Professional Documents
Culture Documents
12 Plex O&m (Definitive Edition)
12 Plex O&m (Definitive Edition)
Phase I
Operation &
Maintenance
Manuals
May 2021
12 Plex Housing Phase I
Operation and Maintenance Manuals
Introduction
The purpose of the procedures outlined in this manual is to provide an adequate and effective
maintenance and operations management practices and standards for 12 Plex Phase I Housing. The
procedures outlined in this manual will provide a clear guideline to be able to practice the correct
management of 12 Plex Phase I. It is intended that thru this manual we can provide maintenance
and operation structures capable of dealing with challenges that could be found in the renovations
of the facilities and equipment.
Project Description
12 Plex Housing is a tow-floor levels building with an area of approximately 800 square meters.
Consist of 12 single occupancy rooms, a toilet and shower room for each room.
Each Floor is distributed in six separate rooms with a closet room and private bathroom, a
mechanical room and an electric room. The construction consists of a slab on grade, reinforced
concrete masonry unit (CMU) exterior and interior walls, and insulated standing seam roofing
system over steel structural deck and supports. The building includes a fire alarm system.
Table of Content
10. Division 28 31 76 – Fire Alarm Control and Mass Notification Panel .......................... 458
Content
2.1 Door Location 12 Plex Housing Phase I
2.2 Hardware Schedule, SPEC 1.3
2.3 Hinges, SPEC 2.2.1
- Stanley 5 Knuckle Full Mortise Hinge FBB199(32D)
- Stanley 5 Knuckle Full Mortise Hinge FBB179
2.4 Locks and Latches, SPEC 2.2.4
- Kaba Simplex 8100
- CL500 Mechanical CL550
- Best 9K Series Cylindrical Lock
2.5 Door Closer, SPEC 2.2.6
- Stanley QDC 100 Door Closer
2.6 Door Protection Plates, SPEC 2.2.7
- Rockwood K1050- Metal Kick Plate US32D/630
2.7 Thresholds, SPEC 2.2.9
- National Guard Products ADA Compliant Bumper Seal Threshold
2.8 Rain Drip, SPEC 2.2.11
- National Guard Products Rain Drip Guard 17
2.9 Weather-stripping, SPEC 2.2.10
- National Guard Products Silicone Dense Bulb Seal 160 S
2.10 Floor and Wall Stop , SPEC 2.2.8
- Rockwood 442- High Dome Stop US26D/626
Door Maintenance
The following items should be periodically checked. The frequency with which these checks are
performed must be established at the discretion of the building owner. Since doors in different
areas of a building access service different traffic, the frequency of periodic inspections would
occur respectively.
1. Hinges: Check all hinges for loose attaching screws, hinge pin wear or other notable
defects. Service the hinges or remove defective parts and replace per the manufacturer’s
recommendations. The door should always swing freely and smoothly without
obstruction from the opened to latched (when latching device is used) position.
2. Locksets and Panic Devices: Check all locksets for loose attaching screws, latch wear or
other notable defects. Service the lockset or remove defective parts and replace per the
manufacturer’s recommendations. The door should always latch freely and smoothly
without obstruction. Self-latching devices should always function freely and smoothly
as the door swings into the closed position. Additional force should not be needed to
achieve latching. Silencers (mutes) should be replaced when latch operation is
compromised by wear.
3. Door and Frame Finish: A general visual inspection of the door and frame finish should
be periodically conducted. Any excessive finish defects should be repaired and
repainted. Adequate protection is needed to help prevent the product from rusting
prematurely and shortening its service life.
4. Gasketing/weather-stripping: A visual and operational inspection is periodically
necessary for gasket or weather-stripped areas such as perimeter seals, threshold seals,
door bottoms, etc. Inspect for signs of deterioration such as splitting, cracking, or
deforming of flexible components. Install replacement components as needed.
Window Maintenance
Regular supervision of the elements is of major importance. Any possible irregularities in the
operation (slowness, unusual sounds) which might occur during maintenance must be reported
immediately to the concerned specialist. Windows should undergo regular maintenance to
prolong their service life and to ensure their functionality and the conservation of value.
1. Remove the dust, grease and graphite annually from the following areas. Clean
hardware exclusively with a soft cloth and mild, pH-neutral cleaning materials in
diluted form.
2. Avoid silicon lubricants, rather use a dry cloth and fitting oil to protect the surface and
prevent dust collection on the hardware parts.
3. Never use aggressive acidifiers cleaning materials or scouring agents. These can cause
damage to the hardware.
2.1
Door Location
1 2 2 2 2 1
4 4
4 4
1 2 2 2 2 1
1 1
1 2 2 2 2 1
4 4
4 4
1 2 2 2 2 1
1 1
DOOR HARDWARE SCHEDULE
12 Plex Housing Phase I
W91278‐19‐F‐0312
Set Door # Hardware Item Quantity Size Reference Finish Mfr Name BHMA Finish
FBB168 – (ANSI A8111) Steel – polished and plated or phosphated and prime coated for painting
FBB199 – (ANSI A2111) Brass or bronze – polished and plated or painted
FBB199 (32) – (ANSI A5111) Stainless steel – highly polished
FBB199 (32D) – (ANSI A5111) Stainless steel – satin finish For exterior doors
• For use on heavy doors or doors where high frequency is expected such as entrance doors to office buildings,
stores, public buildings and corridor entrance doors to offices
• All hinges have template screw hole location for use on either wood or hollow metal doors and frames
• Equipped with four Stanley permanently lubricated non-detachable ball bearings
• Pins in non-ferrous hinges are stainless steel
• Hole in bottom tip for easy pin removal
• Reversible flush tips and pins
• Hinges can be furnished as follows:
with raised barrel (RB)
with electric wires and/or switches (CE and/or CS)
with hospital tips (HT)
with decorative tips
with security studs
with non-removable pins (NRP)
Size Open Gauge Flat Head Screws Quantity Quantity Case Weight
of Metal Per Piece Per Box Per Case Bronze Steel
Inches (mm) Inches (mm) Machine Wood Lbs. (Kg) Lbs. (Kg)
41/2 X 41/2 (114 X 114) .180 (4.6) 8 - 12-24 X 1/2 8 -12 X 11/4 3 EA. 30 EA. 45 (21) 42 (19)
5 X 41/2 (127 X 114) .190 (4.8) 8 - 12-24 X 1/2 8 -12 X 11/2 3 EA. 24 EA. 46 (21) 40 (18)
5X5 (127 X 127) .190 (4.8) 8 - 12-24 X 1/2 8 -12 X 11/2 3 EA. 24 EA. 50 (23) 46 (21)
6 X 41/2 (152 X 114) .203 (5.2) 10 - 1/4 -20 X 1/2 10 -14 X 11/2 3 EA. 24 EA. 63 (29) 53 (24)
6X5 (152 X 127) .203 (5.2) 10 - 1/4 -20 X 1/2 10 -14 X 11/2 3 EA. 24 EA. 65 (30) 55 (25)
6X6 (152 X 152) .203 (5.2) 10 - 1/4 -20 X 1/2 10 -14 X 11/2 3 EA. 24 EA. 76 (35) 61 (28)
8 X 6* (203 X 152) .203 (5.2) 16 - 1/4 -20 X 1/2 16 -14 X 11/2 3 EA. 12 EA. 57 (26) 51 (23)
8 X 8* (203 X 203) .203 (5.2) 16 - 1/4 -20 X 1/2 16 -14 X 11/2 3 EA. 12 EA. 68 (31) 61 (28)
*Available in Steel only
Consult factory for other sizes not listed
E H I N G E S 5
5 KNUCKLE FULL MORTISE HINGES
STANLEY ARCHITECTURAL HIARDWARE
FBB179 – (ANSI A8112) Steel – polished and plated or phosphated and prime coated for painting
FBB191 – (ANSI A2112) Brass or bronze – polished and plated or painted
FBB191 (32) – (ANSI A5112) Stainless steel – highly polished For interior doors
FBB191 (32D) – (ANSI A5112) Stainless steel – satin finish
Size Open Gauge Flat Head Screws Quantity Quantity Case Weight
of Metal Per Piece Per Box Per Case Bronze Steel
Inches (mm) Inches (mm) Machine Wood Lbs. (Kg) Lbs. (Kg)
31/2 X 3 (89 X 76) .123 (3.1) 6 - 10-24 X 1/2 6 -10 X 1 3 EA. 90 EA. 58 (26) 54 (24)
31/2 X 31/2 (89 X 89) .123 (3.1) 6 - 10-24 X 1/2 6 -10 X 1 3 EA. 90 EA. 65 (29) 59 (27)
4 X 31/2 (102 X 89) .130 (3.3) 8 - 12-24 X 1/2 8 -12 X 11/4 3 EA. 48 EA. 43 (19) 39 (18)
4X4 (102 X 102) .130 (3.3) 8 - 12-24 X 1/2 8 -12 X 11/4 3 EA. 48 EA. 45 (20) 42 (19)
41/2 X 4 (114 X 102) .134 (3.4) 8 - 12-24 X 1/2 8 -12 X 11/4 3 EA. 48 EA. 55 (25) 52 (24)
41/2 X 41/2 (114 X 114) .134 (3.4) 8 - 12-24 X 1/2 8 -12 X 11/4 3 EA. 48 EA. 59 (27) 55 (25)
5 X4 (127 X 102) .146 (3.7) 8 - 12-24 X 1/2 4 -12 X 11/4 3 EA. 30 EA. 41 (19) 39 (18)
5 X 41/2 (127 X 114) .146 (3.7) 8 - 12-24 X 1/2 4 -12 X 11/4 3 EA. 30 EA. 45 (20) 43 (19)
5X5 (127 X 127) .146 (3.7) 8 - 12-24 X 1/2 4 -12 X 11/4 3 EA. 30 EA. 50 (23) 46 (21)
*6 X 41/2 (152 X 114) .160 (4.1) 10 - 1/4 -20 X 1/2 5 -14 X 11/2 3 EA. 24 EA. 43 (19) 36 (16)
*6 X 5 (152 X 127) .160 (4.1) 10 - 1/4 -20 X 1/2 5 -14 X 11/2 3 EA. 24 EA. 47 (21) 40 (18)
*6 X 6 (152 X 152) .160 (4.1) 10 - 1/4 -20 X 1/2 5 -14 X 11/2 3 EA. 24 EA. 67 (30) 61 (28)
* Available in Steel only
Consult factory for other sizes not listed
4 5 K N U C K L
2.4 Locks and Latches, SPEC 2.2.4
Simplex ®
Features
Access Control
Mechanical pushbutton lock—eliminates problems and costs associated
with issuing, controlling, and collecting keys and cards. Provides exterior
access by combination, while allowing free egress.
