You are on page 1of 18

ENDMENT 05, AUGUST 4, 2021CD3 AUGUST

14, 2020

SECTION 133123

ETFE SINGLE FILM SYSTEM

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
other Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes an ETFE single film roof structure system and its supporting secondary steel
structure.

A.B. The Works included in this section are a delegated-design system which requires a complete system
designed and engineered to meet the requirements as indicated in this Specification and its related
documents. Coordination with components of the exterior enclosure system is required.

B.C. The ETFE SYSTEM contractor (hereafter referred to as “Subcontractor”) shall be responsible for designing
all the works in accordance with the Specification and the intent of the Architect’s drawings including the
detailing, fabrication, supply, and installation of the work specified herein, some or all of which may be
subcontracted by Subcontractor to others meeting the qualification requirements of Division 1. The intent
of this specification is to establish in the first instance an undivided, single-source responsibility of the
Subcontractor for all of the foregoing functions. The Subcontractor will also be responsible for all structural
analytical work that is necessary to justify his design, and will be required to demonstrate that this has been
carried out. It is expected that the Subcontractor will employ a properly qualified specialist Engineer to
carry out this work. The Subcontractor will be required to demonstrate the competence of those carrying
out the work.

C.D. Subcontractor’s Work shall include, but not necessarily be limited to, the structural design, supply,
fabrication, shipment, and erection of the following principal items:
1. The ETFE system as indicated on the drawings and in these specifications.
2. Perimeter, catenary, and aluminum clamping system.
3. Secondary support cables for ETFE and associated hardware
4. Structural steel, as indicated on the drawings.
5. Fasteners and gasketing.
6. Walkable Gutters or extrusion caps to provide access for maintenance.
7. Secondary steel framing and sheet metal gutters, including associated flashing.
8. Brackets for lightning protection, if required, and other elements that are required on the ETFE roof.
9. Bird deterrent system, if required

D.E. The ETFE system used in these structures shall be a system consisting of ETFE film, aluminum attachment,
perimeter flashings and if necessary cables. All references to "ETFE system" in this Section, without
exception, and whether singular, plural, or capitalized or not, are to such architectural systems.

E.F. The film used in these structures shall be a copolymer ethylene tetrafluoroethylene (“ETFE”, such as
ethylene tetrafluoroethylene). All references to “film and or foil” in this section, without exception, and
whether singular, plural, capitalized or not, are to such architectural film(s).

ETFE Single Film System 133123 - 1


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

F.G. The Subcontractor shall be deemed to have carefully examined all the drawings and performance
specifications referred to in the RFP tender documents and to have ascertained from them the full character
of the works. No warranty or representation is given by the Architect as to the accuracy of dimensions or
the buildability of the details shown on the drawings included in the tender documents.

G.H. Should the Subcontractor, after consideration of all the criteria which in his specialist knowledge are
relevant to the design and construction of the works, wish to make proposals for changes in any of the
details, dimensions or material shown in the drawings or referred to in the Specification, then such
proposals should be submitted to the Architect for his acceptance or rejection.

H.I. Related Sections: The following Construction Specification Institute (CSI) MasterFormat™ divisions
contain requirements relating to this section
1. Division 0: Procurement and Contracting Requirements.
2. Division 1: General Requirements.
3. Division 1: 013573 Delegated Design Procedures
2.4. Division 1: 013573A Delegated Design Summary
3.5. Division 1: 014339 Visual and Performance Mock-ups
4.6. Division 5: Metals
5.7. Division 7: Thermal and Moisture Protection
6.8. Division 9: Finishes, for paints and coatings.

1.3 REFERENCES

A. General: The works are to be carried out in accordance with all relevant American, Brazilian and
International Standards. Where the Subcontractor has preference for justifying his design against U.S.,
British or German Standards he must first seek the Architect’s approval and that of the appropriate local
building officials. Except as otherwise shown or noted, all Work shall comply with the requirements of the
following codes and standards:
1. 2015 International Building Code
2. 2018 Building Code
2.3. 2018 Building Code, Appendix R Corrosion-Resistant Construction
3.4. American Architectural Manufacturers Association (AAMA).
4.5. American Institute of Steel Construction (AISC).
a. AISC/ANSI 360-05 Specifications for Structural Steel Buildings
b. AISC 303-05 Code of Standard Practice for Steel Buildings and Bridges
c. AISC/ANSI 341-05 Seismic Provisions for Structural Steel Buildings
5.6. American Society of Civil Engineers (ASCE).
a. ASCE 7-10: Minimum Design Loads for Buildings and Other Structures
b. ASCE 19: Structural Applications of Steel Cables for Buildings
6.7. American Society for Testing and Materials (ASTM) International.
a. ASTM A36 Standard Specification for Carbon Structural Steel
b. ASTM A153 Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
c. ASTM A307 Standard Specification for Carbon Steel Bolts, Studs, and Threaded Rod
60 000 PSI Tensile Strength
d. ASTM A500 Standard Specification for Cold-Formed Welded and Seamless Carbon
Steel Structural Tubing in Rounds and Shapes
e. ASTM A572 Standard Specification for High-Strength Low-Alloy Columbium-
Vanadium Structural Steel
f. ASTM A586 Standard Specification for Zinc-Coated Steel Structural Strand
g. ASTM A603 Standard Specification for Zinc-Coated Steel Structural Wire Rope
h. ASTM A780 Standard Practice for Repair of Damaged and Uncoated Areas of Hot-
Dip Galvanized Coatings

