Professional Documents
Culture Documents
of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification System for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com
Optional accessory:
Type of Protection: Equipment protection by flameproof enclosures "d", Equipment protection by intrinsic safety "i", Equipment
protection by increased safety "e"
Marking: Size 1 to 5
Ex db e IIB/IIC Gb respectively Ex db e [ia] ib IIB/IIC Gb
Size 6 and 7
Ex db eb IIB/IIC Gb respectively Ex db eb [ia] ib IIB/IIC Gb
Signature:
(for printed version)
Date:
Additional
manufacturing
locations:
This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended
STANDARDS :
The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards
IEC 60079-1:2014-06 Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
Edition:7.0
IEC 60079-11:2011 Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
Edition:6.0
IEC 60079-7:2015 Explosive atmospheres – Part 7: Equipment protection by increased safety ''e''
Edition:5.0
IEC 60079-7:2006-07 Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
Edition:4
This Certificate does not indicate compliance with safety and performance requirements
other than those expressly included in the Standards listed above.
Test Report:
DE/BVS/ExTR10.0002/07
EQUIPMENT:
Equipment and systems covered by this Certificate are as follows:
Description
The Ex-d component consists of a top and bottom part made of Ultramid. After the installations are being built in, both parts are welded. For
enclosure size 7 the bottom plate is additionally screwed. The enclosure must be built into an enclosure in the type of protection Increased
Safety according to IEC 60079-7.
Schedule of Limitations
- The Ex-d components shall be built in an enclosure in type of protection Increased Safety according to
IEC 60079-7.
- The max. temperature at the Ex-d components at rated values shall not exceed +110 °C.
Equipment (continued):
See Annex
Parameters
See Annex
IECEx Certificate
of Conformity
Certificate No.: IECEx BVS 10.0002U Page 5 of 5
Annex:
BVS_10_0002U_Cooper_Annex_issue7.pdf
Certificate No.: IECEx BVS 10.0002U, issue No.: 7
Annex
Page 1 of 1
Parameters
Type GHG 62 * 1/2/3/4 *** * ****
Main contact
Rated voltage max. 690 V; 50 / 60 Hz
Auxiliary contact
Rated voltage max. 440 V; 50 / 60 Hz
Type GHG 62 * 5/6 *** * ****
Main contact
Rated voltage max. 690 V; 50 / 60 Hz
Auxiliary contact
Rated voltage max. 550 V; 50 / 60 Hz
Type GHG 62 * 7 *** * ****
Main contact
Rated voltage max. 690 V; 50 / 60 Hz
Auxiliary contact
Rated voltage max. 690 V; 50 / 60 Hz
Limits of service temperature
IIB/IIC: Type GHG 62 * 1 to 7 *** * **** -20 °C…+110 °C
IIB: Type GHG 62 * 1/2 *** * **** -45 °C…+110 °C