Operation and
Maintenance
Manual
3406C Generator Sets
ZKC1-Up (Generator Set)
C2G1-Up (Generator Set)
C5G1-Up (Generator Set)
C8G1-Up (Generator Set)
NKM1-Up (Generator Set)
C2Y1-Up (Generator Set)
SAFETY.CAT.COM
i03684547
In the United States, the maintenance, replacement, or repair of the emission control devices and
systems may be performed by any repair establishment or individual of the owner's choosing.
SEBU7828-09 3
Table of Contents
Operation Section
Lifting and Storage ................................................ 33
Installation ............................................................. 35
Maintenance Section
Refill Capacities .................................................... 99
4 SEBU7828-09
Foreword
Safety Section
i01914689
Safety Messages
SMCS Code: 1000; 7405
g00997405
Illustration 1
8 SEBU7828-09
Safety Section
Safety Messages
g01024480
Illustration 2
SEBU7828-09 9
Safety Section
Safety Messages
g01024694
Illustration 3
10 SEBU7828-09
Safety Section
Safety Messages
g01024708
Illustration 4
g01023637
g01023635
g01023710
g01018792
g00920549
Hot Coolant Under Pressure (9) Do not allow unauthorized personnel on the engine,
or around the engine when the engine is being
This safety message is located near the top of the serviced.
radiator on the front.
Engine exhaust contains products of combustion
which may be harmful to your health. Always start the
engine and operate the engine in a well ventilated
area. If the engine is in an enclosed area, vent the
engine exhaust to the outside.
• Filler caps
• Grease fittings
g00702020
Illustration 6
• For initial start-up of a new engine or for starting an Always use a board or cardboard when you check
engine that has been serviced, make provisions to for a leak. Leaking fluid that is under pressure can
stop the engine if an overspeed occurs. This may penetrate body tissue. Fluid penetration can cause
be accomplished by shutting off the fuel supply serious injury and possible death. A pin hole leak can
and/or the air supply to the engine. cause severe injury. If fluid is injected into your skin,
you must get treatment immediately. Seek treatment
• Start the engine with the operator controls. Never from a doctor that is familiar with this type of injury.
short across the starting motor terminals or the
batteries. This could bypass the engine neutral Containing Fluid Spillage
start system and/or the electrical system could be
damaged.
NOTICE
Care must be taken to ensure that fluids are contained
Pressurized Air and Water during performance of inspection, maintenance, test-
ing, adjusting and repair of the product. Be prepared to
Pressurized air and/or water can cause debris collect the fluid with suitable containers before open-
and/or hot water to be blown out. This could result in ing any compartment or disassembling any compo-
personal injury. nent containing fluids.
When pressurized air and/or pressurized water is Refer to Special Publication, NENG2500, “Caterpillar
used for cleaning, wear protective clothing, protective Dealer Service Tool Catalog” or refer to Special Pub-
shoes, and eye protection. Eye protection includes lication, PECJ0003, “Caterpillar Shop Supplies and
goggles or a protective face shield. Tools Catalog” for tools and supplies suitable to col-
lect and contain fluids on Caterpillar products.
The maximum air pressure for cleaning purposes
must be below 205 kPa (30 psi) when the air nozzle Dispose of all fluids according to local regulations and
is deadheaded. The maximum water pressure for mandates.
cleaning purposes must be below 275 kPa (40 psi).
SEBU7828-09 15
Safety Section
General Hazard Information
Caterpillar equipment and replacement parts that are Repair any fuel lines, oil lines, tubes, or hoses that
shipped from Caterpillar are asbestos free. Caterpillar are loose or damaged. Leaks can cause fires.
recommends the use of only genuine Caterpillar
replacement parts. Use the following guidelines Inspect all lines, tubes and hoses carefully. Do
when you handle any replacement parts that contain not use bare hands to check for leaks. Always
asbestos or when you handle asbestos debris. use a board or cardboard for checking engine
components for leaks. Tighten all connections to the
Use caution. Avoid inhaling dust that might be recommended torque.
generated when you handle components that contain
asbestos fibers. Inhaling this dust can be hazardous Check for the following conditions:
to your health. The components that may contain
asbestos fibers are brake pads, brake bands, lining • End fittings that are damaged or leaking
material, clutch plates, and some gaskets. The
asbestos that is used in these components is usually • Outer covering that is chafed or cut
bound in a resin or sealed in some way. Normal
handling is not hazardous unless airborne dust that • Wire that is exposed in reinforced hose
contains asbestos is generated.
• Outer covering that is ballooning locally
If dust that may contain asbestos is present, there
are several guidelines that should be followed: • Flexible part of the hose that is kinked or crushed
• Never use compressed air for cleaning. • Armoring that is embedded in the outer covering
• Avoid brushing materials that contain asbestos. Ensure that all of the clamps, the guards, and the
heat shields are installed correctly. This will help to
• Avoid grinding materials that contain asbestos. prevent these effects: vibration, rubbing against other
parts, and excessive heat during operation.
• Use a wet method in order to clean up asbestos
materials.
Dispose of Waste Properly Cooling system conditioner contains alkali. Alkali can
cause personal injury. Do not allow alkali to contact
the skin, the eyes, or the mouth.
Oils
Hot oil and hot lubricating components can cause
personal injury. Do not allow hot oil to contact the
skin. Also, do not allow hot components to contact
the skin.
Batteries
Electrolyte is an acid. Electrolyte can cause personal
injury. Do not allow electrolyte to contact the skin or
Illustration 9
g00706404 the eyes. Always wear protective glasses for servicing
batteries. Wash hands after touching the batteries
Improperly disposing of waste can threaten the and connectors. Use of gloves is recommended.
environment. Potentially harmful fluids should be
disposed of according to local regulations.
i01372262
Always use leakproof containers when you drain Fire Prevention and Explosion
fluids. Do not pour waste onto the ground, down a
drain, or into any source of water. Prevention
SMCS Code: 1000; 7405
i01480768
Burn Prevention
SMCS Code: 1000; 7405
Coolant g00704000
Illustration 10
When the engine is at operating temperature, the
engine coolant is hot. The coolant is also under All fuels, most lubricants, and some coolant mixtures
pressure. The radiator and all lines to the heaters or are flammable.
to the engine contain hot coolant.
Flammable fluids that are leaking or spilled onto hot
Any contact with hot coolant or with steam can cause surfaces or onto electrical components can cause
severe burns. Allow cooling system components to a fire. Fire may cause personal injury and property
cool before the cooling system is drained. damage.
Check the coolant level after the engine has stopped A flash fire may result if the covers for the engine
and the engine has been allowed to cool. crankcase are removed within fifteen minutes after
an emergency shutdown.
Ensure that the filler cap is cool before removing the
filler cap. The filler cap must be cool enough to touch Determine whether the engine will be operated in an
with a bare hand. Remove the filler cap slowly in environment that allows combustible gases to be
order to relieve pressure. drawn into the air inlet system. These gases could
cause the engine to overspeed. Personal injury,
property damage, or engine damage could result.
SEBU7828-09 17
Safety Section
Fire Prevention and Explosion Prevention
• Outer coverings are chafed or cut. Face the unit in order to mount the unit or dismount
the unit. Maintain a three-point contact with the steps
• Wires are exposed. and handholds. Use two feet and one hand or use
one foot and two hands. Do not use any controls as
• Outer coverings are ballooning. handholds.
• Flexible part of the hoses are kinked. Some units require access to the roof of the
enclosure to perform maintenance. Do not stand on
• Outer covers have embedded armoring. components which cannot support your weight. Use
an adequate ladder or use a work platform. Secure
• End fittings are displaced. the climbing equipment so that the equipment will
not move.
Make sure that all clamps, guards, and heat shields
are installed correctly. During engine operation, this Do not carry tools or supplies when you mount the
will help to prevent vibration, rubbing against other engine or when you dismount the engine. Use a hand
parts, and excessive heat. line to raise and lower tools or supplies.
• The sound pressure level of a complete generator Do not start the engine or move any of the controls
set (including the radiator) at 1 meter is 101 if there is a “DO NOT OPERATE” warning tag or
dB(A) for the noisiest configuration when “ISO similar warning tag attached to the start switch or to
8528-10:1998(E) clause 14” is used at 75 percent the controls.
of the rated power.
Before starting the engine, ensure that no one is on,
• The sound power level of a complete generator underneath, or close to the engine. Ensure that the
set (including the radiator) that is not covered by area is free of personnel.
the “European Union Directive 2000/14/EC” is 115
dB(A) for the noisiest configuration when “ISO If equipped, ensure that the lighting system for the
8528-10:1998(E) clause 13” is used at 75 per cent engine is suitable for the conditions. Ensure that all
of the rated power. lights work properly, if equipped.
Note: The preceding sound levels are emission All protective guards and all protective covers must
levels. The preceding sound levels are not be installed if the engine must be started in order
necessarily safe sound levels. There is a correlation to perform service procedures. To help prevent an
between the emission levels and the level of accident that is caused by parts in rotation, work
exposure. The correlation between emission levels around the parts carefully.
and the level of exposure can not be used to
determine if further precautions are required. Do not bypass the automatic shutoff circuits. Do not
disable the automatic shutoff circuits. The circuits are
Refer to the following for factors that influence the provided in order to help prevent personal injury. The
level of exposure: circuits are also provided in order to help prevent
engine damage.
• The characteristics of the area around the
generator set See the Service Manual for repairs and for
adjustments.
• Other sources of noise
i01103904
• The number of machines and other adjacent
processes Engine Starting
• The length of time of exposure to the noise SMCS Code: 1000
This information will enable the user of the machine If a warning tag is attached to the engine start switch
to evaluate the hazard and the risk. or to the controls, DO NOT start the engine or move
the controls. Consult with the person that attached
i03560601 the warning tag before the engine is started.
Before Starting Engine All protective guards and all protective covers must
be installed if the engine must be started in order
SMCS Code: 1000 to perform service procedures. To help prevent an
accident that is caused by parts in rotation, work
NOTICE around the parts carefully.
For initial start-up of a new or rebuilt engine, and for
start-up of an engine that has been serviced, make Start the engine from the operator's compartment or
provision to shut the engine off should an overspeed from the engine start switch.
occur. This may be accomplished by shutting off the
air and/or fuel supply to the engine. Always start the engine according to the procedure
that is described in this Operation and Maintenance
Manual, “Engine Starting” topic (Operation Section).
Knowing the correct procedure will help to prevent
major damage to the engine components. Knowing
Engine exhaust contains products of combustion the procedure will also help to prevent personal injury.
which may be harmful to your health. Always start
and operate the engine in a well ventilated area To ensure that the jacket water heater (if equipped)
and, if in an enclosed area, vent the exhaust to the and/or the lube oil heater (if equipped) is working
outside. properly, check the water temperature gauge and the
oil temperature gauge during the heater operation.
Inspect the engine for potential hazards.
20 SEBU7828-09
Safety Section
Engine Stopping
g00104545
Illustration 12
• power
• sensing
• control
6. Attach a “DO NOT OPERATE” or similar warning
tag to the generator excitation controls.
Product Information
Section
Model Views
i01914966
g00997523
Illustration 13
(1) Generator (6) Exhaust (11) Fuel pressure gauge
(2) Air cleaner (7) Crankcase breather (12) Starting motor
(3) Oil filler cap (8) Radiator filler cap (13) Oil drain valve
(4) Oil level gauge (9) Final fuel filter (14) Oil filter
(5) Turbocharger (10) Fuel priming pump
The Caterpillar 3406C Generator Sets consist of an A hydramechanical governor controls the fuel
engine, a generator and control systems. injection pump output. The output maintains the
desired engine speed. An automatic timing advance
provides the best fuel injection timing over the full
Intended Use range of engine speeds.
The cooling system consists of the following The generator set packages can be utilized for prime
components: power generation or standby power generation. The
generator set packages can be used in land based
• A centrifugal pump that is driven by gears applications or marine applications.
• A thermostat which regulates the engine coolant The generators have four poles. The generators have
temperature six or twelve lead configurations. The configuration
depends on the frame size. The generators are
• An oil cooler capable of producing electrical power in either 50 Hz
or 60 Hz applications.
• A radiator or expansion tank (incorporating a shunt
system)
Specifications
The engine lubricating oil, that is supplied by a gear Table 1
type pump, is cooled. The engine lubricating oil is
also filtered. Bypass valves provide unrestricted flow 3406C Industrial Engine Specifications
of lubrication oil to the engine components during Cylinders and
the following conditions: 6 cylinder in-line block
Arrangement
Bore 137 mm (5.4 inch)
• High oil viscosity
Stroke 165 mm (6.5 inch)
• Plugged oil cooler or plugged oil filter elements Compression Ratio 16:25:1
(paper cartridge)
Aspiration T and JWAC(1)
Engine efficiency, efficiency of emission controls, and
engine performance depend on adherence to proper Displacement 14.6 L (893 in3)
operation and maintenance recommendations. Firing Order 1-5-3-6-2-4
Engine performance and efficiency also depend on
the following items: Rotation (flywheel end) Counterclockwise
(1) Turbocharged with a jacket water aftercooler
• Use of recommended coolant/antifreeze
Note: The front end of the engine is opposite the
• Use of recommended fuels flywheel end of the engine. The left and the right
sides of the engine are determined from the flywheel
• Use of recommended lubrication oils end. The number 1 cylinder is the front cylinder.
• Air cleaner
• Engine oil
• Oil filter
• Fuel
SEBU7828-09 25
Product Information Section
Model Views
g00284836
Illustration 14
Cylinder and valve locations
(A) Inlet valves
(B) Exhaust valves
26 SEBU7828-09
Product Information Section
Product Identification Information
Product Identification
Information
i01954593
Engine Identification
SMCS Code: 1000
European Union
g00303163
Illustration 15
The generator serial number plate is located on the barrel of the
generator.
g01880193
Illustration 18
• Year of Construction____________________________________
• Machine Type ____________________________________________
g00123229
Illustration 20
Typical serial number plate
This plate is positioned on the bottom left side of the The following information is stamped on the Serial
plate for the PIN. Number Plate: engine serial number, model, and
arrangement number.
Note: The CE plate is on machines that are certified
to the European Union requirements that were i01100100
effective at that time.
Information Plate
For machines compliant to 1998/42/EC, the following
information is stamped onto the CE plate. For quick SMCS Code: 1000
reference, record this information in the spaces that
are provided below.
• Year_________________________________________________________
For the name and address of the manufacturer, and
the country of origin of the machine, refer to the PIN
plate.
. Excitation System
S.E. ________________
i01954597
i03665500
Declaration of Conformity
SMCS Code: 1000
Table 2
An EC Declaration of Conformity document was provided with the product if it was manufactured to comply with specific
requirements for the European Union. In order to determine the details of the applicable Directives, review the complete EC
Declaration of Conformity provided with the product. The extract shown below from an EC Declaration of Conformity for
product that are declared compliant to “2006/42/EC” applies only to those product originally “CE” marked by the manufacturer
listed and which have not since been modified.
Note (1) Annex -_____ Guaranteed Sound Power Level -_____dB (A)
Representative Equipment Type Sound Power Level - _____dB (A)
Engine Power per ____-____ kW Rated engine speed - _____ rpm
Technical Documentation accessible through person listed above authorized to compile the Technical File
Note: The above information was correct as of October, 2009, but may be subject to change, please refer to the individual
declaration of conformity issued with the machine for exact details.
30 SEBU7828-09
Product Information Section
Product Identification Information
i03638040 i01912859
g00952201
Illustration 24
g00952030
Illustration 22
g00996322
Illustration 25
5000 12 wire factory connection for wiring code D
Table 4
g00996408
Illustration 26
g00996428
Illustration 27
5000 6 wire factory connection for wiring code D
Table 6
L-L Voltage for Wiring Code D
Winding 50 Hz 60 Hz
9S - 600
SEBU7828-09 33
Operation Section
Lifting and Storage
i03003231
Product Storage
SMCS Code: 1000; 1404; 7002
Engine Storage
If the engine will not be started for several weeks, the
lubricating oil will drain from the cylinder walls and
from the piston rings. Rust can form on the cylinder
liner surface, which will increase engine wear which
can reduce engine service life.
Generator storage
For information on generator storage, refer to this
Operation and Maintenance Manual, “Generator
Set Installation” (Operation Section). For more
information, contact your Caterpillar dealer.
SEBU7828-09 35
Operation Section
Installation
NOTICE
Do not use the engine lifting eyes to remove the en-
gine and generator together.
Location
The location of the generator must comply with all
local regulations. The location of the generator must
also comply with all special industrial regulations.
Locate the generator in an area that meets the
following requirements:
• Clean
• Dry
• Well ventilated
• Easily accessible for inspection and maintenance
36 SEBU7828-09
Operation Section
Gauges and Indicators
Gauges and Indicators If the load is stable and the gauge reading changes
suddenly, perform the following procedure:
SMCS Code: 1900; 7450 3. Check the oil level or determine the cause of the
change.
The electronic engine control system for this engine
utilizes the Generator Set Control+ (GSC+) for engine If the engine oil pressure drops below a preset value,
monitoring and engine control. The GSC+ provides the Low Oil Pressure indicator on the control panel
engine gauges for monitoring engine operating will turn ON and the engine will shut down. The
conditions. The Engine Meter key that is found in the GSC+ and the Electronic Control Module (ECM) will
display area of the GSC+ is used by the operator to log the event in internal memory.
scroll through the engine operating conditions. Alarm
indicators on the GSC+ are used for annunciating System Battery Voltage – This gauge
engine events. If an engine shutdown, or other action indicates the current battery voltage that is
is initiated by the control panel, the alarm indicator being measured by the ECM. A diagnostic
will provide the operator with information that is code will be generated by the ECM if the engine
related to the cause of the action. experiences a high voltage condition or a low voltage
condition. Engine operation may be unpredictable if a
Note: For information about the Generator Set system voltage that is within an acceptable range is
Control+ (GSC+), refer to Operation and Maintenance not maintained.
Manual, SEBU7050, “SR4B Generators And Control
Panels”.
Exhaust Temperature – This gauge
indicates the engine exhaust temperature.
Gauges are used to provide the operator with engine
information that is necessary to monitor engine Maximum exhaust temperature is
performance. Determine the normal operating range approximately 575°C (1065°F).
by observing gauge readings during a variety of
operating conditions. Extend your observations over Engine Oil Temperature – This gauge
a long period in order to establish a reference point. indicates the temperature of the engine
Ensure that the gauges are properly maintained and oil. The GSC+ may be programmed
that the gauges are in good condition. to shut down the engine if an excessive engine
oil temperature is experienced. Maximum oil
Noticeable changes in gauge readings indicate temperature at rated speed with a full load is 107 °C
potential gauge or engine problems. Problems may (224 °F).
also be indicated by gauge readings that abruptly
change, even though the readings remain within Engine Coolant Temperature – The
the normal operating range. Determine and correct typical range for the engine coolant
the cause of any significant change in the readings. temperature is 87 to 98°C (189 to 208°F).
Consult your Caterpillar dealer for assistance. Higher temperatures may occur under certain
conditions. The engine coolant temperature reading
Your engine may not have the same gauges or all of may vary according to load. The maximum allowable
the gauges that are indicated below. temperature with a pressurized cooling system is
107 °C (224 °F). The reading should never exceed
NOTICE the boiling point for the pressurized system that is
If no oil pressure is indicated, STOP the engine. The being used. The GSC+ may be programmed to shut
engine will be damaged from operating without oil down the engine if an excessive engine coolant
pressure. temperature is experienced.
Engine Oil Pressure – This gauge If the engine is operating above the normal range
indicates the pressure of the engine and steam becomes apparent, perform the following
lubrication system. Engine oil pressure will procedure:
be highest after a cold engine has been started.
The engine oil pressure will decrease as the engine 1. Reduce the load and the engine speed.
warms up. The typical range of engine oil pressure at
rated engine speed is 275 to 606 kPa (40 to 88 psi). A 2. Inspect the cooling system for leaks.
lower oil pressure is normal at a lower engine speed.
SEBU7828-09 37
Operation Section
Gauges and Indicators
NOTICE
To help prevent engine damage, never exceed the
high idle rpm. An overspeed can result in serious dam-
age to the engine. The engine can be operated at high
idle without damage, but the engine should never be
allowed to exceed the high idle rpm.
Note: The high idle rpm and the full load rpm are
stamped on the engine's Information Plate.
g00640338
Illustration 30
Caterpillar Monitoring System For The EMCP II+P Control Panels
(1) Main display module
(2) Scroll switch
(3) Clear/mode switch
(4) “LH/RH” switch (not used on 3406E generator sets)
(5) Alert indicators (used on the 3406E generator sets only)
Main Display Module High Inlet Air Temperature Indicator (8) – This
alert indicator is used on 3406E generator sets
only. This indicator illuminates when the inlet air
temperature is high.
In order to enter mode 1, hold the clear/mode switch Service mode or mode 3 assists service technicians
down until “-1-” appears on the display area. Use the with the troubleshooting of diagnostic codes. All
scroll switch in order to advance the display area recorded diagnostic codes are shown on the display
to the next parameter value. The display area will area. The diagnostic codes can be cleared from the
momentarily show the system identifier “PA-X” or the memory in mode 3.
system identifier “GA-X”. The display area will show
the parameter value. In order to enter mode 3, hold the clear/mode
switch down until -3- appears in the display area.
Note: The system identifier “GA-X” is used only on Three identifiers are used to specify each detected
3406E generator sets. For the “PA-X” values and diagnostic code. The identifiers are shown on
the “GA-X” values, refer to the Systems Operation, the display area. The six digit readout alternates
Testing and Adjusting, RENR2472, “Caterpillar between the Module Identifier (MID) display and
Monitoring System for Electronic Modular Control the Component Identifier/Failure Mode Identifier
Panel”. (CID/FMI) display.
Secondary Engine Control Module 047 Tattletale information is retained until the information
De-Nox Control 076 in the memory of the main display module is cleared.
In order to clear the tattletale information from the
Customer Communication Module 097 memory of the main display module, push up the
Programmable Relay Control Module 099 clear/mode switch, while “- -” is shown on the display
area. After the information has been cleared, all of
the tattletale information will be reset to a nominal
Component Identifier (CID) – The CID is displayed value. The recording of new extreme values can
on the first three digits of the display area. The CID begin. In order to clear the individual tattletale values
and the FMI are displayed together immediately after one at a time, push up the clear/mode switch while
the MID is displayed. The CID and the FMI replace the tattletale value is shown on the display area.
the MID. The CID describes the component or the
subsystem that generated a diagnostic code. Note: The memory of the main display module
does not record the date of the tattletale value. The
Failure Mode Identifier (FMI) – The FMI is displayed memory of the main display module does not record
on the last three digits of the six digit display. The the time of the tattletale value. The memory of the
FMI begins with the letter “F” and the FMI ends with main display module does not record the duration of
the two digit failure mode identifier. The CID and the the tattletale value.
FMI are displayed together immediately after the MID
is displayed. The CID and the FMI replace the MID. UNITS MODE
The FMI describes the type of diagnostic code that
has been generated. In order to enter the units mode, hold the clear/mode
switch down until “-5-” appears on the display area.