ETFE Single Film System 133123 - 2


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

i. ASTM B209 Standard Specification for Aluminum and Aluminum-Alloy Sheet and
Plate
j. ASTM B221 Standard Specification for Aluminum and Aluminum-Alloy Extruded
Bars, Rods, Wire, Profiles, and Tubes
k. ASTM C423 Standard Test Method for Sound Absorption and Sound Absorption
Coefficients by the Reverberation Room Method
l. ASTM C518 Standard Test Method for steady-state heat flux measurements and
thermal transmission properties by means of the heat flow meter
apparatus
m. ASTM C1363 Standard Test Method for Thermal Performance of Building Materials
and Envelope Assemblies by Means of a Hot Box Apparatus
n. ASTM D635 Standard Test Method for Rate of Burning and/or Extent and Time of
Burning of Plastics in a Horizontal Position
o. ASTM D1929 Standard Test Method for Determining Ignition Temperature of Plastics
p. ASTM D2863 Standard Test Method for Measuring the Minimum Oxygen
Concentration to Support Candle-Like Combustion of Plastics (Oxygen
Index)
q. ASTM D4851 Standard Test Methods for Coated and Laminated Fabrics for
Architectural Use
r. ASTM E84 Standard Test Method for Surface Burning Characteristics of Building
Materials
s. ASTM E90 Standard Test Method for Laboratory Measurement of Airborne Sound
Transmission Loss of Building Partitions and Elements
t. ASTM E96 Standard Test Methods for Water Vapor Transmission of Materials (dry
cup method)
u. ASTM E108 Standard Test Methods for Fire Tests of Roof Coverings
v. ASTM E424 Standard Test Method for Solar Energy Transmittance and Reflectance
(Terrestrial) of Sheet Materials
w. ASTM G21 Standard Practice for Determining Resistance of Synthetic Polymeric
Materials to Fungi
7.8. American Welding Society (AWS).
a. AWS D1.1: Structural Welding Code
b. AWS 2.4: Symbols for Welding and Nondestructive Testing
8.9. Aluminum Association.
a. Specifications for Aluminum Structures
b. Aluminum Design Manual
9.10. National Fire Protection Association (NFPA).
a. NFPA 701: Standard Methods of Fire Tests for Flame Propagation of Textiles and Films
10.11. Society for Protective Coatings (SSPC).
a. Steel Structures Painting Manual, Volumes 1 and 2
11.12. European Committee for Standardization:
a. EN 10218, “Steel wire and wire products.”
b. EN 10264, “Steel wire and wire products – Steel wire for ropes.”
c. EN 12385, “Steel wire ropes – Safety.”

1.4 SYSTEM REQUIREMENTS

A. General: Provide an ETFE system that complies with requirements specified herein. The subcontractor
shall submit a copy of test results for all tests listed in this section.
1. Basis of Design: Printed ETFE film with 16 mm diameter dots, Grade P46D16, H46D16-Gray4mm
silver dot pattern at 63% coverage.

B. Building Code Criteria: The ETFE system shall comply with the 2018 Building Code, 2015
International Building Code (IBC) with ASCE 7-10.
1. Ground Snow Load: 0 kPa

ETFE Single Film System 133123 - 3


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

2. Risk Category: III


3. Roof Live Load in gutters: 1.0 kPa
1. Roof Live Load on ETFE, distributed load on areas below 600 sf: 1.0 kPa
2. Roof Live Load on ETFE, distributed load on areas above 600 sf: 0.6 kPa
3. Roof Live Load on ETFE, point load: 1.5 kN
4. Basic Wind Speed: 66 m/s (150 mph)
5. Seismic Loads Site Class: E
6. Spectral Response Acceleration SS: 0.11 g
7. Design short Period Spectral Response Acceleration SDS: 0.167 g

C. Wind load: Refer to 2018 Building Code table 1609.

D. Life Safety: All ETFE systems shall be designed so that no life safety issue is created in the event of a loss
of a part of the ETFE film. The ETFE system supporting structure shall not rely on the ETFE film for
structural stability.

E. Designs of ETFE systems are to withstand the most critical effects of load factors and load combinations.

F. Rain Load: The ETFE system as well as the secondary structure shall be checked for ponding instability
and drainage.

G. Fire Performance: Range of characteristics required of ETFE films:


1. Burning Characteristics (ASTM E84)
a. Flame Spread <10 max.
b. Smoke Density <150 max.
2. Fire Resistance of Roof Coverings (ASTM E 108)
a. Burning Brand Class A
3. Flame Resistance (NFPA 701 Small Scale method 1, UL 94)
a. Flame rating V-0
4. UBC-26-7 as CC-1 material
5. NFPA 259 potential heat (BTU/1 pound) l<5800
6. Visible combustion ASTM D635 pass
7. Self-ignition ASTM D1929 >850 deg F
8. Oxygen index ASTM D2863 > 40%

H. Solar Performance: The system shall have a Solar Heat Gain Coefficient (SHGC) less than or equal to 0.59.

I. Visual Light Transmission: The system shall have a Visual Light Transmission (VLT) greater than or equal
to 54%

J. Condensation: Adequate drainage for condensation shall be provided.

K. Thermal Movement: The system shall be able to accommodate changes in dimension resulting from
changes in temperature in any of its parts, its supporting framework and hardware without any reduction in
the performance below the minimum levels required herein.
1. Temperature Change (Range): 67 deg C (120 deg F), ambient; 100 deg C (180 deg F), material
surfaces.

L. Cladding Deflection
1. The ETFE cladding system shall be able to accommodate the movements of the structure as outlined
in the Structural Engineer’s report. Cladding deflections shall not exceed the following limits under
all applicable design loads:

ETFE Single Film System 133123 - 4


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

2. The maximum deflection from dead loads of any main horizontal framing member shall not exceed
clear Span/240 or tighter if deemed necessary to avoid ponding.
3. Cantilever deflection: Where framing members overhang an anchor point, limit deflection to two
times the length of the cantilever, divided by 175 (2L/175).

M. Corrosion
1. Select and install each material so that it is and shall remain compatible with the other materials
around it and within its range of influence, including connections to supporting structure and
adjacent elements, for the design life of the assemblies as appropriate for the environment, as defined
in ISO 12944-2.
2. Ensure adequate measures are taken to prevent bimetallic corrosion between dissimilar metals.
3. Fit separators to eliminate the risk of corrosion, where different metallic materials are used.
3.4. Corrosion resistance to meet the requirements set forth in 2018 Building Code, Appendix R
Corrosion-Resistant Construction for a moderate marine environment.

N. In the event of conflict between pertinent codes and regulations and the requirements of the referenced
standards or these specifications, the provisions of the more stringent shall govern.

