TECHNICAL SPECIFICATIONS
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature 0 ... +50°C/-25 ... +70°C (with no icing)
Max. relative humidity 80% Relative humidity for temperatures up to 31°C, decreasing linearly to 50% at 40°C.
Rated pollution degree According to EN 60529 Front panel : IP65
Rear panel : IP20
Height Max. 2000m
Do not use the device in locations subject to corrosive and flammable gases.
ELECTRICAL CHARACTERISTICS
Supply 230V AC +10% -20%, 50/60Hz or 24V AC ±10%, 50/60Hz or optional 9-30V DC / 7-24V AC ±10% SMPS
Power consumption Max. 7VA
Wiring 2.5mm² screw-terminal connections
Date retention EEPROM (Min. 10 years)
EMC EN 61326-1: 2006
Safety requirements EN 61010-1: 2010 (Pollution degree 2, overvoltage category II, measurement category I)
EI7412 cannot be used if measurement category II, III or IV is required.
CONTROL
Control type Single set-point and alarm control
Control algorithm On-Off control
Hysteresis Adjustable between 1 ... 200
HOUSING
Housing type Suitable for flush-panel mounting according to DIN 43 700.
Dimentions W72xH72xD97mm
Weight Approx. 350g (after packaging)
Enclosure material Self extinguishing plastics.
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
DIMENSIONS
Depth Panel cut-out
97mm 75mm
EI 7412 2 68 mm
OUT ALR
72mm
mm
78mm
68
SET
ENDA
84mm
PROGRAMMABLE INDICATOR
Connection
cables
For removing mounting clamps:
1 1 - Push the flush-mounting
clamp in direction 1 as
Flush shown in the figure left.
mounting 2 - Then, pull out the clamp in Note : 1) While panel mounting, additional distance required
direction 2. for connection cables should be considered.
clamp 2) Panel thickness should be maximum 10mm.
3) If there is no 90mm free space at back side of the device,
it would be difficult to remove it from the panel.
Panel
Rubber packing
CONNECTION DIAGRAM
ENDA EI7412 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The shielding must be grounded
on the instrument side. During an installation, all of the cables that are connected to the device must be free of energy. The device must be protected
against inadmissible humidity, vibrations, severe soiling.Make sure that the operation temperature is not exceeded. All input and output lines that are
not connected to the supply network must be laid out as shielded and twisted cables. These cables should not be close to the power cables or
components. The installation and electrical connections must be carried on by a qualified staff and must be according to the relevant locally applicable
regulations.
ENDA INDUSTRIAL ELECTRONICS ENDA INDUSTRIAL ELECTRONICS ENDA INDUSTRIAL ELECTRONICS ENDA INDUSTRIAL ELECTRONICS ENDA INDUSTRIAL ELECTRONICS
EI7412-230VAC-AS24 Made In Turkey EI7412-230VAC-AS12 Made In Turkey EI7412-230VAC-AS08 Made In Turkey EI7412-230VAC-AS05 Made In Turkey EI7412-230VAC Made In Turkey
INDICATOR INDICATOR INDICATOR INDICATOR INDICATOR
8 680407 703395 8 680407 703401 8 680407 703418 8 680407 703425 8 680407 703432
NOTE : Fuse
SUPPLY : F 100 mA
250V AC Switch
Line 230V AC Holding screw Equipment is protected throughout
184-253V AC 7 0.4-0.5Nm by DOUBLE INSULATION.
50/60Hz 7VA 8 Neutral Supply
Fuse should
be connected Cable size: 1,5mm²
Note : 1) Mains supply cords shall meet the requirements of IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument and it
should be easily accessible by the operator.
2/3 EI7412-E-04-R-201401
Run mode
SET SET SET If first and then keys are pressed
&
Measured 500 499 500 1000 999 1000 MAX MIN
MAX MIN
1000 value OSET OSET MIN OSET MAX ASET ASET MIN ASET MAX together, the maximum and the minimum
Out set value Out set value Alarm set value Alarm set value Alarm set value measurement values become equal to the
SET
Out set value measured value at that time and the
SET
While holding key out set value flashes and by using keys the value can be adjusted. message Res. appears on the display.