No Battery
Fully mechanical lock eliminates the material and labor expense of battery
replacements
Number of Codes
Single access code—one easy-to-manage code for all users
Programming
Lock is easily programmed via keypad without removing lock from the door
Handing
Factory-handed; not field reversible
Operation Modes
• Pushbutton Access
• Passage (select models)—allows access without using the lock entry
code. Feature activated from the inside with a thumbturn or key
(included with all passage feature models).
• Deadbolt (select models)—added security of 1" deadbolt. Access
Model 8146 Model 8148 permitted by combination or key override.
• Lockout (all models)—disables the lock from the inside so that the
entry codes cannot be used to gain access. Access is permitted using
key override.
Economical
• Combination Entry • Combination Entry A cost effective access control solution
• Key Override • Key Override
(not supplied) (not supplied)
• Passage • Passage
• Lockout • Lockout
• Deadbolt
Mechanical Features
Construction Cast front housing; unified trim plate; fixed ADA—compliant levers
Locking Device Options Mortise with 1" (25 mm) deadbolt, ¾" (19 mm) two-piece anti-friction latch
Mortise with ¾" (19 mm) two-piece anti-friction latch
Numeric Keypad Vandal resistant, solid metal pushbuttons
Handing Factory-handed; not field reversible
Standard Finishes Antique Brass 05 (609), Satin Chrome 26D (626)
Optional Finishes Bright Chrome 026 (625), Bright Brass 03 (605)
Backset 2¾" (70 mm)
Latch ¾" (19 mm) two-piece anti-friction latch; 1" (25 mm) optional deadbolt
Minimum Stile Recommended 5" (127 mm)
Weight 9.8 lbs. (3.7 kg)
Strike 4⅞" (124 mm) L x 1¼" (32 mm) W x ¼" (6 mm) D Deadbolt/Latch mortise strike plate
Key Override
Interchangeable Cores Small format—Best and equivalents (6 or 7-pin length); core not included
Removable Cores Large format—Medeco/ASSA/Yale/Abloy (5 or 6-pin length), Corbin Russwin (6-pin length),
Schlage, and Sargent; core not included
Installation
Door Preparation Easily installs on wood or metal doors. Standard (86) mortise preparation
Door Thickness 1¾" (44 mm) to 2¼" (57 mm)
Items Supplied Include Lock assembly, installation manual, full-scale template, combination change tool, and required
installation hardware
Warranty
Warranty 3-year warranty
2⅜"
(60 mm) C
L P
1
2
3 9"
4 (229 mm)
5
7 ⅜" 8" 5⅞"
(187 mm) (203 mm) (149 mm)
HEAVY DUTY
MECHANICAL
ACCESS
Heavy duty mechanical locks with large
full size lever handles, allowing use as the
primary lock on doors.
The CL500 range of mechanical locks offer a variety of options.
Allows the user flexibility on how to manage entry - by key, code or
passage function entry.
2,047
35mm LIMITED
GUARANTEE
60mm LI
FE TI M E
FEATURES
• Large full size lever handles with return to door
• Passage function access options
• Suitable for interior and exterior use
• Tubular latch and mortise lock models available
• Tumbler alignment for easy code change
• Large three coil lever return spring suitable for high traffic use
• Selected models available in stainless steel or polished brass finish
• Neoprene seals included
9K Series: Heavy Duty Cylindrical Locks
Featured Finishes
BEST 9K sets the standard for
premium-quality, heavy-duty
605: Bright Brass 606: Satin Brass 612: Satin Bronze 613: Oil-rubbed 619: Satin Nickel 625: Bright Chrome
Bronze lock solutions.
bestaccess.com
BA-0250
BEST is a trademark of dormakaba Holding. All rights reserved. © 2017 dormakaba Holding
2.5 Door Closer, SPEC 2.2.6
stanleyhardwarefordoors.com
© 2017 Stanley Black & Decker, Inc. STANLEY® and the STANLEY® Notched Rectangle logo are ST-CH-0233
registered trademarks of Stanley Black & Decker Inc. or one of its affiliates, and are used under license. © 2017 dormakaba Holding
2.6 Door Protection Plates, SPEC 2.2.7
• US3/605
• US4/606
• US9/611
• US10/612
• US10B/613
• US10BE/613E
• US26/625
• US26D/626
• US28/628
• US32/629
• US32316
Specifications: • US32D/630
• US32D316
MATERIAL: • US32DMS
.050" Aluminum, Brass, Bronze, Stainless Steel • Powder Coat
FASTENERS:
#
6 x 5/8" Oval Head Sheet Metal Screws
NFPA 80 STANDARDS - 2-4.5 Protection Plates: Factory-installed protection plates shall be installed in accordance with the listing of the door. Field-installed protection plates
shall be labeled and installed in accordance with their listing.
Exception: Labeling is not required where the top of the protection plate is not more than 16 in. (406 mm) above the bottom of the door.
Project:
Submitted by:
Date:
896
10C
Materials & Finishes
Aluminum alloy 6063, T5 temper
Mill finish
DKB - dark bronze finish
Vinyl is gray
NGP-TPV and silicone are black
1/2"
Optional:
( N) NGP-TPV
1/4"
(S) Silicone
5"
Optional Slip Resistant
SIA Finish
896_cutsheet.pdf 4985 East Raines Road, Memphis, TN 38118 • 800-647-7874 © NGP, Inc. 2017
2.8 Rain Drip, SPEC 2.2.10
Project:
Submitted by:
Date:
17
Material
Aluminum alloy 6063, T5 temper
Finishes
17 Mill Aluminum
17B Gold
17DKB Dark Bronze
Options
FATT - Fast Attach Tape
1 1/2"
3/4"
17_cutsheet.pdf 4985 East Raines Road, Memphis, TN 38118 • 800-647-7874 © NGP, Inc. 2017
2.9 Weather- Stripping, SPEC 2.2.10
Project:
Submitted by:
Date:
160S
10C
Material
Aluminum alloy 6063, T5 temper
Synthetic rubber polymer: Siloxane
Dense silicone is black
Options
FATT - Fast Attach Tape
160S_cutsheet.pdf 4985 East Raines Road, Memphis, TN 38118 • 800-647-7874 © NGP, Inc. 2017
2.10 Floor and Wall Stop, Spec 2.2.8
• US3/605
• US4/606
• US10/612
• US10B/613
• US10BE/613E
• US15/619
• US26/625
• US26D/626
SIZE:
Base: Ø 1 7/8" x 1/4"h
Height: 1 1/8"
WEIGHT:
1.5 lbs./10
ANSI A156.16:
L02141
Specifications:
MATERIAL:
Solid Cast Brass with Rubber Bumper
FASTENER:
#
12 x 1 1/4" Flat Head Wood Screw, Plastic Anchor
FEATURES:
For doors without thresholds (not undercut)
OPTIONS:
Exterior Pack screw packs; stainless steel plated to
match - use EXP suffix (440 x EXP) when ordering
• US3/605
• US4/606
• US10/612
• US10B/613
• US10BE/613E
• US15/619
• US26/625
• US26D/626
SIZE:
Base: Ø 1 7/8" x 1/2"h
Height: 1 1/2"
WEIGHT:
2.8 lbs./10
ANSI A156.16:
L02161
Specifications:
MATERIAL:
Solid Cast Brass with Rubber Bumper
FASTENER:
#
12 x 1 1/2" Flat Head Wood Screw, Plastic Anchor
FEATURES:
For doors with thresholds or undercut doors
OPTIONS:
Exterior Pack screw packs; stainless steel plated to
match - use EXP suffix (442 x EXP) when ordering
• US3/605
• US4/606
• US10/612
• US10BE/613E
• US26/625
• US26D/626
• US32D/630
SIZE:
Ø 2 1/2"
Projection: 1"
WEIGHT:
1.25 lbs./10
ANSI A156.16:
L02251
Specifications:
MATERIAL:
Wrought Brass, Bronze, and Stainless Steel with Rubber Bumper
FASTENERS:
#
8 x 1 1/4" Truss Head Sheet Metal Screw, Plastic Toggle
FEATURES:
Concealed mounting, concave bumper. Back plate prevents damage to wall.
BUMPER:
Concave
Content
3.1 General Purpose Gypsum Board, SPEC 2.1.1
- Continental Building Products, General Purpose Drywall
3.2 Moisture Resistant Gypsum Board, SPEC 2.1.2
- Georgia-Pacific DensArmor Plus Inteiror Panels
Moisture Resistant Gypsum Boards
3.3 Ceramic Floor Tile SPEC 2.1
- Castle-Gate Floor Tile Beige CG15
3.4 Ceramic Wall Tile SPEC 2.1.1
- Castle-Gate Wall Tile Biscuit 0091 (1)
3.5 USG Acoustical Ceiling Panel , SPEC 2.2
- USG Ceiling Solutions, USG Radar Basic Acoustical Panels 2110 ME2110
3.6 USG Acoustical Suspension System SPEC 2.3
- USG Ceiling Solutions, USG Donn Brand DX/DXL Acoustical Suspension System
3.7 Paints and Coatings
Gypsum Board and Cementitious Board Maintenance
A yearly revision of drywall and cementitious boards should be performed. The following
should be checked during this time:
1. Damp Ceiling: Damp/ moisture damaged ceilings can result from something as benign
as a little too much rainfall or as serious as a burst piece of plumbing. To adequately
address this common drywall repair issue, a professional will typically use a sander on
the wet area, and then paint a layer of stain-resistant primer on to head off any potential
water damage in the future, following up with a concealing drywall compound.
2. Popped Nails: The ceiling joists and wall studs that are used in drywall can occasionally
pop out of the wall. If they do, a drywall repair professional usually first removes the
popped nails entirely, replacing them with two brand-new screws each, before applying
several layers of joint and drywall compound.
3. Small Holes: Small holes are usually an easy drywall issue to repair. The quickest
solution is to adhere a drywall maintenance plate, which sticks to drywall via
antiadhesive backing. A drywall professional will then conceal the plate with a layer of
paint.
4. Large Holes: A little more difficult to repair than small holes, large drywall holes must
be completely excised from a wall by cutting out the surrounding section of drywall
entirely. After removing the damaged section, a new piece of drywall will be attached
with screws that are then covered in a layer of joint compound and drywall tape and
finished with painting and sanding to make the area match the rest of the wall.
Porcelain and Ceramic Tile Maintenance
Drawing A101
Applications LIGHTWEIGHT,
Drywall is designed to be easy to use
and decorate for both residential and
GENERAL PURPOSE DRYWALL
LIFTLITE DRYWALL
commercial construction applications.
®
• Interior walls
• Interior ceilings
Note: LiftLite is suitable for interior applications only, and should not be used where
temperatures exceed 125º F for extended periods or in areas of extreme humidity.
Likewise, the board should be protected from exposure to adverse conditions during
storage and construction.
