
Electrical isolation electronics to the field level
Voltage resolution ± 50 mV: < 2 µV
± 100 mV: < 4 µV
± 500 mV: < 20 µV
± 1000 mV: < 50 µV
Response characteristic
Resolution 16 Bit
Basic fault limit at 23 °C < 0.2 %
Repeatability 0.05 %
Temperature coefficient < 300 ppm / °C of full scale
Measured-value display 16 bit signed integer
12 bit full range left-justified
Cycle time ≤ 300 ms
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
BL20‑S6S-SBCSBC I I
6827066 12 22
Screw connection Sh Sh
13 23
UL or + + UL or
BR/PF BR/PF
terminal 13 14 24 terminal 13
I I
15 25
Sh Sh
16 26
3‑wire connection
U/I+ U/I+
11 21
– –
12 22
Channel 1 + + Channel 2
UL or Sh Sh UL or
BR/PF BR/PF
terminal 13 13 23 terminal 13
U/I+ U/I+
14 24
– –
+ 15 25 +
Channel 3 Channel 4
UL or Sh Sh UL or
BR/PF BR/PF
terminal 13 16 26 terminal 13
4‑wire connection
98 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-4AI-U/I
Ident no. 6827217
Inputs
Input type 0/4 … 20 mA or -10/0 … 10 VDC
Input resistance < 62 Ω (current) resp.
> 98.5 kΩ ( voltage)
Max. input current 50 mA
Max. input voltage 35 V continuous
Electrical isolation electronics to the field level
Response characteristic
Resolution 16 Bit
Basic fault limit at 23 °C < 0.3 %
Repeatability 0.05 %
Temperature coefficient < 300 ppm / °C of full scale
Measuring principle Delta Sigma
Cycle time ≤ 25 ms
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
▪▪ Fieldbus-independent
▪▪ Electronics and connection technolo‑
gy in one housing
▪▪ Connectivity: Push-in terminals
▪▪ Protection class IP20
▪▪ LEDs indicate status and diagnostic
▪▪ Electronics galvanically separated
from the field level via optocouplers
▪▪ 4 analog inputs for the connection of
thermocouples
▪▪ Types B, C, E, G, J, K, N, R, S and T
▪▪ Cold junction compensation via inte‑
grated Pt1000 probe
Pinning overview
Position Note Pinning assignment
Thermocouple inputs
+ 1
TC1 – 2
+
3
TC2 – 4
+
5
TC3 – 6
+
7
TC4 – 8
9
10
100 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with integrated terminal level
Technical data
Type BL20-E-4AI-TC
Ident no. 6827367
Inputs
Input type types B, C, E, G, J, K, N, R, S, T
Input resistance > 7 MΩ
Electrical isolation electronics to the field level
Voltage resolution ± 50 mV: < 2 µV
± 100 mV: < 4 µV
± 500 mV: < 20 µV
± 1000 mV: < 50 µV
Response characteristic
Resolution 16 Bit
Basic fault limit at 23 °C < 0.2 %
Repeatability 0.05 %
Temperature coefficient < 150 ppm / °C of full scale
Measured-value display 16 bit signed integer
12 bit full range left-justified
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 128.6 x 74.6 mm
▪▪ Fieldbus-independent
▪▪ Electronics and connection technolo‑
gy in one housing
▪▪ Connectivity: Push-in terminals
▪▪ Protection class IP20
▪▪ LEDs indicate status and diagnostic
▪▪ Electronics galvanically separated
from the field level via optocouplers
▪▪ 8 analog 2‑wire inputs U/I
▪▪ Passive input - External supply
▪▪ 0 … 20 mA, 4 … 20 mA,
-10 … +10 VDC or 0 … +10 VDC,
selectable per channel
▪▪ Alternatively: 4PT/NI inputs (always 2
analog inputs are combined to a PT/Ni
2/3‑wire input)
Pinning overview
Position Note Pinning assignment
Analog inputs U/I
2-wire
+
2-wire
PT/NI
3-wire
I+ I+
The pin assignment is dependent on the sensor 1 –
é é
1
2
+
type. Examples of the most common 2‑ and 4‑wire 2 – I– I–
3
4
listed below.
+
7
4 – I– I–
8
é
I+
9
10
15
16
15 +
16
–
potential. GNDSYS 4
15
16
102 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with integrated terminal level
Technical data
Type BL20-E-8AI-U/I-4PT/NI
Ident no. 6827325
Inputs
Input type 0/4…20 mA,
-10/0…10 VDC,
Pt100, Pt200, Pt500, Pt1000,
NI100, NI1000,
0…250 Ω, 0…400 Ω, 0…800 Ω,
0…2000 Ω, 0…4000 Ω
Input resistance < 62 Ω (current) resp.
> 98.5 kΩ ( voltage)
Max. input current current: 50 mA
Max. input voltage Voltage: -20 VDC < U < 20 VDC
Electrical isolation electronics to the field level
Response characteristic
Resolution 16 Bit
Basic fault limit at 23 °C < 0.2 %
Temperature coefficient < 200 ppm / °C of full scale
Measured-value display 16 bit signed integer
12 bit full range left-justified
12 bit left-justified
Conversion time < (44 x [ number of actively
parametrized channels]) ms
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 160 x 74.6 mm
104 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2AO-I(4…20MA)
Ident no. 6827034
Outputs
Load resistance, resistive < 0.45 kΩ
Load resistance, inductive < 1 mH
Output type 0/4…20 mA
Electrical isolation electronics to the field level
Response characteristic
Resolution 16 Bit
Basic fault limit at 23 °C < 0.2 %
Repeatability 0.05 %
Temperature coefficient < 150 ppm / °C of full scale
Measured-value display 16 bit signed integer
12 bit full range left-justified
Cycle time ≤ 10 ms
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
12,6 I +
14 24
106 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2AOH-I
Ident no. 6827332
Outputs
Load resistance, resistive < 0.60 kΩ
Load resistance, inductive < 1 mH
Short circuit 24 mA
Output type 0/4…20 mA
Electrical isolation electronics to the field level
Response characteristic
Resolution 16 Bit
Basic fault limit at 23 °C < 0.2 %
Repeatability 0.1 %
Temperature coefficient < 150 ppm / °C of full scale
Measured-value display 16 Bit signed integer, NE43(PA),
extended
Cycle time ≤ 250 ms
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
108 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2AO-U(-10/0…+10VDC)
Ident no. 6827033
Outputs
Load resistance, resistive > 1 kΩ
Load resistance, capacitive < 1 µF
Short circuit 40 mA
Output type -10/0 …+10 VDC
Electrical isolation electronics to the field level
Response characteristic
Resolution 16 Bit
Basic fault limit at 23 °C < 0.2 %
Repeatability 0.05 %
Temperature coefficient < 300 ppm / °C of full scale
Measured-value display 16 bit signed integer
12 bit signed integer left-justified
12 bit full range left-justified
Cycle time ≤ 10 ms
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
▪▪ Fieldbus-independent
▪▪ Electronics and connection technolo‑
gy in one housing
▪▪ Connectivity: Push-in terminals
▪▪ Protection class IP20
▪▪ LEDs indicate status and diagnostic
▪▪ Electronics galvanically separated
from the field level via optocouplers
▪▪ 4 analog outputs
▪▪ 0…20 mA, 4…20 mA, -10…+10 VDC
or 0…+10 VDC
▪▪ Selectable per channel
Pinning overview
Position Note Pinning assignment
Analog outputs
110 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with integrated terminal level
Technical data
Type BL20-E-4AO-U/I
Ident no. 6827328
Outputs
Load resistance, resistive < 0.45 kΩ (current) or
> 1 kΩ (voltage)
Load resistance, inductive < 0.01 mH (voltage mode)
Load resistance, capacitive < 1 µF (current mode)
Short circuit 40 mA
Output type 0/4 … 20 mA or -10/0 … +10 VDC
Electrical isolation electronics to the field level
Response characteristic
Resolution 16 bit
Basic fault limit at 23 °C < 0.2 %
Temperature coefficient < 200 ppm / °C of full scale
Measured-value display 16 bit signed integer
12 bit left-justified
Cycle time ≤ 50 ms
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 160 x 74.6 mm
12,6
112 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-1RS232
Ident no. 6827169
Transmission
Transmission level active (URS1) -15 to -3 VDC
Transmission level inactive (URSO) 3 to 15 VDC
Common-mode range (UGL) -7 to 12 VDC
Transmission signals RxD, TxD, RTS, CTS
Data buffer received / sent 128 / 64 Byte
Cable length 15 m
Connection type full duplex
Transmission rate 300 to 115200 bps
Parameters Transmission rate, diagnostics, data
bits, stop bits, XON - character, XOFF -
character, parity, flow control
Electrical isolation isolation of electronics and field level
via optocouplers
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
128,9
BL20‑S4S-SBBS
6827047
Screw connection
12,6
TxD-/RxD-/N
11 21
14 24
114 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-1RS485/422
Ident no. 6827165
Transmission
Transmission signals TxD, RxD
Data buffer received / sent 128 / 64 Byte
Cable length 30 m
Connection type 2‑wire half duplex or 4‑wire full
duplex
Transmission rate 300 to 115200 bps
Parameters RS485/422, transmission rate,
diagnostics, data bits, stop bits, XON -
character, XOFF - character, parity,
flow control
Line impedance 120 Ω
Terminating resistor external
Electrical isolation isolation of electronics and field level
via optocouplers
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
128,9
6827047
Screw connection
12,6
116 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-1SSI
Ident no. 6827166
Transmission
Transmission signals CL, D
Cable length 30 m
Connection type 4‑wire full duplex (clock output/signal
input)
Transmission rate 62.5 kbps up to 1 Mbps
Parameters Transmission rate, diagnostics, data
format (binary / GRAY coded), data
frame bits (1‑32), number of invalid
bits (LSB: 0‑15, MSB 0‑7)
Electrical isolation isolation of electronics and field level
via optocouplers
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
▪▪ Fieldbus-independent
▪▪ Electronics and connection technolo‑
gy in one housing
▪▪ Connectivity: Push-in terminals
▪▪ Protection class IP20
▪▪ LEDs indicate status and diagnostic
▪▪ Electronics galvanically isolated from
the field level via optocouplers
▪▪ 2 x counter/encoder channels 200 kHz
▪▪ 2 PWM outputs 20 kHz / 0.5A
▪▪ 2 digital outputs 20 kHz / 0.5A
▪▪ Counting mode: Continuous, single or
periodic count
▪▪ Measuring principle: Frequency, rota‑
tional speed or period duration
measurement
Pinning overview
Position Note Pinning assignment
Counter or PWM channels 1 A1 / DI1 (200kHz)
2 B1 / DI2 (200kHz)
Counter 1 3 Z1 / DI3 (10kHz)
4 +UB
5 GND
6 A2 / DI4 (200kHz)
7 B2 / DI5 (200kHz)
Counter 2 8 Z2 / DI6 (10kHz)
9 +UB
10 GND
11 P1 (0,5A / 20kHz)
PWM 1 12 Direction / DO1 (0,5A)
13 GND
14 P2 (0,5A / 20kHz)
PWM 2 15 Direction / DO2 (0,5A)
16 GND
118 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with integrated terminal level
Technical data
Type BL20-E-2CNT-2PWM Mechanical data
Ident no. 6827341 Protection class IP20
Dimensions 12.6 x 160 x 74.6 mm
Transmission
Frequency measurement up to 200 kHz
Speed measurement factor parametrizable
Period duration measurement resolution 200 ns, max. period
duration (232 - 1) * 200 ns
Upper count limit 0x00000000 up to 0x7FFFFFFF
Lower count limit 0x80000000 up to 0xFFFFFFFF
Electrical isolation isolation of electronics and field level
via optocouplers
Inputs
Low level signal voltage 0 to 1 VDC / 0 to 4.5 VDC
High level signal voltage 3.5 to 30 VDC / 7.5 to 30 VDC
Low level signal current 0 … 0.1 mA / 0 … 0.4 mA
High level signal current 0.3 … 3 mA / 0.6 … 3 mA
Filter on > 16 µs (62.5 kHz)
Filter off < 2.5 µs (200 kHz)
Outputs
Switching frequency ≤ 20000 Hz
Output voltage 24 VDC
Output current per channel 0.5 A
Output type PNP
Load type resistive, inductive, lamp load
Load resistance, resistive > 48 Ω
Lamp load < 10 W
Switching frequency, resistive < 100 Hz
Inductive switching frequency < 2 Hz
Switching frequency, lamp load < 10 Hz
Output delay 0.2 ms
Short-circuit protection yes
Simultaneity factor 1
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
128,9
BL20‑S4S-SBBS Transceiver
11 21
6827047 GND (BU) GND (3 BU)
Screw connection 12 22
Transceiver
12,6 14 24
Data 1 (2 BK)
Data 1 (4 WH)
Connectors …/S2501
Data 0 (WH)
Data 0 (BK)
Transceiver
11 21
12 22
Transceiver
14 24
Data 1 (2 WH)
Data 1 (4 BK)
Connectors …/S2503
Data 0 (BU)
Data 0 (WH)
Transceiver
11 21
12 22
Transceiver
14 24
Data 1 (2 BU)
Data 1 (4 WH)
120 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2RFID-A
Ident no. 6827233
Transmission
Cable length 50 m
Transmission rate 115.2 kbps
Electrical isolation isolation of electronics and field level
via optocouplers
Outputs
Sensor supply 0.25 A per channel, short-circuit proof
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
128,9
BL20‑S4S-SBBS Transceiver
11 21
6827047 GND (BU) GND (3 BU)
Screw connection 12 22
Transceiver
12,6 14 24
Data 1 (2 BK)
Data 1 (4 WH)
Connectors …/S2501
Data 0 (WH)
Data 0 (BK)
Transceiver
11 21
12 22
Transceiver
14 24
Data 1 (2 WH)
Data 1 (4 BK)
Connectors …/S2503
Data 0 (BU)
Data 0 (WH)
Transceiver
11 21
12 22
Transceiver
14 24
Data 1 (2 BU)
Data 1 (4 WH)
122 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with separate terminal level
Technical data
Type BL20-2RFID-S
Ident no. 6827306
Transmission
Cable length 50 m
Transmission rate 115.2 kbps
Electrical isolation isolation of electronics and field level
via optocouplers
Outputs
Sensor supply 0.25 A per channel, short-circuit proof
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -25…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
Mechanical data
Protection class IP20
Dimensions 12.6 x 74.1 x 55.4 mm
▪▪ Fieldbus-independent
▪▪ Electronics and connection technolo‑
gy in one housing
▪▪ Connectivity: Push-in terminals
▪▪ Protection class IP20
▪▪ LEDs indicate status and diagnostic
▪▪ Electronics galvanically separated
from the field level via optocouplers
▪▪ IO-Link master acc. to specification
V1.1, 4‑channel
▪▪ 4 universal digital channels, PNP,
channel diagnostics, 0.5 A
Pinning overview
Position Note Pinning assignment
I/O channels
1 C/Q (Channel 1)
The channels 1 to 4 are IO-Link master channels.
Channels 5 to 8 are XSG channels (optionally usable 2 C/Q (Channel 2)
as digital inputs or outputs). 3 C/Q (Channel 3)
The terminals 9 and 10 are used for sensor supply. 4 C/Q (Channel 4)
5 XSG (Channel 5)
6 XSG (Channel 6)
Attention:
The IO-Link devices must be supplied with the 7 XSG (Channel 7)
same potential as UL of the gateway or the BR / PF 8 XSG (Channel 8)
module (if used). 9 GNDL
10 + UL
124 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
BL20 – Modular I/O system in IP20
Electronic module with integrated terminal level
Technical data
Type BL20-E-4IOL Mechanical data
Ident no. 6827385 Protection class IP20
Dimensions 12.6 x 128.6 x 74.6 mm
Inputs
Input type PNP
Low level signal voltage < 5 V
High level signal voltage > 11 V
Low level signal current < 1.5 mA DI / <5 mA SIO
High level signal current 2.1 … 3.7 mA DI / 5 … 11 mA SIO
Electrical isolation electronics to the field level
Outputs
Output voltage 24 VDC
Output type PNP
Load type resistive, inductive, lamp load
Load resistance, resistive > 48 Ω
Load resistance, inductive < 1.2 H
Lamp load < 3 W
Switching frequency, resistive < 200 Hz
Switching frequency, inductive < 2 Hz
Switching frequency, lamp load < 20 Hz
Output delay 3 ms
Electrical isolation electronics to the field level
Connectivity push-in
IO-Link
IO-Link specification Version 1.1
IO-Link port type Class A
Frame type Supports all specified framet types
Supported devices Max. 14 byte input / 14 byte output
Transmission rate 4.8 kbps (COM 1) / 38.4 kbps (COM 2) /
230 kbps (COM 3)
Environmental conditions
Ambient temperature 0…+55 °C
Relative humidity ≤ 5 to 95 % (internal), Level RH-2,
no condensation (at 45 °C storage)
Storage temperature -40…+85 °C
Vibration test acc. to EN 61131
Shock test acc. to IEC 68‑2‑27
Drop and topple acc. to IEC 68‑2‑31 and free fall to
IEC 68‑2‑32
Electro-magnetic compatibility acc. to EN 61131‑2
MTTF 388 years acc. to SN 29500 (Ed. 99)
20 °C
BL20-Sys
BL20-System - Acce
BL20 System – Accessories
I/O-ASSISTANT-KABEL- RS232 service cable for Gateways with PS2
BL20/BL67 interface
6827133
MINI USB 2.0 cable 1.5 m USB 2.0 service cable for gateways with USB port
6827388
A
USB 2.0 extension active USB 2.0 extension, 5 m, active, with integrated
5 m repeater
A
6827390
126 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
BL20-System - Accessories
stem - Accesso
essories
BL20-Sys
BL20-System - Acce
BL20 System – Accessories
BL20-ANBZ-BL Markers for labelling base modules, clear color
6827072 identification of potentials on the connection level,
10 x strips of 6, blue
BL20-ANBZ-RT Markers for labelling base modules, clear color
6827073 identification of potentials on the connection level,
10 x strips of 6, red
BL20-ANBZ-GN Markers for labelling base modules, clear color
6827074 identification of potentials on the connection level,
10 x strips of 6, green
BL20-ANBZ-SW Markers for labelling base modules, clear color
6827075 identification of potentials on the connection level,
10 x strips of 6, black
BL20-ANBZ-BR Markers for labelling base modules, clear color
6827076 identification of potentials on the connection level,
10 x strips of 6, brown
BL20-ANBZ-RT/BL-BED Markers for labelling base modules, clear color
6827077 identification of potentials on the connection level,
10 x strips of 6, red/blue
BL20-ANBZ-GN/GE-BED Markers for labelling base modules, clear color
6827078 identification of potentials on the connection level,
10 x strips of 6, green/yellow
BL20-ANBZ-WS Markers for labelling base modules, clear color
6827079 identification of potentials on the connection level,
10 x strips of 6, white
128 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
BL20-System - Accessories
stem - Accesso
essories
In Out Function
60,4 42
Power
REP-DP 0002
Segment 2 Segment 2
136
148
130 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
PROFIBUS-DP – Accessories
US-DP – Access
cessories
BMSWS8251-8,5 PROFIBUS-DP field-wireable 1 x M12 male, 5‑pin,
6904724 B-coded, angled, metal housing, shieldable
M12 x 1
M12 x 1
locknut lockwasher
LN-M12 LW-M12
132 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
PROFIBUS-DP – Accessories
US-DP – Access
cessories
FKW4.54-0.5 PROFIBUS-DP flange, 1 x M12 female, 5‑pin,
8016042 B-coded, front-panel mounting (PG9), 0.5 m braid
FKW5L PROFIBUS-DP flange, 1 x M12 female, B-coded,
8016718 front-panel mounting (PG9), solder tail
134 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
DeviceNet™/CANopen – Accessories
et™/CANopen
pen – Accessories
17,5
ø 26,0 38,3
7/8-16UN
7/8-16UN
ø 26,0
P1
41,0
54,0
RSM50-WKM50-0.3XOR- CANopen/DeviceNet™ / Power supply T piece,
7/8-16UN
L RKM50 1 x 7/8“ male, 2 x 7/8“ female, 5‑pin, 0.3 m cable,
6914951 irradiated, 9 A n
ominal current
VB2-FKM-FKM-FSM57 CANopen/DeviceNet™ / Power supply Y piece,
6602331 1 x M12 male, 2 x M12 female, 5‑pin
17,5
19,2
ø 26,0
7/8-16UN 7/8-16UN
136 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
DeviceNet™/CANopen – Accessories
et™/CANopen
pen – Accessories
17,5
19,2
ø 26,0
7/8-16UN 7/8-16UN
38,1
7/8-16UN
ø 26,0
36,0 ø 18,1
63,4
7/8-16UN
locknut sealing gasket
lockwasher thrust washer
138 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
DeviceNet™/CANopen – Accessories
et™/CANopen
pen – Accessories
M12 x 1
locknut lockwasher
LN-M12 LW-M12
101,6
5
100 2
LNK
82,8
25,4
100
10
73
38
8
SE20-84MT-RJ822 Ethernet switch, 8‑port, managed, 10/100 Mbps,
6607011 RJ45, IP20, mounting on standard DIN rail TS-35
LED
120
8,7
97
40,7
82,8
25,4
143
160
182
200
182
200
140 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
Ethernet – Accessories
– Accessories
ries
142 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
Power Supply – Accessories
upply – Access
cessories
P1
41,0
54,0
RSM50-WKM50-0.3XOR- CANopen/DeviceNet™ / Power supply T piece,
7/8-16UN
L RKM50 1 x 7/8“ male, 2 x 7/8“ female, 5‑pin, 0.3 m cable,
6914951 irradiated, 9 A n
ominal current
RSM-2RKM40 Power supply T piece, 1 x 7/8“ male, 2 x 7/8“ female,
6914828 4‑pin, 0° / 0° / 0°, 9 A nominal current
38
25 M12 x 1
M12 x 1
13
17,5
19,2
ø 26,0
7/8-16UN 7/8-16UN
17,5
19,2
ø 26,0
7/8-16UN 7/8-16UN
38,1
7/8-16UN
ø 26,0
36,0 ø 18,1
63,4
144 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
Power Supply – Accessories
upply – Access
cessories
7/8-16UN
7/8-16UN
locknut sealing gasket
lockwasher thrust washer
7/8-16UN
7/8-16UN
locknut sealing gasket
lockwasher thrust washer
146 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
Power Supply – Accessories
upply – Access
cessories
M12 x 1
locknut lockwasher
LN-M12 LW-M12
148 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
Power Supply – Accessories
upply – Access
cessories
The compact IP20 block I/O modules for Net/IP™ and Modbus TCP. The devices
DIN rails can not only be installed in c on- are available in two different designs:
trol cabinets, they can also be used t o in- The small design provides 4 digital in-
tegrate small, decentralized control b ox- puts and 4 universal digital channels; t he
es with a few I/O-signals to a fieldbus large design is available in versions with
network. Block I/O modules are available 16 digital inputs or with 16 universal dig-
for the fieldbus systems PROFIBUS-DP ital I/Os that can be used both as input
and DeviceNet ™ as well as modules with and as output. The m odules can be fitted
multiprotocol Ethernet functionality that directly to a s tandard TS 35 DIN rail.
can be automatically run in each of the
three Ethernet systems PROFINET, Ether
150 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
Short description/Table of contents
modules in IP20
Type Ident No. Description Page
FDP20-16S 6611465 PROFIBUS-DP slave, 16 digital inputs, 24 VDC, PNP, SUB-D 156
Our Stren
Our Strengths – You
Our Strengths – Your Advantages
The compact Ethernet multiprotocol standard TS 35 DIN rail. T he larger variant
modules of the FEN20 series can be o p- FEN20‑16DXP comes w ith 16 universal
erated in any of the three Ethernet sys- digital channels. The I/O signals of these
tems PROFINET, EtherNet/IP™ and Mod- modules are distributed over three inde-
bus TCP. Two IP20 rated designs are pendent potential groups that are isolat-
available: The small FEN20‑4DIP-4DXP ed from each other. This makes it possi-
design comes with four digital input ble, for example, to implement the
channels and four universal digital chan- safety-related off switching of the out-
nels. The module h as two drill holes for puts. The modules can be fitted directly
easy mounting on a mounting plate. The to a standard DIN rail.
FDN20‑BKT-DIN mounting adapter also
enables the device to be fitted to a
The FDP20 product series offers compact The I/O signals of these modules a re dis-
block I/O modules in IP20 for PROFIBUS- tributed over three independent poten-
DP. Four device types are available – two tial groups that are isolated from each
modules with 16 digital inputs as well as other. This makes it possible, for exam-
two modules with 16 universal digital ple, to implement the safety-related off
channels. The modules are available e i- switching of the outputs. The modules
ther with SUB-D connectors or a r emova- can be fitted directly to a standard DIN
ble screw terminal block, so that the rail.
SUB-D male connector is unneces sary.
The FDN20 product series offers a selec wall, or on a standard TS 35 DIN rail using
tion of compact block I/O modules in the FDN20‑BKT-DIN mounting adapter.
IP20 for DeviceNet™. Two modules come Each module is also p rovided with 16
with four digital inputs and four univer- digital inputs and 16 universal digital
sal digital channels. Both modules are channels for mounting on a standard
provided with a screw terminal block for TS 35 DIN rail. The I/O signals of these
the bus connection; the rear of a module modules are distributed over three inde-
is also provided with an M12 × 1 m ale pendent potential groups that a re isolat-
connector which can be routed directly ed from each other. This makes it possi-
outside of the control cabinet w all. The ble, for example, to implement the
two modules are either m ounted on a safety-related off switching of the
mounting plate using two d rill holes pro- outputs.
vided, directly on the control cabinet
152 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
Our Strengths – Your Advantages
ngths – Your A
ur Advantages
Multiprotocol technology and universal digital channels
Thanks to their ultra-compact design, signals are involved. The 8‑channel v er-
the I/O modules of the Fxx20 series can sion is only 62.5 × 55 × 28.5 mm!
be fitted in virtually any control cabinet. The program also includes a module that
This makes it possible to easily provide is provided with an M12 × 1 male con-
bus capability to small local stations or nector on the back. If the device is fitted
operator panels, and to utilize the bene on the control cabinet wall, the user can
fits of fieldbus technology quickly and simply route the bus terminal o ut of the
effectively as an alternative to conven control cabinet.
tional cabling, even when only a few I/O
The Ethernet multiprotocol I/O modules the station configur ation, channel set-
of the FEN20 series are provided with an tings and Ethernet statistics are provid-
integrated web server, thus simplifying ed. Diagnostic information such as the
commissioning and diagnostics. This e n- short circuit of an output a re shown on
ables the user to view the station infor- the web server clearly in plain text. An in-
mation, such as module type or f irmware tegrated ring buffer also e nables the
version, independently of the c ontroller. viewing of a diagnostics history. A link
Data for the network configuration, such enables the user to access the current
as the IP address or the PROFINET name, data sheet of the respective module
can also be viewed and m odified. Fur- quickly and simply.
thermore, additional information such as
F DN 20 – 4 S – 4 XSG – E
154 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
Type code
de
▪▪ PROFIBUS-DP slave
27,8
46,8 ▪▪ 9‑pin SUB-D female, for PROFIBUS
fieldbus connection
35,5 ▪▪ Rotary coding switch for setting the
94,9 PROFIBUS address
▪▪ 3 I/O power supply groups each
galvanically separated
57,1 ▪▪ 16 digital inputs
▪▪ 24 VDC, PNP
▪▪ Protection class IP20
152,4
Pinning overview
Position Notice Pinning assignment
PROFIBUS-DP v 1 = n.c.
Fieldbus cable (example): 2 = n.c.
3 = RD (Bus B)
1
D9T451‑2M (ident no. 6915759) or 6 4 = n.c.
5 = GND
RSSW-D9T451‑2M (ident no. 6915779) 5 9 6 = 5 VDC
7 = n.c.
8 = GN (Bus A)
9 = n.c.
156 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
PROFIBUS-DP slave
Technical data
Type FDP20-16S
Ident no. 6611465
Power supply
Supply voltage 24 VDC
Operating voltage range 18…30 VDC
Galvanic separation 500 V I/Os to PROFIBUS
Number of channels 16
Power loss, typical ≤ 1.8 W
Voltage supply connection pluggable screw terminal
System data
Fieldbus transmission rate 9.6 kbps … 12 Mbps
Fieldbus addressing 2 decimally coded rotary switches
Inputs
Number of channels 16
Input voltage 18…30 VDC
Input type PNP
Type of input diagnostics common diagnostics
Low level signal voltage < 4 V
High level signal voltage 8…24 V
Low level signal current < 0.5 mA
High level signal current 1…3.4 mA
Input delay 2.5 ms
Max. input current total: 700 mA
Environmental Conditions
Ambient temperature -40…+55 °C
MTTF 255 years acc. to SN 29500 (Ed. 99)
20 °C
Mechanical data
Mounting instruction for DIN rail
Protection class IP20
Dimensions 57.1 x 152.2 x 46.8 mm
▪▪ PROFIBUS-DP slave
27,8
46,8 ▪▪ Removable 5‑pin screw-clamp termi-
nal block, for PROFIBUS fieldbus
35,5 connection
94,9 ▪▪ Rotary coding switch for setting the
PROFIBUS address
▪▪ 3 I/O power supply groups each
galvanically separated
57,1
▪▪ 16 digital inputs
▪▪ 24 VDC, PNP
▪▪ Protection class IP20
152,4
Pinning overview
Position Notice Pinning assignment
PROFIBUS-DP
Fieldbus cable (example):
D9T451‑2M (ident no. 6915759) or
RSSW-451‑2M (ident no. 6914229)
158 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
PROFIBUS-DP slave
Technical data
Type FDP20-16S-T
Ident no. 6611485
Power supply
Supply voltage 24 VDC
Operating voltage range 18…30 VDC
Galvanic separation 500 V I/Os to PROFIBUS
Number of channels 16
Power loss, typical ≤ 1.8 W
Voltage supply connection pluggable screw terminal
System data
Fieldbus transmission rate 9.6 kbps … 12 Mbps
Fieldbus addressing 2 decimally coded rotary switches
Inputs
Number of channels 16
Input voltage 18…30 VDC
Input type PNP
Type of input diagnostics common diagnostics
Low level signal voltage < 4 V
High level signal voltage 8…24 V
Low level signal current < 0.5 mA
High level signal current 1…3.4 mA
Input delay 2.5 ms
Max. input current total: 700 mA
Environmental Conditions
Ambient temperature -40…+55 °C
Mechanical data
Mounting instruction for DIN rail
Protection class IP20
Dimensions 57.1 x 152.2 x 46.8 mm
▪▪ PROFIBUS-DP slave
27,8
46,8 ▪▪ 9‑pin SUB-D female, for PROFIBUS
fieldbus connection
35,5 ▪▪ Rotary coding switch for setting the
94,9 PROFIBUS address
▪▪ 3 I/O power supply groups each gal-
vanically separated
57,1 ▪▪ 16 universal digital channels, DI / DO
▪▪ 24 VDC, PNP
▪▪ output current: 0.5 A
▪▪ Protection class IP20
152,4
Pinning overview
Position Notice Pinning assignment
PROFIBUS-DP v 1 = n.c.
Fieldbus cable (example): 2 = n.c.
3 = RD (Bus B)
1
D9T451‑2M (ident no. 6915759) or 6 4 = n.c.
5 = GND
RSSW-D9T451‑2M (ident no. 6915779) 5 9 6 = 5 VDC
7 = n.c.
8 = GN (Bus A)
9 = n.c.
160 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
PROFIBUS-DP slave
Technical data
Type FDP20-16XSG
Ident no. 6611466
Power supply
Supply voltage 24 VDC
Operating voltage range 18…30 VDC
Galvanic separation 500 V I/Os to PROFIBUS
Number of channels 16
Power loss, typical ≤ 1.8 W
Voltage supply connection pluggable screw terminal
System data
Fieldbus transmission rate 9.6 kbps … 12 Mbps
Fieldbus addressing 2 decimally coded rotary switches
Inputs
Number of channels 16
Input voltage 18…30 VDC
Input type PNP
Type of input diagnostics common diagnostics
Low level signal voltage < 4 V
High level signal voltage 8…24 V
Low level signal current < 0.5 mA
High level signal current 1…3.4 mA
Input delay 2.5 ms
Max. input current total: 700 mA
Outputs
Number of channels 16
Switching frequency ≤ 100 Hz
Output voltage 18…30 VDC
Output current per channel 0.5A (from Aux)
Output type PNP
Short-circuit protection yes
Environmental Conditions
Ambient temperature -40…+55 °C
MTTF 170 years acc. to SN 29500 (Ed. 99)
20 °C
Mechanical data
Mounting instruction for DIN rail
Protection class IP20
Dimensions 57.1 x 152.2 x 46.8 mm
▪▪ PROFIBUS-DP slave
27,8
46,8 ▪▪ Removable 5‑pin screw-clamp termi-
nal block, for PROFIBUS fieldbus
35,5 connection
94,9 ▪▪ Rotary coding switch for setting the
PROFIBUS address
▪▪ 3 I/O power supply groups each gal-
vanically separated
57,1
▪▪ 16 universal digital channels, DI / DO
▪▪ 24 VDC, PNP
▪▪ output current: 0.5 A
152,4 ▪▪ Protection class IP20
Pinning overview
Position Notice Pinning assignment
PROFIBUS-DP
Fieldbus cable (example):
D9T451‑2M (ident no. 6915759) or
RSSW-451‑2M (ident no. 6914229)
162 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
PROFIBUS-DP slave
Technical data
Type FDP20-16XSG-T
Ident no. 6611486
Power supply
Supply voltage 24 VDC
Operating voltage range 18…30 VDC
Galvanic separation 500 V I/Os to PROFIBUS
Number of channels 16
Power loss, typical ≤ 1.8 W
Voltage supply connection pluggable screw terminal
System data
Fieldbus transmission rate 9.6 kbps … 12 Mbps
Fieldbus addressing 2 decimally coded rotary switches
Inputs
Number of channels 16
Input voltage 18…30 VDC
Input type PNP
Type of input diagnostics common diagnostics
Low level signal voltage < 4 V
High level signal voltage 8…24 V
Low level signal current < 0.5 mA
High level signal current 1…3.4 mA
Input delay 2.5 ms
Max. input current total: 700 mA
Outputs
Number of channels 16
Switching frequency ≤ 100 Hz
Output voltage 18…30 VDC
Output current per channel 0.5A (from Aux)
Output type PNP
Short-circuit protection yes
Environmental Conditions
Ambient temperature -40…+55 °C
Mechanical data
Mounting instruction for DIN rail
Protection class IP20
Dimensions 57.1 x 152.2 x 46.8 mm
▪▪ DeviceNet™ slave
▪▪ Screw-clamp terminal block, 5‑pin, for
23,5 DeviceNet™ fieldbus connection
▪▪ Rotary coding switch for setting the
ø5 DeviceNet™ address
▪▪ 4 digital Inputs
▪▪ 4 universal digital channels, DI / DO
55 ▪▪ 24 VDC, PNP
44,45 ▪▪ Output current 0.5 A
▪▪ Protection class IP20
31,25
62,5
Pinning overview
Position Notice Pinning assignment
DeviceNet™ and power supply
Fieldbus cable (example): 1=V+
2 = CANH
CBC5‑572‑2M (ident no. 6606065) or 3 = SHD
4 = CANL
RKC5701‑5M (ident no. 6931035) 1 2 3 4 5 5=V–
I/O channels
1=V– 6=I4
2 = I/O 0 7=I5
3 = I/O 1 8=I6
1 2 3 4 5 6 7 8 9 10 4 = I/O 2 9=I7
5 = I/O 3 10 = V +
164 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
DeviceNet™ slave
Technical data
Type FDN20-4S-4XSG
Ident no. 6611359
Power supply
Supply voltage 24 VDC
Operating voltage range 11…26 VDC
Number of channels 8
Power loss, typical ≤ 1.2 W
System data
Fieldbus transmission rate 125…500 kbps
Fieldbus addressing 2 decimally coded rotary switches
Fieldbus address range 0…63
Fieldbus connection technology screw terminals
Outputs
Number of channels 4
Switching frequency ≤ 100 Hz
Output voltage 18…26 VDC
Output current per channel 0.5 A (from DeviceNet™)
Output type PNP
Type of output diagnostics common diagnostics
Short-circuit protection yes
Connectivity Screw
Environmental Conditions
Ambient temperature -40…+70 °C
Mechanical data
Mounting instruction for mounting on panel; on DIN rail
with optional adapter FDN20‑BKT-DIN
( # 6931105)
Protection class IP20
Dimensions 55 x 62.5 x 23.5 mm
Pinning overview
Position Notice Pinning assignment
DeviceNet™ and power supply
Fieldbus cable (example): 1=V+
2 = CANH
CBC5‑572‑2M (ident no. 6606065) or 3 = SHD
4 = CANL
RKC5701‑5M (ident no. 6931035) 1 2 3 4 5 5=V–
I/O channels
1=V– 6=I4
2 = I/O 0 7=I5
3 = I/O 1 8=I6
1 2 3 4 5 6 7 8 9 10 4 = I/O 2 9=I7
5 = I/O 3 10 = V +
166 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
DeviceNet™ slave
Technical data
Type FDN20-4S-4XSG-E
Ident no. 6611343
Power supply
Supply voltage 24 VDC
Operating voltage range 11…26 VDC
Number of channels 8
Power loss, typical ≤ 1.2 W
Voltage supply connection Screw terminals or M12
System data
Fieldbus transmission rate 125…500 kbps
Fieldbus addressing 2 decimally coded rotary switches
Fieldbus address range 0…63
Inputs
Number of channels 8
Input voltage 11…26 VDC
Input type PNP
Type of input diagnostics common diagnostics
Low level signal voltage < 4 V
High level signal voltage 8…24 V
Low level signal current < 0.5 mA
High level signal current 1…3.4 mA
Max. input current Total: 700 mA
Outputs
Number of channels 4
Switching frequency ≤ 100 Hz
Output voltage 18…26 VDC
Output current per channel 0.5 A (from DeviceNet™)
Output type PNP
Type of output diagnostics common diagnostics
Short-circuit protection yes
Connectivity Screw
Environmental Conditions
Ambient temperature -40…+70 °C
Mechanical data
Mounting instruction for mounting on control cabinet wall
Protection class IP20
Dimensions 55 x 62.5 x 23.5 mm
▪▪ DeviceNet™ slave
25
44,1
▪▪ Removable screw-clamp terminal
block, 5‑pin, for DeviceNet™ fieldbus
35,5 connection
94,9 ▪▪ Rotary coding switch for setting the
DeviceNet™ address
▪▪ 3 I/O power supply groups each
galvanically separated
57,1
▪▪ 16 digital inputs
▪▪ 24 VDC, PNP
▪▪ Protection class IP20
152,2
Pinning overview
Position Notice Pinning assignment
DeviceNet™ and power supply
Fieldbus cable (example): 1
2
1=V+
2 = CANH
CBC5‑572‑2M (ident no. 6606065) or 3 3 = SHD
4 4 = CANL
RKC5701‑5M (ident no. 6931035) 5 5=V–
168 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
DeviceNet™ slave
Technical data
Type FDN20-16S
Ident no. 6611312
Power supply
Supply voltage 24 VDC
Operating voltage range 11…26 VDC
Number of channels 16
Power loss, typical ≤ 1.2 W
System data
Fieldbus transmission rate 125…500 kbps
Fieldbus addressing 2 decimally coded rotary switches
Fieldbus address range 0…63
Fieldbus connection technology pluggable screw terminal
Environmental Conditions
Ambient temperature -40…+70 °C
Mechanical data
Mounting instruction for DIN rail
Protection class IP20
Dimensions 57.1 x 152.2 x 44.1 mm
▪▪ DeviceNet™ slave
25
44,1
▪▪ Removable screw-clamp terminal
block, 5‑pin, for DeviceNet™ fieldbus
35,5 connection
94,9 ▪▪ Rotary coding switch for setting the
DeviceNet™ address
▪▪ 3 I/O power supply groups each
galvanically separated
57,1
▪▪ 16 universal digital channels, DI / DO
▪▪ 24 VDC, PNP
▪▪ output current: 0.5A
152,2 ▪▪ Protection class IP20
Pinning overview
Position Notice Pinning assignment
DeviceNet™ and power supply
Fieldbus cable (example): 1
2
1=V+
2 = CANH
CBC5‑572‑2M (ident no. 6606065) or 3 3 = SHD
4 4 = CANL
RKC5701‑5M (ident no. 6931035) 5 5=V–
170 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
DeviceNet™ slave
Technical data
Type FDN20-16XSG
Ident no. 6611373
Power supply
Supply voltage 24 VDC
Operating voltage range 11…26 VDC
Number of channels 16
Power loss, typical ≤ 1.2 W
System data
Fieldbus transmission rate 125…500 kbps
Fieldbus addressing 2 decimally coded rotary switches
Fieldbus address range 0…63
Fieldbus connection technology pluggable screw terminal
Outputs
Number of channels 16
Switching frequency ≤ 100 Hz
Output voltage 18…26 VDC
Output current per channel 0.5A (from Aux)
Output type PNP
Type of output diagnostics common diagnostics
Short-circuit protection yes
Environmental Conditions
Ambient temperature -40…+70 °C
Mechanical data
Mounting instruction for DIN rail
Protection class IP20
Dimensions 57.1 x 152.2 x 44.1 mm
▪▪ EtherNet/IP™ slave
▪▪ Modbus TCP slave
19,5
30 ▪▪ PROFINET slave
▪▪ 2 RJ45 ports for the Ethernet
connection
▪▪ Integrated Ethernet switch
▪▪ 10/100 Mbps
44,5 55 ▪▪ 4 digital Inputs
▪▪ 4 universal digital channels, DI / DO
▪▪ 24 VDC, PNP
▪▪ Output current: 1.0 A
62,5 ▪▪ Protection class IP20
Pinning overview
Position Notice Pinning assignment
Ethernet 1 = TX +
Fieldbus cable (example): 12345678 2 = TX –
3 = RX +
RJ45S-RJ45S-441‑2M (ident no. 6932517) or 4 = n.c.
RJ45‑FKSDD-441‑0.5M/S2174 (ident no. 6914221) 5 = n.c.
6 = RX –
7 = n.c.
8 = n.c.
Power supply
1=
2 = V1 –
3 = V1 +
1 2 3
I/O channels
1 = V1 – 6=I5
2 = I/O 1 7=I6
3 = I/O 2 8=I7
1 2 3 4 5 6 7 8 9 10 4 = I/O 3 9=I8
5 = I/O 4 10 = VOUT1 +
172 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
Multiprotocol Ethernet slave
Technical data
Type FEN20-4DIP-4DXP Outputs
Ident no. 6931090 Number of channels 4
Output voltage 12…30 VDC
Power supply Output current per channel 1A
Supply voltage 24 VDC Output total current 4A
Operating voltage range 12…30 VDC Output type PNP
Galvanic separation 500 V I/Os to Ethernet Load type resistive, inductive, lamp load
Number of channels 8 Short-circuit protection yes
Power loss, typical ≤ 2.4 W
Voltage supply connection screw terminals Environmental Conditions
Ambient temperature -40…+70 °C
System data Storage temperature -40 … +85 ºC
Connection technology Ethernet 2 x RJ45 sockets
Protocol detection automatic Mechanical data
EtherNet/IP™
Addressing acc. to EtherNet/IP™ specification
Quick Connect (QC) < 150 ms
Device Level Ring (DLR) supported
Simultaneous CIP connections 6
PROFINET
Addressing DCP
Conformance Class B (RT)
MinCycleTime 1 ms
Fast Start-Up (FSU) < 150 ms
Diagnostics acc. to PROFINET alarm handling
Topology detection supported
Automatic addressing supported
Inputs
Number of channels 8
Input voltage 24 VDC
Input type PNP
Type of input diagnostics summarized diagnostics
Low level signal voltage < 7 VDC
High level signal voltage 7…30 VDC
Low level signal current < 1.5 mA
High level signal current > 2 mA
Input delay 2.5 ms
Max. input current 6 mA
▪▪ EtherNet/IP™ slave
46,7 ▪▪ Modbus TCP slave
27,8 ▪▪ PROFINET slave
▪▪ 2 RJ45 ports for the Ethernet
95 connection
▪▪ Integrated Ethernet switch
▪▪ 10/100 Mbps
57,2 ▪▪ 16 universal digital channels, DI / DO
▪▪ 24 VDC, PNP
▪▪ Output current: 1.0 A
▪▪ Protection class IP20
152,4
Pinning overview
Position Notice Pinning assignment
Ethernet 1 = TX +
Fieldbus cable (example): 12345678 2 = TX –
3 = RX +
RJ45S-RJ45S-441‑2M (ident no. 6932517) or 4 = n.c.
RJ45‑FKSDD-441‑0.5M/S2174 (ident no. 6914221) 5 = n.c.
6 = RX –
7 = n.c.
8 = n.c.
174 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Compact block I/O modules in IP20
Multiprotocol Ethernet slave
Technical data
Type FEN20-16DXP Outputs
Ident no. 6931089 Number of channels 16
Output voltage 12…30 VDC
Power supply Output current per channel at 70 °C: 0.5 A (8 A in total) or 0.75 A
Supply voltage 24 VDC (6 A in total);
at 50 °C: 0.75 A (12 A in total) or 1 A (8
Operating voltage range 12…30 VDC
A in total)
Galvanic separation 500 V I/Os to Ethernet
Output type PNP
Number of channels 16
Load type resistive, inductive, lamp load
Power loss, typical ≤ 2.4 W
Short-circuit protection yes
Voltage supply connection pluggable screw terminal
Environmental Conditions
System data
Ambient temperature -40…+70 °C
Connection technology Ethernet 2 x RJ45 sockets
Storage temperature -40 … +85 ºC
Protocol detection automatic
EtherNet/IP™
Addressing acc. to EtherNet/IP™ specification
Quick Connect (QC) < 150 ms
Device Level Ring (DLR) supported
Simultaneous CIP connections 6
PROFINET
Addressing DCP
Conformance Class B (RT)
MinCycleTime 1 ms
Fast Start-Up (FSU) < 150 ms
Diagnostics acc. to PROFINET alarm handling
Topology detection supported
Automatic addressing supported
Inputs
Number of channels 16
Input voltage 24 VDC
Input type PNP
Type of input diagnostics summarized diagnostics
Low level signal voltage < 9 VDC
High level signal voltage 11…30 VDC
Low level signal current < 1.5 mA
High level signal current > 2.5 mA
Input delay 2.5 ms
Max. input current 6 mA
Block I/O
Block I/O Modules F
Block I/O Modules Fxx20 – Accessories
8,5
44,5
50 19 50
176 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Accessories
Block I/O Modules Fxx20 – Accessories
O Modules Fxx2
Fxx20 – Accessories
178 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Short Description
excom® – Remote-I/
excom® – Remote-I/O system
excom® is a remote I/O system for use in All modules can be connected particu
Ex and non-Ex areas. This benefits the larly easily: The gateways, power supply
user not only in terms of system compo- units, and I/O modules, are fitted easily
nents optimized for a particular zone, to the module rack. This provides all the
but also because of the standard con- internal connections; only the peripheral
cept for configuring and parametrizing devices have to be connected. All mod-
the periphery and field instrumentation. ules can be fitted or removed (hot
The excom® system provides bus-capa- swapped) during operation. The system
ble, decentralized input and output checks automatically whether the new
modules with protection to IP20 for c on- module matches the settings of the slot.
necting intrinsically safe and non-intrin- The excom® DTM (Device Type Manager)
sically safe digital and analog field d
evic- makes it possible to easily commission
es. Depending on the periphery u sed, the periphery and the field instrumenta
Standardized syste
Standard system features Standard
Redundancy
Re
R e Local
Lo
possible
p o through
gh
gh diagnostics
d
two power supply
ttw pp
ply
ly through
th LED
units
un indication
in
Redundancy
Redund
ndan cy possible
ancy
through two gateways
Choiceeooff bu
buss address
via rotary coding
switches
Connection
C ti to the power
t th Connection off th
Connectiion o the higher- Labeling
Labeling options
ling opt
ptio
ions
supply (on Ex-e terminals level PROFIBUS-DP fieldbus
under the end cap)
180 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Standardized system features
dized system fe
em features
Different I/O
D
module types
m Application range: non-intrinsically safe applications
MT08 MT16
MT08 MT16
6
MT24
4
Application range: intrinsically safe circuits and installation in zone 1
Connection
on of
onnection of the
the Ex-i
Ex-i field
devices via removable screw ter- 6
MT16
minals or cage clamp terminals
Our Stren
Our Strengths – You
Our Strengths – Your advantages
The Remote-I/O system excom® allows stalled in zones 1 and 2, a specially opti-
the user to freely select the location of mized power supply unit is available that
installation. The system can be installed generates the intrinsically safe system
both in zone 1 and in zone 2 or in the voltage. The interface to the fieldbus, in
non-Ex area. This benefits the user not this case PROFIBUS-DP, is also intrinsical-
only in terms of components optimized ly safe. A new module rack offers here
for a particular zone, but also because of the possibility of operating up to 24 I/O
the standard concept for configuring modules in the non-Ex area a nd in zone
and parametrizing the periphery and 2, which further reduces the b asic instal-
field instrumentation. If this system is in- lation costs.
Hot swapping makes the excom® system even in zone 1, without disturbing the
particularly user-friendly: The system can field communication. This increases
be serviced and changed at any time. plant availability and saves time when
The I/O modules – including the power the system is commissioned and
supply modules – can be plugged and extended.
unplugged during ongoing operation,
The new excom® DTM and the advanced project tree of the frame a pplication. All
gateway communication mechanisms in peripheral modules and HART® field de-
the gateway allow the user to easily op- vices will then be available online for the
erate the periphery and the field instru- operator. The entire field w
iring can thus
mentation at any time via the P ROFIBUS be checked and the H ART® field devices
network, with or without the h igher-lev- with their associated DTM diagnosed
el master Class 1 control system. With and configured. In this way, a validated
the help of an FDT frame s uch as PACT- transfer of the field installation to the
ware™, all systems present on the PROFI- control system is possible.
BUS can be scanned and copied to the
182 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Our Strengths – Your Advantages
ngths – Your A
ur Advantages
HART® – End-to-end parametrization from the process control system down to
the field device
excom® takes advantage of the world the control system additional informa
wide use of HART® communication and tion on process values, diagnostics and
allows field devices to be HART® para asset management directly in digital
metrized seamlessly via the bus. The sys- form. Since the communication protocol
tem transmits the process and d iagnos- allows the transmission of data over al-
tic data of the periphery andready installed lines, the user can build,
communicates, if necessary, with the service and maintain the last mile with
HART® field instrumentation. This gives little effort.
System in
System installation
System installation – Overview
184 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
System installation – Overview
nstallation – O
n – Overview
Solutions
Solutions for the Ex
Solutions for the Ex area
The excom® series gives the user com- erates an intrinsically safe system
plete freedom in the choice of the instal- voltage.
lation location. It can be installed in The interface to the fieldbus, in this case
zones 1 and 2 and in the non-Ex area. PROFIBUS-DP, is also intrinsically safe.
The user benefits here not only from the This configuration enables the entire s ys-
components that were optimized for the tem to be fully maintained during o pera-
particular zone provided, but also from a tion in the Ex area. In the cabinets previ-
standard concept for the configuration ously used in excom® installa tions in
and parametrization of the periphery zone 2, the space now available c an be
and field instrumentation. used for additional components, s uch as
A standard Ex-i periphery supports signal valve blocks or load switches.
processing and field device control from A special gateway provides the neces-
zones 0, 1 and 2. If this periphery is in- sary p rotection of the Ex-i periphery to
stalled in zones 1 and 2 in order to detect the b us so that a separate segment cou-
signals as closely as possible to the loca- pler is not required for implementing the
tion of the instrumentation, an opti- intrinsically safe physical bus character
mized power supply module is available istics of RS485‑IS, if the excom® system is
specially for this application, which g en- installed in the safe area.
186 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Short description/Table of contents
The I/O module DM80Ex is designed for sion protection category of inputs/out- value, wire-break and short
circuit
the connection of NAMUR sensors (DIN puts is Ex ia IIC. monitoring.
EN 60 60947‑5‑6) and actuators. When
wire-break or short-circuit monitoring When connecting the field devices, care The user can furthermore determine
are activated, mechanical contacts can has to be taken that all inputs and/or whether an input or an output should
only be connected with a corresponding outputs are on a common potential. be provided at the connecting point.
resistor circuitry (WM1, Ident no. The following configurations are possi-
0912101). Input and output mode can be adjusted ble: 8 inputs/0 outputs; 6 inputs/2 out-
via the PROFIBUS-DP master. The follow- puts up to 0 inputs/8 outputs (GSD-file,
The module features protection class Ex ing parameters can be adjusted: s witch- Mode 2). This guarantees optimal adap-
ib IIC and can be mounted in zone 1 in ing behaviour, switch-on delay, default tation to the corresponding application
combination with excom®. The explo- environment.
188 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type DM80EX Environmental Conditions
Ident no. 6884006 Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Power supply Vibration test acc. to IEC 60068‑2‑6
Supply voltage via the backplanes, central power Shock test acc. to IEC 60068‑2‑27
supply EMC acc. to EN 61326-1 (2006)
Power consumption ≤ 1 W acc. to NAMUR NE21 (2007)
Galvanic separation to int. bus and supply circuit MTTF 141 years acc. to SN 29500 (Ed. 99)
Number of channels 8‑channel 40 °C
Outputs
Output circuits for intrinsically safe actuators
No-load voltage 8 VDC
Nominal current 4 mA
Switching frequency ≤ 100 Hz
Indication
Operational readiness 1 x green / red
State/ Fault 8 x yellow / red
Features
▪▪ Frequency module for the connection
of intrinsically safe sensors (according
to NAMUR)
The input module DF20EX is equipped protection category of inputs/outputs is frequency of one block is 4 kHz; with 2
with 8 channels according to NAMUR Ex ia IIC. blocks the frequency is reduced to
which are split into two blocks. There is 2 kHz.
one frequency input per block and three The module can be used as a counter or
control inputs/outputs. frequency module: It is thus suited for Input and output mode can be adjusted
pulse counting of binary input s ignals or via the PROFIBUS-DP master. Each chan-
The module features protection class Ex frequency measurements of binary nel is equipped with parametrizable
ib IIC and can be mounted in zone 1 in pulse sequences of NAMUR sensors. wire-break/short-circuit m
onitoring.
combination with excom®. When con-
necting the field devices, care has to be The counting direction can either be set
taken that all inputs and/or outputs are externally via a control input or internal-
on a common potential. The explosion ly by setting a parameter. The m aximum
190 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type DF20EX EMC acc. to EN 61326-1 (2006)
Ident no. 6884061 acc. to N AMUR NE21 (2007)
MTTF 101 years acc. to SN 29500 (Ed. 99)
40 °C
Power supply
Supply voltage via the backplanes, central power
Mechanical data
supply
Power consumption ≤ 1 W Housing material plastic
Galvanic separation to int. bus and supply circuit Connection mode module, plugged on rack
Number of channels 2‑channel Protection class IP20
Dimensions 18 x 118 x 103 mm
Inputs
Input circuits acc. to EN 60947‑5‑6 (NAMUR), Approval | Certification ATEX, IECEx, cFMus, TR CU, CMI, KOSHA,
intrinsically safe acc. to EN 60079‑11 INMETRO, GL, DNV, BV, LR
No-load voltage 8 VDC
Short-circuit current 4 mA
Switching frequency ≤ 4000 Hz
Short-circuit < 367 Ω
Wire-break < 0.2 mA
Switch-on threshold: 1.8 mA
Switch-off threshold: 1.4 mA
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Indication
Operational readiness 1 x green / red
State/ Fault 8 x yellow / red
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
BN +
31
BU
32
channel 3
33
34
BN +
41
BU
42
channel 4
43
44
The input module DI401‑EX is designed The module features protection class Ex switching behaviour, switch-on delay,
for the connection of NAMUR sensors ib IIC and can be mounted in zone 1 in default value, wire-break and short cir-
(DIN EN 60947‑5‑6) or mechanical combination with excom®. The explo- cuit monitoring.
contacts. sion protection category of the inputs is
Ex ia IIC. The inputs are galvanically iso-
When wire-break or short-circuit moni- lated from each other.
toring are activated, mechanical con-
tacts can only be connected with a cor- The behaviour of the inputs can be a d-
responding resistor circuitry (WM1, justed via the PROFIBUS-DP master. The
Ident no. 0912101). following parameters can be adjusted:
192 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type DI401EX Mechanical data
Ident no. 6884232 Housing material plastic
Connection mode module, plugged on rack
Power supply Protection class IP20
Supply voltage via the backplanes, central power Dimensions 18 x 118 x 103 mm
supply
Power consumption ≤ 0.75 W Approval | Certification ATEX
Galvanic separation complete galvanic isolation acc. to
EN 60079‑11
Number of channels 4‑channel
Inputs
Input circuits acc. to EN 60947‑5‑6 (NAMUR),
intrinsically safe acc. to EN 60079‑11
No-load voltage 8.2 VDC
Short-circuit current 2.7 mA
Switching frequency ≤ 100 Hz
Short-circuit < 367 Ω
Wire-break < 0.15 mA
Switch-on threshold: 1.8 mA
Switch-off threshold: 1.3 mA
Indication
Operational readiness 1 x green / red
State/ Fault 4 x yellow / red
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. EN 61326‑1 (2013)
acc. to Namur NE21 (2012)
MTTF 111 years acc. to SN 29500 (Ed. 99)
40 °C
Features
▪▪ Output module for intrinsically safe
actuators
▪▪ Complete galvanic isolation
The output module DO401Ex is de- One actuator per channel can be con- The following values are supported for
signed for the connection of intrinsically nected. The choice of connection ena- example:
safe actuators such as valves or indicator bles two intrinsically safe circuits with
lights. different Ex-data per channel. ▪▪ 22.5 V / 5 mA
▪▪ 19.0 V / 15 mA
The module features protection class Ex Please see the load curve for the valve ▪▪ 16.0 V / 25 mA
ib IIC and can be mounted in zone 1 in control values. Please refer to the Ex-ap- ▪▪ 14.0 V / 35 mA
combination with excom®. Explosion proval of the valve manufacturer for the ▪▪ 12.0 V / 45 mA
protection category is Ex ia IIC. The out- admissible limit values.
puts are galvanically isolated from e ach
other.
