FORMANCE
Design Guide
V 1.1
Design Guide Performance Forever
Contents F2 hazardous building mat. .............................................. 6 Thermal Formance Roof / No Snow Load -
Table 1 ............................................................................................ 21
G services and facilities ...................................................... 6
ABOUT THIS GUIDE ...............................1 Thermal Formance Roof / 1kPa Snow Load -
G6 airborne and impact sound ..................................... 8 Table 2 ........................................................................................... 22
ABOUT THE FORMANCE SYSTEM .........1 H1 energy efficiency.............................................................. 8 Reinforced Formance Roof / light roof / No
Snow Load - Table 3 ...........................................................23
Application ..................................................................................... 1
8 STEP FORMANCE DESIGN PROCESS ..9
Reinforced Formance Roof / light roof / 1kPa
Components ................................................................................. 1
1. Demand .................................................................................... 10 Snow Load - Table 4 ...........................................................24
Code Compliance .................................................................... 1
Reinforced Formance Roof / light roof / 1.5kPa
2. Roof Panel span.................................................................. 11
Snow Load - Table 5 ...........................................................25
Sizes and Spec ........................................................................... 1
3. Wall Panel span ................................................................. 13
Reinforced Formance Roof / light roof / 2kPa
SCOPE.....................................................2 4. Cap Plate ................................................................................. 14 Snow Load - Table 6.......................................................... 26
www.formance.co.nz
www.formance.co.nz
1
©©Method
Method Building
Building Systems 2017 -- V1.1
Systems 2017 V1.1 (20180626)
(20180626)
Design Guide Performance Forever
FORMANCE WALL PANEL SPAN......... 31 Cap Plate Lower of the two storey / Floor and Roof Details ............................................................................... 69
medium weight cladding - Table 19 ....................... 41
Top or Single Storey / Light or Heavy Roof - Floor Details ........................................................................... 106
Table 11 ........................................................................................32
FORMANCE BRACING ......................... 42 Bracing Details ....................................................................... 111
Lower of two storey / Light or Heavy Roof -
Formance Bracing Wall 115mm - Table 20 ...... 43 Lintel Details ............................................................................ 114
Table 12 ........................................................................................33
Formance Bracing Wall 165mm - Table 21 ...... 43 Penetration Details and Services ............................119
Subfloor beneath two storey / Light or Heavy
Roof - Table 13....................................................................... 34
TYPES OF HOLD DOWN FIXING ......... 44
CAP PLATE ........................................... 35
CLADDING AND ROOFING FIXING..... 46
Cap Plate upper/single storey - 45mm roof
framing at 900mm crs. - Table 14 ............................ 36 Lintel supporting roof only for all wind zones
- Table 24 ................................................................................... 50
Cap Plate upper/single storey - 45mm roof
framing at 1200mm crs. - Table 15 ...........................37 Lintel supporting roof and wall for all wind
zones - Table 25 .................................................................... 51
Cap Plate upper/single storey – 90mm roof
framing at 1200mm crs. - Table 16 .......................... 38 Lintel supporting roof, floor and wall for all
wind zones – Table 26 .....................................................52
Cap Plate upper or single storey – 90mm roof
framing at 1200mm crs. CONTINUOUS
BUILDING INSPECTION SCHEDULE.... 55
BOUNDARY RAFTER - Table 17 ................................ 39
Example of building inspection schedule ......... 55
Cap Plate Lower of the two storey Floor and
light weight cladding - Table 18 ............................... 40
FORMANCE STANDARD DETAILS ....... 58
www.formance.co.nz
www.formance.co.nz
2
©©Method Building Systems
Method Building Systems 2017 - V1.1
V1.1 (20180626)
(20180626)
Design Guide Performance Forever
www.formance.co.nz
www.formance.co.nz
1
©©Method Building Systems 2017
Method Building 2017 -- V1.1
V1.1 (20180626)
(20180626)
Design Guide Performance Forever
www.formance.co.nz
1
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
2
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
B2 durability
Formance panels are engineered and
manufactured to comply with B2.
www.formance.co.nz
3
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
E2 external moisture
#Roofing Example
Weather tightness is a function of other
building elements, such as but not limited to;
wall cladding, roofing, flashings, cladding and
roofing underlay. The Oriented Strand Board
(OSB) facing board of Formance panels is
treated equivalent to H1.2 treatment and is
therefore required to be dry in use and
Roofing protected from weather. All timber inserted in
Roofing Underlay Formance panels is to be min. H1.2 treated.
www.formance.co.nz
4
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
#Cladding Example
be fixed to the outer OSB facing of Formance
panels. Cladding fixing depends on the
required batten spacing (according to the
cladding manufacturers specification) and the
tables are engineered to ensure appropriate
fixing capacity. Fixing requirements,
Formance Panel depending on weight and wind/eq zones,
can be determined using the fixing tables
E2 compliant cladding contained in this Design Guide.
Window Flashing
E3 internal moisture
Cavity Batten Formance panels should be protected from
moisture in all wet areas, such as but not
Wall Membrane limited to; kitchen, laundry, bathroom.
Formance panels can be protected by
various internal wall linings, complying with
NZBC E3, special plasterboard or various
paint systems. Some paint system
specifications are available on request,
prepared by various paint manufacturers.
Indoor humidity should be kept at range
between 25-65% and not above 70% for an
extended period of time (1week) If it becomes
a problem we recommend installation of a
moisture management system.
www.formance.co.nz
5
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
6
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Electric cables run inside the panel core that Heating Ventilation and Cooling
www.formance.co.nz
7
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Table 1 harness heat being exhausted from the home build a SIP home because SIPs provide the
and utilise it to heat the fresh air coming into structure. In most cases Formance panels are
FORMANCE SOUND INSULATION Rw the home for an even more efficient use of connected with insulated splines (SIP spline
PANEL LAYER VALUE energy. Proper ventilation is crucial in or only strips of OSB)
1 0 29 structures with low air infiltration to prevent
1 1/13mm plaster board 39 condensation that can lead to mould growth. Laboratory tests prove that SIPs maintain
lining on cavity with their full R-value in whole wall testing even
fiberglass insulation G6 airborne and impact when timber splines are used.
1 2/16mm fire rated 51
plasterboard lining direct fix
sound In cases where wall panels or roof panels
Sound reduction (Rw value) of the Formance need to be reinforced with timber splines this
one side
system is sufficient in most residential effectively creates small thermal bridges. This
2/16mm fire rated
implications for compliance with NZBC. If should be calculated in the overall thermal
plasterboard on cavity
higher values are required on specific rating of the area of panel. Table 2 shows the
battens and sound clips.
projects, additional layers of sound insulation R-value of Formance panels with continuous
materials may be added to Formance panels, EPS core. Most projects use SIP splines for
and should be designed by a suitably the connection of panel to panel therefore
qualified acoustic engineer on a project achieve these R values.