JOB NAME:
CONTRACTOR:
DATE:
Sustainability Physical Characteristics
Can contribute to the U.S. Green Core: Non-combustible, dimensionally Available Sizes:
Building Council’s LEED Credit stable, inert gypsum
Qualification in several credit categories Nominal thickness 1/2 in.
to assist in obtaining LEED certification. Paper: 100% recycled; Front and Nominal width 4 ft.
edges = ivory, back = gray
Standard length † 8 ft., 10 ft., 12 ft.
Long Edges: Tapered Nominal width 54 in.
Asbestos free and Standard length † 12 ft. and 14 ft.
GREENGUARD certified
Nominal weight 1.3 lbs./ft.2 – 1.4 lbs./ft.2
LEED and Recycled Content: 99% †Other lengths available by special order
Installation
For best results, a good gypsum board primer should be applied in accordance with
manufacturer’s instructions before painting or before any textured material is applied.
Handling Recommendations
Stack flat, keep dry and lift (do not drag) to avoid scuffing. Avoid damage to edges.
For detailed recommendations, refer to GA-216 and GA-801.
Safety Precautions
Material Safety Data Sheets (MSDS) are available for all Continental products
upon request.
7/15
3.2 Moisture Resistant Gypsum Board, SPEC 2.1.2
Date
Stamps /Signatures
Technical Service Hotline 1.800.225.6119 or
www.gpgypsum.com
Sizes and Edges Installation
DensArmor Plus Thickness: 1/29 (12.7 mm); Width: 48 (1219 mm); DensArmor Plus® Interior Panels should be installed according to the most current
Lengths: 88-128 (2438 mm-3658 mm); Edges: Tapered versions of Gypsum Association Publication GA-216 “Application and Finishing of
DensArmor Plus Fireguard C Thickness: 1/29 (12.7 mm); Width: 48 (1219 mm); Gypsum Board for Non-Fire-Rated Construction.”
Lengths: 88-128 (2438 mm-3658 mm); Edges: Tapered For fire-rated installations, the installation and details shall be in conformity with
DensArmor Plus Fireguard Thickness: 5/89 (15.9 mm); Width: 48 (1219 mm); those assemblies published in the Gypsum Association Fire Resistance Design
Lengths: 88-128 (2438 mm-3658 mm); Edges: Tapered Manual GA-600, UL and ULC Fire Resistance Directories.
DensArmor Plus Fireguard C Thickness: 5/8 9 (15.9 mm); Width: 48 (1219 mm);
Lengths: 88-128 (2438 mm-3658 mm); Edges: Tapered
Physical Properties
DensArmor Plus® DensArmor Plus® DensArmor Plus®
Properties DensArmor Plus® Fireguard C® Fireguard® Fireguard C®
Thickness, nominal4 1/29 (12.7 mm) 1/29 (12.7 mm) 5/89 (15.9 mm) 5/89 (15.9 mm)
± 1/649 (0.4 mm) ± 1/649 (0.4 mm) ± 1/649 (0.4 mm) ± 1/649 (0.4 mm)
Width, standard4 48 (1219 mm) 48 (1219 mm) 48 (1219 mm) 48 (1219 mm)
± 3/329 (2.4 mm) ± 3/329 (2.4 mm) ± 3/329 (2.4 mm) ± 3/329 (2.4 mm)
Length, standard4 88 (2438 mm) to 88 (2438 mm) to 88 (2438 mm) to 88 (2438 mm) to
128 (3658 mm) 128 (3658 mm) 128 (3658 mm) 128 (3658 mm)
± 1/49 (6.4 mm) ± 1/49 (6.4 mm) ± 1/49 (6.4 mm) ± 1/49 (6.4 mm)
Weight1, nominal, lbs./sq. ft., (Kg/ m 2) 2.0 (9.8) 2.0 (9.8) 2.5 (12.2) 2.4 (12.1)
Edges Tapered Tapered Tapered Tapered
Permeance 7, Perms (ng/Pa • s • m2) >10 (570) >10 (570) >10 (570) >10 (570)
Linear expansion with moisture change,
in/in %RH (mm/mm %RH) 6.25 x 10-6 6.25 x 10-6 6.25 x 10-6 6.25 x 10-6
C oefficient of thermal expansion,
in/in/°F (mm/mm/°C) 8.5 x 10-6 (15.3 x 10-6) 8.5 x 10-6 (15.3 x 10-6) 8.5 x 10-6 (15.3 x 10-6) 8.5 x 10-6 (15.3 x 10-6)
Flexural strength, parallel, lbf.3, 4 (N) ≥ 80 (356) ≥ 80 (356) ≥ 100 (444) ≥ 100 (444)
Flexural strength, perpendicular, lbf.3, 4 (N) ≥ 100 (444) ≥ 100 (444) ≥ 140 (622) ≥ 140 (622)
R Value 2, ft 2• °F • hr/BTU (m2• K/ W) .56 (0.099) .56 (0.099) .67 (0.118) .67 (0.118)
Combustibility 6 Noncombustible Noncombustible Noncombustible Noncombustible
Nail pull resistance, lbf.3, 4 (N) ≥ 80 (356) ≥ 80 (356) ≥ 90 (400) ≥ 90 (400)
Hardness core, edges and ends, lbf. (N) ≥15 (67) ≥15 (67) ≥15 (67) ≥15 (67)
Water absorption (% of weight) 3, 4 < 5 <5 <5 <5
Surface water absorption 3, 4 < 1.6 grams < 1.6 grams < 1.6 grams < 1.6 grams
S urface burning characteristics
(per ASTM E84 or CAN/ULC S102):
flame spread/smoke developed 0/0 0/0 0/0 0/0
Humidified deflection 3, 4 ≤ 2/89 (6.4 mm) ≤ 2/89 (6.4 mm) ≤ 1/89 (3 mm) ≤ 1/89 (3 mm)
Bending radius 5 68 (1829 mm) 68 (1829 mm) 88 (2438 mm) 88 (2438 mm)
1
Represents approximate weight for design and shipping purposes 5
Double fasteners on ends as needed
2
Tested in accordance with ASTM C518 6
As defined and tested in accordance with ASTM E136 or CAN/ULC S114.
3
Tested in accordance with ASTM C473 7
Tested in accordance with ASTM E96 (dry cup method)
4
Specified values per ASTM C1658 and ASTM C1177
TRADEMARKS Unless otherwise noted, all trademarks are owned by or licensed to Georgia-Pacific
Gypsum LLC. Collaborative for High Performance Schools and CHPS are trademarks owned by
Collaborative for High Performance Schools Inc.
WARRANTIES, REMEDIES AND TERMS OF SALE For current warranty information for this
product, please go to www.gpgypsum.com and select the product for warranty information. All sales
U.S.A. Georgia-Pacific Gypsum LLC of this product by Georgia-Pacific are subject to our Terms of Sale available at www.gpgypsum.com.
Georgia-Pacific Gypsum II LLC
Canada Georgia-Pacific Canada LP UPDATES AND CURRENT INFORMATION The information in this document may change without
notice. Visit our website at www.gpgypsum.com for updates and current information.
Sales Information and Order Placement
U.S.A. West: 1-800-824-7503 CAUTION For product fire, safety and use information, go to www.buildgp.com/safetyinfo
Midwest: 1-800-876-4746 or call 1-800-225-6119.
South Central: 1-800-231-6060 FIRE SAFETY CAUTION Passing a fire test in a controlled laboratory setting and/or certifying or
Southeast: 1-800-327-2344 labeling a product as having a one-hour, two-hour, or any other fire resistance or protection rating
Northeast: 1-800-947-4497
and, therefore, as acceptable for use in certain fire rated assemblies/systems, does not mean that
CANADA Canada Toll Free: 1-800-387-6823 either a particular assembly/system incorporating the product, or any given piece of the product
Quebec Toll Free: 1-800-361-0486 itself, will necessarily provide one-hour fire resistance, two-hour fire resistance, or any other
TECHNICAL INFORMATION specified fire resistance or protection in an actual fire. In the event of an actual fire, you should
U.S.A. and Canada: 1-800-225-6119, www.gpgypsum.com immediately take any and all actions necessary for your safety and the safety of others without
regard for any fire rating of any product or assembly/system.
©2014 Georgia-Pacific Gypsum LLC. All rights reserved. 1/14. GP-TM Lit. Item #532248.
3.3 Ceramic Floor Tile SPEC 2.1
18 x 18 17-3/4" x 17-3/4"
F W C
5/16" 18.00 8
Floor Tile (45.20 cm x 45.20 cm)
APPLICATIONS
TARGET
SUITABLE
DCOF WET
12 x 12 11-13/16" x 11-13/16"
5/16" 15.00 15
Floor Tile (30.00 cm x 30.00 cm) *
Dry & Level – Interior Floor N/A
*
Wet & Level – Interior Floor ≥ 0.42
9 x 12 9" x 12"
5/16" 11.25 15
Wall Tile p (22.91 cm x 30.54 cm) **
Shower Floors (Residential or Light Commercial) ≥ 0.42
A DCOF value of ≥ 0.42 is the standard for tiles specified for level interior spaces
Wall Bullnose (9" side) p 3x9 S-4309 54 expected to be walked upon when wet, as stated in ANSI A137.1-2012, Section 9.6.
For more information about DCOF and the DCOF AcuTest™, visit
Wall Bullnose Corner p 3x3 SN-4309 32 americanolean.com/DCOF.
APPLICATION NOTES:
Mosaic Bullnose p 2x2 S-886 108 Floor tile suitable for exterior applications in freezing and non-freezing climates, when
proper installation methods are followed.
p Ceramic body ■ Dot-mounted Wall and mosaic tile suitable for exterior applications in non-freezing climates, when
proper installation methods are followed.
* Wall tile not suitable for this application
** Mosaic tile only
INSTALL ATION & PRICING
RECOMMENDED GROUT JOINT: SHADE VARIATION
Floor: 3/16" (Overlap should not exceed 33% when installing tile with a length of NOTES
15" or greater in a staggered brick-joint pattern.)
Since there are variations in all fired ceramic and natural products, tile and trim
Wall: 1/16" supplied for your particular installation may not match samples. Final confirmation should
Mosaic: 1/8" HIGH be made from actual tiles and trim prior to installation. Manufactured in accordance with
(V3) ANSI A137.1 standards.
RELATIVE PRICING: Low
Not for use on ramps. Water, oil, grease, improper drainage and certain footwear can
create slippery conditions. Floor applications expected to be exposed to these conditions
require extra caution in product selection.
PERFORMANCE CHARACTERISTICS For additional information refer to “Factors to Consider” at: americanolean.com/Factors.
Special consideration needs to be given when installing tiles greater than 15 inches. Please
FLOOR WALL MOSAIC
ASTM# refer to americanolean.com/LargeTiles for more information.
