New options for insulation systems 1.

Introduction
The development of new insulation materials has been critical in the evolution of the design of
in power transformers power transformers. Insulation systems for liquid filled power transformers are a combination of
materials that are aimed to provide the required electrical, mechanical, thermal properties
together with a full chemical compatibility for successful operation of the transformer for
several decades under defined operation conditions.
R. SZEWCZYK, J.-C. DUART
2. Materials enabling innovative power transformer solutions
The offering of solid materials like papers or pressboards as well as dielectric fluids has been in
constant evolution in the 20th century as the use of transformers was expanding through the
development of electrical networks around the world. As the timeline in Fig. 1 shows, several
materials have played important role in the design of the transformers over the past century.
While the first half of the 20th century has seen the development and combination of cellulose
Radoslaw Szewczyk Dr Jean-Claude Duart has based materials for the solid insulation [1] and mineral oil for the fluid, the second half of the
received his Master’s been employed at DuPont
degree in Electrical de Nemours in Switzerland century has seen the arrival of new materials based on synthetic polymers.
Engineering at Lodz since 1995. He currently
University of Technology, works as Business
Poland, in 1998. He works Development Leader for
for DuPont™ Nomex® the Nomex® Electrical
Electrical Infrastructure Infrastructure segment, in
business as a Technical charge of technical
Service & Development development in the area of
Expert for EMEA region. power and distribution
With his background of transformers. Dr Duart
transformer design received his PhD in
engineer, he supports Electrical Engineering from
transformer the University of Toulouse
developments with in France while working as
application of Nomex® R&D Engineer for Jeumont
insulation materials. He is Schneider Transformers
a member of IEC, IEEE and from 1990 until 1994. Dr
CIGRE working groups. Duart has published
several international
papers in both electrical
insulation field as well as
electrical arc flash
protection. He is part of IEC
TC112 and TC10.
A new generation of thermally It has been a constant search for solutions that
1920 1930 1940 1960 1970 1980 1990 2010 could provide additional benefits like fire
upgraded paper was introduced -
Nomex® 910, taking advantage of resistance or, more recently, biodegradability.
Kraft paper Pressed PCB TUK Silicone Synthetic Natural TUK paper However, still today mineral oils remain the
board fluid paper fluid ester fluid ester fluid with Nomex® DuPont™ Nomex® to reach an improved
main insulating fluid for liquid immersed
thermal stability compared to regular power transformers.
Mineral oil Nomex® Nomex® thermally upgraded Kraft paper.
paper pressboard
Figure 1 – Timeline of main insulation materials for liquid filled power transformers
In the area of insulating papers, no other The DuPont™ Nomex® pressboard
comparable technical steps were achieved in followed a similar principle as Kraft
With the introduction of high-quality cellulose nylon. Here again, in order to overcome the the 20th century and it was only in the wake of pressboard, i.e. combining specific
pulp, the production of cellulose paper with thermal limitation of the nylon, the polymer the 21st century when another particular paper known ingredients dedicated to
improved performance has seen tremendous was modified to integrate aromatic rings that combining the benefits of thermally upgraded electrical applications and a
progress initiated in the late 1920’s making it would provide improved thermal performance cellulose ingredients and aramid was manufacturing process involving press
the main choice of insulation combined with (Fig.2). The DuPont™ Nomex® paper, an developed. A new generation of thermally capabilities that still remain unique
mineral oil. Another step was the introduction aromatic polyamide, also called aramid, was upgraded paper was introduced, taking today.
of thermally upgraded Kraft (TUK) papers in born. With its thermal class of 220 in the air, it advantage of DuPont™ Nomex® to reach an
the 1960’s. Already at that time the aim was to was initially used in insulation systems for dry improved thermal stability compared to It is also important to indicate that another
improve the thermal stability of the paper type transformers and rotating machines, it regular thermally upgraded Kraft paper (Fig. 3). major material was critical to the development
insulation, a limiting element when took not more than 10 years for the electrical of advanced insulation systems, particularly
transformers have to overcome challenging industry producing oil filled transformers to with the increase of operating voltages that
load profiles or need to meet more stringent consider it as an insulation for the conductors. power grids have seen. Almost 100 years ago
size and weight constrains. An advantage was taken of its significant Kraft pressboard was invented allowing for
thermal capabilities combined with excellent development of insulating components that
An advantage was taken of outstanding electrical and mechanical characteristics, would become critical in high and extra high
thermal capabilities of Nomex® although applicable temperatures had to be voltage transformers. About 50 years later
combined with excellent electrical and Figure 3 – DuPont™ Nomex® 910 structure another pressboard type important for the
reduced due to limited thermal capability of
mechanical characteristics. development of advanced insulation system
dielectric liquids. for power transformer was invented: the
In parallel to the paper evolution the
insulating fluids have also seen major aramid pressboard. The DuPont™ Nomex®
About the same time and in line with the pressboard followed a similar principle as Kraft
interest of the chemical industry for developments in the 20th century. First, fluids
pressboard, i.e. combining specific known
developing products that featured advance like PolyChlorinated Biphenyl’s (known as PCB) ingredients dedicated to electrical applications
characteristics, a 100% synthetic paper was introduced in the 1940’s as dielectric coolant and a manufacturing process involving press
developed based on the known polyamide and then replaced by silicon oil in the 1970’s as capabilities that still remain unique today. This
polymer, most known under the name of they were found harmful to people’s health. aramid pressboard also offers improved
Figure 2 – DuPont™ Nomex® meta-aramid, Then, the upraise of ester fluids, synthetic in thermal capabilities as compared to the Kraft
poly(meta-phenyleneisophthalamide) the 1980’s and then natural in the mid-1990’s. pressboard.
While these materials development may not
describe the only changes than occurred over
the last 100 years in insulation materials for
liquid filled transformers, they indicate
important categories that are used in
transformers today to meet the evolving
constrains to which transformers are exposed.
3. Developments in insulation systems
In recent years it could be seen that transformer
designs have evolved to not only reduce the
size and weight of units, but also improve their
operating flexibility. Many modern design
techniques or available state-of-the-art
technical solutions drive designs to be smaller
and more optimal. However, the use of
aramid-based materials allows a step change in
the ability to make designs significantly more
compact, when compared to “conventional”
designs that are based on cellulose insulation
and mineral oil. These transformers may also
benefit from longer life time as the new
insulation systems are more thermally robust.
They also offer more resistance to overload
conditions that may results from planned or
unplanned demands (planned maintenance
periods or unplanned situations due to summer
heat waves or other operational circumstances).
Industry standards, both IEC and IEEE, define
such insulation systems available for use in
power transformers. The standards define
typical constructions and provide guidance on
how the “high temperature insulation
materials” shall be used. For example, Tables I
and II present the temperature limits according
to IEC 60076-14 [2]. Similar guidance can be
found in IEEE Std. C57.154 [3].