Table 2 specific basis. Some examples of possible
SIPs not only serve as a the framing and
solutions are shown on Table 1
FORMANCE PANEL CORE R VALUE insulation material, but also as an air barrier.
THICKNESS THICKNESS For the actual acoustic performance of sound SIP homes have been routinely tested as
115mm 93mm 2.8 insulation layers and systems, refer to the two/three times more airtight than wood
165mm 143mm 4.3 supplier of these products. frame homes with fiberglass insulation.
215mm 193mm 5.7
265mm 243mm 7.2 H1 energy efficiency
315mm 293mm 8.6 The R value of Formance panels increases
with thickness of the panel, due to the
thickness of the EPS core.
Building with Formance panels does not
require any insulation to be installed on site.
There is very little framing timber required to
www.formance.co.nz
8
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
9
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
1. Demand
Determine demand for your final design, by
using NZS3604:2011. All these parameters
will be used in next steps selecting correct
panel thickness, connection details and fixing.
Project demand is driven by location of the
build, exposure and includes determining
wind zone, earthquake zone and snow zone.
Cladding and roofing loading depends on
selection of actual product.
www.formance.co.nz
10
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Loaded dimension
Determine Loaded dimension of defined Roof
areas, following NZS3604:2011.
Loading
Formance roof panels are taking the load of
the external environment (wind and snow)
and also the live load of selected roofing
(light or heavy roofing). There needs to be
min. 37mm bearing of panels on load bearing
elements (walls or beams).
www.formance.co.nz
11
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
#Reinforced Roof
varies depending on the span requirement.
www.formance.co.nz
12
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Demand
In first section of Formance Design Process,
there were all project demands were
defined. Use proposed wall cladding load
and wind load to determine max height (span)
of wall panels. Review also the allowances
listed in the notes below the tables.
Panel Thickness
Reflect the selected thickness of wall panels
in your Floor Framing Plan (fully
dimensioned).
www.formance.co.nz
13
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
14
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
15
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
FBW-C / Corner Nailing Pattern + TWO steel FBW-D / Corner Nailing Pattern + TWO
straps to ONE side of Formance panels steel strap to ONE side of Formance panels
If panels are to be left exposed for direct Two separate straps on external side of the
internal finishing it is desired to avoid visible panel and fixed to timber joist
steel straps on internal side of the panel.
Timber Floor Foundation
Two steel straps on one side of external face
of Formance panel, fixed to timber stud and
under bottom plate.
Concrete Slab/Foundation
www.formance.co.nz
16
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
17
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
#Formance Lintel
7. Lintels
FORMANCE Lintels
Formance lintels are formed using standard
Formance Wall Panel, reinforced with LVL
timber on all edges and min. height of the
panel, in order to achieve desired span.
#Timber Lintel
www.formance.co.nz
18
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
8. Design Checklist
When all the steps are completed, last thing
to do is to review all considerations, using a
Formance Design Checklist. By answering the
questions in the Checklist, the designer can
confirm all decisions are within the scope of
this Design Guide, or clearly list items that are
outside the scope. The list of these items can
then be used to engage a Structural Engineer
and to scope requirements of Engineering
Producer Statement (PS1).
We ask that a completed Checklist is
provided to Formance, prior to applying for
Building Consent.
www.formance.co.nz
19
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
20
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
2
• Roof live load shall not exceed 25 Kg/m
Thermal Formance Roof / No Snow Load - Table 1 • Max heavy Roof (excluding Formance
2
panel) shall not exceed 70 Kg/m
Light Roof (e.g. Steel Heavy Roof (e.g. Tiled Roof)
Sheeting) • Max. Light Roof (excluding Formance
2
panel) shall not exceed 30 Kg/m
Formance™ Panel Max span Max span
Thickness • No Snow load
www.formance.co.nz
21
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
2
● Roof live load shall not exceed 25 Kg/m
● Max heavy Roof (excluding Formance
Thermal Formance Roof / 1kPa Snow Load - Table 2 panel) shall not exceed 70 Kg/m
2
Light Roof (e.g. Steel Heavy Roof (e.g. Tiled Roof) ● Max. Light Roof (excluding Formance
Sheeting) panel) shall not exceed 30 Kg/m
2
Formance™ Panel Max Span Max Span ● Snow load shall not exceed 100kg/m
2
Thickness
● Deflection limit of SPAN/300 or 25mm
115 mm / R2.8 1.1 m 0.8 m
● Max. axial load eccentricity of face of
165 mm / R4.3 1.6 m 1.2 m panel so e=wall thickness/2
www.formance.co.nz
22
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
2
● Roof live load shall not exceed 25 Kg/m
Reinforced Formance Roof / light roof / No Snow Load - Table 3 ● Max heavy Roof (excluding Formance
2
panel) shall not exceed 70 Kg/m
Spline Grade SG8 SG10 LVL11 LVL13 LVL15 GL16
● Max. Light Roof (excluding Formance
Formance™ Spline Size Max span Max span Max span Max span Max span Max span 2
panel) shall not exceed 30 Kg/m
Panel
Thickness ● No snow load
115 mm / R2.8 2/45x90mm 1.8 m 2.0 m 2.3 m 2.4 m 2.5 m 2.8m ● Deflection limit of SPAN/300 or 25mm
● Max. axial load eccentricity of face of
165 mm / R4.3 2/45x140mm 2.8 m 3.1 m 3.5 m 3.7 m 3.9 m 4.4m panel so e=wall thickness/2
● Max. allowable axial load transferred
215 mm / R5.7 2/45x190mm 3.8 m 4.2 m 4.8 m 5.1 m 5.3 m 6.0m through roof Formance panel shall not
exceed 5KN.