RESULT RESULT RESULT
Use of a latex modified thin-set is recommended for installation. For more information,
Water Absorption C373 < 0.5% < 20.0% < 3.0% visit americanolean.com.
Breaking Strength C648 > 275 lbs. 120 - 230 lbs. > 250 lbs.
ICE WHITE WHITE BISCUIT SALT & PEPPER GLOSS ALMOND CAPPUCCINO MUSHROOM NUTMEG
0025 (1) u 0090 (1) 0091 (1) u 0045 (1) 0012 (1) 0078 (1) 0038 (2) 0037 (2)
SAND DOLL AR MARSHMALLOW LEMON CHILI PEPPER ANTIQUE ROSE POMEGRANATE ARTICHOKE DILL PICKLE
0050 (1) 0065 (1) CHIFFON Q074 (4) v Q073 (4) v Q072 (4) v 0063 (1) l 0083 (2) l
0044 (1)
SUMMER RAIN SAPPHIRE SKY LIGHT SMOKE STORM GRAY SMOKEY QUARTZ GLOSS BL ACK
0081 (1) 0070 (3) S 0042 (1) 0040 (2) 0047 (2) l 0049 (2) u
LEMON ZEST MANDARIN WATERMELON GREEN APPLE SHAMROCK PEACOCK BLUE RUBY RED GRAPE SODA
Q075 (4) v ORANGE SORBET Q076 (4) v GREEN Q084 (4) v 0121 (5) S Q079 (4) v S
Q077 (4) v Q070 (4) v Q078 (4) v
M AT T E
MATTE MATTE SNOW MATTE BISCUIT MATTE ALMOND MATTE MATTE MATTE MATTE SAND
DESIGNER MIST 0092 (1) u 0087 (1) CAPPUCCINO MUSHROOM NUTMEG DOLL AR
WHITE 0061 (1) u 0095 (1) 0009 (1) 0041 (2) 0039 (2) 0067 (1)
MATTE MATTE DILL MATTE GL ACIER MATTE BIMINI MATTE LIGHT MATTE SMOKEY MATTE BL ACK
ARTICHOKE PICKLE 0062 (1) BLUE SMOKE 0004 (1) QUARTZ 0064 (2) u
0069 (1) l 0066 (2) l 0085 (2) l 0028 (2) l
(1), (2), (3), (4) & (5) notations indicate price group, (1) being the least expensive.
u Available in chair rail v These colors are special order and require 1-2 weeks for delivery from date of order.
S Subject to crazing, do not use black grout. l These colors are made to order and require 6-8 weeks for delivery from date of order.
B R I G H T & M AT T E ™
G L A Z E D C E R A M I C WA L L
LOW
6x6 6" x 6" (V1)
5/16" 12.50 50
Wall Tile (15.20 cm x 15.20 cm)
Radius Bullnose 6x6 A-3602 44 1n Dry & Level – Interior Floor N/A
Flat White
050
APPLICATIONS SUBSTRATE
• Schools • Wet-formed mineral fiber
• Corridors
• Offices
• Retail stores
USG RADAR™ BASIC ACOUSTICAL PANELS ORDER SAMPLES/LITERATURE
USG: samplit@usg.com
fax: 888 874-2348 | usg.com
FOR MOST UP-TO-DATE
TECHNICAL INFORMATION
AND LEED REPORT TOOL
CGC: contact Sales Representative usgdesignstudio.com
cgcdesignstudio.com
TECHNICAL SERVICES
800 USG.4YOU (874-4968)
PRODUCT CERTIFIED YEAR HIGH RECYCLED
FOR LOW CHEMICAL AVAILABILITY CONTENT
EMISSIONS: 2110, 2120, 2310, 2742
UL.COM/GG
UL 2818
UL Classified
Edge Panel Size Imperial Fire Item No. Imperial NRC CAC LR3 Color6 Grid VOC Recycled Panel
Metric (mm) Rating2 Metric (mm) Min. Options Emissions Content1 Cost
USG RADAR™ SQ 2'x2'x5/8" Class A 2110 0.55 33 0.83 White A,B Low 25% $
BASIC PANEL 600x600x15 ME2110
FLB 2'x2'x5/8" Class A 2130 0.55 33 0.83 White D,E,F,G Low 25% $
USG RADAR™ BASIC TILE4, 5 BESK 12"x12"x5/8" Class A 2990 0.505 405 0.83 White H Low 44% $$$
USG RADAR™ ILLUSION SLT 2'x4'x3/4" Class A 2742 0.55 35 0.83 White C Low 25-26% $$
BASIC TWO/24 PANEL
SC2288/rev. 8-18 Manufactured by The trademarks USG, CGC, CENTRICITEE, DONN, DX, DXF, DXFF, DXI, DXL, Safety First! Follow good safety/industrial hygiene
© 2018 USG Corporation and/or USG Interiors, LLC DXT, DXW, FINELINE, FIRECODE, IDENTITEE, RADAR, IT’S YOUR WORLD. practices during installation. Wear appropriate personal
its affiliates. All rights reserved. 550 West Adams Street BUILD IT., the USG/CGC logo, the design elements and colors, and related protective equipment. Read SDS and literature before
Printed in USA Chicago, IL 60661 marks are trademarks of USG Corporation or its affiliates. specification and installation.
3.5 USG Acoustical Suspension System, SPEC 2.2
• No Visible Sag
• Mold/Mildew Protection
15/16" TEE SYSTEM10 Intermediate 12' USG DX/DXL24 Flat White A-C 7/8" Molding 12 lb./LF 6.1 lb./ 3.6 lb./LF
Duty 3600 mm 1.64" (42 mm) Standard ACM7 Clip LF
Main Tee
Advantage
CGC DX/DXL24HRC
1.5" (38 mm)
Heavy Duty 12' USG DX/DXL267 Flat White A-F 7/8" Molding 16 lb./LF 7.3 lb./LF 4.9 lb./LF
3600 mm 1.64" (42 mm) Standard ACM7 Clip
DX/DXL26HRC
Advantage
CGC
1.5" (38 mm)
Cross Tee 1-1/2" 20" 1" (25 mm) DX2016 Class A Flat White
30" 1" (25 mm) DX3016 Class A Flat White
3' 1-1/2" (38 mm) DX324 Class A Flat White
4' 1-1/2" DX/DXL424 Flat White
1200 mm 38 mm Standard and Advantage
DX/DXL424HRC
4' (1200 mm) 1" (25 mm) DX416 Class A Flat White
4' (1200 mm) 1-1/2" (38 mm) DX426 HD Class A Flat White
5' (1500 mm) 1-1/2" (38 mm) DX/DXL524 Flat White
Standard
6' 1-1/2" (38 mm) DX624 Class A Flat White
8' 1-1/2" (38 mm) DX824 Class A Flat White
Wall Angle Length Item No. Color
2"
7/8"
M7HRC
11/4" 3/4"
STANDARD COLORS 4
Flat White Flat Black Parchment Manila Beige Straw Sandstone Taupe
050 205 103 246 142 143 090 107
ADVANTAGE COLORS 4
FEATURES AND BENEFITS
• 15/16" exposed tee system. Components for use in general and
fire-rated applications. Breeze Blue Grey Azure Slate Spruce Tuscany Sorbet Squash
2659 564 2660 568 567 2663 2658 2661
• Maximum economy and design simplicity.
• Compatible with USG Logix™ Integrated Ceiling System.
• USG DXL™ system features more than 80 UL designs (up to three hours).
Safari Halo Sienna Redwood Nectar Silvertone Quartz Bronze
• Cross-tee override-ends resist twisting and give a professionally 2662 206 565 566 546 052 082 033
finished look.
PROFILE EDGE DETAIL
• Meets or exceeds all national code requirements, including seismic.
• Proprietary Quick-Release™ cross tees.
• High recycled content (HRC) available.
• Custom colors available. Square Edge Shadowline Tapered Shadowline
Summary of Areas
Summary of Areas
Outside Handrail
SW 7723
Product: F80WSA51 – Kem Enamel Metal 2 Coats
Industrial Fast Dry System 4000 High Gloss Colony Buff
Base E.W. / Industrial Reducer R2K4-1
Air Base José Enrique Soto Cano
Project: 12PLEX
Air Base located in Palmerola
Comayagua, Honduras
Detail of Areas
Area: Outside
Application: 2 Coats
Reference Images:
Air Base José Enrique Soto Cano
Project: 12PLEX
Air Base located in Palmerola
Comayagua, Honduras
Detail of Areas
Area: Inside
Application: 2 Coats
Reference Images:
Air Base José Enrique Soto Cano
Project: 12PLEX
Air Base located in Palmerola
Comayagua, Honduras
Detail of Areas
Application: 2 Coats
Reference Images:
Air Base José Enrique Soto Cano
Project: 12PLEX
Air Base located in Palmerola
Comayagua, Honduras
Detail of Areas
Application: 2 Coats
Reference Images:
Air Base José Enrique Soto Cano
Project: 12PLEX
Air Base located in Palmerola
Comayagua, Honduras
Detail of Areas
Substrate: Metal
Application: 2 Coats
Reference Images:
Air Base José Enrique Soto Cano
Project: 12PLEX
Air Base located in Palmerola
Comayagua, Honduras
Detail of Areas
Substrate: Metal
Application: 2 Coats
Reference Images:
Air Base José Enrique Soto Cano
Project: 12PLEX
Air Base located in Palmerola
Comayagua, Honduras
Detail of Areas
Substrate: Metal
Application: 2 Coats
Reference Images:
4. Division 10 28 13 – Toilet Accessories
Content
4.1 Paper Towel Dispenser, SPEC 2.2.10
-ASI American Specialties, INC. Surface Mounted Roll Paper Towel Dispenser
4.2 Double Robe Hook, SPEC 2.2
- ASI American Specialties, INC. Double Robe Hook
4.3 Surface Mounted Shelf, SPEC 2.2
- ASI American Specialties, INC. Surface Mounted Shelf
4.4 Channel Frame Mirror , SPEC 2.2.2
- ASI American Specialties, INC. Channel Frame Mirror
4.5 Vinyl Shower Curtain, SPEC 2.2.4
- ASI American Specialties, INC. Vinyl Shower Curtain
- ASI American Specialties, INC. Shower Curtain Rod with Concealed, SPEC 2.2.5
4.6 Shower Mounted Towel Shelf, SPEC 2.2.8
- ASI American Specialties, INC. Surface Mounted Towel Shelf with Drying Rod and
Support Brackets
4.7 Soap Dish With Drain Holes, SPEC 2.2.7
- ASI American Specialties, INC. Soap Dish with Drain Holes
4.1 Paper Towel Dispenser, SPEC 2.2.10
SPECIFICATION
Surface Mounted Roll Paper Towel Holder with controlled delivery spindle shall hold and dispense all standard core roll paper towels up to 6"
(152mm) in dia. and shall be fabricated of die cast aluminum with a satin matte silver-gray finish. The “no waste” rocking action spindle shall be
fabricated of impact resistant, ABS thermoplastic and be theft resistant with a concealed release mechanism. Spindle shall rotate 1/2 revolution for
each operation and return to its original position. Roll core shall not be removable until paper is exhausted.