TATTLETALE MODE The units mode is used to toggle the monitoring
system displays between US units of measure and
Tattletale mode is a tool that is used for management Metric units of measure. When the main display
and maintenance. Tattletale mode is used in order to module enters the units mode, the display area will
track the engine history. The main display module show the current setting. The display area will show
records the extreme value for each engine condition “US” when the display is set to the US units. The
that is monitored. The values come from the sensor display area will show “SI” when the display is set to
inputs and from the engine ECM through the CAT Metric units. Press the scroll switch in order to toggle
data link. The tattletale values are updated when the units between “US” and “SI”.
an extreme value occurs. The previously recorded
value is replaced by the more extreme value. These
values are ignored for a short period of time after
Warning Operation (for all generator sets
each engine start-up. This allows the engine systems except 3406E)
to stabilize before the old values can be updated with
new values. The Caterpillar Monitoring System on an instrument
panel that is equipped with EMCP II does not notify
Hold down the clear/mode switch until “-4-” appears the operator of problems with the sensors that
on the display area (for the switchgear conversion are being monitored. The monitor records any
control panel). This enters the tattletale mode. diagnostic codes that are generated. Diagnostic
codes are recorded when one of the following events
The highest reading is for values that abnormally occurs:
increase. The lowest reading is for values that
abnormally decrease. Use the scroll switch. Advance • A switch opens. When a condition exceeds the trip
the display area to the first tattletale value. The point of the switch, the switch opens.
display area will momentarily show the system
identifier “-PA-X-” or “-GA-X-”. The display area will • A sensor signal exceeds the limits. The main
show the tattletale value. Press the scroll switch display module determines the limits.
again for each succeeding tattletale value.
• An abnormal condition is detected by another
electronic control module. The abnormal condition
is then communicated over the CAT data link to
the main display module.
SEBU7828-09 43
Operation Section
Features and Controls
The operator must use the service switches in Self Test Operation
order to view the diagnostic codes. See Testing and
Adjusting, “Accessing Diagnostic Information” for The Self Test verifies that the main display module
more information. is operating properly. The main display module
performs an automatic Self Test each time the engine
Note: The conditions that cause the engine ECM to control switch (ECS) is turned from the OFF/RESET
issue a warning can be modified by the Electronic position to any other position.
Technician (ET).
Note: When the ECS is in the AUTO position, the
Warning Operation (for 3406E generator main display module receives power only when
the remote start/stop switch is in the START/RUN
sets) position or in the COOLDOWN/STOP position.
The Caterpillar Monitoring System notifies the The internal circuits and the outputs are automatically
operator of an immediate problem or an impending
checked. The outputs are displays, indicators and
problem with various engine systems operation.
the action alarm. The operator must observe the
Warning operation begins when the main display following outputs in order to determine if the outputs
module receives a signal that reflects an abnormal
are operating properly.
engine condition or the main display module detects
a problem with the control system. Switches, sensors
and the engine control module (ECM) provide • The display is tested for approximately one second.
The display area flashes on and off.
information to the main display module. The warning
information consists of the following elements.
• The indicators on the 3406E generator sets
are tested for approximately one second. The
• A switch opens. When a condition exceeds the trip indicators flash on and off.
point of the switch, the switch opens.
After the Self Test, the main display module begins
• A sensor signal exceeds the limits of the trip point. the normal mode of operation. The normal mode of
The main display module determines the limits. operation is 0. If an output does not properly perform
during the Self Test, refer to the Systems Operation,
• An abnormal engine condition is detected by Testing and Adjusting, RENR2472, “Caterpillar
the engine control module (ECM). The abnormal Monitoring System for Electronic Modular Control
conditions are communicated over the CAT data
Panel”. You may also consult your Caterpillar dealer.
link to the main display module.
i02916146
g00638566
Illustration 32
Electronic Modular Control Panel II (EMCP II)
(1) Generator set control (GSC) (6) Starting aid switch (SAS) (if equipped) (11) Emergency stop push button (ESPB)
(2) Alarm module (ALM) (7) Panel lights (PL) (12) Engine control switch (ECS)
(3) Custom alarm module (CAM) (if (8) Pump run switch (if equipped) (35) Caterpillar Monitoring System (if
equipped) (9) Voltage adjust rheostat (VAR) equipped)
(4) Panel light switch (PLS) (10) Speed Potentiometer (SP) (if equipped)
(5) Pump stop switch or Governor Switch (GS) (if equipped)
The electronic modular control panel II (EMCP II) is The main control panel may contain all of the
located above the generator distribution housing. The components which are shown in Illustration 32 or
control panel consists of a main panel with indicators, the main control panel may not contain all of the
meters and control switches. This control panel may components which are shown in Illustration 32. Some
be equipped with optional modules in order to match components are optional. The optional components
the customers' needs and requirements. may not be required for your particular application.
The left side of the control panel contains the Generator Set Control (1) – The generator set
generator set control (GSC). This is the main control (GSC) is the main component of the EMCP
component of the system. The GSC displays II. See the topic “Generator Set Control (GSC)” in
generator output, fault conditions, and key engine this section.
parameters. The center section of the control panel
may be a blank or the center section of the control
panel may contain one or two of the optional alarm
modules. The right section may be a blank or the
right section may contain the Caterpillar Monitoring
System (35).
SEBU7828-09 45
Operation Section
Features and Controls
Alarm Module (2) – The alarm module (ALM) is Voltage Adjust Rheostat (9) – The voltage adjust
optional. The ALM provides a visual warning and an rheostat (VAR) is used to adjust the generator output
audible warning of the engine conditions before the voltage to the desired level.
engine conditions become severe enough to shut
down the engine or before the engine conditions Speed Potentiometer (10) – The speed
restrain the engine from starting. potentiometer (SP) is optional. The SP can be used
with the generator set that has an electric governor.
Custom Alarm Module (3) – The custom alarm When the governor is equipped with a speed adjust
module (CAM) is optional. The CAM annunciates motor, the governor switch (GS) can be mounted
faults, alarms or other conditions from customer instead of the SP. The engine speed and frequency
supplied inputs. can be raised or the engine speed and frequency
can be lowered by using the GS. The GS is also an
Panel Light Switch (4) – The panel lights switch option.
(PLS) turns on the panel lights (7) or turns off the
panel lights (7). Emergency Stop Push Button (11) – The
emergency stop push button (ESPB) is used to shut
Pump Stop Switch (5) – The pump stop switch is down the engine during an emergency situation. The
optional on 3406E and 3412C generator sets only. ESPB shuts off the fuel and the ESPB activates the
This push button switch is used with the generator optional air shutoff, if equipped.
mounted automatic fuel transfer system, if equipped.
The pump stop switch is used to manually stop the Engine Control Switch (12) – The engine control
fuel transfer pump. The pump stop switch will be in switch (ECS) determines the status of the control
the depressed position, when the switch is pushed. panel. In the AUTOMATIC position (3 o'clock), the
The red indicator will now be ON. The switch can be engine starts automatically whenever a remote
reset by pressing the switch again. The red indicator contact is closed. The engine will shut down after the
will now be OFF. contact opens and after a programmable cooldown
period has elapsed. The cooldown period can be
Start Aid Switch (6) – The start aid switch (SAS) programmed to give a 0 to 30 minute cooldown
is optional. The SAS is used to inject ether into the period before the engine shuts down.
engine when you are starting the engine in cold
weather conditions. When the SAS is in ON position, In the MANUAL START position (6 o'clock), the
the switch energizes the starting aid solenoid valve engine starts and the engine runs as long as the
(SASV) and the switch meters a specific amount engine control switch (ECS) remains in this position.
of ether in a holding chamber. When the SAS is
released, the solenoid releases the ether to the In the STOP position (9 o'clock), the fuel solenoid
engine. shuts down the engine after a programmable
cooldown period has elapsed.
NOTICE
The engine must be cranking before using the start In the OFF/RESET position (12 o'clock), the
aid switch. Damage to the engine is possible if ether fault lights are reset and the engine shuts down
is released to the engine but not exhausted or burned immediately.
by the engine when cranking.
Caterpillar Monitoring System (35) – This system
is the information center for the engine and related
Panel Lights (7) – The panel lights (PL) are components. See the Operation Section, “Caterpillar
controlled by panel lights switch (4). The panel lights Monitoring System”.
switch (4) is an ON/OFF switch.
Below, you can find the descriptions of the following
Pump Run Switch (8) – The pump run switch is main modules of the EMCP II:
optional. This momentary push button switch is
used with the generator set mounted automatic fuel • Generator Set Control (GSC)
transfer system, if equipped. Pushing the pump
run switch will cause the fuel transfer pump that is • Alarm Module (ALM)
mounted on the generator set to fill the generator set
dry tank. The green indicator will be ON when the • Custom Alarm Module (CAM)
pump is running. The pump will automatically shut
OFF when the fuel reaches the high fuel level. The
pump can be turned off manually by using the pump
stop switch (5). The pump stop switch must be reset.
Reset the pump stop switch by pressing the switch
again.
46 SEBU7828-09
Operation Section
Features and Controls
Generator Set Control (GSC) • Cycle Crank: The GSC can be programmed to
crank for adjustable time periods. For programming
Functions and Features of the GSC instructions, refer to the Systems Operation,
Testing and Adjusting, SENR5809, “Electronic
Modular Control Panel II (EMCP II) For MUI
Engines” or to the Systems Operation, Testing and
Adjusting, SENR5398, “Electronic Modular Control
Panel II (EMCP II) For EUI Engines”.
Fault indicators The red fault shutdown indicator (21) FLASHES when
the GSC detects a shutdown fault. The engine will be
shut down if the engine is running. The engine will
not be allowed to start. Fault shutdown indicator (21)
is accompanied by a fault code that is immediately
shown on the upper display (25). For the descriptions
of the fault codes, refer to the Systems Operation,
Testing and Adjusting, SENR5809, “Electronic
Modular Control Panel II (EMCP II) For MUI Engines”
or to the Systems Operation, Testing and Adjusting,
SENR5398, “Electronic Modular Control Panel II
(EMCP II) For EUI Engines”.
The value for one of these conditions is shown for Keypad (34) is used to control the information that is
two seconds. Then, the display scrolls to the value shown on upper display (25) and lower display (27).
for the next condition. A small pointer identifies The seven keys have two sets of functions: normal
the engine condition that corresponds to the value functions and service functions. For a description of
which is showing. When the engine meter key (30) is the service functions of the keys, see the Systems
pressed, the lower display (27) stops scrolling. The Operation, Testing and Adjusting, SENR5809,
lower display (27) continuously shows one particular “Electronic Modular Control Panel II (EMCP II) for
value. The pointer flashes when the indicated value MUI Engines” or see the Systems Operation, Testing
is above a predetermined value. When engine meter and Adjusting, SENR5398, “Electronic Modular
key (30) is pressed for a second time, the display Control Panel II (EMCP II) for EUI Engines”. The
(27) will return to scrolling. normal functions of the keys are described in the
following paragraphs.
The relay status indicators are on the bottom
of the lower display (27). When a GSC relay is Leftmost Key (28) – This key only functions when
activated, the corresponding indicator (K1, K2, etc) the GSC is in service mode. This key is used to scroll
is shown on lower display (27). When a relay is right.
not activated, the corresponding indicator (K1, K2,
etc) is not shown. For a description of the relay Phase Select Key (29) – This key selects the phase
functions, see the Systems Operation, Testing and of the generator output that is displayed on the GSC.
Adjusting, SENR5809, “Electronic Modular Control When you press this key, the display shows the
Panel II (EMCP II) for MUI Engines” or the Systems voltage, current, and frequency of each phase one
Operation, Testing and Adjusting, SENR5398, at a time.
“Electronic Modular Control Panel II (EMCP II) for
EUI Engines”. Engine Meter Key (30) – This key controls the
viewing of engine parameters on the lower display.
Keypad Pressing the key stops the scrolling of engine
conditions. The value for one particular engine
condition will show continuously. The pointer flashes
indicating that the scrolling is stopped. The scrolling
of the engine conditions will resume when the engine
meter key is pressed again.
Service Mode Key (33) – Pressing this key causes • Four red indicators indicate the following
the GSC to enter service mode. For more information, parameters (depending on the module
see the Systems Operation, Testing and Adjusting, configuration) :Not in AUTO condition, Low DC
SENR5809, “Electronic Modular Control Panel II Voltage, Air Damper Closed, Low Oil Pressure
(EMCP II) for MUI Engines” or see the Systems Shutdown, Overcrank Shutdown, High Coolant
Operation, Testing and Adjusting, SENR5398, Temperature Shutdown, and Overspeed Shutdown
“Electronic Modular Control Panel II (EMCP II) for
EUI Engines”. • An audible alarm and Acknowledge/Silence switch
g00643609
Illustration 37
The Location of the Alarm Module (ALM) on the EMCP II Control
Panel
One basic alarm module is used to satisfy the The custom alarm module (CAM) is optional. The
requirements for a standby NFPA 99 alarm module, CAM is located in the center of the control panel.
standby NFPA 110 alarm module, NFPA 99 remote The custom alarm module provides a visual warning
annunciator panel, and the prime power alarm. and an audible warning of the conditions of the
This is accomplished by using different inputs to customer supplied inputs before these conditions
the module and different decals on the front of the become severe enough that the engine shuts down
module in order to indicate alarms or shutdown or the engine is unable to start. The CAM is equipped
conditions. Refer to the Systems Operation, Testing with a horn, an alarm silence switch, a lamp test
and Adjusting, SENR5809, “Electronic Modular switch and 8 switched inputs for customer use. Refer
Control Panel II (EMCP II) for MUI Engines” or to the Systems Operation, Testing and Adjusting,
to the Systems Operation, Testing and Adjusting, SENR5809, “Electronic Modular Control Panel II
SENR5398, “Electronic Modular Control Panel (EMCP II) for MUI Engines” or to the Systems
II (EMCP II) for EUI Engines” for all wiring and Operation, Testing and Adjusting, SENR5398,
installation information. Refer to the above manuals “Electronic Modular Control Panel II (EMCP II) for EUI
for a list of indicators and alarm functions. Engines” for all wiring and installation information.
Refer to the above manuals for the names of input
The front of the alarm module consists of the signals.
following indicators.
The front of the alarm module consists of the
• Four amber indicators indicate the following following indicators.
parameters (depending on the module
configuration): High Coolant Temperature, Low • Four amber indicators, which are used to display
Coolant Temperature or Low Coolant Level, alarm conditions
Low Oil Pressure, Generator On Load, Charger
Malfunction, Low Oil Level, and Low Fuel Level.
SEBU7828-09 51
Operation Section
Features and Controls
i02363902
g00638311
Illustration 39
Electronic Modular Control Panel II+ (EMCP II+)
(1) Generator set control + (GSC+) (6) Start aid switch (SAS) (optional) (10) Speed potentiometer (SP) (optional) or
(2) Alarm module (ALM) (optional) (7) Panel lights (PL) Governor switch (GS) (optional)
(3) Custom alarm module (CAM) (optional) (8) Pump run switch (optional) (11) Emergency stop push button (ESPB)
(4) Panel light switch (PLS) (9) Voltage adjust rheostat (VAR) (12) Engine control switch (ECS)
(5) Pump stop switch (35) Caterpillar Monitoring System (optional)
The electronic modular control panel II+ (EMCP II+) is The left side of the control panel contains the
located above the generator distribution housing. The generator set control + (GSC+). This is the main
control panel consists of a main panel with indicators, component of the system. The GSC+ displays
meters and control switches. This control panel may generator output, fault conditions, and key engine
be equipped with optional modules in order to match parameters. The center section of the control panel
the customers' needs and requirements. may be blank, or contain one or two of the optional
alarm modules. The right side of the control panel
may be blank, or contain the Caterpillar Monitoring
System (35).
Generator Set Control + (1) – The generator set Voltage Adjust Rheostat (9) – The voltage adjust
control + (GSC+) is the main component of the rheostat (VAR) is used to adjust the generator output
EMCP II+. See the topic “Generator Set Control + voltage to the desired level.
(GSC+)” in this section.
Speed Potentiometer (10) – The speed
Alarm Module (2) – The alarm module (ALM) is potentiometer (SP) is optional. The SP can be used
optional. The function of ALM is to provide a visual with the generator set that has an electric governor.
and audible warning of engine conditions before When the governor is equipped with a speed adjust
these conditions become severe enough to shut the motor, the governor switch (GS) can be mounted
engine down or keep the engine from starting. instead of the SP. The GS is used to raise or lower
the engine speed and frequency. The GS is also an
Custom Alarm Module (3) – The custom alarm option.
module (CAM) is optional. The purpose of the CAM is
to annunciate faults, alarms or other conditions from Emergency Stop Push Button (11) – The
customer supplied inputs. emergency stop push button (ESPB) is used to shut
down the engine during an emergency situation. The
Panel Light Switch (4) – The panel lights switch ESPB shuts off the fuel and activates the optional air
(PLS) turns the panel lights (7) on or off. shutoff, if equipped.
Pump Stop Switch (5) – The pump stop switch is Engine Control Switch (12) – The engine control
optional with 3406E and 3412C generator sets only. switch (ECS) determines the status of the control
This push button switch is used with the generator panel. In the AUTOMATIC position (3 o'clock),
mounted automatic fuel transfer system, if equipped. the engine will start automatically whenever a
The pump stop switch is used to manually stop the remote initiating contact is closed. The engine will
fuel transfer pump. This switch is latched down when shutdown after the initiating contact opens and after
pushed. The red indicator will now be ON. The switch a programmable cooldown time has elapsed. The
can be reset by pressing the switch again. The red cooldown time can be programmed to give a 0 to
indicator will now be OFF. 30 minute cooldown period before the engine shuts
down.
Start Aid Switch (6) – The start aid switch (SAS)
is optional. The SAS is used to inject ether into the In the MANUAL START position (6 o'clock), the
engine when you are starting the engine in cold engine will start and run as long as the ECS switch
weather conditions. When the SAS is in ON position, remains in this position.
the switch energizes the starting aid solenoid valve
(SASV) and meters a specific amount of ether in a In the STOP position (9 o'clock), the fuel solenoid
holding chamber. When the SAS is released, the shuts the engine down, after a programmable cool
solenoid releases the ether to the engine. down time period has elapsed.
Generator Set Control + (GSC+) • Cycle Crank: The GSC+ can be programmed to
crank for adjustable time periods. For programming
Functions and features of the GSC+ instructions, refer to the Systems Operation,
Testing and Adjusting, RENR2484, “Electronic
Modular Control Panel II + (EMCP II+)”.
Fault indicators The red fault shutdown indicator (21) FLASHES when
the GSC+ detects a shutdown fault. The engine will
be shut down if the engine is running. The engine will
not be allowed to start. Fault shutdown indicator (21)
is accompanied by a fault code that is immediately
shown on the upper display (25). For the descriptions
of the fault codes, refer to the Systems Operation,
Testing and Adjusting, RENR2484, “Electronic
Modular Control Panel II + (EMCP II+)”.
Upper display (25) is also used to show the various Note: All real power values are signed with a “+” or a
fault codes for system faults. For more information “−”. A negative value indicates reverse power.
on fault codes, see Systems Operation, Testing and
Adjusting, RENR2484, “Electronic Modular Control Note: Real power phase A, B, and C as well as
Panel II+ (EMCP II+)”. power factor phase A, B, and C are not shown when
setpoint P032 is set to 1 for delta generator sets.
Note: Line to neutral voltages are not shown when
the setpoint P032 is set to 1 for delta generator sets. Note: Total energy output that is greater than 999,999
kW/h will be shown as MW/h in two steps in order to
Lower display maintain a resolution of 1 kW/h. The first step will
show MW/h as a whole number up to six places. The
The lower display (27) shows values for power second step will show MW/h as a decimal to three
metering, engine parameters and the relay status. places. For example: 1,000,001 kW/h will be shown
as 1000 MW/h (first step), followed by .001 MW/h
The left side of the lower display (27) serves as a (second step).
power meter for the generator set. The following
functions will scroll automatically. The right side of lower display (27) shows the value
of certain engine parameters. The parameters are
• Total real power (kW) listed below.
• Total apparent power (kVA) The relay status indicators are on the bottom of the
lower display (27). When a GSC+ relay is activated,
• Total reactive power (KVAR) the corresponding indicator (K1, K2, etc) is shown
on the lower display (27). When a relay is not
• Percentage of rated power (%kW) activated, the corresponding indicator (K1, K2, etc) is
not shown. For a description of the relay functions,
• Power factor (average) see the Systems Operation, Testing and Adjusting,
RENR2484, “Electronic Modular Control Panel II+
• Power factor phase A (EMCP II+)”.
The alarm module (ALM) is optional. The ALM is Custom Alarm Module
located in the center of the control panel. The function
of the alarm module is to provide a visual and audible
warning of engine conditions before these conditions
become severe enough that the engine will shut
down or will be unable to start.
The front of the alarm module consists of the The custom alarm module (CAM) is optional. The
following indicators. CAM is located in the center of the control panel. The
function of the custom alarm module is to provide a
• Four amber indicators, which can (depending visual and audible warning of the conditions of the
on module configuration) indicate High Coolant customer supplied inputs before these conditions
Temperature, Low Coolant Temperature or Low become severe enough that the engine will shut
Coolant Level, Low Oil Pressure, Generator On down or will be unable to start. The CAM is equipped
Load, Charger Malfunction, Low Oil Level and Low with a horn, alarm silence switch, a lamp test switch
Fuel Level and 8 switched inputs for customer use. For all wiring
and installation information, refer to the Systems
• Four red indicators, which can (depending on Operation, Testing and Adjusting, RENR2484,
module configuration) indicate a Not In AUTO “Electronic Modular Control Panel II+ (EMCP II+)”.
condition, Low DC Voltage, Air Damper Closed, Refer to the above manual for the names of input
Low Oil Pressure Shutdown, Overcrank Shutdown, signals.
High Coolant Temperature Shutdown, and
Overspeed Shutdown The front of the alarm module consists of the
following indicators.
• An audible alarm and Acknowledge/Silence switch
• Four amber indicators, which are used to display
For more detailed information, refer to the Systems alarm conditions
Operation, Testing and Adjusting, RENR2484,
“Electronic Modular Control Panel II+ (EMCP II+)”. • Four red indicators, which are used to display
shutdown conditions
SEBU7828-09 59
Operation Section
Features and Controls
i02363871
g00639524
Illustration 46
Electronic Modular Control Panel II+ With Paralleling (EMCP II+P)
(1) Generator set control + (GSC+) (7) Panel lights (PL) (12) Engine control switch (ECS)
(2) Alarm module (ALM) (optional) (8) Pump run switch (optional) (13) Caterpillar Monitoring System
(3) Custom alarm module (CAM) (9) Voltage adjust rheostat (VAR) (14) Synchronization mode switch
(4) Panel light switch (PLS) (10) Speed potentiometer (SP) (optional) or (15) Breaker open pushbutton/indicator
(5) Pump stop switch Governor switch (GS) (optional) (16) Breaker close pushbutton/indicator
(6) Start aid switch (SAS) (optional) (11) Emergency stop push button (ESPB)
The electronic modular control panel II+ with The left side of the control panel contains the
paralleling (EMCP II+P) is located above the generator set control + (GSC+). This is the main
generator distribution housing. The control panel component of the system. The GSC+ displays
consists of a main panel with indicators, meters generator output, fault conditions, and key engine
and control switches. This control panel may be parameters. The center section of the control panel
equipped with optional modules in order to match the may be blank, or contain one or two of the optional
customers' needs and requirements. alarm modules. The right side of the control panel
may be blank, or contain the Caterpillar Monitoring
System.