265 mm / R7.2 2/45x240mm 4.8 m 5.3 m 6.1 m 6.4m 6.7 m 7.5m ● The table gives max. spans for extra high
wind zone
315 mm / R8.6 2/45x290mm 5.8 m 6.5 m 7.4 m 7.7m 8.0 m 8.7m ● Panel width is 1220mm with
reinforcement at each side
www.formance.co.nz
23
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
2
● Roof live load shall not exceed 25 Kg/m
Reinforced Formance Roof / light roof / 1kPa Snow Load - Table 4
● Max heavy Roof (excluding Formance
2
Spline Grade SG8 SG10 LVL11 LVL13 LVL15 GL16 panel) shall not exceed 70 Kg/m
● Max. Light Roof (excluding Formance
Formance™ Spline Size Max span Max span Max span Max span Max span Max span 2
panel) shall not exceed 30 Kg/m
Panel
Thickness ● Snow load shall not exceed 100kg/m
2
115 mm / R2.8 2/45x90mm 1.6 m 1.8 m 2.1 m 2.2 m 2.3 m 2.4m ● Deflection limit of SPAN/300 or 25mm
● Max. axial load eccentricity of face of
165 mm / R4.3 2/45x140mm 2.6 m 2.9 m 3.3 m 3.5 m 3.6 m 3.7m panel so e=wall thickness/2
215 mm / R5.7 2/45x190mm 3.5 m 3.9 m 4.4 m 4.7 m 4.9 m 5.0m ● Max. allowable axial load transferred
through roof Formance panel shall not
265 mm / R7.2 2/45x240mm 4.4 m 5.0 m 5.6 m 6.0m 6.2 m 6.4m exceed 5KN
● The table gives max. spans for extra high
315 mm / R8.6 2/45x290mm 5.4 m 6.0 m 6.8 m 7.2m 7.5 m 7.7m wind zone
*check with timber supplier if required timber member size is available ● Panel width is 1220mm with
reinforcement at each side
www.formance.co.nz
24
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
2
● Roof live load shall not exceed 25 Kg/m
Reinforced Formance Roof / light roof / 1.5kPa Snow Load - Table 5
● Max heavy Roof (excluding Formance
2
Spline Grade SG8 SG10 LVL11 LVL13 LVL15 GL16 panel) shall not exceed 70 Kg/m
Formance™ Panel Spline Size Max span Max span Max span Max span Max span Max span ● Max. Light Roof (excluding Formance
2
Thickness panel) shall not exceed 30 Kg/m
2
● Snow load shall not exceed 150kg/m
115 mm / R2.8 2/45x90mm 1.5 m 1.7 m 1.9 m 2.0 m 2.1 m 2.2m ● Deflection limit of SPAN/300 or 25mm
165 mm / R4.3 2/45x140mm 2.4 m 2.6 m 3.0 m 3.2 m 3.3 m 3.4m ● Max. axial load eccentricity of face of
panel so e=wall thickness/2
215 mm / R5.7 2/45x190mm 3.2 m 3.6 m 4.1 m 4.3 m 4.5 m 4.6m
● Max. allowable axial load transferred
265 mm / R7.2 2/45x240mm 4.1 m 4.5 m 5.2 m 5.4 m 5.7 m 5.8m through roof Formance panel shall not
315 mm / R8.6 2/45x290mm 4.9 m 5.5 m 6.2 m 6.6 m 6.9 m 7.1m exceed 5KN
● The table gives max. spans for extra high
*check with timber supplier if required timber member size is available
wind zone
● Panel width is 1220mm with
reinforcement at each side
www.formance.co.nz
25
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
2
● Roof live load shall not exceed 25 Kg/m
Reinforced Formance Roof / light roof / 2kPa Snow Load - Table 6 ● Max heavy Roof (excluding Formance
2
Spline Grade SG8 SG10 LVL11 LVL13 LVL15 GL16 panel) shall not exceed 70 Kg/m
Formance™ Spline Size Max Max Max Max Max Max ● Max. Light Roof (excluding Formance
2
Panel span span span span span span panel) shall not exceed 30 Kg/m
Thickness ● Snow load shall not exceed 200kg/m
2
115 mm / R2.8 2/45x90mm 1.4 m 1.6 m 1.8 m 1.9 m 2.0 m 2.0m ● Deflection limit of SPAN/300 or 25mm
165 mm / R4.3 2/45x140mm 2.2 m 2.4 m 2.8 m 2.9 m 3.1 m 3.2m ● Max. axial load eccentricity of face of
panel so e=wall thickness/2
215 mm / R5.7 2/45x190mm 3.0 m 3.3 m 3.8 m 4.0 m 4.2 m 4.3m
● Max. allowable axial load transferred
265 mm / R7.2 2/45x240mm 3.8 m 4.2 m 4.8 m 5.1 m 5.3 m 5.4m through roof Formance panel shall not
315 mm / R8.6 2/45x290mm 4.6 m 5.1 m 5.8 m 6.2m 6.5 m 6.6m exceed 5KN
● The table gives max. spans for extra high
*check with timber supplier if required timber member size is available
wind zone
● Panel width is 1220mm with
reinforcement at each side
www.formance.co.nz
26
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
2
● Roof live load shall not exceed 25 Kg/m
Reinforced Formance Roof / heavy roof / No Snow Load - Table 7
● Max heavy Roof (excluding Formance
2
Spline Grade SG8 SG10 LVL11 LVL13 LVL15 GL16 panel) shall not exceed 70 Kg/m
Formance™ Spline Size Max Max Max Max Max Max ● Max. Light Roof (excluding Formance
2
Panel Thickness span span span span span span panel) shall not exceed 30 Kg/m
115 mm / R2.8 2/45x90mm 1.5 m 1.6 m 1.9 m 2.0 m 2.1 m 2.3m ● No snow load
165 mm / R4.3 2/45x140mm 2.3 m 2.6 m 2.9 m 3.1 m 3.2 m 3.6m ● Deflection limit of SPAN/300 or 25mm
● Max. axial load eccentricity of face of
215 mm / R5.7 2/45x190mm 3.1 m 3.5 m 4.0 m 4.2 m 4.4 m 5.0m
panel so e=wall thickness/2
265 mm / R7.2 2/45x240mm 4.0 m 4.4 m 5.0 m 5.3 m 5.6 m 6.3m ● Max. allowable axial load transferred
through roof Formance panel shall not
315 mm / R8.6 2/45x290mm 4.8 m 5.4 m 6.1 m 6.4 m 6.8 m 7.6m
exceed 5KN
*check with timber supplier if required timber member size is available ● The table gives max. spans for extra high
wind zone
● Panel width is 1220mm with
reinforcement at each side
www.formance.co.nz
27
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
2
● Roof live load shall not exceed 25 Kg/m
Reinforced Formance Roof / heavy roof / 1kPa Snow Load - Table 8
● Max heavy Roof (excluding Formance
2
Spline Grade SG8 SG10 LVL11 LVL13 LVL15 GL16 panel) shall not exceed 70 Kg/m
Formance™ Spline Size Max Max Max Max Max Max ● Max. Light Roof (excluding Formance
2
Panel span span span span span span panel) shall not exceed 30 Kg/m
Thickness 2
● Snow load shall not exceed 100kg/m
115 mm / R2.8 2/45x90mm 1.5 m 1.6 m 1.9 m 2.0 m 2.1 m 2.2m ● Deflection limit of SPAN/300 or 25mm
165 mm / R4.3 2/45x140mm 2.3 m 2.6 m 2.9 m 3.1 m 3.2 m 3.4m ● Max. axial load eccentricity of face of