Table I – Hybrid insulation windings – thermal limits as per IEC 60076-14 [2]
Hybrid insulation systems
Conventional
Semi-hybrid Mixed hybrid Full hybrid insulation
insulation
insulation insulation winding
system
winding winding An example illustration of insulation systems is shown in Fig. 4. While few decades ago the Kraft
Minimum required solid insulation in mineral oil system was vastly used in liquid immersed power transformers (Fig. 4a),
105 120 130 130 140 155
high-temperature insulation thermal class we have seen over the last five decades the arrival of different insulation systems. One recently
Top liquid temperature rise (K) 60 60 60 60 60 60
developed system consists of the thermally upgraded Kraft paper enhanced with Nomex® on the
Average winding temperature rise (K) 65 75 65 85 95 105 conductors (referred as Nomex® 910 paper) combined with cellulose pressboard components and
Hot-spot temperature rise for solid 78 90 100 100 110 125 mineral oil (Fig. 4b). This system gives the benefit of longer insulation system lifetime when used
insulation (K)
at conventional operating temperature but also help mitigating a load increase that can be due to
planned demand or due to climatic events, generally unplanned.
Table II – High-temperature insulation windings with ester liquids – thermal limits as per IEC 60076-14 [2]

Minimum required high-temperature solid insulation Another system that has recently emerged is a hybrid system where aramid materials are used
130 140 155 180
thermal class for conductor insulation, spacers and strips, while other materials remain in cellulose pressboard.
Top liquid temperature rise (K) 90 90 90 90 Recently, these systems are combined with ester fluids (Fig. 4c). This system is a response to
increasing fire and environmental constraints that power utilities can see, e.g. in large cities [4].
Average winding temperature rise (K) 85 95 105 125
Historically the solid materials of this system have been associated to mineral oil since the 1980’s
Hot-spot temperature rise (K) 100 110 125 150 in applications for mobile transformers.
a) b)

insulation parts. Then, the materials were


evaluated for the two typical processes of
forming:

