This section includes standard package pre-engineered steel building frame, metal wall and sloped roof
system. Due to extensive use of profiled steel wall and roof on this building type, this section does not
include options for other materials, but can be edited to include them. Specifications for exterior doors or
windows are included. This section does not include foundations, floor slab, or interior finishing.
This section includes performance, proprietary, and descriptive type specifications. Edit to avoid
conflicting requirements.
*************************************************************************************
PART 1 GENERAL
1.1 SUMMARY
B. Related Sections:
1. Section 03 30 00 – Cast-in-Place Concrete: Execution requirements for
placement of [anchor bolts] [base plates] [________] specified in this section in
concrete.
2. Section 05 50 00 – Metal Fabrications.
3. Section 07 90 00 – Joint Protection.
4. Section 08 11 13 – Hollow Metal Doors and Frames.
5. Section 08 33 23 – Overhead Coiling Doors.
6. Section 08 36 13 – Sectional Doors.
7. Section 08 41 13 – Aluminum-Framed Entrances and Storefronts.
8. Section 08 51 13 – Aluminum Windows.
9. Section 08 62 00 – Unit Skylights.
10. Section 08 71 00 – Door Hardware.
11. Section 08 80 00 – Glazing.
12. Section 09 90 00 – Painting and Coating: Finish painting [of exterior primed steel
surfaces,] [inside surface of liner sheet,] [and] [________].
13. Section [______-_____________]: Mechanical rough-in utilities.
14. Section [______-_____________]: Electrical rough-in utilities.
15. Section [______-_____________]: Fire Protection Systems.
1.2 REFERENCES
B. ASTM International:
1. ASTM A36/A36M – Standard Specification for Carbon Structural Steel.
2. ASTM A123/A123M – Standard Specification for Zinc (Hot-Dip Galvanized)
Coatings on Iron and Steel Products.
3. ASTM A153/A153M – Standard Specification for Zinc Coating (Hot-Dip) on
Iron and Steel Hardware.
4. ASTM A307 – Standard Specification for Carbon Steel Bolts and Studs, 60 000
PSI Tensile Strength.
5. ASTM A325 – Standard Specification for Structural Bolts, Steel, Heat Treated,
120/105 ksi Minimum Tensile Strength.
6. ASTM A325M – Standard Specification for Structural Bolts, Steel, Heat Treated,
830MPa Minimum Tensile Strength (Metric).
7. ASTM A490 – Standard Specification for Heat-Treated Steel Structural Bolts,
150 ksi Minimum Tensile Strength.
8. ASTM A490M – Standard Specification for High-Strength Steel Bolts, Classes
10.9 and 10.9.3, for Structural Steel Joints (Metric).
9. ASTM A500 – Standard Specification for Cold-Formed Welded and Seamless
Carbon Steel Structural Tubing in Rounds and Shapes.
10. ASTM A501 – Standard Specification for Hot-Formed Welded and Seamless
Carbon Steel Structural Tubing.
11. ASTM A529/A529M – Standard Specification for High-Strength Carbon-
Manganese Steel of Structural Quality.
12. ASTM A572/A572M – Standard Specification for High-Strength Low-Alloy
Columbium-Vanadium Structural Steel.
13. ASTM A653/A653M – Standard Specification for Steel Sheet, Zinc-Coated
(Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process.
14. ASTM A792/A792M – Standard Specification for Steel Sheet, 55% Aluminum-
Zinc Alloy-Coated by the Hot-Dip Process.
15. ASTM C665 – Standard Specification for Mineral-Fiber Blanket Thermal
Insulation for Light Frame Construction and Manufactured Housing.
16. ASTM C991 – Standard Specification for Flexible Glass Fiber Insulation for Pre-
Engineered Metal Buildings.
17. ASTM C1107 – Standard Specification for Packaged Dry, Hydraulic-Cement
Grout (Nonshrink).
18. ASTM C1371 – Standard Test Method for Determination of Emittance of
Materials Near Room Temperature Using Portable Emissometers.
