Professional Documents
Culture Documents
of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification System for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com
Equipment: GOVAN brand - ES/DS & EM/DM Range of Junction Boxes and Control Stations
Optional accessory:
Type of Protection: Increased safety "e", Dust ignition protection by enclosure "t"
Signature:
(for printed version)
Date:
(for printed version)
Manufacturer: Pepperl+Fuchs SE
Lilienthalstrasse 200
68307 Mannheim
Germany
Manufacturing Pepperl + Fuchs (Australia) Pty Ltd Pepperl & Fuchs Manufacturing
locations: 131-149 Link Drive (India) Private Limited
Campbellfield Vic 3061 Plot No. A-13
Australia Sipcot Industrial Growth centre
ORAGADAM TAMIL NADU 602105
India
This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended
STANDARDS :
The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards
IEC 60079-0:2004 Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
Edition:4.0
IEC 60079-7:2006 Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
Edition:4
IEC 61241-0:2004 Electrical apparatus for use in the presence of combustible dust - Part 0: General requirements
Edition:1
IEC 61241-1:2004 Electrical apparatus for use in the presence of combustible dust - Part 1: Protection by enclosures "tD"
Edition:1
This Certificate does not indicate compliance with safety and performance requirements
other than those expressly included in the Standards listed above.
Test Reports:
AU/SIM/ExTR09.0002/00 AU/SIM/ExTR09.0002/01 AU/SIM/ExTR09.0002/02
EQUIPMENT:
Equipment and systems covered by this Certificate are as follows:
Refer Annex for equipment description, list of the models, limiting parameters and marking details.
Refer Annex
IECEx Certificate
of Conformity
Certificate No.: IECEx SIM 09.0001X Page 4 of 5
Refer Annex
IECEx Certificate
of Conformity
Certificate No.: IECEx SIM 09.0001X Page 5 of 5
Additional information:
Suitable heat-resistant cables and cable glands, with a continuous operating temperature of at least 95 °C must be used at the entry point for
the Range of ES/DS enclosures with temperature classification T5/T95°C.
Annex:
Equipment:
The ES/DS Range of Junction Boxes and Control Stations are of stainless steel construction with
a bolt-on cover. The ES Range employs the increased safety (Ex e) concept whereas the DS
Range are for combustible dust (Ex tD concept) applications. A gasket in the cover provides
protection against ingress of dust and water into the enclosures. The cover may incorporate two
types of windows as per manufacturer's documentation. Cable access is via separately certified
cable glands fitted to holes drilled into the walls of the enclosure for the ES/DS 1110, 1511 and
2315 Enclosures and via gland plates fitted to the ES/DS 3030, 4050, 5060 and 6090 Enclosures
or holes drilled in the walls as per manufacturer's documentation.
The covers for the ES/DS 3030, 4050, 5060 and 6090 Enclosures are fitted with hinges. Either
one (in the bottom of the enclosure) or three (left-hand side, right-hand side and bottom of
enclosure) gland plates can be fitted. The ES/DS 4050, 5060 and 6090 enclosures can be
mounted in either of the two vertical planes with the hinges located to suit.
The cover for the ES Range of Control Stations can be fitted with certified Indicator Lights (IECEx
PTB 06.0016U, IECEx PTB 07.0012U or equivalents), Ammeter (IECEx BAS 07.0043U or
equivalent), Fuse (IECEx PTB 06.0056U or equivalent), separately certified Pushbutton and
Switch operators as per manufacturer's documentation.
The enclosures can be fitted with general type electrical equipment such as motor starters, circuit
breakers, transformer’s, isolator’s, PLC’s and other electrical equipment that:
• Are evenly distributed within the enclosure.
• The watts dissipation is less than maximum values given in annex.
• Does not emit electromagnetic radiation unless separately certified.
ES/DS1110 10 15 6 10
ES/DS1511 12 18 7 12
ES/DS2315 15 20 7 15
ES/DS3030#-X 24 35 12 24
ES/DS4050#-XY 43 60 26 43
ES/DS5060#-XY 67 98 42 67
ES/DS6090#-XY 80 118 50 80
Example: #S#####-XY
V = Enclosure mounted with long side up
H = Enclosure mounted with long side horizontal
The following limiting parameters apply when the equipment is fitted with a window, Ammeter
Type AWAM2 (IECEx BAS 07.0043U) or Fuse Type 8560/.. (IECEx PTB 06.0056U):
• A short circuit protection device, rated at not greater than 10 A, must be fitted in series
with the Ammeter.
