SMOKE MANAGEMENT TEST QCDD FORM

Pin No. Date 14-Sep-22


Location Doha Qatar Application Number
Project Name AL MANSOUR SUITES
Owner

QCDD Approved Drawing Ref. No.


Test Status Passed

Fan Details Smoke Supply Smoke Extraction Ducted Jet Fan


SOLER AND SOLER AND
Make
PALAU PALAU
 Applicable  Applicable

Type FRESH AIR FAN EXHAUST FAN  Not Applicable  Not Applicable
QCDD Product  Air Balancing Report  Performance Report
Cert. Nos. Attached Attached

BASEMENT 1 Smoke Supply Fan Test Sheet


Low Speed Flow High Speed Flow
Unit Power Freq. Current
No.
Area Served Serial No. Design Actual % Of Design Actual % of
KW Hz Amps (L/s) (L/s) Design (L/s) (L/s) Design
CAR PARKING
1 AREA, 05VD8943 6.0 50 13.7 3300 3591 109% 5500 5801 105%
BASEMENT 01
2
3
Total for B-1 3300 3591 109% 5500 5801 105%

BASEMENT 2 Smoke Supply Fan Test Sheet


Low Speed Flow High Speed Flow
Unit Power Freq. Current
No.
Area Served Serial No. Design Actual % of Design Actual % of
KW HZ Amps (L/s) (L/s) Design (L/s) (L/s) Design
CAR PARKING
1 AREA, 00VF7554 6.0 50 13.7 4800 5168 108% 8000 8500 106%
BASEMENT 02
2
3
Total for B-2 4800 5168 108% 8000 8500 106%

Page 1 of 4
SMOKE MANAGEMENT TEST QCDD FORM

BASEMENT 3 Smoke Supply Fan Test Sheet


Low Speed Flow High Speed Flow
Unit Power Freq. Current
No.
Area Served Serial No. Design Actual % of Design Actual % of
KW HZ Amps (L/s) (L/s) Design (L/s) (L/s) Design
CAR PARKING
1 AREA, 00VF7553 6.0 50 13.7 4800 5032 105% 8000 8704 109%
BASEMENT 03
2
3
Total for B-3 4800 5032 105% 8000 8704 109%

BASEMENT 4 Smoke Supply Fan Test Sheet


Low Speed Flow High Speed Flow
Unit Power Freq. Current
No.
Area Served Serial No. Design Actual % of Design Actual % of
KW HZ Amps (L/s) (L/s) Design (L/s) (L/s) Design
CAR PARKING
1 AREA, 00VF7551 6.0 50 13.7 4800 4906 102% 8000 8075 101%
BASEMENT 04
2
3
Total for B-4 4800 4906 102% 8000 8075 101%

BASEMENT 1 Smoke Extraction Fan Test Sheet


Low Speed Flow High Speed Flow
Unit Power Freq. Current
No.
Area Served Serial No. Design Actual % of Design Actual % of
KW HZ Amps (L/s) (L/s) Design (L/s) (L/s) Design
CAR PARKING
1 AREA, N/A 6.0 50 13.7 3300 3120 95% 5500 5359 97%
BASEMENT 01
2
3
Total for B-1 3300 3120 95% 5500 5359 97%

BASEMENT 2 Smoke Extraction Fan Test Sheet


Low Speed Flow High Speed Flow
Unit Power Freq. Current
No.
Area Served Serial No. Design Actual % of Design Actual % of
KW HZ Amps (L/s) (L/s) Design (L/s) (L/s) Design
CAR PARKING
1 AREA, 00VF7552 6.0 50 13.7 4800 5141 107% 8000 8258 103%
BASEMENT 02
2
3
Total for B-2 4800 5141 107% 8000 8258 103%

Page 2 of 4
SMOKE MANAGEMENT TEST QCDD FORM

BASEMENT 3 Smoke Extraction Fan Test Sheet


Low Speed Flow High Speed Flow
Unit Power Freq. Current
No.
Area Served Serial No. Design Actual % Of Design Actual % of
KW HZ Amps (L/s) (L/s) Design (L/s) (L/s) Design
CAR PARKING
1 AREA, 00VF7553 6.0 50 13.7 4800 4532 94% 8000 7398 92%
BASEMENT 03
2
3
Total for B-3 4800 4532 94% 8000 7398 92%

BASEMENT 4 Smoke Extraction Fan Test Sheet


Low Speed Flow High Speed Flow
Unit Power Freq. Current
Area Served Serial No. Design Actual % of Design Actual % of
No.
KW HZ Amps (L/s) (L/s) Design (L/s) (L/s) Design
CAR PARKING
1 AREA, N/A 6.0 50 13.7 4800 5015 104% 8000 8585 107%
BASEMENT 04
2
3
Total for B-4 4800 5015 104% 8000 8585 107%

Total Smoke Supply Fan (High Speed) Total Smoke Extraction Fan (High Speed) % Variance
Area Design Actual Design Actual between Supply
% of Design % Of Design & Extraction
(L/s) (L/s) (L/s) (L/s)
B-1 5500 5801 105% 5500 5359 97%
B-2 8000 8500 106% 8000 8258 103%
B-3 8000 8704 109% 8000 7398 92%
B-4 8000 8075 101% 8000 8585 107%

Page 3 of 4
SMOKE MANAGEMENT TEST QCDD FORM

Total Smoke Supply Fan (Low Speed) Total Smoke Extraction Fan (Low Speed) % Variance
Area Design Actual Design Actual between Supply
% of Design % of Design & Extraction
(L/s) (L/s) (L/s) (L/s)
B-1 3300 3591 109% 3300 3120 95%
B-2 4800 5168 108% 4800 5141 107%
B-3 4800 5032 105% 4800 4532 94%
B-4 4800 4906 102% 4800 5015 104%

Test Equipment
Instrument/s Used Anemometer Calibration Date 02-Aug-2022
Calibration
Serial Nos. LCA501542006 Acit-MAK-IH-2022-12581
Certificate Nos.

CERTIFICATION
The system as specified above has been installed and tested, in accordance with latest edition of NFPA, QCDD FSS and QCDD
approved drawings

________________________________ _______________________________________________
Contractor (ID No. / Mobile No.)
(Signature over Printed Name with Stamp)

CERTIFICATION
The undersigned accepted the testing report for the system as specified herein.

________________________________ _______________________________________________
Consultant (UPDA No. / ID No. / Mobile No.)
(Signature over Printed Name with Stamp)

Page 4 of 4