Generator Set Control + (1) – The generator set Pump Run Switch (8) – The pump run switch is
control + (GSC+) is the main component of the optional. This momentary push button switch is
EMCP II+P. See the topic “Generator Set Control + used with the generator set mounted automatic fuel
(GSC+)” in this section. transfer system, if equipped. Pushing this switch will
cause the generator set mounted fuel transfer pump
Alarm Module (2) – The alarm module (ALM) is to fill the generator set day tank. The green indicator
optional. The function of the ALM is to provide a visual will be ON when the pump is running. The pump will
and audible warning of engine conditions before automatically shut OFF when the fuel reaches the
these conditions become severe enough to shut the high fuel level. The pump can also be turned OFF
engine down or keep the engine from starting. manually by the pump stop switch (5). The pump stop
switch must be reset. Reset the pump stop switch by
Custom Alarm Module (3) – The custom alarm pressing the switch again.
module (CAM) is optional. The purpose of the CAM is
to annunciate faults, alarms or other conditions from Voltage Adjust Rheostat (9) – The voltage adjust
customer supplied inputs. rheostat (VAR) is used to adjust the generator output
voltage to the desired level.
Panel Light Switch (4) – The panel lights switch
(PLS) turns the panel lights (7) on or off. Speed Potentiometer (10) – The speed
potentiometer (SP) is optional. The SP can be used
Pump Stop Switch (5) – The pump stop switch is with the generator set that has an electric governor.
optional with 3406E and 3412C generator sets only. When the governor is equipped with a speed adjust
This push button switch is used with the generator motor, the governor switch (GS) can be mounted
mounted automatic fuel transfer system, if equipped. instead of the SP. The GS is used to raise or lower the
The pump stop switch is used to manually stop the engine speed and frequency. The GS is also optional.
fuel transfer pump. This switch is latched down when
pushed. The red indicator will now be ON. The switch Emergency Stop Push Button (11) – The
can be reset by pressing the switch again. The red emergency stop push button (ESPB) is used to shut
indicator will now be OFF. down the engine during an emergency situation. The
ESPB shuts off the fuel and activates the optional air
Start Aid Switch (6) – The start aid switch (SAS) shutoff, if equipped.
is optional. The SAS is used to inject ether into
the engine when you are starting the engine in Engine Control Switch (12) – The engine control
cold weather conditions. When the SAS is in the switch (ECS) determines the status of the control
ON position, the switch energizes the starting aid panel. In the AUTOMATIC position (3 o'clock),
solenoid valve (SASV) and meters a specific amount the engine will start automatically whenever a
of ether into a holding chamber. When the SAS remote initiating contact is closed. The engine will
is released, the solenoid releases the ether to the shutdown after the initiating contact opens and after
engine. a programmable cooldown time has elapsed. The
cooldown time can be programmed to give a 0 to
NOTICE 30 minute cooldown period before the engine shuts
The engine must be cranking before using the start down.
aid switch. Damage to the engine is possible if ether
is released to the engine but not exhausted or burned In the MANUAL START position (6 o'clock), the
by the engine when cranking. engine will start and run as long as the ECS switch
remains in this position.
Panel Lights (7) – Panel lights (PL) are controlled In the STOP position (9 o'clock), the fuel solenoid
by the panel lights switch (4). The panel lights switch shuts the engine down after a programmable cool
(4) is an ON/OFF switch. down time period has elapsed.
Synchronization Mode Switch (14) – The Breaker Open Pushbutton/Indicator (15) – When
synchronization mode switch (14) is manually the generator is being taken off-line manually, the
operated. The switch has four positions: the AUTO breaker open pushbutton must be pressed by the
position, the SEMI-AUTO position, the MANUAL operator in order to open the breaker. When the
(PERMISSIVE) position, and the OFF position. Refer breaker is open and the engine is running, the
to Illustration 47. breaker open indicator (15) will light continuously.
In the very basic operating conditions, the GSC+ • Power Down: The EMCP II+P system is designed
receives a signal to run the generator set. The GSC+ to remove power from the GSC+ when the engine
turns on the engine's fuel and starter. When the control switch (ECS) is in the OFF/RESET mode
engine speed reaches the crank termination speed, and when the proper jumper wire is removed.
the starter is disengaged. When the GSC+ receives a The GSC+ will not power down until the crank
signal to stop the engine, the GSC+ shuts the fuel off. termination relay and the fuel control relay are both
off for about 70 seconds. If the wire is not removed,
The functions of the GSC+ are listed below. the GSC+ will remain powered up. For the wiring
diagram and the location of the jumper wire, refer
• The GSC+ controls the normal starting and to the Systems Operation, Testing and Adjusting,
stopping of the engine. RENR2484, “Electronic Modular Control Panel II
+ (EMCP II+)”.
• The GSC+ shows engine conditions and generator
output information on two displays. The displays • Fuel Solenoid Type: The GSC+ can be
also show fault codes and GSC+ programming programmed to work with either an energized to
information. run (ETR) fuel system or an energized to shutdown
(ETS) fuel system.
• The GSC+ monitors the system for faults. If a
fault occurs, the GSC+ performs a controlled fault Fault indicators
shutdown or provides a fault alarm annunciation.
The GSC+ uses indicators and displays in order to
describe the fault.
• fault shutdown indicator (25) When the control panel is not in a paralleling mode,
the same three spare fault indicators (28) can be
• spare fault indicators (28) programmed by the customer. The three spare
faults can be programmed to show coolant loss, oil
• dedicated shutdown indicators (27) temperature, spare fault condition or no assignment.
The yellow spare fault indicators (28) FLASH when
The yellow fault alarm indicator (26) FLASHES when the conditions that are associated with that spare
the GSC+ detects an alarm fault. The alarm fault fault are active. The yellow fault alarm indicator
does not cause the engine status to change. The (26) or the red fault shutdown indicator (25) will
engine can be started. The engine will continue accompany the spare fault indicators (28). The
operating only if the engine is running at the time spare fault indicators will tell whether the spare fault
of the alarm fault. Fault alarm indicator (26) is input is programmed to be an alarm condition or a
accompanied by an alarm fault code that is shown shutdown condition. For the descriptions of the fault
on the upper display (29) when the alarm codes codes, refer to the Systems Operation, Testing and
key (30) is pressed. For the descriptions of the fault Adjusting, RENR2484, “Electronic Modular Control
codes, refer to the Systems Operation, Testing and Panel II + (EMCP II+)”.
Adjusting, RENR2484, “Electronic Modular Control
Panel II + (EMCP II+)”. The red dedicated shutdown indicators (27) represent
the following shutdown faults: low oil pressure,
The red fault shutdown indicator (25) FLASHES emergency stop, high water temperature, engine
when the GSC+ detects a shutdown fault. The engine overspeed and engine overcrank. When the GSC+
will shut down if the engine is running. The engine will detects a fault in one of these areas, the dedicated
not be allowed to start. Fault shutdown indicator (25) shutdown indicator (that corresponds to the fault)
is accompanied by a fault code that is immediately FLASHES. The engine is shutdown if the engine
shown on the upper display (29). For the descriptions is running, and the engine is not allowed to start.
of the fault codes, refer to the Systems Operation, No fault codes are associated with the dedicated
Testing and Adjusting, RENR2484, “Electronic shutdown indicators because each indicator has a
Modular Control Panel II + (EMCP II+)”. descriptive label.
The yellow spare fault indicators (28) can be used for Many of the dedicated shutdown faults depend on
paralleling as a redundant sync check. During the certain setpoints in the GSC+. For the descriptions
paralleling process and before the circuit breaker of the fault codes, refer to the Systems Operation,
is closed, the lamps will indicate if the generator is Testing and Adjusting, RENR2484, “Electronic
in sync with the bus. The spare fault indicators are Modular Control Panel II + (EMCP II+)”.
listed below.
The conditions that are required to activate the
• generator voltage match (spare 1 indicator) dedicated fault shutdowns and the results of each
dedicated fault are in the following list.
• generator frequency match (spare 2 indicator)
_________________________________________________________________
• generator phasing match (spare 3 indicator)
Low Oil Pressure – The engine oil pressure drops
If the generator parameters are not matched to below the setpoints for low oil pressure shutdown
the bus, the associated lamp will flash. When the that are programmed into the GSC+. There are two
generator and bus voltages, frequencies and phases low oil pressure setpoints. One setpoint is used when
are in sync, the lamps will light continuously. the engine is at idle speed. The other setpoint is used
when the engine is at rated speed. When a low oil
pressure fault occurs, the low oil pressure indicator
FLASHES, and the engine is shut down. The engine
is not allowed to start until the fault is corrected.
Note: When total current increases above “9999A”, • Power factor (average)
the GSC+ will show current in “kA” units.
• Power factor phase A
• Line to neutral voltage for all three phases at once
• Power factor phase B
Upper display (29) is also used to show the various
fault codes for system faults. For more information on • Power factor phase C
fault codes, see the Systems Operation, Testing and
Adjusting, RENR2484, “Electronic Modular Control • Total energy output (kW/h)
Panel II+ (EMCP II+)”.
• Total reactive energy output (kVARHr)
Note: Line to neutral voltages are not shown when
the setpoint P032 is set to 1 for delta generator sets. Note: All real power values are signed with a “+” or a
“−”. A negative value indicates reverse power.
Lower display
Note: Real power phase A, B, and C as well as
The EMCP II+P lower display (31) displays the power factor phase A, B, and C are not shown when
synchronoscope. This unique display allows a setpoint P032 is set to 1 for delta generator sets.
simultaneous visual indication of both frequency and
phase of the generator set, in reference to the bus. Note: Total energy output that is greater than 999,999
Additionally, the three spare indicator lamps are used kW/h will be shown as MW/h in two steps in order to
to indicate the synchronization status. maintain a resolution of 1 kW/h. The first step will
show MW/h as a whole number up to six places. The
The lower display (31) shows values for power second step will show MW/h as a decimal to three
metering, engine parameters and the relay status. places. For example: 1,000,001 kW/h will be shown
as 1000 MW/h (first step), followed by .001 MW/h
The left side of the lower display (31) serves as a (second step).
power meter for the generator set. The following
functions will scroll automatically. The right side of lower display (31) shows the value
of certain engine parameters. The parameters are
• Total real power (kW) listed below.
The relay status indicators are on the bottom of the Alarm Codes Key (30) – If fault alarm indicator (26)
lower display (31). When a GSC+ relay is activated, is FLASHING, pressing this key causes the upper
the corresponding indicator (K1, K2, etc) is shown display (29) to show the corresponding alarm fault
on lower display (31). When a relay is not activated, code. If this key is pressed again, the generator AC
the corresponding indicator (K1, K2, etc) is not output information will be shown on the upper display
shown. For a description of the relay functions, (29). If fault alarm indicator (26) is OFF, this key has
see the Systems Operation, Testing and Adjusting, no function.
RENR2484, “Electronic Modular Control Panel II+
(EMCP II+)”. Power Meter Key (32) – This key controls the
viewing of power meter information. This information
Keypad is shown on the lower display. Pressing the key for at
least five seconds causes all the power meter data
to scroll once. The default power meter data then
resumes scrolling. If this key is pressed for less than
five seconds, the display will stop scrolling the power
meter functions until the key is pressed again.
g00635769 g00635777
Illustration 52 Illustration 53
The Location of the Alarm Module (ALM) on the EMCP II+P The Location of the Custom Alarm Module (CAM) on the EMCP
Control Panel II+P Control Panel
The alarm module (ALM) is optional. The ALM is The Custom Alarm Module (CAM) is located in
located in the center of the control panel. The function the center of the control panel. The function of the
of the alarm module is to provide a visual and audible custom alarm module is to provide a visual and
warning of engine conditions before these conditions audible warning of the conditions of the customer
become severe enough that the engine will shut supplied inputs before these conditions become
down or will be unable to start. severe enough that the engine will shut down or will
be unable to start. The CAM has eight indicators,
One basic alarm module is used to satisfy the an audible horn, acknowledge/silence switch and
requirements for a standby NFPA 99 alarm module, the lamp test switch. Four of the indicator lamps
standby NFPA 110 alarm module, NFPA 99 remote are yellow. These yellow indicator lamps are
annunciator panel, and prime power alarm. This is used to indicate a fault shutdown. For all wiring
accomplished by using different inputs to the module and installation information, refer to the Systems
and different decals on the front of the module in Operation, Testing and Adjusting, RENR2484,
order to indicate alarms or shutdown conditions. “Electronic Modular Control Panel II+ (EMCP II+)”.
For all wiring and installation information, refer to Refer to the above manual for the names of input
the Systems Operation, Testing and Adjusting, signals.
RENR2484, “Electronic Modular Control Panel II+
(EMCP II+)”. Refer to the above manual for a listing Note: If an optional alarm module is ordered, the
of indicators and alarm (horn) functions. audible horn, acknowledge/silence switch and lamp
test switch will come standard with the optional alarm
The front of the alarm module consists of the module.
following indicators.
The front of the alarm module consists of the
• Four amber indicators, which can (depending following indicators.
on module configuration) indicate High Coolant
Temperature, Low Coolant Temperature or Low • Four amber indicators, which are used to display
Coolant Level, Low Oil Pressure, Generator On alarm conditions
Load, Charger Malfunction, Low Oil Level and Low
Fuel Level • Four yellow indicators, which are used to display
shutdown conditions
• Four red indicators, which can (depending on
module configuration) indicate a Not In AUTO
condition, Low DC Voltage, Air Damper Closed,
Low Oil Pressure Shutdown, Overcrank Shutdown,
High Coolant Temperature Shutdown, and
Overspeed Shutdown
i02363881
g01101389
Illustration 54
View of EMCP 3
(1) Electronic Control Module (ECM) for the (4) Annunciator Module (9) Alarm Horn
Generator Set (5) Lamp Test Switch
(2) Panel Light Switch (6) Alarm Acknowledge Switch
(3) Starting Aid Auto/Manual Switch (7) Speed Potentiometer (optional)
(optional) (8) Emergency Stop Push Button
g01045431
Illustration 55
(1) Display Screen (7) Lamp Test Key (13) Right Key
(2) AC Overview Key (8) Run Key (14) Enter Key
(3) Engine Overview Key (9) Auto Key (15) Down Key
(4) Yellow Warning Lamp (10) Stop Key (16) Left Key
(5) Red Shutdown Lamp (11) Up Key
(6) Alarm Acknowledge Key (12) Escape Key
Navigation Keys Lamp Test Key (7) – Pressing and holding the
“LAMP TEST” key will cause each LED and the
AC Overview (2) – The “AC OVERVIEW” key display screen pixels to turn on continuously until the
will navigate the display to the first screen of AC key is released.
information. The “AC OVERVIEW” information
contains various AC parameters that summarize the RUN Key (8) – Pressing the “RUN” key will cause
electrical operation of the generator set. the engine to enter the “RUN” mode.
Engine Overview (3) – The “ENGINE OVERVIEW” AUTO Key (9) – Pressing the “AUTO” key will cause
key will navigate the display to the first screen of the engine to enter the “AUTO” mode.
engine information. The “ENGINE OVERVIEW”
information contains various engine parameters that STOP Key (10) – Pressing the “STOP” key will
summarize the operation of the generator set. cause the engine to enter the “STOP” mode.
Acknowledge Key (6) – Pressing the Up Key (11) – The “UP” key is used to navigate
“ACKNOWLEDGE” key will cause the horn through the various menus and monitoring screens.
relay to turn off. This will silence the horn. Pressing The “UP” key is also used when a setpoint is entered.
this key will also cause any red or yellow flashing When entering numeric data, the “UP” key is used
lights to either turn off or to come on continuously, in order to increment the digits (0-9). If the setpoint
depending on the active status of the alarms. The requires selection from a list, the “UP” key is used to
“ACKNOWLEDGE” key may also be configured to navigate UP through the list.
send out a global alarm silence on the J1939 Data
Link, which will silence the horns on the annunciators.
70 SEBU7828-09
Operation Section
Features and Controls
Enter Key (14) – The “ENTER” key is used in order Digital Inputs
to navigate through the menus. When the key is
pressed, the user moves forward or the user moves Note: There are 8 digital inputs on “EMCP 3.2” and
downward through the menus. The “ENTER” key is “EMCP 3.3”. There are 6 digital inputs on “EMCP
also used to save any changes while the setpoints 3.1”.
are being programmed. Pressing the “ENTER”
key during programming the setpoints causes the Digital Input 1 – Digital Input 1 is used for the
changes to be saved to memory. emergency stop. This input should be wired to
GROUND through an Emergency Stop switch.
Down Key (15) – The “DOWN” key is used to The input can be set to activate on an active high
navigate downward through the various menus or (normally closed contact) or an active low (normally
screens. The “DOWN” key is also used to program open contact). Activating the emergency stop input
the setpoints. The “DOWN” key is used to decrease will cause the generator set to stop immediately. The
the digits when entering numeric data. If the setpoint emergency stop input will also prevent the generator
requires selection from a list, the “DOWN” key is set from starting. Once Digital Input 1 goes active,
used to navigate DOWN through the list. the engine will not start until the event is cleared.
Refer to System Operation, Troubleshooting, Testing
Left Key (16) – The “LEFT” key is used during and Adjusting, “Digital Input Resetting”.
setpoint adjustment. The “LEFT” key is used to select
the digit that is edited during the entry of numeric Digital Input 2 – Digital Input 2 is used for remotely
data. The “LEFT” key is also used during some of starting and stopping the generator set. This input
the setpoint adjustments to select a check box. The should be wired to GROUND through a switch that
key is also used to unselect a check box. If a check can be initiated remotely. The input can be set to
box has a check mark, pressing the “LEFT” key activate on an active high (normally closed contact)
will disable the function. Pressing the key will also or an active low (normally open contact). If the input
remove the check mark. Pressing the “LEFT” key is active and the engine is in AUTO, the engine will
will also cause the check mark to disappear. If the attempt to start. Once the input becomes inactive
check box does not have a check mark, pressing the engine will enter into cooldown (if programmed)
the “LEFT” key will enable the function. Pressing the and then stop.
“LEFT” key will also cause a check mark to appear.
SEBU7828-09 71
Operation Section
Features and Controls
The remainder of the inputs can be configured. The • ATS in Emergency Position
main purpose for the other “DIGITAL” inputs is to add
additional monitoring capabilities of the parameters • Battery Charger Failure
for the engine or generator. The inputs can be
configured by going to the “EVENT I/P FUNCTIONS” • Generator Breaker Closed
parameter under the “SETPOINTS” menu. The
“DIGITAL INPUTS” parameter can only be set to • Utility Breaker Closed
“ACTIVE HIGH” or “ACTIVE LOW” in order to initiate
a High Warning, Low Warning, High Shutdown, Low • Fuel Leak Detected
Shutdown, or Status.
• Custom Event
The inputs can be programmed to monitor the
following parameters or components. Refer to For detailed information about the electronic control
System Operation, Troubleshooting, Testing and module, see Systems Operation, Troubleshooting,
Adjusting, “Digital Input Programming”. Testing and Adjusting, RENR7902, “3508B, 3512B,
3516 and 3516B Engines EMCP3”.
Pressures
Annunciator Module
• Air Filter Differential Pressure
• Engine Oil Pressure
• Fire Extinguisher Pressure
• Fuel Filter Differential Pressure
• Oil Filter Differential Pressure
• Starting Air Pressure
Temperatures
g00994093
Illustration 58
g00994098
Illustration 61
Coolant Temperature Sensor
If the coolant level drops below the minimum level,
the coolant level sensor may activate an alarm or
the coolant level sensor may cause a shutoff in
order to avoid engine overheating or possible engine
damage. Coolant must be added to the radiator in
order to correct the condition.
g00994095
Illustration 59
g00994097
Illustration 60
i03646563 i01564109
When servicing or repairing electric power gener- For generators with PMG excitation, a permanent
ation equipment: magnet generator is added to the generator at the
rear of the generator. The PMG supplies the voltage
• Make sure the unit is off-line (disconnected regulator with a voltage that is independent of the
from utility and/or other generators power main generator winding. The generator has a short
service) , and either locked out or tagged DO circuit capability of 3 X In for 10 seconds. The
NOT OPERATE. generator also has good immunity to distortion from
the generator load.
• Remove all fuses.
The voltage regulator monitors and corrects the
• Make sure the generator engine is stopped. output voltage of the generator by adjusting the
excitation current.
• Make sure all batteries are disconnected.
• Make sure all capacitors are discharged.
Failure to do so could result in personal injury or
death. Make sure residual voltage in the rotor, sta-
tor and the generator is discharged.
Table 10
Sustained short circuit 3 x In for 10 seconds
capacity (AREP and PMG)
Standard power supply Two auxiliary windings
(AREP)
Supply for shunt max 140 VAC at 50/60 Hz
Rated overload current 10 amperes for 10 seconds
Electronic protection for Excitation ceiling current
overload and loss of for 10 seconds and return
voltage sensing to approximately 1 ampere
THE GENERATOR
MUST BE STOPPED
IN ORDER TO RESET
THE PROTECTION.
Fuse “F1” on input side “X1” and “X2”
Voltage sensing 5 VAC that is isolated by
the transformer
Terminals for 0 and 110 95 to 140 VAC
VAC
Terminals for 0 and 220 170 to 260 VAC
VAC
Terminals for 0 and 380 340 to 520 VAC
VAC
Voltage regulation ±0.5%
Rapid response time or normal response time from the
location of jumper “ST2”
Voltage adjustment via potentiometer “P2”
Quadrature droop adjustment via potentiometer “P1”
Underspeed protection and adjustment of frequency
threshold via potentiometer “P4” (Factory setting)
Maximum adjustment for excitation via potentiometer
“P5” (4 to 10 amperes)
50 or 60 Hz selection with jumper “ST3”(1).
(1) The engine speed setting must be changed in order to change
the frequency of the generator set.
R448 Adjustments
g01015862
Illustration 62
g00995942 g00995949
Illustration 63 Illustration 64
Connections for shunt excitation Connections for shunt excitation
6 wires 12 wires
78 SEBU7828-09
Operation Section
Features and Controls
Note: Do not change the voltage settings after Use the following steps in order to check the internal
this step. protection.
3. Apply the available load. The setting is correct 1. Open switch D. The excitation current should
only if a reactive load is available. Equalize the increase up to the preset maximum value and
Kilowatts or divide the rated power of the units the excitation current should remain at the preset
proportionally by altering the speed. Alter the maximum value for approximately 10 seconds.
quadrature droop potentiometer (P1) in order to The current will decrease to less than 1 Amp.
equalize the currents or divide the currents.
