Maintained Loop devices System Sensor

(See also APPENDIX D: Tables for corresponding of device types)


1251E (Ionization sensor)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and night time working modes. Each of these are assigned different times of filtra-
tion of the FIRE signal. The night time mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
The device maintains day and night time working modes. Both are assigned different thresholds for FIRE
(1-3). Night time mode must be of a lower threshold than that of the daytime one. It is possible to experiment
with various alarm levels.
2251EM (Photoelectric Smoke sensor)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and night time working modes. Each of these are assigned different times of filtra-
tion of the FIRE signal. The night time mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
The device maintains day and night time working modes. Both are assigned different thresholds for FIRE
(1-3). Night time mode must be of a lower threshold than that of the daytime one. It is possible to experiment
with various alarm levels.
2251EIS (Photoelectric Smoke sensor)
- After the initial starting up of the system the type needs to be fine-tuned. The panel shall detect devices like
2251ЕМ. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and night time working modes. Each of these are assigned different times of filtra-
tion of the FIRE signal. The night time mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
6200 (Smoke beam sensor)
- After the initial starting up of the system the type needs to be fine-tuned. The panel shall detect devices like
2251ЕМ. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and night time working modes. Each of these are assigned different times of filtra-
tion of the FIRE signal. The night time mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
FTX-P1 (Photoelectric Smoke sensor)
- After the initial starting up of the system the type needs to be fine-tuned. The panel shall detect devices like
2251ЕМ. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and night time working modes. Each of these are assigned different times of filtra-
tion of the FIRE signal. The night time mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
6500 (Linear smoke sensor)
- After the initial starting up of the system the type needs to be fine-tuned. The panel shall detect devices like
2251ЕМ. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and night time working modes. Each of these are assigned different times of filtra-
tion of the FIRE signal. The night time mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
- The device can be tested by covering the reflector, depending on the selected alarm level. As a result a
FIRE signal is generated to the respective zone. In the case of complete blockage of the reflector a “BEAM
BLOCKAGE” message is generated. If there are any reflective objects in the path of the detector a “SIGNAL
OVER RANGE” message is generated.
5251EM (Temperature sensor)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and night time working modes. Each of these are assigned different times of filtra-
tion of the FIRE signal. The night time mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
5251TEM (Temperature sensor)
- After the initial starting up of the system the type needs to be fine-tuned. The panel shall detect devices like
5251ЕМ. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and night time working modes. Each of these are assigned different times of filtra-
tion of the FIRE signal. The night time mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
5251HTEM (Temperature sensor)
- After the initial starting up of the system the type needs to be fine-tuned. The panel shall detect devices like
5251ЕМ. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and night time working modes. Each of these are assigned different times of filtra-
tion of the FIRE signal. The night time mode must be less than that of the daytime mode. For specific cases
the times of both modes can be 0, disallowing filtration time, having the fire signal is immediately perceived.
2251TEM (Multi- criteria fire sensor)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and night time working modes. Both are assigned different thresholds for FIRE
(1-6). Threshold 6 responds to an alarm signal sent from a thermal detector. It is recommended that threshold
6 be selected for daytime mode. Night time mode must be of a lower threshold than that of the daytime one.
It is possible to experiment with various alarm levels.
The day and night time working modes are assigned different times of filtration of the FIRE signal.
The night time mode must be less than that of the daytime mode. For specific cases the times of both modes
can be 0, disallowing filtration time, having the fire signal is immediately perceived.
7251 (Photoelectric smoke sensor)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of a FIRE signal.
- Introduce the name of the device – 40 digits.
- The device maintains day and night time working modes. Both are assigned different thresholds for FIRE
(1-9). Night time mode must be of a lower threshold than that of the daytime one. It is possible to experiment
with various alarm levels.
The day and night time working modes are assigned different times of filtration of the FIRE signal.
The night time mode must be less than that of the daytime mode. For specific cases the times of both modes
can be 0, disallowing filtration time, having the fire signal is immediately perceived.
M210E (Single input)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
M220E (Dual input)
- After the initial starting up of the system the type needs to be fine tuned. The panel shall detect devices
like М210E. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
M221EINPUT (Input)
- After the initial starting up of the system the type needs to be fine-tuned. The panel shall detect devices
like М210E. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
M221EOUTPUT (output)
- After the initial starting up of the system the type needs to be fine tuned. The panel shall detect devices
like М210E. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the output.
- Introduce the name of the device – 40 digits.
M201E (Main switch output)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
M501ME (Input)
- After the initial starting up of the system the type needs to be fine tuned. The panel shall detect devices
like М210E. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
M503ME (Micro monitor)
- After the initial starting up of the system the type needs to be fine-tuned. The panel shall detect devices
like М210E. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
M500KAC (Call point)
- After the initial starting up of the system the type needs to be fine tuned. The panel shall detect devices
like М210E. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device). On a correct adjustment of the type, after activation
of a Call Point is generated an alarm signal to the relevant device.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
M512ME (Zone monitor)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
EMA24 & DBS24 (Loop sounders)
- After the initial starting up of the system the type needs to be fine tuned. The panel shall detect devices
like М210E. From the menu of types select the correct type of the respective device (this is recommended in
order to ensure the proper performance of the device).
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the output.
- Introduce the name of the device – 40 digits.
CR-6 (Six Relay Control Module)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
CZ-6 (Six Zones Interface Module)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.
IM-10 (Ten Input Monitor Input)
- Following the initial start-up of the system there is no need for further readjustment of the type.
- A number should be set for the zone (1-96), to which the messages from the specific device will be sent,
indicating: ALARM, TROUBLE, etc.
- A specific mode is assigned to the light-emitting diode of the device: BLINK and OFF. In the BLINK mode the
LED blinks at every query addressed by the system. In the OFF mode the LED does not reflect any device
contact. The LED turns ON in case of activation at the input.
- Introduce the name of the device – 40 digits.

Important: Every device can be enabled or disabled. When disabled a “LOOP DEVICE DISABLED”
message is generated to the respective zone. No signals will be perceived from a disabled device.
Device disabling does not terminate after a RESET command.