DEVELOPMENT OF 50 MW SOLAR

PHOTOVOLTAIC PROJECT

TITLE OF THE DOCUMENT


SINGLE LINE DIAGRAM AC

OWNER AND DEVELOPER

EPC CONTRACTOR

00 28-04-2022 FIRST SUBMISSION MI JL SS

REV INITIAL SIGN INITIAL SIGN INITIAL SIGN


DATE STATUS
NO. PREPARED BY CHECKED BY APPROVED BY

HILD DOC. NO.:HILD-MCL-50MW-002 Rev - 0


PROJECT: DEVELOPMENT OF 50 MW SOLAR
PHOTOVOLTAIC PROJECT DATE:28-04-2022 Page 1
TO POWER TRANSFORMER-1 TO POWER TRANSFORMER-2
132/33kV, 15/25MVA, ONAN/ONAF 132/33kV, 15/25MVA, ONAN/ONAF
SPARE FEEDER (SAME SPARE FEEDER (SAME
AS MAIN OUTGOING MAIN OUTGOING MAIN OUTGOING AS MAIN OUTGOING
FEEDER) FEEDER-1 FEEDER-2 FEEDER)
FROM ACDB
*R/PHASE, 33kV(E), 1C x *sqmm, XLPE, *R/PHASE, 33kV(E), 1C x *sqmm, XLPE, DCDB-1 DCDB-2
INSULATED , AL ,ARMOURED CABLE INSULATED , AL ,ARMOURED CABLE
(CABLE LAID INSIDE TRENCH) (CABLE LAID INSIDE TRENCH)

SURGE ARRESTER SURGE ARRESTER SURGE ARRESTER SURGE ARRESTER


INDOOR TYPE 30kV, 10KA, CL:2 30kV, 10KA, CL:2 30kV, 10KA, CL:2 30kV, 10KA, CL:2
33kV SWITCHBOARD (50MW) VOLTAGE TRANSFORMER VOLTAGE TRANSFORMER VOLTAGE TRANSFORMER VOLTAGE TRANSFORMER
TO VT GUARD PRO-D TO VT GUARD PRO-D TO VT GUARD PRO-D TO VT GUARD PRO-D
(DRAW OUT TYPE) 3.15A HRC (DRAW OUT TYPE) 3.15A HRC (DRAW OUT TYPE) 3.15A HRC (DRAW OUT TYPE) 3.15A HRC
FUSE FUSE FUSE FUSE
LOCATION: CMCS 33kV/√3/110V/√3/110V/√3/110V/3 FUSE
VSS
33kV/√3/110V/√3/110V/√3/110V/3 FUSE
VSS
33kV/√3/110V/√3/110V/√3/110V/3 FUSE
VSS
33kV/√3/110V/√3/110V/√3/110V/3 FUSE
VSS
HEATER, ILLUMINATION 110V DC CONTROL SUPPLY FOR RELAY, 110V DC CONTROL SUPPLY FOR RELAY,
CORE1: CL 0.2, 50VA CORE1: CL 0.2, 50VA CORE1: CL 0.2, 50VA CORE1: CL 0.2, 50VA LAMP METERING, CLOSING CKT, TRIPPING CKT, METERING, CLOSING CKT, TRIPPING CKT,
CORE2: CL3P, 50VA CORE2: CL3P, 50VA CORE2: CL3P, 50VA CORE2: CL3P, 50VA SPRING CHARGING MOTOR SPRING CHARGING MOTOR
CORE3: CL3P, 50VA CORE3: CL3P, 50VA CORE3: CL3P, 50VA CORE3: CL3P, 50VA
(OPEN DELTA WITH R Y B (OPEN DELTA WITH R Y B (OPEN DELTA WITH R Y B (OPEN DELTA WITH R Y B
DAMPING RESISTOR) DAMPING RESISTOR) DAMPING RESISTOR) DAMPING RESISTOR)
P2 P2 P2 P2
CURRENT TRANSFORMER CL: 0.2s
BI-DIRECTIONAL
CURRENT TRANSFORMER CL: 0.2s
BI-DIRECTIONAL
CURRENT TRANSFORMER CL: 0.2s
BI-DIRECTIONAL
CURRENT TRANSFORMER CL: 0.2s
BI-DIRECTIONAL
TTB TTB TTB TTB
33kV, 600/1-1A, 25kA/1S TVM WITHOUT ABT 33kV, 600/1-1A, 25kA/1S TVM WITHOUT ABT 33kV, 600/1-1A, 25kA/1S TVM WITHOUT ABT 33kV, 600/1-1A, 25kA/1S TVM WITHOUT ABT
WITH RS485 PORT WITH RS485 PORT WITH RS485 PORT WITH RS485 PORT
CORE :1 CL 0.2s, 5VA CORE :1 CL 0.2s, 5VA CORE :1 CL 0.2s, 5VA CORE :1 CL 0.2s, 5VA
NUMERICAL RELAY NUMERICAL RELAY NUMERICAL RELAY NUMERICAL RELAY