Load curve terminal connection 1+2 Load curve terminal connection 3+4
194 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type DO401EX Indication
Ident no. 6884203 Operational readiness 1 x green / red
State/ Fault 4 x yellow / red
Power supply
Supply voltage via the backplanes, central power Environmental Conditions
supply Ambient temperature -20…+70 °C
Power consumption ≤ 4.5 W Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Galvanic separation complete galvanic isolation acc. to Vibration test acc. to IEC 60068‑2‑6
EN 60079‑11
Shock test acc. to IEC 60068‑2‑27
Number of channels 4‑channel
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
Outputs MTTF 79 years acc. to SN 29500 (Ed. 99)
Output circuits for intrinsically safe actuators 40 °C
Switching frequency ≤ 50 Hz
Short circuit ï 50 mA Mechanical data
Wire-break < 1 mA Housing material plastic
Connection mode module, plugged on rack
Approvals and declarations Protection class IP20
Ex approval acc. to conformity certificate PTB 10 ATEX 2024 Dimensions 18 x 118 x 103 mm
Device designation É II 2 (1) G Ex ib [ia] IIC T4
É II (1) D [Ex ia IIIC] Approval | Certification ATEX, IECEx, cFMus, TR CU, KOSHA,
Max. values: Terminal connection: 1+2 INMETRO, GL, DNV, BV, LR
Max. output voltage Uo ≤ 25 V
Max. output current Io ≤ 80 mA
Max. output power Po ≤ 750 mW
Characteristic angular
+
31
I
Aux
32
channel 3 +
33
34
+
41 I
Aux
42
channel 4 +
43
44
The input module AI401Ex is designed cuits feature protection class Ex ia IIC censed modem. An additional imped-
for the connection of 2‑wire transducers resp. Ex iaD. ance in the circuit is not necessary.
(active input = source mode / transduc-
er passive) or 4‑wire transducers (pas- The field circuits are galvanically isolat-
The measuring range is digitized in the
sive input = sink mode / transducer ed from each other. scope of 0…21 mA. For clear reading,
active). the digitized value is displayed in a
HART® compatible transducers can be range of 0 … 21000 (independent of the
The module features protection class Ex connected to the module. The field d e- parametrized measuring range) and
ib IIC and can be mounted in zone 1 in vice can thus be parametrized directly at transmitted to the host system.
combination with excom®. The field cir- the terminals on the DIN rail with a li-
196 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type AI401Ex External inductance/capacitance Lo/Co
Ident no. 6884204 IIC IIB
Lo [mH] 10 20
Power supply Co [nF] 1900 8600
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 2.2 W Indication
Galvanic separation complete galvanic isolation acc. to Operational readiness 1 x green / red
EN 60079‑11 State/ Fault 4 x red
Number of channels 4‑channel
Environmental Conditions
Inputs Ambient temperature -20…+70 °C
Input circuits intrinsically safe acc. to EN 60079‑11, Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
0/4…20 mA Vibration test acc. to IEC 60068‑2‑6
Supply voltage 15 VDC at 20 mA Shock test acc. to IEC 60068‑2‑27
Overload capability > 21 mA EMC acc. to EN 61326-1 (2006)
Low level control < 3.6 mA acc. to NAMUR NE21 (2007)
Short-circuit > 24 mA (only in live zero mode) MTTF 77 years acc. to SN 29500 (Ed. 99)
Wire-break < 2 mA (only in live zero mode) 40 °C
+
31 U
Aux
32
channel 3 +
33
34
+
41
U
Aux
42
channel 4 +
43
44
The input module AI41Ex is designed for sion protection category of the inputs is played in a range of 0…21000 and
the connection of 4‑wire transducers Ex ia IIC. The inputs are galvanically iso- transmitted to the host system. For
(passive input = sink mode / transducer lated from each other. transmission to the host system, voltage
active). is indicated as a value in a range b e-
The resolution is 14 bit, i.e. the analog tween 0…10000.
The module features protection class Ex value between 0…21 mA is represented
ib IIC and can be mounted in zone 1 in as a number between 0 and 16383. For
combination with excom®. The explo- clear reading, the digitized value is d is-
198 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type AI41EX External inductance/capacitance Lo/Co
Ident no. 6884020 IIC IIB
Lo [mH] Co [µF] Co [µF]
Power supply 2.0 2.0 11
Supply voltage via the backplanes, central power 1.0 2.3 12
supply
0.5 2.7 15
Power consumption ≤ 1 W
0.2 3.3 19
Galvanic separation complete galvanic isolation acc. to
EN 60079‑11
Number of channels 4‑channel Indication
Operational readiness 1 x green / red
Inputs State/ Fault 4 x red
Input circuits intrinsically safe acc. to EN 60079‑11,
0/4…20 mA Environmental Conditions
Overload capability > 22 mA Ambient temperature -20…+60 °C
Low level control < 3.6 mA Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Short-circuit < 5 V (only in live zero mode) Vibration test acc. to IEC 60068‑2‑6
Wire-break < 2 mA (only in live zero mode) Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
Response characteristic acc. to N AMUR NE21 (2007)
Resolution 14 Bit MTTF 98 years acc. to SN 29500 (Ed. 99)
Linearity deviation ≤ 0.1 % full scale 40 °C
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %) Mechanical data
Housing material plastic
Approvals and declarations Connection mode module, plugged on rack
31
31
32
32
channel 3 33 R-3L
33
34
34
41
41
42
42
channel 4 43 R-4L
43
44
44
The analog input module AI43Ex is de- nal bus and from each other. The mod- parametrized substitute value is imme-
signed for the connection of potentio ule features protection class Ex ib IIC diately output and the output value is
meters in 3 or 4‑wire technology. If and can be mounted in zone 1 in c ombi- set to ‚invalid-bit‘. This
state is main-
3‑wire potentiometers are used, the ter- nation with excom®. The explosion pro- tained until valid measured v alues are
minals at the module rack have to be tection category of the inputs is Ex ia IIC. provided again.
bridged. Resistance measurements, i.e.
the evaluation of potentiometers with a Each potentiometer input is monitored The resolution is 14 bit. For clear read-
2‑wire connection, is not possible. for wire break. The interruption of a s in- ing, 0…100 % is digitized and d isplayed
gle connection line is securely detected, in a range of 0…10000 (independent of
The module has four field circuits to as well as any combination of interrup- the parametrized measuring range) and
control 3 or 4‑wire potentiometers. The tions occuring at the four input connec- transmitted to the host system.
field circuits are galvanically isolated tion lines. Short-circuit monitoring is not
from the power supply, from the inter- carried out. In case of a line error, the
200 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type AI43EX Mechanical data
Ident no. 6884137 Housing material plastic
Connection mode module, plugged on rack
Power supply Protection class IP20
Supply voltage via the backplanes, central power Dimensions 18 x 118 x 103 mm
supply
Power consumption ≤ 1.5 W Approval | Certification ATEX, TR CU, CMI, GL, DNV, BV, LR
Galvanic separation complete galvanic isolation acc. to
EN 60079‑11
Number of channels 4‑channel
Inputs
Input circuits intrinsically safe acc. to EN 60079‑11,
potentiometer
Nominal resistance 400 Ω … 12 kΩ
Response characteristic
Resolution 14 Bit
Linearity deviation ≤ 0.1 % full scale
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 % with shielded signal cable
influence ≤ 1 % with unshielded signal cable
Indication
Operational readiness 1 x green / red
State/ Fault 4 x red
Environmental Conditions
Ambient temperature -20…+60 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to N AMUR NE21 (2007)
MTTF 71 years acc. to SN 29500 (Ed. 99)
40 °C
+
31
0/4...20 mA
32
channel 3
33
34
+
41
0/4...20 mA
42
channel 4
43
44
202 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type AO401Ex Environmental Conditions
Ident no. 6884205 Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Power supply Vibration test acc. to IEC 60068‑2‑6
Supply voltage via the backplanes, central power Shock test acc. to IEC 60068‑2‑27
supply EMC acc. to EN 61326-1 (2006)
Power consumption ≤ 2.2 W acc. to NAMUR NE21 (2007)
Galvanic separation complete galvanic isolation acc. to MTTF 78 years acc. to SN 29500 (Ed. 99)
EN 60079‑11 40 °C
Number of channels 4‑channel
Mechanical data
Outputs Housing material plastic
Output circuits intrinsically safe acc. to EN 60079‑11, Connection mode module, plugged on rack
0/4…20 mA Protection class IP20
No-load voltage 16 VDC Dimensions 18 x 118 x 103 mm
External load ≤ 640 Ω
Short circuit < 50 Ω (only in live zero mode) Approval | Certification ATEX, cFMus, TR CU, CMI, INMETRO, GL,
Wire-break < 2 mA (only in live zero mode) DNV, BV, LR
Response characteristic
Resolution 13 Bit
Linearity deviation ≤ 0.05 % full scale
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 %
influence
Indication
Operational readiness 1 x green / red
State/ Fault 4 x red
Features
▪▪ Input module for connection of 2‑wire
transmitters
▪▪ Transmission of HART® data
The input module AIH40Ex is designed field devices, care has to be taken that Up to 8 HART® variables (max. 4 per
for the connection of 2‑wire transducers all inputs are on a common potential. channel) can be read via the cyclical
(active input = source mode/transducer PROFIBUS data traffic. The bidirectional
passive). HART® compatible sensors connected to exchange of variables between the host
the module communicate with the inte- system and the HART® transmitter is im-
The module features protection class Ex grated HART® controller. plemented via PROFIBUS-DPV1.
ib IIC and can be mounted in zone 1 in
combination with excom®. The explo- The resolution is 14 bit, i.e. the analog Parameters like wire-break or short-cir-
sion protection category of the inputs is value between 0…21 mA is represented cuit monitoring, measuring range,
Ex ia IIC. as a number between 0 and 16383. For HART® communication etc., can be a d-
clear reading, the digitized value is d is- justed for each channel separately a nd
The inputs are not galvanically isolated played in a range of 0…21000 and PROFIBUS
are solely initialized by the
from each other. When connecting the transmitted to the host system. master.
204 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type AIH40EX Shock test acc. to IEC 60068‑2‑27
Ident no. 6884001 EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
Power supply MTTF 61 years acc. to SN 29500 (Ed. 99)
40 °C
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 3 W Mechanical data
Galvanic separation to int. bus and supply circuit Housing material plastic
Number of channels 4‑channel Connection mode module, plugged on rack
Protection class IP20
Inputs Dimensions 18 x 118 x 103 mm
Input circuits intrinsically safe acc. to EN 60079‑11,
0/4…20 mA Approval | Certification ATEX, IECEx, cFMus, TR CU, CMI, KOSHA,
Supply voltage 15 VDC at 22 mA NEPSI, INMETRO, GL, DNV, BV, L R
HART® Impedance > 240 Ω
Overload capability > 22 mA
Low level control < 3.6 mA
Short-circuit < 5 V (only in live zero mode)
Wire-break < 2 mA (only in live zero mode)
Response characteristic
Resolution 14 Bit
Linearity deviation ≤ 0.1 % full scale
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 % with shielded signal cable
Indication
Operational readiness 1 x green / red
State/ Fault 4 x red
Environmental Conditions
Ambient temperature -20…+60 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Features
▪▪ Input module for connection of 4‑wire
transmitters
▪▪ Transmission of HART® data
The input module AIH41Ex is designed field devices, care has to be taken that
Up to 8 HART® variables (max. 4 per
for the connection of 4‑wire transducers all inputs are on a common potential. channel) can be read via the cyclical
(passive input = sink mode / transducer PROFIBUS data traffic. The bidirectional
active). HART® compatible sensors connected to exchange of variables between the host
the module communicate with the system and the HART® transmitter is im-
The module features protection class Ex HART® controller. plemented via PROFIBUS-DPV1.
ib IIC and can be mounted in zone 1 in
combination with excom®. The explo- The resolution is 14 bit, i.e. the analog Parameters like wire-break or short-cir-
sion protection category of the inputs is value between 0…21 mA is represented cuit monitoring, measuring range,
Ex ia IIC. as a number between 0 and 16383. For HART® communication etc., can be a d-
clear reading, the digitized value is d is- justed for each channel separately a nd
The inputs are not galvanically isolated played in a range of 0…21000 and PROFIBUS
are solely initialized by the
from each other. When connecting the transmitted to the host system. master.
206 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type AIH41EX MTTF 93 years acc. to SN 29500 (Ed. 99)
Ident no. 6884005 40 °C
Response characteristic
Resolution 14 Bit
Linearity deviation ≤ 0.1 % full scale
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 % with shielded signal cable
influence ≤ 1 % with unshielded signal cable
Indication
Operational readiness 1 x green / red
State/ Fault 4 x red
Environmental Conditions
Ambient temperature -20…+60 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
+
31
0/4...20 mA
32
channel 3
33
34
+
41
0/4...20 mA
42
channel 4
43
44
The output module AOH40Ex is de- The outputs are not galvanically isolated number between 0 and 8191. For easier
signed for the connection of intrinsically from each other. When connecting the operation, the host system operates in a
safe
analog actuators such as control field devices, care has to be taken that value range between 0…21000. This
valves or process indicators. all outputs are on a common potential. raw value is reduced by the AOH40EX to
a 13‑bit resolution.
The module features protection class Ex HART® compatible actuators connected
ib IIC and can be mounted in zone 1 in to the module communicate directly Parameters such as line monitoring, s ub-
combination with excom®. E xplosion with the HART® controller. stitute values etc. can be adjusted for
protection category is Ex ia IIC. each channel separately and are initial-
The resolution is 13 bit, i.e. the analog ized solely by the master.
value of 0…21 mA is represented as a
208 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type AOH40EX MTTF 66 years acc. to SN 29500 (Ed. 99)
Ident no. 6884003 40 °C
Response characteristic
Resolution 13 Bit
Linearity deviation ≤ 0.1 % full scale
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 % with shielded signal cable
influence ≤ 1 % with unshielded signal cable
Indication
Operational readiness 1 x green / red
State/ Fault 4 x red
Environmental Conditions
Ambient temperature -20…+60 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
Features
▪▪ Input module for the connection of
temperature probes
▪▪ Complete galvanic isolation
The input module TI40Ex is designed for sion protection category of the inputs is for all channels via an integrated PT100
the connection of 2, 3 and 4‑wire tem- Ex ia IIC. resistor.
perature probes of the types Pt100,
Pt200, Pt500, Pt1000, Ni100 and CU100, Line compensation of 2‑wire tempera- The internal resolution is 16 bit, the
as well as for the connection of thermo- ture resistors is done by means o
f para- analog value is represented as a number
couples of the types B, E, D, J, K, L , N, R, metrized resistance values. These values between 0 and 32767 on the PROFIBUS-
S, T and U. The module can also be used have to be determined first through DP. The temperature is indicated in Kel-
for the measurement of low v oltages measurements. vin. For conversion to °C, please o
bserve
(-75…+75 mV, -1.2…+1.2 V) and resist- an offset of 273.2.
ance measurements (0…30 Ω, 0 …300 Ω, When using thermocouples, external
0…3 kΩ) cold junction compensation can be c ar- Parameters such as line monitoring, s ub-
ried out separately for each channel by stitute values etc. can be adjusted for
The module features protection class Ex connecting resistors such as the P
t100 each channel separately and are initial-
ib IIC and can be mounted in zone 1 in to the two unused terminals. Internal ized solely by the master.
combination with excom®. The e xplo- compensation instead is parametrized
210 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type TI40Ex External inductance/capacitance Lo/Co
Ident no. 6884000 IIC IIB
Lo [mH] Co [µF] Co [µF]
Power supply 2.0 1.6 9.8
Supply voltage via module rack, central power supply 1.0 1.9 12
module
0.5 2.3 14
Power consumption ≤ 1 W
0.2 3.0 19
Galvanic separation complete galvanic isolation acc. to
EN 60079‑11
Number of channels 4‑channel Indication
Operational readiness 1 x green / red
Inputs State/ Fault 4 x red
Input circuits intrinsically safe acc. to EN 60079‑11,
Cu100, Ni 100, Pt100, Pt200, Pt500, Environmental Conditions
Pt1000, thermocouple
Ambient temperature -20…+60 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Response characteristic
Vibration test acc. to IEC 60068‑2‑6
Resolution 16 Bit
Shock test acc. to IEC 60068‑2‑27
Linearity deviation ≤ 0.05 % measuring range
EMC acc. to EN 61326-1 (2006)
Temperature drift ≤ 0.005 % / K acc. to N AMUR NE21 (2007)
Rise time/fall time ≤ 1.3 s (10 … 90 %) MTTF 62 years acc. to SN 29500 (Ed. 99)
Max. measurement tolerance under EMC ≤ 0.1 % with shielded signal cable 40 °C
influence ≤ 1 % with unshielded signal cable
Mechanical data
Approvals and declarations Housing material plastic
Ex approval acc. to conformity certificate PTB 00 ATEX 2181 Connection mode module, plugged on rack
Device designation É II 2 (1) G Ex ib [ia] IIC T4
21
21
22
22
channel 2 RTH-3L
23
24
24
31
31
32
channel 3 RTH-2L
33
34
34
11
41
12
42
channel 4 13 RTH-4L
43
14
44
The input module TI41Ex is designed for Line compensation of 2‑wire tempera- Parameters such as line monitoring, s ub-
the connection of the 2, 3 and 4‑wire ture resistors is done by means of para- stitute values etc. can be adjusted for
temperature probes Pt100, Ni100 and metrized resistance values. These values each channel separately and are initial-
CU100. have to be determined first through ized solely by the master.
measurements.
The module features protection class Ex
ib IIC and can be mounted in zone 1 in The analog resistance value is digitized
combination with excom®. The explo- to 16‑bit. The temperature is given in
sion protection category of the inputs is Kelvin, the resolution in 0.1 K steps. For
Ex ia IIC. conversion to °C, please observe an off-
set of 273.2.
212 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for intrinsically safe circuits
Technical data
Type TI41Ex EMC acc. to EN 61326-1 (2006)
Ident no. 6884190 acc. to NAMUR NE21 (2007)
MTTF 80 years acc. to SN 29500 (Ed. 99)
40 °C
Power supply
Supply voltage via module rack, central power supply
Mechanical data
module
Power consumption ≤ 1 W Housing material plastic
Galvanic separation complete galvanic isolation acc. to Connection mode module, plugged on rack
EN 60079‑11 Protection class IP20
Number of channels 4‑channel Dimensions 18 x 118 x 103 mm
Response characteristic
Resolution 16 Bit
Linearity deviation ≤ 0.01 % measuring range
Temperature drift ≤ 0.002 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 % with shielded signal cable
influence ≤ 0.5 % with unshielded signal cable
Indication
Operational readiness 1 x green / red
State/ Fault 4 x red
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
PROFIBUS-DP interface
Host Features
PROFIBUS-DP
RS485-IS
The GDP-IS gateway serves to connect A GSD file containing all configuration Redundancy: The use of two gateways
the excom® system to PROFIBUS-DP net- files and parameter sets is available for and two bus cables ensures error-free
works. Connection to the P ROFIBUS-DP system configuration. When connected communication, in case one gateway or
is established via optical fibers or copper to suitable host systems, you can one bus line may fail. If one gateway
cables. When using optical fibers for change the system configuration during fails, the other takes over smoothly, this
data transmission an o ptocoupler pair operation. is called line r edundancy. System redun-
must be installed b etween wired and dancy (two masters, each connected to
optical PROFIBUS which also adapts the The gateway provides the entire range a gateway) is also supported.
level to the IS layer. When using copper of PROFIBUS diagnostic functions in-
cables a s egment coupler (RS485‑IS cou- cluding port-related diagnostics. Addi- Recommended wiring components:
pler) must be installed to ensure explo- tionally, manufacturer-specific error ▪▪ PROFIBUS-DP cable, type 452B
sion p rotection. codes are generated. For example ▪▪ D9T-RS485IS male
HART® communication errors, power ▪▪ Segment coupler SC12Ex
The gateway can be operated at a maxi- supply errors, planning errors as well as ▪▪ Fiber-optic coupler OC11Ex/…
mum transmission rate of 1500 kbps. information on simulators, internal c om-
The bus is connected to a standard min- munication and redundancy status.
iature SUB-D slot on the module rack.
214 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Gateway for installation in zones 1 and 2
Technical data
Type GDP-IS/FW2.2
Ident no. 6884210
Power supply
Supply voltage via module rack, central power supply
module
Power consumption ≤ 1 W
Galvanic separation complete galvanic isolation acc. to
EN 60079‑11
System data
Fieldbus transmission rate 9.6 kbps … 1.5 Mbps
Fieldbus address range 1…99
Indication
Operational readiness 1 x green / red
Int. communication (CAN) 1 x yellow / red
Ext. Communication (PDP) 1 x yellow / red
Redundancy readiness (PRIO) 1 x yellow / red
Error indication 1 x red
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 126 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
PROFIBUS-DP interface
Features
Host
▪▪ Gateway for PROFIBUS-DPV1
Master communication
▪▪ Connection of the excom® station to
the PROFIBUS-DP networks
▪▪ Baud rate max. 1.5 Mbps
excom® ▪▪ PROFIBUS interface acc. to PROFIBUS
user organization (PNO)
PROFIBUS-DP
RS485
The GDP-NI gateway serves to connect A GSD file containing all configuration information on simulators, internal c om-
the excom® system to PROFIBUS-DP net- files and parameter sets is available for munication and redundancy status.
works. Connection to the P ROFIBUS-DP system configuration. When connected
is established via optical fibers or copper to suitable host systems, you can Redundancy: The use of two gateways
cables. When using optical fibers for change the system configuration during and two bus cables ensures error-free
data transmission, an optocoupler pair operation. communication, in case one gateway or
must be installed b etween wired and one bus line may fail. If one gateway
optical PROFIBUS. The gateway provides the entire range fails, the other takes over smoothly, this
of PROFIBUS diagnostic functions in- is called line r edundancy. System redun-
The gateway can be operated at a maxi- cluding port-related diagnostics. Addi- dancy (two masters, each connected to
mum transmission rate of 1500 kbps. tionally, manufacturer-specific error a gateway) is also supported.
The bus is connected to a standard min- codes are generated. For example
iature SUB-D slot on the module rack. HART® communication errors, power Recommended wiring components:
supply errors, planning errors as well as ▪▪ PROFIBUS-DP cable, type 452
▪▪ D9T-RS485 male
216 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Gateway for installation in the safe area
Technical data
Type GDP-NI/FW2.2
Ident no. 6884225
Power supply
Supply voltage via module rack, central power supply
module
Power consumption ≤ 1 W
Galvanic separation complete galvanic isolation
System data
Fieldbus transmission rate 9.6 kbps … 1.5 Mbps
Fieldbus address range 1…99
Indication
Operational readiness 1 x green / red
Int. communication (CAN) 1 x yellow / red
Ext. Communication (PDP) 1 x yellow / red
Redundancy readiness (PRIO) 1 x yellow / red
Error indication 1 x red
Environmental Conditions
Ambient temperature -20…+70 °C
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
PSD24Ex PSD24Ex
+
24 VDC –
PE
+
24 VDC –
PE
The PSD24Ex module supplies the The module is powered with 24 VDC. Redundancy: Two power supply mod-
excom® system with power to the full e x- The external power supply is plugged ules can be installed together with an
tension. The module rack is designed in on the module rack via Ex e clamps. Any appropriate module rack. In case of
a combined protection rating of Ex m, contact with the clamps under power power cut or failure of one device, the
Ex e and Ex i and can therefore be used should be avoided. The clamps are lo- second unit provides the power for the
in zone 1. It is also fully potted and cated under a closure cap. Interventions whole system. Different potentials can
installed in a die-cast aluminium are only allowed after switching off the be supplied.
enclosure. respective supply voltage.
218 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Power supply module for installation in zone 1
Technical data
Type PSD24EX
Ident no. 6881721
Power supply
Nominal voltage 24 VDC
Operating voltage range 19.2…32 VDC
Power consumption ≤ 66.5 W
Output power ≤ 60 W
Galvanic separation Galvanically isolated input and output
circuit, rated voltage 60 V
Indication
Operational readiness 1 x green
Supply voltage 1 x green
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
Mechanical data
Electrical connection via backplane
Terminal cross-section 2.5 mm2 flexible / 4.0 mm2 rigid
Housing material Aluminium
Connection mode Flange, 4 x M4 screws
Protection class IP50
Dimensions 45 x 155 x 106 mm
Converter, 230 VAC
Features
PPSA PPSA
L
VAC N +
PE –
L
VAC N +
PE –
The AC/DC converter PPSA230Ex sup- The module is powered with 230 VAC. Redundancy: Two power supply mod-
plies the excom® system with power to The external power supply is plugged ules can be installed together with an
the full extension. A combined protec- on the module rack via Ex e clamps. Any appropriate module rack. In case of
tion rating of Ex m and Ex e enables ap- contact with the clamps under power power cut or failure of one device, the
plication in zone 1. It is also fully potted should be avoided. The clamps are lo- second unit provides the power for the
and installed in a die-cast aluminium cated under a closure cap. Interventions whole system. Different potentials can
enclosure. are only allowed after switching off the be supplied.
respective supply voltage.
220 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Power supply module for installation in zone 1
Technical data
Type PPSA230EX
Ident no. 6900293
Power supply
Nominal voltage 230 VAC
Operating voltage range 200…250 VAC
Power consumption ≤ 85 VA
Output power ≤ 66.5 W
Galvanic separation Galvanically isolated input and output
circuit, rated voltage 250 V
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 919 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Converter, 115 VAC
Features
PPSA PPSA
L
VAC N +
PE –
L
VAC N +
PE –
The AC/DC converter PPSA115Ex sup- The module is powered with 115 VAC. Redundancy: Two power supply mod-
plies the excom® system with power to The external power supply is plugged ules can be installed together with an
the full extension. A combined protec- on the module rack via Ex e clamps. Any appropriate module rack. In case of
tion rating of Ex m and Ex e enables ap- contact with the clamps under power power cut or failure of one device, the
plication in zone 1. It is also fully potted should be avoided. The clamps are lo- second unit provides the power for the
and installed in a die-cast aluminium cated under a closure cap. Interventions whole system. Different potentials can
enclosure. are only allowed after switching off the be supplied.
respective supply voltage.
222 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Power supply module for installation in zone 1
Technical data
Type PPSA115EX
Ident no. 6900294
Power supply
Nominal voltage 115 VAC
Operating voltage range 100…125 VAC
Power consumption ≤ 85 VA
Output power ≤ 66.5 W
Galvanic separation Galvanically isolated input and output
circuit, rated voltage 250 V
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 829 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
PSM24
+
24 VDC
–
+
24 VDC
–
The PSM24‑3G module supplies the clamps are located under a closure cap. Redundancy: Two power supply mod-
excom® system with power to the full e x- Any contact with the clamps under ules can be installed together with an
tension. The power supply module c an power should be avoided. Interventions appropriate module rack. In case of
be used in zone 2. are only allowed after switching off the power cut or failure of one device, the
The module is powered with 24 VDC. respective supply voltage. second unit provides the power for the
The external power supply is plugged whole system. Different potentials can
on the module rack via Ex e clamps. The be supplied.
224 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Power supply module for installation in zone 2
Technical data
Type PSM24-3G
Ident no. 6881722
Power supply
Nominal voltage 24 VDC
Operating voltage range 19.2…32 VDC
Power consumption ≤ 66.5 W
Output power ≤ 60 W
Galvanic separation Galvanically isolated input and output
circuit, rated voltage 40 V
Indication
Operational readiness 1 x green
Error indication 1 x red
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
Mechanical data
Electrical connection via backplane
Terminal cross-section 2.5 mm2 flexible / 4.0 mm2 rigid
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
The module rack MT-PPS consists of a work on connecting terminals prior to The rack system is made of continuously
backplane and the actual rack system. It removing the AC converters). cast aluminium. This ensures increased
can accommodate two AC converters stability and shielding. The module rack
for the supply of downstream connect- The module rack is designed in a c om- is suited for wall mounting and fits in
ed 24 VDC module racks. bined protection rating of Ex e and E x q the system enclosures.
and can therefore be used in zone 1.
To plug and unplug AC converters pow-
er has to be switched off first. (Do not
226 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Module rack for installation in zone 1
Technical data
Type MT-PPS
Ident no. 9100516
Ports
AC converter 2
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 1211 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Housing material continuously cast aluminium
Connection mode wall mounting
Protection class IP20
Dimensions 110 x 260 x 130 mm
The module rack MT08‑2G consists of a All modules can be plugged and un- This allows you to pull and plug mod-
backplane and the actual rack system. It plugged under power without interrupt- ules in powered state with excom®
can accommodate a gateway, a power ing the data transmission. mounted in zone 1.
supply unit as well as 8 I/O modules. Up
to 64 binary inputs/outputs or 32 analog The module rack is designed in a c om- The rack system is made of continuously
inputs/outputs resp. a mix of both can bined protection rating of Ex e and E x i cast aluminium. This ensures increased
be connected to it. Unlike the MT16, nei- and can therefore be used in zone 1. stability and shielding. The module rack
ther gateways nor power supply u nits is suited for wall and 19“ rack mounting.
can be connected redundantly to the The power supply of modules on the
MT08. backplane is limited to prevent sparking.
228 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Module rack for installation in zone 1
Technical data
Type MT08-2G
Ident no. 9100684
System data
Fieldbus addressing 3 x decimal-coded rotary switches
Fieldbus connection technology 1 x 9‑pin D-SUB
Ports
DC power supply 1
Gateway 1
Block I/O 8
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 1211 years acc. to SN 29500 (Ed. 99)
40 °C
The module rack MT16‑2G consists of a ing the data transmission. The same ap- This allows you to pull and plug mod-
backplane and the actual rack system. It plies to redundant gateways and power ules in powered state with excom®
can accommodate 2 gateways, 2 power supply modules. mounted in zone 1.
supply units as well as 16 I/O modules.
Up to 128 binary inputs/outputs or 64 The module rack is designed in a c om- The rack system is made of continuously
analog inputs/outputs resp. a mix of bined protection rating of Ex e and E x i cast aluminium. This ensures increased
both can be connected to it. and can therefore be used in zone 1. stability and shielding. The module rack
is suited for wall and 19“ rack mounting.
All modules can be plugged and un- The power supply of modules on the
plugged under power without interrupt- backplane is limited to prevent sparking.
230 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Module rack for installation in zone 1
Technical data
Type MT16-2G
Ident no. 9100687
System data
Fieldbus addressing 3 x decimal-coded rotary switches
Fieldbus connection technology 2 x 9‑pin D-SUB
Ports
DC power supply 2
Gateway 2
Block I/O 16
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 1211 years acc. to SN 29500 (Ed. 99)
40 °C
The module rack MT16‑2G/MSA c onsists plies to redundant gateways and power The rack system is made of continuously
of a backplane and the actual rack sys- supply modules. cast aluminium. This ensures increased
tem. It can accommodate 2 gateways, 2 stability and shielding. The module rack
power supply units as well as 16 I/O The module rack is designed in a c om- is suited for wall and 19“ rack mounting.
modules. Up to 128 binary inputs/out- bined protection rating of Ex e and E x i
puts or 64 analog inputs/outputs resp. a and can therefore be used in zone 1. The module rack MT16‑2G/MSA is espe-
mix of both can be connected to it. cially adapted to the requirements for
The power supply of modules on the maritime applications. It is certified acc.
All modules can be plugged and un- backplane is limited to prevent sparking. to the ship classes GL, DNV, BV and LR.
plugged under power without interrupt- This allows you to pull and plug mod-
ing the data transmission. The same ap- ules in powered state with excom®
mounted in zone 1.
232 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Module rack for installation in zone 1
Technical data
Type MT16-2G/MSA
Ident no. 9100688
System data
Fieldbus addressing 3 x decimal-coded rotary switches
Fieldbus connection technology 2 x 9‑pin D-SUB
Ports
DC power supply 2
Gateway 2
Block I/O 16
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF acc. to SN 29500 (Ed. 99) 40 °C
Mechanical data
The module rack MT08‑3G consists of a ing the data transmission. The same ap- This allows you to pull and plug mod-
backplane and the actual rack system. It plies to redundant gateways and power ules in powered state with excom®
can accommodate a gateway, a power supply modules. mounted in zone 2.
supply unit as well as 8 I/O modules. Up
to 64 binary inputs/outputs or 32 analog The module rack is designed in a c om- The rack system is made of continuously
inputs/outputs resp. a mix of both can bined protection rating of Ex e and E x i cast aluminium. This ensures increased
be connected to it. and can therefore be used in zone 2. stability and shielding. The module rack
is suited for wall and rack mounting.
All modules can be plugged and un- The power supply of modules on the
plugged under power without interrupt- backplane is limited to prevent sparking.
234 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Module rack for use in zone 2
Technical data
Type MT08-3G
Ident no. 9100680
System data
Fieldbus addressing 2 x decimal-coded rotary switches
Fieldbus connection technology 2 x 9‑pin D-SUB
Ports
DC power supply 2
Gateway 2
Block I/O 8
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF acc. to SN 29500 (Ed. 99) 40 °C
Mechanical data
The module rack MT16‑3G consists of a ing the data transmission. The same ap- This allows you to pull and plug mod-
backplane and the actual rack system. It plies to redundant gateways and power ules in powered state with excom®
can accommodate 2 gateways, 2 power supply modules. mounted in zone 2.
supply units as well as 16 I/O modules.
Up to 128 binary inputs/outputs or 64 The module rack is designed in a c om- The rack system is made of continuously
analog inputs/outputs resp. a mix of bined protection rating of Ex e and E x i cast aluminium. This ensures increased
both can be connected to it. and can therefore be used in zone 2. stability and shielding. The module rack
is suited for wall and rack mounting.
All modules can be plugged and un- The power supply of modules on the
plugged under power without interrupt- backplane is limited to prevent sparking.
236 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Module rack for installation in zone 2
Technical data
Type MT16-3G
Ident no. 9100681
System data
Fieldbus addressing 2 x decimal-coded rotary switches
Fieldbus connection technology 2 x 9‑pin D-SUB
Ports
DC power supply 2
Gateway 2
Block I/O 16
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 1211 years acc. to SN 29500 (Ed. 99)
40 °C
The module rack MT24‑3G consists of a ing the data transmission. The same ap- This allows you to pull and plug mod-
backplane and the actual rack system. It plies to redundant gateways and power ules in powered state with excom®
can accommodate 2 gateways, 2 power supply modules. mounted in zone 2.
supply units as well as 24 I/O modules.
Up to 192 binary inputs/outputs or 96 The module rack is designed in a c om- The rack system is made of continuously
analog inputs/outputs resp. a mix of bined protection rating of Ex e and E x i cast aluminium. This ensures increased
both can be connected to it. and can therefore be used in zone 2. stability and shielding. The module rack
is suited for wall and rack mounting.
All modules can be plugged and un- The power supply of modules on the
plugged under power without interrupt- backplane is limited to prevent sparking.
238 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Module rack for installation in zone 2
Technical data
Type MT24-3G
Ident no. 9100682
System data
Fieldbus addressing 2 x decimal-coded rotary switches
Fieldbus connection technology 2 x 9‑pin D-SUB
Ports
DC power supply 2
Gateway 2
Block I/O 24
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 1211 years acc. to SN 29500 (Ed. 99)
40 °C
of RS485 and RS485‑IS
▪▪ Connection of max. 62 bus nodes (31
in redundant mode)
▪▪ Redundant power supply
▪▪ Automatic baud rate detection
The PROFIBUS-DP segment coupler The segment coupler SC12Ex is IP20 r at- sequences. Baud rate detection is start-
SC12Ex from TURCK has been d evel- ed, suited for mounting in the non-Ex ed after reset. If telegrams are not re-
oped for intrinsically safe P
ROFIBUS area and can be supplied redundantly. ceived within 1.7 seconds, baud rate
connection. Both power supply inputs are decou- search is activated. Alternatively, the
pled by diods. The load distribution de- baud rate used can be set via rotary
Equipped with one RS485 and two pends on the level of operating voltage. switch.
RS485‑IS interfaces, this coupler is suited Operating voltage 18…32 VDC.
for many Ex-area applications. The In order not to limit the number of
RS485‑IS interface is entirely realized ac- In switch position 0, the coupler identi- nodes and cable length of a PROFIBUS-
cording to the PNO PROFIBUS guideline. fies the baud rate automatically. For this, DP segment, amplitude and phase are
The coupler can thus supply both lines the start-delimiter of the P ROFIBUS tele- reproduced in the coupler. The user can
of the TURCK Ex-Remote-I/O system ex- grams is evaluated. Three consecutive choose between capacitive and direct
com® simultaneously (line redundancy). and valid start-delimiters have to be re- earthing.
Just one device is required for Ex-sepa- ceived before identification locks in.
ration and line redundancy.
All received telegrams are checked for
plausibility by means of start-delimiter
240 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
PROFIBUS network components
Technical data
Type SC12EX
Ident no. 6884047
Power supply
Nominal voltage 24 VDC
Operating voltage range 18…32 VDC
Current consumption < 200 mA
Galvanic separation complete galvanic isolation acc. to
EN 60079‑11
Number of channels 2‑channel
Indication
Operational readiness 2 x green
State/ Fault 3 x yellow / red
Baud rate detection 1 x yellow
Mechanical data
Housing material anodized aluminium
Connection mode snap-fit on DIN rail (DIN 60715)
Front plate FR4, grey / blue
Protection class IP20
Dimensions 142 x 105.5 x 31 mm
OC11Ex/2G
RS485-IS
DP-connector
DP-connector
with integrated Slave excom® Slave
terminating resistor
The optocoupler OC11Ex/2G.2 converts guideline. The optocoupler OC11Ex/ communication interface. Two O C11Ex
the PROFIBUS-DP signals into optical 2G.2 is equipped with devices can be coupled together via the
signals. In this way the bus signals are ▪▪ intrinsically safe RS485‑IS PROFIBUS M8 interface. Wire-break and short-cir-
transmitted potential-free and safely interface (acc. to the RS485‑IS draft cuit are not transmitted from one seg-
over long distances from the non-Ex to worked out by the PNO work group) ment to the next one. All segments can
the Ex area. ▪▪ intrinsically safe optical interface with thus be operated trouble-free and inde-
ST c onnectors for emitter and receiver pendently of one another.
The OC11Ex/3G.2 in zone 2 transmits
the signals via the optical interface to Up to 31 bus nodes can be connected to In order not to limit the number of
the OC11Ex/2G.2 in zone 1 which con- the optocoupler. Baud rates of 9.6 kbps nodes and cable length of a PROFIBUS-
verts them. The signals are then o utput up to 1.5 Mbps are possible, or will be DP segment, amplitude and phase are
intrinsically safe at the RS485‑IS automatically detected. reproduced in the coupler. The OC11Ex/
interface. 2G.2 shield is always capacitively cou-
For diagnostic purposes there are four pled to the equipotential bonding.
The RS485‑IS interface is entirely real- status LEDs that indicate power ON, fib-
ized according to the PNO PROFIBUS er-optic segment, RS485 interface and
baud rate. The device features an M 8
242 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
PROFIBUS network components
Technical data
Type OC11Ex/2G.2
Ident no. 6890427
Power supply
Nominal voltage 24 VDC
Operating voltage range 18…32 VDC
Current consumption < 100 mA
Galvanic separation complete galvanic isolation acc. to
EN 60079‑11
Number of channels 1‑channel
Indication
Operational readiness 1 x green
State/ Fault 2 x yellow / red
Baud rate detection 1 x yellow
Mechanical data
Housing material anodized aluminium
Connection mode snap-fit on DIN rail (DIN 60715) or
wall mounting
Front plate FR4, grey
Protection class IP20
Dimensions 72 x 105.5 x 31 mm
OC11Ex/2G
RS485-IS
DP-connector
DP-connector
with integrated Slave excom® Slave
terminating resistor
The optocoupler OC11Ex/3G.2 converts ▪▪ RS485 interface – standard PROFIBUS- devices can be coupled together via the
the PROFIBUS-DP signals into optical DP interface with RS485 level acc. to M8 interface. Wire-break and short-cir-
signals. In this way the bus signals are EIA 485 (the control cable for direction cuit are not transmitted from one seg-
transmitted potential-free and safely control is not connected) ment to the next one. All segments can
over long distances from the non-Ex to ▪▪ intrinsically safe optical interface with thus be operated trouble-free and inde-
the Ex area. ST c onnectors for emitter and receiver pendently of one another.
The optocoupler can be installed in the Up to 31 bus nodes can be connected to In order not to limit the number of
non-Ex area or in zone 2. The OC11Ex/ the optocoupler. Baud rates of 9.6 kbps nodes and cable length of a PROFIBUS-
3G.2 receives the PROFIBUS-DP signals up to 1.5 Mbps are possible or will be DP segment, amplitude and phase are
at its standard interface RS485 and automatically detected. reproduced in the coupler. The user can
transmits them via the intrinsically safe choose between capacitive and direct
optical interface to the optocoupler For diagnostic purposes there are four earthing.
OC11Ex/2G.2 in zone 1. status LEDs that indicate power ON, fib-
er-optic segment, RS485 interface and
The optocoupler OC11Ex/3G.2 is baud rate. The device features an M 8
equipped with communication interface. Two O C11Ex
244 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
PROFIBUS network components
Technical data
Type OC11Ex/3G.2
Ident no. 6890428
Power supply
Nominal voltage 24 VDC
Operating voltage range 18…32 VDC
Current consumption < 100 mA
Galvanic separation complete galvanic isolation acc. to
EN 60079‑11
Number of channels 1‑channel
Indication
Operational readiness 1 x green
State/ Fault 2 x yellow / red
Baud rate detection 1 x yellow
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Mechanical data
Housing material anodized aluminium
Connection mode snap-fit on DIN rail (DIN 60715) or
wall mounting
Front plate FR4, grey
Protection class IP20
Dimensions 72 x 105.5 x 31 mm
Solutions
Solutions for the no
Solutions for the non-Ex area
The excom® series gives the user com- modules in the non-Ex area, which fur-
plete freedom in the choice of the instal- ther reduces the basic installation costs.
lation location. It can be installed in As TURCK has also developed a special
zones 1 and 2 and in the non-Ex area. power supply unit for this applic ation
This benefits the user not only in terms area, the entire system is considerably
of components optimized for a particular more compact. Even with exclus ively
zone, but also because of the standard non-Ex area applications, the user bene-
concept for configuring and paramet fits from the further developments o f the
rizing the periphery and field excom® series – particularly with t he dig-
instrumentation. ital outputs: For example, an additional
The same peripherals that are used in relay output is also provided that a llows
the Ex area can also be used in the non- the switching of outputs with up t o 0.5 A.
Ex area. A new module rack offers here
the possibility of operating up to 24 I/O
246 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Short description/Table of contents
The I/O module DM80‑N is designed for When connecting the field devices, care The user can furthermore determine
the connection of NAMUR sensors (DIN has to be taken that all inputs and/or whether an input or an output should
EN 60 60947‑5‑6) and actuators. When outputs are on a common potential. be provided at the connecting point.
wire-break or short-circuit monitoring The following configurations are possi-
are activated, mechanical contacts can Input and output mode can be adjusted ble: 8 inputs/0 outputs; 6 inputs/2 out-
only be connected with a corresponding via the PROFIBUS-DP master. The follow- puts up to 0 inputs/8 outputs (GSD-file,
resistor circuitry (WM1, Ident no. ing parameters can be adjusted: s witch- Mode 2). This way, optimal a daptation
0912101). ing behaviour, switch-on delay, default to the corresponding application envi-
value, wire-break and short circuit ronment is guaranteed.
monitoring.
248 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type DM80-N
Ident no. 6884211
Power supply
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 1 W
Galvanic separation to int. bus and supply circuit
Number of channels 8‑channel
Inputs
Input circuits acc. to EN 60947‑5‑6 (NAMUR)
No-load voltage 8 VDC
Short-circuit current 4 mA
Switching frequency ≤ 100 Hz
Short-circuit < 367 Ω
Wire-break < 0.2 mA
Switch-on threshold: 1.8 mA
Switch-off threshold: 1.4 mA
Outputs
Output circuits for low-power actuators
No-load voltage 8 VDC
Nominal current 4 mA
Switching frequency ≤ 100 Hz
Short circuit < 367 Ω
Indication
Operational readiness 1 x green / red
State/ Fault 8 x yellow / red
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to N AMUR NE21 (2007)
MTTF 141 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
Features
▪▪ Frequency module for the connection
of NAMUR sensors
The input module DF20‑N is equipped nals or frequency measurements of b i- blocks the frequency is reduced to
with 8 channels acc. to NAMUR, which nary pulse sequences of NAMUR 2 kHz.
are grouped together in two blocks. sensors.
There is one frequency input per block Input and output mode can be adjusted
and three control inputs/outputs. The counting direction can either be set via the PROFIBUS-DP master. Each chan-
externally via a control input or internal- nel is equipped with parametrizable
The module can be used as a counter or ly by setting a parameter. The m aximum wire-break/short-circuit monitoring.
frequency input module: It is thus suited frequency of one block is 4 kHz; with 2
for pulse counting of binary input sig-
250 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type DF20-N
Ident no. 6884212
Power supply
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 1 W
Galvanic separation to int. bus and supply circuit
Number of channels 2‑channel
Inputs
Input circuits acc. to EN 60947‑5‑6 (NAMUR)
No-load voltage 8 VDC
Short-circuit current 4 mA
Switching frequency ≤ 4000 Hz
Short-circuit < 367 Ω
Wire-break < 0.2 mA
Switch-on threshold: 1.8 mA
Switch-off threshold: 1.4 mA
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Indication
Operational readiness 1 x green / red
State/ Fault 8 x yellow / red
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
BN +
31
BU –
32
channel 3 NAMUR
33
34
BN +
41
BU –
42
channel 4
43
44
The input module DI40‑N is designed for tacts can only be connected with a cor- The behaviour of the inputs can be a d-
the connection of NAMUR sensors (DIN responding resistor circuitry (WM1, justed via the PROFIBUS-DP master. The
EN 60947‑5‑6), 3‑wire sensors (NPN, Ident no. 0912101). following parameters can be adjusted:
PNP) or mechanical contacts. switching behaviour, switch-on delay,
The inputs are galvanically isolated from default value, wire-break and short cir-
When wire-break or short-circuit moni- each other. cuit monitoring.
toring are activated, mechanical con-
252 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type DI40-N
Ident no. 6884213
Power supply
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 2 W
Galvanic separation complete galvanic isolation
Number of channels 4‑channel
Inputs
Input circuits acc. to EN 60947‑5‑6 (NAMUR)
No-load voltage 8.2 VDC
Short-circuit current 2.7 mA
Switching frequency ≤ 100 Hz
Short-circuit < 367 Ω
Wire-break < 0.15 mA
Switch-on threshold: 1.8 mA
Switch-off threshold: 1.3 mA
3-wire input
No-load voltage 12 VDC
Current ≤ 20 mA
0-signal ≤ 4.5 V
1-signal ï 6.5 V
Remark
Indication
Operational readiness 1 x green / red
State/ Fault 4 x yellow / red
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. EN 61326‑1 (2013)
acc. to Namur NE21 (2012)
MTTF 111 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
31
32
channel 3 +
33
–
34
U = 10…18 V
+
41
–
42
channel 4 U = 8…24 V
43
44
The output module DO40‑N is designed One actuator per channel can be con- following values are supported for
for the connection of low-power actua- nected. Via selection of connecting ter- example:
tors such as valves or indicator lights. minals, two circuits per channel are
made available with different supply ▪▪ 22.5 V / 5 mA
The outputs of this module are g alvani- data. ▪▪ 19.0 V / 15 mA
cally isolated from each other. ▪▪ 16.0 V / 25 mA
Please see the load curve, showing the ▪▪ 14.0 V / 35 mA
connection values for valve control. The ▪▪ 12.0 V / 45 mA
Load curve terminal connection 1+2 Load curve terminal connection 3+4
254 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type DO40-N
Ident no. 6884214
Power supply
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 4.5 W
Galvanic separation complete galvanic isolation
Number of channels 4‑channel
Outputs
Output circuits for low-power actuators
No-load voltage 24 VDC
Switching frequency ≤ 50 Hz
Short circuit ï 50 mA
Wire-break < 1 mA
Internal resistance Ri 300 Ω
Indication
Operational readiness 1 x green / red
State/ Fault 4 x yellow / red
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
21
NO ▪▪ Configurable as 4 x changeover
COM contact
▪▪ Configurable as 6 x NO contact
22
channel 2 COM
23
NC
24
NO
31
channel 3 COM
32
NO
33
channel 4 COM
34
NO
41
channel 5 COM
42
NO
43
channel 6 COM
44
The relay module DO60R-N is designed The channels 3/4 and 5/6 are separately es. The connections 12‑13 and 22‑23 are
for
the connection of non-intrinsically switchable to changeover function. For not further protected and should maxi-
safe actuators such as valves or indicator this, an external bridge at the terminals mally be loaded with the switching cur-
lights. is needed. rent of a relay contact. Use preferably
terminal 12 resp. 22 for connection.
The outputs are designed as zero-poten- Note:
tial relay contacts. To protect the module rack, the contact Status and error messages of the single
▪▪ 2 x changeover contacts (channel 1 circuits inside the DO60R-N module are outputs and the module are indicated
and 2) safeguarded by fuses (1 AT). The module via LEDs on the front.
▪▪ 4 x NO contacts (channel 3 to 6) must be replaced after tripping the fus-
256 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type DO60R-N
Ident no. 6884196
Power supply
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 2 W
Galvanic separation complete galvanic isolation
Number of channels 6‑channel
Outputs
Output circuits 6 x relays
(2 x changeover contacts, 4 x NO)
Switching current ï 10 mA
Indication
Operational readiness 1 x green / red
State/ Fault 6 x yellow / red
Environmental Conditions
Ambient temperature -20…+60 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
+
31
I
Aux
32
channel 3 +
33
34
+
41 I
Aux
42
channel 4 +
43
44
The input module AI40‑N is designed for HART® compatible transducers can be the digitized value is displayed in a
the connection of 2‑wire transducers connected to the module. The field d e- range of 0 … 21000 (independent of the
(active input = source mode / transduc- vice can thus be parametrized directly at parametrized measuring range) and
er passive) or 4‑wire transducers (pas- the terminals on the DIN rail with a li- transmitted to the host system.
sive input = sink mode / transducer censed modem. An additional imped-
active). ance in the circuit is not necessary.
The field circuits are galvanically isolat- The measuring range is digitized in the
ed from each other. scope of 0…21 mA. For clear reading,
258 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type AI40-N
Ident no. 6884215
Power supply
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 2.2 W
Galvanic separation complete galvanic isolation
Number of channels 4‑channel
Inputs
Input circuits 0/4…20 mA
Supply voltage 15 VDC at 20 mA
Overload capability > 21 mA
Low level control < 3.6 mA
Short-circuit > 24 mA (only in live zero mode)
Wire-break < 2 mA (only in live zero mode)
Response characteristic
Resolution 14 Bit
Linearity deviation ≤ 0.05 % full scale
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 %
influence
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 77 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
+
31 U
Aux
32
channel 3 +
33
34
+
41
U
Aux
42
channel 4 +
43
44
The input module AI41‑N is designed for The inputs are galvanically isolated from is-
clear reading, the digitized value is d
the connection of 4‑wire transducers each other. played in a range of 0…21000 and
(passive input = sink mode / transducer transmitted to the host system. For
active). The resolution is 14 bit, i.e. the analog transmission to the host system, voltage
value between 0…21 mA is represented is indicated as a value in a range b e-
as a number between 0 and 16383. For tween 0…10000.
260 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type AI41-N
Ident no. 6884216
Power supply
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 1 W
Galvanic separation complete galvanic isolation
Number of channels 4‑channel
Inputs
Input circuits 0/4…20 mA
Overload capability > 22 mA
Low level control < 3.6 mA
Short-circuit < 5 V (only in live zero mode)
Wire-break < 2 mA (only in live zero mode)
Response characteristic
Resolution 14 Bit
Linearity deviation ≤ 0.1 % full scale
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Indication
Operational readiness 1 x green / red
State/ Fault 4 x red
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
31
31
32
32
channel 3 33 R-3L
33
34
34
41
41
42
42
channel 4 43 R-4L
43
44
44
The analog input module AI43‑N is de- from the power supply, from the inter- set to ‚invalid-bit‘. This
state is main-
signed for the connection of p otentiom- nal bus and from each other. tained until valid measured v alues are
eters in 3 or 4‑wire technology. If 3‑wire provided again.
potentiometers are used, the terminals Each potentiometer input is monitored
at the module rack have to be bridged. for wire break. The interruption of a sin- The resolution is 14 bit. For clear read-
Resistance measurements, i.e. the evalu- gle connection line is securely detected, ing, 0…100 % is digitized and d isplayed
ation of potentiometers with a 2‑wire as well as any combination of interrup- in a range of 0…10000 (independent of
connection, is not possible. tions occuring at the four input connec- the parametrized measuring range) and
tion lines. Short-circuit monitoring is not transmitted to the host system.
The module has four field circuits to carried out. In case of a line error, the
control 3 or 4‑wire potentiometers. The programmed substitute v alue is imme-
field circuits are galvanically isolated diately output and the output value is
262 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type AI43-N
Ident no. 6884217
Power supply
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 1.5 W
Galvanic separation complete galvanic isolation
Number of channels 4‑channel
Inputs
Input circuits potentiometer
Nominal resistance 400 Ω … 12 kΩ
Response characteristic
Resolution 14 Bit
Linearity deviation ≤ 0.1 % full scale
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Indication
Operational readiness 1 x green / red
State/ Fault 4 x red
Environmental Conditions
Ambient temperature -20…+70 °C
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
+
31
0/4...20 mA
32
channel 3
33
34
+
41
0/4...20 mA
42
channel 4
43
44
The output module AO40‑N is designed HART® compatible transducers can be The host system transmits a digitized
for the connection of analog actuators connected to the module. The field d e- control value 0…21000 (independent of
such as control valves or process indica- vice can thus be parametrized directly at the parametrized measuring range). This
tors. The outputs are galvanically isolat- the terminals on the DIN rail with a li- raw value is then transformed by the
ed from each other. censed modem. An additional imped- AO40-N into a value between 0…21 mA.
ance in the circuit is not necessary.
264 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type AO40-N
Ident no. 6884218
Power supply
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 2.2 W
Galvanic separation complete galvanic isolation
Number of channels 4‑channel
Outputs
Output circuits 0/4…20 mA
No-load voltage 16 VDC
External load ≤ 640 Ω
Short circuit < 50 Ω (only in live zero mode)
Wire-break < 2 mA (only in live zero mode)
Response characteristic
Resolution 13 Bit
Linearity deviation ≤ 0.05 % full scale
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 %
influence
Indication
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 78 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
Features
▪▪ Input module for connection of 2‑wire
transmitters
▪▪ Transmission of HART® data
The input module AIH40‑N is designed The resolution is 14 bit, i.e. the analog Parameters like wire-break or short-cir-
for the connection of 2‑wire transducers value between 0…21 mA is represented cuit monitoring, measuring range,
(active input = source mode / transduc- as a number between 0 and 16383. For HART® communication etc., can be a d-
er passive). clear reading, the digitized value is d is- justed for each channel separately a nd
played in a range of 0…21000 and are solely initialized by the
PROFIBUS
The inputs are not galvanically isolated transmitted to the host system. master.
from each other. When connecting the
field devices, care has to be taken that Up to 8 HART® variables (max. 4 per
all inputs are on a common potential. channel) can be read via the cyclical
PROFIBUS data traffic. The bidirectional
HART® compatible sensors connected to exchange of variables between the host
the module communicate with the inte- system and the HART® transmitter is im-
grated HART® controller. plemented via PROFIBUS-DPV1.
266 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type AIH40-N
Ident no. 6884219
Power supply
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 3 W
Galvanic separation to int. bus and supply circuit
Number of channels 4‑channel
Inputs
Input circuits 0/4…20 mA
Supply voltage 15 VDC at 22 mA
HART® Impedance > 240 Ω
Overload capability > 22 mA
Low level control < 3.6 mA
Short-circuit < 5 V (only in live zero mode)
Wire-break < 2 mA (only in live zero mode)
Response characteristic
Resolution 14 Bit
Linearity deviation ≤ 0.1 % full scale
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 % with shielded signal cable
influence ≤ 1 % with unshielded signal cable
Environmental Conditions
Ambient temperature -20…+60 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 61 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
Features
▪▪ Input module for connection of 4‑wire
transmitters
▪▪ Transmission of HART® data
The input module AIH41‑N is designed The resolution is 14 bit, i.e. the analog Parameters like wire-break or short-cir-
for the connection of 4‑wire transducers value between 0…21 mA is represented cuit monitoring, measuring range,
(passive input = sink mode / transducer as a number between 0 and 16383. For HART® communication etc., can be a d-
active). clear reading, the digitized value is d is- justed for each channel separately a nd
played in a range of 0…21000 and are solely initialized by the
PROFIBUS
The inputs are not galvanically isolated transmitted to the host system. master.
from each other. When connecting the
field devices, care has to be taken that
Up to 8 HART® variables (max. 4 per
all inputs are on a common potential. channel) can be read via the cyclical
PROFIBUS data traffic. The bidirectional
HART® compatible sensors connected to exchange of variables between the host
the module communicate with the system and the HART® transmitter is im-
HART® controller. plemented via PROFIBUS-DPV1.