2. Open switch A in order to reset the internal
protection.
R448 Adjustment for Maximum
Excitation Note: The voltage must be adjusted after the
maximum excitation current has been set.
Special Use
g01016266
Illustration 67
Table 11
Applications B Volts Time
Voltage build up 12 (1A) 1 - 2 seconds
De-energized parallel
12 (1A) 1 - 2 seconds
operation
Standby parallel
24 (2A) 5 - 10 seconds
operation
Frequency starting 48 (4A) 5 - 10 seconds
Voltage that is sustained
48 (4A) 5 - 10 seconds
at overload
SEBU7828-09 81
Operation Section
Engine Starting
Engine Starting • Do not start the engine or move any of the controls
if there is a “DO NOT OPERATE” warning tag or
similar warning tag attached to the start switch or
i01233590 to the controls.
Before Starting Engine • Ensure that the areas around the rotating parts are
clear.
SMCS Code: 1000; 1400; 1450
• All of the guards must be put in place. Check for
Perform the required daily maintenance and other damaged guards or for missing guards. Repair
periodic maintenance before the engine is started. any damaged guards. Replace damaged guards
Inspect the engine compartment. This inspection can and/or missing guards.
help prevent major repairs at a later date. Refer to
the Operation and Maintenance Manual for more • Disconnect any battery chargers that are not
information. protected against the high current drain that
is created when the electric starting motor (if
• For the maximum service life of the engine, make equipped) is engaged. Check electrical cables
a thorough inspection before starting the engine. and check the battery for poor connections and
Look for the following items: oil leaks, coolant for corrosion.
leaks, loose bolts, and trash buildup. Remove trash
buildup and arrange for repairs, as needed. • Reset all of the shutoffs or alarm components.
• Inspect the cooling system hoses for cracks and • Check the engine lubrication oil level. Maintain the
for loose clamps. oil level between the “ADD” mark and the “FULL”
mark on the oil level gauge.
• Inspect the alternator and accessory drive belts for
cracks, breaks, and other damage. • Check the coolant level. Observe the coolant level
in the coolant recovery tank (if equipped). Maintain
• Inspect the wiring for loose connections and for the coolant level to the “FULL” mark on the coolant
worn wires or frayed wires. recovery tank.
• Check the fuel supply. Drain water from the water • If the engine is not equipped with a coolant
separator (if equipped). Open the fuel supply valve. recovery tank maintain the coolant level within
13 mm (0.5 inch) of the bottom of the filler pipe. If
NOTICE the engine is equipped with a sight glass, maintain
All valves in the fuel return line must be open before the coolant level in the sight glass.
and during engine operation to help prevent high fuel
pressure. High fuel pressure may cause filter housing • Observe the air cleaner service indicator (if
failure or other damage. equipped). Service the air cleaner when the yellow
diaphragm enters the red zone, or when the red
piston locks in the visible position.
If the engine has not been started for several weeks,
fuel may have drained from the fuel system. Air may • Ensure that any driven equipment has been
have entered the filter housing. Also, when fuel filters disengaged. Remove any electrical loads.
have been changed, some air space will be left in the
housing. In these instances, prime the fuel system.
Refer to the Operation and Maintenance Manual, Starting the Engines, Operating the
“Fuel System-Prime” for more information on priming Engines, and Stopping the Engines
the fuel system.
that are Equipped with Control
Panels
For information regarding the generator control panel
Engine exhaust contains products of combustion that is used, refer to the Operation and Maintenance
which may be harmful to your health. Always start Manual that is for the generator and the control panel.
and operate the engine in a well ventilated area
and, if in an enclosed area, vent the exhaust to the
outside.
82 SEBU7828-09
Operation Section
Engine Starting
Automatic Starting
Manual Starting
NOTICE
For initial start-up of a new or rebuilt engine, and for
start-up of an engine that has been serviced, make
provision to shut the engine off should an overspeed
occur. This may be accomplished by shutting off the
air and/or fuel supply to the engine.
SEBU7828-09 83
Operation Section
Engine Starting
• The control is in “AUTO” and the remote initiate When No. 2 diesel fuel is used, a fuel heater will
contact (IC) becomes active. maintain the temperature of the fuel above the cloud
point. Fuel line insulation will help to maintain the fuel
• The operator presses the “AUTO” Key and a temperature.
start command is sent via the RS-485 SCADA
Data Link. Consult your Caterpillar dealer for more information
on the starting aids that are available for cold weather
2. The EMCP 3 checks the system before the crank starting.
cycle begins. The EMCP 3 checks that no system
faults are present. The EMCP 3 checks that all Starting With the Starting Aid
previous shutdown faults have been reset. The
EMCP 3 also checks that the engine is not already Switch
running. If the engine is equipped with prelube,
the EMCP 3 checks the status of the prelube. If
the prelube is not complete, the EMCP 3 will not
crank the engine. Personal injury or property damage can result
from alcohol or starting fluids.
3. The EMCP 3 begins the crank cycle.
Alcohol or starting fluids are highly flammable and
4. The EMCP 3 cranks the engine until the crank toxic and if improperly stored could result in injury
cycle time reaches the setpoint for total crank time or property damage.
or until the engine starts.
i01646248
• Check for any fluid or for any air leaks at idle rpm
and at one-half full rpm (no load on the engine)
before operating the engine under load. This is not
possible in some applications.
Gauge readings should be observed and the data • Ensure that the turbochargers are operating
should be recorded frequently while the engine correctly so that the proper air/fuel ratio is
is operating. Comparing the data over time will maintained. Clean exhaust indicates proper
help to determine normal readings for each gauge. functioning.
Comparing data over time will also help detect
abnormal operating developments. Significant • Maintain a good electrical system.
changes in the readings should be investigated.
One defective battery cell will overwork the alternator.
This will consume excess power and excess fuel.
i00808595
Engine Warm-up • Ensure that the belts are properly adjusted. The
belts should be in good condition.
SMCS Code: 1000
• Ensure that all of the connections of the hoses are
tight. The connections should not leak.
1. Run the engine at low idle for three to five minutes,
or run the engine at low idle until the jacket water
temperature starts to rise. • Ensure that the driven equipment is in good
working order.
More time may be necessary when the
temperature is below −18° C (0° F). • Cold engines consume excess fuel. Utilize heat
from the jacket water system and the exhaust
system, when possible. Keep cooling system
2. Check all of the gauges during the warm-up
components clean and keep cooling system
period.
components in good repair. Never operate the
engine without water temperature regulators.
3. Perform another walk-around inspection. Check
All of these items will help maintain operating
the engine for fluid leaks and air leaks.
temperatures.
4. Increase the rpm to the rated rpm. Check for fluid
leaks and air leaks. The engine may be operated
at full rated rpm and at full load when the engine
oil temperature reaches 60° C (140° F).
SEBU7828-09 87
Operation Section
Engine Operation
• Settings for the fuel system and the limits for the
operating altitude are stamped on the Engine
Information Plate. If an engine is moved to a
higher altitude, the settings must be changed by a
Caterpillar dealer. Changing the settings will help
prevent damage to the turbocharger. Changing the
settings will help to provide the maximum efficiency
for the engine. Engines can be operated safely at
higher altitudes, but the engines will deliver less
horsepower. The fuel settings should be changed
by a Caterpillar dealer in order to obtain the rated
horsepower.
88 SEBU7828-09
Operation Section
Engine Stopping
g00104303
Illustration 71
Typical emergency stop button
The engine will coast to a stop. Ensure that any • Note the service hour meter reading. Perform
system that provides external support to the engine the maintenance that is in the Operation and
is secured after the engine is stopped. Maintenance Manual, “Maintenance Interval
Schedule”.
Automatic Stopping
• Fill the fuel tank in order to help prevent
accumulation of moisture in the fuel. Do not overfill
Automatic stopping will occur when the engine is
the fuel tank.
operating in the automatic mode and the remote
start/stop initiate contact opens. If the cooldown
Note: Only use the antifreeze coolant solutions
feature is utilized, the engine will operate for a
that are recommended in Special Publication,
programmed period of time before the engine stops. SEBU6251, “Caterpillar Commercial Diesel Engine
Otherwise, the engine will immediately shut off.
Fluids Recommendations”. Failure to follow the
recommendations in Special Publication, SEBU6251,
EMCP 3 “Caterpillar Commercial Diesel Engine Fluids
Recommendations” can cause engine damage.
1. Open the main circuit breaker.
• Allow the engine to cool. Check the coolant level.
2. Stop the engine by one of these three methods. Maintain the cooling system at 13 mm (0.5 inch)
from the bottom of the pipe for filling.
• The operator presses the “STOP” Key.
• If freezing temperatures are expected, check the
• The control is in “AUTO” and the remote initiate coolant for proper antifreeze protection. The cooling
contact (IC) becomes inactive. system must be protected against freezing to the
lowest expected outside temperature. See Special
• The operator presses the “AUTO” Key and a Publication, SEBU6251, “Caterpillar Commercial
stop command is sent via the RS-485 SCADA Diesel Engine Fluids Recommendations”. Add the
Data Link. proper coolant/water mixture, if necessary.
3. After receiving the signal to stop, the EMCP 3 • Perform all required periodic maintenance on the
checks that there are no present system faults. generator. The generator maintenance is outlined
in the Operation and Maintenance Manual that is
4. The EMCP 3 begins the cooldown period. In order supplied with the generator.
to bypass the cooldown period, hold down the
“STOP” Key. “PRESS ENTER TO BYPASS” and
“PRESS ESCAPE TO CONTINUE” will be shown
on the display. Press the Enter Key in order to
bypass the cooldown period or press the Escape
Key in order to continue the cooldown period.
Cold Weather Operation When No. 2 diesel fuel is used the following
components provide a means of minimizing problems
in cold weather:
i02237624
• Starting aids
Fuel and the Effect from Cold
Weather • Engine oil pan heaters
The following fuels are the grades that are available • Fuel heaters
for Caterpillar engines:
• Fuel line insulation
• No. 1
For more information on cold weather operation,
• No. 2 see Special Publication, SEBU5898, “Cold Weather
Recommendations”.
• Blend of No. 1 and No. 2
No. 2 diesel fuel is the most commonly used fuel.
Either No. 1 diesel fuel or a blend of No. 1 and No. 2
is best suited for cold weather operation.
i01564140
Fuel Tanks
Condensation can form in partially filled fuel tanks.
Top off the fuel tanks after you operate the engine.
Fuel Filters
It is possible that a primary fuel filter is installed
between the fuel tank and the engine fuel inlet. After
you change the fuel filter, always prime the fuel
system in order to remove air bubbles from the fuel
system. Refer to the Operation and Maintenance
Manual in the Maintenance Section for more
information on priming the fuel system.
NOTICE
In order to maximize fuel system life and prevent pre-
mature wear out from abrasive particles in the fuel,
a two micron absolute high efficiency fuel filter is re-
quired for all Caterpillar Hydraulic Electronic Unit In-
jectors. Caterpillar High Efficiency Fuel Filters meet
these requirements. Consult your Caterpillar dealer
for the proper part numbers.
92 SEBU7828-09
Operation Section
Generator Operation
Generator Operation
i02309602
Generator Operation
SMCS Code: 4450
g00627416
Illustration 73
Allowable Combinations of Unbalanced Loads
Block Loading
When an electrical load is applied to a generator set,
block loading occurs. This load may be anywhere
from a moderate percentage of the rated load up to
the rated load.
Some generators are available with embedded 5. Close the main circuit breaker.
temperature detectors. The detectors are installed in
the slots of the main armature. The main armature is 6. Apply the load. Do not try to apply the full load.
also called a stator. The detectors are used with the Apply the load in increments in order to maintain
equipment that is provided by the customer. Thus, system frequency at a constant level.
the temperature of the main armature winding can be
measured or monitored. RTDtemperature detectors 7. Readjust the governor for rated frequency.
are available. Contact your Caterpillar dealer for
more information.
Adjust the Voltage
Bearing Temperature Detectors Adjust the voltage regulator in order to obtain
the proper voltage. Refer to Operation and
Bearing temperature detectors are available on Maintenance Manual, “Voltage Regulators” for
large-frame generators. Bearing temperature more information about the voltage regulator.
detectors measure the main bearing temperature.
Thus, the temperature of the bearing can be 1. Turn the remote adjustment potentiometer to the
measured or monitored. Bearing temperature center position, if equipped.
measurements may help to prevent premature
bearing failure. Bearing temperature detectors are 2. Connect an analog voltmeter that is calibrated for
used with customer provided equipment. Contact 100 VDC on terminal E+ and terminal E-.
your Caterpillar dealer for more information.
3. Connect a voltmeter that is calibrated for 300 VAC
to 500 VAC or 1000 VAC to the output terminals of
i02292263
the generator.
Single Unit Operation
4. Make sure that the ST3 wire is positioned on the
SMCS Code: 4450 desired frequency. Also, the engine speed must
be changed from the factory setting in order to
change the frequency of the generator.
Initial Start-Up
5. Turn voltage potentiometer (P2) to a full
Measure the insulation resistance of each winding counterclockwise position.
if the generator was exposed to the following
conditions: 6. Turn frequency potentiometer (P4) to a full
clockwise position.
• Rapid changes in temperature
7. Turn stability potentiometer (P3) counterclockwise
• Freezing to about 1/3 of the total rotation for the
potentiometer.
• Wet climate during shipment
8. Start the engine and set the engine speed to a
• Wet climate during storage frequency of 48 Hz for 50 Hz or 58 Hz for 60 Hz.
Refer to this Operation and Maintenance Manual, 9. Adjust the output voltage to the correct value
“Insulation - Test”. with potentiometer P2. This voltage should be
the rated voltage UN for single operation or
Note: These tests should be conducted prior to any UN plus 2% to 4% for parallel operation with
power connections or control connections that are a current transformer. Use potentiometer P3
being made. to make adjustments if the voltage oscillates.
Adjust potentiometer P3 in both directions while
Starting you observe the voltage between E+ and E-.
The voltage between E+ and E- should be
1. Make all preliminary engine starting checks. approximately 10 VDC. The best response times
are obtained at the limit of the instability. Try
2. Be sure that the main circuit breaker or the line cutting or replacing the wire ST2 if no stable
circuit breaker is open. position can be obtained.
3. Start the engine. Allow the engine to warm up. 10. Check the LAM operation. ST5 must be closed.
SEBU7828-09 95
Operation Section
Generator Operation
Stopping
1. Remove the load in increments.
b. Adjust the governor control in order to give the Paralleling Multiple Units
rated frequency at full load.
Units may be paralleled at no load. Units may also
c. Remove the load and check the high idle be paralleled with units under load. After the initial
speed. The high idle speed should be conditions for start-up are satisfied, verify for the
approximately 2 to 5 percent above full load following requirements:
speed for governors that are equipped with
droop. If these speeds cannot be obtained, • One of the governors can be an isochronous
contact your Caterpillar dealer. governor. Electronic load sharing governors are
an exception.
d. For the most consistent results, repeat 2.b
and 2.c until the second condition of “Initial • Generators must have voltage droop compensation
Start-Up” has been met. or cross current compensation.
3. Adjust the voltage.The potentiometers should 1. Start the unit which will be paralleled.
be at the initial settings. Refer to Operation and
Maintenance Manual, “Voltage Regulators”. 2. Turn on the synchronizer lights.
Note: Make sure that the speed droop is identical for 3. After the engine has run a few minutes, bring the
all of the engines before adjustments are made to engine up to synchronous speed. This means
the generator. that the frequency of the incoming unit will be the
same frequency as the unit that is on-line. The
a. Preset the unit for parallel operation by synchronizing lights will begin to blink.
connecting the current transformer to S1 and
S2 of the connector J2. Set potentiometer P1 Note: The frequency of the incoming unit should be
for quadrature droop in the center position. slightly greater than the line frequency. This will allow
Apply the rated load. The voltage should drop the incoming unit to assume some of the load instead
for 2% to 3%. Switch the positions of the of adding to the system load.
two incoming secondary wires of the current
transformer if the voltage increases. 4. By using the governor control, adjust the engine
speed until the lights blink very slowly.
b. The no-load voltages should be identical for all
the generators that are operating in parallel. 5. The lights are off when the voltages of the two
Connect the generators in parallel. Try to obtain units are in-phase. At this point, very quickly close
a 0 kW power exchange by adjusting the speed the breaker while the lights are out.
of the generator. Try to minimize the circulating
currents between generators by altering the 6. Use governor controls in order to share kW load
voltage setting with potentiometer P2 or Rhe between engines.
on one of the generators.
7. Generator temperature will be stabilized in
Note: Do not change the voltage settings after approximately one hour. After the generator
this step. temperature has been stabilized, adjust the
voltage droop rheostat of each generator. This
c. Apply the available load. The setting is correct will share the reactive load and this will limit
only if a reactive load is available. Equalize the the circulating currents. Less droop increases
Kilowatts or divide the rated power of the units the reactive current that is carried by the
proportionally by altering the speed. Alter the generator. Adjusting the voltage droop rheostat
quadrature droop potentiometer (P1) in order in a counterclockwise direction will decrease the
to equalize the currents or divide the currents. droop. Adjusting the voltage droop rheostat in a
clockwise direction will increase droop.
Starting Multiple Units
Load Division and Speed Droop (If
Use the procedure for starting single units in order
to start multiple units. Refer to Operation Section,
Equipped)
“Single Unit Operation”.
Once two units have been paralleled, the unit's
share of the kW load is determined by the governor
control setting. If two units of the same capacity and
the same governor characteristics have the same
governor control settings, the units will share the load
equally. The total load must not exceed the capacity
of the one engine.
SEBU7828-09 97
Operation Section
Generator Operation
In order to transfer the load from one engine to The Speed brick converter changes the analog
another engine, use the following procedure: signal of the speed potentiometer into a pulse width
modulated signal. The engine electronic control can
1. Increase the governor speed control of one unit in recognize this signal. The converter is mounted on
order to increase the load. the subpanel which is located within the control panel.
2. Reduce the governor speed control of the other Function of The Engine Governor
unit in order to decrease the load on that unit.
This section describes the function of the engine
3. Raise the governor speed control or lower the governor in relation to load division between parallel
governor speed control of both units in order to electric sets.
change system frequency.
It is very important to understand two basic facts
Parallel Operation Of Governors about load division between generator sets which
are operating in parallel.
• Each governor should have a three percent speed The circulating current may be as high as 25
droop in order to provide the simplest combination percent of rated amperes with cold generator sets.
of governors for electric sets that are connected in Such current may not even be considered harmful.
parallel. If a constant frequency from no load to full The total generator current should not exceed the
load is required, one governor can be adjusted for amperage rating.
isochronous operation. This isochronous unit will
be called a “lead unit”. As the generators warm, the circulating currents will
decrease. The ammeter readings should decrease
• In order for all paralleled units to accept the slightly, but the voltage meter readings should remain
full share of the load, the following governor constant.
adjustments are required. The governors should
have the same full load speed. The governors
should have the same high idle speed in the case
of governors which are adjusted for speed droop
operation. Governor controls should be set to
the high idle position so that the full range of the
governor is available.
Stopping
In order to remove a generator from the line, perform
the following procedure.
Circulating Currents
Understanding the circulating currents becomes
very important when you parallel the units. These
circulating currents are flowing between generators
in parallel operation. The circulating currents
are caused by voltage differences between the
generators. The circulating currents are not doing
useful work. The amount of the circulating current can
be determined by subtracting the amperage which is
going to the load from the total generator amperage.
SEBU7828-09 99
Maintenance Section
Refill Capacities
publication. Special lubricants are required for some requirements of Caterpillar's ECF-1 specification are met. CI-4,
CI-4 PLUS, and CH-4 oils that have not met the requirements
applications and it will be necessary to continue to
of Caterpillar's ECF-1 specification may cause reduced engine
use these special products. life.
(3) API CG-4 oils are acceptable for all Caterpillar diesel engines.
When API CG-4 oils are used, the oil drain interval should not
NOTICE exceed the standard oil drain interval for your engine.
These recommendations are subject to change with- (4) API CF-4 oils are not recommended for Caterpillar diesel
out notice. Contact your local Caterpillar dealer for the engines.
most up to date fluids recommendations. (5) API CF-2 and CD-2 oils are classifications for two-cycle diesel
engines. Caterpillar does not sell engines that use API CF-2
and CD-2 oils.
ECF-1 Specification Diesel Engine Oils (6) API CF oils are not recommended for use in Caterpillar direct
injection (DI) diesel engines.
(7) API has not authorized the CC, CD, CD-2, and CE
The Engine Crankcase Fluid - 1 (ECF-1) specification classifications since 1 January 1996.
has been introduced by Caterpillar in order to provide
additional performance to the oils that are marketed Note: When oil meets more than one API
under the American Petroleum Institute (API) oil classification, the applicable footnote is determined
classifications. The ECF-1 specification is applicable by the highest API classification that is met.
to those products that meet the requirements of the
specification. Example - An oil that meets both the API CG-4 and
the API CF oil classifications. In this case, the API
CG-4 footnote applies.
• Cat DEO (Diesel Engine Oil) (10W-30) Refer to Table 13 (minimum temperature) in order
to determine the required oil viscosity for starting a
• Cat DEO (Diesel Engine Oil) (15W-40) cold engine.
Cat DEO multigrade is available in various viscosity Refer to Table 13 (maximum temperature) in order
grades that include SAE 10W-30 and SAE 15W-40. to select the oil viscosity for engine operation at the
To choose the correct viscosity grade for the ambient highest ambient temperature that is anticipated.
temperature, see Table 13. Multigrade oils provide
the correct viscosity for a broad range of operating Note: Generally, use the highest oil viscosity that is
temperatures. available to meet the requirement for the temperature
at start-up.
Consult your Caterpillar dealer for part numbers and
for available sizes of containers. If ambient temperature conditions at engine start-up
require the use of multigrade SAE 0W oil, SAE
Commercial Oils 0W-40 viscosity grade is preferred over SAE 0W-20
or SAE 0W-30.
Note: If Caterpillar DEO multigrade is not used,
Table 13
use only commercial oils that meet the following
classifications. Engine Oil Viscosities for Ambient Temperatures
Ambient Temperature
• Only commercial oils that meet the requirements
of Caterpillar's ECF-1 specification are acceptable Viscosity Grade Minimum Maximum
for use in Caterpillar diesel engines. API CH-4,
SAE 0W-20 −40 °C (−40 °F) 10 °C (50 °F)
CI-4, and CI-4 PLUS oils that have not met the
requirements of Caterpillar's ECF-1 specification SAE 0W-30 −40 °C (−40 °F) 30 °C (86 °F)
may cause reduced engine life.