Surface Mounted Roll Paper Towel Holder (controlled delivery) shall be Model No 8165 as fabricated by American Specialties, Inc. 441
Saw Mill River Road Yonkers, New York 10701-4913
INSTALLATION
Unit is surface mounted on wall using N o10 self tapping screws (supplied). For compliance with ADA Accessibility Guidelines, unit should be
installed so that roll centerline is 54" (1372mm) maximum above finished floor (AFF) if clear floor side reach access is provided or 48" (1219mm)
max. AFF if clear floor forward reach access is provided or 46" (1168mm) max. AFF if side reach over an obstruction is only provided (i.e. vanity).
OPERATION
Spindle revolves 1/2 revolution for each operation and then returns to its original position. Paper towel roll core prevents access to release pin and
cannot be removed from spindle until exhausted. Unit is replenished by releasing a concealed pin which in turn releases a spring lock mechanism
on spindle.
THIS MANUFACTURER RESERVES THE RIGHT TO MAKE CHANGES IN DESIGN OR DIMENSIONS WITHOUT FORMAL NOTICE
4.2 Double Robe Hook, SPEC 2.2
SPECIFICATION
Double Robe Hook shall be fabricated of stainless steel alloy 18-8, type 304. Post shall be 1/2" x 1" (13mm x 25mm)
rectangular tubing with formed mounting flange and bracket welded on end. Bow plate shall be 14 gauge, 4" x 1" (102mm x
25mm) with radiused corners and internally welded to outer end. Mounting plate shall be included and shall be 18 gauge. A
stainless steel setscrew shall be provided on bottom perimeter of flange to lock unit to mounting plate. Surface finish shall be
bright or satin as chosen by option and indicated by code suffix.
Double Robe Hook shall be Model No 7345-B or No 7345-S of American Specialties, Inc., 441 Saw Mill River Road,
Yonkers, New York 10701-4913
INSTALLATION
Surface mount unit on door back or wall using No 10 self tapping screws (by others) through holes provided in mounting plate
into suitable prepared mountings (by others) or other suitable mounting hardware (by others) to suit door or wall conditions.
Hang post and flange assembly on mounting plate and tighten setscrew to lock unit to plate. For compliance with ICC/ANSI
A-117.1-2003 and ADA Accessibility Guidelines install unit with top of hook 48" (1219mm) maximum above finished floor
(MAX AFF) if clear floor forward reach or if clear floor side reach access only is provided or 46" (1168mm) MAX AFF if side
reach access over an obstruction (e.g. vanity) with reach depth greater than 10" (254mm) and less than 25" (635mm) is only
provided or 44" (1118mm) MAX AFF if forward reach over an obstruction with reach depth greater than 20" (508mm) and
less than 25" (635mm) is only provided. For general utility install hook with centerline of mounting plate 68" (1727mm) AFF.
OPERATION
Hook is suitable for robes or clothing and small carry bags.
Accessory Specialties AMERICAN DISPENSER Desert Ray Products ,INC.
THIS MANUFACTURER RESERVES THE RIGHT TO MAKE CHANGES IN DESIGN OR DIMENSIONS WITHOUT FORMAL NOTICE
4.3 Surface Mounted Shelf, SPEC 2.2
SPECIFICATION
Surface Mounted Shelf shall be fabricated of alloy 18-8 stainless steel, type 304. Brackets shall be 16 gauge and shelf shall be 18
gauge, with a 1/2" (13) lip on all four (4) sides. Front lip shall be hemmed under for safety. All exposed surfaces shall be No 4 satin
finish and shall be protected during shipment with PVC film easily removable after installation. Structural assembly of shelf
and bracket supports shall be of welded construction. Shelf shall be sized and brackets located as per standard schedule or shall be
custom fabricated to customer supplied drawing. Scheduled shelves equal to or less than 8" (203) deep shall have standard 4" (102)
high brackets and shelves in the depth range greater than 8" (203) to 12" (305) shall have 6" (152) high brackets. Consult factory for
shelves deeper than 12" (305).
Surface Mounted Shelf shall be Model No 0692-xxx as manufactured by American Specialties, Inc., 441 Saw Mill River Road,
Yonkers, New York 10701-4913
SCHEDULE OF AVAILABILITY
SHELF DEPTH & MODEL SUFFIX ADDER SHELF LENGTH DIMENSIONS/BRACKET SPACING
THIS MANUFACTURER RESERVES THE RIGHT TO MAKE CHANGES IN DESIGN OR DIMENSIONS WITHOUT FORMAL NOTICE
4.4 Channel Frame Mirror, SPEC 2.2.2
5/8"
WIDTH 1" [25] [16]
TYP CHANNEL
1-3/4" [44] FRAME
TYP
1/2" [13]
TOP WALL
BRACKET
TOP MIRROR
BRACKET
BOTTOM WALL
3/4" [19] BRACKET
TYP
THEFT-RESISTANT
1/2" [13]
PICTORIAL VIEW NOTE
LOCKING SCREW
OUTLINE
Dimensions ALL DIM’S INCH [MM] OF MIRROR
VERTICAL SECTION
18" W x 24" H ILLUSTRATION FOR REF ONLY AND NTS
SPECIFICATION
Channel Frame Mirror shall have frame of 20 gauge type 304 stainless steel alloy 18-8, with mitered corners. Mirror glazing shall be _____
(insert glazing option) and shall be warranted for 15 years against silver spoilage. All edges of mirror shall be protected by friction and chafe
absorbing fillers. Back of mirror shall be protected by full size shock-absorbing water-resistant filler and full size one piece 20 gauge corrosion
protected steel. Top and bottom wall mounting brackets shall be 20 gauge corrosion protected steel and shall be spot welded into “H” hanger.
Mirror shall be secured to lower bracket with a Phillips Pan Head locking screw.
Channel Frame Mirror shall be Model № 0620-_____(insert glazing option)________________ (note size, W x H) as manufactured by
American Specialties, Inc., 441 Saw Mill River Road, Yonkers, New York 10701-4913
MATERIALS
Frame: 20 gauge type 304, 18-8, stainless steel. Roll-formed one piece construction. Exposed surfaces shall be satin finish. Edges and
corners are burr free.
Glass: Standard glazing is № 1 quality, 1/4" [6,4] thick plate/float, silver coated and hermetically sealed with a uniform copper plating,
and warranted against silver spoilage for 15 years. Mirrors meet Federal Spec DD-M-411C, ASTM C- 1503, and ASTM C-1036-
91.
Filler: Expanded polyethylene microcell foam sheet material, abrasion resistant and shock absorbing, water resistant, 1/8" [3,2] total layer
thickness.
INSTALLATION
Install “H” wall brackets level and plumb per diagram location using ONLY № 8 or № 10 Pan Head screws (by others). Hang mirror on
brackets and tighten locking screw (№ 6-32F x 3/4" Philips Pan Head, supplied separately taped to mirror back) at bottom (note: this screw
should be started prior to hanging mirror on wall bracket). For compliance with 2010 ADA Accessibility Standards and ABA Standards 2015,
bottom edge of reflecting surface should be no higher than 40" [1016] AFF (Above Finished Floor).
GLAZING OPTIONS
Units are supplied with 1/4" [6] thick plate glass. Other glazing options are available. For a complete description of any other available
glazing, see the MIRROR GLAZING OPTIONS char t.
THIS MANUFACTURER RESERVES THE RIGHT TO MAKE CHANGES IN DESIGN OR DIMENSIONS WITHOUT FORMAL NOTICE
4.5 Vinyl Shower Curtain, SPEC 2.2.4
SPECIFICATION
Shower Curtain shall be fabricated of .008" [0,203] thick vinyl treated with Macrobiotic KV-33 anti-bacterial, anti-fungal and anti-
mildew agent, and flame retardant agents. Protection agents shall remain in effect after repeated low-temperature mild soap washing and
air-drying cycles. Top hem shall be 1-1/2" [38] wide, backing reinforced and heat-sealed above and below grommet row. Bottom hem
and vertical edges shall be plain edge. Clear anodized aluminum grommets with 3/8" inside diameter [Ø9.5] shall be machined into top
hem at 6-1/2" ± 1/2" [165 ± 13] intervals on centers starting at 1-1/4" ± 1/4" [32 ± 6] from edges. Color shall be white. Pattern is San
Suede Pebble Emboss № SS9700. Vinyl curtain shall conform to Federal Specification L-C-780-A, L-C-780-A amendment 2, ASTM G-
21-96 for fungal and mildew resistance and CID A-A-2398B.
Vinyl Shower Curtain shall be Model № 1200-Vxx (specify size per chart) of American Specialties, Inc., Yonkers, NY 10701-4913
INSTALLATION
For openings up to 42" [1067] wide curtains should be specified an additional 6" [152] wider than opening and 12" [305] wider for open-
ings exceeding 42" [1067]. Shower curtain should be attached with hooks (not provided, order separately) to rod (not provided, order
separately). Curtain hooks Model № 1200-SHU are recommended.
SIZE SPECIFICATION
OPENING XX OPENING XX OPENING XX
30" [762] 36" [914] 42" [1067] 48" [1219] 60" [1524] 72" [1829]
36" [914] 42" [1067] 48" [1219] 60" [1524] 72" [1829] 84" [2134]
CURTAIN WIDTH HOOK COUNT CURTAIN WIDTH HOOK COUNT CURTAIN WIDTH HOOK COUNT
THIS MANUFACTURER RESERVES THE RIGHT TO MAKE CHANGES IN DESIGN OR DIMENSIONS WITHOUT FORMAL NOTICE
4.6 Shower Curtain Rod with Concealed
SPECIFICATION
Shower Curtain Rod with Concealed Mounting Flanges shall have rod fabricated of alloy 18-8 stainless steel, type 304, No20 gauge 1" dia. tubing.
Exposed finish shall be satin and shall be protected during shipment with a plastic bag. Length shall be as specified. Concealed Mounting Flanges
shall be chrome plated brass with a satin finish. Pair of flanges shall each consist of a wall mounting lug and a locking sleeve. One sleeve shall have
locking screw to prevent rod rotation. Mounting lugs shall be provided with (2) mounting holes to accept #10 round or pan head screws (furnished
by others).
Shower Curtain Rod with Concealed Mounting Flanges shall be Model No 1224-XXX as fabricated by American Specialties, Inc., 441 Saw
Mill River Road, Yonkers, New York 10701-4913
INSTALLATION
Rod is installed in straight section between two (2) mounting flanges. Rods longer than 72" (1829mm) require ceiling hanger Model No1224-C18.