- machine forming for more regular angle ring


sectors (caps and collars),
- hand molding for more complex combined
shapes, like e.g. winding exit snouts.
c) d) Process optimization led to development of
Figure 4 – Example illustration of various insulation systems for power transformers: parts that matched the benchmark mechanical Figure 5 – Test arrangement for partial discharge
a - Kraft with mineral oil (conventional), b - semi-hybrid with Nomex® 910 conductor insulation, and dielectric performance of conventional measurement on laminated aramid board after aging in
c - hybrid system with ester fluid, d - high temperature system with ester fluid synthetic ester (photo: DuPont/Siemens Energy)
cellulose based components.
Recently, an increasing number of Advanced insulation systems with The development of new insulation Aging in hot synthetic ester liquid was part of
developments focus on the use of ester ester liquids may require more the research to ensure the right long-term
components also included laminated aramid
liquids, due to their fire safety and extensive use of aramid materials in board for producing thick insulation blocks,
performance of the laminated material in
environmental advantages. The thermal the transformer construction. The e.g. for clamping rings and associated
service. Compatibility with the selected
capability of ester liquids would allow using research is continuing for better structures. Steps have been made for
synthetic ester liquid was confirmed.
them at higher temperatures (although the characterization of these systems and
producing larger sheets of high-density aramid Additionally, the development was made for
test methods for more precise evaluation of proving their high performance.
thermal capabilities of ester liquids are only pressboard. Comprehensive studies were large winding cylinders. For producing them,
under development). Then, transformer performed for adequate glue selection and the two aramid pressboard options have been
designs can shift from hybrid systems (Table I) process for laminating such boards, and proper evaluated:
towards more advanced high temperature 4. New aramid-based insulation parts characterization of critical properties. The - high-density aramid pressboard - in large
insulation systems (Table II). These systems Plans for more extensive use of aramid testing included mechanical, dielectric and sheets like those used for the laminated board,
will require more extensive use of high insulation in power transformer high voltage or
thermal properties. The dielectric test
temperature materials in the transformer insulation systems drives new developments - lower density aramid pressboard - available
confirmed the partial discharge inception in
construction as illustrated in Fig. 4d. The for adequate insulation parts. One example is in even larger sheets and more flexible but
the development of formed 3-dimensional end the laminated board not happening below the
combination of aramid insulation and ester required threshold of 9 kV/mm (Fig. 5). This requiring more attention in the processing due
liquids has already been used for many years insulation components, such as angle rings, to the air humidity impact on dimensional
lead exit snouts, and edge protectors. For included tests on the laminated board samples
in smaller transformers, e.g. on-board traction stability.
some of these components there is a need to aged in synthetic ester at the temperatures up
units for rolling stock and compact wind
use a wet formable aramid board. The to 155°C. Another test program analyzed
turbine step-up transformers. Nevertheless,
the research is continuing for better development focused first on identifying the dielectric strength and the partial discharge
characterization of these systems and proving grade of wet aramid material most suitable for behavior of the laminated board when
their high performance. forming the required 3D shapes of typical dielectrically tested at elevated temperatures
up to 120°C.
5. Summary 6. REFERENCES
The options offered by the combination of
various insulation materials allow more [1] Prevost, T. A., Oommen, T. V. “Cellulose insulation in oil-filled power transformers: Part I -
flexibility for the designers to develop history and development”. IEEE Electrical Insulation Magazine, Vol. 22(No 1), Jan/Feb 2006, pp.
transformers that will be able to operate in 28–35.
environments where new constraints have [2] IEC 60076-14:2013, Power transformers – Part 14: Liquid-immersed power transformers using
been evolving, whether they are related to high-temperature insulation materials.
space and weight restriction, loading profiles
or ambient temperatures. Materials remain [3] IEEE Std C57.154TM-2012, IEEE Standard for the Design, Testing, and Application of
Figure 6 – Example of insulation kit with winding
one of the critical elements to allow for the Liquid-Immersed Distribution, Power, and Regulating Transformers Using High-Temperature
cylinder shaped from high-density
aramid pressboard Nomex® 994 PSB transformer designs to continue their Insulation Systems and Operating at Elevated Temperatures.
(photo: DuPont™) evolution to meet end-user requirements.
[4] Szewczyk, R., et al., “Replacement of area substation transformers with flexible units of
The above insulation kit shows the assembly reduced footprint and increased overloadability” - e-CIGRE session 2020
of various insulation components mentioned
previously in an innovative insulation kit for
advanced power transformers DuPont™ and Nomex® are trademarks owned by affiliates of DuPont de Nemours, Inc.