50 51 50N 51N 25 95 50 51 50N 51N 25 95 50 51 50N 51N 25 95 50 51 50N 51N 25 95


CORE :2 CL 5P20, 5VA CORE :2 CL 5P20, 5VA VOLTAGE TRANSFORMER VOLTAGE TRANSFORMER CORE :2 CL 5P20, 5VA CORE :2 CL 5P20, 5VA
67 67N 50 LBB 27 86 67 67N 50 LBB 27 86 67 67N 50 LBB 27 86 67 67N 50 LBB 27 86
(DRAW OUT TYPE) (DRAW OUT TYPE)
WITH IEC 61850 COMM PROTOCOL TO POWER TRAFO CRP WITH IEC 61850 COMM PROTOCOL TO POWER TRAFO CRP 33kV/√3/110V/√3/110V/√3/110V/3
WITH IEC 61850 COMM PROTOCOL TO POWER TRAFO CRP WITH IEC 61850 COMM PROTOCOL TO POWER TRAFO CRP
33kV/√3/110V/√3/110V/√3/110V/3
33kV, 600/1-1A, 25kA/1S 33kV, 600/1-1A, 25kA/1S CORE1: CL 0.2, 50VA CORE1: CL 0.2, 50VA 33kV, 600/1-1A, 25kA/1S 33kV, 600/1-1A, 25kA/1S
CORE :3 Vk/2>**V, Rct: **Ω @ 600/1A, TO 64R LV CORE :3 Vk/2>**V, Rct: **Ω @ 600/1A, TO 64R LV CORE2: CL3P, 50VA CORE2: CL3P, 50VA CORE :3 Vk/2>**V, Rct: **Ω @ 600/1A, TO 64R LV CORE :3 Vk/2>**V, Rct: **Ω @ 600/1A, TO 64R LV
Imag ≤ **mA @ Vk/2 Imag ≤ **mA @ Vk/2 CORE3: CL3P,50VA (OPEN DELTA WITH CORE3: CL3P,50VA (OPEN DELTA WITH Imag ≤ **mA @ Vk/2 Imag ≤ **mA @ Vk/2
TO POWER TRAFO CRP TO POWER TRAFO CRP DAMPING RESISTOR) TO POWER TRAFO CRP TO POWER TRAFO CRP
DAMPING RESISTOR)
TO VT GUARD PRO-D TO VT GUARD PRO-D
CORE :4 Vk/2>**V, Rct: **Ω @ 600/1A, TO 87T CORE :4 Vk/2>**V, Rct: **Ω @ 600/1A, TO 87T FUSE FUSE CORE :4 Vk/2>**V, Rct: **Ω @ 600/1A, TO 87T CORE :4 Vk/2>**V, Rct: **Ω @ 600/1A, TO 87T
Imag ≤ **mA @ Vk/2 Imag ≤ **mA @ Vk/2 FOR FOR Imag ≤ **mA @ Vk/2 Imag ≤ **mA @ Vk/2
3.15A HRC PROTECTION 3.15A HRC PROTECTION
FUSE FUSE
P1 O/C RELAY E/F RELAY UV RELAY
P1 O/C RELAY E/F RELAY UV RELAY FOR FOR
P1 O/C RELAY E/F RELAY UV RELAY
P1 O/C RELAY E/F RELAY UV RELAY

EP H TRIP OPTD. OPTD.