1.5 QUALITY ASSURANCE

A. Subcontractor Qualifications: Fabrication and erection of the ETFE system is limited to firms with proven
experience in fabrication and construction of complex membrane structures. Such firms, through their own
experience and/or that of their qualified subcontractors, shall meet the following minimum requirements:
1. The Subcontractor shall have at least fifteen (15) years’ experience in the successful fabrication and
erection of permanent, custom tensile or air inflated membrane structures.
2. The Subcontractor shall have fabricated and erected at least twenty (20) ETFE film structures, with
at least five (5) structures of similar size and complexity as this project.
3. The Subcontractor shall design, procure, fabricate and erect the ETFE system as described in the
below.
4. The Subcontractor shall demonstrate it owns and operates a fabrication facility of adequate capacity
and will maintain a staff experienced in the fabrication of ETFE films that will undertake the
fabrication of this project. Subcontractor shall demonstrate that the facility is ISO-certified and shall
meet the specific requirements listed in Section 3 of this Specification.
5. The Subcontractor shall demonstrate that it has maintained a professional staff personnel
experienced in the design of tensile membrane structures for at least five years, and will provide
engineering drawings and calculations that have been prepared by a Professional Engineer in its
employ, or by a qualified consulting engineer with experience in designing tensile membrane
structures of similar size and complexity. The engineer performing the work for this project shall be
a licensed professional engineer and have the ability to sign and seal all engineering documentation.
The engineer completing the engineering package shall use state-of-the-art form-finding, membrane
analysis and membrane patterning software. The engineering software used by the engineer shall be
software written specifically for design and engineering of permanent membrane structures.
Subcontractor shall submit resumes of the engineers to be involved with the project at bid time.
6. The Subcontractor shall maintain an in-house Warranty and Service department to assist in repair
and service calls.
7. The Subcontractor shall submit a Corporate Quality Control Manual describing the company’s
complete quality assurance program.

B. Qualified Tensile Membrane Structure Contractors, subject to the requirements of this Section:
1. FabriTec Structures LLC
2. Vector Foiltec
3. Dunn Lightweight Architecture

ETFE Single Film System 133123 - 5


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

4. Fabritecture

C. Field measurements: Take field measurements after permanent end terminations are in place and prior to
preparation of shop drawings and fabrication, to ensure fitting of work.

D. Single source responsibility: SS cables and all its components shall be products of a single manufacturer.

E. Pre-installation conference: Prior to commencement of ETFE work, hold a conference to review work to
be accomplished. Include the following:
1. General Contractor (GC), Architect, Engineer, fabricator, installer and other subcontractors whose
work involves architectural rigging system shall attend conference.
2. Contractor shall notify all parties at least 10 days prior to time for conference.
3. Contractor shall record minutes of meeting and distribute to attending parties.
4. Review the following:
a. Method of attachment of components to supporting surfaces.
b. Detailed schedule of Works.
c. Installation, adjusting, cleaning, and protection of cable net system.

F. Coordination with other works.


1. Inspection System: The Subcontractor shall operate an inspection system to verify that all materials,
workmanship and complete work conform with the specified requirements.
2. Tests, Procedural Trials, Trial Assemblies: The Subcontractor shall carry out or arrange to be carried
out all tests on operatives, procedural trials, tests on materials and workmanship and trial assemblies.
The Subcontractor shall carry out such further tests as are necessary to demonstrate compliance with
this Specification and to confirm that the ETFE film has the properties assumed by his design.
3. Personnel: The Subcontractor shall ensure that all personnel performing inspections and tests have
appropriate qualifications.
4. Inspection Status: The Subcontractor shall operate a system for identifying the inspection status at
all stages of fabrication and erection.
5. Period of Notice: The Subcontractor shall agree a period of notice to the Architect for all tests and
submissions and before commencing any prototype.

1.6 SUBMITTALS

A. General: Notwithstanding any provisions of these specifications that may appear to be to the contrary, any
and all submittals by the Subcontractor shall be subject to review, approval, and adoption by the Project
Engineer as part of the overall project design and engineering, and shall not create a contractual or other
professional design relationship between the Subcontractor and either the Project Engineer or the Owner.

B. Delegated-Design Submittal: For shop drawings and calculations indicated to comply with performance
requirements and design criteria, including analysis data signed and sealed by the qualified professional
engineer responsible for their preparation.

B.C. Product Data: Include manufacturer’s specifications for materials, fabrication, installation, and
recommendations for maintenance. Include test reports showing compliance with project requirements
where test method is indicated.
1. Samples: Submit selection and verification samples.

C.D. Submittals with Bid: The General Contractor shall submit with its bid the following materials from the
Subcontractor:
1. Schedule indicating key milestone dates during the project.
2. Pre-qualification package including:
a. Company background and years of experience

ETFE Single Film System 133123 - 6


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

b. Organizational chart and staff C.V.


c. List of past project references pursuant to Section 1.5.A.1 and 1.5.A.2
d. Client recommendations
e. Fabrication facility documentation pursuant to Section 1.5.A.4:
1) Background, including proof of ownership and years of operation
2) Physical address
f. ISO certifications for Design and Fabrication facilities
3. Preliminary ETFE structural calculations, including definition of load cases used for design with
supporting references.
4. Proposed system drawings for the aluminum ETFE support system, cables and steel support system.

D.E. Shop Drawings: Subcontractor shall submit ETFE system drawings defining the completed structure,
anchorage and connection details, interfaces with building construction, and general film seam
arrangements. Design Drawings are to be signed and sealed by a licensed professional engineer.

E.F. Structural Calculations: Subcontractor shall submit ETFE system structural calculations for service,
ultimate and accidental load cases as one package with design drawings, signed and sealed by a licensed
professional engineer. Structural calculations shall include all required loading cases and load combinations
used in the design and resulting member forces, reactions, deflections, and drift. The magnitude of
maximum reactions on the supporting structures from all critical load combinations shall be separately
tabulated. Critical load conditions sued in the final sizing of the members shall be emphasized.

F.G. Solar Calculations: Subcontractor shall submit ETFE system calculations to verify solar and visual
transmittance.