• The maximum power dissipation of the equipment listed in the Table 3 below must not
be exceeded.
Table 3: Maximum Power Dissipation for equipment fitted with window, Ammeter
Type AWAM2, or Fuse Type 8560/..
Maximum allowable power dissipation (W)
Model
(-20 °C ≤ Ta ≤ +40 °C) (-20 °C ≤ Ta ≤ +55 °C)
Number
T6 / T80°C T5 / T95°C T6 / T80°C T5 / T95°C
ES/DS1110 10 15 6 10
ES/DS1511 12 18 7 12
ES/DS2315 15 20 7 7
ES/DS3030 24 35 12 12
ES/DS4050 43 60 26 26
ES/DS5060 67 98 36 36
ES/DS6090 80 87 42 42
The square polycarbonate window, fitted in the ES/DS Range of enclosures, may generate
ignition-capable level of electrostatic charge under certain extreme conditions. The user must
ensure that the equipment is installed and used in accordance with the manufacturer's
instruction manual.
Marking details:
Notes:
T* - refer Tables 1 and 2 (ES Range only)
Ambient temperature range marked for extended range only.
IP** IP66 for all models except when fitted with Indicating lights (Types 8010 & 8013 listed in
Table 4).
IP65 for models fitted with Pushbuttons and Switches, refer Table 4.
Blank for models fitted with Indicating Lights (Types 8010 & 8013 listed in the tables).
# Marking as listed in the Table 4:
Table 4: Marking information for ES Range fitted with separately certified devices
Device Marking
Pushbutton de IIC
Switches de IIC
Meters e II
Indicator light; Types 8010 & 8013 de IIC or dem IIC
Fuse em II
ES/DS4050 60 26
ES/DS5060 95 36
ES/DS6090 87 42
Table 6: Marking information for ES Range when fitted with separately certified devices
Device Marking
Field bus barriers (IECEx PTB 03.0003) me [ia] IIC
Megablock IS terminals (IECEx CSA 06.0003X) e ia IIC
Segment protectors (IECEx PTB 05.0010X) me II
ES/DS1110
10 15 6 10 2 6
EM/DM1110
ES/DS1511
12 18 7 12 3 7
EM/DM1511
ES/DS2315
15 20 7 15 4 9
EM/DM2315
ES/DS3030#-#
24 35 12 24 7 15
EM/DM3030#-#
ES/DS4050#-#V
EM/DM4050#-#V
43 60 26 43 16 32
ES/DS4050#-#H
EM/DM4050#-#H
ES/DS5060#-#V
EM/DM5060#-#V
67 98 42 67 25 50
ES/DS5060#-#H
EM/DM5060#-#H
ES/DS6090#-#V
EM/DM6090#-#V
80 118 50 80 30 60
ES/DS6090#-#H
EM/DM6090#-#H
ES/DS8013#-#V
EM/DM8013#-#V
210 340 120 210 60 150
ES/DS8013#-#H
EM/DM8013#-#H
The following limiting parameters apply when the equipment is fitted with a window, Ammeter
Type AWAM2 (IECEx BAS 07.0043U) or Fuse Type 8560/.. (IECEx PTB 06.0056U):
• A short circuit protection device, rated at not greater than 10A, must be fitted in series
with the Ammeter.
• The maximum power dissipation of the equipment listed in Table 8 must not be
exceeded.
• Meter and window can only be fitted to models: **2315, **3030, **4050, **5060, **6090 &
**8013.
The square polycarbonate window, fitted in the equipment, may generate ignition-capable level
of electrostatic charge under certain extreme conditions. The user must ensure that the
equipment is installed and used in accordance with the manufacturer's instruction manual.
The maximum power dissipation assigned in Table 10 applies when fitted with the separately
certified Field bus barriers (IECEx PTB 03.0003), Megablock IS terminals (IECEx CSA
06.0003X), or Segment protectors (IECEx PTB 05.0010X) in order to limit the maximum
internal ambient temperature of the enclosure to 70 °C.
Table 11: Marking information for ES/EM Range when fitted with
separately certified devices
Device Marking
Operation Heads e IIC
Switches de IIC
Meters e II
Indicator light; Types 8010 and
de IIC or dem IIC
8013
Fuse em II
Field bus barriers me [ia] IIC
Megablock IS terminals e ia IIC
Segment protectors me II
Name/Address Name/Address