SPARE
EP H TRIP OPTD. OPTD.
SPARE
VSS V VSS V EP H TRIP OPTD. OPTD.
SPARE
EP H TRIP OPTD. OPTD.
SPARE

FUSE METERING FUSE METERING


VACUUM CIRCUIT BREAKER 94 80AC 80DC MASTER TRIP OV RELAY
SPARE SPARE VACUUM CIRCUIT BREAKER 94 80AC 80DC MASTER TRIP OV RELAY
SPARE SPARE
(0-36kV) (0-36kV) VACUUM CIRCUIT BREAKER 94 80AC 80DC MASTER TRIP OV RELAY
SPARE SPARE VACUUM CIRCUIT BREAKER 94 80AC 80DC MASTER TRIP OV RELAY
SPARE SPARE
RELAY OPTD. OPTD. RELAY OPTD. OPTD. RELAY OPTD. OPTD. RELAY OPTD. OPTD.

(DRAW OUT TYPE) 1H 2H 3H 4H 5H (DRAW OUT TYPE) 1H 2H 3H 4H 5H (DRAW OUT TYPE) 1H 2H 3H 4H 5H (DRAW OUT TYPE) 1H 2H 3H 4H 5H
TCH FAULTY DC FAILURE SPARE SPARE TCH FAULTY DC FAILURE SPARE SPARE TCH FAULTY DC FAILURE SPARE SPARE TCH FAULTY DC FAILURE SPARE SPARE
36kV, 1250A, 25kA/3s T N C L R 36kV, 1250A, 25kA/3s T N C L R 36kV, 1250A, 25kA/3s T N C L R 36kV, 1250A, 25kA/3s T N C L R
33kV,+/-10%, 3Ph., 630A @ 50°C, 50Hz +/-3% 25kA FOR 1SEC., AL. BUSBAR-1 ** 12W ANNUNCIATOR ** 12W ANNUNCIATOR
R Y B R Y B
** 12W ANNUNCIATOR ** 12W ANNUNCIATOR
33kV,+/-10%, 3Ph., 630A @ 50°C, 50Hz +/-3% 25kA FOR 1SEC., AL. BUSBAR-2
1 2 3 6H 7H 8H 9H
WITH RS485 PORT 4 6H 7H 8H 9H 5 WITH RS485 PORT 6 7 8 9 10 11 6H 7H 8H 9H
WITH RS485 PORT 12 6H 7H 8H 9H
WITH RS485 PORT 13 14
1H 2H 3H 4H 5H 6H 7H 8H 9H 1H 2H 3H 4H 5H 6H 7H 8H 9H 1H 2H 3H 4H 5H 6H 7H 8H 9H 1H 2H 3H 4H 5H 6H 7H 8H 9H 1H 2H 3H 4H 5H 6H 7H 8H 9H 1H 2H 3H 4H 5H 6H 7H 8H 9H 1H 2H 3H 4H 5H 6H 7H 8H 9H

T N C L R T N C L R T N C L R T N C L R T N C L R T N C L R T N C L R
VACUUM CIRCUIT BREAKER VACUUM CIRCUIT BREAKER VACUUM CIRCUIT BREAKER VACUUM CIRCUIT BREAKER VACUUM CIRCUIT BREAKER VACUUM CIRCUIT BREAKER VACUUM CIRCUIT BREAKER
(DRAW OUT TYPE) 94 80AC 80DC (DRAW OUT TYPE) 94 80AC 80DC (DRAW OUT TYPE) 94 80AC 80DC (DRAW OUT TYPE) 94 80AC 80DC (DRAW OUT TYPE) 94 80AC 80DC (DRAW OUT TYPE) 94 80AC 80DC (DRAW OUT TYPE) 94 80AC 80DC