G.H. Samples: Submit samples for proposed ETFE film and aluminum extrusion finishes, including a fabrication
sample, minimum 48” x 48” in dimension. The ETFE film samples shall include any specified coatings
and/or frit and be mounted in the frame in the order as per the proposed design.
1. Refer to Section 014339 Visual and Performance Mock-ups
2. Samples shall include:
a. ETFE film samples
b. Perimeter, catenary and aluminum clamping system.
c. Secondary support cables for ETFE and associated hardware
d. Visible Fasteners and gasketing

H.I. Prototypes and visual Benchmarks:


1. Subcontractor shall provide a visual mock-up as described below. The visual mockup shall show
the final film build up and comprise the proposed aluminum and steel subframes including:
a. Provide ETFE canopy, minimum 6000mm x 6000mm representative section of the NOB
north and south canopies, including steel support structure with aluminum cladding/
tensioned stainless-steel cables and hardware/ cable clamps-standoffs gutter condition/
tensioned ETFE film, with all associated hardware. Demonstrate ridge condition and slope
as designed to verify canopy drainage, and evidence that design will not permit standing or
ponding water remaining on the canopy.
2. Subcontractor shall provide functional mockups to verify friction in secondary steel connections,
strength of roof access system anchors and other performance tests requested elsewhere.

I.J. Quality Assurance Submittals.


1. Test Reports: Provide test reports from a qualified testing laboratory that show compliance of the
Subcontractor’s ETFE system with specification requirements, as follows:
a. Physical test data of the actual film roll goods to be used in the project confirming
conformance with specifications for the film.
b. Product data for other components confirming conformance with specifications.

ETFE Single Film System 133123 - 7


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

2. Certificates: Product certificates signed by the Subcontractor certifying materials comply with
specified characteristics, criteria, and physical requirements.
3. Records: The Subcontractor shall keep records of all tests on operatives, procedural trials and tests
on materials and workmanship. The Subcontractor shall make records available to the Architect for
examination.

J.K. Closeout Submittals.


1. Warranty: Project Warranty documents as described herein.
2. Record Documents: Project record documents for installed materials in accordance with Conditions
of the Contract and Division 1 Submittal Procedures Section.
3. Record Drawings and Maintenance Manual: On completion of the works, the Subcontractor shall
provide full and specific instructions for maintenance of the works, together with drawings of the
works as built. These instructions shall be typed on letter size paper with associated drawings and
illustrations, all bound in suitable binders and submitted no later than practical contract completion
to the Architect. Five copies shall be submitted. The manual shall include a schedule for routine
inspection, an inspection checklist, instructions for emergency repair and use of emergency repair
materials, and warranty. During the system erection period, the Owner shall provide maintenance
personnel to be trained in the use of the repair materials.
4. Repair Kit: The Subcontractor shall also provide a repair kit complete with materials suitable for
minor repairs. The Subcontractor will instruct the Owner’s representatives in the use of the repair
kit.

1.7 PRODUCT DELIVERY, HANDLING, AND STORAGE

A. General: Refer to the Conditions of the Contract for product handling provisions.

B. Materials shall be packed, loaded, shipped, unloaded, stored, and protected in a manner that will avoid
abuse, damage, and defacement.

1.8 WARRANTY

A. General: Refer to Division 1 for project warranty provisions.

B. Unless stated otherwise in these specifications, guarantee shall state that the Contract Work is in accord
with Drawings and Specifications, as amended by any changes authorized by the Architect, free from
defects in materials and workmanship and weather tight for a period of ten (10) years, from the date of
acceptance of the Contract Work by the Owner. Contractor shall agree to repair or replace defective
materials and workmanship to "like new condition", including such exploratory work, required to determine
the cause, during the guarantee period, at no additional cost to the Owner. The Contractor shall include
with his proposal, copy(s) of proposed warranty(s).

C. In addition to Contractor’s guarantee, the paint finish manufacturer shall guarantee the finish for a period
of twenty (20) years from the date of acceptance of the Contract Work against defects, including full labor
and material costs. Contractor shall include with his proposal, copy of warranty from proposed paint finish
manufacturer.

D. The Contractor shall be responsible for damage to the building and furnishings occasioned by defective
materials or workmanship or damage as part of repairs to the Contract Work.

E. The guarantee, the enforcement or lack of enforcement thereof, shall not deprive the Owner of other actions,
rights or remedies available to him. Guarantee shall be in form approved by the Owner. Guarantee does not
cover damage resulting from vandalism or acts of nature exceeding specified performance criteria.

ETFE Single Film System 133123 - 8


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

F. Maintenance
1. Include a separate price for regular inspection and maintenance agreement of the ETFE system to
begin 1 year after Substantial Completion of the Project in order to meet warranty requirements.
The maintenance contract will be directly with the Owner.
2. The ETFE subcontractor shall visit the site on a yearly basis for inspection and maintenance of the
system upon Owners acceptance of the regular inspection and maintenance agreement. The exact
schedule shall be as determined between the Owner and the subcontractor.
3. The Owner agrees to furnish access to the installation. The ETFE subcontractor shall include the
cost for limited access due to those requirements. Repair and replacement of materials and
components covered by warranty shall be performed at no additional cost to the Owner. The
maintenance contract shall include a schedule of prices for replacement of major components not
covered by the warranty.

1.9 DESIGN

A. General: The Subcontractor shall prepare a fully coordinated design for the works and shall ensure that all
elements therein are mutually compatible.

B. The Subcontractor shall determine the size, strength, quality and type of all items and materials to be used
in the Works with reference to the particular characteristics of the site and the buildings. Consideration
shall be given to all the environmental conditions, both actual and potential. These shall include, but not be
limited to:
1. Wind regime.
2. Seismic.
3. Temperature fluctuations.
4. Rain.
5. Solar radiation.
6. Orientation to sun path.

C. The ETFE structures shall be designed so that their components shall not be susceptible to vibration,
fatigue, excessive deflection or instability.

D. The arrangement, shape and dimensions of the ETFE structures and their components shall be as close as
possible to the Architect’s drawings.

E. The ETFE structures shall be designed to have a minimum service life of 30 years. The design and
construction of the structures shall ensure that adequate safety margins are maintained over the life of the
installation allowing for reduction in material and joint strength.

F. The design and configuration of any painted or coated structural connection details shall be such as to
enable full repainting to restore the paint system.

G. Statutory Approvals: The Subcontractor shall be responsible for obtaining approval of his design from
and any relevant local authorities.

H. Loadings: The design loadings given in the Basis of Design are in accordance with the relevant American,
Brazilian and/or other approved Standards and Regulations.