SAE 0W-40 −40 °C (−40 °F) 40 °C (104 °F)
• API CG-4 multigrade oils are acceptable for all SAE 5W-30 −30 °C (−22 °F) 30 °C (86 °F)
Caterpillar diesel engines. When the API CG-4 oils
SAE 5W-40 −30 °C (−22 °F) 50 °C (122 °F)
are used, the oil drain interval should not exceed
the standard oil drain interval for your engine. SAE 10W-30 −18 °C (0 °F) 40 °C (104 °F)
SAE 10W-40 −18 °C (0 °F) 50 °C (122 °F)
Note: Do not use API CF-4 oils in Caterpillar
diesel engines. SAE 15W-40 −9.5 °C (15 °F) 50 °C (122 °F)
• Wear Analysis
Note: Refer to Special Publication, SEBU6251,
“Caterpillar Commercial Diesel Engine Fluids • Oil condition
Recommendations” for additional information that
relates to lubrication for your engine. • Additional tests
Lubricant Viscosity Recommendations Refer to Special Publication, SEBU6251, “Caterpillar
Commercial Diesel Engine Fluids Recommendations”
The proper SAE viscosity grade of oil is determined or contact your local Caterpillar dealer for additional
by the minimum ambient temperature during information concerning the S·O·S Oil Analysis
cold engine start-up, and the maximum ambient program.
temperature during engine operation.
SEBU7828-09 101
Maintenance Section
Refill Capacities
Table 16
Coolant Service Life
Coolant Type Service Life (1)
Coolant Capacities
To maintain the cooling system, the total cooling
system capacity must be known. The approximate
capacity for the engine cooling system is listed.
External system capacities will vary among
applications. Refer to the OEM specifications for the
external system capacity. This capacity information
will be needed in order to determine the amount of
coolant/antifreeze that is required for the total cooling
system.
Table 17
3406C Engine
Approximate Refill Capacities
Compartment or System Liters Quarts
Engine Only 20.8 L (22 qt)
External System(1)
Total Cooling System(2)
(1) The external system includes a radiator or an expansion tank
with the following components: heat exchanger, aftercooler,
and piping. Refer to the Caterpillar specification, or refer to
the specification for the cooling system capacity information.
Enter the information in this row.
(2) The total cooling system includes the capacity for the engine
cooling system plus the capacity for the external system. Enter
the total in this row.
SEBU7828-09 103
Maintenance Section
Maintenance Recommendations
• mechanical
Pressurized system: Hot coolant can cause seri-
• electrical ous burn. To open cap, stop engine, wait until ra-
diator is cool. Then loosen cap slowly to relieve
• thermal the pressure.
• environmental
To relieve the pressure from the coolant system, turn
These stresses may be of varying magnitudes. The off the engine. Allow the cooling system pressure cap
electrical insulation systems are very susceptible to to cool. Remove the cooling system pressure cap
damage that is caused by the stresses that are listed slowly in order to relieve pressure.
above. Exposure to these stresses may shorten
the effective life of the electrical insulation system.
Therefore, the service life of an electric machine will
Fuel System
largely depend on the serviceability of the electrical
To relieve the pressure from the fuel system, turn off
insulation systems. An inspection program and a
the engine.
testing procedure are recommended. An inspection
program and a testing procedure will ensure that the
equipment is maintained in satisfactory condition. High Pressure Fuel Lines (If Equipped)
This will increase field reliability.
2. Wait for ten minutes. Do not ground the welder across the centerline of the
package. Improper grounding could cause damage to
Do not loosen the high pressure fuel lines in order to the bearings, the crankshaft, the rotor shaft, and other
remove air pressure from the fuel system. components.
Engine Oil Clamp the ground cable from the welder to the com-
ponent that will be welded. Place the clamp as close
To relieve pressure from the lubricating system, turn as possible to the weld. This will help reduce the pos-
off the engine. sibility of damage.
i03642798
Note: Perform the welding in areas that are free from
explosive hazards.
Welding on Engines with
1. Stop the engine. Turn the switched power to the
Electronic Controls OFF position.
SMCS Code: 1000 2. Disconnect the negative battery cable from the
battery. If a battery disconnect switch is provided,
NOTICE open the switch.
Because the strength of the frame may decrease,
some manufacturers do not recommend welding onto 3. Disconnect the J1/P1 and J2/P2 connectors from
a chassis frame or rail. Consult the OEM of the equip- the ECM. Move the harness to a position that will
ment or your Caterpillar dealer regarding welding on not allow the harness to accidentally move back
a chassis frame or rail. and make contact with any of the ECM pins.
g01075639
Illustration 77
Use the example above. The current flow from the welder to
the ground clamp of the welder will not cause damage to any
associated components.
(1) Engine
(2) Welding electrode
(3) Keyswitch in the OFF position
(4) Battery disconnect switch in the open position
(5) Disconnected battery cables
(6) Battery
(7) Electrical/Electronic component
(8) Minimum distance between the component that is being welded
and any electrical/electronic component
(9) The component that is being welded
(10) Current path of the welder
(11) Ground clamp for the welder
i01980600
Table 18
GENERATOR START-UP CHECKLIST
RATING INFORMATION
Engine Serial Number: ___________________________________ Arrangement Number: ___________________
Generator Serial Number: _________________________________ Arrangement Number: ___________________
GENERATOR NAME PLATE INFORMATION
Voltage: ___________________ Package (prime, continuous, standby): _________________
Amperage: _________________ Kilowatts: ________________________________________
Storage Location:
Main Stator Megohmmeter Reading: Before Storage: After Storage:
Generator dried for 24 hours prior to start-up? (Y/N) Drying method:
SPACE HEATERS Yes No Comments
Space heaters operating properly?
Space heater operated 48 hours. before
start-up?
MEGOHMMETER TEST (SEHS9124) 30 sec. 60 sec. 30 sec. 60 sec. Ambient Comments
reading reading corrected corrected temp.
Beginning Main Stator
of Storage
Main Rotor
Exciter Stator
Exciter Rotor
PMG Stator
Start-up Main Stator
Main Rotor
Exciter Stator
Exciter Rotor
PMG Stator
(continued)
SEBU7828-09 107
Maintenance Section
Maintenance Recommendations
Table 19
GENERATOR START-UP CHECKLIST (CONT.)
ELECTRICAL Yes No Comments
Unit properly grounded
Check diodes
Over current protection
Over voltage protection
Check for loose wiring
Adjust voltage
Adjust frequency
MECHANICAL Data Comments
Bearing temperature readings at full load Front __________ Rear ___________
Stator temperature readings at full load A0 _______ B0 _______ C0 _______
Air gap on main stator Top __________ Bottom __________
Air gap on exciter stator Top __________ Bottom __________
Air gap of PMG Top __________ Bottom __________
Ambient air to generator at full load Temperature
____________________
Supplier air opening to generator Size of Opening _________________
SWITCH GEAR/PARALLEL OPERATION
Manufacturer:
Setting 1 Setting 2 Setting 3 Comments
Circuit breaker type
Overload setting
Reverse power relay
VAR/PF Controller
Load share
INSTALLATION & LOAD INFORMATION
Neutral grounding system UPS
Enclosure type - Size
Motor: Other loads:
- Total SKVA - Lighting
- Total HP - Computers
- Welding
- Non-linear
- Other
Ensure that all safety information, warnings, and Cooling System Coolant Sample (Level 1) -
Obtain ............................................................... 124
instructions are read and understood before any
Stator Lead - Check ............................................ 162
operation or any maintenance procedures are
performed.
Every Year
The user is responsible for the performance of Alternator - Inspect .............................................. 113
maintenance, including all adjustments, the use of Belts - Inspect/Adjust/Replace ............................. 118
proper lubricants, fluids, filters, and the replacement Cooling System Coolant Sample (Level 2) -
of components due to normal wear and aging. Failure Obtain ............................................................... 124
to adhere to proper maintenance intervals and Cooling System Supplemental Coolant Additive
procedures may result in diminished performance of (SCA) - Test/Add ............................................... 125
the product and/or accelerated wear of components. Crankshaft Vibration Damper - Inspect ............... 126
Engine - Clean .................................................... 127
Use mileage, fuel consumption, service hours, or Engine Air Cleaner Element (Dual Element) -
calendar time, WHICH EVER OCCURS FIRST, Clean/Replace .................................................. 128
in order to determine the maintenance intervals. Engine Crankcase Breather - Clean ................... 131
Products that operate in severe operating conditions Engine Mounts - Inspect ..................................... 131
may require more frequent maintenance. Engine Oil Sample - Obtain ................................ 132
Engine Oil and Filter - Change ........................... 133
Note: Before each consecutive interval is performed, Engine Performance - Test ................................. 134
all maintenance from the previous interval must be Engine Protective Devices - Check .................... 134
performed. Engine Valve Lash - Inspect/Adjust .................... 134
Fan Drive Bearing - Lubricate ............................. 136
When Required Fuel System Primary Filter (Water Separator)
Battery - Recycle ................................................. 116 Element - Replace ............................................ 137
Fuel System Secondary Filter - Replace ............ 138
Circuit Breakers - Reset ....................................... 119
Generator - Dry ................................................... 140
Cooling System Coolant Sample (Level 2) -
Obtain ............................................................... 124 Generator Set Vibration - Inspect ....................... 148
Generator Set Vibration - Test/Record ................ 148
Ether Starting Aid Cylinder - Replace ................. 135
Hoses and Clamps - Inspect/Replace ................ 149
Fuel System - Prime ........................................... 136
Fuel System Primary Filter/Water Separator - Insulation - Test ................................................... 152
Magnetic Pickups - Clean/Inspect ...................... 155
Drain ................................................................. 138
Radiator - Clean .................................................. 158
Generator Bearing - Lubricate ............................ 143
Generator Load - Check ..................................... 147 Starting Motor - Inspect ...................................... 162
Varistor - Check .................................................. 163
Generator Set - Test ........................................... 147
Varistor - Inspect ................................................. 164
Rotating Rectifier - Test ...................................... 159
Water Pump - Inspect ......................................... 165
Every Week
Every 3 Years
Automatic Start/Stop - Inspect ............................. 115
Battery Charger - Check ...................................... 116 Cooling System Coolant (DEAC) - Change ......... 119
Cooling System Coolant Extender (ELC) - Add .. 122
Battery Electrolyte Level - Check ......................... 117
Cooling System Water Temperature Regulator -
Cooling System Coolant Level - Check .............. 123
Electrical Connections - Check ........................... 127 Replace ............................................................. 126
Rotating Rectifier - Check ................................... 159
Engine Air Cleaner Service Indicator - Inspect ... 130
Turbocharger - Inspect ........................................ 162
Engine Oil Level - Check .................................... 132
Fuel Tank Water and Sediment - Drain ............... 139
Generator - Inspect ............................................. 141 Every 6 Years
Generator Bearing Temperature - Test/Record ... 146 Cooling System Coolant (ELC) - Change ........... 121
Generator Lead - Check ..................................... 146
Jacket Water Heater - Check .............................. 155
Power Factor - Check ......................................... 158
Space Heater - Check ........................................ 160
110 SEBU7828-09
Maintenance Section
Maintenance Interval Schedule
Commissioning
Generator Set Alignment - Check ....................... 148
SEBU7828-09 111
Maintenance Section
Maintenance Interval Schedule
Overhaul
Generator Bearing - Inspect/Replace ................. 142
Overhaul Considerations .................................... 155
SEBU7828-09 113
Maintenance Section
Aftercooler Core - Clean/Test
i02676048
NOTICE
Do not use a high concentration of caustic cleaner to
clean the core. A high concentration of caustic cleaner
Alternator - Inspect
can attack the internal metals of the core and cause SMCS Code: 1405-040
leakage. Only use the recommended concentration of
cleaner. Caterpillar recommends a scheduled inspection
of the alternator. Inspect the alternator for loose
3. Back flush the core with cleaner. connections and proper battery charging. Inspect the
ammeter (if equipped) during engine operation in
Caterpillar recommends the use of Hydrosolv order to ensure proper battery performance and/or
liquid cleaner. Table 20 lists Hydrosolv liquid proper performance of the electrical system. Make
cleaners that are available from your Caterpillar repairs, as required.
dealer.
Check the alternator and the battery charger for
Table 20 proper operation. If the batteries are properly
Hydrosolv Liquid Cleaners(1) charged, the ammeter reading should be very near
zero. All batteries should be kept charged. The
Part batteries should be kept warm because temperature
Description Size
Number affects the cranking power. If the battery is too cold,
1U-5490 Hydrosolv 4165 19 L (5 US gallon) the battery will not crank the engine. The battery will
not crank the engine, even if the engine is warm.
174-6854 Hydrosolv 100 19 L (5 US gallon) When the engine is not run for long periods of time
(1) Use a two to five percent concentration of the cleaner or if the engine is run for short periods, the batteries
at temperatures up to 93°C (200°F). Refer to Application may not fully charge. A battery with a low charge will
Guide, NEHS0526 or consult your Caterpillar dealer for more freeze more easily than a battery with a full charge.
information.
Table 21
Daily Engine Log
Date
Authorization
Engine Hours
Engine Speed
Percent Load
Ambient Temperature
Generator Voltage
Generator Amperage
Comments
i02153996
7. Connect the cable from the starting motor to the
POSITIVE “+” battery terminal.
Battery - Replace
8. Connect the cable from the ground plane to the
SMCS Code: 1401-510 NEGATIVE “-” battery terminal.
i01917570
Batteries give off combustible gases which can Battery Charger - Check
explode. A spark can cause the combustible gas-
es to ignite. This can result in severe personal in- SMCS Code: 1401-535
jury or death.
Checking Before Start-Up
Ensure proper ventilation for batteries that are in
an enclosure. Follow the proper procedures in or- Check the battery charger for proper operation. If
der to help prevent electrical arcs and/or sparks the batteries are properly charged, the needle of the
near batteries. Do not smoke when batteries are ammeter will register near “0” (zero).
serviced.
The battery charger must not produce excessive
current during start-up. Alternatively, the charger
must be automatically disconnected for start-up.
If the engine has an alternator, the charger must
The battery cables or the batteries should not be be automatically disconnected during start-up and
removed with the battery cover in place. The bat- during engine operation.
tery cover should be removed before any servic-
ing is attempted.
Charging the Battery
Removing the battery cables or the batteries with
the cover in place may cause a battery explosion
resulting in personal injury.
Never disconnect any charging unit circuit or bat-
1. Turn the key start switch to the OFF position. tery circuit cable from the battery when the charg-
Remove the key and all electrical loads. ing unit is operated. A spark can cause an explo-
sion from the flammable vapor mixture of hydro-
2. Turn OFF the battery charger. Disconnect the gen and oxygen that is released from the elec-
charger. trolyte through the battery outlets. Injury to per-
sonnel can be the result.
3. The NEGATIVE “-” cable connects the NEGATIVE
“-” battery terminal to the ground plane. Disconnect Perform the following procedure to charge the
the cable from the NEGATIVE “-” battery terminal. battery:
Overcharging reduces the service life of batteries. When the plates of the
Use a battery charger that will not overcharge the battery are inspected
battery. DO NOT charge the battery if the meter of through the filler holes, the
the battery charger is in the RED zone. plates may appear to be
warped. This is caused by
Overcharging is indicated by the following symptoms: an excessive temperature.
The battery may not pass
• The battery is very warm to the touch. a load test.
• A strong odor of acid is present. Caterpillar Maintenance The battery may not accept
Free Batteries a charging current.
• The battery emits smoke or a dense vapor (gas). The battery may not pass
a load test.
Perform one of the following procedures if the battery
shows symptoms of overcharging:
Checking After Stopping
• Reduce the rate of charging by a significant
amount. Complete the charging at the reduced Ensure that the battery charger is connected
rate. properly. Observe the meter of the charger. Record
the amperage.
• Turn OFF the charger.
Table 22 describes the effects of overcharging on i02601752
i01492654
3. Tape the leads in order to help prevent accidental 4. Tighten adjusting bolt (2). Tighten mounting
starting. bolts (1). For the proper torque, refer to the
Specifications Manual, SENR3130, “Torque
4. Proceed with necessary system repairs. Reverse Specifications”.
the steps in order to reconnect all of the cables.
5. Reinstall the belt cover.
SEBU7828-09 119
Maintenance Section
Circuit Breakers - Reset
If new belts are installed, check the belt adjustment • Foaming is observed.
again after 30 minutes of engine operation at the
rated rpm. • The oil has entered the cooling system and the
coolant is contaminated.
Replacement of Multiple Drive Belts
• The fuel has entered the cooling system and the
For applications that require multiple drive belts, coolant is contaminated.
replace the belts in matched sets. Replacing only one
belt of a matched set will cause the new belt to carry NOTICE
more load because the older belts are stretched. The Use of commercially available cooling system clean-
additional load on the new belt could cause the new ers may cause damage to cooling system compo-
belt to break. nents. Use only cooling system cleaners that are ap-
proved for Caterpillar engines.
i02456186
Note: Inspect the water pump and the water
Circuit Breakers - Reset temperature regulator after the cooling system has
been drained. This is a good opportunity to replace
SMCS Code: 1417-529; 1420-529 the water pump, the water temperature regulator and
the hoses, if necessary.
Drain
Illustration 79
g01225779 1. Stop the engine and allow the engine to cool.
Loosen the cooling system filler cap slowly in
Push in on the circuit breaker in order to reset the order to relieve any pressure. Remove the cooling
circuit breaker. system filler cap.
(A) 60 Amp Circuit Breaker – This circuit breaker 2. Open the cooling system drain valve (if equipped).
is for the battery charger and the circuit for the If the cooling system is not equipped with a drain
alternator. valve, remove one of the drain plugs.
(B) 15 Amp Circuit Breaker – This circuit breaker is Note: If equipped, be sure to drain the heater and
for the Electronic Control Module (ECM). any related supply and return lines.
(C) 20 Amp Circuit Breaker – This circuit breaker is Allow the coolant to drain.
for the control panel.
NOTICE
Dispose of used engine coolant properly or recycle.
i02139869 Various methods have been proposed to reclaim used
coolant for reuse in engine cooling systems. The full
Cooling System Coolant distillation procedure is the only method acceptable by
(DEAC) - Change Caterpillar to reclaim the used coolant.
NOTICE
3. Fill the cooling system with a mixture of clean Fill the cooling system no faster than 19 L (5 US gal)
water and Caterpillar Fast Acting Cooling System per minute to avoid air locks.
Cleaner. Add 0.5 L (1 pint) of cleaner per 15 L
(4 US gal) of the cooling system capacity. Install
the cooling system filler cap. 3. Fill the cooling system with a mixture of clean
water and Caterpillar Fast Acting Cooling System
4. Start and run the engine at low idle for a minimum Cleaner. Add 0.5 L (1 pint) of cleaner per
of 30 minutes. The coolant temperature should be 3.8 to 7.6 L (1 to 2 US gal) of the cooling system
at least 82 °C (180 °F). capacity. Install the cooling system filler cap.
NOTICE 4. Start and run the engine at low idle for a minimum
Improper or incomplete rinsing of the cooling system of 90 minutes. The coolant temperature should be
can result in damage to copper and other metal com- at least 82 °C (180 °F).
ponents.
NOTICE
To avoid damage to the cooling system, make sure Improper or incomplete rinsing of the cooling system
to completely flush the cooling system with clear wa- can result in damage to copper and other metal com-
ter. Continue to flush the system until all signs of the ponents.
cleaning agent are gone.
To avoid damage to the cooling system, make sure
to completely flush the cooling system with clear wa-
5. Stop the engine and allow the engine to cool. ter. Continue to flush the system until all signs of the
Loosen the cooling system filler cap slowly cleaning agent are gone.
in order to relieve any pressure. Remove the
cooling system filler cap. Open the drain valve
(if equipped) or remove the cooling system drain 5. Stop the engine and allow the engine to cool.
plugs. Allow the water to drain. Flush the cooling Loosen the cooling system filler cap slowly
system with clean water. If equipped, be sure to in order to relieve any pressure. Remove the
flush the heater and any related supply and return cooling system filler cap. Open the drain valve
lines. Close the drain valve (if equipped). Clean (if equipped) or remove the cooling system drain
the drain plugs. Install the drain plugs. Refer to plugs. Allow the water to drain. Flush the cooling
the Specifications Manual, SENR3130, “Torque system with clean water. Close the drain valve
Specifications” for more information on the proper (if equipped). Clean the drain plugs. Install the
torques. drain plugs. Refer to the Specifications Manual,
SENR3130, “Torque Specifications” for more
information on the proper torques.
SEBU7828-09 121
Maintenance Section
Cooling System Coolant (ELC) - Change
Fill • The fuel has entered the cooling system and the
coolant is contaminated.
NOTICE
Fill the cooling system no faster than 19 L (5 US gal) Note: When the cooling system is cleaned, only
per minute to avoid air locks. clean water is needed when the ELC is drained and
replaced.
1. Fill the cooling system with coolant/antifreeze. Note: Inspect the water pump and the water
Refer to the Operation and Maintenance Manual, temperature regulator after the cooling system has
“Refill Capacitites and Recommendations” topic been drained. This is a good opportunity to replace
(Maintenance Section) for more information on the water pump, the water temperature regulator and
cooling system specifications. Do not install the the hoses, if necessary.
cooling system filler cap.
2. Start and run the engine at low idle. Increase the Drain
engine rpm to 1500 rpm. Run the engine at high
idle for one minute in order to purge the air from
the cavities of the engine block. Stop the engine.
Pressurized System: Hot coolant can cause seri-
3. Check the coolant level. Maintain the coolant level ous burns. To open the cooling system filler cap,
within 13 mm (0.5 inch) below the bottom of the stop the engine and wait until the cooling system
pipe for filling. Maintain the coolant level within components are cool. Loosen the cooling system
13 mm (0.5 inch) to the proper level on the sight pressure cap slowly in order to relieve the pres-
glass (if equipped). sure.
Cooling System Coolant (ELC) For information regarding the disposal and the
recycling of used coolant, consult your Caterpillar
- Change dealer or consult Caterpillar Dealer Service Tool
Group:
SMCS Code: 1350-070; 1395-044
Outside Illinois: 1-800-542-TOOL
Clean the cooling system and flush the cooling
Inside Illinois: 1-800-541-TOOL
system before the recommended maintenance
Canada: 1-800-523-TOOL
interval if the following conditions exist:
2. Close the drain valve (if equipped). Clean the 4. Clean the cooling system filler cap. Inspect the
drain plugs. Install the drain plugs. For the gasket that is on the cooling system filler cap. If
proper torque, refer to the Specifications Manual, the gasket that is on the cooling system filler cap
SENR3130, “Torque Specifications”. is damaged, discard the old cooling system filler
cap and install a new cooling system filler cap. If
NOTICE the gasket that is on the cooling system filler cap is
Fill the cooling system no faster than 19 L (5 US gal) not damaged, use a 9S-8140 Pressurizing Pump
per minute to avoid air locks. in order to pressure test the cooling system filler
cap. The correct pressure for the cooling system
filler cap is stamped on the face of the cooling
3. Fill the cooling system with clean water. Install the system filler cap. If the cooling system filler cap
cooling system filler cap. does not retain the correct pressure, install a new
cooling system filler cap.
4. Start and run the engine at low idle until the
temperature reaches 49 to 66 °C (120 to 150 °F). 5. Start the engine. Inspect the cooling system for
leaks and for proper operating temperature.
