rsenic content in drinking water has been regulated in the CO2 gas prior to the arsenic removal system, or along with the
US since 1942, when the Public Health Service established ferric chloride when using it as a coagulant for arsenic. After the
a standard of 50 parts per billion (ppb). In January 2006, arsenic is removed, pH can be left in the depressed state or raised
a new standard of 10 ppb was mandated by the US EPA. back to the initial value or some intermediate, depending on the
Municipal water suppliers in states with higher detectable requirements of the system.
arsenic levels in groundwater have been investigating When CO2 gas is used, pH can be brought back up at least
technologies to protect water quality and reach compliance with partially by dropping the line pressure and allowing the gas to
the new regulations. Treating the water to remove arsenic or vent, or by stripping the CO2 more completely with air. When
some other contaminant, however, may reveal other issues that a mineral acid is used, pH is often restored by the addition of
the owner never knew they had, or even create a second set of caustic.
issues if not handled with care. While the absolute pH is of little importance for a new
Take, for example, a well that has an arsenic level just over the system, it is often important not to shift the pH in an existing
US EPA maximum contaminant level (MCL) of 10 ppb, where the system too dramatically to avoid the release of scale in pipes
arsenic is in its reduced form of As(III). The well also has levels of and the problems it would cause downstream. Even if no pH
iron and manganese just below the US EPA secondary MCL of 0.3 adjustment is planned for the arsenic removal system, it is
and 0.05 mg/L, respectively. Untreated, these iron and manganese possible that pH will be affected by the system unintentionally,
levels may not have caused any issues to end-users. even if for a short while.
120
may only be the beginning when considering other options for
treatment that may be available or required with regard to a 100
Granules, Case B
complete water analysis. 80
60
pH issues
Whether intentional or not, pH of the water before and after 40
e ea s
treatment can often be different. Since the efficiency of arsenic 20
adsorption decreases with increasing pH, it is often economical
0
to lower the pH of very alkaline water when removing arsenic. 0 10 20 30 40 50 60 70
This can be done with the addition of a mineral acid or Bed Volumes