268 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type AIH41-N
Ident no. 6884220
Power supply
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 1 W
Galvanic separation to int. bus and supply circuit
Number of channels 4‑channel
Inputs
Input circuits 0/4…20 mA
HART® Impedance > 240 Ω
Overload capability > 22 mA
Low level control < 3.6 mA
Short-circuit < 5 V (only in live zero mode)
Wire-break < 2 mA (only in live zero mode)
Response characteristic
Resolution 14 Bit
Linearity deviation ≤ 0.1 % full scale
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 % with shielded signal cable
influence ≤ 1 % with unshielded signal cable
Environmental Conditions
Ambient temperature -20…+60 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 93 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
+
31
0/4...20 mA
32
channel 3
33
34
+
41
0/4...20 mA
42
channel 4
43
44
The output module AOH40‑N is de- HART® compatible actuators connected raw value is reduced by the AOH40‑N to
signed for the connection of analog ac- to the module communicate directly a 13‑bit resolution.
tuators such a s control valves or process with the HART® controller.
indicators. Parameters such as line monitoring, s ub-
The resolution is 13 bit, i.e. the analog stitute values etc. can be adjusted for
The outputs are not galvanically isolated value of 0…21 mA is represented as a each channel separately and are initial-
from each other. When connecting the number between 0 and 8191. For easier ized solely by the master.
field devices, care has to be taken that operation, the host system operates in a
all outputs are on a common potential. value range between 0…21000. This
270 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type AOH40-N
Ident no. 6884221
Power supply
Supply voltage via the backplanes, central power
supply
Power consumption ≤ 3 W
Galvanic separation to int. bus and supply circuit
Number of channels 4‑channel
Outputs
Output circuits 0/4…20 mA
No-load voltage 16 VDC
HART® Impedance > 240 Ω
External load ≤ 600 Ω
Short circuit < 50 Ω (only in live zero mode)
Wire-break > 15 V (only in live zero mode)
Response characteristic
Resolution 13 Bit
Linearity deviation ≤ 0.1 % full scale
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 % with shielded signal cable
influence ≤ 1 % with unshielded signal cable
Environmental Conditions
Ambient temperature -20…+60 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 66 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
Features
▪▪ Input module for the connection of
temperature probes
▪▪ Complete galvanic isolation
The input module TI40‑N is designed for Line compensation of 2‑wire tempera- for all channels via an integrated Pt100
the connection of 2, 3 and 4‑wire tem- ture resistors is done by means of para- resistor.
perature probes of the types Pt100, metrized resistance values. These values
PT200, Pt500, Pt1000, Ni100 and CU100, have to be determined first through The resolution is 16 bit, i.e. the analog
as well as for the connection of thermo- measurements. value is represented as a number be-
couples of the types B, E, D, J, K, L , N, R, tween 0 and 65535. The temperature is
S, T and U. The module can also be used When using thermocouples, external indicated in Kelvin. For conversion to °C,
for the measurement of low voltages cold junction compensation can be c ar- please observe an offset of 273.2.
(-75…+75 mV, -1.2…+1.2 V) and resist- ried out separately for each channel by
ance measurements (0…30 Ω, 0 …300 Ω, t100 Parameters such as line monitoring, s ub-
connecting resistors such as the P
0…3 kΩ). to the two unused terminals. Internal stitute values etc. can be adjusted for
compensation instead is parametrized each channel separately and are initial-
ized solely by the master.
272 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type TI40-N
Ident no. 6884222
Power supply
Supply voltage via module rack, central power supply
module
Power consumption ≤ 1 W
Galvanic separation complete galvanic isolation
Number of channels 4‑channel
Inputs
Input circuits Pt100, Pt200, Pt500, Pt1000, Ni 100,
Cu100, thermocouple
Response characteristic
Resolution 16 Bit
Linearity deviation ≤ 0.05 % measuring range
Temperature drift ≤ 0.005 % / K
Rise time/fall time ≤ 1.3 s (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 % with shielded signal cable
influence ≤ 1 % with unshielded signal cable
Indication
Operational readiness 1 x green / red
State/ Fault 4 x red
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
21
21
22
22
channel 2 RTH-3L
23
24
24
31
31
32
channel 3 RTH-2L
33
34
34
11
41
12
42
channel 4 13 RTH-4L
43
14
44
The input module TI41‑N is designed for metrized resistance values. These values conversion to °C, please observe an off-
the connection of the 2, 3 and 4‑wire have to be determined first through set of 273.2.
temperature probes Pt100, Ni100 and measurements.
CU100. Parameters such as line monitoring, s ub-
The analog resistance value is digitized stitute values etc. can be adjusted for
Line compensation of 2‑wire tempera- to 16‑bit. The temperature is given in each channel separately and are initial-
ture resistors is done by means of para- Kelvin, the resolution in 0.1 K steps. For ized solely by the master.
274 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Modules for the non-Ex system
Technical data
Type TI41-N
Ident no. 6884223
Power supply
Supply voltage via module rack, central power supply
module
Power consumption ≤ 1 W
Galvanic separation complete galvanic isolation
Number of channels 4‑channel
Inputs
Input circuits Pt100, Ni100, Cu100
Response characteristic
Resolution 16 Bit
Linearity deviation ≤ 0.01 % measuring range
Temperature drift ≤ 0.002 % / K
Rise time/fall time ≤ 50 ms (10 … 90 %)
Max. measurement tolerance under EMC ≤ 0.1 % with shielded signal cable
influence ≤ 0.5 % with unshielded signal cable
Indication
Operational readiness 1 x green / red
State/ Fault 4 x red
Environmental Conditions
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
PROFIBUS-DP interface
Features
Host
▪▪ Gateway for PROFIBUS-DPV1
Master communication
▪▪ Connection of the excom® station to
the PROFIBUS-DP networks
▪▪ Baud rate max. 1.5 Mbps
excom® ▪▪ PROFIBUS interface acc. to PROFIBUS
user organization (PNO)
PROFIBUS-DP
RS485
The GDP-N gateway serves to connect system configuration. When connected Redundancy: The use of two gateways
the excom® system to PROFIBUS-DP net- to suitable host systems, you can and two bus cables ensures error-free
works. Connection to the P ROFIBUS-DP change the system configuration during communication, in case one gateway or
is established via optical fibers or copper operation. one bus line may fail. If one of the com-
cables. When using optical fibers for ponents fails, the other immediately
data transmission, an optocoupler pair The gateway provides the entire range takes over, this is called line r edundancy.
must be installed b etween wired and of PROFIBUS diagnostic functions in- System redundancy (two m asters, each
optical PROFIBUS. cluding port-related diagnostics. Addi- with its own segment c oupler connect-
tionally, manufacturer-specific error ed to a gateway) is also supported.
The gateway can be operated at a maxi- codes are generated. For example
mum transmission rate of 1500 kbps. HART® communication errors, power Recommended wiring components:
The bus is connected to a standard min- supply errors, planning errors as well as ▪▪ PROFIBUS-DP cable, type 452
iature SUB-D slot on the module rack. information on simulators, internal c om- ▪▪ D9T-RS485 male
munication and redundancy status.
A GSD file containing all configuration
files and parameter sets is available for
276 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Gateway for the non-Ex system
Technical data
Type GDP-N /FW2.2
Ident no. 6884224
Power supply
Supply voltage via module rack, central power supply
module
Power consumption ≤ 1 W
Galvanic separation to int. bus and supply circuit
System data
Fieldbus transmission rate 9.6 kbps … 1.5 Mbps
Fieldbus address range 1…99
Indication
Operational readiness 1 x green / red
Int. communication (CAN) 1 x yellow / red
Ext. Communication (PDP) 1 x yellow / red
Redundancy readiness (PRIO) 1 x yellow / red
Error indication 1 x red
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
Mechanical data
Housing material plastic
Connection mode module, plugged on rack
Protection class IP20
Dimensions 18 x 118 x 103 mm
PSM24
+
24 VDC
–
+
24 VDC
–
The PSM24‑N unit supplies the excom® The external power supply is connected Redundancy: Two power supply mod-
system with power to the full extension. via clamps on the module rack. The ules can be installed together with an
The power supply module can only be clamps should not be contacted under appropriate module rack. In case of
used in non-Ex areas. power. They are located below a closure power cut or failure of one device, the
cap. Switch off power before contact. second unit provides the power for the
The PSM24‑N supplies 24 VDC. whole system. Different potentials can
be supplied.
278 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Power supply module for the non-Ex system
Technical data
Type PSM24-N
Ident no. 6881723
Power supply
Nominal voltage 24 VDC
Operating voltage range 19.2…32 VDC
Power consumption ≤ 66.5 W
Output power ≤ 60 W
Galvanic separation Galvanically isolated input and output
circuit, rated voltage 40 V
Indication
Operational readiness 1 x green
Error indication 1 x red
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 61 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
The module rack MT08‑N consists of a All modules can be plugged and un- The module rack can only be used in
backplane and the actual rack system. It plugged under power without interrupt- non-Ex areas for non-Ex signals.
can accommodate a gateway, a power ing the data transmission. The same ap-
supply unit as well as 8 I/O modules. Up plies to redundant gateways and power The rack system is made of continuously
to 64 binary inputs/outputs or 32 analog supply modules. cast aluminium. This ensures increased
inputs/outputs resp. a mix of both can stability and shielding. The module rack
be connected to it. is suited for wall and rack mounting.
280 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Backplane for the non-Ex system
Technical data
Type MT08-N
Ident no. 9100689
System data
Fieldbus addressing 2 x decimal-coded rotary switches
Fieldbus connection technology 2 x 9‑pin D-SUB
Ports
DC power supply 2
Gateway 2
Block I/O 8
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF acc. to SN 29500 (Ed. 99) 40 °C
Mechanical data
Electrical connection 4 x 4 clamps per module
Terminal cross-section 1.5 mm2
Housing material continuously cast aluminium
Connection mode wall mounting
The module rack MT16‑N consists of a All modules can be plugged and un- The module rack can only be used in
backplane and the actual rack system. It plugged under power without interrupt- non-Ex areas for non-Ex signals.
can accommodate 2 gateways, 2 power ing the data transmission. The same ap-
supply units as well as 16 I/O modules. plies to redundant gateways and power The rack system is made of continuously
Up to 128 binary inputs/outputs or 64 supply modules. cast aluminium. This ensures increased
analog inputs/outputs resp. a mix of stability and shielding. The module rack
both can be connected to it. is suited for wall and rack mounting.
282 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Backplane for the non-Ex system
Technical data
Type MT16-N
Ident no. 9100686
System data
Fieldbus addressing 2 x decimal-coded rotary switches
Fieldbus connection technology 2 x 9‑pin D-SUB
Ports
DC power supply 2
Gateway 2
Block I/O 16
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF acc. to SN 29500 (Ed. 99) 40 °C
Mechanical data
Electrical connection 4 x 4 clamps per module
Terminal cross-section 1.5 mm2
Housing material continuously cast aluminium
Connection mode wall mounting
The module rack MT24‑3G consists of a All modules can be plugged and un- The module rack can only be used in
backplane and the actual rack system. It plugged under power without interrupt- non-Ex areas for non-Ex signals.
can accommodate 2 gateways, 2 power ing the data transmission. The same ap-
supply units as well as 24 I/O modules. plies to redundant gateways and power The rack system is made of continuously
Up to 192 binary inputs/outputs or 96 supply modules. cast aluminium. This ensures increased
analog inputs/outputs resp. a mix of stability and shielding. The module rack
both can be connected to it. is suited for wall and rack mounting.
284 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
Module rack for the non-Ex system
Technical data
Type MT24-N
Ident no. 9100683
System data
Fieldbus addressing 2 x decimal-coded rotary switches
Fieldbus connection technology 2 x 9‑pin D-SUB
Ports
DC power supply 2
Gateway 2
Block I/O 24
Environmental Conditions
Ambient temperature -20…+70 °C
Relative humidity ≤ 95 % at 55 °C acc. to EN 60068‑2
Vibration test acc. to IEC 60068‑2‑6
Shock test acc. to IEC 60068‑2‑27
EMC acc. to EN 61326-1 (2006)
acc. to NAMUR NE21 (2007)
MTTF 1211 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Electrical connection 4 x 4 clamps per module
Terminal cross-section 1.5 mm2
Housing material continuously cast aluminium
EC-VA 65 55 26 / 1 1 1 – 02 0 0 / …
Depth
… housing width in cm
286 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
System enclosure
enclosure
The system enclosures of the EG-VA Features
series contain a module rack, either with
16 or 24 slots. The enclosures are made ▪▪ Stainless steel housing with
of stainless steel, feature ignition integrated module rack
protection type Ex-e and allow ▪▪ Housing door with inspection
installation in zone 1 even in harsh and window
aggressive environments. In order to ▪▪ Integrated module rack MT16-2G,
save the user the trouble of getting terminal clamps (see accessories)
approvals for each system component, ▪▪ Flange plate equipped with cable
TURCK has obtained a single system glands
approval for the stainless steel ▪▪ Dimensions (w x h x d):
enclosures with integrated module rack. ▪▪ Type 400 x 550 x 210 [mm]
All components used have been ▪▪ Type 460 x 550 x 260 [mm]
individually tested and approved. In this ▪▪ Type 650 x 550 x 210 [mm]
way customized solutions are also ▪▪ Type 650 x 550 x 260 [mm]
possible. Assembly and installation are ▪▪ Type 800 x 550 x 210 [mm]
carried out directly at TURCK in order to ▪▪ Type 800 x 550 x 260 [mm]
excom® –
excom® – Accessorie
excom® – Accessories
OC11-LINKCABLE Extension cable to connect two identical OC11Ex
8031339 devices (2G i.e. 3G), length 0.24 m
288 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
excom® – Accessories
– Accessories
es
STB16-4RC/1,5-BK 16‑pcs. set: 4‑pin terminal block,
9909625 cage clamps black
excom® –
excom® – Accessorie
excom® – Accessories
MODEX-SCHALTKLEMME Switching terminal for manual switching in Ex areas
6884069 (enable function for downstream connected
devices)
290 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
excom® – Remote-I/O system
excom® – Accessories
– Accessories
es
292 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology
The TURCK Interface technology pro versal power supply unit and remova
gram offers a complete range of func ble terminal blocks
tions, designs and variants for isolating, ▪▪ IMS series – Slim 6.2 mm modular
conditioning, processing, converting and housing for DIN rail mounting as
matching digital and analog signals in analog signal isolators and temper
control and automation. The various de ature measuring amplifiers
signs meet the highest industrial stand ▪▪ IME series – For DIN rail mounting, for
ards and ensure flexibility in the plan high efficiency with reduced cabling
ning, construction and expansion of and power consumption
industrial plants: ▪▪ IMC series – In a compact IP67 housing
▪▪ IM series – Universally applicable de with rich functionality for distributed
vices for DIN rail mounting with uni use directly in the field
Interface technology
IM/IME/IMS/IMSP - M
IM/IME/IMS/IMSP – Modular housings
IM, IME, IMS and IMSP series – interface technology in modular housings
The interface modules of the IM, IME, IMS ries are also only 6.2 mm wide and are
and IMSP series are integrated in a com‑ connected in front of the corresponding
pact modular housing that can be s nap interface modules. T he 18 or 27 mm wide
fitted easily onto a DIN EN 60715 mount‑ devices of the IM series are particularly
ing rail. The devices can be m
ounted hori‑ versatile thanks to a wide range of func‑
zontally or vertically next to each other. tions and parameter setting options.
The 1 and 2‑channel IMS m odules (Inter‑ Equipped with a universal voltage power
face Module Small) are only 6.2 mm wide supply unit with 20…250 VUC and
and offer galvanic isolation, signal condi‑ 20…250 VAC/20…125 VDC for Ex devic‑
tioning and temperature measuring with es, the modules o f the IM series can be
maximum packing d ensity. The compact connected to virtually any industrial sup‑
surge protection devices of the IMSP se‑ ply network.
294 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
Short description and table of contents
Modular housings
Type Ident No. Description Page
IM31-12-I 7506324 Input analog signal isolator, 1-channel – Signal duplicating 350
IM31-12EX-I 7506321 Input analog signal isolator, 1-channel – Signal duplicating 352
IM31-22-I 7506325 Input analog signal isolator, 2-channel 354
IM31-22EX-I 7506322 Input analog signal isolator, 2-channel 356
IM31-22EX-U 7506326 Input analog signal isolator, 2-channel 358
IM33-11-HI/24VDC 7506447 HART® isolating transducer, 1-channel 360
IM33-11EX-HI/24VDC 7506440 HART® isolating transducer, 1-channel 362
IM33-FSD-EX/L 7506433 Isolating transducer, 1-channel 364
IM33-12EX-HI/24VDC 7506446 HART® isolating transducer, 1-channel 366
IM33-11EX-HI 7506443 HART® isolating transducer, 1-channel 368
IM33-14EX-CDRI 7560015 HART® isolating transducer, 1-channel 370
IM33-12EX-HI 7506444 HART® isolating transducer, 1-channel 372
IM33-22-HI/24VDC 7506564 HART® isolating transducer, 2-channel 374
IM33-22EX-HI/24VDC 7506441 HART® isolating transducer, 2-channel 376
IM33-22EX-HI 7506445 HART® isolating transducer, 2-channel 378
IM34-11-CI 7506638 Temperature measuring amplifier, 1-channel 380
IM34-11EX-CI 7506633 Temperature measuring amplifier, 1-channel 382
IM34-11EX-I 7506630 Temperature measuring amplifier, 1-channel 384
IM34-11Ex-CI/24VDC 7506637 Temperature measuring amplifier, 1-channel 386
IM34-12EX-CRI 7506632 Temperature measuring amplifier, 1-channel 388
IM34-12EX-RI 7506631 Temperature measuring amplifier, 1-channel 390
IM34-12Ex-CRi/K63 7506605 Temperature measuring amplifier, 1-channel 392
IM34-11EX-CI/K51 7506635 Temperature measuring amplifier, 1-channel 394
Interface technology
IM34-11EX-CI/K60 7506636 Temperature measuring amplifier, 1-channel 396
IM34-14EX-CDRI 7506634 Temperature measuring amplifier, 1-channel 398
IM35-11EX-HI/24VDC 7506516 Ouput analog signal isolator, 1-channel 400
IM35-22EX-HI/24VDC 7506515 Ouput analog signal isolator, 2-channel 402
IM35-11EX-HI 7506517 Ouput analog signal isolator, 1-channel 404
IM35-22EX-HI 7506518 Ouput analog signal isolator, 2-channel 406
IM36-11EX-I/24VDC 7509525 Potentiometer amplifier, 1-channel 408
IM36-11EX-U/24VDC 7509526 Potentiometer amplifier, 1-channel 410
IM36-22EX-I 7509528 Potentiometer amplifier, 2-channel 412
IM36-22EX-U 7509530 Potentiometer amplifier, 2-channel 414
IM43-14-SRI 7540043 Trip amplifier, 1-channel 416
IM43-14-RI 7540042 Trip amplifier, 1-channel 418
IM43-13-SR 7540041 Trip amplifier, 1-channel 420
IM43-13-R 7540040 Trip amplifier, 1-channel 422
IM43-14-CDRI 7540045 Trip amplifier, 1-channel 424
IM72-11EX/L 7520703 Solonoid driver, 1-channel 426
IM72-22EX/L 7520702 Solonoid driver, 2-channel 428
IM/IME/IMS/IMSP - M
IM/IME/IMS/IMSP – Modular housings
296 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
Devices with SIL evaluation
Modular housings
Devices with SIL evaluation
Interface technology
IME-AO-11Ex-Hi/L 7541194 Ouput analog signal isolator, 1-channel 2 456
IME-DO-11EX/L 7541196 Solonoid driver, 1-channel 3 458
IME-DO-22EX/L 7541195 Solonoid driver, 2-channel 3 460
IMSP-1x2-24 7504050 Surge protection – 1 floating signal circuit 2 468
IMSP-2-12 7504054 Surge protection – 2 floating signal wires 2 470
IMSP-2-24 7504052 Surge protection – 2 floating signal wires 2 472
IMSP-2x2-24 7504051 Surge protection – 2 floating signal circuits 2 474
IMSP-4-24 7504053 Surge protection – 4 floating signal wires 2 476
IMSP-4-12 7504055 Surge protection – 4 floating signal wires 2 478
Our Stren
Our Strengths – You
Our Strengths – Your Advantages
As the IM modules are designed for a v olt‑ cient power reserves and also meet e x‑
age range between 20…250 VUC and plosion protection requirements. A nother
20…250 VAC/20…125 VDC for Ex devic‑ benefit of the modern interface devices is
es, they can be connected to any indus‑ their flexibility and simple use: The mod‑
trial supply network. This therefore con‑ ules just have two terminals for t he power
siderably simplifies device selection, supply. The terminals can be connected
stock-keeping and spare parts manage to both an AC and DC power s upply. A bi‑
ment. TURCK‘s universal power supply polar DC power supply connection is also
units offer reliable protection against un‑ possible.
dervoltage and overvoltage, offer suffi‑
The interface modules of the IM series clamp terminals and provide a highly ac‑
feature removable terminals to simplify cessible terminal chamber for cable cross
the design, conversion and maintenance sections up to 2 .5 mm2 (14 AWG). The
of installations. This makes handling e asi‑ male connectors are coded with red pins
er for installations, prevents wiring e rrors in order to prevent the incorrect connec
when replacing devices and reduces tion of a terminal block.
mounting and associated costs. T he de‑
vices are available with screw and cage
The isolation, conditioning, processing, and a signal adaption function that can
conversion and matching of digital and be set easily by DIP switches, the 1 and
analog signals – these are offered by the 2‑channel IMS modules set n ew stand‑
IM and IMS series in a compact, space sav‑ ards in terms of channel d ensity and flex‑
ing design, also in two and 4‑channel ver‑ ibility. The devices can be mounted di‑
sions. The universal IM series offers the rectly next to each other. This saves space
complete solution range in a snap- on in the control cabinet without any loss in
modular housing, with a depth of only the usual level of user-friendliness and
110 mm, and a width of 18 mm or 27 mm. reliability.
With a mounting width of only 6.2 mm
298 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
Our Strengths – Your Advantages
ngths – Your A
ur Advantages
Screw and snap fastening – Flexible mounting
The IM and IMS series interface modules ble. The devices can be mounted horizon‑
are designed for snap-on mounting on tally or vertically next to each other.
DIN rails acc. to DIN EN 60715. Screw fas‑
tening on a mounting plate is also possi‑
In daily routine tasks, the simple handling aged in the required design. From the
of interface devices is critical. For t his an compact variant with DIP and rotary cod‑
interface device should have p recisely ing s witch to teachable devices with intu
the range of functions that the u ser re‑ itive menu guidance in the display, to
quires for his application. In order t o meet modules with convenient parameter s et‑
all requirements in terms of handling, ting and diagnostics, to FDT/DTM tech‑
commissioning and diagnostics, the in‑ nology – a tailored solution for every
terface program offers a selection of dif‑ requirement.
ferent operating concepts, suitably pack‑
Interface technology
The interface modules of the IM series SIL certification. Regardless of whether
provide you with the flexibility and versa‑ for standard or special applications, for
tility you need in order to create t ailored simple or complex require ments, with
solutions for your application: compact manual setting or PC p rogramming, with
designs, flexible operating c oncepts and status indication or differentiated diag‑
configurations, as well as a w
ide range of nostic functions: The IM series is suitable
functions for isolating, conditioning, for universal use and covers the entire
processing, converting and m atching range of high performance tasks in inter‑
digital and analog signals in 1 to 4‑chan‑ face technology.
nel versions. The program also includes
solution for the Ex area and d evices with
Power supply
82 Power supply
300 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
Type code
de
Ex Device class - MT Output type / 24VDC Power supply
Ex associated device with R relay switching output 24 VDC supplied with 24 VDC
intrinsically safe field circuits T transistor switching output
I analog current output not wide-range power
0/4…20 mA specified supply
U analog voltage output 0/2…10 V L loop powered, supplied
by the control circuit
MT MOSFET switching output
C FDT/DTM parameterizable
via computer
D display
H HART®
Interface technology
302 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-12EX-MT External inductance/capacitance Lo/Co
Ident no. 7541228 Ex ic IIC IIB
Lo [mH] 1 5 10 1 5 10
Power supply Co [µF] 1.9 1.4 1.2 11 7.5 6.6
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC
Indication
Operating voltage range 20…250 VAC
Operational readiness green
Frequency 40…70 Hz
Switching state yellow
Power consumption ≤ 3 W
Error indication red
Inputs
Environmental Conditions
No-load voltage 8.2 VDC
Ambient temperature -25…+70 °C
Short-circuit current 8.2 mA
Storage temperature -40…+80 °C
Input resistance 1 kΩ
Relative humidity ≤ 95 %
Cable resistance ≤ 50 Ω
Test voltage 2.5 kV
Switch-on threshold 1.55 mA
Switch-off threshold 1.75 mA
Mechanical data
Short-circuit threshold ï 6 mA
Tightening torque 0.5 Nm
Wire breakage threshold ≤ 0.1 mA
Electrical connection 4 x 3‑pin removable terminal blocks,
reverse polarity protected, screw
Outputs connection
Output circuits (digital) 2 x MOSFET (potential-free, short- Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
circuit proof) Housing material Polycarbonate/ABS
Switching voltage ≤ 250 VAC/120 VDC Mounting instruction for DIN rail / panel
Switching current per output ≤ 90 mA Protection class IP20
Switching frequency ≤ 1000 Hz Flammability class acc. to UL 94 V-0
Dimensions 18 x 104 x 110 mm
Approvals and declarations
Ex approval acc. to conformity certificate TÜV 04 ATEX 2553 Approval | Certification ATEX, IECEx, UL, cFMus, CSA, TR CU,
Device designation É II (1) G, II (1) D [Ex ia Ga] IIC; [Ex NEPSI, KOSHA, TIIS, CCOE
ia Da] IIIC
Max. values: Terminal connection: 1+4
Max. output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Rated voltage 250 V
Characteristic linear
Interface technology
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 1 5 10 2 10 20
Co [µF] 1.1 0.83 0.74 5.2 3.8 3.4
Ex approval acc. to conformity certificate TÜV 06 ATEX 552968 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1+4
Max.output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
NEPSI, KOSHA, TIIS, CCOE
▪▪ Installation in zone 2
▪▪ 2 relay outputs (NO)
▪▪ Output mode adjustable (NO/NC
mode)
▪▪ Input circuits monitored for wire-
break and short-circuit
▪▪ Complete galvanic isolation
The 1‑channel isolating switching ampli‑ You can set each channel separately to The Pwr LED lights green to indicate op‑
fier IM1‑12EX-R is equipped with a n in‑ work/closed current, i.e. NO/NC mode erational readiness. The 2‑color LED
trinsically safe input circuit. and duplicate signals via 3 switches on 1 lights yellow to indicate the switching
the front. The switching state of channel status of the associated output. In the
Sensors according to EN 60947‑5‑6 (NA‑ 1 is thereby transmitted to the outputs 1 event of an input circuit error, the a ssoci‑
MUR) or potential-free contact transmit‑ and 2. You can also set the output mode ated 2‑color LED turns red, provided the
ters can be connected to the device. separately for each channel. input circuit monitoring function is acti‑
vated. Thereupon the output relays drop
The output circuit features two relays, You can also set the output mode sepa‑ out.
each with NO contact. rately for each channel.
304 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-12EX-R External inductance/capacitance Lo/Co
Ident no. 7541226 Ex ic IIC IIB
Lo [mH] 1 5 10 1 5 10
Power supply Co [µF] 1.9 1.4 1.2 11 7.5 6.6
Nominal voltage Universal voltage supply unit
Declaration SIL 2 acc. to EXIDA FMEDA
Operating voltage range 20…125 VDC
Operating voltage range 20…250 VAC
Indication
Frequency 40…70 Hz
Operational readiness green
Power consumption ≤ 3 W
Switching state yellow
Error indication red
Inputs
No-load voltage 8.2 VDC
Environmental Conditions
Short-circuit current 8.2 mA
Ambient temperature -25…+70 °C
Input resistance 1 kΩ
Storage temperature -40…+80 °C
Cable resistance ≤ 50 Ω
Relative humidity ≤ 95 %
Switch-on threshold 1.55 mA
Test voltage 2.5 kV
Switch-off threshold 1.75 mA
MTTF 272 years acc. to SN 29500 (Ed. 99)
Short-circuit threshold ï 6 mA 40 °C
Wire breakage threshold ≤ 0.1 mA
Mechanical data
Outputs Tightening torque 0.5 Nm
Output circuits (digital) 2 x relays (NO) Electrical connection 4 x 3‑pin removable terminal blocks,
Switching frequency ≤ 10 Hz reverse polarity protected, screw
Relay switching voltage ≤ 250 VAC/120 VDC connection
Switching current per output ≤ 2 A Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Switching capacity per output ≤ 500 VA/60 W Housing material Polycarbonate/ABS
Contact quality AgNi, 3µ Au Mounting instruction for DIN rail / panel
Protection class IP20
Approvals and declarations Flammability class acc. to UL 94 V-0
Ex approval acc. to conformity certificate TÜV 04 ATEX 2553 Dimensions 18 x 104 x 110 mm
Device designation É II (1) G, II (1) D [Ex ia Ga] IIC; [Ex
ia Da] IIIC Approval | Certification ATEX, IECEx, UL, cFMus, CSA, TR CU,
Max. values: Terminal connection: 1+4 NEPSI, KOSHA, TIIS, CCOE
Max. output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Rated voltage 250 V
Interface technology
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 1 5 10 2 10 20
Co [µF] 1.1 0.83 0.74 5.2 3.8 3.4
Ex approval acc. to conformity certificate TÜV 06 ATEX 552968 X
Application area II 3 G
Protection type Ex nA nC [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1+4
Max.output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
▪▪ 2 transistor outputs, short-circuit
proof, potential-free and reverse-po‑
larity protected
▪▪ Output mode adjustable (NO/NC
mode)
▪▪ Input circuits monitored for wire-
break/short-circuit (ON/OFF
switchable)
▪▪ Complete galvanic isolation
The 1‑channel isolating switching ampli‑ You can set each channel separately to The Pwr LED lights green to indicate op‑
fier IM1‑12EX-T is equipped with a n in‑ work/closed current, i.e. NO/NC mode erational readiness. The 2‑color LED
trinsically safe input circuit. and duplicate signals via 3 switches on 1 lights yellow to indicate the switching
the front. The switching state of channel status of the associated output. In the
Sensors according to EN 60947‑5‑6 (NA‑ 1 is thereby transmitted to the outputs 1 event of an input circuit error, the a ssoci‑
MUR) or potential-free contact transmit‑ and 2. You can also set the output mode ated 2‑color LED turns red, provided the
ters can be connected to the device. separately for each channel. input circuit monitoring function is acti‑
vated. Thereupon the o utput transistors
The output circuits feature 2 potential- You can also set the output mode sepa‑ are blocked.
free and short-circuit protectedrately for each channel.
transistors.
306 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-12EX-T External inductance/capacitance Lo/Co
Ident no. 7541227 Ex ic IIC IIB
Lo [mH] 1 5 10 1 5 10
Power supply Co [µF] 1.9 1.4 1.2 11 7.5 6.6
Nominal voltage Universal voltage supply unit
Declaration SIL 2 acc. to EXIDA FMEDA
Operating voltage range 20…125 VDC
Operating voltage range 20…250 VAC
Indication
Frequency 40…70 Hz
Operational readiness green
Power consumption ≤ 3 W
Switching state yellow
Error indication red
Inputs
No-load voltage 8.2 VDC
Environmental Conditions
Short-circuit current 8.2 mA
Ambient temperature -25…+70 °C
Input resistance 1 kΩ
Storage temperature -40…+80 °C
Cable resistance ≤ 50 Ω
Relative humidity ≤ 95 %
Switch-on threshold 1.55 mA
Test voltage 2.5 kV
Switch-off threshold 1.75 mA
MTTF 314 years acc. to SN 29500 (Ed. 99)
Short-circuit threshold ï 6 mA 40 °C
Wire breakage threshold ≤ 0.1 mA
Mechanical data
Outputs Tightening torque 0.5 Nm
Output circuits (digital) 2 x transistor (potential-free, short- Electrical connection 4 x 3‑pin removable terminal blocks,
circuit proof) reverse polarity protected, screw
Switching voltage ≤ 30 VDC connection
Switching current per output ≤ 50 mA Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Switching frequency ≤ 5000 Hz Housing material Polycarbonate/ABS
Voltage drop ≤ 2.5 V Mounting instruction for DIN rail / panel
Protection class IP20
Approvals and declarations Flammability class acc. to UL 94 V-0
Ex approval acc. to conformity certificate TÜV 04 ATEX 2553 Dimensions 18 x 104 x 110 mm
Device designation É II (1) G, II (1) D [Ex ia Ga] IIC; [Ex
ia Da] IIIC Approval | Certification ATEX, IECEx, UL, cFMus, CSA, TR CU,
Max. values: Terminal connection: 1+4 NEPSI, KOSHA, TIIS, CCOE
Max. output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Rated voltage 250 V
Interface technology
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 1 5 10 2 10 20
Co [µF] 1.1 0.83 0.74 5.2 3.8 3.4
Ex approval acc. to conformity certificate TÜV 06 ATEX 552968 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1+4
Max.output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
▪▪ TR CU
II I
+
7
▪▪ 2 transistor outputs, short-circuit
– 1 proof, potential-free and reverse-po‑
4 BU – 4 10
BN
larity protected
1
1
NAMUR
+1 +8,2 V
1
YE/RD
≤ 30 VDC
≤ 50 mA K ▪▪ Output mode adjustable (NO/NC
+
8 mode)
–
9
2
▪▪ Input circuits monitored for wire-
break and short-circuit
11
▪▪ Complete galvanic isolation
Pwr Power
GN 12
The isolating switching amplifier You can set each channel separately to The Pwr LED lights green to indicate op‑
IM1‑12‑T is a 1‑channel device. work/closed current, i.e. NO/NC mode erational readiness. The 2‑color LED
and duplicate signals via 3 switches on 1 lights yellow to indicate the switching
Sensors according to EN 60947‑5‑6 (NA‑ the front. The switching state of channel status of the associated output. In the
MUR) or potential-free contact transmit‑ 1 is thereby transmitted to the outputs 1 event of an input circuit error, the a ssoci‑
ters can be connected to the device. and 2. You can also set the output mode ated 2‑color LED turns red, provided the
separately for each channel. input circuit monitoring function is acti‑
The output circuits feature 2 potential- vated. Thereupon the o utput transistors
free and short-circuit protectedYou can also set the output mode sepa‑ are blocked.
transistors. rately for each channel.
10 11 12
7 8 9
Power
Pwr
Switching status
1
Output mode
NO NC
Wire-break 1 off WB
monitoring off SC
Short-circuit
monitoring
IM1-12-T
4 5 6
1 2 3
308 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-12-T
Ident no. 7541268
Power supply
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Power consumption ≤ 3 W
Inputs
No-load voltage 8.2 VDC
Short-circuit current 8.2 mA
Input resistance 1 kΩ
Cable resistance ≤ 50 Ω
Switch-on threshold 1.55 mA
Switch-off threshold 1.75 mA
Short-circuit threshold ï 6 mA
Wire breakage threshold ≤ 0.1 mA
Outputs
Output circuits (digital) 2 x transistor (potential-free, short-
circuit proof)
Switching voltage ≤ 30 VDC
Switching current per output ≤ 50 mA
Switching frequency ≤ 5000 Hz
Voltage drop ≤ 2.5 V
Indication
Operational readiness green
Switching state yellow
Error indication red
Environmental Conditions
Interface technology
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Relative humidity ≤ 95 %
Test voltage 2.5 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 18 x 104 x 110 mm
Approval | Certification TR CU
II I
▪▪ ATEX, IECEx, UL, CFMUS, CSA, TR CU,
7 NEPSI, KOSHA, TIIS, CCOE
1 1 ▪▪ Installation in zone 2
▪▪ 2 relay outputs (NO)
BU 4
– YE/RD
10 ≤ 250 VAC/
1
NAMUR BN 1 +8,2 V
30 VDC
≤2A ▪▪ Output mode adjustable (NO/NC
+ 8 ≤ 500 VA/60 W mode)
▪▪ Common alarm output
9
▪▪ Input circuits monitored for wire-
11
break/short-circuit (ON/OFF
Pwr Power switchable)
GN 12
▪▪ Complete galvanic isolation
The 1‑channel isolating switching ampli‑ You can set each channel separately to The Pwr LED lights green to indicate op‑
fier IM1‑12EX-R is equipped with a n in‑ work/closed current, i.e. NO/NC mode erational readiness. The 2‑color LED
trinsically safe input circuit. and duplicate signals via 3 switches on 1 lights yellow to indicate the switching
the front. The switching state of channel status of the associated output. In the
Sensors according to EN 60947‑5‑6 (NA‑ 1 is thereby transmitted to the outputs 1 event of an input circuit error, the a ssoci‑
MUR) or potential-free contact transmit‑ and 2. You can also set the output mode ated 2‑color LED turns red, provided the
ters can be connected to the device. separately for each channel. input circuit monitoring function is acti‑
vated. Thereupon the output and the
The output circuits feature two relays You can also set the output mode sepa‑ alarm relay drop out.
each with NO contact, one of which rately for each channel.
works as alarm output.
310 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-121EX-R Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
Ident no. 7541229 External inductance/capacitance Lo/Co
Ex ic IIC IIB
Power supply Lo [mH] 1 5 10 1 5 10
Nominal voltage Universal voltage supply unit Co [µF] 1.9 1.4 1.2 11 7.5 6.6
Operating voltage range 20…125 VDC
Declaration SIL 2 acc. to EXIDA FMEDA
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Indication
Power consumption ≤ 3 W
Operational readiness green
Switching state yellow
Inputs
Error indication red
No-load voltage 8.2 VDC
Short-circuit current 8.2 mA
Environmental Conditions
Input resistance 1 kΩ
Ambient temperature -25…+70 °C
Cable resistance ≤ 50 Ω
Storage temperature -40…+80 °C
Switch-on threshold 1.55 mA
Relative humidity ≤ 95 %
Switch-off threshold 1.75 mA
Test voltage 2.5 kV
Short-circuit threshold ï 6 mA
MTTF 272 years acc. to SN 29500 (Ed. 99)
Wire breakage threshold ≤ 0.1 mA 40 °C
Interface technology
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 1 5 10 2 10 20
Co [µF] 1.1 0.83 0.74 5.2 3.8 3.4
Ex approval acc. to conformity certificate TÜV 06 ATEX 552968 X
Application area II 3 G
Protection type Ex nA nC [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1+4
Max.output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Characteristic linear
▪▪ ATEX, IECEx, UL, CFMUS, CSA, TR CU,
NEPSI, KOSHA, TIIS, CCOE
▪▪ Installation in zone 2
▪▪ 2 transistor outputs, potential-free
The 1‑channel isolating switching ampli‑ You can set each channel separately to 1 lights yellow to indicate the switching
fier IM1‑121EX-T is equipped with an in‑ work/closed current, i.e. NO/NC mode status of the associated output. In the
trinsically safe input circuit. and duplicate signals via 3 switches on event of an input circuit error, the a ssoci‑
the front. The switching state of channel ated 2‑color LED turns red, provided the
Sensors according to EN 60947‑5‑6 (NA‑ 1 is thereby transmitted to the outputs 1 input circuit monitoring function is acti‑
MUR) or potential-free contact transmit‑ and 2. You can also set the output mode vated. Thereupon the output and the
ters can be connected to the device. separately for each channel. alarm transistor are blocked.
312 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-121EX-T Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
Ident no. 7541230 External inductance/capacitance Lo/Co
Ex ic IIC IIB
Power supply Lo [mH] 1 5 10 1 5 10
Nominal voltage Universal voltage supply unit Co [µF] 1.9 1.4 1.2 11 7.5 6.6
Operating voltage range 20…125 VDC
Declaration SIL 2 acc. to EXIDA FMEDA
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Indication
Power consumption ≤ 3 W
Operational readiness green
Switching state yellow
Inputs
Error indication red
No-load voltage 8.2 VDC
Short-circuit current 8.2 mA
Environmental Conditions
Input resistance 1 kΩ
Ambient temperature -25…+70 °C
Cable resistance ≤ 50 Ω
Storage temperature -40…+80 °C
Switch-on threshold 1.55 mA
Relative humidity ≤ 95 %
Switch-off threshold 1.75 mA
Test voltage 2.5 kV
Short-circuit threshold ï 6 mA
MTTF 314 years acc. to SN 29500 (Ed. 99)
Wire breakage threshold ≤ 0.1 mA 40 °C
Interface technology
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 1 5 10 2 10 20
Co [µF] 1.1 0.83 0.74 5.2 3.8 3.4
Ex approval acc. to conformity certificate TÜV 06 ATEX 552968 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1+4
Max.output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Characteristic linear
▪▪ 2 transistor outputs (MOSFET)
▪▪ Output mode adjustable (NO/NC
mode)
▪▪ Input circuits monitored for wire-
break/short-circuit (ON/OFF
switchable)
▪▪ Complete galvanic isolation
The 2‑channel isolating switching ampli‑ Six front panel switches are available to and 2 light yellow to indicate the switch‑
fier IM1‑22EX-MT is equipped with intrin‑ set the output mode separately for each ing status of the associated output. In the
sically safe input circuits. channel (NO/NC mode), as well as to en‑ event of an input circuit error, the 2‑color
able/disable wire-break (WB) and s hort- LED associated to the affected input
Sensors according to EN 60947‑5‑6 (NA‑ circuit (SC) monitoring separately. turns red, provided the input circuit
MUR) or potential-free contact transmit‑ monitoring function is activated. There‑
ters can be connected to the device. You can also set the output mode sepa‑ upon the associated o utput transistor is
rately for each channel. blocked.
The output circuits feature two p
otential-
free MOSFET transistors. The Pwr LED lights green to indicate op‑
erational readiness. The 2‑color LEDs 1
Power
Switching status
Channel 1
Output mode
Wire-break
monitoring
Short-circuit
monitoring
Channel 2
314 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-22EX-MT Indication
Ident no. 7541213 Operational readiness green
Switching state yellow
Power supply Error indication red
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC Environmental Conditions
Operating voltage range 20…250 VAC Ambient temperature -25…+70 °C
Frequency 40…70 Hz Storage temperature -40…+80 °C
Power consumption ≤ 3 W Relative humidity ≤ 95 %
Test voltage 2.5 kV
Inputs
No-load voltage 8.2 VDC Mechanical data
Short-circuit current 8.2 mA Tightening torque 0.5 Nm
Input resistance 1 kΩ Electrical connection 4 x 3‑pin removable terminal blocks,
Cable resistance ≤ 50 Ω reverse polarity protected, screw
connection
Switch-on threshold 1.55 mA
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Switch-off threshold 1.75 mA
Housing material Polycarbonate/ABS
Short-circuit threshold ï 6 mA
Mounting instruction for DIN rail / panel
Wire breakage threshold ≤ 0.1 mA
Protection class IP20
Flammability class acc. to UL 94 V-0
Outputs
Dimensions 18 x 104 x 110 mm
Output circuits (digital) 2 x MOSFET (potential-free, short-
circuit proof)
Switching voltage ≤ 250 VAC/120 VDC Approval | Certification ATEX, IECEx, UL, cFMus, CSA, TR CU,
NEPSI, KOSHA, TIIS, CCOE
Switching current per output ≤ 100 mA
Switching frequency ≤ 1000 Hz
Interface technology
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 1 5 10 2 10 20
Co [µF] 1.1 0.83 0.74 5.2 3.8 3.4
Ex approval acc. to conformity certificate TÜV 06 ATEX 552968 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1+4 / 2+5
Max.output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Ex ic IIC IIB
Lo [mH] 1 5 10 1 5 10
Co [µF] 1.9 1.4 1.2 11 7.5 6.6
The 2‑channel isolating switching ampli‑ Six front panel switches are available to and 2 light yellow to indicate the switch‑
fier IM1‑22EX-R is equipped with intrinsi‑ set the output mode separately for each ing status of the associated output. In the
cally safe input circuits. channel (NO/NC mode), as well as to en‑ event of an input circuit error, the 2‑color
able/disable wire-break (WB) and s hort- LED associated to the affected input
Sensors according to EN 60947‑5‑6 (NA‑ circuit (SC) monitoring separately. turns red, provided the input circuit
MUR) or potential-free contact transmit‑ monitoring function is activated. There‑
ters can be connected to the device. You can also set the output mode sepa‑ upon the output relay drops out.
rately for each channel.
The output circuits have 2 relays, each
with 1 NO contact. The Pwr LED lights green to indicate op‑
erational readiness. The 2‑color LEDs 1
316 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-22EX-R Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
Ident no. 7541231 External inductance/capacitance Lo/Co
Ex ic IIC IIB
Power supply Lo [mH] 1 5 10 1 5 10
Nominal voltage Universal voltage supply unit Co [µF] 1.9 1.4 1.2 11 7.5 6.6
Operating voltage range 20…125 VDC
Declaration SIL 2 acc. to EXIDA FMEDA
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Indication
Power consumption ≤ 3 W
Operational readiness green
Switching state yellow
Inputs
Error indication red
No-load voltage 8.2 VDC
Short-circuit current 8.2 mA
Environmental Conditions
Input resistance 1 kΩ
Ambient temperature -25…+70 °C
Cable resistance ≤ 50 Ω
Storage temperature -40…+80 °C
Switch-on threshold 1.55 mA
Relative humidity ≤ 95 %
Switch-off threshold 1.75 mA
Test voltage 2.5 kV
Short-circuit threshold ï 6 mA
MTTF 272 years acc. to SN 29500 (Ed. 99)
Wire breakage threshold ≤ 0.1 mA 40 °C
Interface technology
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 1 5 10 2 10 20
Co [µF] 1.1 0.83 0.74 5.2 3.8 3.4
Ex approval acc. to conformity certificate TÜV 06 ATEX 552968 X
Application area II 3 G
Protection type Ex nA nC [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1+4 / 2+5
Max.output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Characteristic linear
break/short-circuit (ON/OFF
switchable)
▪▪ Complete galvanic isolation
The 2‑channel isolating switching ampli‑ Six front panel switches are available to ing status of the associated output. In the
fier IM1‑22EX-T is equipped with intrinsi‑ set the output mode separately for each event of an input circuit error, the 2‑color
cally safe input circuits. channel (NO/NC mode), as well as to en‑ LED associated to the affected input
able/disable wire-break (WB) and s hort- turns red, provided the input circuit
Sensors according to EN 60947‑5‑6 (NA‑ circuit (SC) monitoring separately. monitoring function is activated. There‑
MUR) or potential-free contact transmit‑ upon the associated o utput transistor is
ters can be connected to the device. You can also set the output mode sepa‑ blocked.
rately for each channel.
The output circuits feature 2 potential-
free and short-circuit protectedThe Pwr LED lights green to indicate op‑
transistors. erational readiness. The 2‑color LEDs 1
and 2 light yellow to indicate the switch‑
Power
Switching status
Channel 1
Output mode
Wire-break
monitoring
Short-circuit
monitoring
Channel 2
318 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-22EX-T Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
Ident no. 7541232 External inductance/capacitance Lo/Co
Ex ic IIC IIB
Power supply Lo [mH] 1 5 10 1 5 10
Nominal voltage Universal voltage supply unit Co [µF] 1.9 1.4 1.2 11 7.5 6.6
Operating voltage range 20…125 VDC
Declaration SIL 2 acc. to EXIDA FMEDA
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Indication
Power consumption ≤ 3 W
Operational readiness green
Switching state yellow
Inputs
Error indication red
No-load voltage 8.2 VDC
Short-circuit current 8.2 mA
Environmental Conditions
Input resistance 1 kΩ
Ambient temperature -25…+70 °C
Cable resistance ≤ 50 Ω
Storage temperature -40…+80 °C
Switch-on threshold 1.55 mA
Relative humidity ≤ 95 %
Switch-off threshold 1.75 mA
Test voltage 2.5 kV
Short-circuit threshold ï 6 mA
MTTF 314 years acc. to SN 29500 (Ed. 99)
Wire breakage threshold ≤ 0.1 mA 40 °C
Interface technology
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 1 5 10 2 10 20
Co [µF] 1.1 0.83 0.74 5.2 3.8 3.4
Ex approval acc. to conformity certificate TÜV 06 ATEX 552968 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1+4 / 2+5
Max.output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Characteristic linear
The 2‑channel isolating switching ampli‑ You can set each channel separately to ing status of the associated output. In the
fier IM1‑22EX-R/K51 is equipped with in‑ work/closed current, i.e. NO/NC mode event of an input circuit error, the 2‑color
trinsically safe input circuits. and duplicate signals via 3 switches on LED associated to the affected input
the front. The switching state of channel turns red, provided the input circuit
Sensors according to EN 60947‑5‑6 (NA‑ 1 is thereby transmitted to the outputs 1 monitoring function is activated. There‑
MUR) or potential-free contact transmit‑ and 2. You can also set the output mode upon the output relay drops out.
ters can be connected to the device. separately for each channel.
The output circuits have 2 relays, each The Pwr LED lights green to indicate op‑
with 1 NO contact. erational readiness. The 2‑color LEDs 1
and 2 light yellow to indicate the switch‑
320 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-22EX-R/K51 Indication
Ident no. 7541238 Operational readiness green
Switching state yellow
Power supply Error indication red
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC Environmental Conditions
Operating voltage range 20…250 VAC Ambient temperature -25…+70 °C
Frequency 40…70 Hz Storage temperature -40…+80 °C
Power consumption ≤ 3 W Relative humidity ≤ 95 %
Test voltage 4.0 kV
Inputs
No-load voltage 8.2 VDC Mechanical data
Short-circuit current 8.2 mA Tightening torque 0.5 Nm
Input resistance 1 kΩ Electrical connection 4 x 3‑pin removable terminal blocks,
Cable resistance ≤ 50 Ω reverse polarity protected, screw
connection
Switch-on threshold 1.55 mA
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Switch-off threshold 1.75 mA
Housing material Polycarbonate/ABS
Short-circuit threshold ï 6 mA
Mounting instruction for DIN rail / panel
Wire breakage threshold ≤ 0.1 mA
Protection class IP20
Flammability class acc. to UL 94 V-0
Outputs
Dimensions 18 x 104 x 110 mm
Output circuits (digital) 2 x relays (NO)
Switching frequency ≤ 10 Hz
Approval | Certification ATEX, IECEx, UL, cFMus, CSA, TR CU,
Relay switching voltage ≤ 250 VAC/120 VDC
NEPSI, KOSHA, CCOE
Switching current per output ≤ 2 A
Switching capacity per output ≤ 500 VA/60 W
Contact quality AgNi, 3µ Au
Interface technology
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 1 5 10 2 10 20
Co [µF] 1.1 0.83 0.74 5.2 3.8 3.4
Ex approval acc. to conformity certificate TÜV 06 ATEX 552968 X
Application area II 3 G
Protection type Ex nA nC [ic Gc] IIC/IIB T4 Gc
Max. values Terminal connection: 1+4 / 2+5
Max.output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Ex ic IIC IIB
Lo [mH] 1 5 10 1 5 10
Co [µF] 1.9 1.4 1.2 11 7.5 6.6
▪▪ TR CU
III II I 7 ▪▪ 2 relay outputs (NO)
4 4 BU – 4
1
YE/RD
1
250 VAC/
▪▪ Output mode adjustable (NO/NC
BN
10 125 VDC/ mode)
▪▪ Input circuits monitored for wire-
1 30 VDC
1 1 +1 +8,2 V 2/0,3/6 A
NAMUR
8 500 VA/100 W
2
break/short-circuit (ON/OFF
2
5 5 BU – 5 YE/RD switchable)
2
2 2
BN
+2
9
▪▪ Complete galvanic isolation
NAMUR 11
Pwr Power
GN 12
The isolating switching amplifier Six front panel switches are available to event of an input circuit error, the 2‑color
IM1‑22‑R is a 2-channel device. set the output mode separately for each LED associated to the affected input
channel (NO/NC mode), as well as to en‑ turns red, provided the input circuit
Sensors according to EN 60947‑5‑6 (NA‑ able/disable wire-break (WB) and s hort- monitoring function is activated. There‑
MUR) or potential-free contact transmit‑ circuit (SC) monitoring separately. upon the output relay drops out.
ters can be connected to the device.
The Pwr LED lights green to indicate op‑
The output circuits have 2 relays, each erational readiness. The 2‑color LEDs 1
with 1 NO contact. and 2 light yellow to indicate the switch‑
ing status of the associated output. In the
322 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-22-R Approval | Certification TR CU
Ident no. 7541234
Power supply
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Power consumption ≤ 3 W
Inputs
No-load voltage 8.2 VDC
Short-circuit current 8.2 mA
Input resistance 1 kΩ
Cable resistance ≤ 50 Ω
Switch-on threshold 1.55 mA
Switch-off threshold 1.75 mA
Short-circuit threshold ï 6 mA
Wire breakage threshold ≤ 0.1 mA
Outputs
Output circuits (digital) 2 x relays (NO)
Switching frequency ≤ 10 Hz
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 2 A
Switching capacity per output ≤ 500 VA/60 W
Contact quality AgNi, 3µ Au
Indication
Operational readiness green
Switching state yellow
Error indication red
Environmental Conditions
Interface technology
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Relative humidity ≤ 95 %
Test voltage 2.5 kV
MTTF 272 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 18 x 104 x 110 mm
▪▪ ATEX, IECEx, UL, CFMUS, CSA, TR CU,
NEPSI, KOSHA, TIIS, CCOE
▪▪ Installation in zone 2
▪▪ 2 relay outputs (NO)
▪▪ Output mode adjustable (NO/NC
mode)
▪▪ Duplicating of signals possible
▪▪ Complete galvanic isolation
The 2‑channel isolating switching ampli‑ You can set each channel separately to The Pwr LED lights green to indicate op‑
fier IM12‑22EX-R is equipped with intrin‑ work/closed current, i.e. NO/NC mode erational readiness. LED 1 lights yellow
sically safe input circuits. and duplicate signals via 3 switches on to indicate the switching status o f the
the front. The switching state of channel output.
Sensors according to EN 60947‑5‑6 (NA‑ 1 is thereby transmitted to the outputs 1
MUR) or potential-free contact transmit‑ and 2. You can also set the output mode
ters can be connected to the device. separately for each channel.
The output circuits have 2 relays, each You can also set the output mode sepa‑
with 1 NO contact. rately for each channel.
1 NO
2 NO
NC
NC
1:1 1:2
Zone 2: Do not dis-
connect when live!
IM12-22Ex-R
324 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM12-22EX-R Indication
Ident no. 7541233 Operational readiness green
Switching state yellow
Power supply Error indication red
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC Environmental Conditions
Operating voltage range 20…250 VAC Ambient temperature -25…+70 °C
Frequency 40…70 Hz Storage temperature -40…+80 °C
Power consumption ≤ 3 W Relative humidity ≤ 95 %
Test voltage 2.5 kV
Inputs
No-load voltage 8.2 VDC Mechanical data
Short-circuit current 8.2 mA Tightening torque 0.5 Nm
Input resistance 1 kΩ Electrical connection 4 x 3‑pin removable terminal blocks,
Cable resistance ≤ 50 Ω reverse polarity protected, screw
connection
Switch-on threshold 1.55 mA
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Switch-off threshold 1.75 mA
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Outputs
Protection class IP20
Output circuits (digital) 2 x relays (NO)
Flammability class acc. to UL 94 V-0
Switching frequency ≤ 10 Hz
Dimensions 18 x 104 x 110 mm
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 2 A
Approval | Certification ATEX, IECEx, UL, cFMus, CSA, TR CU,
Switching capacity per output ≤ 500 VA/60 W
NEPSI, KOSHA, TIIS, CCOE
Contact quality AgNi, 3µ Au
Interface technology
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 1 5 10 2 10 20
Co [µF] 1.1 0.83 0.74 5.2 3.8 3.4
Ex approval acc. to conformity certificate TÜV 06 ATEX 552968 X
Application area II 3 G
Protection type Ex nA nC [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1+4 / 2+5
Max.output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 11 mA
Max. output power Po ≤ 26 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Ex ic IIC IIB
Lo [mH] 1 5 10 1 5 10
Co [µF] 1.9 1.4 1.2 11 7.5 6.6
▪▪ ATEX, TR CU
▪▪ Output mode adjustable (NO/NC
mode)
▪▪ Duplicating of signals possible
▪▪ Complete galvanic isolation
The 2‑channel isolating switching ampli‑ You can set each channel separately to The Pwr LED lights green to indicate op‑
fier IM12‑22EX-R/230VAC is e quipped work/closed current, i.e. NO/NC mode erational readiness. LED 1 lights yellow
with intrinsically safe input circuits. and duplicate signals via 3 switches on to indicate the switching status o f the
the front. The switching state of channel output.