I. Deflection: The Subcontractor is to design the ETFE structures, cables and associated steelwork to limit
deflections of the tensioned ETFE panels under load such that the initial shape of the ETFE remains sloped,
i.e. does not invert, under a wind load that is defined by code as having a return period of 10 years, i.e. a
probability factor Sp = 0.934 unless the Subcontractor can show by step by step deflection analysis that the

ETFE Single Film System 133123 - 9


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

initial prestress biaxial tension field does not reduce to zero at any point in the ETFE panels during the
process of the application of the wind load from zero to maximum load.

J. Analysis: The Subcontractor shall carry out a full analysis of the ETFE structures under all relevant loading
conditions and combinations using a suitable non-linear analysis program. This analysis shall be used to
design the steelwork, cables, tensioned membranes, and all fitments, and to provide forces and moments to
permit the design of the supporting structure and foundations. The Subcontractor is to provide the support
forces to the Architect within the period specified. In particular the Subcontractor must satisfy himself as
to the following:
1. That there is compatibility between his mathematical model shape and with his own cutting patterns.
2. That the geometry and stress described by his mathematical model together constitute an equilibrium
form.
3. That the Subcontractor’s mathematical model includes support stiffnesses which adequately
represent the supporting building and foundations to which he is attaching.
4. That the membrane connection plate geometry and other steelwork geometry is compatible with his
mathematical model.
5. That the supporting steelwork and cables for which the Subcontractor is responsible are designed
and constructed to adequately resist the applied forces from the fabric.

K. Clash: The Subcontractor is to check and ensure that the ETFE membranes remain at an adequate separation
distance from any other elements at all stages of deflection under load.

L. Pre-Stress in ETFE and Cables:


1. The Subcontractor shall select levels of pre-stress in relation to the behavior of his structures.
2. The Subcontractor shall determine acceptable variations in the pre-stress which are compatible with
his design
3. The Subcontractor shall also select a level of pre-stress in the ETFE, as well as the process of
installing it, such that subsequent loading and unloading are largely elastic.
4. The initial level of pre-stress shall also be sufficient to avoid the need for re-stressing within 10
years of the completion of the project.
5. Level of pre-stressing and sequence(s) shall be used during installation to avoid any ETFE wrinkles
after installation and during service. Cables shall have adequate pre-stress to avoid sag and excessive
movement of cables during service.
6. On or before the issue of the Practical Completion Certificate the pre-stress shall have stabilized to
the agreed design values and tolerances thereon.
7. The Subcontractor shall take in situ measurements. At the end of the Works, there shall remain
adequate adjustment to allow for future re-stressing.

M. Loadings of the ETFE Structures on Supporting Superstructure: The Subcontractor shall be responsible for
the site connections of the ETFE structures to the building structure. The Subcontractor will submit
reactions (support forces) to the Architect. The Subcontractor shall be responsible for coordinating with the
Architect and Engineer to review the support design of the checking that the support design is both strong
and stiff enough to support the ETFE structures.

N. Tolerances: The design of the ETFE structures shall allow for the permitted tolerances in the buildings
adjacent. The elements of the ETFE structures shall be manufactured within tolerances which ensure that
they fit on site and do not induce excessive loads or deflections in the components. The Subcontractor shall
satisfy himself on the position as constructed of his connection points to the supporting superstructure
1. Coordinate works with Section 051200 Structural Steel Framing

ETFE Single Film System 133123 - 10


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

PART 2 - COMPONENTS

2.1 ETFE SYSTEM

A. General: The ETFE System used in these structures shall be made of a printed and clear single layer ETFE
system. The ETFE thickness shall be determined by the subcontractor according to the below thermal and
structural specifications. The color and/or printing of the ETFE shall be applied as to respond to the required
solar specifications.

B. Basis-of-Design: Design is based on systems as manufactured by Pfeifer FabriTec Structures LLC.


1. Equivalent systems by the following manufacturers may be acceptable provided they comply with
requirements of the Contract Documents:
a. Dunn Lightweight Architecture;
b. Fabritecture
c. Vector Foiltec

2.2 ETFE Film

A. General: The ETFE Film used in these structures shall be based on building conditions (environment,
interior moisture, ect.). ETFE Films shall be manufactured by one of the following:
1. Ashai Glass Corporation, Tokyo, Japan
2. Nowofol Gmbh, Siegsdorf, Germany

B. The ETFE film shall meet the following general requirements:


1. Source Quality Control: The primary materials shall be obtained from a single manufacturer.
Secondary materials shall be those recommended by the primary manufacturer.
2. Physical Characteristics: The following indicates a range of physical properties typical of ETFE
films. The determination of specific characteristics and selection of a film shall be derived from
project engineering by the Project Engineer.
a. Specific Gravity: 1.70 – 1.76 (ASTM D792)
b. Thickness (microns): 60 - 500. (ASTM D4851)
c. Print: Ink to achieve the solar performance criteria,
printing percentage 63%
d. Solar Transmission of clear film: 93% (ASTM E424)
e. Refractive Index: 1.4% (ASTM D542)
f. Water absorption: <0.03% (24 hrs)
g. Solar Translucency (%) clear film (ASTM 93%
424)
h. Solar Reflectance Index (SRI) (%) 50 nom.
(ASTM 424)
i. Solar Heat Gain Coefficient (SHGC) 0.59
j. Visible Light Transmittance (VLT) (%) 54%

2.3 CABLES AND END FITTINGS

A. Material quality
1. The alloy chosen shall neither corrode nor exhibit any surface pitting in its installed condition, nor
shall require regular maintenance to prevent corrosion. Unless noted otherwise, Type 316L (grade
1.4404) shall be used for visible components.

B. Materials:
1. All structural wire rope cables, except stainless steel, shall conform to the latest revision of ASTM
A603.

