MPS P825 / MPS P825S

50 Hz

Features Photos are for reference only

• Compact Structure & High-strength Chassis


• Easy for Operation and Maintenance
• Good Performance Anti-vibration System
• Compliance with International Electrical Safety Standards
• 9/7 Hours Base Tank
• High-performance Free-maintenance Batteries with
Isolation Switch
• 50ºC Radiator
• Top Lifting Point, Fork Lift Holes, Easy for Transportation
• Industrial Type Muffler
• Noise Reduction Structure, Low Overall Noise
• Convenient Power Output Interface and ATS Interface
• IP56 (Control System)
• The Customized Design

Genset Technical Data


Output Frequency 50 Hz
Rated Speed 1500 rpm
Prime Power 750 kVA
Standby Power 825 kVA
Rated Voltage 400 v
Phase 3
Engine Model 4006-23TAG2A
Dimension and Weight
Alternator Model STAMFORD
Generating Set Model MPS P825S MPS P825 Fuel Consumption of 100% load 168.9 L/h
Length (L) mm 5800 3965 Exhaust Gas Flow (after turbo) 180 m³/min.
Width (W) mm 1800 1710 Exhaust Temperature 430ºC
Height (H) mm 2550 2200 Max Back Pressure 6.1 kPa
Dry Weight kg 7530 5480 Max Intake Restriction 3.8 kPa
Tank Capacity L 1350 – Combustion Air 71 m³/min.
Noise Level @1m Full load 90dB – Radiator Air Flow 1200 m³/min.
MPS P825 / MPS P825S

Engine Specifications
Engine Model 4006-23TAG2A
Engine Manufacturer PERKINS
Number of Cylinders 6
Cylinder Arrangement Vertical in-line
Cycle 4 Stroke
Aspiration Turbocharged, air-air charge cooled
Bore x Stroke 160 x 190 mm
Displacement 22.921 Liter
Compression Ratio 13.6
Standby Power/Speed 717 KW / 1500 rpm
Speed Governor Electronic
Cooling System Forced Water Cooling Cycle
Total Lubrication System Capacity 113.4 Liter
Coolant Capacity (with radiator) 105 Liter
Fuel Consumption at 100% load 168.9 L/h (at 1500 rpm)
Starter Motor DC 24 V
Alternator DC 24 V
Alternator Specifications
Alternator Model STAMFORD
Rated Output Prime Power 750 kVA
Efficiency 93.3%
Rated Speed 1500 rpm
Rated Frequency 50 Hz
Phase 3
Rated Voltage 400 V
Exciter Type Self excitation, Brushless
Power Factor 0.8
Voltage Adjust Range ≥±5%
Voltage Regulation NL-FL ≤±1%
Insulation Grade H
Protection Grade IP23
Standby Prime
P.F Standby
Voltage Hz Phase Ratings Ratings
/)
(COS C Amps (KW/kVA) (KW/kVA)
440/254 50 3 0.8 1083 660/825 600/750
415/240 50 3 0.8 1148 660/825 600/750
400/230 50 3 0.8 1191 660/825 600/750
380/220 50 3 0.8 1253 660/825 600/750

Prime Power (PRP): Prime power is available for an unlimited number of annual hours in variable load application, in accordance with
GB/T2820-97 (eqvISO8528); A 10% overload capability is available for a period of 1 hour within a 12-hour period of operation.
Standby Power Rating (ESP): The standby power rating is applicable for supplying emergency power for the duration of a utility power
interruption. No overload, utility parallel or negotiated outage operation capability is available at this rating.
MPS P825 / MPS P825S

Control System
DSE-7320 (Standard)
All MPS Power Gensets have a control cabinet (the Deepsea control module DSE-7320 as standard) mounted on
gensets.

Optional
Main Features
• Manual and Automatic Mode
• Parameter Configuration via RS-232 serial
communication
• Remote Control Automatic Start/Shutdown
• Optional ECU Control
• Optional CAN Engines
• Optional Speed Sensor Access
DSE 8610
• PLC Programming
• Operating Temperature: -20ºC to 70ºC
• IP56 Rating
• Back-Lit icon LCD display
• Power Save Mode
• CAN and Magnetic Pick-up/Alt. versions available (specify
on ordering)
• PC Configurable
• 6 Digital inputs WOODWARD easYgen-3400XT/3500XT
• 4 Outputs (2 configurable on Magnetic Pick up/Alt., 4
configurable) Protecting Functions

The Control Module Display • Over Frequency / Under Frequency


• Over Voltage / Under Voltage
• Generator Voltage • Over Current
• Generator Frequency • Over Speed / Under Speed
• Battery Voltage • Emergency Stop
• Engine Speed • Low Oil Pressure
• Load Current • High Water Temperature
• Engine Run-time Hours • Failure to start / Failure to stop
• Engine Oil Pressure (Panel Meter) • Battery Charger Failure
• Engine Coolant Temperature (Panel Meter) • Comprehensive shutdown or warning on fault condition