Sensors according to EN 60947‑5‑6 (NA‑ 1 is thereby transmitted to the outputs 1
MUR) or potential-free contact transmit‑ and 2. You can also set the output mode
ters can be connected to the device. separately for each channel.
The output circuits have 2 relays, each You can also set the output mode sepa‑
with 1 NO contact. rately for each channel.
326 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM12-22EX-R/230VAC Mechanical data
Ident no. 7505641 Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks,
Power supply reverse polarity protected, screw
connection
Nominal voltage 230 VAC
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Operating voltage range 196…253 VAC
Housing material Polycarbonate/ABS
Frequency 48…62 Hz
Mounting instruction for DIN rail / panel
Power consumption ≤ 7 VA
Protection class IP20
Flammability class acc. to UL 94 V-0
Inputs
Dimensions 18 x 104 x 110 mm
No-load voltage 8.2 VDC
Short-circuit current 8.2 mA
Approval | Certification ATEX, TR CU
Input resistance 1 kΩ
Cable resistance ≤ 50 Ω
Switch-on threshold 1.55 mA
Switch-off threshold 1.75 mA
Outputs
Output circuits (digital) 2 x relays (NO)
Switching frequency ≤ 10 Hz
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 2 A
Switching capacity per output ≤ 500 VA/60 W
Contact quality AgNi, 3µ Au
Interface technology
Ex ia IIC IIIC
Lo [mH] 1 5 1 5
Co [µF] 1.1 0.84 6.2 4.4
(2 terminals)
Co [µF] 1.1 0.8 6.2 4.3
(3 terminals
or more)
Indication
Operational readiness green
Switching state yellow
Error indication red
Environmental Conditions
Ambient temperature -25…+60 °C
Storage temperature -40…+80 °C
Relative humidity ≤ 95 %
Test voltage 2.5 kV
The 2‑channel isolating switching ampli‑ You can set each channel separately to The Pwr LED lights green to indicate op‑
fier IM12‑22EX-R/24VDC is e quipped work/closed current, i.e. NO/NC mode erational readiness. LED 1 lights yellow
with intrinsically safe input circuits. and duplicate signals via 3 switches on to indicate the switching status o f the
the front. The switching state of channel output.
Sensors according to EN 60947‑5‑6 (NA‑ 1 is thereby transmitted to the outputs 1
MUR) or potential-free contact transmit‑ and 2. You can also set the output mode
ters can be connected to the device. separately for each channel.
The output circuits have 2 relays, each You can also set the output mode sepa‑
with 1 NO contact. rately for each channel.
328 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM12-22EX-R/24VDC Mechanical data
Ident no. 7505640 Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks,
Power supply reverse polarity protected, screw
connection
Nominal voltage 24 VDC
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Operating voltage range 10…30 VDC
Housing material Polycarbonate/ABS
Power consumption ≤ 1.5 W
Mounting instruction for DIN rail / panel
Protection class IP20
Inputs
Flammability class acc. to UL 94 V-0
No-load voltage 8.2 VDC
Dimensions 18 x 104 x 110 mm
Short-circuit current 8.2 mA
Input resistance 1 kΩ
Approval | Certification ATEX, cFMus, TR CU
Cable resistance ≤ 50 Ω
Switch-on threshold: 1.55 mA
Switch-off threshold: 1.75 mA
Outputs
Output circuits (digital) 2 x relays (NO)
Switching frequency ≤ 10 Hz
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 2 A
Switching capacity per output ≤ 500 VA/60 W
Contact quality AgNi, 3µ Au
Interface technology
Lo [mH] 1 5 1 5
Co [µF] 1.1 0.84 6.2 4.4
(2 terminals)
Co [µF] 1.1 0.8 6.2 4.3
(3 terminals
or more)
Indication
Operational readiness green
Switching state yellow
Error indication red
Environmental Conditions
Ambient temperature -25…+60 °C
Storage temperature -40…+80 °C
Relative humidity ≤ 95 %
Test voltage 2.5 kV
▪▪ ATEX, IECEx, TR CU, INMETRO
▪▪ Installation in zone 2
▪▪ 2 relay outputs (changeover)
▪▪ Output mode adjustable (NO/NC
mode)
▪▪ Input circuits monitored for wire-
break/short-circuit (ON/OFF
switchable)
▪▪ Common alarm output
▪▪ Complete galvanic isolation
The 2‑channel isolating switching ampli‑ Four front panel switches are available t o LED turns red, provided the input circuit
fier IM1‑231EX-R is equipped with intrin‑ set the output mode separately for each monitoring function is activated. There‑
sically safe input circuits. channel (NO or NC mode), as well a s to upon the output and the alarm relay
enable/disable line monitoring (LM). drop out.
Sensors according to EN 60947‑5‑6 (NA‑
MUR) or potential-free contact transmit‑ You can also set the output mode sepa‑
ters can be connected to the device. rately for each channel.
NO NC
1
connect when live!
Zone 2: Do not dis-
off LM
2
NO NC
off LM
IM1-231Ex-R
330 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-231EX-R External inductance/capacitance Lo/Co
Ident no. 7541239 Ex ic IIC IIC
Lo [mH] 10 5.0 1 20 10.0 2
Power supply Co [µF] 0.91 1.0 1.5 4.3 4.9 6.8
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC
Indication
Operating voltage range 20…250 VAC
Operational readiness green
Frequency 40…70 Hz
Switching state yellow
Power consumption ≤ 3 W
Error indication red
Inputs
Environmental Conditions
No-load voltage 8.2 VDC
Ambient temperature -25…+70 °C
Short-circuit current 8.2 mA
Storage temperature -40…+80 °C
Input resistance 1 kΩ
Relative humidity ≤ 95 %
Cable resistance ≤ 50 Ω
Test voltage 2.5 kV
Switch-on threshold: 1.55 mA
Switch-off threshold: 1.75 mA
Mechanical data
Short-circuit threshold ï 6 mA
Tightening torque 0.5 Nm
Wire breakage threshold ≤ 0.1 mA
Electrical connection 4 x 5‑pin removable terminal blocks,
reverse polarity protected, screw
Outputs connection
Output circuits (digital) 2 x relay (change-over) Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Switching frequency ≤ 10 Hz Housing material Polycarbonate/ABS
Relay switching voltage ≤ 250 VAC/120 VDC Mounting instruction for DIN rail / panel
Switching current per output ≤ 2 A Protection class IP20
Switching capacity per output ≤ 500 VA/60 W Flammability class acc. to UL 94 V-0
Contact quality AgNi, 3µ Au Dimensions 27 x 104 x 110 mm
Interface technology
Internal inductance/capacitance Li/Ci Li = 100 µH, Ci = 1.1 nF
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo[mH] 1.0 5.0 10 2.0 10.0 20.0
Co[µF] 0.84 0.62 0.55 4.0 2.8 2.5
Ex approval acc. to conformity certificate TÜV 06 ATEX 552967 X
Application area II 3 G
Protection type Ex nA nC [ic Gc] IIC T4
Max. values: Terminal connection: 1+2 / 4…7 /
9+10
Max.output voltage Uo ≤ 11.3 V
Max. output current Io ≤ 13 mA
Max. output power Po ≤ 36 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 100 µH; Ci = 1.1 nF
Sensors according to EN 60947‑5‑6 (NA‑ break (WB) and short-circuit (SC) can beThe Pwr LED lights green to indicate op‑
MUR) or potential-free contact makers switched on/off via the eight switches on
erational readiness. The 2‑color LED
can be connected to the 4 ‑channel iso‑ the front. 1 lights yellow to indicate the switching
lating transducer IM1‑451‑R. status of the associated output. In the
When using mechanical contacts, wire- event of an input circuit error, the a ssoci‑
The output circuits each feature a relay break and short-circuit monitoring must ated 2‑color LED turns red, provided the
with NO contact. In addition, the device be switched off or the contacts must be input circuit monitoring function is acti‑
features a common alarm output. wired with resistors (II) (see circuit vated. Thereupon the output and the
diagram). alarm relay drop out.
The output mode (NO/NC) can be set
separately for each channel and wire-
332 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-451-R
Ident no. 7541190
Power supply
Nominal voltage Universal voltage supply unit
Operating voltage range 20…250 VDC
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Power consumption ≤ 3 W
Inputs
No-load voltage 8.2 VDC
Short-circuit current 8.2 mA
Input resistance 1 kΩ
Cable resistance ≤ 50 Ω
Switch-on threshold: 1.55 mA
Switch-off threshold: 1.75 mA
Short-circuit threshold ï 6 mA
Wire breakage threshold ≤ 0.1 mA
Outputs
Output circuits (digital) 5 x relays (NO)
Switching frequency ≤ 10 Hz
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 2 A
Switching capacity per output ≤ 750 VA/60 W
Contact quality AgNi, 3µ Au
Indication
Operational readiness green
Switching state yellow
Error indication red
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Relative humidity ≤ 95 %
Interface technology
Test voltage 2.5 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 5‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 27 x 104 x 110 mm
Approval | Certification TR CU
▪▪ 5 transistor outputs, short-circuit
proof, potential-free and reverse-po‑
larity protected
▪▪ Output mode adjustable (NO/NC
mode)
▪▪ Input circuits monitored for wire-
break/short-circuit (ON/OFF
switchable)
▪▪ Common alarm output
▪▪ Complete galvanic isolation
Sensors according to EN 60947‑5‑6 (NA‑ break (WB) and short-circuit (SC) can be 1 lights yellow to indicate the switching
MUR) or potential-free contact makers switched on/off via the eight switches on status of the associated output. In the
can be connected to the 4 ‑channel iso‑ the front. event of an input circuit error, the a ssoci‑
lating transducer IM1‑451‑T. ated 2‑color LED turns red, provided the
When using mechanical contacts, wire- input circuit monitoring function is acti‑
The output circuits each feature a p oten‑ break and short-circuit monitoring must vated. Thereupon the output and the
tial-free and short-circuit proof t ransistor be switched off or the contacts must be alarm transistor are blocked.
and the device also has a common alarm wired with resistors (II) (see circuit
output. diagram).
The output mode (NO/NC) can be set The Pwr LED lights green to indicate op‑
separately for each channel and wire- erational readiness. The 2‑color LED
334 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-451-T
Ident no. 7520721
Power supply
Nominal voltage Universal voltage supply unit
Operating voltage range 20…250 VDC
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Power consumption ≤ 3 W
Inputs
No-load voltage 8.2 VDC
Short-circuit current 8.2 mA
Input resistance 1 kΩ
Cable resistance ≤ 50 Ω
Switch-on threshold: 1.55 mA
Switch-off threshold: 1.75 mA
Short-circuit threshold ï 6 mA
Wire breakage threshold ≤ 0.1 mA
Outputs
Output circuits (digital) 5 x transistor (potential-free, short-
circuit proof)
Switching voltage ≤ 30 VDC
Switching current per output ≤ 50 mA
Switching frequency ≤ 5000 Hz
Voltage drop ≤ 2.5 V
Indication
Operational readiness green
Switching state yellow
Error indication red
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Relative humidity ≤ 95 %
Interface technology
Test voltage 2.5 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 5‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 27 x 104 x 110 mm
Approval | Certification TR CU
The 4‑channel isolating switching ampli‑ Six front panel switches are available to status of the associated output. In the
fier IM1‑451EX-R is equipped with intrin‑ set the output mode separately for each event of an input circuit error, the a ssoci‑
sically safe input circuits. channel (NO/NC mode), as well as to en‑ ated 2‑color LED turns red, provided the
able/disable wire-break (WB) and s hort- input circuit monitoring function is acti‑
Sensors according to EN 60947‑5‑6 (NA‑ circuit (SC) monitoring separately. vated. Thereupon the output and the
MUR) or potential-free contact transmit‑ alarm relay drop out.
ters can be connected to the device. You can also set the output mode sepa‑
rately for each channel.
The output circuits each feature a relay
with NO contact. In addition, the device The Pwr LED lights green to indicate op‑
features a common alarm output. erational readiness. The 2‑color LED
1 lights yellow to indicate the switching
336 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-451EX-R Max. output power Po ≤ 36 mW
Ident no. 7541188 Characteristic linear
Internal inductance/capacitance Li/Ci Li = 100 µH; Ci = 1.1 nF
Power supply External inductance/capacitance Lo/Co
Nominal voltage Universal voltage supply unit Ex ic IIC IIC
Operating voltage range 20…125 VDC Lo [mH] 10 5.0 1 20 10.0 2
Operating voltage range 20…250 VAC Co [µF] 0.91 1.0 1.5 4.3 4.9 6.8
Frequency 40…70 Hz
Power consumption ≤ 3 W
Indication
Operational readiness green
Inputs
Switching state yellow
No-load voltage 8.2 VDC
Error indication red
Short-circuit current 8.2 mA
Input resistance 1 kΩ
Environmental Conditions
Cable resistance ≤ 50 Ω
Ambient temperature -25…+70 °C
Switch-on threshold: 1.55 mA
Storage temperature -40…+80 °C
Switch-off threshold: 1.75 mA
Relative humidity ≤ 95 %
Short-circuit threshold ï 6 mA
Test voltage 2.5 kV
Wire breakage threshold ≤ 0.1 mA
Mechanical data
Outputs
Tightening torque 0.5 Nm
Output circuits (digital) 5 x relays (NO)
Electrical connection 4 x 5‑pin removable terminal blocks,
Switching frequency ≤ 10 Hz reverse polarity protected, screw
Relay switching voltage ≤ 250 VAC/120 VDC connection
Switching current per output ≤ 2 A Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Switching capacity per output ≤ 750 VA/60 W Housing material Polycarbonate/ABS
Contact quality AgNi, 3µ Au Mounting instruction for DIN rail / panel
Protection class IP20
Approvals and declarations Flammability class acc. to UL 94 V-0
Ex approval acc. to conformity certificate TÜV 04 ATEX 2604 Dimensions 27 x 104 x 110 mm
Device designation É II (1) G, II (1) D [Ex ia Ga] IIC ; [Ex
ia Da] IIIC Approval | Certification ATEX, IECEx, UL, cFMus, CSA, TR CU,
Max. values: Terminal connection: 1+2 / 4…7 / INMETRO, TIIS
9+10
Max. output voltage Uo ≤ 11.3 V
Max. output current Io ≤ 13 mA
Max. output power Po ≤ 36 mW
Interface technology
Rated voltage 250 V
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 100 µH, Ci = 1.1 nF
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo[mH] 1.0 5.0 10 2.0 10.0 20.0
Co[µF] 0.84 0.62 0.55 4.0 2.8 2.5
Application area II 3 G
Protection type Ex nA nC [ic Gc] IIC T4
Max. values: Terminal connection: 1+2 / 4…7 /
9+10
Max.output voltage Uo ≤ 11.3 V
Max. output current Io ≤ 13 mA
9 9
–
9
+
14 ▪▪ Input circuits monitored for wire-
R1
BN
+
–
15 break/short-circuit (ON/OFF
4 R2 switchable)
▪▪ Common alarm output
10 10 NAMUR BU 10
– 19
Pwr
GN 20
Power
▪▪ Complete galvanic isolation
The 4‑channel isolating switching ampli‑ Six front panel switches are available to event of an input circuit error, the a ssoci‑
fier IM1‑451EX-T is equipped with intrin‑ set the output mode separately for each ated 2‑color LED turns red, provided the
sically safe input circuits. channel (NO/NC mode), as well as to en‑ input circuit monitoring function is acti‑
able/disable wire-break (WB) and s hort- vated. Thereupon the output and the
Sensors according to EN 60947‑5‑6 (NA‑ circuit (SC) monitoring separately. alarm transistor are blocked.
MUR) or potential-free contact transmit‑
ters can be connected to the device. You can also set the output mode sepa‑
rately for each channel.
The output circuits each feature a p oten‑
tial-free and short-circuit proof t ransistor The Pwr LED lights green to indicate op‑
and the device also has a common alarm erational readiness. The 2‑color LED
output. 1 lights yellow to indicate the switching
status of the associated output. In the
338 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM1-451EX-T External inductance/capacitance Lo/Co
Ident no. 7541189 Ex ic IIC IIB
Lo [mH] 10 5.0 1 20 10.0 2
Power supply Co [µF] 0.91 1.0 1.5 4.3 4.9 6.8
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC Indication
Operating voltage range 20…250 VAC Operational readiness green
Frequency 40…70 Hz Switching state yellow
Power consumption ≤ 3 W Error indication red
Approvals and declarations Approval | Certification ATEX, IECEx, UL, cFMus, CSA, TR CU,
Ex approval acc. to conformity certificate TÜV 04 ATEX 2604 INMETRO, TIIS
Device designation É II (1) G, II (1) D [Ex ia Ga] IIC ; [Ex
ia Da] IIIC
Max. values: Terminal connection: 1+2 / 4…7 /
9+10
Max. output voltage Uo ≤ 11.3 V
Max. output current Io ≤ 13 mA
Max. output power Po ≤ 36 mW
Rated voltage 250 V
Interface technology
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 100 µH, Ci = 1.1 nF
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo[mH] 1.0 5.0 10 2.0 10.0 20.0
Co[µF] 0.84 0.62 0.55 4.0 2.8 2.5
▪▪ TR CU
▪▪ Monitors over and underrange of limit
values and window limits
▪▪ Line monitoring
▪▪ Operating range 0.06 … 600000 min-1
▪▪ Connection of sensors acc. to
EN 60947-5-6 (NAMUR), 3‑wire sensors
and external power supplies
▪▪ 2 relay outputs and one transistor
output
▪▪ Current output 0/4…20 mA, reversible
▪▪ Pulse output
▪▪ Parametrized via PC (FDT / DTM),
front-panel switch and HART®
▪▪ Complete galvanic isolation
The rotation speed monitor IM21‑ The device can be configured and para‑ stopped with a predefined t rigger event,
14‑CDTRI analyses frequencies, rotation metrized via PC (FDT/DTM); the a ppropri‑ like for example “excess of limit value”.
speeds and pulse trains of rotating mo‑ ate TURCK-PROG III transmission cable is After that, the stored signal sequence
tor, gear or turbine parts a ccording to available from TURCK. A basic scope of can be read out.
over or undershoot of adjusted limit val‑ parameters can b e set via buttons and
ues. The current value is indicated on a display on the front or remotely via the A switching hysteresis is defined by set‑
display on the front of the device. current interface and HART®. ting a switch-on and off point. A s witch-
off delay can also be set to avoid shut
NAMUR sensors monitor the cables for At each of the two relay outputs a prede‑ down due to sudden frequency hops.
wire-break and/or short-circuit d epend‑ fined limit value can be monitored. The
ing on the setting. In the event of an in‑ two relays also monitor overshoot/un‑
put circuit error the relays drop o
ut, the dershoot of window limits. The transistor
transistor is blocked and the Pwr LED output can also be used as a pulse divid‑
changes to red. er. The measured value is permanently
written to a ring buffer with space for
8000 values. The writing process is
340 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM21-14-CDTRI Indication
Ident no. 7505650 Operational readiness green
Pulse input yellow
Power supply Error indication red
Nominal voltage Universal voltage supply unit
Operating voltage range 20…250 VDC Environmental Conditions
Operating voltage range 20…250 VAC Ambient temperature -25…+70 °C
Frequency 40…70 Hz Storage temperature -40…+80 °C
Power consumption ≤ 3 W Relative humidity ≤ 95 %
Test voltage 2.5 kV
Inputs
No-load voltage 8.2 VDC Mechanical data
Short-circuit current 8.2 mA Tightening torque 0.5 Nm
Max. input frequency 600000 min-1 Electrical connection 4 x 5‑pin removable terminal blocks,
Pulse time ï 0.02 ms reverse polarity protected, screw
connection
Pulse stop ï 0.02 ms
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Input resistance 1 kΩ
Housing material Polycarbonate/ABS
Cable resistance ≤ 50 Ω
Mounting instruction for DIN rail / panel
Switch-on threshold: 1.55 mA
Protection class IP20
Switch-off threshold: 1.75 mA
Flammability class acc. to UL 94 V-0
Short-circuit threshold ï 6 mA
Dimensions 27 x 104 x 110 mm
Wire breakage threshold ≤ 0.1 mA
Current ≤ 20 mA
Approval | Certification TR CU
0-signal 0…3 VDC
1-signal 5…30 VDC
Input resistance 26000 Ω
Outputs
Load resistance, current output ≤ 0.6 kΩ
Output current 0/4…20 mA
Output circuits (digital) 2 x relays (NO)
Switching frequency ≤ 10 Hz
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 2 A
Switching capacity per output ≤ 500 VA/60 W
Fault current 0 / 22 mA adjustable
Contact quality AgNi, 3µ Au
Interface technology
Output circuits (digital) 1 x transistor (potential-free, short-
circuit proof)
Switching voltage ≤ 30 VDC
Switching current per output ≤ 50 mA
Switching frequency ≤ 10000 Hz
Voltage drop ≤ 2.5 V
Voltage ≤ 30 V
Current ≤ 10 mA
Response characteristic
Measuring accuracy ≤ 0.05 % of full scale
Reference temperature 23 °C
Temperature drift analogue output 0.0025 %/K
Zone 2: Do not dis-
connect when live!
IM21-14Ex-CDTRi
PC-Connect
342 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM21-14EX-CDTRI Rated voltage 250 V
Ident no. 7505651 Characteristic linear
Max. values: Terminal connection: 6+7
Power supply Max. input voltage Ui ≤ 20 V
Nominal voltage Universal voltage supply unit Max. input current Ii ≤ 21.3 mA
Operating voltage range 20…125 VDC Max. input power Pi ≤ 400 mW
Operating voltage range 20…250 VAC Internal inductance/capacitance Li/Ci negligibly small
Frequency 40…70 Hz External inductance/capacitance Lo/Co
Power consumption ≤ 3 W Ex ia IIC IIB
Lo [mH] 100 5.0 1 100 5 1
Inputs Co [µF] 0.51 0.84 1.2 2.7 4.4 6.3
No-load voltage 8.2 VDC
Ex approval acc. to conformity certificate IBExU 07 ATEX B010 X
Short-circuit current 8.2 mA
Application area II 3 G
Max. input frequency 600000 min-1
Protection type Ex nA nC [ic Gc] IIC/IIB T4 Gc
Pulse time ï 0.02 ms
Max. values: Terminal connection: 1+2 / 6+7 /
Pulse stop ï 0.02 ms 9+10
Input resistance 1 kΩ Max.output voltage Uo ≤ 9.6 V
Cable resistance ≤ 50 Ω Max. output current Io ≤ 10.7 mA
Switch-on threshold: 1.55 mA Max. output power Po ≤ 25 mW
Switch-off threshold: 1.75 mA Internal resistance Ri 900 Ω
Short-circuit threshold ï 6 mA Characteristic linear
Wire breakage threshold ≤ 0.1 mA Max. values: Terminal connection: 6+7
Max. input voltage Ui ≤ 20 V
Outputs Max. input current Ii ≤ 21.3 mA
Load resistance, current output ≤ 0.6 kΩ Max. input power Pi ≤ 400 mW
Output current 0/4…20 mA Internal inductance/capacitance Li/Ci negligibly small
Output circuits (digital) 2 x relays (NO) External inductance/capacitance Lo/Co
Switching frequency ≤ 10 Hz
Ex ic IIC IIB
Relay switching voltage ≤ 250 VAC/120 VDC
Lo [mH] 100 5.0 1 100 5 1
Switching current per output ≤ 2 A
Co [µF] 0.765 1.2 1.8 4.0 6.6 9.4
Switching capacity per output ≤ 500 VA/60 W
Fault current 0 / 22 mA adjustable
Contact quality AgNi, 3µ Au Indication
Output circuits (digital) 1 x transistor (potential-free, short- Operational readiness green
circuit proof) Pulse input yellow
Switching voltage ≤ 30 VDC Error indication red
Switching current per output ≤ 50 mA
Interface technology
Switching frequency ≤ 10000 Hz Environmental Conditions
Voltage drop ≤ 2.5 V Ambient temperature -25…+70 °C
Voltage ≤ 30 V Storage temperature -40…+80 °C
Current ≤ 10 mA Relative humidity ≤ 95 %
Test voltage 2.5 kV
Response characteristic
Measuring accuracy ≤ 0.05 % of full scale Mechanical data
Reference temperature 23 °C Tightening torque 0.5 Nm
Temperature drift analogue output 0.0025 %/K Electrical connection 4 x 5‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Approvals and declarations
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Ex approval acc. to conformity certificate IBExU 07 ATEX 1132
Housing material Polycarbonate/ABS
Device designation É II (1) G, II (1) D [Ex ia Ga] IIC , [Ex
Mounting instruction for DIN rail / panel
ia Da] IIIC
Max. values: Terminal connection: 1+2 / 6+7 / Protection class IP20
9+10 Flammability class acc. to UL 94 V-0
Max. output voltage Uo ≤ 9.6 V Dimensions 27 x 104 x 110 mm
Max. output current Io ≤ 10.7 mA
Max. output power Po ≤ 25 mW Approval | Certification ATEX, IECEx, cFMus, TR CU, NEPSI, TIIS
Internal resistance Ri 900 Ω
The 1‑channel analog signal isolator one short-circuit proof output circuit of zero signal at the input (0…10 V /
IM31‑11EX-I is designed to transmit nor‑ 0/4…20 mA. 0…20 mA) is converted and provided as
malized active voltage or current s ignals a live-zero signal at the associated o
ut‑
galvanically isolated from the Ex area to The transmission characteristic is adjust‑ put (4…20 mA).
the non-Ex area. ed via a DIP switch on the front. In switch
position “1:1“, the input signal is trans‑ A green LED indicates operational
The device is equipped with one input mitted directly to the output in the non- readiness.
circuit of 0/2…10 V or 0/4…20 mA and Ex area. In “LZ“ switch position, a dead-
344 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM31-11EX-I Indication
Ident no. 7506320 Operational readiness green
Response characteristic
Approval | Certification ATEX, IECEx, UL, cFMus, TR CU, NEPSI
Measuring accuracy ≤ 0.2 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.01 % / K
Rise time (10-90%) ≤ 50 ms
Dropout time (90…10%) ≤ 50 ms
Interface technology
Internal inductance/capacitance Li/Ci Li = 65 µH; Ci = 52 nF
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 0.5 4.5 9.5 1.5 9.5 20
Co [µF] 2 1.5 1.3 9 6.7 6.1
Ex approval acc. to conformity certificate TÜV 06 ATEX 553387 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1…3
Max.output voltage Uo ≤ 7.2 V
Max. output current Io ≤ 1 mA
Max. output power Po ≤ 2 mW
Characteristic linear
External inductance/capacitance Lo/Co
Ex ic IIC IIB
Lo [mH] 0.5 4.5 9.5 1.5 9.5 20
Co [µF] 3.9 2.5 2.2 17 12 10
Standard active voltage or current sig‑ The transmission characteristic is adjust‑ A green LED indicates operational
nals are transmitted via the 1‑channel ed via a DIP switch on the front. In switch readiness.
analog signal isolator IM31‑11Ex-U. position “1:1“, the input signal is trans‑
mitted directly to the output in the non-
The device is equipped with one input Ex area. In “LZ“ switch position, a dead-
circuit of 0/2…10 V or 0/4…20 mA and zero signal at the input (0…10 V /
one short-circuit proof output circuit of 0…20 mA) is converted and provided as
0/2…10 V. a live-zero signal at the associated o ut‑
put (2…10 V).
346 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM31-11EX-U Indication
Ident no. 7506327 Operational readiness green
Response characteristic
Approval | Certification ATEX, IECEx, UL, cFMus, TR CU, NEPSI
Measuring accuracy ≤ 0.2 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.01 % / K
Rise time (10-90%) ≤ 50 ms
Dropout time (90…10%) ≤ 50 ms
Interface technology
Internal inductance/capacitance Li/Ci Li = 65 µH; Ci = 52 nF
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 0.5 4.5 9.5 1.5 9.5 20
Co [µF] 2 1.5 1.3 9 6.7 6.1
Ex approval acc. to conformity certificate TÜV 06 ATEX 553387 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1…3
Max.output voltage Uo ≤ 7.2 V
Max. output current Io ≤ 1 mA
Max. output power Po ≤ 2 mW
Characteristic linear
External inductance/capacitance Lo/Co
Ex ic IIC IIB
Lo [mH] 0.5 4.5 9.5 1.5 9.5 20
Co [µF] 3.9 2.5 2.2 17 12 10
▪▪ TR CU
▪▪ Transmission of normalized analog
signals
7+ ▪▪ Input circuit: 0/2…10 V or 0/4…20 mA
+2 1
0/4…20 mA ▪▪ Output circuit: 0/4…20 mA
0/4...20 mA
1 alternat. –3
50 Ω R ≤ 500 Ω
10 – L
▪▪ Complete galvanic isolation
0/2...10 V 11
50 kΩ Pwr Power
+1 GN
12
Standard active voltage or current sig‑ one short-circuit proof output circuit of switch position, a dead-zero signal at the
nals are transmitted galvanically isolated 0/4…20 mA. input (0…10 V / 0…20 mA) is c onverted
via the 1‑channel analog signal isolator and provided as a live-zero signal at the
IM31‑11‑I. The transmission characteristic is adjust‑ output (4…20 mA).
ed via a DIP switch on the front. In switch
The device is equipped with one input position “1:1“, the input signal is trans‑ A green LED indicates operational
circuit of 0/2…10 V or 0/4…20 mA and mitted directly to the output. In “LZ“ readiness.
348 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM31-11-I
Ident no. 7506323
Power supply
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Power consumption ≤ 2.2 W
Inputs
Voltage input 0/2…10 VDC
Input resistance (voltage) ï 50 kΩ
Current input 0/4…20 mA
Input resistance (current) ≤ 50 Ω
Outputs
Load resistance, current output ≤ 0.5 kΩ
Output current 0/4…20 mA
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.005 % / K
Rise time (10-90%) ≤ 50 ms
Dropout time (90…10%) ≤ 50 ms
Indication
Operational readiness green
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Relative humidity ≤ 95 %
Test voltage 2.5 kV
Mechanical data
Interface technology
Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 18 x 104 x 110 mm
Approval | Certification TR CU
▪▪ TR CU
▪▪ Transmission of normalized analog
7+
1 signals
+2 10 – 0/4…20 mA ▪▪ Input circuit: 0/2…10 V or 0/4…20 mA
50 Ω
RL ≤ 500 Ω
▪▪ Output circuit: 2 x 0/4…20 mA
▪▪ Complete galvanic isolation
0/4...20 mA 8+
2
1 alternat. –3
0/2...10 V 9–
50 kΩ
+1 11
Pwr Power
GN
12
Standard active voltage or current sig‑ short-circuit proof output circuits of input (0…10 V / 0…20 mA) is c onverted
nals are transmitted galvanically isolated 0/4…20 mA. and provided as a live-zero signal at the
via the 1‑channel analog signal isolator output (4…20 mA).
IM31‑12‑I. The signal is duplicated and The transmission characteristic is adjust‑
provided at both outputs. ed via a DIP switch on the front. In switch A green LED indicates operational
position “1:1“, the input signal is trans‑ readiness.
The device features one input circuits of mitted directly to the outputs. In “LZ“
0/2…10 V or 0/4…20 mA as well as two switch position, a dead-zero signal at the
350 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM31-12-I
Ident no. 7506324
Power supply
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Power consumption ≤ 2.2 W
Inputs
Voltage input 0/2…10 VDC
Input resistance (voltage) ï 50 kΩ
Current input 0/4…20 mA
Input resistance (current) ≤ 50 Ω
Outputs
Load resistance, current output ≤ 0.5 kΩ
Output current 0/4…20 mA
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.005 % / K
Rise time (10-90%) ≤ 50 ms
Dropout time (90…10%) ≤ 50 ms
Indication
Operational readiness green
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Relative humidity ≤ 95 %
Test voltage 2.5 kV
Mechanical data
Interface technology
Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 18 x 104 x 110 mm
Approval | Certification TR CU
The 1‑channel analog signal isolator short-circuit proof output circuits of 0…20 mA) is converted and provided as
IM31‑12EX-I is designed to transmit nor‑ 0/4…20 mA. a live-zero signal at the output
malized active voltage or current s ignals (4…20 mA).
galvanically isolated from the Ex area to The transmission characteristic is adjust‑
the non-Ex area. The signal is duplicated ed via a DIP switch on the front. In switch A green LED indicates operational
and provided at both outputs. position “1:1“, the input signal is trans‑ readiness.
mitted directly to the outputs in the non-
The device features one input circuits of Ex area. In “LZ“ switch position, a dead-
0/2…10 V or 0/4…20 mA as well as two zero signal at the input (0…10 V /
352 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM31-12EX-I Indication
Ident no. 7506321 Operational readiness green
Response characteristic
Approval | Certification ATEX, IECEx, UL, cFMus, TR CU, NEPSI
Measuring accuracy ≤ 0.2 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.01 % / K
Rise time (10-90%) ≤ 50 ms
Dropout time (90…10%) ≤ 50 ms
Interface technology
Internal inductance/capacitance Li/Ci Li = 65 µH; Ci = 52 nF
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 0.5 4.5 9.5 1.5 9.5 20
Co [µF] 2 1.5 1.3 9 6.7 6.1
Ex approval acc. to conformity certificate TÜV 06 ATEX 553387 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1…3
Max.output voltage Uo ≤ 7.2 V
Max. output current Io ≤ 1 mA
Max. output power Po ≤ 2 mW
Characteristic linear
External inductance/capacitance Lo/Co
Ex ic IIC IIB
Lo [mH] 0.5 4.5 9.5 1.5 9.5 20
Co [µF] 3.9 2.5 2.2 17 12 10
▪▪ TR CU
▪▪ Transmission of normalized signals
0/4...20 mA
+2
50 Ω
7+
1 ▪▪ Input circuit: 2 x 0/2…10 V or 0/
1 alternat. –3 10 – 0/4…20 mA
4…20 mA
0/2...10 V 50 kΩ
RL ≤ 500 Ω
▪▪ Output circuit: 2 x 0/4…20 mA
▪▪ Complete galvanic isolation
+1 8+
2
+5
9–
0/4...20 mA 50 Ω
2 alternat. –6 11
0/2...10 V 50 kΩ Pwr Power
GN
+4 12
Standard active voltage or current sig‑ short-circuit proof output circuits of “LZ“ switch position, a dead-zero s ignal
nals are transmitted galvanically isolated 0/4…20 mA. at the input (0…10 V / 0…20 mA) is con‑
via the 2‑channel analog signal isolator verted and provided as a live-zero signal
IM31‑22‑I. The transmission characteristic is adjust‑ at the output (4…20 mA).
ed via a DIP switch on the front. In „1: 1“
The device features two input circuits of switch position, the input signals are A green LED indicates operational
0/2…10 V or 0/4…20 mA as well as two transmitted directly to the outputs. In readiness.
354 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM31-22-I
Ident no. 7506325
Power supply
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Power consumption ≤ 2.2 W
Inputs
Voltage input 0/2…10 VDC
Input resistance (voltage) ï 50 kΩ
Current input 0/4…20 mA
Input resistance (current) ≤ 50 Ω
Outputs
Load resistance, current output ≤ 0.5 kΩ
Output current 0/4…20 mA
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.005 % / K
Rise time (10-90%) ≤ 50 ms
Dropout time (90…10%) ≤ 50 ms
Indication
Operational readiness green
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Relative humidity ≤ 95 %
Test voltage 2.5 kV
Mechanical data
Interface technology
Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 18 x 104 x 110 mm
Approval | Certification TR CU
The 2‑channel analog signal isolator short-circuit proof output circuits of zero signal at the input (0…10 V /
IM31‑22EX-I is designed to transmit nor‑ 0/4…20 mA. 0…20 mA) is converted and provided as
malized active voltage or current s ignals a live-zero signal at the o utput
galvanically isolated from the Ex area to The transmission characteristic is adjust‑ (4…20 mA).
the non-Ex area. ed via a DIP switch on the front. In switch
position “1:1“, the input signals a re trans‑ A green LED indicates operational
The device features two input circuits of mitted directly to the outputs in the non- readiness.
0/2…10 V or 0/4…20 mA as well as two Ex area. In “LZ“ switch position, a dead-
356 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM31-22EX-I Indication
Ident no. 7506322 Operational readiness green
Response characteristic
Approval | Certification ATEX, IECEx, UL, cFMus, TR CU, NEPSI
Measuring accuracy ≤ 0.2 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.01 % / K
Rise time (10-90%) ≤ 50 ms
Dropout time (90…10%) ≤ 50 ms
Interface technology
Internal inductance/capacitance Li/Ci Li = 65 µH; Ci = 52 nF
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 0.5 4.5 9.5 1.5 9.5 20
Co [µF] 2 1.5 1.3 9 6.7 6.1
Ex approval acc. to conformity certificate TÜV 06 ATEX 553387 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1…3 / 4…6
Max.output voltage Uo ≤ 7.2 V
Max. output current Io ≤ 1 mA
Max. output power Po ≤ 2 mW
Characteristic linear
External inductance/capacitance Lo/Co
Ex ic IIC IIB
Lo [mH] 0.5 4.5 9.5 1.5 9.5 20
Co [µF] 3.9 2.5 2.2 17 12 10
The 2‑channel analog signal isolator short-circuit proof output circuits of zero signal at the input (0…10 V /
IM31‑22EX-U is designed to transmit nor‑ 0…10 V. 0…20 mA) is converted and provided as
malized active voltage or current s ignals a live-zero signal at the o
utput (0…10 V).
galvanically isolated from the Ex area to The transmission characteristic is adjust‑
the non-Ex area. ed via a DIP switch on the front. In switch A green LED indicates operational
position “1:1“, the input signals a re trans‑ readiness.
The device features two input circuits of mitted directly to the outputs in the non-
0/2…10 V or 0/4…20 mA as well as two Ex area. In “LZ“ switch position, a dead-
358 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM31-22EX-U Indication
Ident no. 7506326 Operational readiness green
Response characteristic
Approval | Certification ATEX, IECEx, UL, cFMus, TR CU, NEPSI
Measuring accuracy ≤ 0.2 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.01 % / K
Rise time (10-90%) ≤ 50 ms
Dropout time (90…10%) ≤ 50 ms
Interface technology
Internal inductance/capacitance Li/Ci Li = 65 µH; Ci = 52 nF
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 0.5 4.5 9.5 1.5 9.5 20
Co [µF] 2 1.5 1.3 9 6.7 6.1
Ex approval acc. to conformity certificate TÜV 06 ATEX 553387 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC/IIB T4 Gc
Max. values: Terminal connection: 1…3 / 4…6
Max.output voltage Uo ≤ 7.2 V
Max. output current Io ≤ 1 mA
Max. output power Po ≤ 2 mW
Characteristic linear
External inductance/capacitance Lo/Co
Ex ic IIC IIB
Lo [mH] 0.5 4.5 9.5 1.5 9.5 20
Co [µF] 3.9 2.5 2.2 17 12 10
▪▪ TR CU
▪▪ Power supply of 2‑wire measuring
transducers with HART® communica‑
tion as well as connection to active
2‑wire and passive 3‑wire transmitters
▪▪ Input circuit: 0/4…20 mA
▪▪ Output circuit: 0/4…20 mA
▪▪ SIL2
The 1‑channel HART® isolating transduc‑ The device features one input and one measuring transducer circuit are indicat‑
er IM33‑11‑HI/24VDC is designed to op‑ output circuit, each with 0/4…20 mA. ed as currents of 0 mA resp. > 22.5 mA.
erate 2‑wire HART® transducers (III) and A green LED indicates operational
to transmit the measured signal galvani‑ readiness. The removable terminal blocks feature
cally isolated. Besides the analog signals, test sockets (Ø 2 mm) for connection of a
digital HART® communication signals The input signal is transmitted 1:1 and is HART® handheld. Other device variants
can also be transmitted bidirectionally. presented to the relevant output in the are available on request.
non-Ex area.
Alternatively, active 2‑wire H
ART® trans‑
mitters (II) and passive 3‑wire HART® Due to the 1:1 transmission characteris‑
transmitters (I) can be operated. tic, wire-break or short-circuit of in the
360 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM33-11-HI/24VDC
Ident no. 7506447
Power supply
Nominal voltage 24 VDC
Operating voltage range 19…29 VDC
Power consumption ≤ 2.2 W
Inputs
Supply voltage ï 17 V / 20 mA
Current 25 mA
Current input 0/4…20 mA
Input resistance (current) ≤ 250 Ω
Outputs
Load resistance, current output ≤ 0.5 kΩ
Output current 0/4…20 mA
Wire break monitoring ≤ 0 mA
Short circuit monitoring ï 22 mA
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.005 % / K
Rise time (10-90%) ≤ 50 ms
Dropout time (90…10%) ≤ 50 ms
Indication
Operational readiness green
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Relative humidity ≤ 95 %
Interface technology
Test voltage 2.5 kV
MTTF 159 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks
with test socket, reverse polarity
protected, screw connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 18 x 110 x 110 mm
Approval | Certification TR CU
The 1‑channel HART® isolating transduc‑ The device features one input and one The removable cage clamp terminals f ea‑
er IM33‑22EX-HI/24 VDC is designed to output circuit, each with 0/4…20 mA. ture test sockets (Ø 2 mm) for connection
operate intrinsically safe HART® 2‑wire A green LED indicates operational of a HART® handheld.
transducers (III) in the Ex area and to readiness.
transmit the measured signals to the
non-Ex area. Besides the analog s ignals, The input signal is transmitted 1:1 and is
digital HART® communication signals presented to the relevant output in the
can also be transmitted bidirectionally. non-Ex area.
IM33-11Ex-Hi
24VDC
362 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM33-11EX-HI/24VDC External inductance/capacitance Lo/Co
Ident no. 7506440 Ex ic IIC IIB
Lo [mH] 3 10.0
Power supply Co [µF] 0.12 0.81
Nominal voltage 24 VDC
Internal resistance Ri 331 Ω
Operating voltage range 19…29 VDC
Declaration SIL 2 acc. to EXIDA FMEDA
Power consumption ≤ 2.2 W
Indication
Inputs
Operational readiness green
Supply voltage ï 17 V / 20 mA
Current 25 mA
Environmental Conditions
Current input 0/4…20 mA
Ambient temperature -25…+70 °C
Input resistance (current) ≤ 250 Ω
Storage temperature -40…+80 °C
Relative humidity ≤ 95 %
Outputs
Test voltage 2.5 kV
Load resistance, current output ≤ 0.5 kΩ
MTTF 159 years acc. to SN 29500 (Ed. 99)
Output current 0/4…20 mA 40 °C
Internal resistance Ri 317 Ω
Mechanical data
Response characteristic Tightening torque 0.5 Nm
Measuring accuracy ≤ 0.1 % of full scale Electrical connection 4 x 3‑pin removable terminal blocks
Reference temperature 23 °C with test socket, reverse polarity
Temperature drift ≤ 0.005 % / K protected, screw connection
Rise time (10-90%) ≤ 50 ms Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Dropout time (90…10%) ≤ 50 ms Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Approvals and declarations Protection class IP20
Ex approval acc. to conformity certificate TÜV 00 ATEX 1595 Flammability class acc. to UL 94 V-0
Device designation Dimensions 18 x 110 x 110 mm
É II (1) G, II (1) D [Ex ia Ga] IIC; [Ex
ia Da] IIIC
Max. values: Terminal connection: 1…3 Approval | Certification ATEX, IECEx, UL, cFMus, TR CU, TIIS,
Max. output voltage Uo ≤ 21.9 V CCOE
Max. output current Io ≤ 95 mA
Max. output power Po ≤ 747 mW
Rated voltage 250 V
Characteristic Trapezoidal
Max. input voltage Ui ≤ 40 V
Interface technology
Max. input power Pi ≤ 650 mW
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 2.8 11
Co [µF] 0.057 0.370
Ex approval acc. to conformity certificate TÜV 06 ATEX 552977 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC T4 Gc
Max. values: Terminal connection: 1…3
Max.output voltage Uo ≤ 21.9 V
Max. output current Io ≤ 95 mA
Characteristic trapezoidal
Max. input voltage Ui ≤ 40 V
Max. input power Pi ≤ 650 mW
▪▪ Removable terminal blocks, screw
able, with 2 mm test socket
▪▪ Complete galvanic isolation
The 1‑channel isolating transducer for The isolating transducer is loop-powered A current-to-ground error can be d
etect‑
fire and smoke detectors IM33‑FSD-EX/L and has to be connected d irectly to pow‑ ed safely via an external current- to-
is designed especially for connection of er-supplying input circuits of evaluation ground detector.
conventional fire and smoke detectors in units. Thereby normalized current sig‑
the Ex-area. nals of 0/4…20 mA are transmitted. The
voltage drop across the device is to be
They are supplied with energy. A ctuation observed.
of a smoke detector results in a current
change and the according signal is trans‑ Input and output circuits are g alvanically
mitted to the non-Ex area. Several detec‑ isolated from each other. T he inputs of
tors can be connected to one circuit. the isolating transducer a re reverse po‑
larity protected.
10 11 12
7 8 9
IM33-FSD-Ex/L
4 5 6
1 2 3
364 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM33-FSD-EX/L
Ident no. 7506433
Power supply
Nominal voltage 24 VDC loop-powered
Inputs
Supply voltage UPwr - 1 VDC - 300 Ω x IA
Supply voltage ï 17 V / 20 mA
Input resistance 300 Ω
Voltage input max. 30 VDC
Current input 0/4…20 mA
Outputs
Output circuits 0…40 mA
Load ≤ 500 Ω
Output current 0/4…20 mA
Response characteristic
Measuring accuracy ≤ 2 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.1 % / K
Rise time (10-90%) ≤ 10 ms
Dropout time (90…10%) ≤ 10 ms
Interface technology
Environmental Conditions
Ambient temperature -20…+70 °C
Storage temperature -40…+80 °C
Test voltage 2.5 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks
with test socket, reverse polarity
protected, screw connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 18 x 110 x 110 mm
2‑wire and passive 3‑wire transmitters
▪▪ Input circuit: 0/4…20 mA
▪▪ Output circuits: 0/4…20 mA
▪▪ SIL2
▪▪ Removable terminal blocks, screw
able, with 2 mm test socket
▪▪ Complete galvanic isolation
The 1‑channel HART® isolating transduc‑ The device features one input and two The removable cage clamp terminals f ea‑
er IM33‑22Ex-HI/24 VDC is designed to output circuits, for 0/4…20 mA. A green ture test sockets (Ø 2 mm) for connection
operate intrinsically safe HART® 2‑wire LED indicates operational readiness. of a HART® handheld.
transducers (III) in the Ex area and to
transmit the measured signals to the The input signal is transmitted 1:1 and is
non-Ex area. Besides the analog s ignals, presented to the relevant outputs in the
digital HART® communication signals non-Ex area. The HART® signal is trans‑
can also be transmitted bidirectionally. mitted to output 1.
366 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM33-12EX-HI/24VDC External inductance/capacitance Lo/Co
Ident no. 7506446 Ex ic IIC IIB
Lo [mH] 3 10.0
Power supply Co [µF] 0.12 0.81
Nominal voltage 24 VDC
Internal resistance Ri 331 Ω
Operating voltage range 19…29 VDC
Declaration SIL 2 acc. to EXIDA FMEDA
Power consumption ≤ 3.2 W
Indication
Inputs
Operational readiness green
Supply voltage ï 17 V / 20 mA
Current input 0/4…20 mA
Environmental Conditions
Input resistance (current) ≤ 250 Ω
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Outputs
Relative humidity ≤ 95 %
Load resistance, current output ≤ 0.5 kΩ
Test voltage 2.5 kV
Output current 0/4…20 mA
MTTF 159 years acc. to SN 29500 (Ed. 99)
Internal resistance Ri 317 Ω 40 °C
Interface technology
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 2.8 11
Co [µF] 0.057 0.370
Ex approval acc. to conformity certificate TÜV 06 ATEX 552977 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC T4 Gc
Max. values: Terminal connection: 1…3
Max.output voltage Uo ≤ 21.9 V
Max. output current Io ≤ 95 mA
Characteristic trapezoidal
Max. input voltage Ui ≤ 40 V
Max. input power Pi ≤ 650 mW
HHT
1
0/4...20 mA 17
The 1‑channel HART® isolating transduc‑ The device features one input and one The removable cage clamp terminals f ea‑
er IM33‑11EX-HI is designed to operate output circuit, for 0/4…20 mA. A green ture test sockets (Ø 2 mm) for connection
intrinsically safe HART® 2‑wire transduc‑ LED indicates operational readiness. of a HART® handheld.
ers (III) in the Ex area and to transmit the
measured signal to the non-Ex area. Be‑ The input signal is transmitted 1:1 and is
sides the analog signals, digital H ART® presented to the relevant output in the
communication signals can also be trans‑ non-Ex area.
mitted b idirectionally.
Due to the 1:1 transmission characteris‑
Alternatively, active 2‑wire H
ART® trans‑ tic, wire-break or short-circuit of in the
mitters (II) and passive 3‑wire HART® measuring transducer circuit are indicat‑
transmitters (I) can be operated. ed as currents of 0 mA resp. > 22.5 mA.
368 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM33-11EX-HI Internal inductance/capacitance Li/Ci Li = 75 µH, Ci negligibly small
Ident no. 7506443 External inductance/capacitance Lo/Co
Ex nL IIC Ex nL IIB
Power supply Lo [mH] 4.5 10
Nominal voltage Universal voltage supply unit Co [nF] 157 890
Operating voltage range 20…125 VDC
Internal resistance Ri 365 Ω
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Indication
Power consumption ≤ 3 W
Operational readiness green
Inputs
Environmental Conditions
Supply voltage ï 17 V / 20 mA
Ambient temperature -25…+70 °C
Current 25 mA
Storage temperature -40…+80 °C
Current input 0/4…20 mA
Test voltage 2.5 kV
Input resistance (current) ≤ 250 Ω
Mechanical data
Outputs
Tightening torque 0.5 Nm
Load resistance, current output ≤ 0.5 kΩ
Electrical connection 4 x 5‑pin removable terminal blocks
Output current 0/4…20 mA with test socket, reverse polarity
protected, screw connection
Response characteristic Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Measuring accuracy ≤ 0.1 % of full scale Housing material Polycarbonate/ABS
Reference temperature 23 °C Mounting instruction for DIN rail / panel
Temperature drift ≤ 0.005 % / K Protection class IP20
Rise time (10-90%) ≤ 50 ms Flammability class acc. to UL 94 V-0
Dropout time (90…10%) ≤ 50 ms Dimensions 27 x 110 x 110 mm
Approvals and declarations Approval | Certification ATEX, IECEx, cFMus, TR CU, INMETRO
Ex approval acc. to conformity certificate TÜV 05 ATEX 2910
Device designation É II (1) G; II (1) D [Ex ia Ga] IIC; [Ex
ia Da] IIIC
Max. values: Terminal connection: 1…3
Max. output voltage Uo ≤ 21.3 V
Max. output current Io ≤ 86 mA
Max. output power Po ≤ 675 mW
Internal resistance Ri 365 Ω
Rated voltage 250 V
Interface technology
Characteristic Trapezoidal
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 0.47 10
Co [µF] 0.093 0.45
Ex approval acc. to conformity certificate TÜV 06 ATEX 2967 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC T4 Gc
Max. values: Terminal connection: 1…3
Max.output voltage Uo ≤ 21.3 V
Max. output current Io ≤ 86 mA
Max. output power Po ≤ 675 mW
Characteristic trapezoidal
▪▪ ATEX, IECEx, TR CU
▪▪ Intrinsically safe input circuit Ex ia
▪▪ Installation in zone 2
▪▪ Monitors over and underrange of
analog values and window limits
▪▪ Parametrized via PC (FDT / DTM),
front-panel switch or HART®
▪▪ Power supply of 2 and 3‑wire measur‑
ing transducers
▪▪ Suited for active and passive signals
▪▪ Output circuit: 0/4…20 mA, reversible
▪▪ 3 relay outputs
▪▪ Complete galvanic isolation
Zone 2: Do not dis-
connect when live!
IM33-14Ex-CDRi
PC-Connect
370 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM33-14EX-CDRI Max. values: Terminal connection: 1…4
Ident no. 7560015 Max.output voltage Uo ≤ 21.6 V
Max. output current Io ≤ 85 mA
Power supply Max. output power Po ≤ 459 mW
Nominal voltage Universal voltage supply unit Internal resistance Ri 408 Ω
Operating voltage range 20…125 VDC Characteristic trapezoidal
Operating voltage range 20…250 VAC Max. input voltage Ui ≤ 40 V
Frequency 40…70 Hz Max. input power Pi ≤ 600 mW
Power consumption ≤ 3 W Internal inductance/capacitance Li/Ci negligible
Residual ripple ≤ 10 mVss External inductance/capacitance Lo/Co
Ex ic IIC IIB
Inputs Lo [mH] 4 0.5 0.15 5 1 0.15
Supply voltage ï 17 V / 20 mA Co [µF] 0.17 0.21 0.25 1 1.2 1.4
Current 25 mA
Voltage input 0/2…10 VDC
Indication
Current input 0/4…20 mA
Operational readiness green
Switching state yellow
Outputs
Error indication red
Load resistance, current output ≤ 0.6 kΩ
Output current 0/4…20 mA
Environmental Conditions
Output circuits (digital) 3 x relays (NO)
Ambient temperature -25…+70 °C
Switching frequency ≤ 10 Hz
Storage temperature -40…+80 °C
Relay switching voltage ≤ 250 VAC/120 VDC
Test voltage 2.5 kV
Switching current per output ≤ 2 A
Switching capacity per output ≤ 500 VA/60 W
Mechanical data
Fault current 0 / 22 mA adjustable
Tightening torque 0.5 Nm
Contact quality AgNi, 3µ Au
Electrical connection 4 x 5‑pin removable terminal blocks,
reverse polarity protected, screw
Response characteristic connection
Measuring accuracy ≤ 0.05 % of full scale Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Reference temperature 23 °C Housing material Polycarbonate/ABS
Temperature drift analogue output 0.0025 %/K Mounting instruction for DIN rail / panel
Protection class IP20
Approvals and declarations Flammability class acc. to UL 94 V-0
Ex approval acc. to conformity certificate IBExU 07 ATEX 1156 Dimensions 27 x 104 x 110 mm
Device designation É II (1) G, II (1) D [Ex ia Ga] IIC; [Ex
ia Da] IIIC Approval | Certification ATEX, IECEx, TR CU
Interface technology
Max. values: Terminal connection: 1…4
Max. output voltage Uo ≤ 21.6 V
Max. output current Io ≤ 85 mA
Max. output power Po ≤ 459 mW
Internal resistance Ri 408 Ω
Rated voltage 250 V
Characteristic Trapezoidal
Max. input voltage Ui ≤ 40 V
Max. input power Pi ≤ 600 mW
Internal inductance/capacitance Li/Ci negligible
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 0.3 0.15 5 1 0.15
Co [µF] 30 50 630 680 950
Ex approval acc. to conformity certificate IBExU 07 ATEX B015 X
Application area II 3 G
Protection type Ex nA nC [ic Gc] IIC T4 Gc
▪▪ Input circuit: 0/4…20 mA
▪▪ Output circuit: 0/4…20 mA
▪▪ Removable terminal blocks, screw
able, with 2 mm test socket
▪▪ Complete galvanic isolation
The 1‑channel HART® isolating transduc‑ The device features one input and two The removable cage clamp terminals f ea‑
er IM33‑12EX-HI is designed to operate output circuits, for 0/4…20 mA. A green ture test sockets (Ø 2 mm) for connection
intrinsically safe HART® 2‑wire transduc‑ LED indicates operational readiness. of a HART® handheld.
ers (III) in the Ex area and to transmit the
measured signals to the non-Ex area. Be‑ The input signal is transmitted 1:1 and is
sides the analog signals, digital H ART® presented to the relevant outputs in the
communication signals can also be trans‑ non-Ex area. The HART® signal is trans‑
mitted b idirectionally. mitted to output 1.
372 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM33-12EX-HI Internal inductance/capacitance Li/Ci Li = 75 µH, Ci negligibly small
Ident no. 7506444 External inductance/capacitance Lo/Co
Ex nL IIC Ex nL IIB
Power supply Lo [mH] 4.5 10
Nominal voltage Universal voltage supply unit Co [nF] 157 890
Operating voltage range 20…125 VDC
Internal resistance Ri 365 Ω
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Indication
Power consumption ≤ 3 W
Operational readiness green
Residual ripple ≤ 10 mVss
Environmental Conditions
Inputs
Ambient temperature -25…+70 °C
Supply voltage ï 17 V / 20 mA
Storage temperature -40…+80 °C
Current 25 mA
Test voltage 2.5 kV
Current input 0/4…20 mA
Input resistance (current) ≤ 250 Ω
Mechanical data
Tightening torque 0.5 Nm
Outputs
Electrical connection 4 x 5‑pin removable terminal blocks
Load resistance, current output ≤ 0.5 kΩ with test socket, reverse polarity
Output current 0/4…20 mA protected, screw connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Response characteristic Housing material Polycarbonate/ABS
Measuring accuracy ≤ 0.1 % of full scale Mounting instruction for DIN rail / panel
Reference temperature 23 °C Protection class IP20
Temperature drift ≤ 0.005 % / K Flammability class acc. to UL 94 V-0
Rise time (10-90%) ≤ 50 ms Dimensions 27 x 110 x 110 mm
Dropout time (90…10%) ≤ 50 ms
Approval | Certification ATEX, IECEx, cFMus, TR CU, INMETRO
Approvals and declarations
Ex approval acc. to conformity certificate TÜV 05 ATEX 2910
Device designation É II (1) G; II (1) D [Ex ia Ga] IIC; [Ex
ia Da] IIIC
Max. values: Terminal connection: 1…3
Max. output voltage Uo ≤ 21.3 V
Max. output current Io ≤ 86 mA
Max. output power Po ≤ 675 mW
Internal resistance Ri 365 Ω
Interface technology
Rated voltage 250 V
Characteristic Trapezoidal
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 0.47 10
Co [µF] 0.093 0.45
Ex approval acc. to conformity certificate TÜV 06 ATEX 2967 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC T4 Gc
Max. values: Terminal connection: 1…3
Max.output voltage Uo ≤ 21.3 V
Max. output current Io ≤ 86 mA
Max. output power Po ≤ 675 mW
Characteristic trapezoidal
▪▪ TR CU
▪▪ Power supply of 2‑wire measuring
transducers with HART® communica‑
tion as well as connection to active
2‑wire and passive 3‑wire transmitters
▪▪ Input circuit: 0/4…20 mA
able, with 2 mm test socket
▪▪ Complete galvanic isolation
The 2‑channel HART® isolating transduc‑ The device features 0/4…20 mA input measuring transducer circuit are indicat‑
er IM33‑22‑HI/24VDC is designed to op‑ and output circuits. A green LED indi‑ ed as currents of 0 mA resp. > 22.5 mA.
erate intrinsically safe HART® transduc‑ cates operational readiness.
ers. Besides the analog signals, digital The removable terminal blocks feature
HART® communication signals can also The input signals are transmitted 1:1 a nd test sockets (Ø 2 mm) for connection of a
be transmitted bidirectionally. are presented to the relevant o utputs in HART® handheld.
the non-Ex area.