ETFE Single Film System 133123 - 11


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

2. All structural strand cables, except stainless steel, shall conform to the latest revision of ASTM
A586.
3. All cables in contact with the membrane shall be coated or sleeved to prevent damage of the foil.
4. Reinforcement cable for the ETFE structures shall be made of stainless steel, AISI 304 or AISI 316.
5. Stainless steel wire: Comply with requirements of ASTM A492, for the type and strength as
indicated on the Contract Drawings or higher in accordance to compatible standards as below. The
drawn wire shall show no surface defects or internal defects prejudicial to its use.
6. Characteristic Breaking Load (CBL):
a. Spiral strand rope (OSS) stainless steel modulus of elasticity shall be as specified by the
manufacturer. Modulus of elasticity shall be defined as the secant line slope between points
on the stress-strain curve defined by 10% of the nominal cable strength and 90% of the pre-
stretching force, as shown in the ASCE 19 Standard Guidelines for the Structural
Applications of Steel Cables for construction purposes. Unless otherwise approved by the
manufacturer the modulus of elasticity of the cables to be used in the works shall be within
the prescribed range.
b. The ultimate capacity of each complete cable assembly, including all end fittings, shackles,
rigging screws etc., must be equal or greater than 95% of the CBL. In addition, individual
shackles rigging screws etc., shall possess a factor of safety of at least 2.5 x "design load" if
justified by separate tests.
c. The Contractor shall submit for approval the design of any strand or rope used and ensure
sufficient local flexibility to prevent stress concentrations or other undesirable effects such
as "buckling" of wires due to the presence of clamps, connections and other attachments.

C. Fabrication.
1. Cable fabricator shall provide effective quality control over all fabrication activities. Inspection of
the place of fabrication may occur at any time to verify proper quality control. This inspection does
not relieve the fabricator from meeting the requirements of this specification.
2. Cables that are designated to be prestretched shall be prestretched per ASTM A603 for wire rope
and ASTM A586 for structural strand. Cables of the same type shall have the same modulus of
elasticity.
3. All cables shall be manufactured to the following length tolerances at 70 degrees Fahrenheit (23
degrees Celsius):
a. Length < 70 feet (21.3 meters) ¼ inch (6.4 mm)
b. Length 70 to 270 feet (32.3 to 82.3 meters) 0.03% of length
c. Length > 270 feet (82.3 meters) 1 inch (25.4 mm)
4. Cables shall have a continuous longitudinal paint stripe (1/4 inch wide max.) along their top surface
unless noted otherwise.
5. Index markings shown shall be a circumferential paint stripe (1/4 inch wide max.).
6. All cables and end fittings shall be delivered clean and dry.
7. All swaged and speltered fittings shall be designed and attached to develop the full breaking strength
of the cable. Thimble end fittings shall develop a minimum of 90 percent of the cable breaking
strength.
8. Swaged end fittings, pins, nuts, and washers shall be stainless steel.
9. Fittings and Accessories
a. Stainless steel fittings: Comply with requirements of ASTM A582
b. Stainless steel fasteners, bolts and studs shall conform to ASTM F593, nuts shall conform to
ASTM F594.
c. Tensioners: Stainless steel turnbuckles complying with ASTM F1145.
d. Clamps: Confirm friction value of clamps through load testing.
e. Accessories - Provide low friction, high strength washers as necessary for separation of
components as required:
1) Acetal homopolymer: Complying with ASTM D6100, Delrin® as manufactured by
DuPont™ or approved equal.

ETFE Single Film System 133123 - 12


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

2.4 ALUMINUM CLAMPING SYSTEM

A. General
1. Aluminum Clamping System shall include bird wire bird deterrent system made of stainless steel
grade 304

B. Materials
1. Alloy and temper recommended by manufacturer and meeting the requirements and standards listed
herein for type of use and finish indicated in accordance with:
a. Sheet and Plate: ASTM B209
b. Extruded Bars, Rods, Profiles, and Tubes: ASTM B221
c. Extruded Structural Pipe and Tubes: ASTM B429
d. Structural Profiles: ASTM B308/B308M
e. Welding Rods and Bare Electrodes: AWS A5.10 / A5.10M
f. Castings: ASTM B26, ASTM B85, or ASTM B108 as appropriate

C. Fabrication
1. Aluminum fabricator shall provide effective quality control over all fabrication activities. Inspection
of the place of fabrication may occur at any time to verify proper quality control. This inspection
does not relieve the fabricator from meeting the requirements of this specification.
2. Fabricated aluminum shall have no sharp edges.
3. Stamp all parts with the appropriate mark number.
4. All fabricated aluminum shall be free of oil, grease, and machining chips.
5. Tolerances shall be as follows:
a. Cross sectional dimensions +/- 10%, 0.03-inch (0.8 mm) max.
b. Bolt hole locations +/- 1/32 inch (0.8 mm)
c. Overall length +/- 1/16 inch (1.6 mm)
6. All welded joints shall conform to AWS D1.2.

D. Finishes
1. Anodized finish
a. Carry out anodizing under conditions of acceptable good practice for architectural
applications. Hold the processing conditions constant for the period required for completion
of the contract. Keep records of these conditions and make available for inspection in the
event of a dispute as to the quality of the finished anodic coating.
b. Clear Anodic Finish: AA-M12C22A41, Class I, 0.71 mil or thicker, as complying with
AAMA 611.

2.5 BRACKETS, FASTENERS AND ANCHORAGE

A. General:
1. All brackets and fasteners shall be designed so that there will be no risk of loosening due to the
effects of vibrations, or to the cyclic effects of load, deflections and thermal movements.
2. The design of brackets for site drilled fasteners shall allow for the possibility of reinforcement or
other obstructions being encountered and the fixing position being moved as a result of this event
occurring.
3. No reinforcement or other obstructions shall be cut without the approval of the Architect or
Structural Engineer.

B. Fasteners:
1. Fastener design shall be no less than the most stringent standards as required by Code and its
reference standards, or the following requirements:

ETFE Single Film System 133123 - 13


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

a. Fastener design for aluminum components shall be as per the Aluminum Association
Aluminum Design Manual (AA-ADM).
b. Allowable loads for fasteners shall be the lesser of the fastener manufacturers’ requirements
or per AAMA TIR A9 with the most recent amendments.
c. When utilizing a fastener that is not included in any of the above references, available
standards or design guides, a minimum factor of safety of 2 shall be used for permissible
load design of anchoring assemblies.
2. Fastener design shall account for any reduction in safe working loads due to their spacing, location
in areas of tension, near edges or proximity to cast in inserts/existing fasteners, or thickness of shims.
3. Unless shown in the Architectural Drawings, exposed fasteners are not permitted.
a. Where exposed fasteners are shown and required, countersunk security heads shall be used.
4. All exterior fasteners or fasteners in wet areas shall be of a suitable grade of stainless steel. Weather
coatings for corrosion resistance may only be used with the approval of the Architect.
5. Where post drilled or site fasteners are used for connections to the external structural steel frame,
the integrity of the steel corrosion protection system shall not be compromised.
6. The general requirement for torqueing of bolts shall be highlighted in the shop drawings and
tightening torque values are to be clearly stated.
7. The Contractor shall provide to the Architect for review documentation that demonstrates the use
of all proprietary fasteners installed have been reviewed and approved by the fastener manufacturer
and shall, prior to the installation, submit the manufacturer's written certification that the details
proposed by the Contractor are appropriate for their intended use.

