Professional Documents
Culture Documents
SecuriFire FCP 2000
Fire Alarm Control Panel • Compact 2–4-loop fire alarm control panel
• Intuitive operation thanks to integrated
Operation functioning of the fire alarm system for a certain
or remote SecuriFire MIC
The compact SecuriFire 2000 fire alarm control length of time in the event of a mains failure, and
• Easy to use planning and commissioning
panel controls the system components and remain fully charged for their entire service life.
tools
evaluates the detector data, either centralised or Due to these high product requirements, the
• Networks up to 16 control panels in
decentralised in the control panels networked in charging and discharging characteristics of the
the SecuriLan
the SecuriLan. The detectors, the wide range of batteries are subject to special requirements,
• Various basic configurations
different input/output modules and the special specifications and tests. Also, the charge curves
• More than 20 languages available
detectors communicate directly with the control of the batteries must exactly match the power
panel via the SecuriLine eXtended. Even already supply unit in use. The installation location for
installed Securiton detectors can be integrated the batteries is on the housing base of each
into a SecuriFire system problem-free. Thanks SecuriFire FCP 2000 control panel; two batter-
to the system design, SecuriFire 2000 is also ies connected in series are used in each case.
tested and approved as a control panel for
single-zone extinguishing systems (EN 12094-1 SecuriLine eXtended
compliant). The detectors and modules of the fire alarm
system are connected to the ring-shaped
Design installed SecuriLine eXtended from the control
In its basic configuration each SecuriFire 2000 panel. The SecuriLine eXtended is a 2-wire
fire alarm control panel comprises a map case field bus that guarantees the highest possible
with cable entry cut-outs in the rear panel; a transmission reliability. Thanks to the short-
main control unit with interfaces for connecting circuit isolator integrated in each SecuriStar
tions between the individual control panels
control panels, peripherals, service PC, a power detector and in each addressable loop module, ensures that each control panel remains
supply unit, mains terminals and battery cable. the SecuriLine eXtended remains fully functional connected with the network even in the event
The main control unit comprises all the neces- even in the event of a fault. If a detector fails or of connection faults.
sary interfaces for connecting with the fire in the event of a short-circuit or wire breakage
services (transmission and alarm unit, interfaces on the line, the detector is isolated and all
for connecting various fire brigade maps), and other detectors and connected input and
five 230 V/3 A relay outputs and a connection output modules remain fully functional, without
for the external device bus (MMI-BUS). The grey restriction, since the fault is isolated. The fault
map case is made entirely of metal, providing is localised and information about its exact
the system with optimum EMC protection. position is shown in plain text on the display
The virtual MIC can be connected with the and output on the printer. This is why cable
integrated Ethernet interface. routing beyond fire sections can be optimised.
A separate calculation program is included for
Power supply computing the maximum possible addressable
The internal 4A power supply unit delivers the loop length based on the connected elements
output voltages of 3.3 V, 5 V and 27 V required and the wire cross-section used.
in every SecuriFire FCP 2000 control panel.
On the underside of the power supply unit SecuriLan
is a 2-pin terminal for connecting the battery For applications that require several fire alarm
and a 10-pin plug-in screw terminal to which control panels, up to 16 control panels can be
external consumers can be connected via five networked in the SecuriLan via SpiderNet.
separately fused outputs. The B6-PSU power Various interfaces (RS485, fibre optic, TCP/IP)
supply unit is equipped with battery monitoring, are available for the connections. The entirely
which is controlled and evaluated by the control freely selectable cabling topology allows the
panel’s main control unit. The emergency power network to be ideally adapted to the structural
batteries must be able to maintain the proper conditions on site. Creating redundant connec-
445 mm 145 mm
1 2 3
4 5 6
7 8 9
400 mm
All specifications subject to
correction. Securiton planning
guidelines are binding.
Specifications subject to change
without notice. Delivery subject
to availability.
Product summary
B6-SCP2010 SecuriFire 2000 basic version
B6-SCP2020 SecuriFire 2000 basic version, with built-in operating panel MIC11
B6-SCP2030 SecuriFire 2000 basic version, with built-in operating panel MIC 11 and printer
B6-SCP2040 SecuriFire 2000 basic version, with built-in operating panel MIC11, printer and cut-out for
EPI devices or Ext. Zone panel
B6-SCP2050 SecuriFire 2000 basic version, with built-in operating panel MIC11 and control map
and cut-out for EPI device or one-sector extinguishing display