panel so e=wall thickness/2
215 mm / R5.7 2/45x190mm 3.1 m 3.5 m 4.0 m 4.2 m 4.4 m 4.6m
● Max. allowable axial load transferred
265 mm / R7.2 2/45x240mm 4.0 m 4.4 m 5.0 m 5.3 m 5.6 m 5.8m through roof Formance panel shall not
315 mm / R8.6 2/45x290mm 4.8 m 5.4 m 6.1 m 6.4 m 6.8 m 7.1m exceed 5KN
● The table gives max. spans for extra high
*check with timber supplier if required timber member size is available
wind zone
● Panel width is 1220mm with
reinforcement at each side
www.formance.co.nz
28
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
2
● Roof live load shall not exceed 25 Kg/m
Reinforced Formance Roof / heavy roof / 1.5kPa Snow Load - Table 9
● Max heavy Roof (excluding Formance
2
Spline Grade SG8 SG10 LVL11 LVL13 LVL15 GL16 panel) shall not exceed 70 Kg/m
Formance™ Spline Size Max span Max span Max span Max span Max span Max span ● Max. Light Roof (excluding Formance
2
Panel panel) shall not exceed 30 Kg/m
Thickness 2
● Snow load shall not exceed 150kg/m
115 mm / R2.8 2/45x90mm 1.4 m 1.6 m 1.8 m 1.9 m 2.0 m 2.0m
● Deflection limit of SPAN/300 or 25mm
165 mm / R4.3 2/45x140mm 2.2 m 2.4 m 2.8 m 2.9 m 3.1 m 3.2m
● Max. axial load eccentricity of face of
215 mm / R5.7 2/45x190mm 3.0 m 3.3 m 3.8 m 4.0 m 4.2 m 4.3m panel so e=wall thickness/2
265 mm / R7.2 2/45x240mm 3.8 m 4.2 m 4.8 m 5.1 m 5.3 m 5.4m ● Max. allowable axial load transferred
through roof Formance panel shall not
315 mm / R8.6 2/45x290mm 4.6 m 5.1 m 5.8 m 6.2 m 6.5 m 6.6m exceed 5KN
*check with timber supplier if required timber member size is available ● The table gives max. spans for extra high
wind zone
www.formance.co.nz
29
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
2
● Roof live load shall not exceed 25 Kg/m
Reinforced Formance Roof / heavy roof / 2kPa Snow Load - Table 10
● Max heavy Roof (excluding Formance
2
Spline Grade SG8 SG10 LVL11 LVL13 LVL15 GL16 panel) shall not exceed 70 Kg/m
Formance™ Spline size Max Max Max Max Max Max ● Max. Light Roof (excluding Formance
2
Panel span span span span span span panel) shall not exceed 30 Kg/m
Thickness 2
● Snow load shall not exceed 200kg/m
115 mm / R2.8 2/45x90mm 1.3 m 1.5 m 1.7 m 1.8 m 1.9 m 1.9m
● Deflection limit of SPAN/300 or 25mm
165 mm / R4.3 2/45x140mm 2.1 m 2.3 m 2.6 m 2.8 m 2.9 m 3.0m ● Max. axial load eccentricity of face of
215 mm / R5.7 2/45x190mm 2.8 m 3.2 m 3.6 m 3.8 m 4.0 m 4.1m panel so e=wall thickness/2
● Max. allowable axial load transferred
265 mm / R7.2 2/45x240mm 3.7 m 4.0 m 4.5 m 4.8 m 5.0 m 5.1m
through roof Formance panel shall not
315 mm / R8.6 2/45x290mm 4.3 m 4.8 m 5.5 m 5.8 m 6.1 m 6.2m exceed 5KN
*check with timber supplier if required timber member size is available ● The table gives max. spans for extra high
wind zone
● Panel width is 1220mm with
reinforcement at each side
www.formance.co.nz
30
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
31
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
2
• Roof live load not exceed 25kg/m
Top or Single Storey / Light or Heavy Roof - Table 11
Max Panel 2.4m 2.7m 3.0m 3.6m 4.2m 4.8m • Max. heavy roofing (excluding
Height Formance) shall not exceed 60kg/m
2
www.formance.co.nz
32
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
2
• Roof live load not exceed 25kg/m
Lower of two storey / Light or Heavy Roof - Table 12
Max Panel 2.4m 2.7m 3.0m 3.6m • Max. heavy roofing (excluding
Height Formance) shall not exceed 60kg/m
2
www.formance.co.nz
33
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Subfloor beneath two storey / Light or Heavy Roof - Table 13 • Max. heavy roofing (excluding
2
Formance) shall not exceed 60kg/m
Max Panel Height 2.4m 2.7m 3.0m
Wind zone Loaded Dimension Panel thickness Panel thickness Panel thickness • Max. light roofing (excluding Formance)
2
Extra High 2m 115mm 115mm 165mm shall not exceed 20kg/m
4m 115mm 115mm 165mm 2
6m 115mm 115mm 165mm • Snow load shall not exceed 200kg/m
Very High 2m 115mm 115mm 115mm
• Deflection limit of SPAN/180 or 15mm
4m 115mm 115mm 115mm
6m 115mm 115mm 115mm • Max axial load eccentricity on face of
High 2m 115mm 115mm 115mm panels so e=wall thickness/2
4m 115mm 115mm 115mm
6m 115mm 115mm 115mm • Medium wall cladding (excluding
2
Medium 2m 115mm 115mm 115mm Formance) shall not exceed 80kg/m
4m 115mm 115mm 115mm • Loaded dimension is roof loaded
6m 115mm 115mm 115mm dimension, a 5.2m joist span is allowed
Low 2m 115mm 115mm 115mm for the floor load. A floor liver load of
4m 115mm 115mm 115mm 2kPa is allowed for.
6m 115mm 115mm 115mm
Internal 2m 115mm 115mm 115mm • The upper wall and lower walls has
4m 115mm 115mm 115mm been allowed as 2.7m high with medium
6m 115mm 115mm 115mm weight cladding
www.formance.co.nz
34
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Cap plate
www.formance.co.nz
35
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
36
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Cap Plate upper/single storey - 45mm roof framing at 1200mm crs. ● Applies for roof elements, such as rafters, spaced and
no greater than 900mm crs with a minimum width of
- Table 15 45mm width
Wind Up to High Very High Extra High ● Fasteners of OSB facing board to top plate to be 2.87
x 65mm FH ring shank nails at 150crs
LD(m) 2 4 6 2 4 6 2 4 6 ● Max Roof pitch 45 degrees
<1kPa Light 0 45 SED 45 SED SED 45 SED SED ● No snow load shedding (NZS3604:2011 clause 15.3)
1.5kPa Light 18 45 SED 45 SED SED 45 SED SED ● Table valid for thermal Formance wall panel
Heavy 18 SED SED 18 SED SED 45 SED SED ● Fixing of Cap to Top plate with 4.8dia screws at
300mm crs., fully embedded
2kPa Light 18 SED SED 45 SED SED 45 SED SED ● Uniform loading and bearing of OSB facing is required.