19. ASTM C1549 – Standard Test Method for Determination of Solar Reflectance
Near Ambient Temperature Using a Portable Solar Reflectometer.
20. ASTM E84 – Standard Test Method for Surface Burning Characteristics of
Building Materials.
G. National Fire Protection Association: NFPA 255 – Standard Method of Test of Surface
Burning Characteristics of Building Materials.
*************************************************************************************
Use this article carefully; restrict statements to describe components used to assemble system. Do not
repeat statements made in SUMMARY Article, “Section includes” paragraph.
*************************************************************************************
*************************************************************************************
Include the following paragraph when Drawings do not indicate bay spacing.
*************************************************************************************
C. Primary Framing: Rigid frame of rafter beams and columns, [canopy beams,]
[intermediate columns,] [braced end frames,] [end wall columns,]
[____________________,] and wind bracing.
D. Secondary Framing: [Purlins,] [girts,] [eave struts,] [flange bracing,] [sill supports,]
[____________________,] clips, and other items detailed.
E. Lateral Bracing: Horizontal loads not resisted by main frame action shall be resisted by
[cable] [rod] and/or [diaphragm] [portal frames] [fixed base columns] [ ] in the sidewall.
[Diaphragm] and/or [cable] [rod] [portal frame] [fixed base columns] [ ] in the endwall.
[Cable] [rod] and/or [diaphragm] [ ] in the roof.
F. Wall System: Preformed metal panels of [horizontal] [vertical] [________] profile, [with
sub-girt framing/anchorage assembly,] [insulation,] [liner sheets,] and accessory
components.
G. Roof System: Preformed metal panels of [upslope] [parallel to eave] [________] profile,
[with sub-girt framing/anchorage assembly,] [insulation,] [liner sheets,] and accessory
components.
*************************************************************************************
Include the following paragraph when Drawings do not indicate roof slope.
*************************************************************************************
H. Roof Slope: [1/8] [1] [2] [4] inch[es] in 12 inches ([1/100] [1/12] [1/6] [1/3]).
*************************************************************************************
Use this article carefully; restrict statements to identify system design requirements only.
*************************************************************************************
E. Design roof framing and roofing to withstand Code prescribed forces [and forces defined
by [FM Global] [ ] underwriters].
G. Maximum Allowable Deflection: [1/90] [1/180] of span with imposed loads for exterior
wall and roof system.
H. Maximum Allowable Deflection: [1/180] [1/240] of span with imposed loads for
horizontal member framing. Decrease deflection as required to eliminate ponding of roof
framing and roofing. Camber roof members as required.
I. Provide drainage to exterior for water entering or condensation occurring within wall or
roof system.
J. Permit movement of components without buckling, failure of joint seals, undue stress on
fasteners or other detrimental effects, when subject to temperature range of
[________] degrees F ([________] degrees C).
K. Size and fabricate wall and roof systems free of distortion or defects detrimental to
appearance or performance.
L. [Design exterior gutters and downspouts for a rain fall intensity based on a 5-year
recurrence interval for a five-minute duration. Design interior gutters, valleys and
downspouts for a rainfall intensity based on a 25-year recurrence interval based on a
5-minute duration].
*************************************************************************************
Use this article carefully; restrict statements to identify system performance requirements or function
criteria only.
*************************************************************************************
C. Provide components of each type from one manufacturer compatible with adjacent
materials.
1.6 SUBMITTALS
A. Refer to the Submittal Schedule at the end of Part 3 for a list of submittal requirements
for this Section.
A. Perform Work in accordance with [AISC 360] [MBMA Low Rise Building Systems
Manual.]
*************************************************************************************
IBC requires surface burning to be tested in accordance with ASTM E84.
For IBC, surface burning rating is not required for insulation facings installed in Construction Type III,
Type IV, and Type V. Facing must be in substantial contact with ceiling, wall, or floor finish.
*************************************************************************************
*************************************************************************************
Edit sustainable design requirements to suit content of this section and Project sustainable design
requirements specified in Section 01 81 13 – Sustainable Design Requirements.