For use with standard shower curtain model No’s 1200 or 1200-V having 72" (1829mm) length and standard hooks Model No1200-SHU unit should
be installed with rod centerline 74-1/2" (1892mm) AFF or 67" (1702mm) above tub rim to obtain 6" (152mm) bottom overlap.
SURFACE MOUNTED TOWEL SHELF WITH DRYING ROD AND SUPPORT BRACKETS
SPECIFICATION
Surface Mounted Towel Shelf with Drying Rod and Support Brackets shall be fabricated of stainless steel alloy 18-8, type 304.
Shelf posts shall be 1/2" x 1" (13mm x 25mm) rectangular tubing with formed mounting flange and bracket welded on end.
Cross tubes shall be 3/8" diameter (Ø10mm) and shall be held in receiver holes in support posts. A solid stainless steel 1/4"
diameter (Ø 6.4mm) drying rod shall be attached at midpoint of support posts and support brackets shall be provided. Mounting
plates shall be included and shall be 18 gauge. Stainless steel setscrews shall be provided on bottom perimeter of flanges to
lock unit to mounting plates. Surface finish shall be bright or satin as chosen by option and indicated by code suffix. Length
shall be as chosen from schedule and indicated by code suffix.
Surface Mounted Towel Shelf with Drying Rod and Support Brackets shall be Model No 7310-B __or No 7310-S __ of
American Specialties, Inc., 441 Saw Mill River Road, Yonkers, New York 10701-4913
INSTALLATION
Surface mount unit on wall using No 10 self tapping screws (by others) through holes provided in mounting plates into suitable
prepared mountings (by others) or other suitable mounting hardware (by others) to suit wall conditions. Hang post and flange
assembly on mounting plates and tighten setscrews to lock unit to plates. For compliance with ICC/ANSI A-117.1-2003 and
ADA Accessibility Guidelines install unit with top of shelf 48" (1219mm) maximum above finished floor (MAX AFF) if clear
floor forward reach or if clear floor side reach access only is provided or 46" (1168mm) MAX AFF if side reach access over
an obstruction (e.g. vanity) with reach depth greater than 10" (254mm) and less than 25" (635mm) is only provided or 44"
(1118mm) MAX AFF if forward reach over an obstruction (e.g. commode) with reach depth greater than 20" (508mm) and
less than 25" (635mm) is only provided. For general utility install 68" (1727mm) MAX AFF.
THIS MANUFACTURER RESERVES THE RIGHT TO MAKE CHANGES IN DESIGN OR DIMENSIONS WITHOUT FORMAL NOTICE
4.8 Soap Dish with Drain Holes, SPEC 2.2.7
SPECIFICATION
Soap Dish With Drain Holes shall be fabricated of stainless steel alloy 18-8, type 304. Soap dish shall be of drawn seamless
construction and shall be fabricated with integral ribs. Support post shall be 1" x 1/2" (25mm x 13mm) rectangular tubing with
formed mounting flange and bracket welded on end. A stainless steel setscrew shall be provided on bottom perimeter of
flange to lock unit to mounting plate. Mounting plate shall be provided and shall be 18 gauge. Surface finish shall be bright
or satin as chosen by option and indicated by code suffix.
Soap Dish With Drain Holes shall be Model No 7320-B or No 7320-S of American Specialties, Inc., 441 Saw Mill River Road,
Yonkers, New York 10701-4913
INSTALLATION
Surface mount unit on wall using No10 self tapping screws (by others) through holes provided in mounting plate into suitable
prepared mountings (by others) or other suitable mounting hardware (by others) to suit wall conditions. Hang post and flange
assembly on mounting plate and tighten setscrew to lock unit to plate. For compliance with ICC/ANSI A-117.1-2003 and
ADA Accessibility Guidelines install unit with top of soap dish 48" (1219mm) maximum above finished floor (MAX AFF) if
clear floor forward reach or if clear floor side reach access only is provided or 46" (1168mm) MAX AFF if side reach access
over an obstruction (e.g. vanity) with reach depth greater than 10" (254mm) and less than 25" (635mm) is only provided or 44"
(1118mm) MAX AFF if forward reach over an obstruction with reach depth greater than 20" (508mm) and less than 25"
(635mm) is only provided. For general utility mount unit with top of soap dish 8" to 12" (203mm to 305mm) above vanity
basin.
OPERATION
Soap dish has raised ribs to elevate soap slightly above dish surface to promote drying. Drain holes in bottom of dish allow
excess water to drain away from soap.
Accessory Specialties AMERICAN DISPENSER Desert Ray Products ,INC.
THIS MANUFACTURER RESERVES THE RIGHT TO MAKE CHANGES IN DESIGN OR DIMENSIONS WITHOUT FORMAL NOTICE
5. Division 21- Fire Suppression
presupuestos@suprefuego.com
1
presupuestos@suprefuego.com
1. DESCRIPTION
2. OPERATING INSTRUCTION
2.1 START-UP OPERATION OF THE SPRINKLER SYSTEM
A- Waterflow sensor
B- Check Valve w/ trim
C- Control Riser Valve
D- Test Header Control Valve
E- 2.5” Hose Valve
F- Fire Department Connection (FDC)
G- Main Drain Valve
H- Test and Drain Valve
I- Double check valve
RISER
2
presupuestos@suprefuego.com
2.1.4. Slowly open the Riser control valve “C”, when the
water begins to flow, the flow sensor activates the
alarm and detection system.
2.1.6. Notify the fire station that the system is ready for
operation.
3
presupuestos@suprefuego.com
2.2.2. Place the test and drain valve “H” in the "DRAIN"
position, which is located at the outer end of the
building.
Drain
2.3.1. Verify that the control valves are fully open and
the drain valves are closed.
4
presupuestos@suprefuego.com
3. EMERGENCY OPERATIONS
3.1. Make sure the fire is out! Make a complete
inspection of all areas covered by the system,
including areas not involved in the fire area.
5
presupuestos@suprefuego.com
5. REPAIR
5.1. RECOMMENDED SPARE PARTS: The spare sprinkler head box
will contain the recommended quantity of spare,
sprinklers per NFPA 13, along with a sprinkler head
and an NFPA 25-2017
List Of Spares Provided
# Description Unit Qty
1/2“ K4.9 155F Pendent White Residential Sprinkler model GL4910 -Globe
2 GL-4910+155-03 ea 3
1/2” K5.6 155F 3MM Upright Brass Quick Response Sprinkler model GL5615 Globe
3 ea 3
6
presupuestos@suprefuego.com
1/2”x48“ Stainless
Steel Braided 30 13 13.00 10 SprinkFlex -SFB 1/2” Room 6
Sprinkler Hose UL/FM
Mechanical
1/2” K5.6 155F 3MM
Globe room and
Upright Brass Quick 31 13 13.00 10 1/2" 6
GL5615 electric
Response Sprinkler
room
7
presupuestos@suprefuego.com
Items: TYCO
DISTRIBUTOR: TYCO
400 Pennbrook Parkway
Lansdale, PA 19446
Phone:+1- 215-362-0700
Items: VICTAULIC
DISTRIBUTOR: Louis P. Canuso Inc.
7522 Morris Court
Suite 101
Allentown, PA 18106
Phone: +1-610-366-7914
Items: NIBCO
DISTRIBUTOR: NIBCO INC.
1516 Middlebury Street
Elkhart, IN 46515-1167
Phone: +1- 312-859-380
Email: kellys@nibco.com
Items: WATTS
DISTRIBUTOR: HAYWARD PIPE & SUPPLY CO.
3218 DIABLO AVE
8
presupuestos@suprefuego.com
9
6. Division 22- Plumbing
Content
6.1 Siphonic Dual Flush Elongated Toilet, SPEC 2.4.3
-DB Dearborn Semi-cast Grid Patent Overflow Plugs Technical Specification 760-1
-Omni Pro, Stainless Steel 25” x 22” x 8- 1/16” Single Bowl Top Mount Sink Model
OM2522-8-3
❑ 2887.216
• Vitreous china
• High efficiency, low consumption
- Full Flush (6.0 Lpf/1.6 gpf)
- Partial Flush (3.8 Lpf/1.0 gpf)
• Elongated siphon action bowl with direct-fed jet
• Meets EPA WaterSenseSM criteria
• Qualifies in LEEDS Program
• 305mm (12") rough-in
• Fully glazed 2" Trapway
• Generous 9" x 8" water surface area
• Chrome plated top mounted push button actuator
• Sanitary bar on bowl
• 2 color matched bolt caps
• 100% factory flush tested
• 5 Year Limited Warranty on Total Toilet
❑ 4339.216 Tank
❑ 4339.516 Tank with AquaGuard Liner
14"
C/L OF SEAT POST HOLES (356 mm)
5-1/2" (140 mm) CENTERS
Nominal Dimensions: 18-1/2"
(470 mm)
756 x 380 x 749mm SUPPLY
AS
(29-3/4" x 15" x 29-1/2") REQ'D
(92mm)
3-5/8 "
Compliance Certifications -
*6"
Meets or Exceeds the Following Specifications: 7"
(180 mm)
13-1/4"
(335 mm) FINISHED FLOOR
(152 mm)
9-1/2"
• ASME A112.19.2-2008/CSA B45.1-08 12"
(308 mm) C/L OF OUTLET
(238 mm)
13
© 2009 AS America Inc. Revised 7/09
6.2 Toilet Seat, SPEC 2.4
To Be Specified:
❏ Color: ❏
White
Model # 5901
A 18-9/16" (471mm)
B 14-3/8" (365mm)
C 7-7/8" (200mm)
A
D 3-1/2" (89mm) C
E 5-1/2" (140mm)
Ring Thickness 7/8" (22mm)
Ring Thickness
1" (25mm) D
with Bumper
RELIANT® 3
SINGLE CONTROL LAVATORY FAUCET
0.5 GPM
MODEL NUMBER:
❏ 7385.058 Reliant 3 Single Control Centerset
Indexed metal lever handle. Metal Speed Connect ® drain.
0.5 gpm pressure compensating vandal resistant spray.
❏ 7385.053 Reliant 3 Single Control Centerset
Metal lever handle. Grid drain LESS pop-up hole.
0.5 gpm pressure compensating vandal resistant spray.
❏ 7385.050 Reliant 3 Single Control Centerset
Indexed metal lever handle. LESS drain. LESS pop-up hole.
0.5 gpm pressure compensating vandal resistant spray.
142 mm
(5-5/8") 154 mm
(6-1/16")
117 mm
(4-5/8")
98 mm
(3-7/8")
32 mm
30mm (1-1/4")DIA. 498 mm
66 mm (1-1/4") MOUNTING (19-5/8")
123 mm (2-5/8")
(4-7/8") HOLE
63 mm
(2-1/2")
BRAIDED
(32 mm) O.D.