Heavy 45 SED SED 45 SED SED 45 SED SED ● Durability, including treatment of fasteners, is to
comply with NZBC
www.formance.co.nz
37
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
38
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Cap Plate upper or single storey – 90mm roof framing at 1200mm ● Applies for roof elements, such as trusses and rafters,
spaced and no greater than 1200mm crs with a
crs. CONTINUOUS BOUNDARY RAFTER - Table 17 minimum of 90mm width
Wind Up to High Very High Extra High ● 45mm SG8 (min.) Boundary Rafter/Plate continuous
between 2 roof rafters/trusses with connection to top
LD(m) 2 4 6 2 4 6 2 4 6 plate required.
2kPa Light 0 45 SED 0 45 SED 0 45 SED ● Table valid for thermal Formance wall panel
www.formance.co.nz
39
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
● Table vaild for floor joists at 600mm crs. Max. and min
width of 45mm and boundary plate or full depth
Cap Plate Lower of the two storey Floor and light weight cladding blocking
<1kPa Light 18 45 SED 18 45 SED 18 45 SED ● Top&Cap plate to have continuity fixing to
NZS3604:2011.
Heavy 45 SED SED 45 SED SED 45 SED SED ● Table valid for thermal Formance wall panel
1.5kPa Light 18 45 SED 18 45 SED 18 45 SED ● Fixing of Cap to Top plate with 4.8dia screws at
300mm crs., fully embedded
Heavy 45 SED SED 45 SED SED 45 SED SED
● Uniform loading and bearing of OSB facing is required.
2kPa Light 18 45 SED 18 45 SED 18 45 SED ● Durability, including treatment of fasteners, is to
comply with NZBC
Heavy 45 SED SED 45 SED SED 45 SED SED
● Equilibrium Moisture content of SIP and all timber
components is to be <18%
www.formance.co.nz
40
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
● Table vaild for floor joists at 600mm crs. Max. and min
width of 45mm and boundary plate or full depth
Cap Plate Lower of the two storey / Floor and medium weight blocking
<1kPa Light 45 SED SED 45 SED SED 45 SED SED ● Top&Cap plate to have continuity fixing to
NZS3604:2011.
Heavy 45 SED SED 45 SED SED 45 SED SED ● Table valid for thermal Formance wall panel
1.5kPa Light 45 SED SED 45 SED SED 45 SED SED ● Fixing of Cap to Top plate with 4.8dia screws at
300mm crs., fully embedded
Heavy 45 SED SED 45 SED SED 45 SED SED
● Uniform loading and bearing of OSB facing is required.
2kPa Light 45 SED SED 45 SED SED 45 SED SED
● Durability, including treatment of fasteners, is to
comply with NZBC
Heavy 45 SED SED 45 SED SED 45 SED SED
● Equilibrium Moisture content of SIP and all timber
components is to be <18%
www.formance.co.nz
41
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Formance Bracing
www.formance.co.nz
42
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
43
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Types of Hold Down Fixing FBW-A / Corner Nailing Pattern + FBW-B / Corner Nailing Pattern +
There are various types of hold down, that contribute to no hold down ONE steel strap, BOTH sides of
different bracing capacity of the same Formance panels. Corner nailing pattern at both ends of each Formance panels
bracing unit. For higher bracing capacity
Nailing pattern: 50-50-50-75-75-150-150- One continuous strap under the bottom plate
and up both sides of the panel
Concrete Slab/Foundation
Any foundation
www.formance.co.nz
44
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
45
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
46
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Wall Cladding - Table 21 • NZS3604 scope and terminology applies. • R<1, where R=average height divided
WEIGHT WIND H IGH V ERY H E XTRA H by smaller of width/length.
• Max. Roof Pitch is 45deg.
L IGHT A B C • Fixing to be 4mm dia. screw fixing (10
M EDIUM B B C • Max EQ zone for Heavy cladding is 2, with gauge) fully threaded and embedded.
H EAVY D D D cladding maximum 3.6m high.
Spacing Direction • Durability including fasteners is to be
• Equilibrium Moisture Content of SIP and all to the requirements of the NZBC.
M2 900 600 450 300 Square timber components is to be <18%
A 287 430 574 861 508 • External weathering system is to be
#Cladding Fixing
B 222 333 444 667 447 to the requirements of the NZBC.
C 184 275 367 551 407
#Roofing Fixing
D 154 232 309 463 373
Roofing - Table 22
L OCATION WIND H IGH V ERY H E XTRA H
G ENERAL A B C
C ORNER * D E F Spacing Direction
S PACING DIRECTION
M2 900 600 450 300 Square
A 207 311 414 622 432 Spacing Direction
B 160 241 321 481 380
C 133 199 265 398 346
Fixing Crs.
D 138 207 276 414 353
E 107 160 214 321 310
F 88 133 177 265 282 Fixing Crs.
*Corner when fixing within ‘A’ of 2 edges
‘A’ = smaller of 0.2 x width / 0.2 x length / average height
Refer #Corner Fixing
www.formance.co.nz
47
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
#Corner Fixing
www.formance.co.nz
48
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Formance Lintel
www.formance.co.nz
49
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
4.0 2.5 3.5 4.7 ● Lintel deflection limit is span/300, with span/200 for
wind case but never exceeding 12mm
6.0 2.2 3.1 4.3 ● Designed for Formance box beam with 11mm thick
OSB webs and LVL13 for the flanges
Heavy Roof 2.0 2.8 3.8 5.1 ● Snow Load shall not exceed 100kg/m2
www.formance.co.nz
50
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Lintel supporting roof and wall for all wind zones - Table 25 ● Assumed 50% of the bending and shear deflection
should be taken for nail slip
Loaded Dimension 200mm deep 300mm deep 500mm
of Lintel deep ● Roof live load shall not exceed 25kg/m2
Light Roof 2.0 2.7 3.8 5.0 ● Max heavy roof shall not exceed 75kg/m2
Light Wall 3.0 2.5 3.5 4.7
4.0 2.3 3.3 4.5 ● Max. light roof shall not exceed 35kg/m2
6.0 2.1 2.9 4.1 ● Lintel deflection limit is span/300, with span/200 for
Light Roof 2.0 2.5 3.5 4.7 wind case but never exceeding 12mm
Medium wall 3.0 2.4 3.3 4.5
● Designed for Formance box beam with 11mm thick
4.0 2.2 3.1 4.3 OSB webs and LVL13 for the flanges
6.0 2.0 2.8 4.0
● Snow load shall not exceed 100kg/m2
Heavy Roof 2.0 2.4 3.4 4.6
Light Wall 3.0 2.2 3.2 4.4 ● Spans shown are for extra high wind
4.0 2.1 2.9 4.2 ● Spans shown are for all thicknesses of panel
6.0 1.9 2.6 3.8
Heavy roof 2.0 2.2 3.4 4.3 ● Wall height above lintel was taken as 2.4m high
Medium Wall 3.0 2.1 2.9 4.1 ● Light wall cladding not exceeding 40kg/m2
4.0 1.9 2.7 3.9
● Medium wall cladding not exceeding 80kg/m2
6.0 1.8 2.5 3.7
www.formance.co.nz
51
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
52
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
53
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
APPOINTED ENGINEER
www.formance.co.nz
54
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
a. Timber lintel sizes and fixing Because Formance Panels are a solid
element, that fully encapsulates the bottom
b. Wall Panel fixing plate when slotted over, the inspection of
bottom plates has to occur prior to erection of
c. Roof Panel fixing
Formance wall panels.