36kV, 1250A, 25kA/3s 36kV, 1250A, 25kA/3s 36kV, 1250A, 25kA/3s 36kV, 1250A, 25kA/3s 36kV, 1250A, 25kA/3s 36kV, 1250A, 25kA/3s 36kV, 1250A, 25kA/3s
EP H EP H EP H EP H EP H EP H EP H
P2 FROM BUS PT P2 FROM BUS PT P2 FROM BUS PT P2 FROM BUS PT P2 FROM BUS PT P2 FROM BUS PT P2 FROM BUS PT
CURRENT TRANSFORMER CL: 0.5s CURRENT TRANSFORMER CL: 0.5s CURRENT TRANSFORMER CL: 0.5s CURRENT TRANSFORMER CL: 0.5s CURRENT TRANSFORMER CL: 0.5s CURRENT TRANSFORMER CL: 0.5s CURRENT TRANSFORMER CL: 0.5s
UNIDIRECTIONAL BI-DIRECTIONAL BI-DIRECTIONAL BI-DIRECTIONAL BI-DIRECTIONAL BI-DIRECTIONAL UNIDIRECTIONAL
33kV, **/1-1A, 25kA*/1S MFM 33kV, 300/1-1A, 25kA/1S TTB
MFM 33kV, 300/1-1A, 25kA/1S TTB
MFM 33kV, 600/1-1A, 25kA/1S TTB
MFM 33kV, 300/1-1A, 25kA/1S TTB
MFM 33kV, 300/1-1A, 25kA/1S TTB
MFM 33kV, **/1-1A, 25kA*/1S MFM
CORE :1 CL 0.5s, 5VA WITH RS485 PORT CORE :1 CL 0.5s, 5VA WITH RS485 PORT CORE :1 CL 0.5s, 5VA WITH RS485 PORT CORE :1 CL 0.5s, 5VA WITH RS485 PORT
BUS VTG INPUT CORE :1 CL 0.5s, 5VA WITH RS485 PORT CORE :1 CL 0.5s, 5VA WITH RS485 PORT CORE :1 CL 0.5s, 5VA WITH RS485 PORT
BUS VTG INPUT BUS VTG INPUT BUS VTG INPUT TO RELAY BUS VTG INPUT BUS VTG INPUT BUS VTG INPUT
NUMERICAL RELAY
TO RELAY TO RELAY TO RELAY TO RELAY TO RELAY TO RELAY
NUMERICAL RELAY NUMERICAL RELAY NUMERICAL RELAY NUMERICAL RELAY NUMERICAL RELAY NUMERICAL RELAY
50 51 50N 51N
CORE :2 CL 5P20, 5VA 50 51 50N 51N 95 86 CORE :2 CL 5P20, 5VA 50 51 50N 51N 95 86 CORE :2 CL 5P20, 5VA 50 51 50N 51N 95 86 CORE :2 CL 5P20, 5VA 25
CORE :2 CL 5P20, 5VA 50 51 50N 51N 95 86 CORE :2 CL 5P20, 5VA 50 51 50N 51N 95 86 CORE :2 CL 5P20, 5VA 50 51 50N 51N 95 86
95 86
WITH IEC 61850 COMM PROTOCOL WITH IEC 61850 COMM PROTOCOL WITH IEC 61850 COMM PROTOCOL WITH IEC 61850 COMM PROTOCOL WITH IEC 61850 COMM PROTOCOL WITH IEC 61850 COMM PROTOCOL
P1 P1 P1 P1 WITH IEC 61850 COMM PROTOCOL P1 P1 P1
TRAFO PROTECTION RELAY TRAFO PROTECTION RELAY
63/PTx 49/WA 49/WTx 63/BTx SURGE ARRESTER SURGE ARRESTER SURGE ARRESTER SURGE ARRESTER 63/PTx 49/WA 49/WTx 63/BTx

49/OA 49/OTx 71/MOGA 63/BA 30kV, 10KA, CL:2 30kV, 10KA, CL:2 30kV, 10KA, CL:2 30kV, 10KA, CL:2 49/OA 49/OTx 71/MOGA 63/BA

SURGE ARRESTER SURGE ARRESTER


30kV, 10KA, CL:2 30kV, 10KA, CL:2

*R, 33kV(E), *C x *sqmm, XLPE,


AUXILIARY *R, 33kV(E), *C x *sqmm, XLPE,
AUXILIARY
INSULATED , AL ,ARMOURED CABLE TRANSFORMER INSULATED , AL ,ARMOURED CABLE TRANSFORMER
FEEDER-1 1R/PHASE, 33kV(E), 1C x *sqmm, XLPE, 1R/PHASE, 33kV(E), 1C x *sqmm, XLPE, 1R/PHASE, 33kV(E), 1C x *sqmm, XLPE, 1R/PHASE, 33kV(E), 1C x *sqmm, XLPE, FEEDER-2
INSULATED , AL ,ARMOURED CABLE INSULATED , AL ,ARMOURED CABLE INSULATED , AL ,ARMOURED CABLE INSULATED , AL ,ARMOURED CABLE