FLEXIBLE
(1-1/4" O.D.) PRODUCT FEATURES:
SUPPLY HOSES
WITH 3/8" Pressure Compensating Spray: Provides a constant water
COMPRESSION flow of 0.5 gpm throughout the pressure range.
CONNECTORS
Cast Brass Waterway with Flexible Supply Hoses:
GENERAL DESCRIPTION: Strong and durable. Less potential for leaks.
All metal body with indexed metal lever handle or optional Ceramic Disc Valve Cartridge: Assures smooth, precise valve
extra long lever handle. Washerless 47 mm ceramic disc control and a lifetime of drip-free, maintenance-free performance.
valve cartridge with integral hot limit safety stop. Durable Adjustable Hot Limit Safety Stop: Limits the amount of hot
cast brass waterway. 20" (500 mm) long flexible stainless water allowed to mix with cold. Reduces the risk of accidental
steel drain cable is pre-assembled to faucet body scalding.
(on 7385.058). Metal Speed Connect ® drain body (on
Lead Free: Faucet contains ≤ 0.25% total lead content by
7385.058) with 1-1/4" (32 mm) tail piece. Braided flexible
weighted average.
supply hoses with 3/8" compression connections.
Pressure compensating vandal resistant spray with Simple One-Person Installation: Faucet drops in from top.
0.5 gpm/1.9 L/min. maximum flow rate. Quick spin nuts secure faucet in place.
SUGGESTED SPECIFICATION
Single control lavatory fitting shall feature an all metal body with metal lever handle. Shall feature a cast brass waterway with
flexible hose connections. Shall also feature a washerless ceramic disc valve cartridge with integral hot limit safety stop. Shall
feature water conserving vandal resistant 0.5 gpm/1.9 L/min. pressure compensating spray. Shall also feature a metal drain
body with stainless steel cable actuation. Fitting shall be American Standard Model # 7385.05__.___.
0.0
20 40 60 80
INLET PRESSURE (PSI)
*Flow rates shown are for mixed hot and cold.
Finish
Option
Polished
Chrome
Product
Number Description 002
Reliant 3 Single Control Centerset. Indexed (Red/Blue) metal lever handle. with grid drain,
7385.053
LESS pop-up hole. Pressure compensating vandal resistant 0.5 gpm spray.
Reliant 3 Single Control Centerset. Indexed (Red/Blue) metal lever handle. Less drain, LESS
7385.050 pop-up hole. Pressure compensating vandal resistant 0.5 gpm spray.
Parts
AVAILABLE MODIFICATIONS***
Suffix**
**To modify a product, add suffix after the 4th digit (ex. 2064F05101.002)
***Modified product models are NOT WaterSense certified.
Compliance Certifications -
Meets or Exceeds the Following Specifications: * See faucet section for additional models available
• ASME A112.19.2 / CSA B45.1 for Vitreous
China Fixtures MEETS THE AMERICANS WITH DISABILITIES ACT GUIDE-
LINES AND ANSI A117.1 ACCESSIBLE AND USABLE
BUILDINGS AND FACILITIES - CHECK LOCAL CODES.
Top of front rim mounted 864mm (34") from finished floor.
© 2016 AS America Inc.
M37
spec_0355-0356 Lucerne WallHung Lavs Rev. A 8/16
LUCERNE™
WALL-HUNG LAVATORY
VITREOUS CHINA
BARRIER FREE
0356.028 8" CTRS FOR EXPOSED BRACKET SUPPORT 0355.027 4" CTRS FOR EXPOSED BRACKET SUPPORT
0356.015 8" CTRS FOR WALL HANGER 0355.012 4" CTRS FOR WALL HANGER OR
OR CONCEALED ARMS CONCEALED ARMS
0356.915 LESS OVERFLOW 0355.912 LESS OVERFLOW
8mm 8mm
(5/16") (5/16")
(6) 25mm
(6) 25mm
(1") DIA.
(1") DIA.
ACCESS
ACCESS 13mm 13mm
HOLES
HOLES FOR (1/2") (1/2")
521mm FOR 521mm
CONC. ARMS
(20-1/2") CONC. (20-1/2")
ARMS
425mm 425mm
(16-3/4") (16-3/4")
267mm 267mm
(10-1/2") 54mm (2-1/8") DIA. (10-1/2")
114mm HOLES FOR 114mm
(4-1/2") CONCEALED ARMS (4-1/2") 54mm (2-1/8") DIA.
44mm HOLES FOR
102mm 44mm 25mm 102mm (1-3/4") CONCEALED ARMS
(4") (1-3/4") (1") (4") 25mm
(1")
79mm 79mm
*(11-3/8")
(3-1/8")
298mm
(3-1/8")
*(11-3/8")
298mm
(8-1/8")
206mm
206mm
(8-1/8")
38mm
38mm 10mm (3/8") (1-1/2") 10mm
*(11-1/4")
*(10-1/4")
286mm
260mm
(1-1/2") DIA. ANCHOR (3/8")
DIA. ANCHOR
SCREW HOLES
*(13-7/8")
352mm
*(13-7/8")
SCREW HOLES
352mm
203mm 203mm
S-9 HANGER S-9 HANGER
(8") (8")
27mm X 14mm 27mm x 14mm
(1-1/16 x 5/16")
787mm (31)
864mm (34)
(1-1/16" x 5/16") SLOTS
SLOTS
SUPPLIES SUPPLIES
AS REQUIRED 787mm (31") AS REQUIRED
1-1/4" O.D. WASTE 1-1/4" O.D. WASTE 864mm (34") 1-1/4" O.D. WASTE 1-1/4" O.D. WASTE
OUTLET FOR OUTLET FOR FINISHED OUTLET FOR OUTLET FOR FINISHED
DRAIN PLUG POP-UP DRAIN FLOOR DRAIN PLUG POP-UP DRAIN FLOOR
11" 11"
(279mm) (279mm)
NOTES:
*PROVIDE
DIMENSIONS SHOWN FOR LOCATION OF SUPPLIES AND “P” TRAP ARE SUGGESTED.
SUITABLE REINFORCEMENT FOR ALL WALL SUPPORTS.
FITTINGS NOT INCLUDED AND MUST BE ORDERED SEPARATELY.
CONCEALED ARM SUPPORT AS REQUIRED TO BE FURNISHED BY OTHERS.
IMPORTANT: Dimensions of fixtures are nominal and may vary within the range of tolerances established
by ANSI Standard A112.19.2. These measurements are subject to change or cancellation. No responsibility
is assumed for use of superseded or voided pages.
SPECIFICATIONS
Dearborn Brass Two Piece Patent Overflow Plug is designed for use in
tubular drain applications with lavatory sinks. Two piece design allows
overflow to flow to sink drain. Available in 5", 6" 8" or 12" lengths.
DESCRIPTION
• Chrome Finish
• 20 Gauge Brass
• Two Piece Assembly
PRODUCT SELECTOR
SEMI-CAST GRID PATENT OVERFLOW PLUGS
Product Carton
P Number
Size Description
Quantity
Semi-Cast Grid Patent
1-1/4"
760-1 Overflow Plug w/ 1-1/4" x 25
x 6"
6" - 17 Ga. Tailpiece
Semi-Cast Grid Patent
1-1/2"
761-1 Overflow Plug w/ 1-1/2" x 25
x 6"
6" - 17 Ga. Tailpiece
Data is subject to manufacturing tolerances.
DIMENSIONS
[A]: Diameter A 2.2" [C]: Height C 2.8"
See
[B]: Diameter B Chart [D]: Height D 6"
A.1
A.1 - LENGTHS
Oatey Co. | 20600 Emerald Parkway, Cleveland, OH 44135 | P: 1.800.321.9532 | oatey.com LCS1172 5/20
6.6 Wall Mount Concealed, SPEC 2.4.1
SERIES 17120
2"
1 1/2"
2 3/4" F
C (13" MIN-22.5" MAX)
5"
FINISHED
WALL
1 1/2"
FINISHED WALL
DENOTES VARIABLE. DIMENSION
FINISHED FLOOR DEPENDS ON FIXTURE. STANDARD
ADJUSTABLE SLEEVE IS 4" LONG
MANUFACTURER
_______________
2" NUMBER
_______________
2 3/4" -BP* WITH BACK PLATES
-MMB* WITH MOVABLE MOUNTING BRACKETS SIZE
2" _______________
EXTENSION SLEEVES LONGER THAN
-10* STANDARD (SPECIFY WALL THICKNESS)
NAME
-75 2" CHROME PLATED ESCUTCHEONS _______________
-76 4" CHROME PLATED ESCUTCHEONS
5" DIMENSIONS
-77 6" CHROME PLATED ESCUTCHEONS
A _____________
-26$0&203$1<
DATE OF LAST CHANGE: 02/21/14 NOTES
DIMENSIONS ARE SUBJECT TO MANUFACTURERS
TOLERANCES AND CHANGE WITHOUT NOTICE.
WE CAN ASSUME NO RESPONSIBILITY FOR
USE OF SUPERSEDED OR VOID DATA.
0,&+,*$1&,7<,1',$1$
6.7 Single Bowl Top Mount Sink, SPEC 2.4.4
lnstallation Profile:
1-1/2" (38mm) Diameter Faucet Holes on 4" (102mm) Centers Sinks are listed by IAPMQ®as meeting the applicable
requirements of the Unifonm Plumbing Code®, lnternational
e ® Plumbing Code®, and National Plumbing Code of Canada .
Product Compliance: ASME A 112.19.3/CSA 845.4
BUY AMERICAN ACT
OM2522-8-3 OM2522-84
l 1
hl 22"
e
(559mm)
15-3/4"
(400mm)
4" R
IV(102mm)
!
21 "
(533mm)
25"
(635mm)
8-1116''
3-1/4" R 205mm)
/ (83mm) [ ]
PART: _ _ _ _ _ _ _ _ _ _ _ _ _QTY: _ _ _ __
---- - .....,,;..,-- -----
PROJECT :_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
CONTACT: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
DATE :_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
NOTES :._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __
APPROVAL :_ _ _ _ _ _ _ __ _ _ _ _ _ _ _ __
In keeping with our policy of continuing product improvement, we reserve the right to change product specifications without notice.
MATERIAL SPECIFICATIONS
No. Part Material
1 Post C.P ABS
2 Basket SS430
3 Gasket Rubber
4 Body SS430
5 Washer Rubber
6 Washer Paper
7 Cup Galvanized
8 Lock Nut Zinc
9 Washer PE
10 Slip Nut Zinc – Yellow
Chromate Dip
6.9 Single Handle Kitchen Faucet, SPEC 2.4.4
OPB-100C OPB-100SS
OPB-140C OPB-140SS
Water Efficiency
TEL: 800-217-4603
Visit Our Web Site : www.omniprofaucets.com
OPB-100C OPB-100SS
OPB-140C OPB-140SS
5 Sleeve A041026
6 Ceramic Disc Cartridge A507348N-32
7.