5. Building and Sill Wrap or Cavity
Bottom plates are fixed to foundation
Batten
following NZS3604:2011 requirements or to
6. Flashings Specific Engineering Design (SED).
www.formance.co.nz
55
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
56
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Panel Inspection
#Straps example
#Timber Lintel
• Inspect sizes, fixing and locations of lintels.
Leave Timber lintels exposed (do not install
the header Formance panel, until inspection
is completed).
www.formance.co.nz
57
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
www.formance.co.nz
58
© Method Building Systems 2017 - V1.1 (20180626)
Design Guide Performance Forever
Wall Details
www.formance.co.nz
59
© Method Building Systems 2017 - V1.1 (20180626)
DETAIL TO BE READ IN CONJUNCTION WITH
FD-RO-WA-01/08
[Formance Roof panel secured with Formance Screws
see detail for fixing specifications]
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE WALL PANEL
45mm BOTTOM PLATE FIXED TO
SIPS PANEL WITH 60mm NAILS @
150 CRS EACH SIDE
BOTTOM PLATE FIXED
AS PER NZS:3604
16mm Fyreline Gib both side of
Formance SIP wall
[as per manufacturers specification]
45mm BOTTOM PLATE ON
18mm (MIN.) H3.2 SG
PLYWOOD BOTTOM PLATE,
ON DPC.
FOUNDATION BY OTHERS
LEGEND 16mm Fyreline Gib is fixed vertically over Formance panels with
sheet joints at the same location as the panel joints, using
EXPANDING FOAM 41mm Gib Grabber HT drywall screws, at 300mm crs., along
ADHESIVE the edges and along the sheet center line.
NOTES All screws heads are stopped and all sheet joints taped and
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE stopped in accordance with the Gib Site Guide, noting that no
stopping is required under a cladding and drained cavity
2. CAVITY FIXED CLADDING NOT SHOWN FOR CLARITY system.
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE WALL PANEL 3 mm GAP
EXTERIOR
INTERIOR
SPLINE FIXED TO FORMANCE PANEL FORMANCE SIPS TAPE
WITH 45mm NAILS @ 150mm CRS.
EACH SIDE
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
90mm NAILS @ 300 CRS 3mm GAP
EXTERIOR
INTERIOR
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE WALL PANEL
EXTERIOR INTERIOR
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
INTERIOR FORMANCE TAPE
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
EXTERIOR
INTERIOR
FORMANCE WALL PANEL
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
EXTERIOR
INTERIOR
FORMANCE WALL PANEL
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
Design Guide Performance Forever
Roof Details
www.formance.co.nz
69
© Method Building Systems 2017 - V1.1 (20180626)
Version Number:
01
LEGEND
EXPANDING FOAM
ADHESIVE
FD-RO-RO
REINFORCED ROOF PANELS
TIMBER SPLINE (as per roof panel span table)
Drawing Number:
NOTES
FIXED TO FORMANCE PANEL
1. ALL TIMBER FRAMING WITH 60mm NAILS @ 150mm CRS.
MIN H1.2 TR SG8 GRADE EACH SIDE
12/06/17
NOT SHOWN FOR CLARITY
3. INTERNAL LINING
Date:
NOT SHOWN FOR
CLARITY
1:5
90mm NAILS @ 300 CRS
TITLE:
Scale:
FORMANCE SIPS TAPE [inside only]
3. INTERNAL LINING
NOT SHOWN FOR
CLARITY
©
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING
MIN H1.2 TR SG8 GRADE 3mm GAP
SPLINE FIXED TO FORMANCE PANEL WITH
40mm NAILS @150 mm CRS.
2. CAVITY FIXED CLADDING FORMANCE SCREWS WITH LOAD
NOT SHOWN FOR CLARITY SPEADING WASHER @ 300CRS.
WITH min. 40mm EMBEDMENT IN
3. INTERNAL LINING TIMBER BEAM
NOT SHOWN FOR
CLARITY
FORMANCE TAPE
INSIDE ONLY
©
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING
MIN H1.2 TR SG8 GRADE SPLINE FIXED TO FORMANCE PANEL WITH 3mm GAP
40mm NAILS @150 mm CRS.
2. CAVITY FIXED CLADDING FORMANCE SCREWS WITH LOAD
NOT SHOWN FOR CLARITY SPEADING WASHER @ 300CRS.
WITH min. 40mm EMBEDMENT IN
3. INTERNAL LINING TIMBER BEAM
NOT SHOWN FOR
CLARITY
FORMANCE TAPE
INSIDE ONLY
DHS 250 WITH 45x90mm
TIMBER BLOCKING
©
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING TIMBER BLOCKING INFILL,
MIN H1.2 TR SG8 GRADE FIXED TO SIPS PANEL WITH
60mm NAILS @ 150mm CRS.
2. CAVITY FIXED CLADDING EACH SIDE
NOT SHOWN FOR CLARITY
2 x M12 COACH SCREWS @
3. INTERNAL LINING 300mm CRS
NOT SHOWN FOR
CLARITY
FORMANCE THERMAL
ROOF PANEL
BEAM AND FIXING TO SED
©
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING
MIN H1.2 TR SG8 GRADE RIDGE BEAM
(by others)
2. CAVITY FIXED CLADDING
NOT SHOWN FOR CLARITY FORMANCE ROOF PANEL
un-reinforced / thermal
FORMANCE TAPE
(inside only)
©
45mm PLATE FIXED TO
FORMANCE PANELS WITH 60mm
NAILS @150mm CRS. EACH SIDE
LEGEND
EXPANDING FOAM
ADHESIVE FORMANCE SCREWS WITH LOAD
SPREADING WASHER @ 300CRS.
NOTES WITH 40mm EMBEDMENT IN TIMBE
PLATE OF ADJOINING ROOF PANEL.
1. ALL TIMBER FRAMING
MIN H1.2 TR SG8 GRADE
3. INTERNAL LINING
NOT SHOWN FOR
CLARITY
©
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING
MIN H1.2 TR SG8 GRADE
FORMANCE
SIPS TAPE
RIDGE BEAM (by others)
beam can be positioned higher
to not be visible internally
©
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING
MIN H1.2 TR SG8 GRADE FORMANCE SCREWS @ 300CRS.