Alternatively, active 2‑wire H
ART® trans‑
mitters (II) and passive 3‑wire HART® Due to the 1:1 transmission characteris‑
transmitters (I) can be operated. tic, wire-break or short-circuit of in the
374 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM33-22-HI/24VDC
Ident no. 7506564
Power supply
Nominal voltage 24 VDC
Operating voltage range 19…29 VDC
Power consumption ≤ 3.2 W
Inputs
Supply voltage ï 17 V / 20 mA
Current input 0/4…20 mA
Input resistance (current) ≤ 250 Ω
Outputs
Load resistance, current output ≤ 0.5 kΩ
Output current 0/4…20 mA
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.005 % / K
Rise time (10-90%) ≤ 50 ms
Dropout time (90…10%) ≤ 50 ms
Indication
Operational readiness green
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Relative humidity ≤ 95 %
Test voltage 2.5 kV
MTTF 159 years acc. to SN 29500 (Ed. 99)
40 °C
Approval | Certification TR CU
2‑wire and passive 3‑wire transmitters
▪▪ Input circuits: 0/4…20 mA
▪▪ Output circuits: 0/4…20 mA
▪▪ SIL2
▪▪ Removable terminal blocks, screw
able, with 2 mm test socket
▪▪ Complete galvanic isolation
The 2‑channel HART® isolating transduc‑ The device features 0/4…20 mA input The removable cage clamp terminals f ea‑
er IM33‑22EX-HI/24VDC is designed to and output circuits. A green LED indi‑ ture test sockets (Ø 2 mm) for connection
operate intrinsically safe HART® 2‑wire cates operational readiness. of a HART® handheld.
transducers (III) in the Ex area and to
transmit the measured signals to the The input signals are transmitted 1:1 a nd
non-Ex area. Besides the analog s ignals, are presented to the relevant o utputs in
digital HART® communication signals the non-Ex area.
can also be transmitted bidirectionally.
Due to the 1:1 transmission characteris‑
Alternatively, active 2‑wire H
ART® trans‑ tic, wire-break or short-circuit of in the
mitters (II) and passive 3‑wire HART® measuring transducer circuit are indicat‑
transmitters (I) can be operated. ed as currents of 0 mA resp. > 22.5 mA.
376 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM33-22EX-HI/24VDC External inductance/capacitance Lo/Co
Ident no. 7506441 Ex ic IIC IIB
Lo [mH] 3 10.0
Power supply Co [µF] 0.12 0.81
Nominal voltage 24 VDC
Internal resistance Ri 331 Ω
Operating voltage range 19…29 VDC
Declaration SIL 2 acc. to EXIDA FMEDA
Power consumption ≤ 3.2 W
Indication
Inputs
Operational readiness green
Supply voltage ï 17 V / 20 mA
Current input 0/4…20 mA
Environmental Conditions
Input resistance (current) ≤ 250 Ω
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Outputs
Relative humidity ≤ 95 %
Load resistance, current output ≤ 0.5 kΩ
Test voltage 2.5 kV
Output current 0/4…20 mA
MTTF 159 years acc. to SN 29500 (Ed. 99)
Internal resistance Ri 317 Ω 40 °C
Interface technology
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 2.8 11
Co [µF] 0.057 0.370
Ex approval acc. to conformity certificate TÜV 06 ATEX 552977 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC T4 Gc
Max. values: Terminal connection: 1…3 / 4…6
Max.output voltage Uo ≤ 21.9 V
Max. output current Io ≤ 95 mA
Characteristic trapezoidal
Max. input voltage Ui ≤ 30 V
Max. input power Pi ≤ 650 mW
▪▪ Input circuits: 0/4…20 mA
The 2‑channel HART® isolating transduc‑ The device features 0/4…20 mA input The removable cage clamp terminals f ea‑
er IM33‑22EX-HI is designed to operate and output circuits. A green LED indi‑ ture test sockets (Ø 2 mm) for connection
intrinsically safe HART® 2‑wire transduc‑ cates operational readiness. of a HART® handheld.
ers (III) in the Ex area and to transmit the
measured signals to the non-Ex area. Be‑ The input signals are transmitted 1:1 a nd
sides the analog signals, digital H ART® are presented to the relevant o utputs in
communication signals can also be trans‑ the non-Ex area.
mitted b idirectionally.
Due to the 1:1 transmission characteris‑
Alternatively, active 2‑wire HART® t rans‑ tic, wire-break or short-circuit of in the
mitters (II) and passive 3‑wire HART® measuring transducer circuit are indicat‑
transmitters (I) can be operated. ed as currents of 0 mA resp. > 22.5 mA.
378 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM33-22EX-HI Internal inductance/capacitance Li/Ci Li = 75 µH, Ci negligibly small
Ident no. 7506445 External inductance/capacitance Lo/Co
Ex nL IIC Ex nL IIB
Power supply Lo [mH] 4.5 10
Nominal voltage Universal voltage supply unit Co [nF] 157 890
Operating voltage range 20…125 VDC
Internal resistance Ri 365 Ω
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Indication
Power consumption ≤ 3 W
Operational readiness green
Inputs
Environmental Conditions
Supply voltage ï 17 V / 20 mA
Ambient temperature -25…+70 °C
Current 25 mA
Storage temperature -40…+80 °C
Current input 0/4…20 mA
Test voltage 2.5 kV
Input resistance (current) ≤ 250 Ω
Mechanical data
Outputs
Tightening torque 0.5 Nm
Load resistance, current output ≤ 0.5 kΩ
Electrical connection 4 x 5‑pin removable terminal blocks
Output current 0/4…20 mA with test socket, reverse polarity
protected, screw connection
Response characteristic Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Measuring accuracy ≤ 0.1 % of full scale Housing material Polycarbonate/ABS
Reference temperature 23 °C Mounting instruction for DIN rail / panel
Temperature drift ≤ 0.005 % / K Protection class IP20
Rise time (10-90%) ≤ 50 ms Flammability class acc. to UL 94 V-0
Dropout time (90…10%) ≤ 50 ms Dimensions 27 x 110 x 110 mm
Approvals and declarations Approval | Certification ATEX, IECEx, cFMus, TR CU, INMETRO
Ex approval acc. to conformity certificate TÜV 05 ATEX 2910
Device designation É II (1) G; II (1) D [Ex ia Ga] IIC; [Ex
ia Da] IIIC
Max. values: Terminal connection: 1…3 / 6…8
Max. output voltage Uo ≤ 21.3 V
Max. output current Io ≤ 86 mA
Max. output power Po ≤ 675 mW
Internal resistance Ri 365 Ω
Rated voltage 250 V
Interface technology
Characteristic Trapezoidal
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 0.47 10
Co [µF] 0.093 0.45
Ex approval acc. to conformity certificate TÜV 06 ATEX 2967 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC T4 Gc
Max. values: Terminal connection: 1…3 / 6…8
Max.output voltage Uo ≤ 21.3 V
Max. output current Io ≤ 86 mA
Max. output power Po ≤ 675 mW
Characteristic trapezoidal
▪▪ TR CU
▪▪ Input for Pt100/ Ni100 resistors, ther‑
mocouples and millivolt signals in 2, 3
or 4‑wire technology
▪▪ Output circuit: 0/4…20 mA
▪▪ Parametrized via PC (FDT / DTM)
▪▪ Complete galvanic isolation
The 1‑channel temperature measuring used as external cold junction compen‑ ▪▪ Measuring range end
amplifier IM34-11-CI is designed to eval‑ sation for the thermocouple or as inde‑ ▪▪ Input circuit monitoring for
uate the temperature-dependent c hang‑ pendent measuring input. wire-break
es of Ni100/Pt100 RTDs, thermocouples ▪▪ Current output behaviour in the event
types B, E, J, K, L, N, R, S and T or low volt‑ The device can be configured via PC w ith of input circuit errors: 0 or > 22 mA
ages in a range of -160…+160 mV and to the software tool Device Type M anager ▪▪ Internal or external cold junction
output them as linear temperature cur‑ (DTM); the appropriate transmission ca‑ compensation
rent signals. ble IM-PROG III is available from TURCK. ▪▪ Output current (0/4…20 mA)
▪▪ Temperature (°C or °K)
Alternatively, Ni100/Pt100 in 2, 3 or The following settings are available: ▪▪ Mode (resistor, thermocouples, low
4‑wire-technology can be operated at ▪▪ Connection mode (2, 3 and 4‑wire voltage, line compensation)
the measuring amplifier‘s input circuit. technology)
The Ni100/Pt100 input can either be ▪▪ Measuring range start
380 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM34-11-CI Mechanical data
Ident no. 7506638 Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks,
Power supply reverse polarity protected, screw
connection
Nominal voltage Universal voltage supply unit
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Operating voltage range 20…125 VDC
Housing material Polycarbonate/ABS
Operating voltage range 20…250 VAC
Mounting instruction for DIN rail / panel
Frequency 40…70 Hz
Protection class IP20
Power consumption ≤ 3 W
Flammability class acc. to UL 94 V-0
Dimensions 18 x 104 x 110 mm
Inputs
Input circuits thermocouple, Ni100, Pt100, mV
signals Approval | Certification TR CU
Pt100 (IEC 751), 2, 3 and 4‑wire technology
Ni100 (DIN 43760), 2, 3 and 4‑wire
technology
Probe current ≤ 0.2 mA
Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L
(DIN 43710)
Voltage input -0.160…+0.160 VDC
Outputs
Load resistance, current output ≤ 0.6 kΩ
Output current 0/4…20 mA
Fault current 0 / 22 mA adjustable
Response characteristic
Reference temperature 23 °C
Accuracy current output ± 5 µA
Temperature drift analogue output 0.0025 %/K
Temperature drift RTD input ± 3 mΩ/K
Temperature drift TC input 3.2 µV / K (of 320 mV)
Accuracy RTD input ± 50 mΩ
Accuracy TC input ± 15 µV
Cold junction compensation error 2‑wire < 100 mΩ after line
compensation
3‑wire < 100 mΩ with a symmetrical
wiring
Interface technology
4‑wire < 50 mΩ
with cold junction c ompensation< 2 K
with IM-3‑CJT < 1 K
Rise time (10-90 %) ≤ 1000 ms
Dropout time (90…10 %) ≤ 1000 ms
Indication
Operational readiness green
Error indication red
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Test voltage 2.5 kV
The 1‑channel Ex-area temperature used as external cold junction compen‑ ▪▪ Measuring range end
measuring amplifier IM34‑11EX-CI is de‑ sation for the thermocouple or as inde‑ ▪▪ Input circuit monitoring for
signed to evaluate the temperature-de‑ pendent measuring input. wire-break
pendent changes of Ni100/Pt100 RTDs, ▪▪ Current output behaviour in the event
thermocouples types B, E, J, K, L, N, R, S The device can be configured via PC w ith of input circuit errors: 0 or > 22 mA
and T or low voltages in a range o
f -160… the software tool Device Type M anager ▪▪ Internal or external cold junction
+160 mV and to output them a s temper‑ (DTM); the appropriate transmission ca‑ compensation
ature-linear current signals 0/4…20 mA. ble IM-PROG III is available from TURCK. ▪▪ Output current (0/4…20 mA)
▪▪ Temperature (°C or °K)
Alternatively, Ni100/Pt100 in 2, 3 or The following settings are available: ▪▪ Mode (resistor, thermocouples, low
4‑wire-technology can be operated at ▪▪ Connection mode (2, 3 and 4‑wire voltage, line compensation)
the measuring amplifier‘s input circuit. technology)
The Ni100/Pt100 input can either be ▪▪ Measuring range start
Pwr
PC-Connect
Zone 2: Do not dis-
connect when live!
IM34-11Ex-Ci
382 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM34-11EX-CI External inductance/capacitance Lo/Co
Ident no. 7506633 Ex ia IIC IIB
Lo [mH] 100 100
Power supply Co [µF] 2 9.1
Operating voltage range 20…125 VDC
Ex approval acc. to conformity certificate TÜV 06 ATEX 552978 X
Operating voltage range 20…250 VAC
Application area II 3 G
Frequency 40…70 Hz
Protection type Ex nA [ic Gc] IIC T4
Power consumption ≤ 3 W
Max. values: Terminal connection: 1…6
Max.output voltage Uo ≤ 5 V
Inputs
Max. output current Io ≤ 2.5 mA
Input circuits intrinsically safe acc. to EN 60079,
thermocouple, Pt100, Ni100, mV Max. output power Po ≤ 3 mW
signals Characteristic linear
Pt100 (IEC 751), 2, 3 and 4‑wire technology Internal inductance/capacitance Li/Ci negligibly small
Ni100 (DIN 43760), 2, 3 and 4‑wire External inductance/capacitance Lo/Co
technology Ex ic IIC IIB
Probe current ≤ 0.2 mA
Lo [mH] 100 100
Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L
Co [µF] 3.6 18
(DIN 43710)
Voltage input -0.160…+0.160 VDC
Indication
Outputs Operational readiness green
Load resistance, current output ≤ 0.6 kΩ Error indication red
Output current 0/4…20 mA
Fault current 0 / 22 mA adjustable Environmental Conditions
Output adjustable output mode Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Response characteristic Test voltage 2.5 kV
Reference temperature 23 °C
Accuracy current output ± 5 µA Mechanical data
Temperature drift analogue output 0.0025 %/K Tightening torque 0.5 Nm
Temperature drift RTD input ± 3 mΩ/K Electrical connection 4 x 3‑pin removable terminal blocks,
Temperature drift TC input 3.2 µV / K (of 320 mV) reverse polarity protected, screw
connection
Accuracy RTD input ± 50 mΩ
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Accuracy TC input ± 15 µV
Housing material Polycarbonate/ABS
Cold junction compensation error 2‑wire < 100 mΩ after line
compensation Mounting instruction for DIN rail / panel
3‑wire < 100 mΩ with a symmetrical Protection class IP20
Interface technology
wiring Flammability class acc. to UL 94 V-0
4‑wire < 50 mΩ Dimensions 18 x 104 x 110 mm
with cold junction c ompensation< 2 K
with IM-3‑CJT < 1 K
Rise time (10-90%) ≤ 1000 ms Approval | Certification ATEX, IECEx, UL, cFMus, TR CU,
INMETRO, CCOE
Dropout time (90…10%) ≤ 1000 ms
The 1‑channel Ex-area temperature be used as external cold junction com‑ ▪▪ Measuring range, lower limit
measuring amplifier IM34‑11EX-I is de‑ pensation for the thermocouple or as in‑ -100…- 1 °C in 1‑K steps, 0
…990 °C in
signed to evaluate the temperature-de‑ dependent measuring input. 10‑K steps
pendent changes of Ni100/Pt100 RTDs, ▪▪ Measuring range upper limit
thermocouples types B, E, J, K, L, N, R, S The measuring range and the device 0…1990 °C in 10‑K steps
and T or low voltages in a range o
f -100… functions are set via coded rotary switch‑ ▪▪ Input circuit monitoring for
+160 mV and to output them a s temper‑ es or slide switches (located on the right wire-break
ature-linear current signals 0/4…20 mA. side of the device). ▪▪ Current output behaviour in the event
of input circuit errors: 0 or > 22 mA
Alternatively, Ni100/Pt100 RTDs in 2, 3 or The following settings are available: ▪▪ Internal or external cold junction
4‑wire technology can also be o perated ▪▪ Type of probe compensation
at the input circuit of the m
easuring am‑ ▪▪ Connection of the Ni100/Pt100 resis‑
plifier. The Ni100/Pt100 input can either tor in 2, 3 or 4‑wire technology
Pwr
IM34-11Ex-i
384 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM34-11EX-I External inductance/capacitance Lo/Co
Ident no. 7506630 Ex ia IIC IIB
Lo [mH] 100 100
Power supply Co [µF] 2 9.1
Operating voltage range 20…125 VDC
Ex approval acc. to conformity certificate TÜV 06 ATEX 552978 X
Operating voltage range 20…250 VAC
Application area II 3 G
Frequency 40…70 Hz
Protection type Ex nA [ic Gc] IIC T4
Power consumption ≤ 3 W
Max. values: Terminal connection: 1…6
Max.output voltage Uo ≤ 5 V
Inputs
Max. output current Io ≤ 2.5 mA
Input circuits intrinsically safe acc. to EN 60079,
thermocouple, Ni100, Pt100, mV Max. output power Po ≤ 3 mW
signals Characteristic linear
Pt100 (IEC 751), 2, 3 and 4‑wire technology Internal inductance/capacitance Li/Ci negligibly small
Ni100 (DIN 43760), 2, 3 and 4‑wire External inductance/capacitance Lo/Co
technology Ex ic IIC IIB
Probe current ≤ 0.2 mA
Lo [mH] 100 100
Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L
Co [µF] 3.6 18
(DIN 43710)
Voltage input -0.160…+0.160 VDC
Indication
Outputs Operational readiness green
Load resistance, current output ≤ 0.6 kΩ Error indication red
Output current 0/4…20 mA
Fault current 0 / 22 mA adjustable Environmental Conditions
Output adjustable output mode Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Response characteristic Test voltage 2.5 kV
Reference temperature 23 °C
Accuracy current output ± 5 µA Mechanical data
Temperature drift analogue output 0.0025 %/K Tightening torque 0.5 Nm
Temperature drift RTD input ± 3 mΩ/K Electrical connection 4 x 3‑pin removable terminal blocks,
Temperature drift TC input 3.2 µV / K (of 320 mV) reverse polarity protected, screw
connection
Accuracy RTD input ± 50 mΩ
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Accuracy TC input ± 15 µV
Housing material Polycarbonate/ABS
Cold junction compensation error 2‑wire < 100 mΩ after line
compensation Mounting instruction for DIN rail / panel
3‑wire < 100 mΩ with a symmetrical Protection class IP20
Interface technology
wiring Flammability class acc. to UL 94 V-0
4‑wire < 50 mΩ Dimensions 18 x 104 x 110 mm
with cold junction c ompensation< 2 K
with IM-3‑CJT < 1 K
Rise time (10-90%) ≤ 1000 ms Approval | Certification ATEX, IECEx, UL, cFMus, TR CU,
INMETRO, CCOE
Dropout time (90…10%) ≤ 1000 ms
The temperature measuring amplifier used as external cold junction compen‑ ▪▪ Measuring range start
IM34-11Ex-Ci/24VDC is designed to e val‑ sation for the thermocouple or as inde‑ ▪▪ Measuring range end
uate the temperature-dependent c hang‑ pendent measuring input. ▪▪ Input circuit monitoring for
es of Ni100/Pt100 RTDs, thermocouples wire-break
types B, E, J, K, L, N, R, S and T or low volt‑ The device can be configured and para‑ ▪▪ Current output behaviour in the event
ages in a range of -160…+160 mV and to metrized via PC (FDT/DTM); the a ppropri‑ of input circuit errors: 0 or > 22 mA
output them as temperature-linear cur‑ ate TURCK-PROG III transmission cable is ▪▪ Internal, external or constant cold
rent signals. available from TURCK. junction compensation
▪▪ Output current (0/4…20 mA)
Alternatively, Ni100/Pt100 in 2, 3 or The following settings can be adjusted ▪▪ Temperature (°C or °K)
4‑wire-technology can be operated at via DTM: ▪▪ Mode (resistor, thermocouples, low
the measuring amplifier‘s input circuit. ▪▪ Connection mode (2, 3 and 4‑wire voltage, line compensation)
The Ni100/Pt100 input can either be technology)
386 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM34-11Ex-CI/24VDC External inductance/capacitance Lo/Co
Ident no. 7506637 Ex ia IIC IIB
Lo [mH] 100 100
Power supply Co [µF] 2 9.1
Nominal voltage 24 VDC
Ex approval acc. to conformity certificate TÜV 06 ATEX 552978 X
Operating voltage range 20…30 VDC
Application area II 3 G
Power consumption ≤ 1.5 W
Protection type Ex nA [ic Gc] IIC T4
Max. values: Terminal connection: 1…6
Inputs
Max.output voltage Uo ≤ 5 V
Input circuits intrinsically safe acc. to EN 60079,
thermocouple, Ni100, Pt100, mV Max. output current Io ≤ 2.5 mA
signals Max. output power Po ≤ 3 mW
RTD Pt100 (IEC 751), NI100 (DIN 43760), 2‑ Characteristic linear
und 3‑Leiter-Technik, nach Gost: Internal inductance/capacitance Li/Ci negligibly small
Pt100, Cu50, Cu53, Cu100, CuZn100 External inductance/capacitance Lo/Co
Ni100 (DIN 43760), 2, 3 and 4‑wire
technology Ex ic IIC IIB
Probe current ≤ 0.2 mA Lo [mH] 100 100
Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L Co [µF] 3.6 18
(DIN 43710), acc. to Gost: L, M, A1, A2,
A3
Indication
Voltage input -0.160…+0.160 VDC
Operational readiness green
Error indication red
Outputs
Load resistance, current output ≤ 0.6 kΩ
Environmental Conditions
Output current 0/4…20 mA
Ambient temperature -25…+70 °C
Fault current 0 / 22 mA adjustable
Storage temperature -40…+80 °C
Output adjustable output mode
Test voltage 2.5 kV
Response characteristic
Mechanical data
Reference temperature 23 °C
Tightening torque 0.5 Nm
Accuracy current output ± 20 µA
Electrical connection 4 x 3‑pin removable terminal blocks,
Temperature drift analogue output 0.0025 %/K
reverse polarity protected, screw
Temperature drift RTD input ± 3 mΩ/K connection
Temperature drift TC input 3.2 µV / K (of 320 mV) Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Accuracy RTD input ± 50 mΩ Housing material Polycarbonate/ABS
Accuracy TC input ± 15 µV Mounting instruction for DIN rail / panel
Cold junction compensation error 2‑wire < 100 mΩ after line Protection class IP20
compensation
Interface technology
Flammability class acc. to UL 94 V-0
3‑wire < 100 mΩ with a symmetrical
wiring Dimensions 18 x 104 x 110 mm
4‑wire < 50 mΩ
with cold junction c ompensation< 2 K Approval | Certification ATEX, IECEx, TR CU, INMETRO, CCOE
with IM-3‑CJT < 1 K
Rise time (10-90%) ≤ 1000 ms
Dropout time (90…10%) ≤ 1000 ms
The 1‑channel Ex-area temperature pensation for the thermocouple or as in‑ ▪▪ Measuring range end
measuring amplifier IM34‑12EX-CRI is dependent measuring input. ▪▪ Limit value
designed to evaluate the temperature- The device has an additional relay output ▪▪ Input circuit monitoring for
dependent changes of Ni100/Pt100 to monitor over or underrange of a limit wire-break
RTDs, thermocouples types B, E, J, K, L, N, value. ▪▪ Current output behaviour in the event
R, S and T or low voltages in a range o f of input circuit errors: 0 or > 22 mA
-160…+160 mV and to output them a s The device can be configured and para‑ ▪▪ Internal or external cold junction
temperature-linear current signals metrized via PC (FDT/DTM); the a ppropri‑ compensation
0/4…20 mA. ate TURCK-PROG III transmission cable is ▪▪ Output current (0/4…20 mA)
available from TURCK. ▪▪ Temperature (°C or °K)
Alternatively, Ni100/Pt100 RTDs in 2, 3 or ▪▪ Mode (resistor, thermocouples, low
4‑wire technology can also be o perated The following settings are available: voltage, line compensation)
at the input circuit of the m
easuring am‑ ▪▪ Connection mode (2, 3 and 4‑wire
plifier. The Ni100/Pt100 input can either technology)
be used as external cold junction com‑ ▪▪ Measuring range start
Pwr
1
PC-Connect
Zone 2: Do not dis-
connect when live!
IM34-12Ex-CRi
388 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM34-12EX-CRI Max. values: Terminal connection: 1…6
Ident no. 7506632 Max. output voltage Uo ≤ 5 V
Max. output current Io ≤ 2.5 mA
Power supply Max. output power Po ≤ 3 mW
Operating voltage range 20…125 VDC Rated voltage 250 V
Operating voltage range 20…250 VAC Characteristic linear
Frequency 40…70 Hz Internal inductance/capacitance Li/Ci negligibly small
Power consumption ≤ 3 W External inductance/capacitance Lo/Co
Ex ia IIC IIB
Inputs Lo [mH] 100 100
Input circuits intrinsically safe acc. to EN 60079, Co [µF] 2 9.1
thermocouple, Pt100, Ni100, mV
signals Ex approval acc. to conformity certificate TÜV 06 ATEX 552978 X
Pt100 (IEC 751), 2, 3 and 4‑wire technology Application area II 3 G
Ni100 (DIN 43760), 2, 3 and 4‑wire Protection type Ex nA nC [ic Gc] IIC T4
technology Max. values: Terminal connection: 1…6
Probe current ≤ 0.2 mA Max.output voltage Uo ≤ 5 V
Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L Max. output current Io ≤ 2.5 mA
(DIN 43710)
Max. output power Po ≤ 3 mW
Voltage input -0.160…+0.160 VDC
Characteristic linear
Internal inductance/capacitance Li/Ci negligibly small
Outputs
External inductance/capacitance Lo/Co
Load resistance, current output ≤ 0.6 kΩ
Output current 0/4…20 mA Ex ic IIC IIB
Output circuits (digital) 1 x relays (NO) Lo [mH] 100 100
Switching frequency ≤ 10 Hz Co [µF] 3.6 18
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 2 A Indication
Switching capacity per output ≤ 500 VA/60 W Operational readiness green
Fault current 0 / 22 mA adjustable Switching state yellow
Contact quality AgNi, 3µ Au
Output adjustable output mode Environmental Conditions
Ambient temperature -25…+70 °C
Response characteristic Storage temperature -40…+80 °C
Reference temperature 23 °C Test voltage 2.5 kV
Accuracy current output ± 5 µA
Temperature drift analogue output 0.0025 %/K Mechanical data
Temperature drift RTD input ± 3 mΩ/K Tightening torque 0.5 Nm
Interface technology
Temperature drift TC input 3.2 µV / K (of 320 mV) Electrical connection 4 x 3‑pin removable terminal blocks,
Accuracy RTD input ± 50 mΩ reverse polarity protected, screw
connection
Accuracy TC input ± 15 µV
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Cold junction compensation error 2‑wire < 100 mΩ after line
compensation Housing material Polycarbonate/ABS
3‑wire < 100 mΩ with a symmetrical Mounting instruction for DIN rail / panel
wiring Protection class IP20
4‑wire < 50 mΩ Flammability class acc. to UL 94 V-0
with cold junction c ompensation< 2 K
Dimensions 18 x 104 x 110 mm
with IM-3‑CJT < 1 K
Rise time (10-90%) ≤ 1000 ms
Dropout time (90…10%) ≤ 1000 ms Approval | Certification ATEX, IECEx, UL, cFMus, TR CU,
INMETRO, CCOE
The 1‑channel Ex-area temperature pensation for the thermocouple or as in‑ ▪▪ Measuring range, lower limit -100…
measuring amplifier IM34‑12EX-RI is de‑ dependent measuring input. -1 °C in 1‑K steps, upper limit
signed to evaluate the temperature-de‑ The device has an additional relay output 0…990 °C in 10‑K steps
pendent changes of Ni100/Pt100 RTDs, to monitor over or underrange of a limit ▪▪ Limit value
thermocouples types B, E, J, K, L, N, R, S value. ▪▪ Measuring range upper limit
and T or low voltages in a range o
f -100… 0…1990 °C in 10‑K steps
+160 mV and to output them a s temper‑ The measuring range, limit value and the ▪▪ Input circuit monitoring for
ature-linear current signals 0/4…20 mA. device functions are set via rotary c oding wire-break
switches or rather slide switches. ▪▪ Current output behaviour in the event
Alternatively, Ni100/Pt100 RTDs in 2, 3 or of input circuit errors: 0 or > 22 mA
4‑wire technology can also be o perated The following settings are available: ▪▪ Internal or external cold junction
at the input circuit of the m
easuring am‑ ▪▪ Type of probe compensation
plifier. The Ni100/Pt100 input can either ▪▪ Connection of the Ni100/Pt100 resis‑ ▪▪ Relay output mode
be used as external cold junction com‑ tor in 2, 3 or 4‑wire technology
Pwr
1
Zone 2: Do not dis-
connect when live!
IM34-12Ex-Ri
390 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM34-12EX-RI Max. values: Terminal connection: 1…6
Ident no. 7506631 Max. output voltage Uo ≤ 5 V
Max. output current Io ≤ 2.5 mA
Power supply Max. output power Po ≤ 3 mW
Nominal voltage Universal voltage supply unit Characteristic linear
Operating voltage range 20…125 VDC Internal inductance/capacitance Li/Ci negligibly small
Operating voltage range 20…250 VAC External inductance/capacitance Lo/Co
Frequency 40…70 Hz Ex ia IIC IIB
Power consumption ≤ 3 W Lo [mH] 100 100
Co [µF] 2 9.1
Inputs
Ex approval acc. to conformity certificate TÜV 06 ATEX 552978 X
Input circuits intrinsically safe acc. to EN 60079,
thermocouple, Ni100, Pt100, mV Application area II 3 G
signals Protection type Ex nA nC [ic Gc] IIC T4
Pt100 (IEC 751), 2, 3 and 4‑wire technology Max. values: Terminal connection: 1…6
Ni100 (DIN 43760), 2, 3 and 4‑wire Max.output voltage Uo ≤ 5 V
technology Max. output current Io ≤ 2.5 mA
Probe current ≤ 0.2 mA Max. output power Po ≤ 3 mW
Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L Characteristic linear
(DIN 43710)
Internal inductance/capacitance Li/Ci negligibly small
Voltage input -0.160…+0.160 VDC
External inductance/capacitance Lo/Co
Interface technology
connection
Temperature drift RTD input ± 3 mΩ/K
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Temperature drift TC input 3.2 µV / K (of 320 mV)
Housing material Polycarbonate/ABS
Accuracy RTD input ± 50 mΩ
Mounting instruction for DIN rail / panel
Accuracy TC input ± 15 µV
Protection class IP20
Cold junction compensation error 2‑wire < 100 mΩ after line
compensation Flammability class acc. to UL 94 V-0
3‑wire < 100 mΩ with a symmetrical Dimensions 18 x 104 x 110 mm
wiring
4‑wire < 50 mΩ Approval | Certification ATEX, IECEx, UL, cFMus, TR CU,
with cold junction c ompensation< 2 K INMETRO, CCOE
with IM-3‑CJT < 1 K
Rise time (10-90%) ≤ 1000 ms
Dropout time (90…10%) ≤ 1000 ms
392 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM34-12Ex-CRi/K63 Approvals and declarations
Ident no. 7506605 Ex approval acc. to conformity certificate TÜV 02 ATEX 1898
Device designation É II (1) G, II (1) D [Ex ia Ga] IIC ; [Ex
Power supply ia Da] IIIC ;
Nominal voltage Universal voltage supply unit Max. values: Terminal connection: 1…6
Operating voltage range 20…125 VDC Max. output voltage Uo ≤ 5 V
Operating voltage range 20…250 VAC Max. output current Io ≤ 2.5 mA
Frequency 40…70 Hz Max. output power Po ≤ 3 mW
Power consumption ≤ 3 W Rated voltage 250 V
Characteristic linear
Inputs Internal inductance/capacitance Li/Ci negligibly small
Input circuits intrinsically safe acc. to EN 60079, External inductance/capacitance Lo/Co
thermocouple, Ni100, Pt100, mV Ex ia IIC IIB
signals
Lo [mH] 100 100
Pt100 (IEC 751), 2, 3 and 4‑wire technology,
Co [µF] 2 9.1
acc. to Gost: Pt100, Cu50, Cu53,
Cu100, CuZn100 Ex approval acc. to conformity certificate TÜV 06 ATEX 552978 X
Ni100 (DIN 43760), 2, 3 and 4‑wire Application area II 3 G
technology
Protection type Ex nA nC [ic Gc] IIC T4
Probe current ≤ 0.2 mA
Max. values: Terminal connection: 1…6
Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L
Max.output voltage Uo ≤ 5 V
(DIN 43710), acc. to Gost: L, A-1, A-2,
A-3, M Max. output current Io ≤ 2.5 mA
Voltage input -0.160…+0.160 VDC Max. output power Po ≤ 3 mW
Characteristic linear
Outputs Internal inductance/capacitance Li/Ci negligibly small
Load resistance, current output ≤ 0.6 kΩ External inductance/capacitance Lo/Co
Output current 0/4…20 mA Ex ic IIC IIB
Output circuits (digital) 1 x relays (NO) Lo [mH] 100 100
Switching frequency ≤ 10 Hz Co [µF] 3.6 18
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 2 A
Indication
Switching capacity per output ≤ 500 VA/60 W
Operational readiness green
Fault current 0 / 22 mA adjustable
Switching state yellow
Contact quality AgNi, 3µ Au
Error indication red
Output adjustable output mode
Environmental Conditions
Response characteristic
Ambient temperature -25…+70 °C
Interface technology
Reference temperature 23 °C
Storage temperature -40…+80 °C
Accuracy current output ± 5 µA
Test voltage 2.5 kV
Temperature drift analogue output 0.0025 %/K
Temperature drift RTD input ± 3 mΩ/K
Mechanical data
Temperature drift TC input 3.2 µV / K (of 320 mV)
Tightening torque 0.5 Nm
Accuracy RTD input ± 50 mΩ
Electrical connection 4 x 3‑pin removable terminal blocks,
Accuracy TC input ± 15 µV reverse polarity protected, screw
Cold junction compensation error 2‑wire < 100 mΩ after line connection
compensation Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
3‑wire < 100 mΩ with a symmetrical Housing material Polycarbonate/ABS
wiring
Mounting instruction for DIN rail / panel
4‑wire < 50 mΩ
with cold junction c ompensation< 2 K Protection class IP20
with IM-3‑CJT < 1 K Flammability class acc. to UL 94 V-0
Rise time (10-90%) ≤ 1000 ms Dimensions 18 x 104 x 110 mm
Dropout time (90…10%) ≤ 1000 ms
Approval | Certification ATEX, IECEx, UL, cFMus, TR CU,
INMETRO, CCOE
The 1‑channel Ex-area temperature The device can be configured and para‑ ▪▪ Internal or external cold junction
measuring amplifier IM34‑11EX-CI/K51 is metrized via PC with the software tool compensation
designed to evaluate the temperature- Device Type Manager (DTM). For this, ▪▪ Output current (0/4…20 mA)
dependent changes of Ni100/Pt100 connect the device to the PC via the ▪▪ Temperature (°C or °K)
RTDs, thermocouples types B, E, J, K, L, N, 3.5 mm jack on the front (the matching ▪▪ Mode (resistor, thermocouples, low
R, S and T or low voltages in a range of transmission cable IM-PROG III can be o
r‑ voltage, line compensation)
-160…+160 mV and to o utput them as dered separately from TURCK).
temperature-linear current
signals
0/4…20 mA. The following settings are available: The signals are transformed according t o
▪▪ Connection mode (2, 3 and 4‑wire ITS 90/IEC 584 for thermocouples and IEC
Alternatively, Ni100/Pt100 RTDs in 2, 3 or technology) 751 for Pt100 RTDs and provided as tem‑
4‑wire technology can also be o perated ▪▪ Measuring range start perature-linear signals at the current
at the input circuit of the m
easuring am‑ ▪▪ Measuring range end output.
plifier. The Ni100/Pt100 input can either ▪▪ Input circuit monitoring for
be used as external cold junction com‑ wire-break
pensation for the thermocouple or as in‑ ▪▪ Current output behaviour in the event
dependent measuring input. of input circuit errors: 0 or > 22 mA
Pwr
1
IM34-12Ex-Ri
394 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM34-11EX-CI/K51 External inductance/capacitance Lo/Co
Ident no. 7506635 Ex ia IIC IIB
Lo [mH] 100 100
Power supply Co [µF] 2 9.1
Nominal voltage Universal voltage supply unit
Ex approval acc. to conformity certificate TÜV 06 ATEX 552978 X
Operating voltage range 20…125 VDC
Application area II 3 G
Operating voltage range 20…250 VAC
Protection type Ex nA [ic Gc] IIC T4
Frequency 40…70 Hz
Max. values: Terminal connection: 1…6
Power consumption ≤ 3 W
Max.output voltage Uo ≤ 5 V
Max. output current Io ≤ 2.5 mA
Inputs
Max. output power Po ≤ 3 mW
Input circuits intrinsically safe acc. to EN 60079,
thermocouple, Ni100, Pt100, Characteristic linear
intrinsically safe acc. to EN 60079 Internal inductance/capacitance Li/Ci negligibly small
Pt100 (IEC 751), 2, 3 and 4‑wire technology External inductance/capacitance Lo/Co
Ni100 (DIN 43760), 2, 3 and 4‑wire Ex ic IIC IIB
technology Lo [mH] 100 100
Probe current ≤ 0.2 mA
Co [µF] 3.6 18
Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L
(DIN 43710)
Voltage input -0.160…+0.160 VDC Indication
Operational readiness green
Outputs
Load resistance, current output ≤ 0.6 kΩ Environmental Conditions
Output current 0/4…20 mA Ambient temperature -25…+70 °C
Switching frequency ≤ 1 Hz Storage temperature -40…+80 °C
Fault current 0 / 22 mA adjustable Test voltage 4.0 kV
Interface technology
3‑wire < 100 mΩ with a symmetrical Dimensions 18 x 104 x 110 mm
wiring
4‑wire < 50 mΩ Approval | Certification ATEX, IECEx, UL, cFMus, TR CU,
with cold junction c ompensation< 2 K INMETRO, CCOE
with IM-3‑CJT < 1 K
Rise time (10-90%) ≤ 1000 ms
Dropout time (90…10%) ≤ 1000 ms
The 1‑channel temperature measuring junction compensation for the thermo‑ „Fast Mode“ after 200 ms at the very lat‑
amplifier IM34‑11Ex-CI/K60 is designed couple or as independent measuring est after a gradient of 200 µV/s has b
een
to evaluate the temperature-dependent input. exceeded. Thereafter the cycle time
changes of Ni100/Pt100 (RTD), thermo‑ of the thermal voltage measurement is
couples (TC) types B, E, J, K, L, N, R, S If the thermocouples lines are routed to < 80 ms. This means that no wire-break
and T or low voltages in a range of the temperature measuring amplifier monitoring and no measurement of the
-160…+160 mV and to output them as TURCK recommends the use the cold cold junction temperature will occur. Af‑
temperature-linear current signals of junction compensation module IM-3‑CJT ter the g radient drops below 80 µV/s the
0/4…20 mA. Alternatively, Ni100/Pt100 (Ident no.: 6900524) This way the maxi‑ device will switch back to „Normal
RTDs in 2, 3 or 4‑wire technology can also mum possible accuracy is achieved. In Mode“.
be operated at the input circuit of the order to increase the measurment speed
measuring amplifier. The Ni100/Pt100 in‑ with fast temperature changes on ther‑
put can either be used as e xternal cold mocouples, the device switches into t he
396 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM34-11EX-CI/K60 Ex approval acc. to conformity certificate TÜV 06 ATEX 552978 X
Ident no. 7506636 Application area II 3 G
Protection type Ex nA [ic Gc] IIC T4
Power supply Max. values: Terminal connection: 1…6
Operating voltage range 20…125 VDC Max.output voltage Uo ≤ 5 V
Operating voltage range 20…250 VAC Max. output current Io ≤ 2.5 mA
Frequency 40…70 Hz Max. output power Po ≤ 3 mW
Characteristic linear
Inputs Internal inductance/capacitance Li/Ci negligibly small
Input circuits intrinsically safe acc. to EN 60079, External inductance/capacitance Lo/Co
thermocouple, Pt100, Ni 00, mV
Ex ic IIC IIB
signals
Pt100 (IEC 751), 2, 3 and 4‑wire technology Lo [mH] 100 100
Ni100 (DIN 43760), 2, 3 and 4‑wire Co [µF] 3.6 18
technology
Probe current ≤ 0.2 mA Environmental Conditions
Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L Ambient temperature -25…+70 °C
(DIN 43710)
Storage temperature -40…+80 °C
Voltage input -0.160…+0.160 VDC
Test voltage 2.5 kV
Outputs
Mechanical data
Output current 0/4…20 mA
Tightening torque 0.5 Nm
Switching frequency ≤ 1 Hz
Electrical connection 4 x 3‑pin removable terminal blocks,
Fault current 0 / 22 mA adjustable reverse polarity protected, screw
Output adjustable output mode connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Response characteristic Housing material Polycarbonate/ABS
Reference temperature 23 °C Mounting instruction for DIN rail / panel
Accuracy current output ± 5 µA Protection class IP20
Temperature drift analogue output 0.0025 %/K Flammability class acc. to UL 94 V-0
Temperature drift RTD input ± 3 mΩ/K Dimensions 18 x 104 x 110 mm
Temperature drift TC input 3.2 µV / K (of 320 mV)
Accuracy RTD input ± 50 mΩ Approval | Certification ATEX, IECEx, UL, cFMus, TR CU,
Accuracy TC input ± 15 µV INMETRO, CCOE
Cold junction compensation error 2‑wire < 100 mΩ after line
compensation
3‑wire < 100 mΩ with a symmetrical
wiring
4‑wire < 50 mΩ
Interface technology
with cold junction c ompensation< 2 K
with IM-3‑CJT < 1 K
▪▪ Monitors over and underrange of
analog values and window limits
▪▪ Line monitoring
▪▪ Parametrized via PC (FDT / DTM),
front-panel switch or HART®
▪▪ Input for Pt100/ Ni100 resistors, varia‑
ble resistors, thermocouples and milli‑
volt s ignals
▪▪ Output circuit: 0/4…20 mA
▪▪ 3 relay outputs
Zone 2: Do not dis-
connect when live!
IM34-14Ex-CDRi
PC-Connect
398 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM34-14EX-CDRI Max. values: Terminal connection: 4…10
Ident no. 7506634 Max. output voltage Uo ≤ 5 V
Max. output current Io ≤ 9 mA
Power supply Max. output power Po ≤ 11 mW
Operating voltage range 20…125 VDC Rated voltage 250 V
Operating voltage range 20…250 VAC Characteristic linear
Frequency 40…70 Hz Internal inductance/capacitance Li/Ci Li = 75 µH, Ci negligibly small
Power consumption ≤ 3 W External inductance/capacitance Lo/Co
Ex ia IIC IIB
Inputs Lo [mH] 5 10
Input circuits intrinsically safe acc. to EN 60079, Co [µF] 2.9 13
thermocouple, Ni100, Pt100, mV
signals Ex approval acc. to conformity certificate TÜV 05 ATEX 2889 X
Pt100 (IEC 751), 2, 3 and 4‑wire technology Application area II 3 G
Ni100 (DIN 43760), 2, 3 and 4‑wire Protection type EEx nA nC [nL]
technology Max. values: Terminal connection: 4…10
Probe current ≤ 0.2 mA Max.output voltage Uo ≤ 5 V
Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L Max. output current Io ≤ 9 mA
(DIN 43710)
Max. output power Po ≤ 11 mW
Nominal resistance 0…1.5 kΩ
Characteristic linear
Voltage input -0.160…+0.160 VDC
Internal inductance/capacitance Li/Ci Li = 75 µH, Ci negligibly small
External inductance/capacitance Lo/Co
Outputs
Load resistance, current output ≤ 0.6 kΩ Ex ia IIC IIB
Output current 0/4…20 mA Lo [mH] 10 20
Output circuits (digital) 3 x relays (NO) Co [µF] 4.4 21
Switching frequency ≤ 10 Hz
Relay switching voltage ≤ 250 VAC/120 VDC Indication
Switching current per output ≤ 2 A Operational readiness green
Switching capacity per output ≤ 500 VA/60 W Switching state yellow
Fault current 0 / 22 mA adjustable Error indication red
Contact quality AgNi, 3µ Au
Output adjustable output mode Environmental Conditions
Ambient temperature -25…+70 °C
Response characteristic Storage temperature -40…+80 °C
Reference temperature 23 °C Relative humidity ≤ 95 %
Accuracy current output ± 5 µA Test voltage 2.5 kV
Temperature drift analogue output 0.0025 %/K
Interface technology
Temperature drift RTD input ± 3 mΩ/K Mechanical data
Temperature drift TC input 3.2 µV / K (of 320 mV) Tightening torque 0.5 Nm
Accuracy RTD input ± 50 mΩ Electrical connection 4 x 5‑pin removable terminal blocks,
Accuracy TC input ± 15 µV reverse polarity protected, screw
connection
Cold junction compensation error 2‑wire < 100 mΩ after line
compensation Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
3‑wire < 100 mΩ with a symmetrical Housing material Polycarbonate/ABS
wiring Mounting instruction for DIN rail / panel
4‑wire < 50 mΩ Protection class IP20
with cold junction c ompensation< 2 K
Flammability class acc. to UL 94 V-0
with IM-3‑CJT < 1 K
Rise time (10-90%) ≤ 1000 ms Dimensions 27 x 104 x 110 mm
Dropout time (90…10%) ≤ 1000 ms
Approval | Certification ATEX, IECEx, cFMus, TIIS
Approvals and declarations
Ex approval acc. to conformity certificate TÜV 05 ATEX 2877
Device designation É II (1) GD [EEx ia] IIC
HHT
HART® 110 Ω 0/4...20 mA
+1 10 –
P ▪▪ Output circuit: 0/4…20 mA,
I –2 11 + intrinsically-safe
Pwr Power 24 VDC ▪▪ SIL2
0/4...20 mA GN
12 –
▪▪ Removable terminal blocks, screw
able, with 2 mm test socket
▪▪ Galvanic isolation of input circuits,
output circuits and power supply
The 1‑channel signal isolator IM35-11EX- Typical applications are for example, the [HHT] can be connected to the output
HI/24VDC is designed to transmit the control of I/P converters (at control and input terminals 7/10.
normalized current signal galvanically valves for example) or indicators in the
isolated 1:1 from the non-Ex a rea to the Ex-area. In addition, the removable terminal
Ex-area. Besides the analog signals, digi‑ blocks are equipped with 2 mm test
tal HART® communication signals can The actuators are connected to the out‑ sockets for signal control.
also be transmitted bidirectionally. put terminals 1/2. Handheld terminals
IM35-11Ex-Hi
24VDC
400 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM35-11EX-HI/24VDC Indication
Ident no. 7506516 Operational readiness green
Interface technology
Lo [mH] 5 0.5 10 0.5
Co [nF] 135 330 860 2200
Ex approval acc. to conformity certificate TÜV 06 ATEX 553057 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC T4 Gc
Max. values: Terminal connection: 1+2
Max.output voltage Uo ≤ 15.9 V
Max. output current Io ≤ 60 mA
Max. output power Po ≤ 470 mW
Internal resistance Ri 528 Ω
Characteristic trapezoidal
Internal inductance/capacitance Li/Ci Li=negligibly small; Ci=5nF
External inductance/capacitance Lo/Co
Ex ic IIC IIB
Lo [mH] 5 0.5 10 0.5
Co [nF] 290 640 1700 3900
Declaration SIL 2 acc. to EXIDA FMEDA
HHT
110 Ω 1 0/4...20 mA HART® communication interface
10 –
I –2
▪▪ Input circuits: 0/4…20 mA
1
0/4...20 mA
8+ ▪▪ Output circuits: 0/4…20 mA,
intrinsically-safe
HHT
110 Ω 2 0/4...20 mA
HART® +4
9–
▪▪ SIL2
P
11 + ▪▪ Removable terminal blocks, screw
I –5 able, with 2 mm test socket
2
Pwr
GN
12 –
Power 24 VDC
▪▪ Complete galvanic isolation
0/4...20 mA
The 2‑channel signal isolator IM35‑22EX- Typical applications are for example, the minals [HHT] can be connected to the
HI/24VDC is designed to transmit the control of I/P converters (at control output and input terminals 7/10 and 8/9.
normalized current signal galvanically valves for example) or indicators in the
isolated 1:1 from the non-Ex a rea to the Ex-area. In addition, the removable terminal
Ex-area. Besides the analog signals, digi‑ blocks are equipped with 2 mm test
tal HART® communication signals can The actuators are connected to the out‑ sockets for signal control.
also be transmitted bidirectionally. put terminals 1/2 and 4/5. Handheld ter‑
IM35-22Ex-Hi
24VDC
402 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM35-22EX-HI/24VDC Indication
Ident no. 7506515 Operational readiness green
Interface technology
Lo [mH] 5 0.5 10 0.5
Co [nF] 135 330 860 2200
Ex approval acc. to conformity certificate TÜV 06 ATEX 553057 X
Application area II 3 G
Protection type Ex nA [ic Gc] IIC T4 Gc
Max. values: Terminal connection: 1+2 / 4+5
Max.output voltage Uo ≤ 15.9 V
Max. output current Io ≤ 60 mA
Max. output power Po ≤ 470 mW
Internal resistance Ri 528 Ω
Characteristic trapezoidal
Internal inductance/capacitance Li/Ci Li=negligibly small; Ci=5nF
External inductance/capacitance Lo/Co
Ex ic IIC IIB
Lo [mH] 5 0.5 10 0.5
Co [nF] 290 640 1700 3900
Declaration SIL 2 acc. to EXIDA FMEDA
▪▪ ATEX, TR CU
▪▪ Installation in zone 2
▪▪ Intelligent actuators supplied via
HART® communication interface
▪▪ Input circuit: 0/4…20 mA
▪▪ Output circuit: 0/4…20 mA,
intrinsically-safe
▪▪ Universal operating voltage
▪▪ Complete galvanic isolation
The 1‑channel signal isolator IM35‑11EX- Typical applications are for example, the [HHT] can be connected to the output
HI is designed to transmit the normalized control of I/P converters (at control and input terminals 16/17.
current signal galvanically isolated 1:1 valves for example) or indicators in the
from the non-Ex a rea to the Ex-area. Be‑ Ex-area. In addition, the removable terminal
sides the analog signals, digital HART® blocks are equipped with 2 mm test
communication signals can also be trans‑ The actuators are connected to the out‑ sockets for signal control.
mitted bidirectionally. put terminals 1/2. Handheld terminals
IM35-11Ex-Hi
404 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM35-11EX-HI Indication
Ident no. 7506517 Operational readiness green
Interface technology
Ex ia IIC IIB
Lo [mH] 5 1 5 1
Co [µF] 0.135 0.285 1.1 1.8
Ex approval acc. to conformity certificate IBEXU 08 ATEX B020 X
Application area II 3 G
Protection type Ex nA [nL] IIC/IIB T4 X
Max. values: Terminal connection: 1+2
Max.output voltage Uo ≤ 15.9 V
Max. output current Io ≤ 59.5 mA
Max. output power Po ≤ 467 mW
Internal resistance Ri 528 Ω
Characteristic trapezoidal
Internal inductance/capacitance Li/Ci Li negligible, Ci = 5.2 nF
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Lo [mH] 5 1 5 1
Co [µF] 0.285 0.515 2.1 3.2
▪▪ ATEX, TR CU
▪▪ Installation in zone 2
▪▪ Intelligent actuators supplied via
HART® communication interface
▪▪ Input circuits: 0/4…20 mA
▪▪ Output circuits: 0/4…20 mA,
intrinsically-safe
▪▪ Universal operating voltage
▪▪ Complete galvanic isolation
The 2‑channel signal isolator IM35‑22EX- Typical applications are for example, the output and input terminals 16/17 and
HI is designed to transmit the normalized control of I/P converters (at control 11/12.
current signal galvanically isolated 1:1 valves for example) or indicators in the
from the non-Ex a rea to the Ex-area. Be‑ Ex-area. In addition, the removable terminal
sides the analog signals, digital HART® blocks are equipped with 2 mm test
communication signals can also be trans‑ The actuators are connected to the out‑ sockets for signal control.
mitted bidirectionally. put terminals 1/2 and 6/7. Handheld ter‑
minals [HHT] can be connected to the
406 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM35-22EX-HI Indication
Ident no. 7506518 Operational readiness green
Interface technology
Ex ia IIC IIB
Lo [mH] 5 1 5 1
Co [µF] 0.135 0.285 1.1 1.8
Ex approval acc. to conformity certificate IBEXU 08 ATEX B020 X
Application area II 3 G
Protection type Ex nA [nL] IIC/IIB T4 X
Max. values: Terminal connection: 1+2 / 6+7
Max.output voltage Uo ≤ 15.9 V
Max. output current Io ≤ 59.5 mA
Max. output power Po ≤ 467 mW
Internal resistance Ri 528 Ω
Characteristic trapezoidal
Internal inductance/capacitance Li/Ci Li negligible, Ci = 5.2 nF
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Lo [mH] 5 1 5 1
Co [µF] 0.285 0.515 2.1 3.2
▪▪ ATEX, TR CU
▪▪ Transmission of potentiometer signals
from the Ex area
▪▪ Potentiometer, nominal resistance:
0.8…20 kΩ
▪▪ Output circuit: 0…20 mA
▪▪ Complete galvanic isolation
The 1‑channel potentiometer amplifier 0 Ω and the nominal resistance value tiometers featuring a nominal resistance
IM36‑11EX-I/24VDC is designed to trans‑ (end value) of the potentiometer and of 1 kΩ or 10 kΩ can thus be u sed. The
mit signals from 3 or 5‑wire potentiome‑ converted into a linear value. admissible line resistance is maximally
ters galvanically isolated from the Ex area 50 Ω with a potentiometer r esistance of
to the non-Ex area and to converted A potentiometer is defined by its nomi‑ 800 Ω.
them into normalized 0…20 mA analog nal resistance. Any potentiometer can be
signals. The resistance value of the wiper connected, provided the nominal r esist‑
contact is collected in a range between ance is 800…200000 Ω. Common poten‑
408 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM36-11EX-I/24VDC
Ident no. 7509525
Power supply
Nominal voltage 24 VDC
Operating voltage range 19…29 VDC
Power consumption ≤ 2 W
Inputs
Input circuits potentiometer
Cable resistance ≤ 50 Ω
Voltage on resistor 5 VDC
Nominal resistance 0.8…20 kΩ
Outputs
Output current 0…20 mA
Response characteristic
Measuring accuracy ≤ 0.3 % of full scale
Indication
Operational readiness green
Interface technology
Environmental Conditions
Ambient temperature -25…+60 °C
Storage temperature -40…+80 °C
Test voltage 2.5 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 18 x 104 x 110 mm
▪▪ ATEX, TR CU
Rp 800...20000
▪▪ Transmission of potentiometer signals
from the Ex area
▪▪ Potentiometer, nominal resistance:
4
7+
1 0...10 V
RL 1 k 0.8…20 kΩ
8
2 ▪▪ Output circuit: 0…10 V
▪▪ Complete galvanic isolation
0...Rp 8,2 M
5V 11 +
3
Pwr Power
12
6 GN
The 1‑channel potentiometer amplifier 0 Ω and the nominal resistance value tiometers featuring a nominal resistance
IM36-11EX-U/24VDC is designed to (end value) of the potentiometer and of 1 kΩ or 10 kΩ can thus be u sed. The
transmit signals from 3 or 5‑wire p otenti‑ converted into a linear value. admissible line resistance is maximally
ometers galvanically isolated from the Ex 50 Ω with a potentiometer resistance of
area to the non-Ex area and to converted A potentiometer is defined by its nomi‑ 800 Ω.
them into normalized 0…10 V analog nal resistance. Any potentiometer can be
signals. The resistance value of the wiper connected, provided the nominal r esist‑
contact is collected in a range between ance is 800…200000 Ω. Common poten‑
410 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM36-11EX-U/24VDC
Ident no. 7509526
Power supply
Nominal voltage 24 VDC
Operating voltage range 19…29 VDC
Power consumption ≤ 2 W
Inputs
Input circuits potentiometer
Cable resistance ≤ 50 Ω
Voltage on resistor 5 VDC
Nominal resistance 0.8…20 kΩ
Outputs
Output voltage 0…10 V
Response characteristic
Measuring accuracy ≤ 0.3 % of full scale
Indication
Operational readiness green
Interface technology
Environmental Conditions
Ambient temperature -25…+60 °C
Storage temperature -40…+80 °C
Test voltage 2.5 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 18 x 104 x 110 mm
5
15
DZ/LZ
▪▪ Potentiometer, nominal resistance:
0.8…100 kΩ
6
11 + ▪▪ Output circuit: 0/4…20 mA
7
0/4...20 mA
2 (source) ▪▪ Complete galvanic isolation
12 – RL ≤ 500 Ω
2 8
0…Rp 10 MΩ
UB = 5 V 19
9 20…250 VAC eff
Pwr 20…125 VDC
20 ≤ 2,2 W
10 GN
The 2‑channel potentiometer amplifier (end value) of the potentiometer and 50 Ω with a potentiometer resistance of
IM36-22EX-U is designed to transmit s ig‑ converted into a linear value. 800 Ω.
nals from 3 or 5‑wire potentiometers g al‑
vanically isolated from the Ex area to the A potentiometer is defined by its nomi‑ The incremental potentiometer‘s start
non-Ex area and to convert them into nal resistance. Any potentiometer can be and end point can be adjusted separately
normalized 0…20 mA analog signals. connected, provided the nominal r esist‑ for each channel. This is n
ecessary to pro‑
Live-zero operation is activated for both ance is 800…100000 Ω. Common poten‑ tect the incremental potentiometer from
channels through bridging terminals 14 tiometers featuring a nominal resistance damage which can be caused by critical
and 15. The resistance value of the wiper of 1 kΩ or 10 kΩ can thus be u sed. The rotation angles smaller than 5 % and
contact is collected in a range between admissible line resistance is maximally greater than 95 % of the absolute rota‑
0 Ω and the nominal resistance value tional torque.