OSET MAX MIN
While holding key out set value flashes and by using keys the value can be adjusted. Res.
OSET MAX MIN
Out set value changes fastly if increase or decrease key is pressed for 0.6 second. Out set value changes fastly if increase or decrease key is pressed for 0.6 second.
SET SET
& If first and then keys are pressed together programming mode is entered.
OSET ASET
OSET ASET
Programming mode
out. Alr. d.Cnf. U.opt. d.Cal. SeCU.
ASET ASET ASET ASET ASET ASET
o.HYS. = Out hysteresis value. A.HYS. = Alarm hysteresis value. i.typ. = Input type. CAL.t. = Calibration type. s.Cod. = Access code for calibration s.Cod. = Access code for safety menu.
o.Hys. Can be adjusted between 1 and a.HYS. Can be adjusted between 1 and 200. i.typ. Input type can be selected as 0-20mA, Cal.t. Selectable as S.inP. or U.inP. S.Cod. menu. This parameter should be 222. S.Cod. This parameter should be 333.
200. See NOTE 1 for programming. 4-20mA, 0-1V or 0-10V. If S.inp. is selected, input type is See NOTE 1 for programming. See NOTE 1 for programming.
See NOTE 1 for programming. See NOTE 1 for programming. one the four standard input types.
MAX MIN MAX MIN MAX MIN If U.inP is selected, input types MAX MIN MAX MIN
o.StA. = State of out. A.tyP. = Function of alarm output. dSP.C. = Display configuration. can be modified. A.CAL. = Current calibration. ou.SC. = out. menu protection level
o.StA. If H1 is selected then out output is A.typ. Three kinds of functions can be selected. dsp.C. Selectable as PrcS. or Pr.Un. . If PrcS. See NOTE 1 for modification. a.CAL. At this state, 20mA current is ou.sC. parameter.
energized above the out setpoint . IndE = Independent. is selected, process value appears. If MAX MIN applied to the input of the device. SET
nonE = No menu is seen.
If Lo is selected then out output is De = Deviation. Pr.Un. is selected, process value and d.Pnt. = Decimal point. To initialize calibration, first P. no = Menu is seen but can not be
energized below the out setpoint . band = Band. then measurement unit are displayed 4 d.pnt. Decimal point can be adjusted
OSET
programmed.
See NOTE 1 for programming. See NOTE 1 for programming. and 2 seconds successively. between 1. and 3. digits. then keys are pressed
MAX
P.yES. = Menu is seen and programming
See NOTE 1 for programming. See NOTE 1 for programming. together and held until ‘CAL' is possible.
MAX MIN MAX MIN MAX MIN
MAX MIN message appears. See NOTE 3. See NOTE 1 for programming.
o.UP.L = Out value upper limit. A.Sta. = State of alarm output. RAtE = Sampling rate. MAX MIN
L.SCL. = Lower limit for the scale.
o.UP.L. Can be adjusted between out value a.sta. If independent or deviation alarm is rate Measurement is performed at each
l.sCl. It can be adjusted between -1999 and
1.CA. = 1V input calibration. MAX MIN
lower limit (o.lo.l.) and upper limit selected the alarm output can be Lo and 200ms. However, 1.CA. At this state, 1V is applied to the AL.SC. = ALr. menu protection level
for scale (H.SCL.). HI. For Lo, alarm output is energized for FASt rate, each measurement is (H.SCL. -100). input of the device. SET
AL.sC. parameter.
displayed. See NOTE 1 for programming. To initialize calibration, first nonE = No menu is seen.