60mm NAILS @150MM CRS. WITH 40mm EMBEDMENT IN TIMBER
2. CAVITY FIXED CLADDING RIDGE BEAM
NOT SHOWN FOR CLARITY LOAD SPREAD WASHER WHEN
TIMBER SPLINE >50mm FROM STRUCTURAL SPLINE
3. INTERNAL LINING
NOT SHOWN FOR FORMANCE REINFORCED ROOF PANEL
CLARITY ensure min. 37mm
bearing of timber spline
©
LEGEND
EXPANDING FOAM
ADHESIVE FORMANCE SCREWS @ 300CRS.
WITH 40mm EMBEDMENT IN TIMBER
NOTES RIDGE BEAM
LOAD SPREAD WASHER WHEN
1. ALL TIMBER FRAMING >50mm FROM STRUCTURAL SPLINE
MIN H1.2 TR SG8 GRADE 60mm NAILS @150MM CRS.
FORMANCE
SIPS TAPE
RIDGE BEAM
BLOCKING and FIXING
(by others)
©
FORMANCE SCREWS @ 300CRS.
60mm nails @ 150mm crs. WITH 40mm EMBEDMENT IN TIMBER
RIDGE BEAM
LOAD SPREAD WASHER WHEN
>50mm FROM STRUCTURAL SPLINE
SED alternative connection
1 Multigrip bracket connecting timber
spline with level ridge beam
FORMANCE
SIPS TAPE
FORMANCE ROOF PANEL
reinforced
RIDGE BEAM
(by others)
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE SCREWS WITH LOAD
SPREAD WASHER @ 300mm CRS WITH
40mm EMBEDMENT IN TOP PLATE OF
WALL PANEL BELOW
45mm PLATE FIXED TO FORMANCE FORMANCE ROOF PANEL
PANELS WITH 60mm NAILS @150mm CRS. ensure min. 37mm bearing
EACH SIDE
FORMANCE TAPE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
3/90mm nails @ 300crs.
FORMANCE ROOF PANEL
un-reinforced / thermal roof
Long Formance Screws @300mm crs
use load spreading washer when
2/45mm VALLEY BEAMS more than 50mm from timber insert
[BY OTHERS]
FORMANCE TAPE
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
VALLEY BEAM embeded inside the Formance panel.
Design and span by others (NZS3604:2011 or SED)
45mm PLATE FIXED TO UPPER ROOF PANEL WITH
3/SCREWS @ 300mm CRS.
TIMBER WEDGE TO
ACCOMMODATE PITCH CHANGE.
TO BE CONTINUOUS
FORMANCE TAPE
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
TIMBER PLATE (not continuous)
TIMBER SPLINE
to the edge of the panel
to achieve min. 37mm bearing FORMANCE REINFORCED ROOF
on timber blocking Fixed with Long Formance Screws
with load speading washer
@300mm crs.
VALLEY BEAM
Min. 40mm embedment in timber beam
and BLOCKING FIXING
by SED
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
SED DETAIL
TIMBER SPLINE fixed to trimmer
with one multigrip [by others]
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE SCREWS WITH
LOAD SPREADING WASHER
@ 300 CRS WITH 40mm EMBEDMENT
IN TOP PLATE
max. 31 overhang, 23 backspan in span direction
max. 1300mm
max. 600mm in opposite direction FORMANCE ROOF PANEL
LEGEND
EXPANDING FOAM
ADHESIVE 45mm END PLATE FIXED TO FORMANCE
PANEL WITH 60mm NAILS @ 150mm CRS.
NOTES EACH SIDE
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE SCREWS WITH
LOAD SPREADING WASHER @ 300mm CRS.
WITH 40mm EMBEDMENT IN
TOP PLATE
EAVES WIDTH BY OTHERS
FORMANCE TAPE
TIMBER CAPPING TO WIDTH OF
PANEL (CONTINUOUS)
2/90mm NAILS @300crs.
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
max. 31 overhang, 32 backspan in span direction
max. 1300mm
max. 600mm in opposite direction
45mm END PLATE FIXED TO FORMANCE
PANEL WITH 60mm NAILS @ 150
CRS EACH SIDE
CAP PLATE
TO WIDTH OF PANEL, TO BE
CONTINUOUS
2/90mm framing nails @300mm crs.
LEGEND FORMANCE
TAPE 45mm TOP PLATE FIXED TO
EXPANDING FOAM
FORMANCE PANEL WITH 60mm
ADHESIVE NAILS @ 150mm CRS.
EACH SIDE
NOTES FORMANCE
WALL PANEL
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
EAVES WIDTH
(by others)
TIMBER FRAMED EAVES (by others)
CAP PLATE
TO WIDTH OF PANEL, TO BE
CONTINUOUS
2/90mm framing naisl @300mm crs.
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
©
FORMANCE SCREWS WITH LOAD
SPREAD WASHER
@ 300mm CRS. WITH 40mm
EMBEDMENT IN TOP PLATE
Formance Tape
CAP PLATE
TO WIDTH OF PANEL, TO BE
CONTINUOUS
2/90mm framing naisl @300mm crs.
LEGEND
EXPANDING FOAM
ADHESIVE 45mm END PLATE FIXED TO FORMANCE
PANEL WITH 60mm NAILS @ 150mm CRS.
NOTES EACH SIDE
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE SCREWS WITH
EAVES WIDTH (by others) LOAD SPREAD WASHER
@300mm CRS.
WITH 40mm EMBEDMENT IN
TOP PLATE
Formance Tape
CAP PLATE
TO WIDTH OF PANEL, TO BE
CONTINUOUS
2/90mm framing naisl @300mm crs.
LEGEND
EXPANDING FOAM
ADHESIVE TIMBER FRAMED EAVES (by others)
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE SCREWS WITH
EAVES WIDTH(by others)
LOAD SPREAD WASHER
@300mm CRS.
WITH 40mm EMBEDMENT IN
TOP PLATE
FORMANCE ROOF PANEL
Formance Tape
CAP PLATE
TO WIDTH OF PANEL, TO BE
CONTINUOUS
2/90mm framing naisl @300mm crs.
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
©
©
FORMANCE 300mm SCREWS @ 300
CRS WITH 40mm EMBEDMENT IN
TOP PLATE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE 300mm SCREWS
@ 300mm CRS. WITH 40mm
EMBEDMENT IN TOP PLATE
FORMANCE TAPE
LEGEND
EXPANDING FOAM FORMANCE WALL PANEL
ADHESIVE OR TIMBER FRAMED INTERNAL
LOAD BEARING WALL
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
TRUSS DESIGNED BY
TRUSS MANUFACTURER
2 screws each side of the truss
and 2@300mm crs.
TRUSS FIXING TO
TRUSS MANUFACTURER
(Steel Straps or Steel Brackets)
CAP PLATE
full with of Formance panel
2/90mm framing nails
@300mm crs.