5. Stop the engine and allow the engine to cool.
Loosen the cooling system filler cap slowly
i02482066
in order to relieve any pressure. Remove the
cooling system filler cap. Open the drain valve
(if equipped) or remove the cooling system
Cooling System Coolant
drain plugs. Allow the water to drain. Flush the Extender (ELC) - Add
cooling system with clean water. Close the drain
valve (if equipped). Clean the drain plugs. Install SMCS Code: 1352-045; 1395-081
the drain plugs. For the proper torque, refer to
the Specifications Manual, SENR3130, “Torque Cat ELC (Extended Life Coolant) does not require
Specifications”. the frequent additions of any supplemental cooling
additives which are associated with the present
conventional coolants. The Cat ELC Extender only
Fill needs to be added once.
NOTICE
NOTICE
Fill the cooling system no faster than 19 L (5 US gal)
Use only Cat Extended Life Coolant (ELC) Extender
per minute to avoid air locks.
with Cat ELC.
1. Fill the cooling system with Extended Life Coolant Do NOT use conventional supplemental coolant addi-
(ELC). See Special Publication, SEBU6251, tive (SCA) with Cat ELC. Mixing Cat ELC with conven-
“Caterpillar Commercial Diesel Engine Fluids tional coolants and/or conventional SCA reduces the
Recommendations” for more information on Cat ELC service life.
cooling system specifications. Do not install the
cooling system filler cap. Check the cooling system only when the engine is
stopped and cool.
2. Start and run the engine at low idle. Increase the
engine rpm to high idle. Run the engine at high
idle for one minute in order to purge the air from
the cavities of the engine block. Stop the engine.
i01197583
NOTICE g00285520
Care must be taken to ensure that fluids are contained Illustration 80
during performance of inspection, maintenance, test- Cooling system filler cap
ing, adjusting and repair of the product. Be prepared to
collect the fluid with suitable containers before open-
ing any compartment or disassembling any compo-
nent containing fluids.
Pressurized System: Hot coolant can cause seri-
ous burns. To open the cooling system filler cap,
Refer to Special Publication, NENG2500, “Caterpillar
stop the engine and wait until the cooling system
Dealer Service Tool Catalog” for tools and supplies
components are cool. Loosen the cooling system
suitable to collect and contain fluids on Caterpillar
pressure cap slowly in order to relieve the pres-
products.
sure.
Dispose of all fluids according to local regulations and
mandates. 1. Remove the cooling system filler cap slowly in
order to relieve pressure.
1. Loosen the cooling system filler cap slowly in
order to relieve pressure. Remove the cooling 2. Maintain the coolant level within 13 mm (0.5 inch)
system filler cap. of the bottom of the filler pipe. If the engine is
equipped with a sight glass, maintain the coolant
2. It may be necessary to drain enough coolant from level to the proper level in the sight glass.
the cooling system in order to add the Cat ELC
Extender.
g00103639
Illustration 81
Typical filler cap gaskets
124 SEBU7828-09
Maintenance Section
Cooling System Coolant Sample (Level 1) - Obtain
3. Clean the cooling system filler cap and check the Obtain the sample of the coolant as close as possible
condition of the filler cap gaskets. Replace the to the recommended sampling interval. In order
cooling system filler cap if the filler cap gaskets are to receive the full effect of S·O·S analysis, you
damaged. Reinstall the cooling system filler cap. must establish a consistent trend of data. In order
to establish a pertinent history of data, perform
4. Inspect the cooling system for leaks. consistent samplings that are evenly spaced.
Supplies for collecting samples can be obtained from
your Caterpillar dealer.
i02837191
Cooling System Coolant Use the following guidelines for proper sampling of
the coolant:
Sample (Level 1) - Obtain
• Complete the information on the label for the
SMCS Code: 1350-008; 1395-008; 1395-554; 7542 sampling bottle before you begin to take the
samples.
Note: Obtaining a Coolant Sample (Level 1) is
optional if the cooling system is filled with Cat • Keep the unused sampling bottles stored in plastic
ELC (Extended Life Coolant). Cooling systems that bags.
are filled with Cat ELC should have a Coolant Sample
(Level 2) that is obtained at the recommended interval • Obtain coolant samples directly from the coolant
that is stated in the Maintenance Interval Schedule. sample port. You should not obtain the samples
from any other location.
Note: Obtain a Coolant Sample (Level 1) if the
cooling system is filled with any other coolant • Keep the lids on empty sampling bottles until you
instead of Cat ELC. This includes the following are ready to collect the sample.
types of coolants:
• Place the sample in the mailing tube immediately
• Commercial long life coolants that meet the after obtaining the sample in order to avoid
Caterpillar Engine Coolant Specification -1 contamination.
(Caterpillar EC-1)
• Never collect samples from expansion bottles.
• Cat DEAC (Diesel Engine Antifreeze/Coolant)
• Never collect samples from the drain for a system.
• Commercial heavy-duty coolant/antifreeze
Submit the sample for Level 1 analysis.
Table 23
Recommended Interval For additional information about coolant analysis,
see this Operation and Maintenance Manual, “Refill
Type of Coolant Level 1 Level 2 Capacities and Recommendations” or consult your
Every 250 Caterpillar dealer.
Cat DEAC Yearly(1)(2)
Hours(1)
Cat ELC Optional(2) Yearly(2) i01987714
(1) This is the recommended interval for coolant samples for all
conventional heavy-duty coolant/antifreeze. This is also the
Cooling System Coolant
recommended interval for coolant samples of commercial
coolants that meet the Cat EC-1 specification for engine
Sample (Level 2) - Obtain
coolant.
(2) The Level 2 Coolant Analysis should be performed sooner if a SMCS Code: 1350-008; 1395-008; 1395-554; 7542
problem is suspected or identified.
NOTICE
NOTICE Always use a designated pump for oil sampling, and
Always use a designated pump for oil sampling, and use a separate designated pump for coolant sampling.
use a separate designated pump for coolant sampling. Using the same pump for both types of samples may
Using the same pump for both types of samples may contaminate the samples that are being drawn. This
contaminate the samples that are being drawn. This contaminate may cause a false analysis and an incor-
contaminate may cause a false analysis and an incor- rect interpretation that could lead to concerns by both
rect interpretation that could lead to concerns by both dealers and customers.
dealers and customers.
Refer to Operation and Maintenance Manual,
Note: Level 1 results may indicate a need for “Cooling System Coolant Sample (Level 1) - Obtain”
Level 2 Analysis. for the guidelines for proper sampling of the coolant.
SEBU7828-09 125
Maintenance Section
Cooling System Supplemental Coolant Additive (SCA) - Test/Add
NOTICE
Add the SCA, If Necessary
Do not exceed the recommended six percent supple-
mental coolant additive concentration. NOTICE
Do not exceed the recommended amount of sup-
Use the 8T-5296 Coolant Conditioner Test Kit plemental coolant additive concentration. Excessive
or use the 4C-9301 Coolant Conditioner Test Kit supplemental coolant additive concentration can form
in order to check the concentration of the SCA. deposits on the higher temperature surfaces of the
Refer to this Operation and Maintenance Manual, cooling system, reducing the engine's heat transfer
“Refill Capacities and Recommendations” for more characteristics. Reduced heat transfer could cause
information. cracking of the cylinder head and other high temper-
ature components. Excessive supplemental coolant
additive concentration could also result in radiator
Water and SCA tube blockage, overheating, and/or accelerated water
pump seal wear. Never use both liquid supplemental
NOTICE coolant additive and the spin-on element (if equipped)
Do not exceed the recommended eight percent sup- at the same time. The use of those additives together
plemental coolant additive concentration. could result in supplemental coolant additive concen-
tration exceeding the recommended maximum.
Test the concentration of the SCA with the 8T-5296
Coolant Conditioner Test Kit. Refer to the Special
Publication, SEBU6251, “Caterpillar Commercial
Diesel Engine Fluids Recommendations” for more
information.
126 SEBU7828-09
Maintenance Section
Cooling System Water Temperature Regulator - Replace
NOTICE
1. Slowly loosen the cooling system filler cap in Failure to replace your water temperature regulator
order to relieve the pressure. Remove the cooling on a regularly scheduled basis could cause severe
system filler cap. engine damage.
Note: Always discard drained fluids according to Caterpillar engines incorporate a shunt design cooling
local regulations. system and require operating the engine with a water
temperature regulator installed.
2. If necessary, drain some coolant from the cooling
system into a suitable container in order to allow If the water temperature regulator is installed incor-
space for the extra SCA. rectly, the engine may overheat, causing cylinder head
damage. Ensure that the new water temperature reg-
3. Add the proper amount of SCA. Refer ulator is installed in the original position. Ensure that
to the Special Publication, SEBU6251, the water temperature regulator vent hole is open.
“Caterpillar Commercial Diesel Engines Fluids
Recommendations” for more information on SCA Do not use liquid gasket material on the gasket or
requirements. cylinder head surface.
4. Clean the cooling system filler cap. Inspect the
gaskets of the cooling system filler cap. If the Refer to two articles in the Disassembly and
gaskets are damaged, replace the old cooling Assembly Manual, “Water Temperature Regulators
system filler cap with a new cooling system filler - Remove and Water Temperature Regulators -
cap. Install the cooling system filler cap. Install” for the replacement procedure of the water
temperature regulator, or consult your Caterpillar
dealer.
i03645060
Cooling System Water Note: If only the water temperature regulators are
replaced, drain the coolant from the cooling system to
Temperature Regulator - a level that is below the water temperature regulator
housing.
Replace
SMCS Code: 1355-510 i00894991
Steam cleaning the engine will remove accumulated Replace the dirty paper air cleaner elements with
oil and grease. A clean engine provides the following clean air cleaner elements. Before installation, the
benefits: air cleaner elements should be thoroughly checked
for tears and/or holes in the filter material. Inspect
• Easy detection of fluid leaks the gasket or the seal of the air cleaner element for
damage. Maintain a supply of suitable air cleaner
• Maximum heat transfer characteristics elements for replacement purposes.
i01553486
The dual element air cleaner contains a primary
air cleaner element and a secondary air cleaner
Engine Air Cleaner Element element. The primary air cleaner element can be
used up to six times if the element is properly cleaned
(Dual Element) - Clean/Replace and inspected. The primary air cleaner element
should be replaced at least one time per year. This
SMCS Code: 1054-037; 1054-510 replacement should be performed regardless of the
number of cleanings.
NOTICE
Never run the engine without an air cleaner element The secondary air cleaner element is not serviceable
installed. Never run the engine with a damaged air or washable. The secondary air cleaner element
cleaner element. Do not use air cleaner elements with should be removed and discarded for every three
damaged pleats, gaskets or seals. Dirt entering the cleanings of the primary air cleaner element. When
engine causes premature wear and damage to engine the engine is operating in environments that are
components. Air cleaner elements help to prevent air- dusty or dirty, air cleaner elements may require more
borne debris from entering the air inlet. frequent replacement.
NOTICE
Never service the air cleaner element with the engine
running since this will allow dirt to enter the engine.
• The air cleaner element may be cleaned up to 2. The secondary air cleaner element should be
six times if the element is properly cleaned and removed and discarded for every three cleanings
inspected. of the primary air cleaner element.
• The air cleaner element should be replaced at least Note: Refer to “Cleaning the Primary Air Cleaner
one time per year. This replacement should be Elements”.
performed regardless of the number of cleanings.
3. Cover the turbocharger air inlet with tape in order
to keep dirt out.
5. Remove the tape for the turbocharger air inlet. There are two common methods that are used to
Install the secondary air cleaner element. Install a clean primary air cleaner elements:
primary air cleaner element that is new or cleaned.
• Pressurized air
6. Install the air cleaner cover.
• Vacuum cleaning
7. Reset the air cleaner service indicator.
Pressurized Air
Cleaning the Primary Air Cleaner
Pressurized air can be used to clean primary air
Elements cleaner elements that have not been cleaned more
than two times. Pressurized air will not remove
NOTICE deposits of carbon and oil. Use filtered, dry air with a
Caterpillar recommends certified air filter cleaning ser- maximum pressure of 207 kPa (30 psi).
vices that are available at Caterpillar dealers. The
Caterpillar cleaning process uses proven procedures
to assure consistent quality and sufficient filter life.
Use clean primary air cleaner elements while dirty Vacuum Cleaning
elements are being cleaned.
Vacuum cleaning is a good method for cleaning
primary air cleaner elements which require daily
NOTICE cleaning because of a dry, dusty environment.
Do not clean the air cleaner elements by bumping or Cleaning with pressurized air is recommended prior
tapping. This could damage the seals. Do not use el- to vacuum cleaning. Vacuum cleaning will not remove
ements with damaged pleats, gaskets or seals. Dam- deposits of carbon and oil.
aged elements will allow dirt to pass through. Engine
damage could result. Note: Refer to “Inspecting the Primary Air Cleaner
Elements”.
Visually inspect the primary air cleaner elements
before cleaning. Inspect the air cleaner elements for
damage to the seal, the gaskets, and the outer cover.
Discard any damaged air cleaner elements.
130 SEBU7828-09
Maintenance Section
Engine Air Cleaner Service Indicator - Inspect
Inspecting the Primary Air Cleaner Do not use paint, a waterproof cover, or plastic as a
Elements protective covering for storage. An airflow restriction
may result. To protect against dirt and damage, wrap
the primary air cleaner elements in Volatile Corrosion
Inhibited (VCI) paper.
• Date of cleaning
• Number of cleanings
Store the box in a dry location.
g00281693
Illustration 84
i01900118
g00281694
Illustration 85
g00103777
Illustration 86
Typical service indicator
SEBU7828-09 131
Maintenance Section
Engine Crankcase Breather - Clean
Typical example
• Check the movement of the yellow core when the (1) Hose clamp
engine is accelerated to the engine rated speed. (2) Cover clamp
The yellow core should latch approximately at the (3) Crankcase breather cover
greatest vacuum that is attained.
1. Loosen hose clamp (1) and remove the hose from
If the service indicator does not reset easily, or if the crankcase breather (2).
yellow core does not latch at the greatest vacuum,
the service indicator should be replaced. If the new 2. Remove the crankcase breather (2).
service indicator will not reset, the hole for the service
indicator may be plugged. 3. Wash the breather element in solvent that is clean
and nonflammable. Allow the breather element to
The service indicator may need to be replaced dry before installation.
frequently in environments that are severely dusty, if
necessary. Replace the service indicator annually 4. Install a breather element that is clean and dry.
regardless of the operating conditions. Replace the Install the crankcase breather (2). Refer to the
service indicator when the engine is overhauled, and Operation and Maintenance Manual for the proper
whenever major engine components are replaced. torque.
Note: When a new service indicator is installed, 5. Install the hose. Install hose clamp (1). Refer to
excessive force may crack the top of the service the Operation and Maintenance Manual for the
indicator. Tighten the service indicator to a torque proper torques.
of 2 N·m (18 lb in).
i02139969
i01564253
Engine Mounts - Inspect
Engine Crankcase Breather -
Clean SMCS Code: 1152-040
SMCS Code: 1317-070 Inspect the engine mounts for deterioration and for
proper bolt torque. Engine vibration can be caused
by the following conditions:
NOTICE
Perform this maintenance with the engine stopped.
• Improper mounting of the engine
If the crankcase breather is not maintained on a • Deterioration of the engine mounts
regular basis, the crankcase breather will become
plugged. A plugged crankcase breather will cause Any engine mount that shows deterioration should
excessive crankcase pressure that may cause be replaced. Refer to the Specifications Manual,
crankshaft seal leakage. SENR3130, “Torque Specifications”. Refer to your
Caterpillar dealer for more information.
132 SEBU7828-09
Maintenance Section
Engine Oil Level - Check
• Engine model
• Service hours on the engine
• The number of hours that have accumulated since
g00110310 the last oil change
Illustration 88
(Y) “ADD” mark. (X) “FULL” mark. • The amount of oil that has been added since the
last oil change
NOTICE
Perform this maintenance with the engine stopped. To ensure that the sample is representative of the
oil in the crankcase, obtain a warm, well mixed oil
sample.
1. Maintain the oil level between “ADD” mark (Y) and
“FULL” mark (X) on oil level gauge (1). Do not fill To avoid contamination of the oil samples, the tools
the crankcase above “FULL” mark (X). and the supplies that are used for obtaining oil
samples must be clean.
NOTICE
Operating your engine when the oil level is above the Caterpillar recommends using the sampling valve
“FULL” mark could cause your crankshaft to dip into in order to obtain oil samples. The quality and the
the oil. The air bubbles created from the crankshaft consistency of the samples are better when the
dipping into the oil reduces the oil's lubricating char- sampling valve is used. The location of the sampling
acteristics and could result in the loss of power. valve allows oil that is flowing under pressure to be
obtained during normal engine operation.
2. Remove the oil filler cap and add oil, if necessary. The 169-8373 Fluid Sampling Bottle is
Clean the oil filler cap. Install the oil filler cap. recommended for use with the sampling valve. The
fluid sampling bottle includes the parts that are
i03542996
needed for obtaining oil samples. Instructions are
also provided.
Engine Oil Sample - Obtain
NOTICE
SMCS Code: 1000-008; 1348-554-SM; Always use a designated pump for oil sampling, and
7542-554-OC, SM use a separate designated pump for coolant sampling.
Using the same pump for both types of samples may
In addition to a good preventive maintenance contaminate the samples that are being drawn. This
program, Caterpillar recommends using S·O·S oil contaminate may cause a false analysis and an incor-
analysis at regularly scheduled intervals in order rect interpretation that could lead to concerns by both
to monitor the condition of the engine and the dealers and customers.
maintenance requirements of the engine. S·O·S oil
analysis provides infrared analysis, which is required
for determining nitration and oxidation levels. If the engine is not equipped with a sampling valve,
use the 1U-5718 Vacuum Pump. The pump is
designed to accept sampling bottles. Disposable
tubing must be attached to the pump for insertion
into the sump.
SEBU7828-09 133
Maintenance Section
Engine Oil and Filter - Change
For instructions, see Special Publication, PEgj0047, Replace the Oil Filter
“How To Take A Good S·O·S Oil Sample”. Consult
your Caterpillar dealer for complete information and
NOTICE
assistance in establishing an S·O·S program for your
Caterpillar oil filters are built to Caterpillar speci-
engine.
fications. Use of an oil filter not recommended by
Caterpillar could result in severe engine damage to
i02107152 the engine bearings, crankshaft, etc., as a result of
the larger waste particles from unfiltered oil entering
Engine Oil and Filter - Change the engine lubricating system. Only use oil filters
recommended by Caterpillar.
SMCS Code: 1318-510; 1348-044
1. Remove the oil filter with a 1U-8760 Chain
Wrench.
Hot oil and hot components can cause personal 2. Cut the oil filter open with a 175-7546 Oil Filter
injury. Do not allow hot oil or hot components to Cutter Gp. Break apart the pleats and inspect the
contact the skin. oil filter for metal debris. An excessive amount
of metal debris in the oil filter may indicate early
Do not drain the oil when the engine is cold. As the oil wear or a pending failure.
cools, suspended waste particles settle on the bottom
of the oil pan. The waste particles are not removed Use a magnet to differentiate between the ferrous
with the draining cold oil. Drain the crankcase with metals and the nonferrous metals that are found in
the engine stopped. Drain the crankcase with the the oil filter element. Ferrous metals may indicate
oil warm. This draining method allows the waste wear on the steel and cast iron parts of the engine.
particles that are suspended in the oil to be drained
properly. Nonferrous metals may indicate wear on the
aluminum parts, brass parts or bronze parts of
Failure to follow this recommended procedure will the engine. Parts that may be affected include
cause the waste particles to be recirculated through the following items: main bearings, rod bearings,
the engine lubrication system with the new oil. turbocharger bearings, and cylinder heads.
After the oil has drained, the oil drain plugs should
be cleaned and installed.
g00103713
Illustration 89
Typical filter mounting base and filter gasket
i01042067
Engine Valve Lash -
Inspect/Adjust
Engine Performance - Test
SMCS Code: 1102-025
SMCS Code: 1000-081
The initial valve lash adjustment on new engines,
Operate the engine for a minimum of two hours at a rebuilt engines, or remanufactured engines is
minimum load of 60 percent. recommended at the first scheduled oil change. The
adjustment is necessary due to the initial wear of
• Monitor the operation of the generator set. the valve train components and to the seating of the
valve train components.
• Observe the gauges. Ensure that the gauges are
in the normal ranges.
SEBU7828-09 135
Maintenance Section
Engine Valve Rotators - Inspect
i00805059
Ensure that the engine cannot be started while this Ether Starting Aid Cylinder -
maintenance is being performed. To help prevent
possible injury, do not use the starting motor to
Replace
turn the flywheel. (If Equipped)
Hot engine components can cause burns. Allow SMCS Code: 1456-510-CD
additional time for the engine to cool before mea-
suring/adjusting valve lash clearance.
i01597115
i02784507 Prime the fuel system in order to fill dry fuel filters.
You must also prime the fuel system after any one of
Fan Drive Bearing - Lubricate the following conditions exist:
SMCS Code: 1359-086-BD • The fuel system has run dry.
Some of the fan drives have grease fittings and some • The engine has been in prolonged storage.
of the fan drives do not have grease fittings. If there is
no grease fitting, periodic lubrication is not required. • The fuel filter has been cleaned.
The fan drive requires grease only if the fan drive
is equipped with a zerk. • The fuel filter has been replaced.
Note: If the engine does not have a fuel priming
pump, refer to Step 4.
NOTICE
Do not crank the engine for more than 30 seconds. Al-
low the starter to cool for two minutes before cranking
Illustration 91
g00746166 again. Turbocharger damage can result if the engine
Typical location of the grease fitting (if equipped) that is for the fan
rpm is not kept low until the oil gauge display verifies
drive bearing that the oil pressure is sufficient.
The pulley is shown with the belt guards that have been removed.
3. Crank the engine.
Lubricate the grease fitting that is on the fan drive
bearing with High Speed Ball Bearing Grease or the If the engine starts and the engine runs rough,
equivalent. run the engine at low idle. Continue running the
engine until the engine runs smoothly.
Inspect the fan drive pulley assembly for wear or for
damage. If the shaft is loose, an inspection of the
internal components should be performed. Refer to NOTICE
the Systems Operation Testing and Adjusting Manual During periodic service, DO NOT remove the fuel filter
for additional information. plug that is in the fuel filter base in order to purge air
from the fuel system. The periodic removal of the fuel
filter plug will result in increased wear on the threads
i00891826 in the fuel filter base. This wear leads to fuel leakage.
Fuel System - Prime
4. Open the vent valve (if equipped) on the fuel
SMCS Code: 1258-548 injection pump's housing.
g00290109
Illustration 92
i01254694
NOTICE
Use a suitable container to catch any fuel that might
Fuel System Primary
spill. Clean up any spilled fuel immediately. Filter/Water Separator - Drain
SMCS Code: 1260-543; 1263-543
5. Remove the fuel filter bowl (1) and wash the fuel
filter bowl with clean diesel fuel.