See NOTE1 for programming. below the alarm setpoint. For HI, alarm
output is energized above the alarm for SLo.1 rate, the average of 4 MAX MIN OSET
P. no = Menu is seen but can not be
MAX MIN
setpoint. If band alarm is selected this successive measurements is displayed. H.SCL. = Upper limit for scale. then keys are pressed programmed.
o.lo.L. = Out value lower limit.
o.lo.L. Can be adjusted between lower parameter can be bI.HI and bo.HI. For for SLo.2 rate, the average of 8 H.sCl. It can be adjusted between (L.SCL. +100) MAX
together and held until ‘CAL' P.yES. = Menu is seen and programming
bI.HI, alarm output is energized successive measurements is displayed. and 4000. message appears. See NOTE 3. is possible.
limit for scale (L.SCL.) and out See NOTE 1 for programming.
between the band. For bo.HI, alarm for SLo.3 rate, the average of 16 See NOTE 1 for programming.
value upper limit (o.UP.l.) MIN
MAX MIN
output is energized out of the band. successive measurements is displayed. No MAX MIN
See NOTE1 for programming. 10.CA. = 10V input calibration. d.C.SC. = ConF. menu protection level
See NOTE1 for programming. See NOTE 1 for programming. CAL.t.=U.ınP.
MAX MIN
MAX MIN 10.CA. At this state, 10V is applied to the D.C.sC. parameter.
a.UP.L. = Alarm value upper limit. input of the device. SET nonE = No menu is seen.
A.UP.L. Hold = Display holding parameter. Yes
Can be adjusted between higher limit for To initialize calibration, first P. no = Menu is seen but can not be
Hold Selecting NonE , this parameter
At this state, the reference voltage or current OSET
programmed.
scale (H.SCL.) and alarm value lower limit that corresponds to L.SCL. parameter is
(a.Lo.L.). becomes inactive. l.inp. then keys are pressed P.yES. = Menu is seen and programming
applied to the input. MAX
See NOTE1 for programming. Selecting Lo. , always the minimum SET together and held until ‘CAL' is possible.
MAX MIN measured value is displayed. To initialize calibration, first then message appears. See NOTE 3. MAX MIN
See NOTE 1 for programming.
OSET MAX
a.Lo.L. = Alarm value lower limit. Selecting Hi. , always the maximum
Uo.SC. = U.oPt. menu protection level
A.Lo.L. Can be adjusted between lower limit for MAX MIN
measured value is displayed. keys are pressed together and held until ‘CAL' Uo.sC. parameter.
scale (L.SCL.) and alarm value upper limit message appears. See NOTE 2.
Unit = Measurement unit. nonE = No menu is seen.
(a.UP.L.). Unit A constant, a message etc. to be P. no = Menu is seen but can not be
See NOTE1 for programming.
displayed can be entered. If a decimal programmed.
MAX MIN
point is desired, it should be included P.yES. = Menu is seen and programming
NOTE 1 Parameter adjustment method At this state, the reference voltage or current
before entering the character. is possible.
SET SET SET SET For including decimal point first, then,
SET
H.inp. that corresponds to HSCL. parameter is See NOTE 1 for programming.
applied to the input. MAX MIN
L.SCL. 1000 999 1000 OSET
SET
d.CA.S. = d.CAL. menu protection level
OSET OSET MIN OSET MAX OSET keys are pressed and held together. To initialize calibration, first then
MAX OSET MAX
D.Ca.s. parameter.
SET And then, by using key decimal point nonE = No menu is seen.
keys are pressed together and held until ‘CAL'
While holding key out set value flashes and by using keys the value can be adjusted. can be adjusted. MIN
P. no = Menu is seen but can not be
message appears. See NOTE 2.
OSET MAX MIN
programmed.
If increment key is pressed and held 0.6 seconds, the value of the selected parameter changes rapidly. P.yES. = Menu is seen and programming
If waited enough, the value increases 100 at each step. After 1 second following the release of the key, is possible.
MAX
initial condition is returned. The same procedure is valid for the decrement key. See NOTE 1 for programming.