PRODUCT
Control Performance
Monitor (CPM) R601.2
SUMMARY:
Saving to the database fails when importing the loops in CPM Configurator. This article describes a
solution to this problem, if it is caused by incomplete ImportLoop job on a previous occasion.
QUESTION / PROBLEM:
Saving to the database fails when importing the loops in CPM Configurator. This is caused by an
incomplete execution of ImportLoop job on a previous occasion.
Feedback
ANSWER / SOLUTION:
Saving the loops to database fails from the CPM Configurator when the ImportLoop job is incomplete on a
previous attempt. To confirm if ImportLoop is causing the issue, the user can navigate
to C:\ProgramData\Honeywell\CPM folder, and look for a Previous job is not yet completed error in the
Configuration Service logs.
https://process.honeywell.com/us/en/secure/services-and-support/support-center/technical-support/technical-solutions/article-detail.ka_000171340 1/2
9/19/22, 8:47 AM Knowledge Article Detail
4. Against the Honeywell.CPM.LoopImportingStatus key, set the value of the "Completed" to "true" from
"false".
5. Once done, close the the Intuition page .Open the CPM Configurator with 'Run as Administrator', and
save the loops to the database.
FAQs
RELATED BUSINESSES Need Help
SUBSCRIBE
Thermal Solutions
Performix
Feedback
Sparta Systems
Copyright © 2022 Honeywell International Terms & Privacy Do Not Sell My Personal Global
Cookies
Inc. Conditions Statement Information Unsubscribe
https://process.honeywell.com/us/en/secure/services-and-support/support-center/technical-support/technical-solutions/article-detail.ka_000171340 2/2