INCOMING FEEDER-1 INCOMING FEEDER-2 INCOMING FEEDER-3 INCOMING FEEDER-4


12.5 MW 12.5 MW 12.5 MW 12.5 MW

AUX. AUX.
TRANSFORMER MARSHALLING TRANSFORMER MARSHALLING
BOX BOX
50 kVA* 50 kVA*
33kV/0.415kV, 33kV/0.415kV,
Dyn11, Z=4.0%, Dyn11, Z=4.0%,
AN AN

MAIN ACDB PANEL (CMCS) MAIN ACDB PANEL (CMCS)

TO MAIN INDOOR MV INDICATION LEGENDS:- EQUIPMENT LEGENDS:- LIST OF FEEDER PANELS:


SWITCHBOARD AT CMCS
SR. NO. INSTALLATION PANEL PANEL QTY
LEGEND DESCRIPTION SYMBOL DESCRIPTION FEEDER NAME / CUBICAL NAME
AREA TYPE 50MW
12.5MW PCU BLOCK BREAKER "ON" (RED) Nos. OF POWER TRANSFORMER FEEDERS
1R/PHASE, 33kV(E), 1C x *sqmm, XLPE, 1H PCU 1 DB 4
TOTAL FEEDER NOS.: 4 INDICATION LAMP /OUTGOING FEEDER (FEEDERS TOWARDS
INSULATED , AL ,ARMOURED CABLE FPI FAULT PRESENCE INDICATOR POWER TRANSFORMER)
FROM STATION ACDB
BREAKER "OFF" (GREEN)
2H INDICATION LAMP 2 AUXILIARY TRANSFORMER FEEDERS DB 2
CORE BALANCE CT
BREAKER "TRIP" (AMBER) 3 CMCS Nos. OF INCOMER FEEDERS (FEEDERS DC 4
OUTDOOR TYPE - IP 55 3H INDICATION LAMP TOWARDS INVERTER STATION)
INDICATION LAMP
33kV ICOG TYPE PANEL
4 TIE INCOMER FEEDER DE-IC 1
1H 2H 3H 4H 4H BREAKER "SPRING CHARGE" (BLUE) TRIP, NEUTRAL, CLOSE SWITCH
AC SUPPLY FOR INDICATION LAMP 5 TIE OUTGOING FEEDER DE-OG 1
33kV,+/-10%, 630A @ 50°C,3Ph., 50Hz ILLUMINATION LAMP,
SPACE HEATER LOCAL & REMOTE SWITCH
+/-3% 25kA FOR 1SEC., AL. BUSBAR BREAKER "TRIP CKT HEALTHY" (WHITE) 6 BUS PT PANEL G 2
5H 6H 7H 8H 5H OPEN, CLOSE SWITCH FOR FIXED
INDICATION LAMP
TYPE VCB TOTAL NOS. OF 33KV PANELS AT CMCS 14
BREAKER "IN TEST" (GREEN) INDICATION
R Y B 6H LAMP VDI WITH VPU STAND-ALONE TRANSFORMER FEEDER
VDI WITH VPU EP H INVERTER
7 (STANDALONE PANEL WITH BOTH INCOMING ICOG 4
T N C STATION
BREAKER "IN SERVICE" (RED) INDICATION & OUTGOING CABLES)
7H CURRENT TRANSFORMER
LAMP
VACUUM CIRCUIT BREAKER POTENTIAL TRANSFORMER
L R
(DRAW OUT TYPE) 94 8H "AC SUPPLY FAIL" INDICATION LAMP
36kV, 1250A, 25kA/3s SYSTEM PARAMETERS:-
9H
HRC FUSE
80AC
"DC SUPPLY FAIL" INDICATION LAMP
S. No. DESCRIPTION 33kV 630V 415V
FUSE
80DC DC SUPPLY HEALTHY 1 SYSTEM OPERATING VOLTAGE 33kV 630V 415V
P2 IEC 61850 COMM MCB
CURRENT TRANSFORMER NUMERICAL RELAY PROTOCAL 2 MAX. OPERATING VOLTAGE OF THE SYSTEM 36kV - 433V
33kV, 300/1-1A, 25kA/1S 50 51 50N 51N 87T 95 86
80AC AC SUPPLY HEALTHY