*************************************************************************************
*************************************************************************************
*************************************************************************************
List materials specified in this section required to have recycled content in the following paragraph when
recycled percentage is determined by Contractor.
*************************************************************************************
a. [____________________.]
2. Regional Materials: Furnish materials extracted, processed, and manufactured
within 500 miles (800 km) of Project site [including:] [.]
*************************************************************************************
List materials specified in this section required to be regional materials.
*************************************************************************************
a. [____________________.]
*************************************************************************************
Include the following paragraph only when cost of acquiring specified standards is justified.
*************************************************************************************
1.8 QUALIFICATIONS
C. Design structural components, develop shop drawings, and perform shop and site work
under direct supervision of professional engineer experienced in design of this Work and
licensed [at Project location.] [in State of [________].]
1.10 WARRANTY
*************************************************************************************
This article extends warranty period beyond one year. Extended warranties increase construction costs
and Owner enforcement responsibilities. Specify warranties with caution.
*************************************************************************************
B. Furnish [5]-year warranty to include coverage for exterior pre-finished surfaces color
coat against chipping, cracking or crazing, blistering, peeling, chalking, or fading.
Include coverage for weather tightness of building enclosure elements after installation.
PART 2 PRODUCTS
*************************************************************************************
In this article, list manufacturers acceptable for this Project.
*************************************************************************************
A. Manufacturers:
1. Behlen Building Systems.
2. Butler Manufacturing Co.
3. Ceco Building Systems.
4. Chief Buildings/Division of Chief Industries, Inc.
5. Garco Building Systems.
6. Kirby Building Systems, Inc.
7. Nucor Building Systems.
8. Star Building Systems.
9. Varco-Pruden Buildings.
10. [____________________.]
11. Substitutions: [Section 01 60 00 – Products Requirements.] [Not Permitted.]
C. Manufacturers, Insulation:
1. Johns Manville.
2. Owens Corning.
3. [____________________.]
E. Bolts, Nuts, and Washers: [ASTM A325,] [ASTM A325M,] [ASTM A490,] [ASTM
A490M,] [galvanized].
F. Welding Materials: AWS D1.1; type required for materials being welded.
*************************************************************************************
Sustainable design requirements normally specify maximum VOC content for products that affect indoor
air quality. Delete option to extend requirement to exterior applications.
*************************************************************************************
*************************************************************************************
Non-shrink grout in the following paragraph is primarily for setting base plates.
*************************************************************************************
*************************************************************************************
The following materials listing is oriented to site assembled wall and roof component assemblies. When
shop pre-fabricated wall and roof components are desired, edit the following for Project conditions.
*************************************************************************************
C. Insulation: [Semi-rigid] [Batt] [Roll] glass fiber type, [unfaced,] [faced with reinforced
[foil] [white vinyl]], friction fit, [________] inches ([________] mm) thick.
*************************************************************************************
In the following paragraph, when using ASTM reference standards, coordinate selected type and class
with descriptive text. Subparagraphs 1 and 2 below are examples; edit to reflect project conditions.
*************************************************************************************
D. Insulation: [ASTM C665 [Type I] [Type II Class [A] [B] [C]] [Type III Class [A] [B]
[C]]] [ASTM C991 Type [I] [II]]; [________] inches ([________] mm) thick.
1. [Roof: One layer for installation over top of steel roof purlins, minimum R-11,
and a second layer of full-purlin-depth insulation between roof purlins, with
thermal blocks at purlins.]
2. [Walls: One layer of full-purlin-depth insulation with thermal break tape at
purlins.]
E. Thermal Blocks: polystyrene, 1 inch thickness, 4 inches wide, 24 inches long; minimum
R3.5.
F. Thermal Break Tape: 3 inches wide by 3/16-inch thick by continuous roll length, with
adhesive backing.
G. [Insulation, Edge of Slab Locations: ASTM C578, Type X, 1.3 pcf density, extruded
cellular polystyrene; mean thermal resistance "R" per inch of 5.0; water absorption by
volume in accordance with ASTM D2842 0.3 percent maximum.]