16 17 18 19 20
11 12 13 14 15
Power Pwr
1 2
End
Start
IM36-22Ex-i
6 7 8 9 10
1 2 3 4 5
412 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM36-22EX-I Environmental Conditions
Ident no. 7509528 Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Power supply Test voltage 2.5 kV
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC Mechanical data
Operating voltage range 20…250 VAC Tightening torque 0.5 Nm
Frequency 40…70 Hz Electrical connection 4 x 5‑pin removable terminal blocks,
Power consumption ≤ 2.2 W reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Inputs
Housing material Polycarbonate/ABS
Input circuits potentiometer
Mounting instruction for DIN rail / panel
Cable resistance ≤ 50 Ω
Protection class IP20
Voltage on resistor 5 VDC
Flammability class acc. to UL 94 V-0
Nominal resistance 0.8…100 kΩ
Dimensions 27 x 104 x 110 mm
Outputs
Approval | Certification ATEX, IECEx, TR CU
Output current 0/4…20 mA
Response characteristic
Rise time (10-90%) ≤ 35 ms
Dropout time (90…10%) ≤ 40 ms
Interface technology
Ex approval acc. to conformity certificate TÜV 12 ATEX 093479 X
Application area II 3 G
Protection type Ex nA nC [ic Gc] IIC T4 Gc
Max. values: Terminal connection: 1…5 / 6…10
Max.output voltage Uo ≤ 14.1 V
Max. output current Io ≤ 40.6 mA
Max. output power Po ≤ 143 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 87 µH; Ci = 15 nF
External inductance/capacitance Lo/Co
Ex ic IIC IIB
Lo [mH] 1 5 10 1 5 10
Co [nF] 735 515 445 4300 3000 2700
Indication
Operational readiness green
5
▪▪ Potentiometer, nominal resistance:
0.8…100 kΩ
6
11 + ▪▪ Output circuit: 0…10 V
7 2 0…10 V
RL ≥ 1 kΩ
▪▪ Complete galvanic isolation
12 –
2 8
0…Rp 10 MΩ
UB = 5 V 19
9 20…250 VAC eff
Pwr 20…125 VDC
20 ≤ 2,2 W
10 GN
The 2‑channel potentiometer amplifier A potentiometer is defined by its nomi‑ for each channel. This is n
ecessary to pro‑
IM36-22EX-U is designed to transmit s ig‑ nal resistance. Any potentiometer can be tect the incremental potentiometer from
nals from 3 or 5‑wire potentiometers g al‑ connected, provided the nominal r esist‑ damage which can be caused by critical
vanically isolated from the Ex area to the ance is 800…100000 Ω. Common poten‑ rotation angles smaller than 5 % and
non-Ex area and to convert them into tiometers featuring a nominal resistance greater than 95 % o f the absolute rota‑
normalized 0…10 V analog signals. The of 1 kΩ or 10 kΩ can thus be u sed. The tional torque.
resistance value of the wiper contact is admissible line resistance is maximally
collected in a range between 0 Ω and the 50 Ω with a potentiometer r esistance of
nominal resistance value (end value) of 800 Ω.
the potentiometer and c onverted into a
linear value. The incremental potentiometer‘s start
and end point can be adjusted separately
16 17 18 19 20
11 12 13 14 15
Power Pwr
1 2
End
Start
IM36-22Ex-U
6 7 8 9 10
1 2 3 4 5
414 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM36-22EX-U Environmental Conditions
Ident no. 7509530 Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Power supply Test voltage 2.5 kV
Nominal voltage Universal voltage supply unit
Operating voltage range 20…125 VDC Mechanical data
Operating voltage range 20…250 VAC Tightening torque 0.5 Nm
Frequency 40…70 Hz Electrical connection 4 x 5‑pin removable terminal blocks,
Power consumption ≤ 2.2 W reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Inputs
Housing material Polycarbonate/ABS
Input circuits potentiometer
Mounting instruction for DIN rail / panel
Cable resistance ≤ 50 Ω
Protection class IP20
Voltage on resistor 5 VDC
Flammability class acc. to UL 94 V-0
Nominal resistance 0.8…100 kΩ
Dimensions 27 x 104 x 110 mm
Outputs
Approval | Certification ATEX, IECEx, TR CU
Output voltage 0…10 V
Response characteristic
Rise time (10-90%) ≤ 35 ms
Dropout time (90…10%) ≤ 40 ms
Interface technology
Ex approval acc. to conformity certificate TÜV 12 ATEX 093479 X
Application area II 3 G
Protection type Ex nA nC [ic Gc] IIC T4 Gc
Max. values: Terminal connection: 1…5 / 6…10
Max.output voltage Uo ≤ 14.1 V
Max. output current Io ≤ 40.6 mA
Max. output power Po ≤ 143 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 87 µH; Ci = 15 nF
External inductance/capacitance Lo/Co
Ex ic IIC IIB
Lo [mH] 1 5 10 1 5 10
Co [nF] 735 515 445 4300 3000 2700
Indication
Operational readiness green
▪▪ CFMUS, TR CU
▪▪ Monitors 3 limit values at a current or
voltage input
▪▪ Power supply of 2‑wire or 3‑wire trans‑
mitters/sensors
▪▪ Input circuit: 0/4…20 mA; 0/2…10 V
▪▪ Output circuit: 0/4…20 mA, 3 inde‑
pendent limit value relays
▪▪ Limit value relay adjusted via TEACH
button
▪▪ Relay outputs adjusted via buttons on
the front
▪▪ Universal operating voltage
▪▪ Complete galvanic isolation
The IM43‑14‑SRI 1‑channel trip amplifier The measured values are transmitted via Live-zero signals are converted into
monitors 0/4…20 mA currents o r a galvanically isolated analog output to dead-zero through bridging terminals
0/2…10 V voltages according to over/ other devices. 5/9. In live-zero mode the range between
underrange of limit values. 4…20 mA is monitored. Any state out‑
The green LED indicates operational side this range (< 3.6 mA or > 24 mA) is
The three limit values are set via teach readiness. Three yellow LEDs indicate signalled with an error message. In this
buttons at the front. the switching status of the correspond‑ case the power LED will illuminate red,
ing output. the relays drop off and a fault current of
Additionally 18 V (at max. 35 mA) are p
ro‑ > 22 mA is output. If a faulty transmitter
vided for transmitters or sensors. The output mode is adjusted via bridges causes a short circuit, the relays drop off
at the terminals 5 to 8. and a fault current of > 22 mA is output.
416 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM43-14-SRI Protection class IP20
Ident no. 7540043 Flammability class acc. to UL 94 V-0
Dimensions 27 x 104 x 110 mm
Power supply
Nominal voltage Universal voltage supply unit Approval | Certification cFMus, TR CU
Operating voltage range 20…250 VDC
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Power consumption ≤ 5 W
Inputs
Supply voltage ï 17 V / 20 mA
Current 35 mA
Voltage input 0/2…10 VDC
Input resistance (voltage) ï 50 kΩ
Current input 0/4…20 mA
Input resistance (current) ≤ 50 Ω
Outputs
Load resistance, current output ≤ 0.6 kΩ
Output current 0/4…20 mA
Output circuits (digital) 3 x relays (NO)
Switching frequency ≤ 10 Hz
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 6 A
Switching capacity per output ≤ 1500 VA
Contact quality AgNi, 3µ Au
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.00075 % / K
Indication
Operational readiness green
Switching state yellow
Error indication red
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 5‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
▪▪ CFMUS, TR CU
▪▪ Monitors 3 limit values at a current or
voltage input
▪▪ Power supply of 2‑wire or 3‑wire trans‑
mitters/sensors
▪▪ Input circuit: 0/4…20 mA; 0/2…10 V
▪▪ Output circuit: 0/4…20 mA, 3 inde‑
pendent limit value relays
▪▪ Limit value relay adjusted via rotary
coding switches
▪▪ Hysteresis and relay outputs adjusted
via DIP switch
▪▪ Universal operating voltage
▪▪ Complete galvanic isolation
The IM43‑14‑RI 1‑channel trip amplifier The green LED indicates operational case the power LED will illuminate red,
monitors 0/4…20 mA currents o r readiness. Three yellow LEDs indicate the relays drop off and a fault current is
0/2…10 V voltages according to over/ the switching status of the correspond‑ output. If a faulty transmitter causes a
underrange of limit values. ing output. short circuit, the relays drop off and a
fault current is also o
utput. The fault cur‑
The three limit values are set via the lat‑ The output mode of the relays and the rent can be 0 mA or > 22 mA, depending
eral rotary coding switches. hysteresis are set via DIP switches. on the DIP switch activated.
418 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM43-14-RI Approval | Certification cFMus, TR CU
Ident no. 7540042
Power supply
Nominal voltage Universal voltage supply unit
Operating voltage range 20…250 VDC
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Power consumption ≤ 5 W
Inputs
Supply voltage ï 17 V / 20 mA
Current 35 mA
Voltage input 0/2…10 VDC
Input resistance (voltage) ï 50 kΩ
Current input 0/4…20 mA
Input resistance (current) ≤ 50 Ω
Outputs
Load resistance, current output ≤ 0.6 kΩ
Output current 0/4…20 mA
Output circuits (digital) 3 x relays (NO)
Switching frequency ≤ 10 Hz
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 6 A
Switching capacity per output ≤ 1500 VA
Contact quality AgNi, 3µ Au
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.00075 % / K
Indication
Operational readiness green
Switching state yellow
Error indication red
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 5‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 27 x 104 x 110 mm
▪▪ CFMUS, TR CU
▪▪ Monitors 3 limit values at a current or
voltage input
▪▪ Power supply of 2‑wire or 3‑wire trans‑
mitters/sensors
▪▪ Input circuit: 0/4…20 mA; 0/2…10 V
▪▪ Output circuit: 3 independent limit
value relays
▪▪ Limit value relay adjusted via Teach
button
▪▪ Relay outputs adjusted via buttons on
the front
▪▪ Universal operating voltage
▪▪ Complete galvanic isolation
The IM43‑13‑SR 1‑channel trip amplifier Additionally, 18 V (with max. 35 mA) are The output mode is adjusted via bridges
monitors 0/4…20 mA currents o r provided for transmitters or sensors. at the terminals 5 to 8.
0/2…10 V voltages according to over/
underrange of limit values. The green LED indicates operational
readiness. Three yellow LEDs indicate
The three limit values are set via teach the switching status of the correspond‑
buttons at the front. ing output.
420 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM43-13-SR
Ident no. 7540041
Power supply
Nominal voltage Universal voltage supply unit
Operating voltage range 20…250 VDC
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Power consumption ≤ 5 W
Inputs
Supply voltage ï 17 V / 20 mA
Current 35 mA
Voltage input 0/2…10 VDC
Input resistance (voltage) ï 50 kΩ
Current input 0/4…20 mA
Input resistance (current) ≤ 50 Ω
Outputs
Output circuits (digital) 3 x relays (NO)
Switching frequency ≤ 10 Hz
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 6 A
Switching capacity per output ≤ 1500 VA
Contact quality AgNi, 3µ Au
Response characteristic
Reference temperature 23 °C
Temperature drift ≤ 0.00075 % / K
Indication
Operational readiness green
Switching state yellow
Error indication red
Environmental Conditions
Ambient temperature -25…+70 °C
Interface technology
Storage temperature -40…+80 °C
Test voltage 2.5 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 5‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 27 x 104 x 110 mm
▪▪ CFMUS, TR CU
▪▪ Monitors 3 limit values at a current or
voltage input
▪▪ Power supply of 2‑wire or 3‑wire trans‑
mitters/sensors
▪▪ Input circuit: 0/4…20 mA; 0/2…10 V
▪▪ Output circuit: 3 independent limit
value relays
▪▪ Limit value relay adjusted via rotary
coding switches
▪▪ Hysteresis and relay outputs adjusted
via DIP switch
▪▪ Universal operating voltage
▪▪ Complete galvanic isolation
The IM43‑13‑R 1‑channel trip amplifier Additionally, 18 V (with max. 35 mA) are The output mode of the relays and the
monitors 0/4…20 mA currents o r provided for transmitters or sensors. hysteresis are set via DIP switches.
0/2…10 V voltages according to over/
underrange of limit values. The green LED indicates operational
readiness. Three yellow LEDs indicate
The three limit values are set via the lat‑ the switching status of the correspond‑
eral rotary coding switches. ing output.
422 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM43-13-R
Ident no. 7540040
Power supply
Nominal voltage Universal voltage supply unit
Operating voltage range 20…250 VDC
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Power consumption ≤ 5 W
Inputs
Supply voltage ï 17 V / 20 mA
Current 35 mA
Voltage input 0/2…10 VDC
Input resistance (voltage) ï 50 kΩ
Current input 0/4…20 mA
Input resistance (current) ≤ 50 Ω
Outputs
Output circuits (digital) 3 x relays (NO)
Switching frequency ≤ 10 Hz
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 6 A
Switching capacity per output ≤ 1500 VA
Contact quality AgNi, 3µ Au
Response characteristic
Reference temperature 23 °C
Temperature drift ≤ 0.00075 % / K
Indication
Operational readiness green
Switching state yellow
Error indication red
Environmental Conditions
Ambient temperature -25…+70 °C
Interface technology
Storage temperature -40…+80 °C
Test voltage 2.5 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 5‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 27 x 104 x 110 mm
▪▪ TR CU
▪▪ Input circuit: 0/4…20 mA; 0/2…10 V
▪▪ Output circuit: 0/4…20 mA, 3 inde‑
pendent limit value relays
▪▪ Universal operating voltage
▪▪ Monitors over and underrange of limit
values and window limits
▪▪ Connection of passive 2‑wire and ac‑
tive 3‑wire transmitters
▪▪ Parametrized via PC (FDT/DTM), front-
panel switch and HART®
▪▪ Many diagnostic functions
▪▪ Ring buffer for up to 8000 measured
values
▪▪ Display
▪▪ Complete galvanic isolation
The 1‑channel trip amplifier IM43-14- yellow LEDs indicate the switching status that, the stored signal sequence can be
CDRI is designed to operate 2‑wire trans‑ of the individual channels. read out.
ducers (III) and to galvanically isolate and
transmit the measured signals. Alterna‑ At each of the three outputs a predefined The device can be parametrized and con‑
tively, active 2‑wire transmitters (II) and setpoint value can be monitored accord‑ figured via PC (FDT/DTM). For this, con‑
passive 3‑wire transmitters (I) can also be ing to overshoot/ undershoot. The nect the device to the PC via the 3.5 mm
operated. switching hysteresis is d efined by pro‑ jack on the front (the matching transmis‑
gramming the switch-on and switch-off sion cable IM-PROG III can be o rdered
The three limit values are set via teach point. Furthermore, a switch-off delay separately from TURCK). A basic s cope of
buttons at the front. can be set individually for each output. parameters can be set via b uttons and
display on the front or remotely via the
The device features one output for The measured value is permanently writ‑ current interface and HART®.
analog signals 0/4…20 mA and three ten to a ring buffer with space for 8000
outputs for limit value relays. The unit of values. The writing process is stopped
the measured value is freely selectable with a predefined trigger event, like for
and indicated on a 2‑line display. A green example “excess of limit value“. A fter
LED indicates operational readiness, 3
424 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM43-14-CDRI
Ident no. 7540045
Power supply
Nominal voltage Universal voltage supply unit
Operating voltage range 20…250 VDC
Operating voltage range 20…250 VAC
Frequency 40…70 Hz
Power consumption ≤ 3 W
Residual ripple ≤ 10 mVss
Inputs
Supply voltage ï 17 V / 20 mA
Current 25 mA
Voltage input 0/2…10 VDC
Current input 0/4…20 mA
Outputs
Output current 0/4…20 mA
Output circuits (digital) 3 x relays (NO)
Switching frequency ≤ 10 Hz
Relay switching voltage ≤ 250 VAC/120 VDC
Switching current per output ≤ 2 A
Switching capacity per output ≤ 500 VA/60 W
Fault current 0 / 22 mA adjustable
Contact quality AgNi, 3µ Au
Response characteristic
Measuring accuracy ≤ 0.05 % of full scale
Reference temperature 23 °C
Temperature drift analogue output 0.0025 %/K
Indication
Operational readiness green
Switching state yellow
Error indication red
Interface technology
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Test voltage 2.5 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 5‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 27 x 104 x 110 mm
Approval | Certification TR CU
The 1‑channel solonoid driverpotentially explosive atmospheresvoltage and are adapted to the valves of
IM72‑11EX/L provides intrinsically safe caused by dust or gas, provided they different manufacturers (see output
limited power at the output. This enables comply with the applicable regulations. curve on next page).
them to be used directly for supplying
loads in the Ex area. Typical applications are the control of Exi The loads are actuated by applying the
pilot valves as well as the supply of d is‑ operating voltage.
Within the area of applicability of the E u‑ plays and transmitters. The output v alues
ropean directive 94/9/EC (ATEX) it is per‑ of the two connections U1 and U2 per A yellow LED indicates the switching
mitted to operate connected loads in channel differ in terms of their n o-load state of the associated output.
IM72-11Ex/L
426 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM72-11EX/L Application area II 3 G
Ident no. 7520703 Protection type Ex nA [nL] IIC/IIB T4
Max. values: Terminal connection: 1+3
Power supply Max.output voltage Uo ≤ 27 V
Nominal voltage 24 VDC loop-powered Max. output current Io ≤ 96 mA
Power consumption ≤ 1.5 W Max. output power Po ≤ 678 mW
Characteristic trapezoidal
Inputs Internal inductance/capacitance Li/Ci negligibly small
0-signal 0…5 VDC External inductance/capacitance Lo/Co
1-signal 19…30 VDC Ex nL IIC IIB
Voltage input max. 30 VDC Lo [mH] 0.68 0.5 13 2
Current input 45 mA Co [nF] 120 130 570 620
Input delay ≤ 2 ms
Max. values: Terminal connection: 2+3
Max.output voltage Uo ≤ 17.6 V
Outputs
Max. output current Io ≤ 96 mA
Output circuits intrinsically safe acc. to EN 60079
Max. output power Po ≤ 678 mW
Output current 40 mA
Characteristic trapezoidal
Output voltage U1=24 V
Internal inductance/capacitance Li/Ci negligibly small
Output voltage U2=15 V
External inductance/capacitance Lo/Co
Output curve
Ex nL IIC IIB
Lo [mH] 1.2 0.5 13 2.0
Co [µF] 0.37 0.42 1 2.1
Declaration SIL 3 acc. to EXIDA FMEDA
Indication
Response characteristic
Switching state yellow
Limit frequency ≤ 500 Hz
Environmental Conditions
Approvals and declarations
Ambient temperature -25…+70 °C
Ex approval acc. to conformity certificate TÜV 05 ATEX 2846 X
Storage temperature -40…+80 °C
Device designation É II (1) GD [EEx ia] IIC
Test voltage 2.5 kV
Max. values: Terminal connection: 1+3
Max. output voltage Uo ≤ 27 V
Mechanical data
Max. output current Io ≤ 96 mA
Tightening torque 0.5 Nm
Max. output power Po ≤ 678 mW
Electrical connection 4 x 3‑pin removable terminal blocks,
Rated voltage 250 V
reverse polarity protected, screw
Interface technology
Characteristic Trapezoidal connection
Internal inductance/capacitance Li/Ci negligibly small Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
External inductance/capacitance Lo/Co Housing material Polycarbonate/ABS
EEx ia IIC IIB Mounting instruction for DIN rail / panel
Lo [mH] 0.68 0.5 13 2 Protection class IP20
Co [nF] 62 70 260 300 Flammability class acc. to UL 94 V-0
Max. values: Terminal connection: 2+3 Dimensions 18 x 104 x 110 mm
Max. output voltage Uo ≤ 17.6 V
Max. output current Io ≤ 96 mA Approval | Certification ATEX, IECEx, UL, cFMus, TR CU, NEPSI,
INMETRO
Max. output power Po ≤ 678 mW
Characteristic trapezoidal
Internal inductance/capacitance Li/Ci negligibly small
External inductance/capacitance Lo/Co
EEx ia IIC IIB
Lo [mH] 1.2 0.5 13.0 2.0
Co [µF] 0.13 0.15 0.47 1.1
Ex approval acc. to conformity certificate TÜV 06 ATEX 553388 X
–3
YE 12 –
▪▪ Voltage outuput 15 VDC resp. 24 VDC
24 V (U1) 19...30 VDC ▪▪ Output current ≤ 40 mA
15 V (U2)
U1
<3W
▪▪ Switching frequency ≤ 500 Hz
+4
8+ ▪▪ SIL3
▪▪ Removable terminal blocks
U2 2
2 +5 2
YE 9–
–6
▪▪ Galvanic isolation between input and
output circuits
The 1‑channel solonoid driver IM72‑ potentially explosive atmospheresvoltage and are adapted to the valves of
22EX/L provides intrinsically safe limited caused by dust or gas, provided they different manufacturers (see output
power at the output. This enables them comply with the applicable regulations. curve on next page).
to be used directly for supplying loads in
the Ex area. Typical applications are the control of Exi The loads are actuated by applying the
pilot valves as well as the supply of d is‑ operating voltage.
Within the area of applicability of the E u‑ plays and transmitters. The output v alues
ropean directive 94/9/EC (ATEX) it is per‑ of the two connections U1 and U2 per A yellow LED indicates the switching
mitted to operate connected loads in channel differ in terms of their n o-load state of the associated output.
428 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM72-22EX/L Application area II 3 G
Ident no. 7520702 Protection type Ex nA [nL] IIC/IIB T4
Max. values: Terminal connection: 1+3 / 4+6
Power supply Max.output voltage Uo ≤ 27 V
Nominal voltage 24 VDC loop-powered Max. output current Io ≤ 96 mA
Power consumption ≤ 2.2 W Max. output power Po ≤ 678 mW
Characteristic trapezoidal
Inputs Internal inductance/capacitance Li/Ci negligibly small
0-signal 0…5 VDC External inductance/capacitance Lo/Co
1-signal 19…30 VDC Ex nL IIC IIB
Voltage input max. 30 VDC Lo [mH] 0.68 0.5 13 2
Current input 45 mA Co [nF] 120 130 570 620
Input delay ≤ 2 ms
Max. values: Terminal connection: 2+3 / 5+6
Max.output voltage Uo ≤ 17.6 V
Outputs
Max. output current Io ≤ 96 mA
Output circuits intrinsically safe acc. to EN 60079
Max. output power Po ≤ 678 mW
Output current 40 mA
Characteristic trapezoidal
Output voltage U1=24 V
Internal inductance/capacitance Li/Ci negligibly small
Output voltage U2=15 V
External inductance/capacitance Lo/Co
Output curve
Ex nL IIC IIB
Lo [mH] 1.2 0.5 13 2.0
Co [µF] 0.37 0.42 1 2.1
Declaration SIL 3 acc. to EXIDA FMEDA
Indication
Response characteristic
Switching state yellow
Limit frequency ≤ 500 Hz
Environmental Conditions
Approvals and declarations
Ambient temperature -25…+70 °C
Ex approval acc. to conformity certificate TÜV 05 ATEX 2846 X
Storage temperature -40…+80 °C
Device designation É II (1) GD [EEx ia] IIC
Test voltage 2.5 kV
Max. values: Terminal connection: 1+3 / 4+6
Max. output voltage Uo ≤ 27 V
Mechanical data
Max. output current Io ≤ 96 mA
Tightening torque 0.5 Nm
Max. output power Po ≤ 678 mW
Electrical connection 4 x 3‑pin removable terminal blocks,
Rated voltage 250 V
reverse polarity protected, screw
Interface technology
Characteristic Trapezoidal connection
Internal inductance/capacitance Li/Ci negligibly small Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
External inductance/capacitance Lo/Co Housing material Polycarbonate/ABS
EEx ia IIC IIB Mounting instruction for DIN rail / panel
Lo [mH] 0.68 0.5 13 2 Protection class IP20
Co [nF] 62 70 260 300 Flammability class acc. to UL 94 V-0
Max. values: Terminal connection: 2+3 / 5+6 Dimensions 18 x 104 x 110 mm
Max. output voltage Uo ≤ 17.6 V
Max. output current Io ≤ 96 mA Approval | Certification ATEX, IECEx, UL, cFMus, TR CU, NEPSI,
INMETRO
Max. output power Po ≤ 678 mW
Characteristic trapezoidal
Internal inductance/capacitance Li/Ci negligibly small
External inductance/capacitance Lo/Co
EEx ia IIC IIB
Lo [mH] 1.2 0.5 13.0 2.0
Co [µF] 0.13 0.15 0.47 1.1
Ex approval acc. to conformity certificate TÜV 06 ATEX 553388 X
▪▪ TR CU
▪▪ Output circuit: 2 relays each with 1
changeover contact
250 VAC / 5 A
24 ▪▪ 5 A switching current at 250 VAC
22
▪▪ Operating voltage 184…276 VDC
SIL 3
21 A1 184...276 VAC
▪▪ SIL3
▪▪ Galvanic isolation between input cir‑
14 +
250 VAC / 5 A YE
12
11
A2 ≤ 15 mA cuits and output circuits
The IM73‑12‑R/230VAC 1‑channel relay If applied in SIL-3 circuits, the following ▪▪ The contact circuit is equipped with a
coupler is particularly suitable for use as conditions have to be observed: fuse and is activated at 60 % nominal
a coupling module for the safe galvanic ▪▪ If the output relay triggers a contactor current.
isolation of binary signals. 2 s ynchronous directly, the contactor must be
controlled relays, each with 1 changeo‑ equipped with a protective circuitry at The status of the relay is indicated via
ver contact are provided at the output. the coil connection. LED on the front.
▪▪ Both relays have to be connected in
series.
Factor
nom.
10
5
AC
2 resistive
load
1
0,5
DC
0,2 resistive
load
0,1
10 20 50 100 200 500 [V]
430 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM73-12-R/230VAC
Ident no. 7520511
Power supply
Nominal voltage 230 VAC
Operating voltage range 184…276 VAC
Frequency 48…62 Hz
Power consumption ≤ 3.5 VA
Inputs
Current input 15 mA
Outputs
Output circuits (digital) 2 x relay (change-over)
Switching frequency ≤ 5 Hz
Relay switching voltage ≤ 250 VAC
Switching current per output ≤ 5 A
Switching capacity per output ≤ 2000 VA/180 W
Contact quality AgNi, 3µ Au
Indication
Switching state yellow
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Test voltage 2.5 kV
MTTF 947 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Tightening torque 0.5 Nm
Electrical connection 4 x 3‑pin removable terminal blocks,
reverse polarity protected, screw
Interface technology
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 18 x 104 x 110 mm
Approval | Certification TR CU
▪▪ TR CU
▪▪ Output circuit: 2 relays each with 1
changeover contact
250 VAC / 5 A
24 ▪▪ 5 A switching current at 250 VAC
22 ▪▪ Operating voltage 19…29 VDC
SIL 3
21 A1 19...29 VUC
▪▪ Removable terminal blocks
▪▪ SIL3
14 +
250 VAC / 5 A YE
12
11
A2 ≤ 25 mA ▪▪ Galvanic isolation between input cir‑
cuits and output circuits
The IM73‑12‑R/24VUC 1‑channel relay If applied in SIL-3 circuits, the following ▪▪ The contact circuit is equipped with a
coupler is particularly suitable for use as conditions have to be observed: fuse and is activated at 60 % nominal
a coupling module for the safe galvanic ▪▪ If the output relay triggers a contactor current.
isolation of binary signals. 2 s ynchronous directly, the contactor must be
controlled relays, each with 1 changeo‑ equipped with a protective circuitry at The status of the relay is indicated via
ver contact are provided at the output. the coil connection. LED on the front.
▪▪ Both relays have to be connected in
series.
Load curve
Factor
nom.
10
5
AC
2 resistive
load
1
0,5
DC
0,2 resistive
load
0,1
10 20 50 100 200 500 [V]
432 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM73-12-R/24VUC
Ident no. 7520712
Power supply
Nominal voltage 24 VUC
Operating voltage range 19…29 VDC
Operating voltage range 19…29 VAC
Frequency 48…62 Hz
Power consumption ≤ 0.6 VA
Inputs
Voltage input 19…29 VAC/ VDC
Current input 25 mA
Outputs
Output circuits (digital) 2 x relay (change-over)
Switching frequency ≤ 5 Hz
Relay switching voltage ≤ 250 VAC
Switching current per output ≤ 5 A
Switching capacity per output ≤ 2000 VA/180 W
Contact quality AgNi, 3µ Au
Indication
Switching state yellow
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Test voltage 2.5 kV
MTTF 963 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Tightening torque 0.5 Nm
Interface technology
Electrical connection 4 x 3‑pin removable terminal blocks,
reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail / panel
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 18 x 104 x 110 mm
Approval | Certification TR CU
▪▪ ATEX, TR CU
▪▪ Installation in zone 2
▪▪ Relay coupler for switching of intrinsi‑
cally safe and current limited circuits
▪▪ High-quality reed relays with rhodium
contacts
▪▪ Switching frequency up to 50 Hz
▪▪ Galvanic isolation between input and
output circuits
The 2‑channel relay coupler IM73‑22Ex- LEDs on the front indicate the switching The reed relay with Rhodium contacts
R/24VUC is used for the switching of in‑ status. are also suitable for general control t asks,
trinsically safe circuits and for g
alvani‑ especially if normal relays reach their lim‑
cally isolating contact and control With 50 Hz the switching frequency of its in terms of switching frequency and
circuitry according to EN 60079‑11. the reed relay is significantly higher than the permissible contact data.
that of standard relays.
IM73-22Ex-R
24VUC
434 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM73-22Ex-R/24VUC Electrical connection 4 x 3‑pin removable terminal blocks,
Ident no. 7520513 reverse polarity protected, screw
connection
Terminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Power supply
Housing material Polycarbonate/ABS
Nominal voltage 24 VUC
Mounting instruction for DIN rail / panel
Operating voltage range 10…30 VDC
Protection class IP20
Operating voltage range 10…30 VAC
Flammability class acc. to UL 94 V-0
Frequency 48…62 Hz
Dimensions 18 x 104 x 110 mm
Inputs
Approval | Certification ATEX, TR CU
Voltage input 10…30 VAC/ VDC
Current input 30 mA
Outputs
Output circuits (digital) 2 x relay (change-over)
Relay switching voltage ≤ 28 VDC
Switching current per output ≤ 240 mA
Switching capacity per output ≤ 7 W
Contact quality AgNi, 3µ Au
Response characteristic
Limit frequency ≤ 50 Hz
Interface technology
Max. input voltage Ui ≤ 28 V
Max. input current Ii ≤ 240 mA
Max. input power Pi ≤ 7000 mW
Internal inductance/capacitance Li/Ci negligibly small
Indication
Switching state yellow
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Test voltage 1.5 kV
Mechanical data
Tightening torque 0.5 Nm
Power supply
Features
The IM82‑24‑2.5 power supply units are The power supply provides 24 VDC out‑ tra-low voltage (
SELV) according to
designed for DC loads, particularly the put voltage and 2.5 A output current. The EN 60950.
switching and monitoring devices of the output voltage is adjusted in a range be‑
TURCK IM, IME, IMS and IMC interface tween 24…28 VDC with the potentiom‑ The power supply can be set to single or
module series. eter Vout. The device provides safety ex‑ parallel operating mode (with d ecou‑
pling diode).
Pout [%]
100
75
0
-25 60 70 [°C]
Parallel operation
– VO
+ VO
Rdy Rdy
54321 54321
678 678
NL NL
436 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM82-24-2,5
Ident no. 7545041
Power supply
Nominal voltage Universal voltage supply unit
Operating voltage range 90…370 VDC
Operating voltage range 85…264 VAC
Frequency 47…63 Hz
Power consumption ≤ 83 VA
Efficiency 89 %
Internal fuse T 2 A / 250 VAC
inrush current Ui = 115 VAC, 20 A; Ui = 230 VAC, 40
A
Mains buffering Ui = 115 VAC, 20 ms; Ui = 230 VAC,
30 ms
Outputs
Nominal output voltage 24 V
Nominal current 2.5 A
Output circuits (digital) 1 x transistor (potential-free, short-
circuit proof), > 18.8…19.6 V
Switching voltage ≤ 24 VDC
Switching current per output ≤ 35 mA
Surge limiting 125‑138 %
Overload protection 110‑150 %
Parallel mode yes, via diods
Pollution degree 2
Surge category II
Short-circuit behaviour Hiccup mode
Response characteristic
Limit frequency ≤ 80000 Hz
Indication
Operational readiness green
Environmental Conditions
Ambient temperature -25…+70 °C
Interface technology
Storage temperature -25…+85 °C
Relative humidity ≤ 95 %
Derating -2.5%/°C from 60 °C
Test voltage 3.0 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection screw terminals
Terminal cross-section 0.2 … 2.0 mm2
Housing material plastic
Mounting instruction for DIN rail
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 40.5 x 90 x 114 mm
Power supply
Features
▪▪ UL Class 1, Div 2
▪▪ Safety extra-low voltage SELV IEC/
EN 60950
▪▪ SEMI-F47
Rdy DC ON /– N
90 ... 132 VAC
180 ... 264 VAC
▪▪ Output voltage adjustable
+ GN
/+ L
210 ... 370 VDC 22.5…28.5 VDC
22,5 ... 28,5 VDC +
5A
DC LOW
▪▪ Nominal current 5 A
(max. 120 W) – RD
▪▪ Single/parallel operating mode
▪▪ Surge protection
–
▪▪ Removable terminals
▪▪ Mains buffering up to 30 ms
▪▪ Power-good relay
The IM82‑24‑5.0 power supply units are The power supply provides 24 VDC out‑ extra-low
voltage (SELV) according to
designed for DC loads, particularly the put voltage and 5.0 A output current. The EN 60950.
switching and monitoring devices of the output voltage is adjusted in a range be‑
TURCK IM, IME, IMS and IMC interface tween 22.5…28.5 VDC with t he potenti‑ The power supply can be set to single or
module series. ometer Vout. T he device provides safety parallel operating mode.
Derating Short-circuit behaviour
Pout [%]
100
75
0
-25 60 70 [°C]
Parallel operation
– VO
+ VO
Rdy Rdy
654321 654321
789 789
LN LN
438 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM82-24-5,0 Protection class IP20
Ident no. 7545042 Flammability class acc. to UL 94 V-0
Dimensions 64 x 143.5 x 116.6 mm
Power supply
Nominal voltage Universal voltage supply unit Approval | Certification cULus
Operating voltage range 210…370 VDC
Operating voltage range 90…132 VAC
Operating voltage range 186…264 VAC
Frequency 47…73 Hz
Power consumption ≤ 145 VA
PFC 0.7
Efficiency 86 %
Internal fuse T 3.15 A / 250 VAC
inrush current Ui = 115 VAC, 24 A; Ui = 230 VAC, 48
A
Mains buffering Ui = 115 VAC, 25 ms; Ui = 230 VAC,
30 ms
Outputs
Nominal output voltage 24 V
Nominal current 5 A
Output circuits (digital) relay (NO), > 17.6 … 19.4 V
Relay switching voltage ≤ 60 VDC
Switching current per output ≤ 300 mA
Surge limiting 125‑145 %
Overload protection 105‑145 %
Parallel mode yes, switchover initiated by a switch,
max. 3 devices each with 90 % load
current
Pollution degree 2
Surge category II
Short-circuit behaviour Current limiting
Response characteristic
Limit frequency ≤ 80000 Hz
Indication
Operational readiness green
Interface technology
Error indication red
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -25…+85 °C
Relative humidity ≤ 95 %
Derating -2.5%/°C from 60 °C
Test voltage 3.0 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection screw terminals
Terminal cross-section 0.2 … 2.0 mm2
Housing material metal
Mounting instruction for DIN rail
Power supply
Features
▪▪ UL Class 1, Div 2
▪▪ Safety extra-low voltage SELV IEC/
EN 60950
▪▪ SEMI-F47
Rdy DC ON /– N
93 ... 132 VAC
180 ... 264 VAC
▪▪ Output voltage adjustable
+ GN
/+ L
210 ... 370 VDC 22.5…28.5 VDC
22,5 ... 28,5 VDC +
10 A
DC LOW
▪▪ Nominal current 10 A
(max. 240 W) – RD ▪▪ Single/parallel operating mode
–
▪▪ Surge protection
▪▪ Mains buffering up to 30 ms
▪▪ Power-good relay
The IM82‑24‑10 power supply units are The power supply provides 24 VDC out‑ extra-low
voltage (SELV) according to
designed for DC loads, particularly the put voltage and 10 A output current. T he EN 60950.
switching and monitoring devices of the output voltage is adjusted in a range be‑
TURCK IM, IME, IMS and IMC interface tween 22.5…28.5 VDC with t he potenti‑ The power supply can be set to single or
module series. ometer Vout. T he device provides safety parallel operating mode.
0
-25 60 70 [°C]
Parallel operation
– VO
+ VO
Rdy Rdy
654321 654321
789 789
LN LN
440 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM82-24-10 Mounting instruction for DIN rail
Ident no. 7545043 Protection class IP20
Flammability class acc. to UL 94 V-0
Power supply Dimensions 83.5 x 124.5 x 116.6 mm
Nominal voltage Universal voltage supply unit
Operating voltage range 210…370 VDC Approval | Certification cULus
Operating voltage range 90…132 VAC
Operating voltage range 186…264 VAC
Frequency 47…73 Hz
Power consumption ≤ 276 VA
PFC 0.7
Efficiency 89 %
Internal fuse T 6.3 A / 250 VAC
inrush current Ui = 115 VAC, 30 A; Ui = 230 VAC, 60
A
Mains buffering Ui = 115 VAC, 25 ms; Ui = 230 VAC,
30 ms
Outputs
Nominal output voltage 24 V
Nominal current 10 A
Output circuits (digital) relay (NO), > 17.6 … 19.4 V
Relay switching voltage ≤ 60 VDC
Switching current per output ≤ 300 mA
Surge limiting 120‑145 %
Overload protection 110‑150 %
Parallel mode yes, switchover initiated by a switch,
max. 3 devices each with 90 % load
current
Pollution degree 2
Surge category II
Short-circuit behaviour Current limiting
Response characteristic
Limit frequency ≤ 40000 Hz
Indication
Operational readiness green
Interface technology
Error indication red
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -25…+85 °C
Relative humidity ≤ 95 %
Derating -2.5%/°C from 60 °C
Test voltage 3.0 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection screw terminals
Terminal cross-section 0.2 … 2.0 mm2
Housing material metal
Power supply
Features
▪▪ UL Class 1, Div 2
▪▪ Safety extra-low voltage SELV IEC/
EN 60950
▪▪ SEMI-F47
Rdy DC ON /+ L
90 ... 264 VAC ▪▪ Output voltage adjustable
+ GN
/– N
120 ... 370 VDC 22.5…28.5 VDC
22,5 ... 28,5 VDC +
20 A
DC LOW
▪▪ Nominal current 20 A
(max. 480 W) – RD ▪▪ Single/parallel operating mode
–
▪▪ Surge protection
▪▪ Mains buffering up to 30 ms
▪▪ Parallel operation
▪▪ Power-good relay
The IM82‑24‑20 power supply units are The power supply provides 24 VDC out‑ extra-low
voltage (SELV) according to
designed for DC loads, particularly the put voltage and 20 A output current. T he EN 60950.
switching and monitoring devices of the output voltage is adjusted in a range be‑
TURCK IM, IME, IMS and IMC interface tween 22.5…28.5 VDC with t he potenti‑ The power supply can be set to single or
module series. ometer Vout. T he device provides safety parallel operating mode.
0
-40 56 70 [°C]
Parallel operation
N L Rdy N L Rdy
– VO
+ VO
442 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IM series
Technical data
Type IM82-24-20 Protection class IP20
Ident no. 7545044 Flammability class acc. to UL 94 V-0
Dimensions 175.5 x 124.5 x 116.6 mm
Power supply
Nominal voltage Universal voltage supply unit Approval | Certification cULus
Operating voltage range 120…370 VDC
Operating voltage range 90…264 VAC
Frequency 47…63 Hz
Power consumption ≤ 564 VA
PFC 0.99
Efficiency 89 %
Internal fuse T 10 A / 250 VAC
inrush current Ui = 115 VAC, 25 A; Ui = 230 VAC, 50
A
Mains buffering Ui = 115 VAC, 30 ms; Ui = 230 VAC,
30 ms
Outputs
Nominal output voltage 24 V
Nominal current 20 A
Output circuits (digital) relay (NO), > 17.6 … 19.4 V
Relay switching voltage ≤ 60 VDC
Switching current per output ≤ 300 mA
Surge limiting 125‑137 %
Overload protection 120‑140 %
Parallel mode yes, switchover initiated by a switch,
max. 3 devices each with 90 % load
current
Pollution degree 2
Surge category II
Short-circuit behaviour Current limiting
Response characteristic
Limit frequency ≤ 60000 Hz
Indication
Operational readiness green
Error indication red
Mechanical data
Tightening torque 0.6 Nm
Electrical connection screw terminals
Terminal cross-section 0.2 … 6.0 mm2
Housing material metal
Mounting instruction for DIN rail
The 2‑channel isolating switching ampli‑ When using mechanical contacts, the ciated output. In the event of an input
fier IME-DI-22EX-T/24VDC is equipped contacts must be wired with resistors (II) circuit error, the 2‑color LED a ssociated
with intrinsically safe input circuits. Sen‑ because of wire-break and short-circuit to the affected input turns red. Thereup‑
sors according to EN 60947‑5‑6 (NAMUR) monitoring (see circuit diagram). For this, on the associated output transistor is
or potential-free contact transmitters can use the resistor module WM1, ident n o. blocked.
be connected to the device. 0912101.
The output circuits each feature a p oten‑ The Pwr LED lights green to indicate op‑
tial-free transistor output. You can t oggle erational readiness.
between working or closed c urrent, resp.
NO or NC mode via a wire jumper. The 2‑color LEDs 1 and 2 light yellow to
indicate the switching status of the asso‑
444 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface Technology in Modular Housing
DIN rail mounted devices of the IME series
Technical data
Type IME-DI-22EX-T/24VDC Max. output current Io ≤ 10 mA
Ident no. 7541197 Max. output power Po ≤ 24 mW
Characteristic linear
Power supply Internal inductance/capacitance Li/Ci Li = 150 µH, Ci = negligibly small
Nominal voltage 24 VDC External inductance/capacitance Lo/Co
Operating voltage range 20…30 VDC Ex nL IIC IIB
Power consumption ≤ 1.5 W Lo [mH] 5 0.85 10 0.85
Co [µF] 1.4 1.9 6.6 11
Inputs
Declaration SIL 2 acc. to EXIDA FMEDA
No-load voltage 8.2 VDC
Short-circuit current 8.2 mA
Indication
Input resistance 1 kΩ
Operational readiness green
Cable resistance ≤ 50 Ω
Switching state yellow
Switch-on threshold: 1.55 mA
Error indication red
Switch-off threshold: 1.75 mA
Short-circuit threshold ï 6 mA
Environmental Conditions
Wire breakage threshold ≤ 0.1 mA
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Outputs
Test voltage 2.5 kV
Output circuits (digital) 2 x transistor (potential-free, short-
circuit proof) MTTF 407 years acc. to SN 29500 (Ed. 99)
40 °C
Switching voltage ≤ 30 VDC
Switching current per output ≤ 100 mA
Mechanical data
Switching frequency ≤ 3000 Hz
Electrical connection Spring terminal made of Beryllium-
Voltage drop ≤ 2.5 V Bronze
Terminal cross-section 1.5 mm2
Approvals and declarations Housing material Polycarbonate/ABS
Ex approval acc. to conformity certificate TÜV 07 ATEX 553234 Mounting instruction for DIN rail
Device designation É II (1) GD [Ex ia] IIC/IIB Protection class IP20
Max. values: Terminal connection: 3+4 / 5+6 Flammability class acc. to UL 94 V-0
Max. output voltage Uo ≤ 9.6 V Dimensions 18 x 112 x 110 mm
Max. output current Io ≤ 10 mA
Max. output power Po ≤ 24 mW Approval | Certification ATEX, IECEx, TR CU, NEPSI
Rated voltage 250 V
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 150 µH, Ci = negligibly small
External inductance/capacitance Lo/Co
Interface technology
Ex ia IIC IIB
Lo [mH] 10 0.85 20 1.85
Co [µF] 0.75 1.1 3.4 5.3
Max. output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 10 mA
Max. output power Po ≤ 24 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 150 µH, Ci = negligibly small
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Lo [mH] 5 0.85 10 0.85
Co [µF] 1.4 1.9 6.6 11
Ex approval acc. to conformity certificate TÜV 07 ATEX 554299 X
Application area II 3 G
Protection type Ex nA nC [nL] IIC/IIB T4
Max. values: Terminal connection: 3+4 / 5+6
Max.output voltage Uo ≤ 9.6 V
▪▪ Input circuit monitoring of wire-break/
short-circuit
▪▪ Galvanic isolation of input circuits,
output circuits and supply voltage
The 2‑channel isolating switching ampli‑ NO or NC mode for both channels v ia a The Pwr LED lights green to indicate op‑
fier IME-DI-22EX-R/24VDC is e quipped wire jumper. erational readiness.
with intrinsically safe input circuits. Sen‑
sors according to EN 60947‑5‑6 (NAMUR) When using mechanical contacts, the The 2‑color LEDs 1 and 2 light yellow to
or potential-free contact transmitters can contacts must be wired with resistors (II) indicate the switching status of the asso‑
be connected to the device. because of wire-break and short-circuit ciated output. In the event of an input
monitoring (see circuit diagram). For this, circuit error, the 2‑color LED a ssociated
The output circuits each feature a relay use the resistor module WM1, ident n o. to the affected input turns red, provided
with NO contact. You can toggle be‑ 092101. the input circuit monitoring function is
tween working or closed current, resp. activated. Thereupon the output relay
drops out.
446 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface Technology in Modular Housing
DIN rail mounted devices of the IME series
Technical data
Type IME-DI-22Ex-R/24VDC Max.output voltage Uo ≤ 9.6 V
Ident no. 7541191 Max. output current Io ≤ 10 mA
Max. output power Po ≤ 24 mW
Power supply Characteristic linear
Nominal voltage 24 VDC Internal inductance/capacitance Li/Ci Li = 150 µH, Ci = negligibly small
Operating voltage range 20…30 VDC External inductance/capacitance Lo/Co
Power consumption ≤ 1.7 W Ex nL IIC IIB
Lo [mH] 5 0.85 10 0.85
Inputs Co [µF] 1.4 1.9 6.6 11
No-load voltage 8.2 VDC
Declaration SIL 2 acc. to EXIDA FMEDA
Short-circuit current 8.2 mA
Input resistance 1 kΩ
Indication
Cable resistance ≤ 50 Ω
Operational readiness green
Switch-on threshold: 1.55 mA
Switching state yellow
Switch-off threshold: 1.75 mA
Error indication red
Short-circuit threshold ï 6 mA
Wire breakage threshold ≤ 0.1 mA
Environmental Conditions
Ambient temperature -25…+70 °C
Outputs
Storage temperature -40…+80 °C
Output circuits (digital) 2 x relays (NO)
Test voltage 2.5 kV
Switching frequency ≤ 10 Hz
MTTF 235 years acc. to SN 29500 (Ed. 99)
Relay switching voltage ≤ 250 VAC/120 VDC 40 °C
Switching current per output ≤ 2 A
Switching capacity per output ≤ 500 VA/60 W Mechanical data
Contact quality AgNi, 3µ Au Electrical connection Spring terminal made of Beryllium-
Bronze
Approvals and declarations Terminal cross-section 1.5 mm2
Ex approval acc. to conformity certificate TÜV 07 ATEX 553234 Housing material Polycarbonate/ABS
Device designation É II (1) GD [Ex ia] IIC/IIB Mounting instruction for DIN rail
Max. values: Terminal connection: 3+4 / 5+6 Protection class IP20
Max. output voltage Uo ≤ 9.6 V Flammability class acc. to UL 94 V-0
Max. output current Io ≤ 10 mA Dimensions 18 x 112 x 110 mm
Max. output power Po ≤ 24 mW
Rated voltage 250 V Approval | Certification ATEX, IECEx, TR CU, NEPSI
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 150 µH, Ci = negligibly small
External inductance/capacitance Lo/Co
Interface technology
Ex ia IIC IIB
Lo [mH] 10 0.85 20 1.85
Co [µF] 0.75 1.1 3.4 5.3
Max. output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 10 mA
Max. output power Po ≤ 24 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 150 µH, Ci = negligibly small
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Lo [mH] 5 0.85 10 0.85
Co [µF] 1.4 1.9 6.6 11
Ex approval acc. to conformity certificate TÜV 07 ATEX 554299 X
Application area II 3 G
Protection type Ex nA nC [nL] IIC/IIB T4
Max. values: Terminal connection: 3+4 / 5+6
Standard active current signals are gal‑ The device features one input circuit 0/ transmitted 1:1 and are presented to t he
vanically isolated and transmitted via t he 4… 20 mA and one short-circuit proof relevant outputs in the non-Ex area.
1‑channel analog signal isolator IME-AI- output circuit 0/4…20 mA.
11EX-i/L from the Ex area to the n on-Ex The device is loop-powered and HART®
area. Input and output circuit are safely gal‑ transmissible.
vanically isolated. The input signals are
IME-AI-11Ex-Hi/L
448 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface Technology in Modular Housing
DIN rail mounted devices of the IME series
Technical data
Type IME-AI-11Ex-Hi/L Terminal cross-section 1.5 mm2
Ident no. 7541192 Housing material Polycarbonate/ABS
Mounting instruction for DIN rail
Power supply Protection class IP20
Nominal voltage 24 VDC loop-powered Flammability class acc. to UL 94 V-0
Power consumption ≤ 0.75 W Dimensions 18 x 112 x 110 mm
Outputs
Load resistance, current output ≤ 0.4 kΩ
Output current 0…20 mA
Output voltage max. 13 V
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.001 % / K
Rise time (10-90%) ≤ 10 ms
Dropout time (90…10%) ≤ 10 ms
Interface technology
Max. values: Terminal connection: 3+4
Max. input voltage Ui ≤ 27 V
Max. input current Ii ≤ 150 mA
Max. input power Pi ≤ 1000 mW
Internal inductance/capacitance Li/Ci negligibly small
Declaration SIL 2 acc. to EXIDA FMEDA
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Test voltage 2.5 kV
MTTF 537 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Electrical connection Spring terminal made of Beryllium-
Bronze
Standard active current signals are gal‑ The device features one input and one
result of the 1:1 transmission behaviour,
vanically isolated and transmitted via t he output circuit, each with 0/4…20 mA.
wire-break and short circuit are output a s
1‑channel analog signal isolator IME-AI- currents of 0 mA or > 22.5 mA in the
11EX-Hi/24VDC from the Ex area to the A green LED indicates operational measuring transducer circuit.
non-Ex area. readiness.
Besides the analog signals, digital HART® Input and output circuit are safely gal‑
communication signals can also be trans‑ vanically isolated. The input signal is
idirectionally.
mitted b transmitted 1:1 and is presented to the
relevant output in the non-Ex area. As a
450 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface Technology in Modular Housing
DIN rail mounted devices of the IME series
Technical data
Type IME-AI-11Ex-Hi/24VDC Mechanical data
Ident no. 7541198 Electrical connection Spring terminal made of Beryllium-
Bronze
Power supply Terminal cross-section 1.5 mm2
Nominal voltage 24 VDC Housing material Polycarbonate/ABS
Operating voltage range 20…30 VDC Mounting instruction for DIN rail
Power consumption ≤ 0.75 W Protection class IP20
Flammability class acc. to UL 94 V-0
Inputs Dimensions 18 x 112 x 110 mm
Current input 0/4…20 mA
Control circuits Current limiting 42 mA Approval | Certification ATEX, IECEx, TR CU, NEPSI
Outputs
Load resistance, current output ≤ 0.7 kΩ
Output current 0/4…20 mA
Wire break monitoring ≤ 1 mA
Short circuit monitoring ï 22.5 mA
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Temperature drift ≤ 0.001 % / K
Rise time (10-90%) ≤ 10 ms
Dropout time (90…10%) ≤ 10 ms
Interface technology
Max. values: Terminal connection: 3+4
Max. input voltage Ui ≤ 27 V
Max. input current Ii ≤ 150 mA
Max. input power Pi ≤ 1000 mW
Internal inductance/capacitance Li/Ci negligibly small
Declaration SIL 2 acc. to EXIDA FMEDA
Indication
Operational readiness green
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Test voltage 2.5 kV
MTTF 435 years acc. to SN 29500 (Ed. 99)
40 °C
The 1‑channel HART® isolating t ransduc‑ The device features one input and one wire-break and short circuit are output a s
er IME-AIA-11EX-Hi/24VDC is u sed to en‑ output circuit for 4…20 mA. currents of 0 mA or > 22.5 mA in the
ergize intrinsically safe 2‑wire H ART® measuring transducer circuit.
transducers (III) in the Ex area and to A green LED indicates operational
transmit the measured signal to the n on- readiness.
Ex area.
Input and output circuit are safely gal‑
Besides the analog signals, digital HART® vanically isolated. The input signal is
communication signals can also be trans‑ transmitted 1:1 and is presented to the
idirectionally.
mitted b relevant output in the non-Ex area. As a
result of the 1:1 transmission behaviour,
452 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface Technology in Modular Housing
DIN rail mounted devices of the IME series
Technical data
Type IME-AiA-11Ex-Hi/24VDC Indication
Ident no. 7541193 Operational readiness green
Interface technology
Lo [mH] 0.804 0.424 0.024 4.8 0.9 0.12
Co [nF] 46 62 121 358 418 718
Ex approval acc. to conformity certificate TÜV 08 ATEX 554909 X
Application area II 3 G
Protection type Ex nA [nL] IIB/IIC T4
Max. values: Terminal connection: 3+4
Max.output voltage Uo ≤ 23 V
Max. output current Io ≤ 64.5 mA
Max. output power Po ≤ 799 mW
Characteristic trapezoidal
Internal inductance/capacitance Li/Ci Ci = 22 nF, Li = 76.5 µH
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Lo [mH] 0.12 19.9
Co [nF] 188 786
Declaration SIL 2 acc. to EXIDA FMEDA
The temperature measuring amplifier The devices are parametrized and con‑ ▪▪ Input circuit monitoring for
IME-TI-11Ex-CI/24VDC is designed to figured via PC with the software tool „De‑ wire-break
evaluate the temperature-dependent vice Type Manager“ (DTM). For this, c on‑ ▪▪ Current output behaviour in the event
changes of Ni100/Pt100 RTDs, thermo‑ nect the temperature measuring of input circuit errors: 0 or > 22 mA
couples types B, E, J, K, L, N, R, S a nd T or amplifier to the PC with the 3.5 mm jack ▪▪ Internal or external cold junction
low voltages in a range of -160…+160 mV plug on the front. The ready-made t rans‑ compensation
and to output them as linear tempera‑ mission cable can be ordered from ▪▪ Output current (0/4…20 mA)
ture current signals 0/4…20 mA. TURCK under the type name IM-PROG ▪▪ Temperature (°C or °K)
(ident no. 6890422). ▪▪ Mode (resistor, thermocouples, low
Alternatively, Ni100/Pt100 RTDs in 2, 3 or voltage, line compensation)
4‑wire technology can also be o perated The following settings can be adjusted
at the input circuit of the m
easuring am‑ via DTM:
plifier. The Ni100/Pt100 input can either ▪▪ Connection mode (2, 3 and 4‑wire The signals are transformed according t o
be used as external cold junction com‑ technology) ITS 90/IEC 584 for thermocouples and IEC
pensation for the t hermocouple (2‑wire) ▪▪ Measuring range start 751 for Pt100 RTDs and provided as tem‑
or as independent measuring input. ▪▪ Measuring range end perature-linear signals at the current
output.