C. Brackets and anchorage:


1. The design of brackets and anchorage shall allow for adjustments in small increments in and out, up
and down and side to side in the position of the Contract Work supports relative to other
constructions to accommodate the full variations in the underlying construction and fabrication
tolerances.
2. Shimming required to accommodate local variations in construction tolerances only. The maximum
allowable shim dimension shall be stated in the shop drawings.
3. Concrete and masonry inserts shall be hot-dip galvanized cast-iron, malleable-iron, or steel inserts
as required by ASTM A123 / A123M or ASTM A153/A153M.

2.6 GASKETING

A. General
1. Gaskets/dry weather seals shall not be installed in a pre-stretched condition.
2. Gaskets shall be accessible for inspection/replacement.
3. Gaskets and seals used to achieve the required weather and airtightness shall be selected in
accordance with ASTM C716 to fully accommodate the range of dimensional tolerances associated
with fabrication and installation of the Work. They shall be formed with materials capable of
maintaining their elastic qualities, dimensions and resistance to physical and chemical attack
sufficient to maintain the full performance during the design life. Gaskets shall be free from contact
and migration stain and shall be compatible with all substrate, sealant and finishes with which they
are likely to come in contact.
4. Gaskets shall maintain their performance and properties for the expected service life of the product.
5. The gaskets shall be free of mold flash.

B. Extruded rubber gaskets shall comply with ASTM C509.


1. Dense compression gaskets shall be molded or extruded of profile and hardness required to maintain
watertight seal, made from Silicone complying with ASTM C1115.
a. Use where soft compression gaskets will be compressed by inserting dense compression
gaskets on opposite side of glazing or pressure applied by means of pressure-glazing stops
on opposite side of glazing.

ETFE Single Film System 133123 - 14


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

2. Soft compression gaskets shall be extruded or molded, closed-cell, integral-skinned silicone gaskets
complying with ASTM C509, Type II, black; of profile and hardness required to maintain watertight
seal.

2.7 FINISHES GENERAL


1. Finishes shall be chosen such that touch-up finishes match factory finish.
2. Discoloration, fading, chalking, excessive non-uniformity, pitting, cracking, peeling, corrosion, or
crazing of finish shall not be allowed.
3. The terms below used in conjunction with finish Guarantee are defined as follows:
a. "Excessive fading": means a change in appearance that is perceptible and objectionable as
determined by the Architect when viewed visually in comparison with the original color
range standards.
b. "Excessive non-uniformity": means non-uniform fading during the period of the guarantee
to the extent that adjacent parts have a color difference greater than the original acceptable
color range.
c. "Will not pit or otherwise corrode": means there shall be no pitting or other type of corrosion
of finish discernible from a distance of ten (10) feet, resulting from the natural elements in
the atmosphere at the Project site.
d. Deterioration includes, but is not limited to, the following:
e. Color fading more than 5 Hunter units when tested according to ASTM D2244.
f. Chalking in excess of a No. 8 rating when tested according to ASTM D4214.
g. Cracking, checking, peeling, or failure of paint to adhere to bare metal.
4. Surfaces that might get in contact with ETFE foil shall be finished so that there are no burrs.

2.8 FLASHING

A. Provide corrosion-resistant, nonstaining, nonbleeding flashing compatible with adjacent materials


constructed with one of the following waterproof materials:
1. Stainless steel, ASTM A240/A240M of thickness recommended by manufacturer
2. Coated aluminum
3. One of the following membrane materials:
a. Flexible ethylene-propylene diene monomer (EPDM)
b. Silicone sheet

B. Flashings shall maintain their performance and properties for the expected service life of the Contract
Work.

C. Flashings shall have the necessary mechanical properties to withstand installation and specified design
loads.

D. Flashings visible externally or internally shall be aluminum sheet with finish to match the facade.

E. Flashings and smoke barriers visible externally or internally shall be aluminum sheet with finish to match
the facade.

F. At movement joints, use slip-joint linings, spacers, and sleeves of material and type recommended by
manufacturer.

2.9 BIRD DETERRENTS

A. Bird deterrents shall be provided on all horizontal or near horizontal surfaces. The Contractor shall provide
details and product data of the bird deterrent in accordance with the submittal requirements and Related
Sections.

ETFE Single Film System 133123 - 15


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

2.10 MAINTENANCE KIT

A. Film Maintenance Kit: The owner shall be supplied with the following materials for emergency repair or
maintenance. The materials shall be neatly packaged into a maintenance kit for storage by the owner.
1. 50mm x 50m for every 10,000 square meters of plan area

PART 3 - FABRICATION AND ERECTION

3.1 FABRICATION OF ETFE ASSEMBLIES

A. General.
1. ETFE assembly shop drawings shall include all information necessary for the fabrication of the
ETFE System. They shall include size and shape of ETFE panels, type and location of shop and
field connections, size, type, and extent of all heat-welded seams.
2. ETFE Foil materials are to be designed such that maximum foil stress is not exceeded under any
ultimate limit state design condition.
3. The film shall not be cracked or bent, dragged or pulled on any type of ground or surface without
adequate protection, stood or walked on.
4. The Subcontractor shall take necessary care to plan and assemble the fabricated sections such that
the assembly has no shop patches. Splices, if any, shall be patterned into a symmetrical and repetitive
geometric arrangement within the assembly, shown on the shop drawings and, where feasible,
hidden by structural members.
5. All fabricated joints shall have a minimum of 90 percent of the total strength of the film in strip
tensile testing. All structural joints shall be fused in accordance with industry standards and shall
maintain the integrity of the ETFE films and shall be heat sealed only.
6. Uniaxial Test: At least one (1) representative sample of the ETFE film shall be uniaxially test loaded.
Compensation in patterning shall be based upon the results of the uniaxial test loading.