H. Insulation Hangers: preformed and punched, 1 inch wide, 32 inches long, 20 gauge
thickness. Formed to hang from purlins and to hold insulation in permanent position.
*************************************************************************************
In the following paragraph, describes a proprietary insulation system that provides insulation full depth of
building purlin (girt) in roof and walls with a continuous fabric vapor retarder on inside of framing
members. This system provides the advantage of full thickness insulation rather than draping insulation
blankets over the girts, which reduces the insulation thickness at each framing member.
*************************************************************************************
A. [Liner Fabric, Roof and Wall: woven reinforced high-density polyethylene yarns coated
on both sides with a continuous polyethylene film; flame spread and smoke developed 25
H. Trim, Closure Pieces, Caps, Flashings, [Rain Water Diverter,] [Fascias] [Infills], [and]
[________]: Same material, thickness and finish as exterior sheets; brake formed to
required profiles. [Flexible Closure Strips: Closed cell, expanded cellular rubber, self-
extinguishing, cut or pre-molded to match corrugation configuration of wall [and roofing]
sheets].
*************************************************************************************
In this article, list manufacturers acceptable for this Project.
*************************************************************************************
A. Manufacturers:
1. [____________________], Model [________].
2. [____________________], Model [________].
3. [____________________], Model [________].
B. Doors and Frames: Specified in Section 08 11 13 – Hollow Metal Doors and Frames.
*************************************************************************************
In this article, list manufacturers acceptable for this Project.
*************************************************************************************
A. Manufacturers:
1. [____________________], Model [________].
2. [____________________], Model [________].
3. [____________________], Model [________].
C. Overhead Door Frame: Formed steel sections braced to building frame specified in
Section 05 50 00 – Metal Fabrications.
*************************************************************************************
In this article, list manufacturers acceptable for this Project.
*************************************************************************************
A. Manufacturers:
1. [____________________], Model [________].
2. [____________________], Model [________].
3. [____________________], Model [________].
*************************************************************************************
In this article, list manufacturers acceptable for this Project.
*************************************************************************************
A. Manufacturers:
1. [____________________], Model [________].
2. [____________________], Model [________].
3. [____________________], Model [________].
*************************************************************************************
Most skylight domes are manufactured of acrylic plastic. Polycarbonate is available at extra cost.
******************************************
*************************************************************************************
In the following paragraph, consider double insulated dome where condensation on dome inner surface
may be a problem; this should minimize problem of having to discharge collected condensate.
*************************************************************************************
*************************************************************************************
I. Unit Frame: Extruded aluminum [thermally broken,] integral curb frame [and
counterflashing,] with integral condensation drainage gutter.
*************************************************************************************
Include the following paragraph only when skylights are to be provided with integral support curb.
*************************************************************************************
A. Fabricate members in accordance with AISC Specification for plate, bar, tube, or rolled
structural shapes.
B. Anchor Bolts: Formed with [bent] [straight] shank, assembled with template for casting
into concrete.
C. Provide framing for [door] [window] [louver] [skylight,] [ventilator,] [and] [________]
openings.
************************************************************************************
The following text describes installation of full thickness insulation and fabric vapor retarder. Delete or
edit to agree with project design.
*************************************************************************************
*************************************************************************************
Select SRI 79 for low sloped roofs, less than or equal to 2:12 pitch. Select SRI 29 for steep sloped roofs,
greater than 2:12 pitch.
*************************************************************************************
F. Girts/Purlins: Rolled formed structural shape to receive siding, roofing [and liner] sheet.
G. Internal and External Corners: Same material thickness and finish as adjacent material,
profile [brake formed] [shop cut and factory mitered] to required angles. Back brace
mitered internal corners with [________]-inch ([________]-mm)-thick sheet.
*************************************************************************************
Verify locations of expansion joints are indicated on Drawings.
*************************************************************************************
H. Expansion Joints: Same material and finish as adjacent material [where exposed],
[________]-inch ([________]-mm) thick, [manufacturer's standard brake formed] [infill]
[________] type, of profile [to suit system.] [formed as detailed.]