NOTICE
In order to maximize fuel system life and prevent pre-
mature wear out from abrasive particles in the fuel,
use Caterpillar fuel filters.
g00668636
Consult your Caterpillar dealer for proper part num- Illustration 94
bers. (1) Bowl
(2) Element
(3) Drain
9. Install the new fuel filter (2). Spin the fuel filter
onto the fuel filter base until the gasket contacts Bowl (1) should be monitored daily for signs of water.
the base. Use the rotation index marks on the If water is present, drain the water from the bowl.
filters as a guide for proper tightening. Tighten the
filter for an additional 3/4 turn by hand. Do not 1. Open drain (3). The drain is a self-ventilated drain.
overtighten the filter. Catch the draining water in a suitable container.
Dispose of the water properly.
NOTICE
Do not fill the fuel filters with fuel before installing them. 2. Close drain (3).
The fuel would not be filtered and could be contami-
nated. Contaminated fuel will cause accelerated wear NOTICE
to fuel system parts. The water separator is under suction during normal
engine operation. Ensure that the drain valve is tight-
10. Install the clean fuel filter bowl (1) on the new fuel ened securely to help prevent air from entering the fuel
filter. system.
NOTICE
The water separator is under suction during normal i01250684
12. Start the engine and check for leaks. Run the
engine for one minute. Stop the engine and check
the engine for leaks again. Fuel leaked or spilled onto hot surfaces or elec-
trical components can cause a fire. To help pre-
Detection of leaks is very difficult especially if vent possible injury, turn the start switch off when
the engine is running. The primary filter/water changing fuel filters or water separator elements.
separator is under suction. A leak will allow air to Clean up fuel spills immediately.
enter the fuel. The air in the fuel can cause low
power due to aeration of the fuel. If air enters the
fuel, check the components for overtightening or
undertightening.
SEBU7828-09 139
Maintenance Section
Fuel Tank Water and Sediment - Drain
NOTICE
Do not fill the secondary fuel filter with fuel before in-
stalling. The fuel would not be filtered and could be
contaminated. Contaminated fuel will cause acceler-
ated wear to fuel system parts.
5. Install the new fuel filter. Spin the fuel filter onto
the fuel filter base until the gasket contacts the
base. Use the rotation index marks on the filters
as a guide for proper tightening. Tighten the
filter for an additional 3/4 turn by hand. Do not
overtighten the filter.
g00410343
Illustration 95 6. Open the fuel tank supply valve and prime the fuel
(1) Fuel priming pump system.
(2) Fuel filter
(3) Fuel block
(4) Fuel filter air purge plug i03645042
NOTICE
Fuel Tank Water and Sediment
Do not allow dirt to enter the fuel system. Thoroughly - Drain
clean the area around a fuel system component that
will be disconnected. Fit a suitable cover over any dis- SMCS Code: 1273-543-M&S
connected fuel system components.
NOTICE
Care must be taken to ensure that fluids are contained
NOTICE during performance of inspection, maintenance, test-
Use a suitable container to catch any fuel that might ing, adjusting and repair of the product. Be prepared to
spill. Clean up any spilled fuel immediately. collect the fluid with suitable containers before open-
ing any compartment or disassembling any compo-
1. It may be necessary to relieve residual fuel nent containing fluids.
pressure from the fuel system before removing
the fuel filter. Refer to Special Publication, NENG2500, “Caterpillar
Dealer Service Tool Catalog” or refer to Special Pub-
Loosen the fuel filter air purge plug (4) in order to lication, PECJ0003, “Caterpillar Shop Supplies and
purge any residual pressure. Tools Catalog” for tools and supplies suitable to col-
lect and contain fluids on Caterpillar products.
NOTICE Dispose of all fluids according to local regulations and
Do not loosen fuel lines or fittings at the fuel manifold mandates.
or ECM. The engine components may be damaged.
Open the drain valve on the bottom of the fuel tank i01936148
in order to drain the water and the sediment. Close
the drain valve. Generator - Dry
Note: Failure to properly close the drain can allow air SMCS Code: 4450-569
into the system, which could have detrimental results
to performance.
Check the fuel daily. Drain the water and sediment Personal injury or death can result from improper
from the fuel tank after operating the engine or drain troubleshooting and repair procedures.
the water and sediment from the fuel tank after the
fuel tank has been filled. Allow five to ten minutes The following troubleshooting and repair proce-
before performing this procedure. dures should only be performed by qualified per-
sonnel familiar with this equipment.
Fill the fuel tank after operating the engine in
order to drive out moist air. This will help prevent
condensation. Do not fill the tank to the top. The Note: The use of space heaters and occasional
fuel expands as the fuel gets warm. The tank may cranking of the engine will help to avoid drying
overflow. the generator. Space heaters should be used
continuously while the machine is stopped in order
Some fuel tanks use supply pipes that allow water for the space heaters to be effective.
and sediment to settle below the end of the fuel
supply pipe. Some fuel tanks use supply lines that Refer to Safety Section, “Generator Isolating for
take fuel directly from the bottom of the tank. If Maintenance” for information regarding the procedure
the engine is equipped with this system, regular to safely isolate the generator.
maintenance of the fuel system filter is important.
If the insulation resistance values are less than 1
megohm for the stator or the insulation resistance
Fuel Storage Tanks values are less than 100,000 ohms for the other
windings, one of the following drying procedures
Drain the water and the sediment from the fuel must be selected. This decision should be based on
storage tank during the following conditions: the following factors:
Self-Circulating Air Method 6. Operate the generator at the rated speed. Adjust
the current in the exciter field with the rheostat.
Blow hot air into the air intake for the generator. Obtain the rated output current in the short circuit
Disconnect the exciter field and run the engine. This connections.
will help circulate air. Operate the generator space
heaters.
i01461264
If harmful dirt accumulations are present, a variety A high pressure wash sprays a high velocity fluid
of cleaning techniques are available. The cleaning stream of this solution over the generator that is
procedure that is used may be determined by one of being cleaned. This detergent washing is followed by
the items on the following list: multiple sprays of clean water. The clean water is
used in order to remove the detergent or the clean
• The extent of the cleaning procedure that is being water is used in order to dilute the detergent.
attempted
Allow the generator to dry at room temperature.
• The type of enclosure of the generator Check the insulation resistance. The insulation
resistance should now be normal. If the insulation
• The voltage rating of the generator resistance is not normal, repeat the procedure. It
may be necessary to use solvents if the generator
• The type of dirt that is being removed is contaminated with oil or if the generator is
contaminated with grease.
Cleaning (Assembled Generators) Note: For more information on drying methods, refer
to Special Instructions, SEHS9124, “Cleaning and
Cleaning may be required at the point of installation.
Drying of Electric Set Generators”.
At this point, complete disassembly of the generator
may not be necessary or feasible. In this case,
a vacuum cleaner should be used to pick up the i03099722
following items: dry dirt, dust, and carbon. This will
prevent the spreading of these contaminants. Generator Bearing -
A small nonconductive tube may need to be
Inspect/Replace
connected to the vacuum cleaner. This will allow the (SR4 Generator)
vacuum cleaner to clean the surfaces that are not
exposed. After most of the dust has been removed, SMCS Code: 4471-040; 4471-510
a small brush may be attached to the vacuum hose
in order to loosen dirt that is more firmly attached to The following maintenance procedure for generator
the surface. bearings should be followed at every major engine
overhaul:
After the initial cleaning with a vacuum, compressed
air may be used to remove the remaining dust and
dirt. Compressed air that is used for cleaning should
Inspect
be free of moisture and free of oil. Air pressure
1. Remove the bearing bracket. Inspect the following
should be a maximum of 210 kPa (30 psi) in order to
items: bracket bore, bearing outer race, and
prevent mechanical damage to the insulation. If the
rolling elements. On standby power units, the
above cleaning procedures are not effective, consult
bearing must be inspected and the grease must
a Caterpillar dealer.
be replaced at three year intervals. The sleeve
in the bearing bracket should be inspected for
Cleaning (Disassembled out of roundness, excessive wear, and a bracket
Generators) step that is less than 0.0762 mm (0.0030 inch). If
there is no sleeve in the bearing bracket, inspect
An initial insulation resistance check should be the bore of the bearing bracket. The bearing
made on the generator in order to confirm electrical should be inspected for damage to the outer race,
integrity. A minimum reading of one megohm would severe fretting, and smoothness of operation.
be expected with severely contaminated generators. When possible, the bearing elements should be
A zero megohm reading may indicate an insulation inspected. Some double shielded ball bearings
breakdown. An insulation breakdown requires more prevent visual inspection of the elements of the
than cleaning. An insulation breakdown requires bearing. Other double shielded ball bearings
repair. have a retaining ring. This retaining ring can be
removed in order to allow access for a visual
A high pressure wash is normally an effective way inspection of the elements of the bearing.
to clean windings. This includes windings that have
been exposed to flooding or windings that have been On two-bearing generators, the front bearing
contaminated by salt. A solution of hot water and can only be removed after the drive coupling
detergent is used for this method of cleaning. is removed. Refer to the Systems Operation
Testing and Adjusting Disassembly and Assembly,
“Coupling - Remove” for the generator for
instructions for removing the drive coupling.
SEBU7828-09 143
Maintenance Section
Generator Bearing - Lubricate
Replace
1. All ball bearings should be cleaned. The cavity
in the bracket should be repacked with 2S-3230
Grease. Pack the ball bearings (one-third to
one-half of the volume of the cavity).
i03840850
Table 25
Bearing Bearing Frame Temperature Grease Interval Weight Volume Shaft
Part Type Size Min/Max(1) Part Diameter
Number Number
108-1760 321 BC 680 −29 °C 2S-3230 Every 2000 51.2 g 59 mL (2 oz) 105.0 mm
Ball Bearing 225.0 mm (−20.2 °F) Bearing service (1.8 oz) (4.1 inch)
(8.9 inch) minimum Lubricant hours or 12
OD / months
80 °C
105.0 mm (176 °F)
(4.1 inch) ID maximum
108-1761 322 BC 690 / −29 °C 2S-3230 Every 2000 51.2 g 59 mL (2 oz) 110.0 mm
Ball Bearing 240.0 mm 800 (−20.2 °F) Bearing service (1.8 oz) (4.3 inch)
(9.4 inch) / Lubricant hours or 12
OD 80 °C months
(176 °F)
110.0 mm
(4.3 inch) ID
139-0349 Roller 2900 / −40 °C Mobilith Every 250 2.8 g NA 127.0 mm
Roller 2800 (−40 °F) SHC220 service (0.1 oz) (5.0 inch)
Bearing / hours
80 °C
(176 °F)
139-0350 Roller 2900 / −40 °C Mobilith Every 250 2.8 g NA 127.0 mm
Roller 2800 (−40 °F) SHC220 service (0.1 oz) (5.0 inch)
Bearing / hours
80 °C
(176 °F)
154-3032 326 BC 820 / −29 °C 2S-3230 Every 2000 51.2 g 59 mL (2 oz) 130.0 mm
Ball Bearing 280.0 mm 2600 / (−20.2 °F) Bearing service (1.8 oz) (5.1 inch)
(11.0 inch) 2700 / Lubricant hours or 12
OD 80 °C months
(176 °F)
130.0 mm
(5.1 inch) ID
241-4644 320 BC LC7 −29 °C UNIREX Every 4500 60 g NA 100.0 mm
Bearing 215.0 mm (−20.2 °F) N3 service (2.1 oz) (3.9 inch)
(8.5 inch) / hours or 12
OD 60 °C months
(140 °F)(2)
100.0 mm
(3.9 inch) ID
243-5220 315 BB LC6100 −29 °C UNIREX Non- Non- Non- 75.0 mm
Bearing 160.0 mm / (−20.2 °F) N3 regreasable regreasable regreasable (3.0 inch)
(6.3 inch) LC5000 / bearing(3) bearing bearing
OD 60 °C
(140 °F)(2)
75.0 mm
(3.0 inch) ID
261-3545 307 BB LC2000 −29 °C UNIREX Non- Non- Non- 35.0 mm
Bearing 80.0 mm (−20.2 °F) N3 regreasable regreasable regreasable (1.4 inch)
(3.1 inch) / bearing(3) bearing bearing
OD 50 °C
(122 °F)(2)
35.0 mm
(1.4 inch) ID
(continued)
SEBU7828-09 145
Maintenance Section
Generator Bearing - Lubricate
5. Wipe off the excess grease. Remove the top Resistive Temperature Detectors
grease fitting. Install the plug. (RTDs)
6. Operate the generator for one hour. This will allow
Caterpillar Generators may be equipped with
the grease to expand. The expanding grease will resistance temperature detectors for generator
force the excess grease from the cavity. When
bearings. These detectors are 100 ohm resistance
the excess grease is forced from the cavity, the
temperature detectors. A resistance temperature
internal pressure will be reduced. The generator detector may be monitored by the optional monitor for
should continue to operate until the grease stops
the EMCP 3.2/3.3 resistance temperature detector. A
purging.
resistance temperature detector may be monitored by
equipment that is provided by the customer. Consult
7. Stop the engine. Install the plug in the bottom
with your Caterpillar dealer about other methods of
grease pipe. Wipe off the excess grease.
measuring the bearing temperature.
8. Install the louver assembly or install the rear plate.
The EMCP 3.2/3.3 may be configured to “ALARM”
or the EMCP 3.2/3.3 may be configured to
i03642839 “SHUTDOWN”. An alarm is activated if the
temperature of the bearing reaches 85 °C (185 °F).
Generator Bearing A shutdown occurs if the temperature of the bearing
Temperature - Test/Record reaches 95 °C (203 °F).
i01228480
Generator Load - Check Personal injury or death can result from high volt-
age.
SMCS Code: 4450-535-LA
When power generation equipment must be in op-
During normal operation, monitor the power factor eration to make tests and/or adjustments, high
and monitor generator loading. voltage and current are present.
When a generator is installed or when a generator Improper test equipment can fail and present a
is reconnected, ensure that the total current in any high voltage shock hazard to its user.
one phase does not exceed the nameplate rating.
Each phase should carry the same load. This allows Make sure the testing equipment is designed for
the generator to work at the rated capacity. If one and correctly operated for high voltage and cur-
phase current exceeds the nameplate amperage, rent tests being made.
an electrical imbalance will occur. An electrical
imbalance can result in an electrical overload and an When servicing or repairing electric power gener-
electrical imbalance can result in overheating . ation equipment:
The power factor can be referred to as the efficiency • Make sure the unit is off-line (disconnected
of the load. This can be expressed as the ratio of kVA from utility and/or other generators power
to actual kW. The power factor can be calculated by service), and either locked out or tagged DO
dividing kW by kVA. Power factor is expressed as a NOT OPERATE.
decimal. Power factor is used to mean the portion
of current that is supplied to a system that is doing • Make sure the generator engine is stopped.
useful work. The portion of the current that is not
doing useful work is absorbed in maintaining the • Make sure all batteries are disconnected.
magnetic field in motors. This current (reactive load)
can be maintained without engine power. • Make sure all capacitors are discharged.
Electric sets normally have a low idle setting that Table 26
is higher than industrial engines. Low idle will be
Tools Needed
approximately 66% of the full speed that is achieved
by 60 Hz units. This would be equal to 80% of the full Part Number Part Quantity
speed that is achieved by 50 Hz units.
Digital
6V-7070 1
Multimeter
Some electric sets are equipped with Woodward
governors and some electric sets are equipped 12 VDC battery 1
with Caterpillar electronic governors. These electric
Potential
sets have no low idle stop. On electric sets with 1
Transformer
mechanical governors and natural gas electric sets,
the low idle is set at the factory. Adjustment of the
low idle on these machines should only be done by The generator set functional test is a simplified test
a Caterpillar dealer. that can be performed in order to determine if the
generator is functional. The generator set functional
Note: Operating the electric set at low idle speed for test should be performed on a generator set that is
an extended time will cause some voltage regulators under load.
to shut off. The electric set must be completely shut
down and the electric set must be restarted. This The generator set functional test determines if the
will allow the voltage regulator to again produce an following statements happen:
output.
• A phase voltage is being generated.
• The phase voltages are balanced.
148 SEBU7828-09
Maintenance Section
Generator Set Alignment - Check
• The phase voltages change relative to engine Keep a record of the measurement of the alignment.
speed. The record may be used to check the trend of the
alignment. The record may be used to analyze the
The generator set functional test consists of the trend of the alignment.
following steps:
The genset must be aligned when the genset is
1. Stop the generator. Connect the potential moved into a final position. The genset must be
transformer's high voltage winding to the aligned if the genset is moved into a different position.
generator terminals (T1) and (T2). Connect
the voltmeter to the low voltage winding. If two
i01228545
transformers are available, connect the high
voltage winding of the second transformer to the
generator terminals (T1) and (T3). Connect the
Generator Set Vibration -
secondary terminals that correspond to generator Inspect
terminal (T2) of both transformers together.
SMCS Code: 4450-040-VI
2. Disconnect wires “E+” and “E-” from the voltage
regulator. Disconnect the generator from the load. Check for vibration damage. Vibration may cause the
following problems:
3. Connect a 12 VDC automotive battery to wires
“E+” and “E-”. • loose fittings
4. Measure the AC voltage across the low voltage • loose bolts
terminals of the transformer that correspond to the
following generator terminals: “T1” and “T2”, “T2” • excessive noise
and “T3”, and “T3” and “T1”. Record the voltages.
• cracked insulation
i03100396 The following areas are susceptible to vibration
Generator Set Alignment - damage:
• Coupling for the generator set Note: Always use a board or cardboard when the
engine components are checked for leaks. Leaking
• Generator bearings fluid that is under pressure can cause serious
injury or possible death. This includes leaks that
• Stator output leads are the size of a pin hole. Refer to Operation and
Maintenance Manual, “General Hazard Information”
• Protective sleeving for more information.
Replace hoses that are cracked or soft. Replace 4. Remove the filler cap for the cooling system.
hoses that show signs of leakage. Replace hoses
that show signs of damage. Replace hose clamps 5. Drain the coolant from the cooling system to a
that are cracked or damaged. Tighten or replace level that is below the hose that is being replaced.
hose clamps which are loose. Drain the coolant into a suitable clean container.
The coolant can be reused.
Replace the Hoses and the Clamps 6. Remove the hose clamps.
Lubrication System
3. Disconnect the old hose. 3. Replace the old hose with a new hose.
4. Replace the old hose with a new hose. 4. Install hose clamps which have been inspected or
install new hose clamps. Refer to Specifications,
5. Install hose clamps which have been inspected or SENR3130, “Torque Specifications”, “Hose
install new hose clamps. Refer to Specifications, Clamps” for information about selecting and
SENR3130, “Torque Specifications”, “Hose installing the proper hose clamps.
Clamps” for information about selecting and
installing the proper hose clamps. 5. Start the engine. Inspect the air lines for leaks.
Check the condition of all of the gauges. If a gauge • The generator set is operating in a humid
is broken, repair the gauge or replace the gauge environment. Test every three months.
immediately.
• The generator set is not protected from the
Frequently monitor the gauges during normal elements in an enclosed area. Test every three
operation. months.
Record the data in a log. Compare the new data to • The generator set is installed in an enclosed area.
the data that was previously recorded. Comparing This area needs to be low in humidity and this area
the new data to the recorded data will help to needs to have steady temperatures. Test every
establish the trends of engine performance. A gauge twelve months (minimum).
reading that is abnormal may indicate a problem with
operation or a problem with the gauge. • The generator set has not been run under load
for three months. Test the generator set weekly.
Use space heaters around the generator set if the
i01951994
generator is exposed to a sea water environment or
Insulation - Test if the humidity is above 75 percent. Also use space
heaters if a test result was below 3 megohms.
SMCS Code: 4453-081; 4454-081; 4457-081;
4470-081 Space heaters must be used whenever the generator
set is not under load. Space heaters must also be
used whenever salt is present or whenever high
Recommended Periodic Insulation humidity is present. Using a space heater in this
Tests fashion is the only way to maintain insulation tester
readings above one megohm. Use space heaters
only when the generator is not running.
• The generator set is started for the first time. 3. Inspect the installation. Determine the equipment
that will be tested by the insulation tester.
• The generator set is removed from storage.
4. Discharge the capacitance of the windings.
SEBU7828-09 153
Maintenance Section
Insulation - Test
8. For units that are 600 volts or less, set the voltage
to 500 Volts. For units that are more than 600
volts, set the voltage to 1000 Volts.
a. Apply voltage.
d. Record temperature.
e. Record humidity.
f. Remove voltage.
g00633226
Illustration 96
SEBU7828-09 155
Maintenance Section
Jacket Water Heater - Check
SMCS Code: 1907-040; 7400-040; 7400-070 The need for an overhaul is generally indicated
by increased fuel consumption, increased oil
consumption, excessive engine blowby, and
reduced power. Arctic temperatures, extremely high
temperatures, corrosive environments, or extremely
dusty conditions contribute to premature wear and
the need for an overhaul.
The oil consumption rate (brake specific oil Note: Overhaul programs vary according to the
consumption) is measured in grams per kW/h (lb per engine application and according to the dealer that
bhp). The brake specific oil consumption (BSOC) performs the overhaul. Consult your Caterpillar
depends on the engine load. Consult your Caterpillar dealer for specific information about the available
dealer for assistance in determining the typical oil overhaul programs and about overhaul services for
consumption rate for your engine. extending the engine life.
When an engine's oil consumption has risen to three If an overhaul is performed without overhaul service
times the original oil consumption rate due to normal from your Caterpillar dealer, be aware of the following
wear, an engine overhaul should be scheduled. maintenance recommendations.
There may be a corresponding increase in blowby
and a slight increase in fuel consumption. Rebuild or Exchange
Overhaul Options Cylinder Head Assembly, Cylinder Packs, Oil
Pump, and Fuel Transfer Pump
Before Failure Overhaul
These components should be inspected according to
A planned overhaul before failure may be the best the instructions that are found in various Caterpillar
value for the following reasons: reusability publications. The Special Publication,
SEBF8029 lists the reusability publications that are
• Costly unplanned downtime can be avoided. needed for inspecting the engine parts.
• Many original parts can be reused according to the If the parts comply with the established inspection
standards for reusable parts. specifications that are expressed in the reusable
parts guideline, the parts should be reused.
• The engine's service life can be extended without
the risk of a major catastrophe due to engine Parts that are not within the established inspection
failure. specifications should be dealt with in one of the
following manners:
• The best cost/value relationship per hour of
extended life can be attained. • Salvaging
After Failure Overhaul • Repairing
If a major engine failure occurs and the engine • Replacing
must be removed, many options are available. An
overhaul should be performed if the engine block or Using out-of-spec parts can result in the following
the crankshaft needs to be repaired. problems:
• Thrust bearings
NOTICE
• Main bearings Do not use caustic cleaners to clean the core.
• Rod bearings Caustic cleaners can attack the internal metals of the
core and cause leakage.
• Valve rotators
• Crankshaft seals Note: Use this cleaning procedure to clean the oil
cooler core.
Caterpillar Inc. recommends the installation of new
parts at each overhaul period. 1. Remove the oil cooler core.
Inspect these parts while the engine is disassembled 2. Remove any debris from the oil cooler core. To
for an overhaul. remove debris from the oil cooler core, turn the oil
cooler core onto one end.