SURGE ARRESTER 3 RATED FREQUENCY 50 Hz 50 Hz 50 Hz
CORE :1 PS CLASS
P1 4 No. OF PHASES 3 3 3
R.Y.B PHASE INDICATION LAMP
TRAFO PROTECTION RELAY
AUXILIARY TRANSFORMER RATED INSULATION LEVELS ±170kVp ±8kVp N/A
Tx x BTx
WA WT ACR
63/
P
49/
4
49/
4
63/ NON-DIRECTIONAL INSTANTANEOUS THREE - 1. FULL WAVE LIGHTNING IMPULSE WITHSTAND
50 PHASE OVER CURRENT PROTECTION INVERTER TRANSFORMER 5 VOLTAGE (1.2/50 microsec.)
x GA
OA OT MO BA 2. ONE MINUTE POWER FREQUENCY DRY & WET
49/ 49/ 71/ 63/ (5 WINDING) 70kVrms 2.5kVrms 3kVrms
WITHSTAND VOLTAGE (rms)
110V DC CONTROL SUPPLY FOR SPRING NON-DIRECTIONAL INSTANTANEOUS NEUTRAL VACUUM CIRCUIT BREAKER
CHARGING MOTOR, CLOSING COIL, SHUNT TRIP 50N RATED 3-PH. SYMMETRICAL SHORT CIRCUIT
COIL, NUMERICAL RELAY, INDICATION LAMP OVER CURRENT PROTECTION (DRAWOUT TYPE)
6 25kA/1Sec - -
CURRENT WITHSTAND CAPACITY
NON-DIRECTIONAL IDMT THREE - PHASE OVER 7 SYSTEM NEUTRAL EARTHING
SOLIDLY FLOATING SOLIDLY
51 CURRENT PROTECTION H HOOTER EARTHED EARTHED
LIST OF REFERENCE DRAWINGS:
SURGE ARRESTER 8 RATED AMBIENT TEMPERATURE 50° C 50° C 50° C
NON-DIRECTIONAL IDMT NEUTRAL OVER EP EMERGENCY PUSH BUTTON
30kV, 10KA, CL:2 51N
CURRENT PROTECTION
DC POWER PACK
9 PERMISSIBLE VARIATION IN VOLTAGE ±10% ±10% ±10% SR. NO. DESCRIPTION DRAWING NO.
63/BTx BUCHHOLZ TRIP SFU
10 PERMISSIBLE VARIATION IN FREQUENCY ±3% ±3% ±3% 1 SLD- SINGLE LINE DIAGRAM DC HILD-MCL-50MW-001
UPS
V VOLTMETER DIGITAL COMBINED VARIATIONS IN VOLTAGE &
63/BTx BUCHHOLZ ALARM 11 FREQUENCY (ABSOLUTE) ±10% ±10% ±10% 2 DC AND AC CABLE SIZING HILD-MCL-50MW-016
1R/PHASE, 33kV(E), 1C x *sqmm, XLPE, ANNUNCIATOR 12 MINIMUM CREEPAGE DISTANCE (25MM / KV ) 900 MM - - 3 SLD -AUXILIARY POWER SUPPLY SYSTEM-ICR HILD-MCL-50MW-036
INSULATED , AL ,ARMOURED CABLE 63/PTx TRANSFORMER TANK PRESSURE RELAY (PRV)
13 ALTITUDE ABOVE MSL N/A N/A N/A 4 SLD -AUXILIARY POWER SUPPLY SYSTEM-MCR -
MFM MULTI FUNCTION METER
49/WA WINDING OVER TEMPERATURE ALARM 14 SESMIC ZONE ZONE III ZONE III ZONE III
5 SINGLE LINE DIAGRAM SWITCHYARD HILD-MCL-50MW-003
TVM TRIVECTOR METER
INVERTER DUTY 49/WTx WINDING OVER TEMPERATURE TRIP
TRANSFORMER 12.5 MVA EARTH SWITCH
33kV/0.63-0.63-0.63-0.63 kV MARSHALLING 49/OA OIL OVER TEMPERATURE ALARM VACUUM CIRCUIT BREAKER
BOX
Yd11d11d11d11, Z=8%, ONAN (FIXED TYPE)
OCTC, ±5% @ STEPS 2.5% 49/OTx OIL OVER TEMPERATURE TRIP