I. Flashings, Closure Pieces, [Fascia], [Infills], [Caps], and [________]: Same material and
finish as adjacent material, profile [to suit system.] [formed as detailed.]
*************************************************************************************
Describe ventilator type to be used: Continuous ridge type, intermittent ridge type, end wall type,
dampered, exhaust grilles, gravity vent, screens, operators.
*************************************************************************************
L. Wall Louvers: [________] type [Z] [Y] [________] blade design, [same finish as
adjacent material] [________], with steel mesh [bird] [insect] screen and frame, [blank
sheet metal] [________] at unused portions.
B. Form gutters including end pieces and outlet tubes, and downspouts [and scuppers] of
[________] profile and size [indicated] to collect and remove water. Fabricate with
connection pieces.
C. Form sections in maximum possible lengths. Provide expansion joints with cover plates
[or as shown on Drawings]. Hem exposed edges. [Allow for expansion at joints.]
D. Fabricate support straps of same material and finish as roofing metal, color as selected.
*************************************************************************************
ASTM A123/A123M includes specific zinc coating thickness based on type of material and steel
thickness of component. An example listing of the minimum and maximum material thicknesses is
indicated below. Other material thicknesses are listed in the standard. Specific coating thicknesses can be
specified, if necessary.
*************************************************************************************
A. Framing Members: Clean, prepare, and [shop prime.] [prime to SSPC Manual
requirements.] [galvanize to ASTM A123/A123M; [minimum [1.2] [2.0] ounces per
square foot ([355] [600] g/sq m) coating thickness]; galvanize after fabrication.] [Do not
prime surfaces to be field welded.]
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify foundation, floor slab, mechanical and electrical utilities, and placed anchors are
in correct position, and installed in accordance with Section 03 30 00 – Cast-in-Place
Concrete.
B. Provide for erection and wind loads. Provide temporary bracing to maintain structure
plumb and in alignment until completion of erection and installation of permanent
bracing. [Locate braced bays as indicated on Drawings.]
C. Set column base plates with non-shrink grout to achieve full plate bearing.
E. After erection, prime welds, abrasions, and surfaces not [shop primed.] [galvanized.]
A. Exercise care when cutting prefinished material to ensure cuttings do not remain on finish
surface.
C. Locate end laps over supports. End laps minimum [2] [________] inches ([50]
[________] mm). Place side laps over bearing.
A. Rigidly support and secure components. Join lengths with formed seams sealed
watertight. Flash and seal gutters to downspouts. [Provide expansion joints with cover
plates].
B. Apply bituminous paint on aluminum surfaces of units in contact with dissimilar metals.
*************************************************************************************
When accessories are referenced to another section, coordinate related section; delete applicable
statements below.
A. Install [door frame,] [door,] [overhead door,] [window and glass,] [skylight,] [louvers,]
[and] [________].
B. Seal wall and roof accessories watertight [and weather tight] with sealant [in accordance
with Section 07 90 00 – Joint Protection].
A. Framing Members: [1/4] inch ([6] mm) from level; [1/8] inch ([3] mm) from plumb.
*************************************************************************************
Only request submittals needed to verify compliance with Project requirements.
Do not include submittals that are listed in Division 01 unless there is additional specific information
required for materials or equipment in this Section.
Do not request submittals if Drawings and Specifications sufficiently describe required products of this
Section or if proprietary specifying techniques are used. The review of submittals increases the possibility
of unintended variations to Drawings and Specifications, thereby increasing CH2M HILL’s liability.
Include submission of physical samples for selection of finish, color, texture, and other properties.
Edit material certifications list to suit products specified in this section and Project sustainable design
requirements. Specific certificate submittal and supporting data requirements are specified in Section
01 81 13 – Sustainable Design Requirements.
Edit list of material cost data to suit products specified in this section and Project sustainable design
requirements. Specific cost data requirements are specified in Section 01 81 13 – Sustainable Design
Requirements.
*************************************************************************************
WITH BID