454 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface Technology in Modular Housing
DIN rail mounted devices of the IME series
Technical data
Type IME-TI-11Ex-CI/24VDC External inductance/capacitance Lo/Co
Ident no. 7541199 Ex ia IIB IIC
Lo [mH] 100 10 1 100 10 1
Power supply Co [µF] 10 13 21 2.2 2.7 3.9
Nominal voltage 24 VDC
Ex approval acc. to conformity certificate TÜV 09 ATEX 555274 X
Operating voltage range 20…30 VDC
Application area II 3 G
Power consumption ≤ 1.5 W
Protection type Ex nA [nL] IIB/IIC T4
Max. values: Terminal connection: 1…6
Inputs
Max.output voltage Uo ≤ 5 V
Input circuits thermocouple, Pt100, Ni100
Max. output current Io ≤ 2 mA
Pt100 (IEC 751), 2, 3 and 4‑wire technology
Max. output power Po ≤ 2.5 mW
Ni100 (DIN 43760), 2, 3 and 4‑wire
technology Characteristic linear
Probe current ≤ 0.2 mA Internal inductance/capacitance Li/Ci negligibly small
Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L External inductance/capacitance Lo/Co
(DIN 43710) Ex nL IIB IIC
Nominal resistance 0…1.5 kΩ Lo [mH] 100 10 1 100 10 1
Voltage input -0.160…+0.160 VDC Co [µ] 18 23 37 3.6 4.5 6.6
Outputs
Indication
Load resistance, current output ≤ 0.6 kΩ
Operational readiness green
Output current 0/4…20 mA
Error indication red
Switching frequency ≤ 1 Hz
Fault current 0 / 22 mA adjustable
Environmental Conditions
Ambient temperature -25…+70 °C
Response characteristic
Storage temperature -40…+80 °C
Reference temperature 23 °C
Test voltage 2.5 kV
Accuracy current output ± 20 µA
Temperature drift analogue output 0.0025 %/K
Mechanical data
Temperature drift RTD input ± 3 mΩ/K
Electrical connection Spring terminal made of Beryllium-
Temperature drift TC input 3.2 µV / K (of 320 mV)
Bronze
Accuracy RTD input ± 50 mΩ Terminal cross-section 1.5 mm2
Accuracy TC input ± 15 µV Housing material Polycarbonate/ABS
Cold junction compensation error 2‑wire < 100 mΩ after line Mounting instruction for DIN rail
compensation
Protection class IP20
3‑wire < 100 mΩ with a symmetrical
wiring Flammability class acc. to UL 94 V-0
4‑wire < 50 mΩ Dimensions 18 x 112 x 110 mm
Interface technology
with cold junction c ompensation< 2 K
with IM-3‑CJT < 1 K Approval | Certification ATEX, IECEx, TR CU, NEPSI
Rise time (10-90%) ≤ 30 ms
The 1‑channel analog data transmitter The normalized current signal is trans‑ cally analog actuators like I/P converters
IME-AO-11Ex-i/L has an intrinsically safe mitted, galvanically isolated 1:1, from the (e.g. at control valves) or displays can be
output circuit. non-Ex to the Ex-area. applied in the Ex area.
456 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface Technology in Modular Housing
DIN rail mounted devices of the IME series
Technical data
Type IME-AO-11Ex-Hi/L Max. output current Io ≤ 97 mA
Ident no. 7541194 Max. output power Po ≤ 322 mW
Characteristic linear
Power supply Internal inductance/capacitance Li/Ci negligibly small
Nominal voltage 24 VDC loop-powered External inductance/capacitance Lo/Co
Power consumption ≤ 0.75 W Ex nL IIC IIB
Lo [mH] 5 0.5 10 1
Inputs Co [µF] 0.51 1.2 2.9 5.8
Voltage input max. 30 VDC
Declaration SIL 2 acc. to EXIDA FMEDA
Current input 0…20 mA
Control circuits Current limiting 42 mA
Environmental Conditions
Ambient temperature -25…+70 °C
Outputs
Storage temperature -40…+80 °C
Output circuits 0…20 mA
Test voltage 2.5 kV
Load resistance, current output ≤ 0.4 kΩ
MTTF 515 years acc. to SN 29500 (Ed. 99)
Output current 0…20 mA 40 °C
Output voltage max. 13 V
Mechanical data
Response characteristic Electrical connection Spring terminal made of Beryllium-
Measuring accuracy ≤ 0.1 % of full scale Bronze
Reference temperature 23 °C Terminal cross-section 1.5 mm2
Temperature drift ≤ 0.001 % / K Housing material Polycarbonate/ABS
Rise time (10-90%) ≤ 10 ms Mounting instruction for DIN rail
Dropout time (90…10%) ≤ 10 ms Protection class IP20
Flammability class acc. to UL 94 V-0
Approvals and declarations Dimensions 18 x 112 x 110 mm
Ex approval acc. to conformity certificate TÜV 08 ATEX 554800
Device designation É II (1) G, II (1) D [Ex ia] IIB/IIC; [Ex Approval | Certification ATEX, IECEx, TR CU, NEPSI
iaD]
Max. values: Terminal connection: 3+4
Max. output voltage Uo ≤ 13.3 V
Max. output current Io ≤ 97 mA
Max. output power Po ≤ 322 mW
Rated voltage 250 V
Characteristic linear
Internal inductance/capacitance Li/Ci negligibly small
External inductance/capacitance Lo/Co
Interface technology
Ex ia IIC IIB
Lo[mH] 2 0.2 2 0.2
Co[µF] 0.42 0.91 2.7 5.5
Max. output voltage Uo ≤ 13.3 V
Max. output current Io ≤ 97 mA
Max. output power Po ≤ 322 mW
Characteristic linear
Internal inductance/capacitance Li/Ci negligibly small
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Lo [mH] 5 0.5 10 1
Co [µF] 0.51 1.2 2.9 5.8
Ex approval acc. to conformity certificate TÜV 08 ATEX 554818 X
Application area II 3 G
Protection type Ex nA [nL] IIC/IIB T4
Max. values: Terminal connection: 3+4
Max.output voltage Uo ≤ 13.3 V
The 1‑channel solonoid driver IME-DO- potentially explosive atmospheresterms of their no-load voltage (see out‑
11Ex/L provides limited current and volt‑ caused by dust or gas, provided they put curve on next page). They are adapt‑
age at the intrinsically safe output. This comply with the applicable regulations. ed to the valves of different m
anufactur‑
enables them to be used d irectly for sup‑ Typical applications are the control of ers. The loads are actuated by applying
plying loads in the Ex area. Ex i pilot valves as well as the supply of the operating voltage.
displays and transmitters.
Within the area of applicability of the E u‑ A yellow LED indicates the switching
ropean directive 94/9/EC (ATEX) it is per‑ The output values of the two connec‑ state of the associated output.
mitted to operate connected loads in tions U1 and U2 per channel differ in
458 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface Technology in Modular Housing
DIN rail mounted devices of the IME series
Technical data
Type IME-DO-11EX/L Internal inductance/capacitance Li/Ci negligibly small
Ident no. 7541196 External inductance/capacitance Lo/Co
Ex nL IIC IIB
Power supply Lo [mH] 1.0 0.5 5.0 0.5
Nominal voltage 24 VDC loop-powered Co [µF] 0.11 0.14 0.75 0.91
Power consumption ≤ 1.5 W
Characteristic trapezoidal
Internal inductance/capacitance Li/Ci negligibly small
Inputs
External inductance/capacitance Lo/Co
0-signal 0…5 VDC
1-signal 20…30 VDC Ex nL IIC IIB
Voltage input max. 30 VDC Lo [mH] 2.0 0.5 5.0 1.0
Current input 45 mA Co [µF] 0.3 0.42 1.6 2.5
Input delay ≤ 0.4 ms Declaration SIL 3 acc. to EXIDA FMEDA
Outputs Indication
Output current 40 mA Switching state yellow
Output voltage U1=24 V
Output voltage U2=15 V Environmental Conditions
Output curve Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Test voltage 2.5 kV
MTTF 363 years acc. to SN 29500 (Ed. 99)
40 °C
Mechanical data
Response characteristic Electrical connection Spring terminal made of Beryllium-
Limit frequency ≤ 500 Hz Bronze
Terminal cross-section 1.5 mm2
Approvals and declarations Housing material Polycarbonate/ABS
Ex approval acc. to conformity certificate TÜV 06 ATEX 2977 X Mounting instruction for DIN rail
Device designation É II (1) GD [Ex ia] IIC/IIB Protection class IP20
Max. output voltage Uo ≤ 25.4 V Flammability class acc. to UL 94 V-0
Max. output current Io ≤ 96 mA Dimensions 18 x 112 x 110 mm
Max. output power Po ≤ 678 mW
Rated voltage 250 V Approval | Certification ATEX, IECEx, TR CU, NEPSI
Characteristic Trapezoidal
Internal inductance/capacitance Li/Ci negligibly small
Interface technology
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 0.68 0.5 13.0 2.0
Co [µF] 0.067 0.076 0.31 0.34
Max. output voltage Uo ≤ 17.6 V
Max. output current Io ≤ 96 mA
Max. output power Po ≤ 678 mW
Characteristic Trapezoidal
Internal inductance/capacitance Li/Ci negligibly small
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 1.2 0.5 13.0 2.0
Co [µF] 0.13 0.15 0.47 1.1
Ex approval acc. to conformity certificate TÜV 06 ATEX 2979 X
Application area II 3 G
Protection type Ex nA [nL] IIC / IIB T4
Characteristic trapezoidal
The 2‑channel solonoid driver IME-DO- potentially explosive atmospheresterms of their no-load voltage (see out‑
22Ex/L provides limited current and volt‑ caused by dust or gas, provided they put curve on next page). They are adapt‑
age at the intrinsically safe output. This comply with the applicable regulations. ed to the valves of different m anufactur‑
enables them to be used d irectly for sup‑ Typical applications are the control of Ex ers. The loads are actuated by applying
plying loads in the Ex area. i pilot valves as well as the supply of dis‑ the operating voltage.
plays and transmitters.
Within the area of applicability of the E u‑ A yellow LED indicates the switching
ropean directive 94/9/EC (ATEX) it is per‑ The output values of the two connec‑ state of the associated output.
mitted to operate connected loads in tions U1 and U2 per channel differ in
460 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface Technology in Modular Housing
DIN rail mounted devices of the IME series
Technical data
Type IME-DO-22EX/L Internal inductance/capacitance Li/Ci negligibly small
Ident no. 7541195 External inductance/capacitance Lo/Co
Ex nL IIC IIB
Power supply Lo [mH] 1.0 0.5 5.0 0.5
Nominal voltage 24 VDC loop-powered Co [µF] 0.11 0.14 0.75 0.91
Power consumption ≤ 3 W
Characteristic trapezoidal
Internal inductance/capacitance Li/Ci negligibly small
Inputs
External inductance/capacitance Lo/Co
0-signal 0…5 VDC
1-signal 20…30 VDC Ex nL IIC IIB
Voltage input max. 30 VDC Lo [mH] 2.0 0.5 5.0 1.0
Input delay ≤ 0.4 ms Co [µF] 0.3 0.42 1.6 2.5
Declaration SIL 3 acc. to EXIDA FMEDA
Outputs
Output current 40 mA Indication
Output voltage U1=24 V Switching state yellow
Output voltage U2=15 V
Output curve Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Test voltage 2.5 kV
MTTF 363 years acc. to SN 29500 (Ed. 99)
40 °C
Interface technology
Ex ia IIC IIB
Lo [mH] 0.68 0.5 13.0 2.0
Co [µF] 0.067 0.076 0.31 0.34
Max. output voltage Uo ≤ 17.6 V
Max. output current Io ≤ 96 mA
Max. output power Po ≤ 678 mW
Characteristic Trapezoidal
Internal inductance/capacitance Li/Ci negligibly small
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 1.2 0.5 13.0 2.0
Co [µF] 0.13 0.15 0.47 1.1
Ex approval acc. to conformity certificate TÜV 06 ATEX 2979 X
Application area II 3 G
Protection type Ex nA [nL] IIC / IIB T4
Characteristic trapezoidal
Standard active voltage or current sig‑ a variable short-circuit proof output cir‑ setting and made available at the
nals are transmitted galvanically isolated cuit of 0/4…20 mA or 0…10 V. output.
and converted to other signal types via
the 1‑channel universal analog signal The transmission characteristic (for input The green LED indicates operational
isolator IMS-AI-UNI/24VDC. and output signal type) is adjusted via readiness.
side-mounted DIP switches. The input
The device is equipped with available in‑ signals are transmitted according to the With a width of 6.2 mm, the device is gal‑
put circuit of 0/4…20 mA or 0…10 V a nd vanically isolated up to 1.5 kV.
462 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IMS series
Technical data
Type IMS-AI-UNI/24V
Ident no. 7504009
Power supply
Nominal voltage 24 VDC
Operating voltage range 19…29 VDC
Power consumption ≤ 0.312 W
Residual ripple ≤ 5 mVss
Inputs
Voltage input 0/2…10 VDC
Input resistance (voltage) ï 330 kΩ
Current input 0/4…20 mA
Input resistance (current) ≤ 100 Ω
Outputs
Load resistance, current output ≤ 0.4 kΩ
Load resistance voltage output ï 1 kΩ
Output current 0/4…20 mA
Output voltage 0…10 V
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Temperature drift ≤ 0.00015 % / K
Rise time (10-90%) ≤ 10 ms
Dropout time (90…10%) ≤ 10 ms
Indication
Operational readiness green
Environmental Conditions
Ambient temperature -20…+60 °C
Storage temperature -40…+80 °C
Test voltage 1.5 kV
Mechanical data
Tightening torque 0.5 Nm
Interface technology
Electrical connection screw terminals
Terminal cross-section 2.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 6.2 x 114.5 x 90 mm
The 2‑channel analog signal isolator IMS- The device features two input circuits The input signals are transmitted 1:1 a nd
AI-DLI-22‑DLI/L is designed to transmit 0/4…20 mA and two short-circuit proof are presented to the relevant o
utput.
normalized active current signals galvan‑ output circuits 0/4…20 mA.
ically isolated. The device is loop-powered. Separate
The device is loop powered, transmission power supply is not necessary.
starts with 250 µA. Required minimum
voltage 2.8 V + (20 mA x Rload).
464 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IMS series
Technical data
Type IMS-AI-DLI-22-DLI/L
Ident no. 7504011
Power supply
Nominal voltage 24 VDC loop-powered
Power consumption ≤ 0.312 W
Residual ripple ≤ 5 mVss
Inputs
Voltage input max. 29 VDC
Current input 0/4…20 mA
Input resistance (current) ≤ 100 Ω
Outputs
Load resistance, current output ≤ 0.4 kΩ
Output current 0/4…20 mA
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Temperature drift ≤ 0.00015 % / K
Rise time (10-90%) ≤ 10 ms
Dropout time (90…10%) ≤ 10 ms
Environmental Conditions
Ambient temperature -20…+60 °C
Storage temperature -40…+80 °C
Test voltage 1.5 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection screw terminals
Terminal cross-section 2.5 mm2
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 6.2 x 114.5 x 90 mm
▪▪ Output circuit: 0/4…20 mA or 0…10 V
▪▪ Linearity < 0.1 % f.s.
▪▪ Accuracy < 0.3 % f.s.
▪▪ Complete galvanic isolation
▪▪ 6.2 mm width
The 1‑channel temperature measuring or 0…10 V) as well as the measuring In the event of error (wire-break or short-
amplifier IMS-TI-Pt100/24V is designed range are adjusted via DIP switch. circuit), 12 V or 22 mA are p
rovided at the
to evaluate the temperature-dependent output and the error is additionally sig‑
changes of Pt100 RTDs, to isolate them Wire-break and short-circuit are detect‑ nalled by the flashing p ower LED.
galvanically and to output them as tem‑ ed. In the event of error, 12 V or 22 mA are The IM34 temperature measuring ampli‑
perature-linear voltage or current s ignals provided at the output and the error is fiers from TURCK offer more s olutions for
of 0…10 V, 0…20 mA or 4…20 mA. additionally signalled by the flashing applications with other measuring rang‑
power LED. es and temperature p robes.
Alternatively, Pt100 RTDs in 2, 3 or 4
‑wire
technology can also be operated a t the The following measuring ranges can be
input circuit of the measuring amplifier. adjusted:
▪▪ -50…+150 °C
The number of Pt100 wires, the t ransmis‑ ▪▪ 0…+100 °C
sion characteristic (0…20 mA, 4
…20 mA ▪▪ 0…+200 °C
466 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IMS series
Technical data
Type IMS-TI-PT100/24V
Ident no. 7504012
Power supply
Nominal voltage 24 VDC
Operating voltage range 19…29 VDC
Power consumption ≤ 0.32 W
Residual ripple ≤ 5 mVss
Inputs
Pt100 -50…150°C; 0…100°C; 0…200°C
Input resistance (voltage) ï 1000 kΩ
Outputs
Load resistance, current output ≤ 0.4 kΩ
Load resistance voltage output ï 1 kΩ
Output current 0/4…20 mA
Output voltage 0…10 V
Response characteristic
Measuring accuracy ≤ 0.3 % of full scale
Temperature drift ≤ 0.00015 % / K
Rise time (10-90%) ≤ 30 ms
Dropout time (90…10%) ≤ 30 ms
Indication
Operational readiness green
Environmental Conditions
Ambient temperature -20…+60 °C
Storage temperature -40…+80 °C
Test voltage 1.5 kV
Mechanical data
Tightening torque 0.5 Nm
Electrical connection screw terminals
Terminal cross-section 2.5 mm2
Interface technology
Housing material Polycarbonate/ABS
Mounting instruction for DIN rail
Protection class IP20
Flammability class acc. to UL 94 V-0
Dimensions 6.2 x 114.5 x 90 mm
▪▪ ATEX, IECEx, UL
▪▪ Nominal voltage 24 VDC
▪▪ For one floating 2‑wire signal circuit
7 8 ▪▪ IEC category: C1 / C2 / C3 / D1
1 1 ▪▪ Flammability class V-0
5 6 ▪▪ HART® transmissible
3 4
1 2
The IMSP-1X2‑24 is a surge protection The HART® transmissible d evices are IP20 The only 6.2 mm slim housing can be
module, designed for the MSR technolo‑ rated and can be i nstalled in Ex as well as mounted on DIN rail acc. to DIN NS35.
gy. It protects one floating 2
‑wire signal non-Ex areas.
circuit.
468 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IMSP series
Technical data
Type IMSP-1x2-24 Approvals and declarations
Ident no. 7504050 Ex approval acc. to conformity certificate DEKRA 11 ATEX 0016 X
Device designation É II 1 G, II 1 D Ex ia IIC T4…T6; Ex
Nominal voltage Un 24 VDC iaD 20 T85°C…T135°C
IEC category C1; C2; C3; D1 Max. values: Terminal connection: 5+7 / 6+8
Surge arrester, rated voltage Uc 25 VAC / 36 VDC Max. input voltage Ui ≤ 36 V
Max. input current Ii ≤ 350 mA
Nominal current In (≤ 40 °C) 350 mA Max. input power Pi ≤ 3000 mW
Active current Ic with given Uc 2 μA Internal inductance/capacitance Li/Ci Li = 1 µH; Ci = 1.3 nF
Leakage current acc. to PE with given Uc 2 μA Declaration SIL 2 acc. to EXIDA FMEDA
Nominal discharge surge current In (8/20) μs 5 kA
(core-core) Environmental Conditions
Nominal discharge surge current In (8/20) μs 5 kA Ambient temperature -40…+80 °C
(core-ground) Storage temperature -40…+80 °C
Total surge current (8/20) μs 20 kA
Total surge current (10/350) μs 1 kA
Mechanical data
Discharge surge current Imax (8/20)μs (core-to- 10 kA
Tightening torque 0.8 Nm
core)
Discharge surge current Imax (8/20)μs (core-to- 10 kA Electrical connection screw terminals
earth) Terminal cross-section 2.5 mm2
Nominal pulse current Ian (10/1000) μs (core- 50 A Housing material plastic
core) Mounting instruction for DIN rail
Nominal pulse current Ian (10/1000) μs (core- 50 A
Protection class IP20
ground)
Lightning test current (10/350)μs, peak current 500 A Flammability class acc. to UL 94 V-0
Iimp Dimensions 6.2 x 93.1 x 102.5 mm
Output voltage limitation 1kV/μs (core-to- ≤ 60 V Approval | Certification ATEX, IECEx, UL
core)
Output voltage limitation 1kV/μs (core-to-earth) ≤ 650 V
Residual voltage In (core-to-core) ≤ 70 V
Residual voltage Ian (core-to-core) ≤ 50 V
Protection level UP C2 - 10 kV/5 kA (core-core) ≤ 70 V (C2 - 10 kV / 5 kA)
Protection level UP C3 - 10 A (core-core) ≤ 50 V (C3 - 10 A)
Protection level UP D1 - 500 A (core-core) ≤ 80 V (D1 - 500 A)
Protection level UP C1 - 500 V/250 A (core- ≤ 650 V (C1 - 500 V / 250 A)
ground)
Protection level UP C2 - 10 kV/5 kA (core-ground) ≤ 700 V (C2 - 10kV / 5 kA)
Protection level UP D1 - 500 A (core-ground) ≤700 V (D1 - 500 A)
Interface technology
Response time tA (core-to-core) ≤ 1 ns
Response time tA (core-to-earth) ≤ 100 ns
Insertion loss aE, sym. Typ 0.7 dB (1 MHz / 50 Ω)
Insertion loss aE, sym. Typ. 0.3 dB (350 MHz / 150Ω)
Cutoff frequency fg (3dB), asym. (GND) 50 Ω Typ. 6 MHz
system
Cutoff frequency fg (3dB), asym. (GND) 150 Ω Typ. 2 MHz
system
Capacitance ≤1.3 nF (per path)
Resistance per path 3.3 Ω 20 %
Required backup fuse, max. 315 mA
Surge protection acc. to IEC 61643-21 (core-to- C2 (10 kV / 5 kA); C3 (25 A)
core)
Surge protection acc. to IEC 61643-21 (core-to- C2 (10 kV / 5 kA); C3 (25 A); D1 (500 A)
earth)
AC protection acc. to IEC 61643-21 5A-1s
▪▪ ATEX, IECEx, UL
▪▪ Nominal voltage 12 VDC
▪▪ For 2 floating signal conductors
7 8
▪▪ IEC category: C1 / C2 / C3 / D1
5 6
▪▪ Flammability class V-0
3 4
1 2
The IMSP-2‑12 is a surge protection mod‑ The devices are IP20 protected and can The only 6.2 mm slim housing can be
ule, designed for the MSR t echnology. It be installed in Ex as well as non-Ex areas. mounted on DIN rail acc. to DIN NS35.
protects two 12 V operated floating sig‑
nal conductors.
470 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IMSP series
Technical data
Type IMSP-2-12 Approvals and declarations
Ident no. 7504054 Ex approval acc. to conformity certificate DEKRA 11 ATEX 0016 X
Device designation É II 1 G, II 1 D Ex ia IIC T4…T6; Ex
Nominal voltage Un 12 VDC iaD 20 T85°C…T135°C
IEC category C1; C2; C3; D1 Max. values: Terminal connection: 5+7 / 6+8
Surge arrester, rated voltage Uc 13 VAC / 18 VDC Max. input voltage Ui ≤ 18 V
Max. input current Ii ≤ 500 mA
Nominal current In (≤ 40 °C) 500 mA Max. input power Pi ≤ 635 mW
Active current Ic with given Uc 2 μA (per path) Internal inductance/capacitance Li/Ci Li = 1 µH; Ci = 3 nF
Leakage current acc. to PE with given Uc 2 μA Declaration SIL 2 acc. to EXIDA FMEDA
Nominal discharge surge current In (8/20) μs 350 A
(core-core) Environmental Conditions
Nominal discharge surge current In (8/20) μs 5 kA Ambient temperature -40…+80 °C
(core-ground) Storage temperature -40…+80 °C
Total surge current (8/20) μs 20 kA
Total surge current (10/350) μs 1 kA
Mechanical data
Discharge surge current Imax (8/20)μs (core-to- 350 A
Tightening torque 0.8 Nm
core)
Discharge surge current Imax (8/20)μs (core-to- 10 kA Electrical connection screw terminals
earth) Terminal cross-section 2.5 mm2
Nominal pulse current Ian (10/1000) μs (core- 70 A Housing material plastic
core) Mounting instruction for DIN rail
Nominal pulse current Ian (10/1000) μs (core- 50 A
Protection class IP20
ground)
Lightning test current (10/350)μs, peak current 500 A Flammability class acc. to UL 94 V-0
Iimp Dimensions 6.2 x 93.1 x 102.5 mm
Output voltage limitation 1kV/μs (core-to- ≤ 50 V Approval | Certification ATEX, IECEx, UL
core)
Output voltage limitation 1kV/μs (core-to-earth) ≤ 650 V
Residual voltage In (core-to-core) ≤ 50 V
Residual voltage Ian (core-to-core) ≤ 50 V
Protection level UP C1 - 500 V/250 A (core-core) ≤ 50 V (C1‑500 V / 250 A)
Protection level UP C1 - 500 V/250 A (core- ≤ 650 V (C1 - 500 V / 250 A)
ground)
Protection level UP C2 - 10 kV/5 kA (core-ground) ≤ 650 V (C2 - 10 kV / 5 kA)
Protection level UP D1 - 500 A (core-ground) ≤700 V (D1 - 500 A)
Interface technology
Insertion loss aE, sym. Typ 0.1 dB (1 MHz / 50 Ω)
Insertion loss aE, sym. Typ. 0.1 dB (300 kHz / 150 Ω)
Cutoff frequency fg (3dB), asym. (GND) 50 Ω Typ. 5 MHz
system
Cutoff frequency fg (3dB), asym. (GND) 150 Ω Typ. 1.5 MHz
system
Capacitance ≤1.5 nF (per channel)
Resistance per path 0Ω
Required backup fuse, max. 500 mA
Surge protection acc. to IEC 61643-21 (core-to- C1 (500 V / 250 A); C3 (25 A)
core)
Surge protection acc. to IEC 61643-21 (core-to- C2 (10 kV / 5 kA); C3 (25 A); D1 (500 A)
earth)
AC protection acc. to IEC 61643-21 5A-1s
▪▪ ATEX, IECEx, UL
▪▪ Nominal voltage 24 VDC
▪▪ For 2 floating signal conductors
7 8
▪▪ IEC category: C1 / C2 / C3 / D1
5 6
▪▪ Flammability class V-0
3 4
1 2
The IMSP-2‑24 is a surge protection mod‑ The devices are IP20 protected and can The only 6.2 mm slim housing can be
ule, designed for the MSR t echnology. It be installed in Ex as well as non-Ex areas. mounted on DIN rail acc. to DIN NS35.
protects two 24 V operated floating sig‑
nal conductors.
472 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IMSP series
Technical data
Type IMSP-2-24 Approvals and declarations
Ident no. 7504052 Ex approval acc. to conformity certificate DEKRA 11 ATEX 0016 X
Device designation É II 1 G, II 1 D Ex ia IIC T4…T6; Ex
Nominal voltage Un 24 VDC iaD 20 T85°C…T135°C
IEC category C1; C2; C3; D1 Max. values: Terminal connection: 5+7 / 6+8
Surge arrester, rated voltage Uc 25 VAC / 36 VDC Max. input voltage Ui ≤ 36 V
Max. input current Ii ≤ 500 mA
Nominal current In (≤ 40 °C) 500 mA Max. input power Pi ≤ 635 mW
Active current Ic with given Uc 2 μA (per path) Internal inductance/capacitance Li/Ci Li = 1 µH; Ci = 1.3 nF
Leakage current acc. to PE with given Uc 2 μA Declaration SIL 2 acc. to EXIDA FMEDA
Nominal discharge surge current In (8/20) μs 250 A
(core-core) Environmental Conditions
Nominal discharge surge current In (8/20) μs 5 kA Ambient temperature -40…+80 °C
(core-ground) Storage temperature -40…+80 °C
Total surge current (8/20) μs 10 kA
Total surge current (10/350) μs 1 kA
Mechanical data
Discharge surge current Imax (8/20)μs (core-to- 250 A
Tightening torque 0.8 Nm
core)
Discharge surge current Imax (8/20)μs (core-to- 10 kA Electrical connection screw terminals
earth) Terminal cross-section 2.5 mm2
Nominal pulse current Ian (10/1000) μs (core- 50 A Housing material plastic
core) Mounting instruction for DIN rail
Nominal pulse current Ian (10/1000) μs (core- 50 A
Protection class IP20
ground)
Lightning test current (10/350)μs, peak current 500 A Flammability class acc. to UL 94 V-0
Iimp Dimensions 6.2 x 93.1 x 102.5 mm
Output voltage limitation 1kV/μs (core-to- ≤ 60 V Approval | Certification ATEX, IECEx, UL
core)
Output voltage limitation 1kV/μs (core-to-earth) ≤ 650 V
Residual voltage In (core-to-core) ≤ 60 V
Residual voltage Ian (core-to-core) ≤ 60 V
Protection level UP C1 - 500 V/250 A (core-core) ≤ 60 V (C1 - 500 V / 250 A)
Protection level UP C3 - 10 A (core-core) ≤ 60 V (C3 - 10 A)
Protection level UP C1 - 500 V/250 A (core- ≤ 650 V (C1 - 500 V / 250 A)
ground)
Protection level UP C2 - 10 kV/5 kA (core-ground) ≤ 650 V (C2 - 10 kV / 5 kA)
Protection level UP D1 - 500 A (core-ground) ≤700 V (D1 - 500 A)
Interface technology
Response time tA (core-to-earth) ≤ 100 ns
Insertion loss aE, sym. Typ 0.1 dB (1 MHz / 50 Ω)
Insertion loss aE, sym. Typ. 0.1 dB (450 kHz / 150 Ω)
Cutoff frequency fg (3dB), asym. (GND) 50 Ω Typ. 7.5 MHz
system
Cutoff frequency fg (3dB), asym. (GND) 100 Ω Typ. 2.5 MHz
system
Capacitance ≤1.3 nF (per path)
Resistance per path 0Ω
Required backup fuse, max. 500 mA
Surge protection acc. to IEC 61643-21 (core-to- C1 (500 V / 250 A); C3 (25 A)
core)
Surge protection acc. to IEC 61643-21 (core-to- C2 (10 kV / 5 kA); C3 (25 A); D1 (500 A)
earth)
AC protection acc. to IEC 61643-21 5A-1s
▪▪ ATEX, IECEx, UL
▪▪ Nominal voltage 24 VDC
▪▪ For two floating 2‑wire signal circuits
7 8 ▪▪ IEC category: C1 / C2 / C3 / D1
2 2 ▪▪ Flammability class V-0
5 6 ▪▪ HART® transmissible
3 4
1 1
1 2
The IMSP-2X2‑24 is a surge protection The HART® transmissible d evices are IP20 The only 6.2 mm slim housing can be
module, designed for the MSR technolo‑ rated and can be i nstalled in Ex as well as mounted on DIN rail acc. to DIN NS35.
gy. It protects two floating 2‑wire signal non-Ex areas.
circuits.
474 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IMSP series
Technical data
Type IMSP-2x2-24 Approvals and declarations
Ident no. 7504051 Ex approval acc. to conformity certificate DEKRA 11 ATEX 0016 X
Device designation É II 1 G, II 1 D Ex ia IIC T4…T6; Ex
Nominal voltage Un 24 VDC iaD 20 T85°C…T135°C
IEC category C1; C2; C3; D1 Max. values: Terminal connection: 1…8
Surge arrester, rated voltage Uc 25 VAC / 36 VDC Max. input voltage Ui ≤ 36 V
Max. input current Ii ≤ 350 mA
Nominal current In (≤ 40 °C) 350 mA Max. input power Pi ≤ 3000 mW
Active current Ic with given Uc 2 μA Internal inductance/capacitance Li/Ci Li = 1 µH; Ci = 1.3 nF
Leakage current acc. to PE with given Uc 4 μA Declaration SIL 2 acc. to EXIDA FMEDA
Nominal discharge surge current In (8/20) μs 5 kA
(core-core) Environmental Conditions
Nominal discharge surge current In (8/20) μs 5 kA Ambient temperature -40…+80 °C
(core-ground) Storage temperature -40…+80 °C
Total surge current (8/20) μs 20 kA
Total surge current (10/350) μs 2 kA
Mechanical data
Discharge surge current Imax (8/20)μs (core-to- 10 kA
Tightening torque 0.8 Nm
core)
Discharge surge current Imax (8/20)μs (core-to- 10 kA Electrical connection screw terminals
earth) Terminal cross-section 2.5 mm2
Nominal pulse current Ian (10/1000) μs (core- 50 A Housing material plastic
core) Mounting instruction for DIN rail
Nominal pulse current Ian (10/1000) μs (core- 50 A
Protection class IP20
ground)
Lightning test current (10/350)μs, peak current 500 A Flammability class acc. to UL 94 V-0
Iimp Dimensions 6.2 x 93.1 x 102.5 mm
Output voltage limitation 1kV/μs (core-to- ≤ 60 V Approval | Certification ATEX, IECEx, UL
core)
Output voltage limitation 1kV/μs (core-to-earth) ≤ 650 V
Residual voltage In (core-to-core) ≤ 70 V
Residual voltage Ian (core-to-core) ≤ 50 V
Protection level UP C2 - 10 kV/5 kA (core-core) ≤ 70 V (C2 - 10 kV / 5 kA)
Protection level UP C3 - 10 A (core-core) ≤ 50 V (C3 - 10 A)
Protection level UP D1 - 500 A (core-core) ≤ 80 V (D1 - 500 A)
Protection level UP C1 - 500 V/250 A (core- ≤ 650 V (C1 - 500 V / 250 A)
ground)
Protection level UP C2 - 10 kV/5 kA (core-ground) ≤ 700 V (C2 - 10kV / 5 kA)
Protection level UP D1 - 500 A (core-ground) ≤700 V (D1 - 500 A)
Interface technology
Response time tA (core-to-core) ≤ 1 ns
Response time tA (core-to-earth) ≤ 100 ns
Insertion loss aE, sym. Typ 0.7 dB (1 MHz / 50 Ω)
Insertion loss aE, sym. Typ. 0.3 dB (350 MHz / 150Ω)
Cutoff frequency fg (3dB), asym. (GND) 50 Ω Typ. 6 MHz
system
Cutoff frequency fg (3dB), asym. (GND) 150 Ω Typ. 2 MHz
system
Capacitance ≤1.3 nF (per path)
Resistance per path 3.3 Ω 20 %
Required backup fuse, max. 315 mA
Surge protection acc. to IEC 61643-21 (core-to- C2 (10 kV / 5 kA); C3 (25 A)
core)
Surge protection acc. to IEC 61643-21 (core-to- C2 (10 kV / 5 kA); C3 (25 A); D1 (500 A)
earth)
AC protection acc. to IEC 61643-21 5A-1s
▪▪ ATEX, IECEx, UL
▪▪ Nominal voltage 24 VDC
7 8 ▪▪ For 4 floating signal conductors
▪▪ IEC category: C1 / C2 / C3 / D1
5 6 ▪▪ Flammability class V-0
3 4
1 2
The IMSP-4‑24 is a surge protection mod‑ The devices are IP20 protected and can The only 6.2 mm slim housing can be
ule, designed for the MSR t echnology. It be installed in Ex as well as non-Ex areas. mounted on DIN rail acc. to DIN NS35.
protects four 24 V operated floating sig‑
nal conductors.
476 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IMSP series
Technical data
Type IMSP-4-24 Approvals and declarations
Ident no. 7504053 Ex approval acc. to conformity certificate DEKRA 11 ATEX 0016 X
Device designation É II 1 G, II 1 D Ex ia IIC T4…T6; Ex
Nominal voltage Un 24 VDC iaD 20 T85°C…T135°C
IEC category C1; C2; C3; D1 Max. values: Terminal connection: 1…8
Surge arrester, rated voltage Uc 25 VAC / 36 VDC Max. input voltage Ui ≤ 36 V
Max. input current Ii ≤ 500 mA
Nominal current In (≤ 40 °C) 500 mA Max. input power Pi ≤ 550 mW
Active current Ic with given Uc 2 μA (per path) Internal inductance/capacitance Li/Ci Li = 1 µH; Ci = 2.5 nF
Leakage current acc. to PE with given Uc 4 μA Declaration SIL 2 acc. to EXIDA FMEDA
Nominal discharge surge current In (8/20) μs 250 A
(core-core) Environmental Conditions
Nominal discharge surge current In (8/20) μs 5 kA Ambient temperature -40…+80 °C
(core-ground) Storage temperature -40…+80 °C
Total surge current (8/20) μs 20 kA
Total surge current (10/350) μs 2 kA
Mechanical data
Discharge surge current Imax (8/20)μs (core-to- 250 A
Tightening torque 0.8 Nm
core)
Discharge surge current Imax (8/20)μs (core-to- 10 kA Electrical connection screw terminals
earth) Terminal cross-section 2.5 mm2
Nominal pulse current Ian (10/1000) μs (core- 50 A Housing material plastic
core) Mounting instruction for DIN rail
Nominal pulse current Ian (10/1000) μs (core- 50 A
Protection class IP20
ground)
Lightning test current (10/350)μs, peak current 500 A Flammability class acc. to UL 94 V-0
Iimp Dimensions 6.2 x 93.1 x 102.5 mm
Output voltage limitation 1kV/μs (core-to- ≤ 60 V Approval | Certification ATEX, IECEx, UL
core)
Output voltage limitation 1kV/μs (core-to-earth) ≤ 650 V
Residual voltage In (core-to-core) ≤ 60 V
Residual voltage Ian (core-to-core) ≤ 60 V
Protection level UP C1 - 500 V/250 A (core-core) ≤ 60 V (C1 - 500 V / 250 A)
Protection level UP C3 - 10 A (core-core) ≤ 60 V (C3 - 10 A)
Protection level UP C1 - 500 V/250 A (core- ≤ 650 V (C1 - 500 V / 250 A)
ground)
Protection level UP C2 - 10 kV/5 kA (core-ground) ≤ 650 V (C2 - 10 kV / 5 kA)
Protection level UP D1 - 500 A (core-ground) ≤700 V (D1 - 500 A)
Interface technology
Response time tA (core-to-earth) ≤ 100 ns
Insertion loss aE, sym. Typ 0.1 dB (1 MHz / 50 Ω)
Insertion loss aE, sym. Typ. 0.1 dB (450 kHz / 150 Ω)
Cutoff frequency fg (3dB), asym. (GND) 50 Ω Typ. 7.5 MHz
system
Cutoff frequency fg (3dB), asym. (GND) 100 Ω Typ. 2.5 MHz
system
Capacitance ≤1.3 nF (per path)
Resistance per path 0Ω
Required backup fuse, max. 500 mA
Surge protection acc. to IEC 61643-21 (core-to- C1 (500 V / 250 A); C3 (25 A)
core)
Surge protection acc. to IEC 61643-21 (core-to- C2 (10 kV / 5 kA); C3 (25 A); D1 (500 A)
earth)
AC protection acc. to IEC 61643-21 5A-1s
▪▪ ATEX, IECEx, UL
▪▪ Nominal voltage 12 VDC
7 8 ▪▪ For 4 floating signal conductors
▪▪ IEC category: C1 / C2 / C3 / D1
5 6 ▪▪ Flammability class V-0
3 4
1 2
The IMSP-4‑12 is a surge protection mod‑ The devices are IP20 protected and can The only 6.2 mm slim housing can be
ule, designed for the MSR t echnology. It be installed in Ex as well as non-Ex areas. mounted on DIN rail acc. to DIN NS35.
protects four 12 V operated floating sig‑
nal conductors.
478 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in modular housing
DIN rail devices, IMSP series
Technical data
Type IMSP-4-12 Approvals and declarations
Ident no. 7504055 Ex approval acc. to conformity certificate DEKRA 11 ATEX 0016 X
Device designation É II 1 G, II 1 D Ex ia IIC T4…T6; Ex
Nominal voltage Un 12 VDC iaD 20 T85°C…T135°C
IEC category C1; C2; C3; D1 Max. values: Terminal connection: 1…8
Surge arrester, rated voltage Uc 13 VAC / 18 VDC Max. input voltage Ui ≤ 18 V
Max. input current Ii ≤ 500 mA
Nominal current In (≤ 40 °C) 500 mA Max. input power Pi ≤ 550 mW
Active current Ic with given Uc 2 μA (per path) Internal inductance/capacitance Li/Ci Li = 1 µH; Ci = 6 nF
Leakage current acc. to PE with given Uc 4 μA Declaration SIL 2 acc. to EXIDA FMEDA
Nominal discharge surge current In (8/20) μs 350 A
(core-core) Environmental Conditions
Nominal discharge surge current In (8/20) μs 5 kA Ambient temperature -40…+80 °C
(core-ground) Storage temperature -40…+80 °C
Total surge current (8/20) μs 20 kA
Total surge current (10/350) μs 2 kA
Mechanical data
Discharge surge current Imax (8/20)μs (core-to- 350 A
Tightening torque 0.8 Nm
core)
Discharge surge current Imax (8/20)μs (core-to- 10 kA Electrical connection screw terminals
earth) Terminal cross-section 2.5 mm2
Nominal pulse current Ian (10/1000) μs (core- 70 A Housing material plastic
core) Mounting instruction for DIN rail
Nominal pulse current Ian (10/1000) μs (core- 50 A
Protection class IP20
ground)
Lightning test current (10/350)μs, peak current 500 A Flammability class acc. to UL 94 V-0
Iimp Dimensions 6.2 x 93.1 x 102.5 mm
Output voltage limitation 1kV/μs (core-to- ≤ 50 V Approval | Certification ATEX, IECEx, UL
core)
Output voltage limitation 1kV/μs (core-to-earth) ≤ 650 V
Residual voltage In (core-to-core) ≤ 50 V
Residual voltage Ian (core-to-core) ≤ 50 V
Protection level UP C1 - 500 V/250 A (core-core) ≤ 50 V (C1‑500 V / 250 A)
Protection level UP C3 - 10 A (core-core) ≤ 50 V (C3 - 10 A)
Protection level UP C1 - 500 V/250 A (core- ≤ 650 V (C1 - 500 V / 250 A)
ground)
Protection level UP C2 - 10 kV/5 kA (core-ground) ≤ 650 V (C2 - 10 kV / 5 kA)
Protection level UP D1 - 500 A (core-ground) ≤700 V (D1 - 500 A)
Interface technology
Response time tA (core-to-earth) ≤ 100 ns
Insertion loss aE, sym. Typ 0.1 dB (1 MHz / 50 Ω)
Insertion loss aE, sym. Typ. 0.1 dB (300 kHz / 150 Ω)
Cutoff frequency fg (3dB), asym. (GND) 50 Ω Typ. 5 MHz
system
Cutoff frequency fg (3dB), asym. (GND) 150 Ω Typ. 1.5 MHz
system
Capacitance ≤1.5 nF (per channel)
Resistance per path 0Ω
Required backup fuse, max. 500 mA
Surge protection acc. to IEC 61643-21 (core-to- C1 (500 V / 250 A); C3 (25 A)
core)
Surge protection acc. to IEC 61643-21 (core-to- C2 (10 kV / 5 kA); C3 (25 A); D1 (500 A)
earth)
AC protection acc. to IEC 61643-21 5A-1s
With the highly compact and rugged d e- lation, the devices provide “intrinsically
vices of the IMC series the Ex junction safe“ explosion protection. Field use is
plane can be moved from the control made possible by means of approval to
cabinet directly into the field, thus p ro- 3 GD, i.e. allows use in zone 2/22 p oten-
viding more flexibility to the system. The tially explosive areas caused by c ombusti-
vibration resistant connectors of the IP67 ble dusts or gases (only permissible in
modules ensure safe and reliable opera- combination with the IMC-SG protective
tion, even under harsh environ mental housing).
conditions In addition to the g
alvanic iso-
480 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in a IP67 housing
Short description and table of contents
ule cartridge
Typ Ident-Nr. Beschreibung Seite
IMC-Di-22Ex-PNO/24VDC 7560003 Isolating switching amplifier, 2-channel 486
IMC-DI-22EX-PNC/24VDC 7560010 Isolating switching amplifier, 2-channel 488
IMC-DO-11EX/L 7560008 Solonoid driver, 1-channel 490
IMC-AI-11EX-I/L 7560004 Input analog signal isolator, 1-channel 492
IMC-AIA-11EX-I/24VDC 7560009 Isolating transducer, 1-channel 494
IMC-AO-11EX-I/L 7560006 Ouput analog signal isolator, 1-channel 496
Interface technology
The Interface module cartridge (IMC) se- ard control cabinet solutions – provides
ries opens up new possibilities in the field additional flexibility for the installation.
of process automation: The IS barrier is The IMC modules are highly compact,
moved from the control cabinet directly rugged and IP67 rated. T he vibration re-
to the installation, thus making it possible sistant connectors e nsure safe and relia-
to create further decentralized s tructures ble operation, even under harsh environ-
in the installation. The use of d istributed mental conditions.
IMC modules – in parallel w ith the stand-
In addition to the galvanic isolation, the are available. The IS cables are provided
devices provide “intrinsically safe“ explo with premolded connectors at one end.
sion protection. Field use is made p ossi- Note: Use in zone 2 is only permissible in
ble by means of approval to 3 GD, i.e. al- combination with the IMC-SG protective
lows use in in explosion hazardous areas housing (can be ordered as a separate
(zone 2) with combustible dusts or g ases. accessory).
Different lengths of connection cables
482 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in IP67 housing
Our Strengths – Your Advantages
ngths – Your A
ur Advantages
Wide range of functions
The modules of the IMC series are the interface devices to be installed and
equipped with standard M12 connectors commissioned simply and safely using
for the electrical connection. This e nables plug-and-play.
Interface technology
IMC Interface modul cartridge DI isolating switching amplifier Number of channels on control side
with line monitoring 1 one output channel
SG additional protection for IMC 2 two output channels
housing
AI analog input amplifier Number of channels on field side
AIA isolating transducer 1 one input channel
AO analog output amplifier 2 two input channels
DO digital output/solonoid driver
484 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology in IP67 housing
Type code
de
Ex Device class - PNO Output type / 24VDC Power supply
Ex associated device with P N O PNP transistor output NO 24 VDC supplied with 24 VDC
intrinsically safe field circuits P N C PNP transistor output NC
I analog current output L loop powered, supplied by
0/4…20mA the control circuit
Interface technology
▪▪ ATEX, IECEx, TR CU
▪▪ Installation in zone 2/22
▪▪ Isolating switching amplifier with
M12 x 1 connectors, 2‑channel
▪▪ Line monitored for wire-break/short-
circuit (ON/OFF switchable)
▪▪ PNP transistor output NO
▪▪ Complete galvanic isolation
▪▪ Protection class IP67
The 2‑channel isolating switching ampli- contactors can be connected to the The device must be protected against
fier IMC-Di-22Ex-PNO/24VDC is equipped device. mechanical load on connector and hous-
with intrinsically safe input circuits. ing when mounted in zone 2 or 22. For
The output circuits feature two NO tran- this, use the TURCK cover plate IMC-SG
Sensors according to EN 60947-5-6 (NA- sistors. A green LED indicates operational (ident no. 7560016).
MUR), variable resistors or potential free readiness.
2 2
3 1 1 3
IMC-Di-22Ex-PNO/24VDC
4 5 5 4
486 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Distributed interface modules in IP67 housing
For direct field installation, IMC series
Technical data
Type IMC-Di-22Ex-PNO/24VDC Max. values: M12 female connection: 1+4 / 2+3
Ident no. 7560003 Max.output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 10 mA
Max. output power Po ≤ 24 mW
Power supply
Characteristic linear
Nominal voltage 24 VDC
Internal inductance/capacitance Li/Ci Li = 0.15 mH, Ci = negligibly small
Operating voltage range 20…30 VDC
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Inputs Lo [mH] 5.0 0.85 10 0.85
No-load voltage 8.2 VDC Co [nF] 1400 1900 6600 11000
Short-circuit current 8.2 mA
Ex approval acc. to conformity certificate TÜV 07 ATEX 554027 X
Input resistance 1 kΩ
Approval SIL2 acc. to EXIDA FMEDA
Cable resistance ≤ 50 Ω
Switch-on threshold: 1.55 mA
Switch-off threshold: 1.75 mA Indication
Operational readiness green
Switching state yellow
Outputs
Error indication red
Output circuits (digital) 2 x transistors (pnp, short-circuit
proof)
Switching voltage ≤ 30 VDC Environmental Conditions
Switching current per output ≤ 50 mA Ambient temperature -25…+70 °C
Switching frequency ≤ 3000 Hz Storage temperature -40…+80 °C
Test voltage 2.5 kV
Approvals and declarations MTTF 295 years acc. to SN 29500 (Ed. 99)
40 °C
Ex approval acc. to conformity certificate TÜV 07 ATEX 553447
Device designation É II (1) GD [Ex ia] IIC/IIB
Max. values: M12 female connection: 1+4 / 1+3 Mechanical data
Max. output voltage Uo ≤ 9.6 V Tightening torque 3.5 Nm
Max. output current Io ≤ 10 mA Electrical connection M12 flange connection
Max. output power Po ≤ 24 mW Housing material Polycarbonate/ABS
Rated voltage 250 V Mounting instruction for panel
Characteristic linear Protection class IP67
Internal inductance/capacitance Li/Ci Li = 0.15 mH, Ci = negligibly small Dimensions 32 x 100 x 25 mm
External inductance/capacitance Lo/Co
Ex ia IIC IIB Approval | Certification ATEX, IECEx, TR CU
Lo [mH] 0.85 10 1.85 20
Interface technology
Co [nF] 1100 750 5300 3400
Max. output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 10 mA
Max. output power Po ≤ 24 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 0.15 mH, Ci = negligibly small
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Lo [mH] 5.0 0.85 10 0.85
Co [nF] 1400 1900 6600 11000
Ex approval acc. to conformity certificate TÜV 07 ATEX 554027 X
Application area II 3 GD
Protection type Ex nA [nL] IIC/IIB T4 or rather Ex tD
A22 IP67 T96 °C
▪▪ ATEX, IECEx, TR CU
▪▪ Installation in zone 2/22
▪▪ Isolating switching amplifier with
M12 x 1 connectors, 2‑channel
▪▪ Line monitored for wire-break/short-
circuit (ON/OFF switchable)
▪▪ PNP transistor output, NC
▪▪ Complete galvanic isolation
▪▪ Protection class IP67
The 2‑channel isolating switching ampli- contactors can be connected to the The device must be protected against
fier IMC-DI-22EX-PNC/24VDC is e quipped device. mechanical load on connector and hous-
with intrinsically safe input circuits. ing when mounted in zone 2 or 22. For
The output circuits feature two NO tran- this, use the TURCK cover plate IMC-SG
Sensors according to EN 60947-5-6 (NA- sistors. A green LED indicates operational (ident no. 7560016).
MUR), variable resistors or potential free readiness.
2 2
3 1 1 3
IMC-Di-22Ex-PNC/24VDC
4 5 5 4
488 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Distributed interface modules in IP67 housing
For direct field installation, IMC series
Technical data
Type IMC-DI-22EX-PNC/24VDC Max. values: M12 female connection: 1+4 / 2+3
Ident no. 7560010 Max.output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 10 mA
Max. output power Po ≤ 24 mW
Power supply
Characteristic linear
Nominal voltage 24 VDC
Internal inductance/capacitance Li/Ci Li = 0.15 mH, Ci = negligibly small
Operating voltage range 20…30 VDC
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Inputs Lo [mH] 5.0 0.85 10 0.85
No-load voltage 8.2 VDC Co [nF] 1400 1900 6600 11000
Short-circuit current 8.2 mA
Ex approval acc. to conformity certificate TÜV 07 ATEX 554027 X
Input resistance 1 kΩ
Approval SIL2 acc. to EXIDA FMEDA
Cable resistance ≤ 50 Ω
Switch-on threshold: 1.55 mA
Switch-off threshold: 1.75 mA Indication
Operational readiness green
Switching state yellow
Outputs
Error indication red
Output circuits (digital) 2 x transistors (pnp, short-circuit
proof)
Switching voltage ≤ 30 VDC Environmental Conditions
Switching current per output ≤ 50 mA Ambient temperature -25…+70 °C
Switching frequency ≤ 3000 Hz Storage temperature -40…+80 °C
Test voltage 2.5 kV
Approvals and declarations MTTF 295 years acc. to SN 29500 (Ed. 99)
40 °C
Ex approval acc. to conformity certificate TÜV 07 ATEX 553447
Device designation É II (1) GD [Ex ia] IIC/IIB
Max. values: M12 female connection: 1+4 / 2+3 Mechanical data
Max. output voltage Uo ≤ 9.6 V Tightening torque 3.5 Nm
Max. output current Io ≤ 10 mA Electrical connection M12 flange connection
Max. output power Po ≤ 24 mW Housing material Polycarbonate/ABS
Rated voltage 250 V Mounting instruction for panel
Characteristic linear Protection class IP67
Internal inductance/capacitance Li/Ci Li = 0.15 mH, Ci = negligibly small Dimensions 32 x 100 x 25 mm
External inductance/capacitance Lo/Co
Ex ia IIC IIB Approval | Certification ATEX, IECEx, TR CU
Lo [mH] 0.85 10 1.85 20
Interface technology
Co [nF] 1100 750 5300 3400
Max. output voltage Uo ≤ 9.6 V
Max. output current Io ≤ 10 mA
Max. output power Po ≤ 24 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Li = 0.15 mH, Ci = negligibly small
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Lo [mH] 5.0 0.85 10 0.85
Co [nF] 1400 1900 6600 11000
Ex approval acc. to conformity certificate TÜV 07 ATEX 554027 X
Application area II 3 GD
Protection type Ex nA [nL] IIC/IIB T4 or rather Ex tD
A22 IP67 T96 °C
▪▪ ATEX, IECEx, TR CU
▪▪ Installation in zone 2/22
▪▪ Valve control module with
M12 x 1 connectors, 1‑channel
▪▪ Complete galvanic isolation
▪▪ Protection class IP67
The 1‑channel solonoid driver IMC-DO- The device must be protected against Typical applications are the control of Ex
11Ex/L features an intrinsically safe out- mechanical load on connector and hous- i pilot valves and pilot lights as well as the
put circuit. The device can be m
ounted in ing when mounted in zone 2 or 22. For supply of transmitters.
zone 2. this, use the TURCK cover plate IMC-SG
(ident no. 7560016). The device is loop-powered. External
power supply is not required.
2 2
3 1 1 3
Zone 2/22: Do not disconnect, when live!
4 5 5 4
IMC-DO-11Ex/L
490 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Distributed interface modules in IP67 housing
For direct field installation, IMC series
Technical data
Type IMC-DO-11EX/L Max. values: M12 female connection: 1+3
Ident no. 7560008 Max.output voltage Uo ≤ 27 V
Max. output current Io ≤ 95 mA
Max. output power Po ≤ 674 mW
Power supply
Characteristic trapezoidal
Nominal voltage 24 VDC loop-powered
Internal inductance/capacitance Li/Ci negligibly small
Power consumption ≤ 1.3 W
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Inputs Lo [mH] 4.0 0.5 20 5
0-signal 0…5 VDC Co [nF] 74 130 490 630
1-signal 20…30 VDC
max.Output voltage Uo ≤ 27 V
Voltage input max. 30 VDC
max. Output current Io ≤ 95 mA
Current input 45 mA
max. Output power Po ≤ 674 mW
Input delay ≤ 1 ms
Approval SIL3 acc. to EXIDA FMEDA
Outputs
Indication
Output circuits intrinsically safe acc. to EN 60079
Switching state yellow
Output current 40 mA
Output voltage 24 V
Output curve Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
Test voltage 2.5 kV
MTTF 326 years acc. to SN 29500 (Ed. 99)
40 °C
Response characteristic
Mechanical data
Limit frequency ≤ 500 Hz
Tightening torque 3.5 Nm
Measuring accuracy ≤ 0.1 % of full scale
Electrical connection M12 flange connection
Housing material Polycarbonate/ABS
Approvals and declarations Mounting instruction for panel
Ex approval acc. to conformity certificate TÜV 07 ATEX 553265 Protection class IP67
Device designation É II (1) GD [Ex ia] IIC/IIB Dimensions 32 x 100 x 25 mm
Max. values: M12 female connection: 1+3
Max. output voltage Uo ≤ 27 V
Approval | Certification ATEX, IECEx, TR CU
Max. output current Io ≤ 95 mA
Interface technology
Max. output power Po ≤ 674 mW
Rated voltage 250 V
Characteristic Trapezoidal
Internal inductance/capacitance Li/Ci negligibly small
External inductance/capacitance Lo/Co
Ex ia IIC IIB
Lo [mH] 0.75 0.5 2 0.5
Co [nF] 60 70 310 450
Characteristic Trapezoidal
Internal inductance/capacitance Li/Ci negligibly small
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Lo [mH] 4.0 0.5 20 5
Co [nF] 74 130 490 630
Ex approval acc. to conformity certificate TÜV 07 ATEX 553647 X
Application area II 3G, II 3D
Protection type Ex nA [nL] IIC/IIB T4 or rather Ex tD
A22 IP67 T86 °C
▪▪ ATEX, IECEx, TR CU
▪▪ Installation in zone 2/22
▪▪ Analog signal isolator with
M12 x 1 connectors, 1‑channel
▪▪ Input circuit: 0/4…20 mA
▪▪ Output circuit: 0/4…20 mA
▪▪ Complete galvanic isolation
▪▪ Protection class IP67
The 1‑channel analog signal isolator I MC- this, use the TURCK cover plate IMC-SG Intrinsically save analog data transmit-
AI-11EX-I/L features an intrinsically safe (Ident no. 7560016). ters can be connected to the device in
input circuit. The device can be mounted the Ex area.
in zone 2. The standard current signal is transmit-
ted from the Ex-area to the safe area The device is loop-powered.
