You are on page 1of 2

SOUND LEVEL TEST QCDD FORM

Pin No. 25180010 Date 29-8-2022


Location BLDG 68 , 3505, STREET 874 ZONE 25 Application No. N/2022/0000170
Project Name AL MANSOURA SUITES
Owner SHEIKH MANSOUR BIN JABR JASSIM AL-THANI

QCD Approved Drawing Ref. No.


Date Test Status √ Passed

Alarm
Ambient
Mode Voice Audibility/Clearness
Sound Remark
Location Sound (Speakers)
Level
Level
Floor/ Exact Location dB dB Pass dB Pass

55-60 √
BASEMENT 4 86 dB
dB

55-60 √
BASEMENT 3 86 dB
dB
BASEMENT
55-60
BASEMENT 2 dB 86 dB √
55-60 √
BASEMENT 1 dB 86 dB
55-60 √
GROUND dB
LIFT LOBBY 85 dB
FLOOR

VIP, BATH, SAUNA 55-60 √


Mezzanine Floor ROOM, FOOT dB 85 dB
MASSAGE
55-60 √
FIRST FLOOR LIFT LOBBY dB 87 dB

55-60 √
SECOUND dB
LIFT LOBBY 86 dB
FLOOR
55-60 √
THIRED dB
LIFT LOBBY 86 dB
FLOOR
55-60 √
FOURTH dB
LIFT LOBBY 87 dB
FLOOR
55-60 √
FIFTH FLOOR LIFT LOBBY dB 87 dB

55-60 √
SIXTH FLOOR LIFT LOBBY dB 87 dB

55-60 √
SEVENTH dB
LIFT LOBBY 87 dB
FLOOR

Page 1 of 2
SOUND LEVEL TEST QCDD FORM

Please provide additional information if necessary.

Notes: Public Mode - Sound Level is at least 15 dB above the average ambient sound

level.Private Mode - Sound Level is at least 10 dB above the average ambient sound

level.

Sleeping Area - Sound Level is at least 15 dB above the average ambient sound level or a sound
level ofat least 75 dB.

Reference - Latest NFPA 72.

CERTIFICATION
The system as specified above has been installed and tested, in accordance with latest edition of NFPA, QCDD FSS and QCDD
approved drawings

Contractor (QCDD Certificate No. / ID No. / Mobile No.)


(Signature over Printed Name with Stamp)

CERTIFICATION
The undersigned accepted the testing report for the system as specified herein.

Consultant (UPDA No. / ID No. / Mobile No.)


(Signature over Printed Name with Stamp)

Page 2 of 2

You might also like