3.2 ERECTION OF ETFE SYSTEM

A. Prior to installation of the ETFE System, the Subcontractor shall meet with the General Contractor to review
the erection procedure and scheduling. The Subcontractor shall coordinate all work with other trades.

B. Structural Steel.
1. Coordinate all temporary bracing and final works, including movement and tolerance requirements
and interfaces with the structural steel framing contractor and the General Contractor. See Section
051200 Structural Steel Framing.
2. All steel shall be accurately aligned before permanent connections are made.

C. Metal Protection
1. Where aluminum will contact dissimilar metals, protect against galvanic action by painting contact
surfaces with primer or by applying sealant or tape or installing nonconductive spacers as
recommended by manufacturer for this purpose.
2. Isolate all galvanized steel and unfinished aluminum components in direct contact with, but not
totally encased in, cementitious surfaces with thin dense PVC or EPDM isolation packs.
3. Where unfinished aluminum will contact concrete or masonry, protect against corrosion by painting
contact surfaces with bituminous paint.

D. Stainless Steel Cables


1. Any thread on cable connections must be cleaned thoroughly and greased prior to installation.
Damaged or dirty threads must not be assembled because this could lead to the tension member unfit
for use.

ETFE Single Film System 133123 - 16


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

a. For cable tension members made of non-alloyed steel, any provided thread on hot-galvanized
and spray-galvanized rope end fittings shall be degreased immediately after installation and
provided with lasting corrosion protection.
2. Cable members must not be installed twisted.
3. Cable tension members shall be pulled into their installation position using a suitable hoisting device
(e.g. winch) or using a suitable lifting device (e.g. suspension bar, spreading bar), so as to avoid
buckling or other damage to the cables.
4. Cables shall not be crushed, kinked, nor handled in any way that causes permanent deformation.

E. ETFE Handling:
1. Take the following precautions during storage:
a. material rolls stored dry and dark location in hanging position
b. protect the material against any dust or dirty
2. Handling procedure to limit the risk of optical damages such a scratches, buckling and dents, as well
as fingerprints on material surface and applying appropriate handling procedures. During
manufacture and on each contact with the material:
a. wear aseptic cotton-gloves
b. avoid any unnecessary roll out or movement
c. in case of unrolling the ground has to be clean and free of dirt or hindrances.
3. Both surfaces of the ETFE shall be left clean at the time of Practical Completion of the work to the
satisfaction of the Architect

F. ETFE and Cable Pre-Stress:


1. The Subcontractor shall determine acceptable variations in the pre-stress which are compatible with
his design.
2. On or before the issue of the Practical Completion Certificate the pre-stress shall have stabilized to
the agreed design values and tolerances thereon.
3. The Subcontractor shall take in situ measurements. At the end of the Works, there shall remain
adequate adjustment to allow for future re-stressing.
a. The subcontractor shall quantify adjustment allowance for future re-stressing;
b. Coordinate all work, including movement and tolerance requirements with the structural
steel framing contractor and the General Contractor. See Section 051200 Structural Steel
Framing.

3.3 FIELD QUALITY CONTROL

A. Testing Agency: Contractor must engage a qualified testing agency, acceptable to the Owner, to perform
tests and inspections.

B. Testing and inspection of representative areas of the Contract Work shall take place as installation proceeds
to determine compliance with installed assemblies with specified requirements. Refer to Related Sections
for field quality control testing requirements.
1. Water Spray Test: After completing the installation and before installation of follow-on trades has
begun, carry-out hose testing on 10% of the canopy as designated by Architect for water penetration
according to AAMA 501.2 requirements.
a. There shall be no evidence of water penetration.
b. Test Area: A minimum area of 300 square feet approximately including representative areas
of all perimeter and ridge framing members and drainage system.
c. Provide 1 week notice to all parties to allow them to attend all hose testing.

ETFE Single Film System 133123 - 17


ENDMENT 05, AUGUST 4, 2021CD3 AUGUST
14, 2020

d. Repair or remove and replace Work that does not meet requirements or that is damaged by
testing; replace to conform to specified requirements. For every leak located on the canopy,
hose test an additional 5% of the tested area.
e. For the purposes of this testing, a leak is defined as water entering beyond the secondary
drainage channels.
f. The Facade contractor shall prepare and submit an inspection and test report.
g. Repair or remove Work if test results and inspections indicate that it does not comply with
specified requirements.
h. Additional testing and inspecting, at Facade contractor's expense, will be performed to
determine compliance of replaced or additional work with specified requirements.

C. Protect work from damage and deterioration during installation.

D. Further protection of the work and final cleaning, if necessary, shall be the responsibility of the General
Contractor

3.4 TOUCH-UP

A. Touch-Up Painting: Field paint marred or abraded shop paint and welds after cleaning these areas. Separate
dissimilar metals and metals in contact with concrete or masonry with dielectric separator or gaskets. Do
not extend coatings onto exposed surfaces.

3.5 CLEANING

A. Maintenance of Installation: Maintain the assemblies throughout the construction period in a clean and
properly protected condition so that it will not be damaged at the time of acceptance by the Owner. Cleaning
and protection methods shall be carefully selected, applied and maintained so that finishes will not become
uneven or otherwise impaired as a result of unequal exposure to light and weathering. Immediately remove
deleterious material from finished surfaces.

B. Cleaning: Upon completion of installation wash exposed surface to leave clean and free from blemishes.
Protect the work during all construction activities so that it will be without indication of deterioration, use
or damage at times of acceptance.

3.6 PROTECTION

A. Protection: Protect the work during shipment, delivery, storage, handling, erection and construction for any
and all damages and avoid any non-uniformity of appearance or other defects in the Work. When requested
for inspection of finishes, remove and replace temporary protection. Provide board protection at
construction entrances and near construction chutes. Remove and dispose of protection when no longer
required.

END OF SECTION

ETFE Single Film System 133123 - 18

You might also like