Inspect the crankshaft for any of the following
conditions: 3. Flush the oil cooler core internally with cleaner in
order to loosen foreign substances. This will also
• Deflection help to remove oil from the oil cooler core.
Inspect the following components for signs of wear or 4. Use steam to clean the oil cooler core. This
for signs of scuffing: removes any remaining residue from the cleaner.
Flush the fins of the oil cooler core. Remove any
• Camshaft bearings other trapped debris.
• Camshaft followers 5. Wash the oil cooler core with hot, soapy water.
Rinse the oil cooler core thoroughly with clean
Caterpillar Inc. recommends replacing the crankshaft water.
vibration damper.
6. Dry the oil cooler core with compressed air. Direct i01191656
the air in the reverse direction of the normal flow.
Power Factor - Check
7. Inspect the components in order to ensure
cleanliness. The oil cooler core should be SMCS Code: 4450-535-PWR
pressure tested. Repair the oil cooler core, if
necessary. Install the oil cooler core. The power factor of a system can be determined by
a power factor meter or by calculations. The power
For more information about cleaning the cores, factor can be calculated by dividing kW by kVA.
consult your Caterpillar dealer. Power factor is expressed as a decimal.
An S·O·S Coolant Analysis (Level 2) is a Pressurized air is the preferred method for removing
comprehensive coolant analysis which completely loose debris. Direct the air in the opposite direction
analyzes the coolant and the effects on the cooling of the fan's air flow. Hold the nozzle approximately
system. An S·O·S Coolant Analysis (Level 2) provides 6 mm (0.25 inch) away from the fins. Slowly move the
the following information: air nozzle in a direction that is parallel with the tubes.
This will remove debris that is between the tubes.
• Complete S·O·S Coolant Analysis (Level 1)
Pressurized water may also be used for cleaning.
• Visual inspection of properties The maximum water pressure for cleaning purposes
must be less than 275 kPa (40 psi). Use pressurized
• Identification of metal corrosion water in order to soften mud. Clean the core from
both sides.
• Identification of contaminants
Use a degreaser and steam for removal of oil and
• Identification of built up impurities (corrosion and grease. Clean both sides of the core. Wash the core
scale) with detergent and hot water. Thoroughly rinse the
core with clean water.
S·O·S Coolant Analysis (Level 2) provides a report of
the results of both the analysis and the maintenance After cleaning, start the engine and accelerate the
recommendations. engine to high idle rpm. This will help in the removal
of debris and drying of the core. Stop the engine.
For more information about coolant analysis, see Use a light bulb behind the core in order to inspect
your Caterpillar dealer. the core for cleanliness. Repeat the cleaning, if
necessary.
SEBU7828-09 159
Maintenance Section
Rotating Rectifier - Check
Inspect the fins for damage. Bent fins may be opened 2. Make an assembly for separate excitation. The
with a “comb”. Inspect these items for good condition: assembly can use a 12 volt battery or a variable
welds, mounting brackets, air lines, connections, DC power supply as a power source. Refer to
clamps, and seals. Make repairs, if necessary. Step 3 for an assembly that uses a 12 Volt battery.
Refer to Step 4 for an assembly that uses a
For more detailed information on cleaning and variable DC power supply.
inspection, refer to Special Publication, SEBD0518,
“Know Your Cooling System”.
i01880286
i01936391
A standby generator set may not need to be used Unless other instructions are provided, perform
very often. However, the generator set is usually maintenance and repairs under the following
needed for operation in an emergency situation. conditions:
Maintenance of the standby generator set is very
important for the following reasons: • The engine is stopped.
• The generator set must always be in excellent • The starting system is disabled.
operating condition.
• The generator does not pose an electrical shock
• The generator set must be ready to work under hazard.
load at any time.
• The generator is disconnected from the load.
Establishing a Preventive Maintenance Program will
provide these benefits: Operation
• Maximum availability of the standby generator set To ensure proper operation, the generator set must be
exercised regularly. For instructions on operating the
• Longer service life for the generator set generator set, see the Operation and Maintenance
Manual for the generator set control panel.
• Minimum of expensive repairs
162 SEBU7828-09
Maintenance Section
Starting Motor - Inspect
If the turbocharger fails during engine operation, 2. Turn the compressor wheel and the turbine wheel
damage to the turbocharger compressor wheel by hand. The assembly should turn freely. Inspect
and/or to the engine may occur. Damage to the the compressor wheel and the turbine wheel for
turbocharger compressor wheel can cause additional contact with the turbocharger housing. There
damage to the pistons, the valves, and the cylinder should not be any visible signs of contact between
head. the turbine wheel or compressor wheel and the
turbocharger housing. If there is any indication of
NOTICE contact between the rotating turbine wheel or the
Turbocharger bearing failures can cause large quan- compressor wheel and the turbocharger housing,
tities of oil to enter the air inlet and exhaust systems. the turbocharger must be reconditioned.
Loss of engine lubricant can result in serious engine
damage. 3. Check the compressor wheel for cleanliness.
If only the blade side of the wheel is dirty, dirt
Minor leakage of a turbocharger housing under ex- and/or moisture is passing through the air filtering
tended low idle operation should not cause problems system. If oil is found only on the back side of the
as long as a turbocharger bearing failure has not oc- wheel, there is a possibility of a failed turbocharger
curred. oil seal.
When a turbocharger bearing failure is accompanied The presence of oil may be the result of extended
by a significant engine performance loss (exhaust engine operation at low idle. The presence of oil
smoke or engine rpm up at no load), do not continue may also be the result of a restriction of the line for
engine operation until the turbocharger is repaired or the inlet air (plugged air filters), which causes the
replaced. turbocharger to slobber.
i03291802
NOTICE
Varistor - Inspect Accumulated grease and/or oil on an engine or deck is
a fire hazard. Remove this debris with steam cleaning
SMCS Code: 4466-040
or high pressure water.
The varistor must be visually inspected at regular
intervals. For generator sets with 1400 or with • Ensure that cooling lines are properly clamped.
1600 frames, discoloration of the varistor indicates Check for leaks. Check the condition of all pipes.
that replacement of the varistor is necessary. For
generator sets with 1800 frames, physical signs of • Inspect the water pump for coolant leaks.
failure indicate that replacement of the varistor is
necessary. Note: The water pump seal is lubricated by coolant
in the cooling system. It is normal for a small amount
of leakage to occur as the engine cools down and
i01491868
the parts contract.
Voltage and Frequency - Check Excessive coolant leakage may indicate the need
SMCS Code: 4450-535-EL to replace the water pump seal. For the removal of
water pump and the installation of water pump and/or
Check for the proper voltage setting and check for seals, refer to the Service Manual for the engine or
the proper frequency setting. Check for stability. consult your Caterpillar dealer.
For the correct voltage and frequency, refer to the • Inspect the lubrication system for leaks at the front
generator set's Serial Plate. crankshaft seal, the rear crankshaft seal, the oil
pan, the oil filters and the valve cover.
i01908686 • Inspect the fuel system for leaks. Look for loose
fuel line clamps.
Walk-Around Inspection
• Inspect the piping for the air inlet system and the
SMCS Code: 1000-040 elbows for cracks and for loose clamps.
Inspect the Engine for Leaks and • Inspect the alternator belt and the accessory drive
belts for cracks, breaks or other damage.
for Loose Connections
Belts for multiple groove pulleys must be replaced as
A walk-around inspection should only take a few matched sets. If only one belt is replaced, the belt will
minutes. When the time is taken to perform these carry more load than the belts that are not replaced.
checks, costly repairs and accidents can be avoided. The older belts are stretched. The additional load on
the new belt could cause the belt to break.
For maximum engine service life, make a thorough
inspection of the engine compartment before starting
the engine. Look for items such as oil leaks or coolant
• Drain the water and the sediment from fuel tanks
on a daily basis in order to ensure that only clean
leaks, loose bolts, worn belts, loose connections and fuel enters the fuel system.
trash buildup. Make repairs, as needed:
• Inspect the wiring and the wiring harnesses for
• The guards must be in the proper place. Repair loose connections and for worn wires or frayed
damaged guards or replace missing guards. wires.
• Wipe all caps and plugs before the engine is • Inspect the ground strap for a good connection and
serviced in order to reduce the chance of system for good condition.
contamination.
• Inspect the engine-to-frame ground strap for a
NOTICE good connection and for good condition.
For any type of leak (coolant, lube, or fuel) clean up the
fluid. If leaking is observed, find the source and correct • Disconnect any battery chargers that are not
the leak. If leaking is suspected, check the fluid levels protected against the current drain of the starting
more often than recommended until the leak is found motor. Check the condition and the electrolyte level
or fixed, or until the suspicion of a leak is proved to be of the batteries, unless the engine is equipped with
unwarranted. a maintenance free battery.
SEBU7828-09 165
Maintenance Section
Water Pump - Inspect
i03543200
Warranty Section
Warranty Information
i01237445
Emissions Warranty
Information
SMCS Code: 1000
• Specific gravity of .849 at 15 °C (60 °F) Continuous – This rating allows a constant load
or a load that varies for an unlimited number of
• Density of 850 kg/m3 (7.085 lb/US gal) hours per year. The normal load factor is up to 100
percent for an unlimited number of hours per year.
The engine ratings are gross output ratings. The following applications are suggested: base load,
utility, cogeneration, and parallel operation.
Gross Output Ratings – The total output capability
of the engine that is equipped with standard Prime – This rating allows a load that varies for an
accessories. unlimited number of hours per year. The normal load
factor is up to 80 percent for an unlimited number of
Standard accessories include the following hours per year. A 100 percent load is only allowed
components: for 5 percent of the operating cycle. The following
applications are suggested: industrial, pumping,
• Oil pumps construction, and cogeneration.
i01028392
• Part number
• Part name
• Quantity
If there is a question concerning the part number,
please provide your dealer with a complete
description of the needed item.
• Data Sheet, PEHJ0059, “Cat DEO (SAE 10W-30 • Special Publication, PELJ0176, “Cat ELC
and SAE 15W-40)” (North America - Canada, (Extended Life Coolant) 223-9116 Dilution Test Kit”
Mexico, and United States)
• Data Sheet, PEHP9554, “Cat DEAC (Diesel
• Data Sheet, PEHJ0021, “Cat DEO (SAE 10W-30 Engine Antifreeze/Coolant) (Concentrate)”
and SAE 15W-40)” (Worldwide - except North
America, Egypt, Saudi Arabia, and Brazil) • Special Publication, PEHP7057, “S·O·S Coolant
Analysis”
• Data Sheet, PEHJ0072, “Cat DEO (SAE 10W-30
and SAE 15W-40)” (Brazil) • Special Publication, SEBD0518, “Knowing Your
Cooling System”
• Data Sheet, PEHJ0091, “Cat DEO (SAE 10W-30
and SAE 15W-40)” (Egypt and Saudi Arabia) • Special Publication, SEBD0970, “Coolant and Your
Engine”
• Data Sheet, PEHP7062, “Cat DEO SYN (SAE
5W-40)” Miscellaneous
• Special Publication, SEBD0640, “Oil and Your • Service Manual, SENR9750, “3406C Generator
Engine” Sets”
• Special Publication, PEDP7036, “S·O·S Fluid • Special Instructions, REHS1596, “3406 and 3456
Analysis” Global Design Generator Sets”
• Data Sheet, PEHJ0088, “Cat Multipurpose Grease” • Troubleshooting, RENR7941, “Voltage Regulator”
(NLGI grade 2)
• Parts Manual, SEBP3898, “3406C Generator Set”
• Data Sheet, PEHP0002, “Cat Advanced 3Moly
Grease” (NLGI grade 2) • Parts Manual, SEBP3900, “3406C Generator Set”
• Data Sheet, NEHP6010, “Cat Ultra 5Moly Grease” • Special Publication, SEBF8029, “Index to
(NLGI grades 1 and 2) Guidelines for Reusable Parts and Salvage
Operations”
• Data Sheet, NEHP6015, “Cat High Speed Ball
Bearing Grease” (NLGI grade 2) • Special Publication, SEBU9067, “One Safe
Source”
172 SEBU7828-09
Reference Information Section
Reference Materials
i01176304
Maintenance Log
SMCS Code: 1000
Table 31
Engine Model Customer Identifier
Serial Number Arrangement Number
Service Quantity
Service Item Date Authorization
Hours Of Fuel
SEBU7828-09 175
Index Section
Index
A Cooling System Coolant Sample (Level 1) -
Obtain ................................................................ 124
After Starting Engine ............................................. 85 Cooling System Coolant Sample (Level 2) -
After Stopping Engine............................................ 89 Obtain ................................................................ 124
Aftercooler Core - Clean/Test ............................... 113 Cooling System Supplemental Coolant Additive
Air Shutoff.............................................................. 74 (SCA) - Test/Add................................................ 125
Alternator - Inspect ............................................... 113 Add the SCA, If Necessary .............................. 125
Annunciator Panel - Inspect ................................. 113 S·O·S Coolant Analysis.................................... 125
Record the Performance of the Engine............. 114 Test for SCA Concentration ............................. 125
Automatic Start/Stop - Inspect.............................. 115 Cooling System Water Temperature Regulator -
Replace.............................................................. 126
Crankshaft Vibration Damper - Inspect ............... 126
B Rubber Damper ............................................... 127
Visconic Damper.............................................. 127
Battery - Recycle .................................................. 116 Crushing Prevention and Cutting Prevention ........ 18
Battery - Replace.................................................. 116 Customer Assistance........................................... 169
Battery Charger - Check....................................... 116 Outside of the USA and of Canada.................. 169
Checking After Stopping ................................... 117 USA and Canada ............................................. 169
Checking Before Start-Up ................................. 116 Customer Service ................................................ 169
Battery Disconnect Switch (If Equipped) ............... 74
Battery Electrolyte Level - Check ......................... 117
Battery or Battery Cable - Disconnect .................. 118 D
Before Starting Engine .................................... 19, 81
Starting the Engines, Operating the Engines, and Declaration of Conformity ...................................... 29
Stopping the Engines that are Equipped with Decommissioning and Disposal .......................... 172
Control Panels.................................................. 81
Belts - Inspect/Adjust/Replace.............................. 118
Adjustment ........................................................ 118 E
Inspection.......................................................... 118
Replacement of Multiple Drive Belts ................. 119 Electrical Connections - Check............................ 127
Burn Prevention..................................................... 16 Electrical System ................................................... 20
Batteries............................................................. 16 Grounding Practices .......................................... 20
Coolant............................................................... 16 Electronic Modular Control Panel 3 (EMCP 3) (If
Oils..................................................................... 16 Equipped) ............................................................ 68
Annunciator Module ........................................... 71
Electronic Control Module (Generator Set)........ 69
C Electronic Modular Control Panel II (EMCP II) (If
Equipped) ............................................................ 44
Caterpillar Monitoring System (If Equipped).......... 38 Alarm Module..................................................... 50
Main Display Module.......................................... 39 Custom Alarm Module ....................................... 50
Modes of Operation ........................................... 40 Generator Set Control (GSC)............................. 46
Switches............................................................. 39 Electronic Modular Control Panel II+ (EMCP II+) (If
Circuit Breakers - Reset ....................................... 119 Equipped) ............................................................ 51
Cold Weather Operation........................................ 90 Alarm Module..................................................... 57
Cold Weather Starting ........................................... 83 Custom Alarm Module ....................................... 58
Starting With the Starting Aid Switch ................. 83 Generator Set Control + (GSC+) ....................... 53
Cooling System Coolant (DEAC) - Change.......... 119 Electronic Modular Control Panel II+ with Paralleling
Cooling Systems with Heavy Deposits or (EMCP II+P) (If Equipped)................................... 59
Plugging ......................................................... 120 Alarm Module..................................................... 67
Drain ................................................................. 119 Custom Alarm Module ....................................... 67
Fill .................................................................... 121 Generator Set Control + (GSC+) ....................... 61
Flush ................................................................ 120 Emergency Stopping ............................................. 88
Cooling System Coolant (ELC) - Change............ 121 Emergency Stop Button (If Equipped) ............... 88
Drain ................................................................ 121 Emissions Certification Film .................................. 30
Fill .................................................................... 122 Emissions Warranty Information.......................... 166
Flush ................................................................ 121 Engine - Clean..................................................... 127
Cooling System Coolant Extender (ELC) - Add... 122
Cooling System Coolant Level - Check ............... 123
176 SEBU7828-09
Index Section
Engine Air Cleaner Element (Dual Element) - Fuel System Primary Filter/Water Separator -
Clean/Replace ................................................... 128 Drain .................................................................. 138
Cleaning the Primary Air Cleaner Elements .... 129 Fuel System Secondary Filter - Replace ............. 138
Servicing the Air Cleaner Elements ................. 128 Fuel Tank Water and Sediment - Drain ............... 139
Engine Air Cleaner Service Indicator - Inspect (If Drain the Water and the Sediment................... 139
Equipped) .......................................................... 130 Fuel Storage Tanks .......................................... 140
Test the Service Indicator................................. 131 Fuel Tank ......................................................... 139
Engine Crankcase Breather - Clean.................... 131
Engine Identification .............................................. 26
Engine Mounts - Inspect...................................... 131 G
Engine Oil and Filter - Change ............................ 133
Drain the Engine Oil......................................... 133 Gauges and Indicators .......................................... 36
Fill the Engine Crankcase ................................ 134 General Hazard Information .................................. 13
Replace the Oil Filter ....................................... 133 Asbestos Information ......................................... 15
Engine Oil Level - Check ..................................... 132 Containing Fluid Spillage ................................... 14
Engine Oil Sample - Obtain ................................. 132 Dispose of Waste Properly ................................ 16
Obtain the Sample and the Analysis................ 132 Fluid Penetration................................................ 14
Engine Operation................................................... 86 Lines, Tubes, and Hoses ................................... 15
Engine Performance - Test .................................. 134 Pressurized Air and Water ................................. 14
Engine Protective Devices - Check ..................... 134 General Maintenance Information ....................... 103
Visual Inspection.............................................. 134 Generator - Dry.................................................... 140
Engine Rating Conditions .................................... 167 Controlled Current Method............................... 141
Engine Rating Definitions .................................... 167 Oven Method ................................................... 141
Load Management Peak Shaving Rating Self-Circulating Air Method .............................. 141
Guidelines ...................................................... 168 Generator - Inspect.............................................. 141
Engine Ratings .................................................... 167 Cleaning (Assembled Generators)................... 142
Engine Starting ................................................ 19, 81 Cleaning (Disassembled Generators).............. 142
Ether .................................................................. 20 Generator Bearing - Inspect/Replace (SR4
Engine Stopping .............................................. 20, 88 Generator) ......................................................... 142
Engine Valve Lash - Inspect/Adjust ..................... 134 Inspect ............................................................. 142
Engine Valve Rotators - Inspect .......................... 135 Replace............................................................ 143
Engine Warm-up.................................................... 86 Generator Bearing - Lubricate ............................. 143
Ether Starting Aid Cylinder - Replace (If Lubricating Process (If Applicable) .................. 143
Equipped) .......................................................... 135 Generator Bearing Temperature - Test/Record ... 146
Infrared Thermometers .................................... 146
Resistive Temperature Detectors (RTDs) ........ 146
F Generator Identification ......................................... 26
Control Panel Identification ................................ 26
Fan Drive Bearing - Lubricate.............................. 136 European Union ................................................. 26
Features and Controls ........................................... 38 Generator Isolating for Maintenance ..................... 21
Fire Prevention and Explosion Prevention ............ 16 Generator Lead - Check ...................................... 146
Fire Extinguisher ................................................ 17 Generator Lead Connections ................................ 30
Lines, Tubes and Hoses .................................... 17 5000/6000 6 Wire Connection Diagrams ........... 32
Foreword ................................................................. 5 5000/6100 12 Wire Connection Diagrams ......... 31
California Proposition 65 Warning ....................... 5 Grounding the Frame......................................... 30
Literature Information........................................... 4 Neutral Connections .......................................... 30
Maintenance ........................................................ 4 Single Units........................................................ 31
Maintenance Intervals.......................................... 4 Generator Load - Check ...................................... 147
Operation ............................................................. 4 Generator Operation.............................................. 92
Overhaul .............................................................. 4 Block Loading .................................................... 92
Safety................................................................... 4 Excitation Systems............................................. 93
Fuel and the Effect from Cold Weather ................. 90 Generator Options ............................................. 93
Fuel Conservation Practices.................................. 86 Loading of the Generator ................................... 92
Fuel Related Components in Cold Weather .......... 91 Low Idle Adjustment........................................... 93
Fuel Filters ......................................................... 91 Power Factor...................................................... 93
Fuel Tanks.......................................................... 91 Standby Generator Sets .................................... 93
Fuel System - Prime ............................................ 136 Generator Set - Test ............................................ 147
Fuel System Primary Filter (Water Separator) Generator Set Alignment - Check (Generator
Element - Replace ............................................. 137 Sets) .................................................................. 148
Replace the Element........................................ 137 Generator Set Intended for Stationary Use Only... 30
Generator Set Vibration - Inspect ........................ 148
SEBU7828-09 177
Index Section
R
M
Radiator - Clean .................................................. 158
Magnetic Pickups - Clean/Inspect ....................... 155 Reference Information Section ............................ 167
Maintenance Interval Schedule (Prime Power Reference Material .............................................. 171
Generator Sets) .................................................. 111 Additional Reference Material.......................... 172
Maintenance Interval Schedule (Standby Generator Coolants........................................................... 171
Sets) .................................................................. 109 Fuels ................................................................ 171
Maintenance Log ................................................. 174 Lubricants ........................................................ 171
Maintenance Recommendations ......................... 103 Miscellaneous .................................................. 171
Maintenance Records.......................................... 172 Reference Materials ............................................ 171
Maintenance Section ............................................. 99 Reference Numbers .............................................. 28
Manual Stop Procedure......................................... 88 Record for Reference......................................... 28
EMCP 3.............................................................. 89 Refill Capacities..................................................... 99
EMCP II, EMCP II+ and EMCP II+P .................. 88 Refill Capacities and Recommendations............... 99
Model View Illustrations......................................... 22 Cooling System................................................ 101
Model Views .......................................................... 22 Engine Oil .......................................................... 99
Mounting and Dismounting.................................... 18 Fuel .................................................................. 101
Rotating Rectifier - Check.................................... 159
Rotating Rectifier - Test ....................................... 159
O
Operation Section.................................................. 33 S
Ordering Replacement Parts ............................... 170
Overhaul Considerations ..................................... 155 Safety Messages ..................................................... 6
Oil Consumption as an Overhaul Indicator ...... 155 Safety Section ......................................................... 6
Overhaul Recommendation ............................. 156
Overspeed ............................................................. 74
178 SEBU7828-09
Index Section
Table of Contents..................................................... 3
Turbocharger - Inspect ........................................ 162
Cleaning and Inspecting .................................. 163
Removal and Installation.................................. 163
Delivery Date:
Product Information
Model:
Attachment Information:
Dealer Information
Name: Branch:
Address:
Sales:
Parts: