Installation Qualification(IQ) Tests:
1. Control System Architecture Layout This defines the architecture of the entire
Software (it includes flow starting from PLC, I/O
Module, Network switch, Communication
Adapter, Power Module, IPC connections and
HMI Monitor
2. Verification of Control System Hardware This Includes the following, but not limited to:
and Software (Make, Model, Quantities)
PLC
Communication Adapter
Digital Input Module
Digital Output Module
Analog Input Module
RTD Module
Power Module
Network Switch
IPC
HMI/Monitor
Others
3. Verification of IPC Hardware & This Includes the following, but not limited to:
Software configurations and Back up (Record the ‘Observed Value’ w.r.t ‘Specified
details Value):
1) IPC Specifications:
Operating System (name/version)
Processor
RAM
System Type
Hard Disk
2) SCADA Specifications:
Application software name (e.g. Zenon)
Application software version (e.g. 7.60
pro)
3) Back Up:
Data backup path
Auto backup path
4. Verification of Communication Cables This Includes the following, but not limited to:
(Record the ‘Observed Value’ w.r.t ‘Specified
Value):
PLC to IPC (e.g. RJ 45 Ethernet)
IPC to Monitor
PLC to Remote Modules
Raktim Dey
Dy. Manager-Validations & Qualifications
Granules India Limited, Place: Hyderabad
A Brief outline for a typical PLC/SCADA system Qualification of Process Equipment
(Example: FBP)
S.No IQ Check Point Remarks
5. Verification of Electrical Utilities of the This Includes the following, but not limited to:
Control System. (Record the ‘Observed Value’ w.r.t ‘Specified
Value):
PLC Voltage Range (e.g. 24V ±10%)
IPC Voltage Range
Monitor Voltage Range
6. Verification of Access groups/ levels This includes, PLC logical security access levels
available in the system w.r.t the following Levels:
Operator
Supervisor
Maintenance
Administrator
7. Verification of Environmental This includes the desired environmental
conditions: conditions for the system hardwares w.r.t
Temperature and % RH
(Record the ‘Observed Value’ w.r.t ‘Specified
Value):
PLC (e.g.: Temp: 0-40ºC, %RH: 5- 95%)
IPC
Monitor
8. Verification of Control Panel: Record the ‘Observed Value’ w.r.t ‘Specified
Value for the following:
1) Control Panel Box:
Control panel should be clean and dust free
2) Wires and cables:
Wires or Cables should not be terminated or
Broken
3) Components:
Exhaust Fans, Service lights, Cables Ferruling,
tags etc. should be available
4) Earthing:
Control system must be Earthed properly
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~END OF IQ TESTS~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
Raktim Dey
Dy. Manager-Validations & Qualifications
Granules India Limited, Place: Hyderabad
A Brief outline for a typical PLC/SCADA system Qualification of Process Equipment
(Example: FBP)
Operational Qualification(OQ) Tests:
1. Verification of Functional Keys and In this section, each of the functional keys from HMI
GUI (Graphical User Interface) shall be tested to verify; what is ‘Specified’ is what
Screens is ‘Observed’. Few of the examples are, but not
limited to:
1. Verification of Welcome Window
2. Verification of Log in Screens (Verify the
Login, Logout, Create/Deactivate user
and Close the Log in screen)
3. Verification of User Management Function
(Verify the New, Change and Delete user
functionality)
4. Verification of New/Change functionality
(Verify the creation of New user, Change
password, Authorization Levels etc.)
5. Verification of Home Functionality
(Verify the functionality w.r.t: Auto Mode,
Manual Mode, Charging Function, Spray
Check, Maintenance Function, WIP Function,
Bag Up/Down Functions, Events Function
for Audit trail screen, Recipe Function,
Parameter Function, Input/output function,
Trends function, Alarms Function to see
details of Alarms generated, Reports function,
Acknowledge Function to acknowledge
alarms, Reset function to reset alarms,
SCADA exit function to close the
Application Software)
6. Verification of Bag Up/Down:
(Verify the functionality w.r.t: Filter Selection,
Finger Bag, UP- to move bag upward, Down-
to bring bag down, Lock-to lock the bag in
position, Unlock-to unlock the bag, Seal-to
Seal the bag, Unseal-to unseal the bag, Open-
Open the inlet damper, Close-to close the inlet
damper.)
7. Verification of Modes:
(Verify the modes of operation:
Auto- to select Auto mode of operation,
Manual-to select Manual mode of operation,
Charging-to select charging mode, Spray
Check-to select spray check mode,
Maintenance-to select maintenance mode,
WIP- to select WIP spray mode, Top Spray- to
select Top spray functions, Bottom Spray- to
select bottom spray function)
Raktim Dey
Dy. Manager-Validations & Qualifications
Granules India Limited, Place: Hyderabad
A Brief outline for a typical PLC/SCADA system Qualification of Process Equipment
(Example: FBP)
S.No OQ Tests Remarks
Raktim Dey
Dy. Manager-Validations & Qualifications
Granules India Limited, Place: Hyderabad
A Brief outline for a typical PLC/SCADA system Qualification of Process Equipment
(Example: FBP)
S.No OQ Tests Remarks
Raktim Dey
Dy. Manager-Validations & Qualifications
Granules India Limited, Place: Hyderabad
A Brief outline for a typical PLC/SCADA system Qualification of Process Equipment
(Example: FBP)
S.No OQ Tests Remarks
3. Verification of access control and Verify the following privileges w.r.t Operator,
rights for different access levels Supervisor, Maintenance and Administrator.
1. Login and Log out Verification:
For example,
Attempt to log in with Wrong User ID and
Incorrect password- Software should not allow
Operator, Supervisor, Maintenance and Admin to
log in.
Similarly,
Attempt to log in with Correct user ID and
correct password- Software should allow all
levels to log in.
2. User Privileges:
Al the functionalities shall be defined with user
privileges:
For example,
Bag Up and Down- The privilege of this
functionality is given to all levels. However, Delete
recipe-this privilege is given only to Admin.
Like this there are so many functionalities, for
which Privilege shall be defined and provided
accordingly in software. Few of the privileges are as
follows:
Modes, Events, Recipe, New recipe, delete recipe,
save recipe, upload recipe, download recipe,
parameters view, parameters set, change parameters,
Trends, Alarms, Reports, Audit trails, user
management etc.
4. Verification of Boundaries of set In this section we need to verify the Range of
parameters different parameters.
The system should Reject values below/above the
range but accepts value within the range
Few of the parameters are as follows:
Step time-1 (Range: 0- 999)
Set Blower Speed (Range: 0 -100)
Set Airflow (Range: 0-3000)
Set Atomization Pressure (Range: 0.1 – 10.0)
Etc.
Raktim Dey
Dy. Manager-Validations & Qualifications
Granules India Limited, Place: Hyderabad
A Brief outline for a typical PLC/SCADA system Qualification of Process Equipment
(Example: FBP)
S.No OQ Tests Remarks
5. Verification of PLC inputs and In this section we need to verify the link between
Outputs field device, IPC display and respective PLC tags
for all Analog and Digital input/output points
associated with the control system.
Few of the I/O tests are as follows:
a) PLC TAG: D10 (For example)
Description: Emergency Stop
Specified: ON, Observed: ON
Specified: OFF, Observed: OFF
6 Verification of alarms & interlocks Verify the functions of all alarms and interlocks.
Few of the Alarms that should generate are as
follows:
Emergency Stop- Appropriate alarm should
be generated.
Product Container-Earth fault.
Finger Bag Broken
RH Explosion Flap Open
LH Explosion Flap Open
Needle Air Pressure Low
Dew point temperature low
Dew point temperature high
Spray Gun Choked
Main air pressure low
Etc.
Raktim Dey
Dy. Manager-Validations & Qualifications
Granules India Limited, Place: Hyderabad
A Brief outline for a typical PLC/SCADA system Qualification of Process Equipment
(Example: FBP)
S.No OQ Tests Remarks
Raktim Dey
Dy. Manager-Validations & Qualifications
Granules India Limited, Place: Hyderabad