MCCB
71/MOGA MAGNETIC OIL LEVEL GAUGE ALARM
NOTES:
1. FOR DC INPUT DETAILS REFER DC SINGLE LINE DIAGRAM.
*RUN, 1.9/3.3kV, *C x *sqmm, XLPE CT: 3500/1A, CL: PS 2. FOR AUX. SYSTEM REFER AUX. SINGLE LINE DIAGRAM.
INSULATED , AL ,ARMOURED CABLE ACR AIR CELL PUNCTURE RELAY 3. ALL PROTECTION RELAYS SHALL BE PROVIDED WITH IEC-61850
COMMUNICATION. ALL DIGITAL METERS, ANNUNCIATOR SHALL
86 COMMUNICATE WITH MODBUS RS485 PROTOCOL.
MASTER TRIP RELAY / LOCKOUT RELAY
4. VCB BREAKER WILL BE TRIPPED WHEN BREAKER DOOR IS OPENED.
*R/PHASE, 1.9/3.3kV, 1Cx *sqmm, 5. CT & PT SIZING CALCULATION ALONG WITH KNEE POINT VOLTAGE &
AUXILIARY TRANSFORMER
XLPE INSULATED, AL, ARMOURED 95 SUPERVISION RELAY BURDEN SHALL BE PROVIDED DURING DETAILED ENGINEERING.
WITH ACDB CABLE 6. RATING OF AUXILIARY TRANSFORMER MENTIONED AT 33KV
SWITCHBOARD & PCU BLOCK ARE TENTATIVE ONLY. SAME SHALL BE
94 ANTI PUMPING PROTECTION
FUSE: 1P, 630V, *A, 36kA R Y B UPDATED AS PER AUXILIARY TRANSFORMER SIZING.
DISCONNECTOR: 3P, 630V, *A, 7. ** MARKED VALUES SHALL BE UPDATED AFTER VENDOR
36kA ACB-690VAC
59 OVER VOLTAGE RELAY FINALIZATION.
8. * MARKED VALUES WILL BE UPDATED DURING DETAIL ENGINEERING.
9. THE INSULATION CLASS OF CT & PT WILL BE CLASS-E OR BETTER.
27 UNDER VOLTAGE RELAY 10. THE SWITCHGEAR SHALL HAVE AN INTERNAL ARC CLASSIFICATION OF
PCU-X.1 IAC FLR CORRESPONDING TO SYSTEM FAULT CURRENT FOR 1 SEC.
DRY TYPE AUXILIARY PCU-X.2 PCU-X.3 PCU-X.4 TRANSFORMER CURRENT DIFFERENTIAL
TRANSFORMER 87T 11. TRIP CIRCUIT SUPERVISION SHALL BE PROVIDED FOR ALL FEEDERS TO
3125 kVA 3125 kVA 3125 kVA 3125 kVA RELAY
* kVA MONITOR THE CIRCUIT BREAKER TRIP CIRCUIT BOTH IN PRE TRIP AND
0.63kV/0.415kV, POST TRIP CONDITIONS.
Dyn11, 25 SYNC CHECK FUNCTION
%IMPEDANCE=4.0%,
AIR NATURAL COOLING

THIS DOCUMENT IS WHOLE OR IN PART MAY NOT BE USED BY ANY


PERSON FOR ANY PURPOSE OTHER THAN THAT SPECIFIED,
PV MODULE PV MODULE PV MODULE PV MODULE WITHOUT THE EXPRESS WRITTEN PERMISSION OF HILD ENERGY
TO AUX LOADS
ARRAY ARRAY ARRAY ARRAY PVT LTD. ANY LIABILITY ARISING OUT OF USE BY A THIRD PARTY
OF THIS DOCUMENT FOR PURPOSE NOT WHOLLY CONNECTED
WITH THE ABOVE SHALL BE THE RESPONSIBILITY OF THE PARTY
WHO SHALL INDEMNIFY HILD ENERGY AGAINST ALL CLAIMS
COSTS DAMAGES AND LOSSES ARISING OUT OF SUCH USE.

You might also like