The device must be protected against without attenuation (1:1). The output cir-
mechanical load on connector and hous- cuit is equipped with a short-circuit pro-
ing when mounted in zone 2 or 22. For tected power source.
2 2
3 1 1 3
Zone 2/22: Do not disconnect, when live!
4 5 5 4
IMC-AI-11Ex-i/L
492 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Distributed interface modules in IP67 housing
For direct field installation, IMC series
Mechanical data
Power supply Tightening torque 3.5 Nm
Nominal voltage 24 VDC loop-powered Electrical connection M12 flange connection
Power consumption ≤ 3 W Housing material Polycarbonate/ABS
Mounting instruction for panel
Inputs Protection class IP67
Voltage input max. 30 VDC Dimensions 32 x 100 x 25 mm
Current input 0…20 mA
Approval | Certification ATEX, IECEx, TR CU
Outputs
Load resistance, current output ≤ 0.4 kΩ
Output voltage max. 13 VDC
Output current 0…20 mA
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale
Reference temperature 23 °C
Temperature drift ≤ 0.005 % / K
Rise time (10-90%) ≤ 10 ms
Dropout time (90…10%) ≤ 10 ms
Interface technology
Protection type Ex nA [nL] IICIIB T4 or rather Ex tDA 22
IB67 T80°C
Max. values: M12 female connection: 2+4
Max. input voltage Ui ≤ 27 V
Max. input current Ii ≤ 150 mA
Max. input power Pi ≤ 1000 mW
Approval SIL2 acc. to EXIDA FMEDA
Environmental Conditions
Ambient temperature -25…+70 °C
Storage temperature -40…+80 °C
▪▪ ATEX, IECEx, TR CU
▪▪ Installation in zone 2/22
▪▪ Isolating transducer with
M12 x 1 connectors, 1‑channel
▪▪ Output circuit: 0/4…20 mA
▪▪ Complete galvanic isolation
▪▪ Protection class IP67
The 1‑channel isolating transducer IMC- this, use the TURCK cover plate IMC-SG Intrinsically save analog data transmit-
AIA-11Ex-i/24VDC features an intrinsical- (Ident no. 7560016). ters can be connected to the device in
ly safe input circuit. The device can be the Ex area.
mounted in zone 2. The standard current signal is transmit-
ted from the Ex-area to the safe area The device is designed for a 24 VDC s up-
The device must be protected against without attenuation (1:1). The output cir- ply. A green LED indicates operational
mechanical load on connector and hous- cuit is equipped with a short-circuit pro- readiness.
ing when mounted in zone 2 or 22. For tected power source.
2 2
3 1 1 3
Zone 2/22: Do not disconnect, when live!
IMC-AIA-11Ex-i/24VDC
4 5 5 4
494 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Distributed interface modules in IP67 housing
For direct field installation, IMC series
Technical data
Type IMC-AIA-11EX-I/24VDC Max. values: M12 female connection: 1+2
Ident no. 7560009 Max.output voltage Uo ≤ 21.8 V
Max. output current Io ≤ 64.5 mA
Max. output power Po ≤ 1130 mW
Power supply
Characteristic trapezoidal
Nominal voltage 24 VDC
Internal inductance/capacitance Li/Ci Li = negligibly small; Ci = 11 nF
Operating voltage range 20…30 VDC
External inductance/capacitance Lo/Co Ci = 11nF, Li = negligibly small
Power consumption ≤ 1.5 W
Approval SIL2 acc. to EXIDA FMEDA
Inputs
Indication
Supply voltage ≤ 14 V / 20 mA
Operational readiness green
Current 25 mA
Current input 4…20 mA
Environmental Conditions
Ambient temperature -25…+70 °C
Outputs
Storage temperature -40…+80 °C
Load resistance, current output ≤ 0.5 kΩ
Test voltage 2.5 kV
Output current 0…20 mA
MTTF 294 years acc. to SN 29500 (Ed. 99)
40 °C
Response characteristic
Measuring accuracy ≤ 0.1 % of full scale Mechanical data
Reference temperature 23 °C Tightening torque 3.5 Nm
Temperature drift ≤ 0.005 % / K Electrical connection M12 flange connection
Rise time (10-90%) ≤ 10 ms Housing material Polycarbonate/ABS
Dropout time (90…10%) ≤ 10 ms Mounting instruction for panel
Protection class IP67
Approvals and declarations Dimensions 32 x 100 x 25 mm
Ex approval acc. to conformity certificate TÜV 07 ATEX 553644
Device designation É II (1) GD [Ex ia] IIB Approval | Certification ATEX, IECEx, TR CU
Max. values: M12 female connection: 1+2
Max. output voltage Uo ≤ 21.8 V
Max. output current Io ≤ 64.5 mA
Max. output power Po ≤ 1130 mW
Rated voltage 250 V
Characteristic Trapezoidal
Internal inductance/capacitance Li/Ci Li = negligibly small; Ci = 11 nF
Interface technology
External inductance/capacitance Lo/Co
Ex ia IIB
Lo[mH] 5.8 0.2
Co[nF] 469 799
Max. output voltage Uo ≤ 21.8 V
Max. output current Io ≤ 64.5 mA
Max. output power Po ≤ 1130 mW
Characteristic linear
Internal inductance/capacitance Li/Ci Ci = 11nF, Li = negligibly small
External inductance/capacitance Lo/Co
Ex nL IIC IIB
Lo [mH] 0.85 0.2 22 10
Co [nF] 129 219 800 1200
Ex approval acc. to conformity certificate TÜV 07 ATEX 554129 X
Application area II 3G, II 3D
Protection type Ex nA [nL] IIB/IIC T4 or rather Ex tD
A22 IP67 T 80 °C Dc
▪▪ ATEX, IECEx, TR CU
▪▪ Installation in zone 2/22
▪▪ Analog signal isolator with
M12 x 1 connectors, 1‑channel
▪▪ Input circuit: 0/4…20 mA
▪▪ Output circuit: 0/4…20 mA
▪▪ Complete galvanic isolation
▪▪ Protection class IP67
The 1‑channel analog signal isolator I MC- this, use the TURCK cover plate IMC-SG Intrinsically analog actuators like I/P con-
AO-11Ex-i/L features an intrinsically safe (Ident no. 7560016). verters (e.g. at control valves) or displays
output circuit. The device can be m
ount- can be applied in the Ex area.
ed in zone 2. The normalized current signal is trans-
mitted, galvanically isolated 1:1, from the The device is loop-powered.
The device must be protected against non-Ex to the Ex-area. The output circuit
mechanical load on connector and hous- is equipped with a short- circuit proof
ing when mounted in zone 2 or 22. For power source.
2 2
3 1 1 3
Zone 2/22: Do not disconnect, when live!
4 5 5 4
IMC-AO-11Ex-i/L
496 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Distributed interface modules in IP67 housing
For direct field installation, IMC series
Technical data
Type IMC-AO-11EX-I/L External inductance/capacitance Lo/Co
Ident no. 7560006 Ex ia IIC IIB
Lo [mH] 5 0.5 10 1.0
Power supply Co [nF] 510 1200 2900 5800
Nominal voltage 24 VDC loop-powered Approval SIL2 acc. to EXIDA FMEDA
Power consumption ≤ 3.5 W
Environmental Conditions
Inputs Ambient temperature -25…+70 °C
Voltage input max. 30 VDC Storage temperature -40…+80 °C
Current input 0…20 mA Test voltage 2.5 kV
MTTF 566 years acc. to SN 29500 (Ed. 99)
40 °C
Outputs
Load resistance, current output ≤ 0.4 kΩ
Output current 0…20 mA Mechanical data
Tightening torque 3.5 Nm
Electrical connection M12 flange connection
Response characteristic Housing material Polycarbonate/ABS
Measuring accuracy ≤ 0.1 % of full scale Mounting instruction for panel
Reference temperature 23 °C Protection class IP67
Temperature drift ≤ 0.005 % / K Dimensions 32 x 100 x 25 mm
Rise time (10-90%) ≤ 10 ms
Dropout time (90…10%) ≤ 10 ms
Approval | Certification ATEX, IECEx, TR CU
Interface technology
Lo [mH] 2 0.2 2 0.2
Co [nF] 420 910 2700 5500
Ex approval acc. to conformity certificate TÜV 07 ATEX 553946 X
Application area II 3G, II 3D
Protection type Ex nA [nL] IIC/IIB T4 or rather Ex tD
A22 IP67 T80°C
Max. values: M12 female connection: 1+3
Max.output voltage Uo ≤ 13.3 V
Max. output current Io ≤ 97 mA
Max. output power Po ≤ 322 mW
Characteristic linear
Internal inductance/capacitance Li/Ci negligibly small
Accessori
WM1
WIDERSTANDSMODUL
0912101
IM-3-CJT
6900524
The resistor module WM1 meets the requirements
for line monitoring between a mechanical contact
and a TURCK signal processor. The input circuit of
the signal processor is designed for sensors acc. to
EN 60947‑5‑6 (NAMUR) and equipped with a wire-
break and short-circuit monitoring function.
IM-PROG III The IM-PROG is intended for the parametrization
7525111 of TURCK devices with PACTware™ via
the serial interface of a PC.
498 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Interface technology
Interface Technology – Accessories
e Technology –
gy – Accessories
ies
IMC-SG
7560016
SC-M12/3GD
6900390
Metal cover plate for IMC modules (required for ap‑
plication in zones 2/22)
Interface technology
Basics of explosion
Basics of explosion protection Basics o
protectio
Directives and standards ▪▪ The legislator responsible for industrial supervision, trade orga-
nizations, TÜV and experts as supervisory authorities.
Development of directives ▪▪ All plant personnel are required to act responsibly and observe
precautionary measures such as smoking restrictions and work
Up to the end of 1975, only national regulations covering the f ield regulations during the servicing and operation of electrical
of explosion protection existed in the individual European states. equipment located in the hazardous area.
On 18 December 1975, the first framework directive for above ▪▪ Plant builders who must meet safety requirements according
ground explosion protection came into effect, and b ecame appli- to EN 60079-14, (RL 1999/92/EC), ATEX 137.
cable in the member states of the European Union: Directive ▪▪ The manufacturers of components subject to construction re-
76/117/EEC. quirements set forth by IEC/EN 60079 and ATEX 95a (RL 94/9/
EC).
By 1990 Directive 76/117/EEC had been modified several times.
This directive referred to the characteristics and structure of the EN 60079-14 and DIN VDE 0165 – Installation of electrical
equipment at issue and was directly related to standards which equipment in explosion hazardous areas
applied exclusively to electrical equipment and explosion p rotec-
tion (except mining). As national regulations were still in force, the The DIN VDE 0165 standard includes the safety requirements that
free transport of goods was still restricted. must be observed (e.g. classification of explosion hazardous areas
into zones, temperature classes, cable routing, requirements for
At the beginning of 1994, the “Framework Directive 94/9/EC of the the installation of electrical devices in zones 0, 1 a nd 2, many spe-
European Parliament and Council of 23 March 1994 on the appro- cific provisions). Unlike the standards described a bove, which are
ximation of laws of the Member States concerning equipment and primarily for manufacturers, this standard applies to plant buil-
protective systems intended for use in potentially explosive at- ders, operators and test personnel.
mospheres” was passed. This directive refers to the “Single Euro-
pean Act” of 1985 in accordance with Article 100a of the First Tre- The rules for the interconnection are based on the installation re-
aty for Establishing the European Community in the version of quirements of IEC 60079-14 and EN 60079-14. These stipulate that
February 7, 1992. “ATEX 100a” is the standard abbreviation (ATEX the safety-related maximum values of the input and output para-
derived from the French term “atmosphère explosible”). Besides meters of the equipment must be compared in order to a ssess if
Article 100a, there are other articles that have not been transposed the interconnection of several devices with intrinsically safe cir-
in directives. In TURCK catalogs, the t erm ATEX always refers to the cuits complies with the requirements of intrinsic safety.
regulations pertaining to ATEX 100a.
Ordinance on Industrial Safety and Health – (BetrSichV)
The ATEX 100a Directive was integrated into national laws in the
The industrial safety ordinance BetrSichV governs the health and
individual Member States of the EU, such as in Germany, with the
safety aspects of the provision of work equipment and its use at
Gerätesicherheitsgesetz (§11 GSGV - Equipment Safety Law) –
work. Furthermore BetrSichV regulates the operation of e quip-
since 1 December 2011, Produktsicherheitsgesetz (§34 ProdSG –
ment requiring supervision and the organization of o ccupational
Product Safety Law) – and the Explosionsschutzverordnung ExVO
health and safety precautions.
(11. ProdSV - Explosion Protection Ordinance).
ATEX 137 – Directive for plant operators
The validity of the previous regulations for explosion protection
expired on 30.06.2003. ATEX 100a came into force on 1 July 2003, The 1999/92/EC Directive of the European Parliament and Council,
and was superseded by ATEX 95a. dated 16 December 1999, describes the minimum health and safe-
ty requirements for improving the health and safety of employees
Efforts to harmonize explosion protection regulations worldwide exposed to the potential hazards of a potentially explosive atmos-
led to the creation of IEC 60079. The aim here is to enable the free phere (previously ATEX 118, now ATEX 137). The directive is aimed
movement of goods worldwide. The IECEx scheme specifying ap- at plant operators and employers and s tipulates the requirements
proval requirements for equipment was first of all defined for t his to be observed. These include the assessment of the risks resulting
purpose. This also stipulates the provision of a quality manage- from a potentially explosive a tmosphere, the classification of areas
ment system which is binding for the manufacturer. exposed to potentially explosive atmospheres, and the keeping of
an explosion protection document.
Installation and operation of electrical equipment in hazar-
dous areas – standards and regulations
500 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Basics of explosion protection
Terms and explanations
of explosion
protection
on
The explosion protection ordinance – ExVO (11. ProdSV) Definition of terms
The explosion protection ordinance – ExVO (11. ProdSV) regulates
Explosion
the placing on the market of devices, protective s ystems and com-
ponents intended for use in potentially explosive atmospheres By an explosion is meant an exothermic reaction of material (gas,
and is the German transposition of the Directive 94/9/EC. The ordi- vapor, mist or dust) that takes place at a very high speed of reac-
nance describes the essential health a nd safety requirements and tion. The risk of an explosion exists wherever there is the p
robabi-
mandatory conformity assessment procedures. The explosion pro- lity of an explosive atmosphere. This is possible wherever dust,
tection ordinance is therefore mainly aimed at manufacturers of flammable gases or liquids are manufactured, processed, trans-
devices, maintenance, test and s ales personnel. ported or stored. Such hazardous atmospheres can be present for
instance in chemical industries, gas stations, refineries, power
Like Directive 94/9/EC, the explosion protection ordinance exclu- plants, paint shops, vehicles, sewage plants, grain mills, airports,
des the following equipment from its scope. The following is an grain silos and filling plants.
extract of exceptions: medical devices, explosive substances, o r
unstable chemicals, personal protective equipment, seagoing ves- Explosion hazards
sels, offshore systems and products for military.
Explosion hazards only exist in locations
EN 60079-0 – Electrical equipment for explosive atmosphe- ▪▪ in which ignitable concentrations of flammable substances can
res, general requirements exist under normal operating conditions or in the event of
faults, and when these conditions provide the probability that
EN 60079-0 lays down general requirements for the design and a dangerous substance to air mixture is enough to form an ex-
testing of electrical equipment required for the hazardous area. plosive mixture;
The following standards of the EN 60079 series describe the tech-
nical implementation of different protection types:
▪▪ where the explosive or ignitable mixtures can come in contact
with a source of ignition and continue to burn after ignition.
▪▪ Flameproof enclosure (EN 60079-1)
▪▪ Pressurized enclosure (EN 60079-2) Explosive mixture (generic term)
▪▪ Powder filling (EN 60079-5)
▪▪ Oil immersion (EN 60079-6) An explosive mixture is a mixture of gases or vapors, mists or d
usts,
▪▪ Increased safety(EN 60079-7) capable of propagating a reaction after ignition.
▪▪ Intrinsic safety (EN 60079-11)
▪▪ Protection type n (EN 60079-15) Potentially explosive atmosphere
▪▪ Encapsulation(EN 60079-18)
▪▪ Intrinsically safe electrical systems (EN 60079-25) A potentially explosive atmosphere contains gases, vapors, mists
▪▪ Optical radiation (EN 60079-28) or dusts mixed with air, as well as the usual filler materials that can
explode spontaneously under atmospheric conditions (see a lso
EN 60079-11 – Intrinsic safety “i” ‘Explosive mixture’). This can occur wherever dust, f lammable ga-
ses or liquids are manufactured, processed, t ransported or stored.
Apart from the „intrinsic safety“ ignition protection, all methods of
protection attempt to “contain” an explosion on the inside of t he Potentially explosive atmosphere (hazardous)
housing and to prevent the penetration of an ignitable gaseous
mixture. A hazardous explosive atmosphere is a mixture containing con-
centrations of flammable gases or vapors that, when ignited, can
Ex protection
Protection with “intrinsic safety” is based on a different approach: cause damage to persons directly or indirectly through an e xplosi-
It limits the electrical energy in a circuit to such an extent, that in- on (see also ‘Hazardous explosive atmosphere’).
creased temperatures, sparks or arcs are incapable of generating
the energy needed to ignite a potentially explosive a tmosphere. Hazardous area
Due to the limitation of electrical energy, these circuits are mainly A hazardous area is an area in which there is a risk of explosion, i .e.
suited for use in the field of measuring, control and instrumentati- a hazardous explosive atmosphere can occur due to local o pera-
on and offer some considerable advantages c ompared to other ting conditions. Such hazardous atmospheres can be present for
protection types. An intrinsically safe circuit can therefore be instance in chemical industries, gas stations, refineries, power
maintained or connected under live conditions w ithout the need plants, paint shops, vehicles, sewage plants, grain mills, airports,
for a hot work permit; the easy-to-use systems are also economical grain silos and filling plants.
thanks to the use of inexpensive components. Last but not least,
there are also many suppliers of components with protection type
“i”.
An ignition is only possible if three factors are present at the same Secondary explosion protection consists of measures with which
time: the ignition of a hazardous atmosphere is prevented. For this pur-
oxygen pose the electrical equipment is designed so that
▪▪ the equipment does not form an effective ignition source and
the combining of ignition source and potentially explosive at-
mosphere is prevented.
▪▪ the penetration of ignition into the surrounding explosive at-
mosphere is prevented.
(see also ‘Primary explosion protection’)
Primary explosion protection consists of measures with which t he Simple components and simple equipment that do not generate
formation of a hazardous atmosphere can be prevented: or store more than 1.5 V, 0.1 A and 25 mW do not require a test
▪▪ Avoiding the use of flammable liquids certificate and are classified as “simple electrical equipment” (e.g.
▪▪ Increasing the flash point thermocouples). This equipment is defined in the standard EN
▪▪ Limiting the concentration 60079-14.
▪▪ Natural and technical ventilation
▪▪ Monitoring the concentration…
(see also ‘Secondary explosion protection’)
502 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Basics of explosion protection
Terms and explanations
Categories
The subdivision of group II equipment is based on the different
Intrinsically safe and associated electrical equipment are subdivi- ignition energy of the flammable materials. The different groups
ded into three categories according to EN 60079-11. The s ubdivi- are classified by capital letters in ascending alphabetical order ac-
sion is based on the fault probability in the intrinsically safe circuit cording to the hazard risk of the associated materials. Materials
in conjunction with the possibility of ignition. belonging to group C require less ignition energy than Group A
materials. (see Tab. 1)
Category ia
Category “ia” indicates that the electrical equipment should not be T1 T2 T3 T4 T5 T6
able to ignite a dangerous mixture during normal operation, in the methane
I
event of a single fault, and in the event of any combination of two
faults. Intrinsic safety must be maintained when two independent II A acetone, ethyl alcohol, benzines, acetaldehyde,
ethane, i-amyl diesel fuel, ethyl aether
faults occur at the same time. Components of any equipment of ethyl acetate, acetate, aviation
category “ia” that are susceptible to faults must therefore be ammonia, n-butane, fuels,
available in triplicate. benzene, n-butyl fuel oils,
acetic acid, alcohol, n-hexane
Category ib carbon
monoxide,
methanol,
Category “ib” states that no ignition must occur in normal operati- propane,
on in the event of a fault. The intrinsic safety must be e nsured in toluene
the event of a fault. A fault could be the failure of a safety-relevant town gas ethylene*)
II B
component. With category ib equipment, safety-related compo- (coal gas)
nents must therefore be provided in duplicate. II C hydrogen ethylene*) carbon
disulfide*)
Category ic *) no authorized regulations available
Ignition temperature Devices classified as Group I (firedamp) use the prefix M, e.g. M1, i n
addition to the category classification.
The ignition temperature (defined as the temperature at which a
mixture is susceptible to ignition in the course of a defined test The third feature is the Substance group which characterizes the
procedure) is directly related to the temperature class. The tempe- application of devices in particular atmospheres:
rature class indicates the maximum surface temperature of the
electrical equipment and must be lower than the ignition tempe- ▪▪ Substance group G: Explosion protection in potentially explosi-
rature of the flammable material in order to prevent an ignition. ve atmospheres due to gases, vapor or mists (G: Gas)
(see Tab. 2) ▪▪ Substance group D: Explosion protection in potentially explosi-
ve atmospheres due to dusts (D: Dust)
IEC/EN NEC 505-10 Maximum surface Ignition temperatu-
temperature class temperature of the res of the flammable The device marking also determines whether the device is a ssoci-
equipment (°C) material (°C) ated equipment or intrinsically safe equipment. If it is associated
T1 450 >450 equipment, the equipment category is placed in round brackets,
e.g. II (1) G.
T2 300 >300 ≤ 450
280 >280 ≤ 300 Equipment protection level (EPL)
260 > 260 ≤ 280
Devices are classified according to their potential hazard. A
ccor-
230 > 230 ≤ 260 ding to IEC 60079-0 the following equipment protection levels are
215 > 215 ≤ 230 defined for gas and dust explosion protection:
T3 200 > 200 ≤ 300
Gas explosion protection
180 > 180 ≤ 200
165 > 165 ≤ 180 EPL Ga:
160 > 160 ≤ 165 ▪▪ Device with very high protection level
T4 135 > 135 ≤ 200
▪▪ The device does not constitute a potential source of ignition
when used for its intended purpose and when subject to faults
120 > 120 ≤ 135 which cannot necessarily be expected on a regular basis
T5 100 > 100 ≤ 135 EPL Gb:
T6 85 > 85 ≤ 100 ▪▪ Device with high protection level
▪▪ The device does not constitute a potential source of ignition
when used for its intended purpose and when subject to faults
Tab. 2: Temperature classes with maximum permissible surface which cannot necessarily be expected on a regular basis
temperatures and ignition temperatures EPL Gc:
▪▪ Device with increased protection level
▪▪ The device does not constitute a potential source of ignition
Device groups and equipment categories according to ATEX when used for its intended purpose
504 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Basics of explosion protection
Terms and explanations
Zone 0
A test certificate from a test authority is not required for use in
zone 2 as is compulsory in zone 0 and zone 1. Devices must com-
ply with category 3. The equipment must meet the following c rite-
ria (EN 60079-15):
Zone 1
Use of devices in Zone 0 to 2
Zone 1 consists of areas in which a hazardous explosive atmosphe-
re is present occasionally. No change has been made h ere by the The intrinsically safe and associated equipment used in Zone 0 to
ATEX Directive. The example shows zone 1 is present during refu- 2 (gases, vapors) must comply at least with the requirements sti-
eling in the area of the gas pump. pulated for the zone at the location where the intrinsically safe
equipment is used. If the equipment meets higher requirements,
In industrial plants zone 1 is normally present in the following operation is obviously permitted. The national regulations apply
areas: to THE interconnected assembly and installation of devices. (For
this refer to the information stated under General Notes for the
▪▪ in the close vicinity of zone 0 User on the Use of Equipment with Intrinsically Safe Circuits).
▪▪ in the area surrounding inspection openings
▪▪ in the area of filling and draining equipment
▪▪ inside equipment.
Zone 20
Marking of equipment
Device marking according to CENELEC regulations
506 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Basics of explosion protection
Terms and explanations
▪▪ Group with the appropriate subdivision (e.g. IIC) For intrinsically safe devices the marking would be:
▪▪ Temperature class or maximum surface temperature (for group
II devices)
II 1 G
▪▪ Entry of test authority with date and consecutive number
▪▪ Equipment protection level (e.g. “Ga”) II All areas except mining
1 Suitable for a very high level of safety for zone 0
An intrinsically safe device is marked as follows:
G Explosion protected against gas, vapor and mist
Ex ia IIC T6 Ga
With associated equipment, the equipment category is placed in
Ex Complies with explosion protection regulations round brackets:
ia Protection type (Category)
IIC Explosion group II (1) G
T6 Temperature class II All areas except mining
Ga Equipment protection level (1) Must not be installed in the explosion hazardous area
G Explosion protected against gas, vapor and mist
Associated equipment for example is marked as follows:
CE marking procedures
Within the European Union the devices must meet the relevant
requirements. If the manufacturer fulfills these, he is permitted to Devices for use in explosion hazardous areas are provided with t he
affix the CE mark with the identification number of the notified CE marking and the identification code of the testing authority.
body, which carried out the quality assurance system approval. The procedure for issuing the CE marking is clearly d efined and
depends on the equipment category. The example shown for
equipment category 1 illustrates the highest safety level and the
0102
Ex protection
Approval can be achieved directly within the scope of certification ▪▪ protection against external electrical or magnetic fields (e.g.
according to ISO 9000ff. Approval of those fields a ssociated with power current cables)
explosion protection is accomplished in cooperation with an ex- ▪▪ prevent conductor splicing of fine wires using ferrules
pert from the approval body. If the ISO certificate has already been ▪▪ min. cross section (also for single wires of a conductor): 0.1 mm
granted, it is possible to certify those parts relating to explosion ▪▪ protection from damage (mechanical, chemical, thermic…)
protection subsequently within the s cope of an additional audit. ▪▪ armoring, metal cladding, shielding of cables and lines
The following illustration shows both methods. ▪▪ no common use of single-core cables for intrinsically and non-
intrinsically safe circuits in one line
▪▪ separate fault assessment when using multi-core cables and
16 17 18 19 20 10 11 12 10 11 12
11 12 13 14 15 7 8 9 7 8 9
⇒ Cable inductances and capacitances: Total cable length: 130 m 0.13 14.3
(Manufactures spec. or LC = 1 mH/km. CC = 110 nF/km)
Total inductances and capacitances: (ΣLi and ΣCi) 150.13 164.3
Intrinsic safety is achieved if all conditions are fulfilled: U0 ≤ Ui I0 ≤ Ii P0 ≤ Pi L0 ≥ ΣLi C0 ≥ ΣCi
The manufacturer‘s specifications must be observed for the cables. Applicability of approvals
If these specifications are not available, the following values can
be assumed (according to EN 60017-14, Part 12.2.2.2.): 2 00 pF/m Scope of approvals/national approvals
and 1 mH/m or 30 μH/Ω.
If the value P0 of the associated equipment is not stated, a linear Equipment that conforms to the ATEX Directive can be freely tra-
characteristic must be present. From this P0 can be calculated by P0 ded, installed and operated in the member states of the European
= ¼ × I0 × U0. Union.
The connection of proximity switches to isolating switching amp- ATEX approval is recognized in Switzerland although this country
lifiers, two-wire transmitters to isolating transducers or solenoid is not a member of the EU. An approval by the SEV is no longer
valves to valve control modules can be regarded as e xamples of required if the customer is provided with the necessary d ocumen-
simple circuits. The conformance certificate and the E C type exa- tation. This includes the operating instructions of the d
evice, the
mination certificate contain different indices for the limit values. In type examination certificate, the CE declaration and the certificate
this description only the indices according to EN 60079-14 are of the manufacturer‘s Ex audit.
used. The index 0 here stands for maximum limit d ata that can be
output and I for the maximum limit data that c an supplied. Many states worldwide require their own national approval of the
Standardized documents should be used for the intrinsic safety equipment. TURCK devices are therefore often provided with ap-
verification in order to ensure greater clarity. Besides the date and provals for different states. National approvals are required, for
the name of the issuer, the document should also contain the cir- example, in the USA, Canada, China, Japan, Australia or the CIS
cuit designation or number. countries. Other countries accept the issued approvals of other
states. For this reason, knowledge of national regulations is
Interconnection/assembly of several devices essential.
The second case considers the interconnection of several active In many countries, approvals are only issued for a limited period.
associated apparatus. The electrical limit values of the EC type e x- When purchasing a device it should therefore be ensured that t he
amination certificate must not in this case be used as proof of in- time limit for the approval was renewed. Further operation is a c-
trinsic safety. This procedure is fundamentally different to the first cepted in many countries if an approval elapses after the
case. This considers a new assembly based on the interconnection installation.
of the individual associated apparatus into a single assembly with
new limit values. This kind of interconnected assembly is then al- The ATEX approval and the approvals in the USA and Canada are
ways assigned to category “ ib”, even if all the individual apparatus not time limited.
are assigned to category “ia”. The use of such an assembly for zone
0 is therefore not permitted. A detailed description of the intercon-
nection and assembly of several devices is beyond the scope of
this introduction. The related calculation methods and an example
Approvals available on the internet
are contained in annexes A and B of EN 60079-14. The ignition cur-
Current overview of approvals
ves of IEC 60079-11 are also required for this. These ignition c urves
are also contained in EN 50020. The approvals of all TURCK devices are available on the Internet
and can be downloaded directly from the TURCK website: www.
A special procedure must be observed when interconnecting as- turck.com
sociated equipment that does not have linear characteristics
throughout. This is described in detail in EN 60079-25.
510 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Basics of explosion protection
Terms and explanations
Ex protection
Alarm output Attenuating elements consist of a special material and serve for
the damping of sensors.
A detected error resulted in the shutdown of the corresponding
output. The alarm output remains on as long as the input circuit Backplane
monitoring does not detect any faults. If a fault occurs in a circuit,
the alarm output switches off (see also ‘Common alarm output’). A backplane is a mounting plate which provides slots for taking
module cards.
Alarm output (interface technology)
Baud
Electrical output that is set to LOW in the event of an error.
Baud is a unit for the transmission speed. One baud corresponds
Analog to the transfer of one step/signal change per second. If one bit is
transferred per step, the baud rate is identical to the transfer rate
Representation of a signal with continuous, interruption-free in bits per second, if a step is transferred in 0.2 s, the baud rate is 5
.
history.
Baud rate
Analog output
See Baud
The analog output signal of the device is used for the continuous
output of a measured variable. The format of an analog signal is for Bidirectional
example 0/4 … 20 mA or 0/2 … 10 V.
Bidirectional means that the data and signals are transmitted at
Analog signal the same time from point to point in both directions.
512 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Glossary
Terms and explanations
Bus is determined by the different electron density of the wires, as well
as by the temperature difference between the measuring point
A bus collects and transmits data and control information bet- and cold junction. Thus, a thermocouple measures not absolute
ween different components such as CPU, memory and I/O level temperature at the measuring point, but the differential tempera-
following a defined protocol. A bus can be composed of a n umber ture between the measuring point and the cold junction. Since the
of parallel cables for data transfer, addressing, control a nd power voltage is usually measured at a mbient temperature, the measu-
supply. red voltage value is too low by the amount which corresponds to
the voltage of the ambient temperature. Therefore, the so-called
Bus cycle time “cold junction compensation“ is carried out to determine the value
for the absolute temperature at the measuring point. To do so,
The bus cycle time is the time required by a master to serve all temperature at the cold junction must either be kept constant - as
stations of a bus system once, i.e. to write the corresponding o
ut- in the past by an ice bath with constant 0 °C (“cold junction“) - or
puts and read the inputs. the temperature of the cold junction must additionally be measu-
red as a reference point.
Bus system
A bus system describes the totality of all units that communicate Common alarm output
with one another via a bus. Serial bus systems transfer the i nforma- A detected error resulted in the shutdown of the corresponding
tion serially via a common line; parallel bus systems c onsist of se- output. As long as the error monitoring detects no errors, the
veral parallel lines on which data, address or control information is alarm output is switched on. When an error occurs in a circuit, the
transferred in parallel. alarm output switches off (see also alarm output).
DIN is the mark for the collective work of the Deutsches Institut f ür Electrical equipment is an object that is used for the generation,
Normung e. V., a central body for normative and s tandardization conversion, transfer, distribution or application of electrical ener-
work in Germany. gy, such as sensors, cables, machines, control devices.
The drop-off time defines the time required for a signal to change Electrostatic Discharge – ESD is the abbreviation for electrostatic
its signal level from 90% to 10 % (see also ‘Rise time’). discharge, and describes the balancing of electrical charge bet-
ween two differently charged materials.
DTM
EtherCAT®
DTM stands for Device Type Manager and defines the a pplication-
independent driver for computer-programmable and c ommuni- EtherCAT® is an Ethernet-based standard bus system with a m as-
cation devices within a defined FDT frame application such as ter/slave architecture for fast applications and time-sensitive in-
PACTware™. The DTM includes among others: dustrial applications, and is standardized in compliance with
▪▪ User interface for the device IEC 61158, IEC 61784 and ISO 15745-4. It offers the cyclical t rans-
▪▪ Device logic and parameterization mission of I/O data and acyclical transmission of requested data
such as parameters, diagnostics and device identification d
ata.
EC Declaration of Conformity
EtherNet/IP™
With the EC Declaration of Conformity the manufacturer of a de-
vice certifies legally binding, that the device complies with the r e- EtherNet/IP is an open Ethernet standard for industrial networks
levant European Directives. The manufacturer must ensure this b y standardized to IEC 61158. It is mainly used in America and offers
appropriate manufacturing and testing. the connection to server-based office functions such as email cli-
ents or web servers.
EC type examination certificate
External inductance
The EC type examination certificate is issued by a certified testing
laboratory and contains the technical data of a device or values at By external inductance is meant those inductances that have an
which the device may be operated. The EC type examination c erti- effect outside of an Ex device, such as in a cable.
ficate also states any “special conditions” for the use of the device
as well as the basic safety and health regulations. ExVO
The efficiency is generally the ratio between output power ( effec- Fault current
tive power) and input power.
Output current in the event of a wire break or short-circuit in the
ElexV - Ordinance for electrical installations in hazardous input circuit, selectable between 0 mA or > 21.5 mA
rooms (old) /areas (new)
FDT
ElexV is applicable in Germany and is aimed at those responsible
for the technological causes of the formation of explosive mixtu- FDT stands for Field Device Tool and describes the interface d
efini-
res. The former ElexV of 1980 related to European regulations on tion between the specific device DTMs used and the frame a ppli-
explosion protection of industrial electrical equipment. This “old” cation (such as PACTware™). The FDT includes:
version constituted the legal basis for almost the entire field of ex- ▪▪ A standard user environment for all DTMs
514 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Glossary
Terms and explanations
Power supply for the field devices and the signal voltage I/O
Factory Mutual - certification and test lab for North American ap- I/P converter
provals for the Ex and non-Ex area (see also UL)
An I/P converter converts a current signal on the input side
Force mode (0/4…20 mA) to a pressure on (e.g. 0.5…4 bar) on the output side.
The frequency f is the number of vibrations per second and can be Ignition category
calculated as the reciprocal of the period (T = 1/f). The SI unit o f
frequency is the Hertz (1/s). Often, as well other units are used s uch The EN 60079 (IEC 60079) standard stipulates general require-
as 1/min. ments for the design and testing of electrical equipment required
for the hazardous area:
Function code ▪▪ Oil immersion “o” (EN / IEC 60079-6)
▪▪ Pressurized enclosure “p” (EN /IEC 60079-2)
The function codes are used in the Modbus fieldbus to control the ▪▪ Powder filling “q” (EN / IEC 60079-5)
type and method of access to the devices. The function codes are ▪▪ Flameproof enclosure “d” (EN / IEC 60079-1)
incorporated and contained in the Modbus data telegram, inclu- ▪▪ Increased safety “e” (EN / IEC 60079-7)
ding commands for reading and writing input and output data. ▪▪ Intrinsic safety “i” (EN / IEC 60079-11)
▪▪ Non-sparking equipment “nA” (EN / IEC 60079-15)
Galvanic isolation ▪▪ Sparking equipment “nC” , “nR” (EN / IEC 60079-15)
▪▪ Encapsulation “m” (EN / IEC 60079-18)
Electric circuits are separated by means of a transformer such as a n ▪▪ Optical radiation “o” (EN / IEC 60079-28)
optocoupler. ▪▪ Intrinsically safe electrical systems “i-SYST” (EN / IEC 60079-25)
(see also the section ‘Basics of explosion protection’)
GND
Impedance
GND – Abbreviation for “Ground” (see Mass)
The impedance (also: apparent resistance) is the resistance, w hich
HART® a device or a circuit of several devices has for an a lternating current
of a specific frequency. The size of the impedance is therefore not
HART® stands for “Highway Addressable Remote Transducer” and
constant in relation to the different f requency values. This is due to
consists of digital communication via a common data bus. The
the fact that the impedance also consists of a reactive resistance as
data transfer is implemented according to the Bell 202 standard b y
well as the pure ohmic r esistance (active resistance).
means Frequency Shift Keying (FSK). The low-frequency a nalog
signal is superimposed with a high frequency oscillation (± 0.5 mA).
Inductance
A digital “1” is represented with a frequency of 1.2 kHz (1200 Hz)
and a “0” with the frequency 2.2 kHz (2200 Hz). The inductance is an electrical property of a current-carrying con-
ductor or other component, to build a magnetic field due to a
Hexadecimal change in the electrical current, which counteracts the power
change.
Number system with the base 16. The sequence begins with 0 to 9
and continues with the letters A, B, C, D, E and F.
Inductive coupling
Glossary
The input circuit monitoring monitors the connected loop. For The limit or cutoff frequency defines the maximum or minimum
analog signals, usually the 4…20 mA signal is used (example: wire value of the frequency that can or should be processed. To e nsure
breakage I < 3.6 mA; Short circuits I > 21.5 mA). The NAMUR wor- interference immunity, an upstream filter is installed in the pulse
king group makes recommendations on the threshold. N AMUR inputs of rotational speed monitors. Input frequencies that are
sensors offer line monitoring for digital signals. Sensors c ompliant above the limit frequency of this filter can no longer be processed
with EN 60947-5-6 (NAMUR) have an impedance of < 400 Ω in a by the speed monitoring device.
non-operational state and otherwise have a maximum impedance
that ensures a minimum current of > 0.05 mA. These limit values Line monitoring
can be used for detecting wire breaks and/or short-circuits in the
control circuit of switching amplifiers. TURCK interface devices with cable monitoring are used to moni-
tor the input circuit for short-circuits and wire breaks (see a lso ‘In-
Input delay put circuit monitoring’).
The input delay specifies the time required by a device (e.g. a v alve Linearity deviation
control module) to provide the output signal after a signal is pre-
sent at the input. Indicated by sensors with an analog output. Permitted deviation
of the output signal from an ideal linear output characteristic as a
Input frequency % of the full scale value of the output signal.
The input frequency is the maximum rate that must be applied to Load resistance
the input of the unit or that can be measured.
The load resistance is the electrical resistance, by which a power
Input lock time and signal source is loaded.
During the input lock-out time pulses at the sensor input of the Loop-powered
interface device are suppressed for the set time.
Loop-powered devices are fed from the signal and do not require
Input resistance a separate power supply.
The input resistance is present at the input of a device and loads LSB
the voltage source present at the input.
LSB stands for Least Significant Bit; and represents the lowest va-
Insulation resistance lue of a digital bit string.
“Intrinsic safety i” is a protection type for the hazardous area that The closeness of the measured value to the nominal value (see a lso
is described by the EN 60079-11 standard. The electrical energy of Measurement deviation).
a device here is limited so that it cannot cause ignition in a poten-
tially explosive atmosphere (see also the section “Basics of explo- Measuring range
sion protection”).
Indicated by sensors with analog output. It is the size of the range
in which the output signal is changed.
IP protocol
516 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Glossary
Terms and explanations
Modbus TCP is an open Ethernet standard with a client/server ar- The On signal defines the signal level (e.g. in Volts) required by a
chitecture for industrial automation that is standardized in device to detect the input pulse (e.g. 5…30 V – see also ‘Zero
IEC 61158. Modbus communication is implemented with function signal’).
codes that are incorporated in the data telegram. For d ata trans-
mission in Ethernet-TCP/IP networks, Modbus TCP uses t he Trans- Operational safety Ordinance (BetrSichV)
port Control protocol (TCP) for the transfer of the Modbus applica-
tion protocol. The Operational Safety Ordinance (BetrSichV) is the German im-
plementation of the work equipment directive 89/655/EEC [1], la-
Module bus (TURCK BL stations and modules) ter replaced by Directive 2009/104/EC [2], and regulates in Germa-
ny the provision of work equipment by the employer, the u se of
The internal bus of a BL20 or BL67 station is called the module bus. work equipment by workers at work, as well as the m onitoring of
The module bus is independent of the fieldbus. The BL20 a nd BL67 systems within the meaning of the occupational health and
modules communicate via the module bus with the gateway. safety.
MSB stands for „Most significant bit“; in a digital signal of a specific The output current is the current that a device can provide at the
length, the bit that represents the highest value. output circuit.
The Ethernet multiprotocol describes a special function of I/O m o- Typical output functions are: NAMUR: Normalized output signal in
dules that enables the modules to be used in any of the three accordance with EN 60947-5-6 NO contact (NO): The output is
Ethernet systems PROFINET, Modbus TCP or EtherNet/IP™. The open when the sensor is non-activated and closed when the sen-
Ethernet multiprotocol modules detect the protocol used auto- sor is activated. Normally closed (NC): The output is closed when
matically by listening to the communication traffic during the star- the sensor is non-activated and open when the sensor is a ctivated.
tup phase. Complementary/Antivalent (two-way contact): One of the two
outputs is closed in the non-activated state and the other output
NAMUR is closed in the activated state. Analog output: The output supplies
a normalized output signal (0/4…20 mA or 0/2…10 V).
International Association of automation technology users of the
process industry. Output power
Ni100 The output power is the power that a device can provide at the
output circuit, such as a valve control module for the associated
Temperature-dependent resistor to DIN 43760, consisting of n i- valve controlled (see also ‘Switching capacity’).
ckel; less expensive than Pt100 resistors. The temperature c oeffici-
ent of a nickel resistance thermometer is virtually 2 × greater than Output voltage
that of a platinum resistance thermometer.
The output voltage is the voltage that a device can provide at the
No-load voltage output circuit.
The open circuit voltage is the voltage on the output side if no load Overhead
is connected.
In data communication, overhead stands for all information addi-
Nominal voltage tional to the user data that has to be transferred or stored. T his
includes headers in the data packets, routing data or a check c ode
The nominal or rated voltage specified by the manufacturer for the that a receiver has sent back to the transmitter, in order to confirm
normal operation of a device. correct data transmission.
as diagnosed if r equired.
or with a non-activated inductive NAMUR sensor.
Parameterization denotes the setting of parameters to specific va- Protection class according to IEC/EN 60529 and DIN 40050-9, d efi-
lues, e.g. the device type, format and length data, as well as the nes the protection of the enclosure against contact with and in-
number of inputs and outputs in the configuration software of a gress of foreign matters and humidity. The customary p rotection
fieldbus master. classes of TURCK products are:
▪▪ IP20: Protection against solid foreign objects with Ø > 50 mm;
Passive metal part no protection against water (use only in the control cabinet)
▪▪ IP65: Full protection against dust and hose water
Passive metal parts are conductive elements that are not ener- ▪▪ IP67: Full protection against dust and short submersion in
gized during (normal) operation, but may become energized in water
the event of a fault. ▪▪ IP69K: Full protection against dust and high-pressure/steam-jet
cleaning
Period duration measuring process
Protective conductor
With the rotational speed monitors, the time between two succes-
sive input pulses is measured directly and compared with the in- A protective conductor is primarily used to offer protection against
ternally defined reference time. This measuring principle also ena- fatal shock currents and must discharge a fault current for at least
bles acceptable reaction times in applications with relatively large a short time. Protective earth/ground conductors are r epresented
pulse intervals. by the abbreviation PE/PG (protective earth/ground). The PE/PG
for insulated conductors and cables must have a y ellow-green
Ping marking over the entire length.
PROFINET The reference potential is the potential from which the voltages of
all connected circuits are considered and/or measured.
PROFINET is an open Ethernet standard based on PROFIBUS and
standardized in IEC 61158 and IEC 61784 for the connection of de-
centralized devices to a controller. It offers cyclical and a cyclical
data exchange based on a provider - consumer model.
518 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Glossary
Terms and explanations
Repeater Shield
A repeater is a device that is used in data cables to electrically a m- A shield is the term given to the electrically conductive covering of
plify and refresh the signals to be transferred. This enables d ata to cables, housings and cabinets that prevents the formation of elec-
be transported over large distances. trical or magnetic fields in order to ensure the proper functioning
of an electrical system and improve electromagnetic c ompatibility
(see also “Shielding”).
A bus system response time is the time interval between sending Shielding describes the entirety of all measures to protect sensiti-
a read request and the receipt of a reply. The reaction time in r ela- ve electronic components or lines against interference through
tion to an input module is the time between the occurrence of a magnetic or electrical fields (see also „Shield“).
signal change at the module input and the output of the signal
change to the bus system. Short circuit proof
Ring memory A short circuit proof apparatus resists the thermal and dynamic
stresses that can occur at its place of installation due to a short
A ring memory stores data continuously in a certain period of t ime, circuit.
and overrides the data after a given amount of time to r eclaim the
space for new data. This process is inevitably best illustrated gra- Short-circuit
phically in a ring form, thus the name of this technology.
A short circuit is a conductive connection between two or several
Ripple points in a circuit that are normally energized. The fault current
circuit has no effective resistance.
Irregularities in the DC voltage may occur after the VAC mains v ol-
tage is rectified to a VDC voltage (due to the original s inusoidal Short-circuit current
wave of the mains voltage). The remaining wave t roughs can be
compensated (“smoothed”) by means of a c apacitor connected in The short-circuit current defines the value of the current present in
parallel to the load or a coil connected in series to the load. The the event of a short-circuit.
remaining AC component after smoothing is called the ripple or
hum voltage. A 10 % ripple (peak-peak) of the supply voltage is Short-circuit detection
normally tolerated.
Several TURCK interface devices, such as isolating switching amp-
Rise time lifiers, are provided with short-circuit monitoring in the input c ir-
cuit (see also ‘Input circuit monitoring’ and ‘Short-circuit
The rise time defines the time required for a signal to change its threshold’).
signal level from 10% to 90 % (see also ‘Drop-off time’).
Short-circuit threshold
RS485
The short-circuit threshold is the value at which a device, such as
RS485 (EIA-485) is a serial (bus) interface according to EIA standard an isolating switching amplifier, detects a short-circuit in the input
for fast, wired data transmission at high data rates. circuit.
RS485-IS SIL
Standard RS485 with reduced, adapted intrinsically safe IS signal SIL stands for Safety Integrity Level. The IEC 62061, IEC 61508 and
levels IEC 61511 standards offer methods of making probabilistic risk a s-
sessments of safety circuits. These standards define four safety le-
Segment coupler vels (SIL level) which describe the measures required for the m iti-
gation of risk in installation sections.
The segment coupler is used to adapt the standard RS485 signal to
an intrinsically safe RS485-IS signal. The signal is transferred via Simultaneity factor
copper cables. The repeater functionality of the segment coupler
ensures that the amplitude and phase of the signal are regenera- The simultaneity factor indicates how many channels can be o
pe-
ted; thus preventing any losses in signal strength and quality. rated simultaneously with nominal load.
With serial data transmission, digital data is transmitted sequenti- Adjustable time for bridging the startup phase, e.g. of a drive in
ally – bit by bit – via a cable. Standardized serial interfaces are which the alarms are switched off.
available for the serial transfer of digital data.
Glossary
Station
The supply voltage is the voltage that a device requires for t rouble- A terminating resistor (terminator) is used in a network at the be-
free operation. ginning and the end of a bus line in order to prevent disturbing
signal reflections.
Supply voltage range
Test voltage
The supply voltage range is the range between the minimum and
maximum value that a device requires to ensure a power supply. The test voltage is the voltage used for testing the insulation r esis-
tance (see also ‘Insulation resistance’).
Switch-off delay
Thermocouples
Adjustable time by which the switching of the output can be de-
layed (see also ‘Switch-on delay’). Thermocouples are used for industrial temperature measuring.
The most common types are type B, E, J, K, L, N, R, S and T thermo-
Switch-off threshold/Switch-off point couples. Depending on type, thermocouples can be used f or tem-
perature ranges from -270…1800 °C.
A switch-off point is exceeded or falls below a set value.
Topology
Switch-on threshold
In networks, the topology denotes the arrangement and connec-
The switch-on threshold defines the signal level at which a s witch- tion of network components (stations, nodes). Network compo-
on is initiated, e.g. by means of a limit value relay. nents can be connected in different ways Point-to-point connec-
tions (such as star, ring and hybrid topology) as well as point to
Switching capacity multipoint connections (bus and cell topology).
The switching capacity is the power that an electrical device can Transmitter
switch safely.
Transmitters are devices that convert signals into a different, most-
Switching current ly normalized signal (e.g. transducer).
The switching current is the current that an electrical device can Trigger event
safely switch.
A trigger event is normally the triggering of an event, such as the
Switching frequency (interface devices) exceeding of a limit value, on account of which, for example, the
write process to a ring memory is stopped.
The switching frequency indicates the number of status changes
per second. UDP
520 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Glossary
Terms and explanations
Wire-break
Wire-break threshold
A “zero signal” is the signal level (e.g. in Volts) that a device requi-
res to detect the input pulse as a zero signal (e.g. 0…3 V) (see also
‘On signal’).
Glossary
Index of types
Type
Index of t
Index of types
Ident No. Page Type Ident No. Page
6ES7972-0BA12-0XA0 6890934 131 BL20-32DI-24VDC-P 6827015 68
6GK1901-1BB10-2AA0/FC-RJ45 6780031 141 BL20-32DO-24VDC-0.5A-P 6827220 86
AI401Ex 6884204 196 BL20-4AI-U/I 6827217 98
AI40-N 6884215 258 BL20-4DI-24VDC-N 6827013 58
AI41EX 6884020 198 BL20-4DI-24VDC-P 6827012 56
AI41-N 6884216 260 BL20-4DI-NAMUR 6827212 60
AI43EX 6884137 200 BL20-4DO-24VDC-0.5A-P 6827023 78
AI43-N 6884217 262 BL20-ABPL 6827123 127
AIH40EX 6884001 204 BL20-ANBZ-BL 6827072 128
AIH40-N 6884219 266 BL20-ANBZ-BR 6827076 128
AIH41EX 6884005 206 BL20-ANBZ-GN 6827074 128
AIH41-N 6884220 268 BL20-ANBZ-GN/GE-BED 6827078 128
AO401Ex 6884205 202 BL20-ANBZ-RT 6827073 128
AO40-N 6884218 264 BL20-ANBZ-RT/BL-BED 6827077 128
AOH40EX 6884003 208 BL20-ANBZ-SW 6827075 128
AOH40-N 6884221 270 BL20-ANBZ-WS 6827079 128
B4151-0/13.5 6904715 145 BL20-BR-24VDC-D 6827006 46
B4151-0/9 6904717 145 BL20-BR-24VDC-RED 6827366 48
B4251-0/9 6901113 145 BL20-E-16DI-24VDC-P 6827231 64
B8151-0/9 6904604 146 BL20-E-16DO-24VDC-0.5A-P 6827230 82
B8251-0/9 6904603 146 BL20-E-2CNT-2PWM 6827341 118
BIC-44-E424 6604407 141 BL20-E-4AI-TC 6827367 100
BK4140-0/9 6914551 146 BL20-E-4AO-U/I 6827328 110
BL20-16DI-24VDC-P 6827014 66 BL20-E-4IOL 6827385 124
BL20-16DO-24VDC-0.5A-P 6827027 84 BL20-E-8AI-U/I-4PT/NI 6827325 102
BL20-1RS232 6827169 112 BL20-E-8DI-24VDC-P 6827227 62
BL20-1RS485/422 6827165 114 BL20-E-8DO-24VDC-0.5A-P 6827226 80
BL20-1SSI 6827166 116 BL20-E-GW-CO 6827252 24
BL20-2AIH-I 6827331 90 BL20-E-GW-DN 6827301 28
BL20-2AI-I(0/4…20MA) 6827021 88 BL20-E-GW-DP 6827250 20
BL20-2AI-PT/NI-2/3 6827017 94 BL20-E-GW-EC 6827380 36
BL20-2AI-THERMO-PI 6827020 96 BL20-E-GW-EN 6827329 32
BL20-2AI-U(-10/0…+10VDC) 6827022 92 BL20-E-GW-PN 6827377 34
BL20-2AOH-I 6827332 106 BL20-E-GW-RS-MB/ET 6827381 30
BL20-2AO-I(4…20MA) 6827034 104 BL20-GWBR-CANOPEN 6827167 22
BL20-2AO-U(-10/0…+10VDC) 6827033 108 BL20-GWBR-DNET 6827168 26
BL20-2DI-120/230VAC-P 6827011 54 BL20-GW-DPV1 6827234 18
BL20-2DO-120/230VAC-0.5A 6827137 74 BL20-GW-EN 6827237 38
BL20-2DO-24VDC-0.5A-N 6827025 70 BL20-GW-EN-IP 6827247 40
BL20-2DO-24VDC-2A-P 6827026 72 BL20-LABEL-BLOCK 6827071 127
BL20-2DO-R-CO 6827030 76 BL20-LABEL-SCHEIBE 6827070 127
BL20-2RFID-A 6827233 120 BL20-PF-120/230VAC-D 6827008 52
BL20-2RFID-S 6827306 122 BL20-PF-24VDC-D 6827007 50
522 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Index of types
types
Type Ident No. Page Type Ident No. Page
BL20-PG-EN 6827249 42 FDN20-4S-4XSG 6611359 164
BL20-PG-EN-IP 6827248 44 FDN20-4S-4XSG-E 6611343 166
BL20-QV/1 6827104 127 FDN20-BKT-DIN 6931105 176
BL20-QV/2 6827105 127 FDN-DN1 6603596 134
BL20-QV/3 6827106 127 FDP20-16S 6611465 156
BL20-QV/4 6827107 127 FDP20-16S-T 6611485 158
BL20-QV/5 6827108 127 FDP20-16XSG 6611466 160
BL20-QV/6 6827109 127 FDP20-16XSG-T 6611486 162
BL20-QV/7 6827110 127 FEN20-16DXP 6931089 174
BL20-QV/8 6827111 127 FEN20-4DIP-4DXP 6931090 172
BL20-WEW-35/2-SW 6827124 127 FK57 6602216 147
BM1 6884036 289 FKDW4.54-0.5 8015777 133
BM-N 6884226 289 FKFDW4.54-0.5 8016041 133
BM-PS 6884044 289 FKM-FS57-M12 6602223 147
BMSWS8251-8.5 6904724 131 FKSDD-RJ45SF-44 6611523 141
BMWS8251-8.5 6904723 131 FKW4.54-0.5 8016042 133
BS3511/KLBUE4-31.5 6827342 126 FKW5L 8016718 133
BS4140-0/9 6914550 145 FKW-FSW45-M12 6602309 132
BS4151-0/13.5 6904716 145 FS57 6602314 147
BS4151-0/9 6904718 145 FSDW4.54-0.5 8015776 133
BS4251-0/9 6901112 145 FSFDW4.54-0.5 8016043 133
BS8151-0/9 6904613 146 FSM-2FKM57 6622101 143
BS8251-0/9 6904615 146 FSW4.54-0.5 8016038 132
D9T-RS485 6890942 288 FSW5L 8016717 133
D9T-RS485IS 6890944 288 FW-D9TLEDKU9PG-W-FC-ME-SH-8.5 6604220 131
D9T-RS485PG 6890943 288 FW-D9TLEDKU9XX-G-FC-ME-SH-8.5 6604221 132
DF20EX 6884061 190 FW-M12KU5D-G-SB-ME-SH-8 6604219 141
DF20-N 6884212 250 FW-M12KU5W-G-ZF-ME-SH-9 6604210 131
DI401EX 6884232 192 FW-M12ST5D-G-SB-ME-SH-8 6604218 141
DI40-N 6884213 252 FW-M12ST5W-G-ZF-ME-SH-9 6604211 131
DM80EX 6884006 188 GDP-IS/FW2.2 6884210 214
DM80-N 6884211 248 GDP-N /FW2.2 6884224 276
DO401EX 6884203 194 GDP-NI/FW2.2 6884225 216
DO40-N 6884214 254 I/O-ASSISTANT-KABEL-BL20/BL67 6827133 126
DO60R-N 6884196 256 IM1-121EX-R 7541229 310
EC-FKDW4.54-0.5/16 8030752 132 IM1-121EX-T 7541230 312
EC-FKFDW4.54-0.5/16 8030753 132 IM1-12EX-MT 7541228 302
EC-FSDW4.54-0.5/16 8030756 132 IM1-12EX-R 7541226 304
EC-FSFDW4.54-0.5/16 8030757 132 IM1-12EX-T 7541227 306
ELST-M20EX 6884033 289 IM1-12-T 7541268 308
Index of types
524 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Index of types
526 Hans Turck GmbH & Co. KG ■ Tel. +49 208 49 52-0 ■ Fax +49 208 49 52-264
Notice
D301331 2014/08
*D301331ßß0814*
Sense it! Connect it! Bus it! Solve it!