Type FRESH AIR FAN EXHAUST FAN Not Applicable Not Applicable
QCDD Product Air Balancing Report Performance Report
Cert. Nos. Attached Attached
Page 1 of 4
SMOKE MANAGEMENT TEST QCDD FORM
Page 2 of 4
SMOKE MANAGEMENT TEST QCDD FORM
Total Smoke Supply Fan (High Speed) Total Smoke Extraction Fan (High Speed) % Variance
Area Design Actual Design Actual between Supply
% of Design % Of Design & Extraction
(L/s) (L/s) (L/s) (L/s)
B-1 5500 5801 105% 5500 5359 97%
B-2 8000 8500 106% 8000 8258 103%
B-3 8000 8704 109% 8000 7398 92%
B-4 8000 8075 101% 8000 8585 107%
Page 3 of 4
SMOKE MANAGEMENT TEST QCDD FORM
Total Smoke Supply Fan (Low Speed) Total Smoke Extraction Fan (Low Speed) % Variance
Area Design Actual Design Actual between Supply
% of Design % of Design & Extraction
(L/s) (L/s) (L/s) (L/s)
B-1 3300 3591 109% 3300 3120 95%
B-2 4800 5168 108% 4800 5141 107%
B-3 4800 5032 105% 4800 4532 94%
B-4 4800 4906 102% 4800 5015 104%
Test Equipment
Instrument/s Used Anemometer Calibration Date 02-Aug-2022
Calibration
Serial Nos. LCA501542006 Acit-MAK-IH-2022-12581
Certificate Nos.
CERTIFICATION
The system as specified above has been installed and tested, in accordance with latest edition of NFPA, QCDD FSS and QCDD
approved drawings
________________________________ _______________________________________________
Contractor (ID No. / Mobile No.)
(Signature over Printed Name with Stamp)
CERTIFICATION
The undersigned accepted the testing report for the system as specified herein.
________________________________ _______________________________________________
Consultant (UPDA No. / ID No. / Mobile No.)
(Signature over Printed Name with Stamp)
Page 4 of 4