Top plate
FORMANCE
LEGEND WALL PANEL
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
TRUSSES and FIXING of TRUSSES TO TOP PLATE
DESIGNED BY TRUSS ENGINEER
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
©
Design Guide Performance Forever
Foundation Details
www.formance.co.nz
101
© Method Building Systems 2017 - V1.1 (20180626)
FORMANCE OSB SIPS
WALL PANEL 45mm BOTTOM PLATE FIXED TO
SIPS PANEL WITH 60mm NAILS (2.8Ø)@
150 CRS EACH SIDE
BOTTOM PLATE H3.2
FIXED AS PER NZS:3604
FORMANCE TAPE
FOUNDATION BY OTHERS
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE WALL PANEL 45mm PLATE FIXED TO SIPS PANEL
WITH 60mm NAILS @ 150mm CRS.
EACH SIDE
Fixing to NZS3604
FORMANCE SIPS TAPE
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE
WALL PANEL
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE WALL PANEL
45mm BOTTOM PLATE MSG8 H3.2
fixed to timber sub-floor
Plywood Structural Flooring min
2/FORMANCE SCREWS to joists 12mm / T&G flooring / 11mm OSB
@max.800mm 40mm embedment in board
timber joists [to strengthen panels for point
loads]
Flooring Screw @150mm crs. to
timber joists before fixing following FORMANCE FLOOR PANEL
panel. on top of timber joists
fixed with Formance Screws and
load spreading washer
to timber joists @600mm crs.
PROPRIATRY CAVITY CLADDING 40mm embedment in joists
[to comply with NZBC E2]
[by others]
Timber Floor to NZS3604 or SED
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
Design Guide Performance Forever
Floor Details
www.formance.co.nz
106
© Method Building Systems 2017 - V1.1 (20180626)
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING
MIN H1.2 TR SG8 GRADE
©
LEGEND
EXPANDING FOAM 45mm BOTTOM PLATE H3.2
ADHESIVE
2 / 14G screws
one side of Joist, before installing
next panel
FORMANCE
WALL PANEL
©
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
45mm Bottom plate H3.2
2. CAVITY FIXED CLADDING NOT SHOWN FOR CLARITY
Fixing to NZS3604:2011
3. INTERNAL LINING NOT SHOWN FOR CLARITY
45mm CAP PLATE [to width of the panel]
Fixing to top plate with
1/ Formance Screw @300mm crs.
2/ 90mm framing nails @300mm crs.
Formance Tape
Midfloor joists on
Top-flange Metal Hangers
[by others]
©
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
Formance tape
Midfloor joists on
Metal Hangers
[by others]
©
Design Guide Performance Forever
Bracing Details
www.formance.co.nz
111
© Method Building Systems 2017 - V1.1 (20180626)
LEGEND
EXPANDING FOAM CAP PLATE CONTINUOUS AS TOP PLATE TIMBER TOP PLATE FIXED TO
APPLICABLE CONTINUOUS FORMANCE
50 50 50 75 75 150 150
ADHESIVE PANEL WITH 60mm NAILS EACH
SIDE @ SPACINGS AS OTHERSIDE
NOTES
75 75 50 50 50
1. ALL TIMBER FRAMING
MIN H1.2 TR SG8 GRADE
TIMBER STUD FIXED TO FORMANCE
150
2. CAVITY FIXED CLADDING PANEL WITH 60mm NAILS EACH
SIDE @ SPACINGS AS OTHERSIDE
NOT SHOWN FOR CLARITY
150
3. INTERNAL LINING
NOT SHOWN FOR
CLARITY
©
FBW-B 600 x 25 x 1mm Galvanised Steel Straps
using 50x2.80mm flat head Galv Fibre cement nails -
strap centered to stud, taken under the bottom plate and up
150mm each side of the stud Apply this hold-down detail at each
3 nails each side bottom plate & 6 nails to stud - both sides end of bracing unit.
STRAP FIXED OVER FORMANCE PANEL
Bracing capacities vary with
CONTINUOUS BOTTOM PLATE thickness of panels and hold-down
detail.
FBW-C
2 / 200 x 25 x 1mm Galvanised Steel Straps
on ONE side of panel
using 50x2.80mm flat head Galv Fibre cement nails -
1st strap right at edge, second beside.
6 nails to underside of bottom plate prior to installation
3 nails to bottom plate & 6 nails to stud - both straps
STRAPS FIXED OVER FORMANCE PANEL
CONTINUOUS BOTTOM PLATE
BOUNDARY JOIST IN
TIMBER SUB FLOOR
©
(by others)
Design Guide Performance Forever
Lintel Details
www.formance.co.nz
114
© Method Building Systems 2017 - V1.1 (20180626)
90mm NAILS @ 300 CRS
TIMBER BLOCKING
FORMANCE PANEL 3mm GAP
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
ADJOINING FORMANCE SIPS WALL PANEL,
panel extend shown hatched
Formance screw 6' through top of lintel
into the stud
CAP PLATE [full width of the wall panel]continuous
TOP PLATE continuous
DOUBLING STUD
FIXED TO TRIMMING STUD AS
PER NZS:3604
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
FORMANCE WALL PANEL
WITH REBATED EPS CORE FOR
WINDOW LINTEL
ENGINEER or NZS3604
LINTEL TO STRUCTURAL ENGINEER'S
SPECIFICATIONS WITH OSB
FACING
SCREWS 2/2.8Ø@300crs.
LEGEND
EXPANDING FOAM
ADHESIVE
NOTES
1. ALL TIMBER FRAMING MIN H1.2 TR SG8 GRADE
©
3. INTERNAL LINING NOT SHOWN FOR CLARITY
ADJOINING FORMANCE
SIPS WALL PANEL, CUT TO FIT THE LINTEL PANEL
Formance screw 6' through top of lintel
into the stud
CAP PLATE [full width of the wall panel]
continuous
LVL13 Flange
FORMANCE LINTEL
[boxed beam OSB sheets and LVL flanges]
span as per lintel span tables
note:
LINTEL HEIGHT
Nailed to timber with Dia.2.8mm, flat head,
ring shank galv. 60mm nail @ 150mm crs.
LVL13 Flange
DOUBLING STUD
WELL NAILED TO TRIMMING STUD INSIDE
FORMANCE PANEL
©
Design Guide Performance Forever
www.formance.co.nz
119
© Method Building Systems 2017 - V1.1 (20180626)
PIPE FOAMED IN PLACE
WITH LOW EXPANSION
PU FOAM BOTH SIDE OF THE PANEL
PIPE SEALED WITH BOND PENETRATION MUST HAVE
BREAKER/SILICONE/ MIN. 5' SLOPE OUTWARDS
FLASHING TAPE
Exterior Interior
©
SURFACE MOUNTED PLUMBING IN CAVITY
NOTES:
CONSIDER PLUMBING FITTING
DIMENSIONS WHEN SELECTING
BATTEN THICKNESS
FD-WA-PL
THE SAME PRINCIPAL CAN BE
USED FOR ELECTRICAL WIRING
©
©
Design Guide Performance Forever