7 Spout Assembly A666928W
8 O-ring Set 14.
11.
(Φ1-1/4" ID * Φ1-1/2" OD) A608220 8.
9.
9 Diverter A501374N
18.
10 Spray Head A503002N
17.
11 Spray Holder Assembly A664283
12.
12 Spray Hose A512139N
13 Cover Plate & Putty plate A667003
14 Aerator A500872N
15 Mounting Hardware Assembly A603222
15.
16 Wrench 13.
(H 2.5 * 19 mm L * 53 mm L) A031000NI
17 O-Ring Set
16.
(Φ1/4" ID * Φ3/8" OD) A668178N
18 Mounting Hardware A66G424-T
10 11/16"
(271mm)
4"
(102mm) 9"
(229mm)
15º
(169mm)
6 5/8"
5º
(121mm)
(168mm)
Ø 1 3/4"
4 3/4"
(147mm)
5 13/16"
6 5/8"
(109mm)
(120mm)
4 5/16"
(Ø 44mm)
4 3/4"
Ø 1 15/16" Ø 1 1/8"
(Ø 50mm) (Ø 28.5mm)
Ø 1 15/16"
1/16" ~ 2 5/16"
(1mm ~ 58mm)
(139mm)
(177mm)
6 15/16"
(Ø 50mm)
(118mm)
5 1/2"
4 5/8"
1"-20UNEF
1 11/32"-20UNS
1/2"-14NPSM
2 7/16"
(11mm)
7/16"
10 1/4" (62mm)
(260.5mm)
TEL: 800-217-4603
Visit Our Web Site : www.omniprofaucets.com
6.10 Floor Drains, 2.6.1
SPECIFICATION
JOSAM 30000 Series coated cast iron Floor Drain, two-piece body with double
drainage flange and 1/2” primer tap with plug, bottom outlet, WEJLOC® invertible
non-puncturing flashing collar with weepholes, threaded to receive a JOSAM
adjustable strainer.
Available Options
▼ -PD Prison Drain -91 Rough Bronze Body
▼ -ST Shallow Trap -92 Galvanized Cast Iron Parts
▼ -TSO Threaded Side Outlet OUTLETS:
-ARE Acid-Resisting Epoxy -T Threaded Outlet
-49 3/4" Primer Tap -X Inside Caulk Outlet
1/2" Primer Tap (Std.) -Y Hub Outlet with Gasket
-Z No-Hub Outlet
CONFORMS WITH ASTM-C564.
FLOOR DRAINS
30004 4 13
SPECIFICATION
JOSAM 30000-PD Series galvanized steel security Floor Drain with flashing flange,
threaded side outlet, integral trap wall. Threaded to receive any JOSAM adjustable
strainer furnished with security screws.
Available Options
-50 1/2" Primer Tap
-92 Galvanized Cast Iron Parts
-C Bolted Flashing Clamp Device
OUTLET:
-T Threaded Outlet
WARNING: Cancer and Reproductive Harm - www.p65warnings.ca.gov ▼ Product Illustration follows. 117
Floor Drains_08.qxd 5/1/08 1:44 PM Page 115
Available Options
-2 Satin Finish Bronze
-80 Perforated Stainless Steel Basket
-VP Secured Grate, Vandal-Proof Screws
Available Options
FLOOR DRAINS
-2 Satin Finish Bronze
-80 Perforated Stainless Steel Basket
-J Backwater Valve
-VP Secured Grate, Vandal-Proof Screws
Available Options
-SS Stainless Steel, 5S, 6S, 8S
-2 Satin Finish Bronze
-80 Perforated Stainless Steel Basket
-CP Chrome Plated, 5S, 6S
-J Backwater Valve
-VP Secured Grate, Vandal-Proof Screws
Available Options
-SS Stainless Steel, 5A, 6A, 7A, 8A
-2 Satin Finish Bronze
-80 Perforated Stainless Steel Basket
-CP Chrome Plated, 5A, 6A
-J Backwater Valve
-VP Secured Grate, Vandal-Proof Screws
TYPE NO. A B C D FREE AREA LBS.
5A 5 1-15/16 1-1/8 4-5/8 7.8 2
6A 6 2-1/4 15/16 5-1/4 11.0 3
7A 7 2-11/16 1-1/2 6-7/16 13.2 4
8A 8 2-1/2 7/8 7-1/8 16.2 5
9A• 9 2-1/4 1 8-1/8 21.1 7
•Not SUPER-FLO® Design
10A• 10 2-1/4 1-1/8 9 28.0 9
Available Options
-2 Satin Bronze Top
FLOOR DRAINS
Available Options
-2 Satin Finish Bronze
-80 Perforated Stainless Steel Basket
-J Backwater Valve
-VP Secured Grate, Vandal-Proof Screws
T13020▲
T13020-▲DPE
TUB AND SHOWER
FAUCET TRIM
■ Classic Bath Collection
T13220-▲SHC T13420-▲SHC ■ Valve Only (T13020 Series)
T13120 T13220- T13420-▲ ■ Tub Only (T13120 Series)
T13120-LTS T13220▲ ▲SHCCER T13220-H2O T13220-▲H2OT SHCCER
■ Shower Only (T13220 Series)
Submitted Model No.:________________________________________________
■ Tub and Shower (T13420 Series)
Specific Features:___________________________________________________ FEATURES:
• 13 Series pressure balanced bath mixing valve trim
• "-H2O" models include H2Okinetic® Technology shower head
STANDARD SPECIFICATIONS:
• Maintains a balanced pressure of hot and cold water even
RP21633▲ when a valve is turned on or off elsewhere in the system.
Deep Escutcheon
(Use if valve • For use with MultiChoice® Universal rough valve body.
is underflush.) (R10000 Series)
• Back-to-back installation capability.
RP19809▲
Escutcheon • Solid brass forged body.
• Temperature only controlled with metal lever handle.
7" • Field adjustable to limit handle rotation into hot water zone.
(178 mm) Supply • 120° maximum handle rotation.
Dia.
• All parts replaceable from the front of the valve.
• Models with "LTS" suffix supplied with 7" long non-diverter
slip-on spout (RP36498).
• T13220-H2O uses RP46384.
Face of plasterguard • T13220-H2OT uses RP54752.
should be flush with
finish wall line • DPE = 1" deeper escutcheon (RP21633).
• Models with "CER" use ceramic cartridge RP74236.
• Stem extension kit RP77991 can be ordered to allow for an
8" (203 mm) additional 1 3/4" wall thickness. RP77991 ships with
2 3/4"
min. (70 mm) chrome escutcheon screws. For special finishes also order
18" (457 mm)
max. RP12630 escutcheon screws in desired finish.
• Shower head max flow rate 1.5 gpm @ 80 psi,
RP5833 RP48717 RP43381s 1.75 GPM 5.7 L/min @ 550 kPa
Touch-Clean® Raincan Shower Head
• Shower head max flow rate 1.75 gpm @ 80 psi,
2 3/4" 6.6 L/min @ 550 kPa
(70 mm)
4 3/4" • Tub port max flow rate 8.6 gpm @ 60 psi
(121 mm) with R10000-UNBX
4 3/4" 3 3/16" Full Body
(81 mm) • Note: Product will be marked with flow rate of specific
(121 mm) Spray shower head.
RP36498▲ (Slip-On Metallic) WARRANTY
• Parts and Finish - Lifetime limited warranty; or for
2 1/2" Massaging commercial purchasers, 10 years for multi-family
Spray
(64 mm) residential (apartments and condominiums) and
4 7/8" 5 years for all other commercial uses, in each case
(124 mm)
from the date of purchase.
7"
(177.8 mm) Soft Drench • Electronic Parts and Batteries (if applicable) - 5
Spray years from the date of purchase; or for commercial
purchasers, 1 year from the date of purchase. No
RP46384▲ 4 3/4" RP38357 2 3/4" warranty is provided on batteries.
1.5 GPM (121 mm) 1.75 GPM (70 mm)
H2O Shower Head Touch-Clean® Shower Head
(66 mm)
POMME(S) DE DOUCHE
TYPE NO. PIPE SIZE B C D E F LBS. TYPE NO. PIPE SIZE B C E F LBS.
58604-COT2 2 4-1/4 1-3/4 6-3/8 2 5-3/8 11 58614-CO2 2 1-1/2 4-5/8 6 5-1/2 6
58604-COT3 3 5-1/4 2-1/2 7-3/4 3 5-3/8 14 58614-CO3 3 2-1/2 4-5/8 6 5-1/2 7
58604-COT4 4 6 3-1/2 8-7/8 4 5-3/8 20 58614-CO4 4 3-1/2 4-5/8 6 5-1/2 9
58608-COT6 6 7 4-1/2 12-1/2 6 10-5/8 34 58616-CO6 6 5-1/2 6-3/4 8-1/4 7-3/4 15
TYPE NO. PIPE SIZE B C D E F LBS. TYPE NO. PIPE SIZE B CXC LBS.
58614-COT2 2 4-1/4 1-3/4 6-3/8 2 6 13 58631-CO2 2 1-1/2 8x8 9
58614-COT3 3 5-1/4 3-1/2 7-3/4 3 6 16 58631-CO3 3 2-1/2 8x8 9
58614-COT4 4 6 3-1/2 8-7/8 4 6 22 58631-CO4 4 3-1/2 8x8 11
58616-COT6 6 7 4-1/2 12-1/2 6 8-1/4 37 58632-CO6 6 5-1/2 12 x 12 20
SPECIFICATION ADJUSTABLE
X - MIN CAST IRON
JOSAM 55000 Series coated cast iron LEVELEZE® KLEENATRON® II Floor Cleanout, OPTIONAL (-41)
Y - MAX BUSHING CLAMP RING
internal ABS cleanout plug, adjustable cast iron housing with special-duty scoriated THREADED
ABS PLUG
secured round cast iron cover. OPTIONAL (-F)
FLANGE
Available Options
▼ -1 Satin Finish Nikaloy Top -SS-SQ Square Top, Stainless Steel
▼ -1-SD Special-Duty Satin Finish ▼ -5 Ductile Iron Top B
Nikaloy Top -14 Carpet Cleanout Marker
D
▼ -1-SQ Square Top, -VP Secured Cover,
Satin Finish Nikaloy Vandal-Proof Screws
▼ -1-12 Cover Recessed for Tile, -22 Taper Thread Bronze Plug
Satin Finish Nikaloy PIPE SIZE
-31 Galvanized Cast Iron Parts
▼ -1-13 Terrazzo Tile Cover, C
-41 Clamp Ring and Flange
Satin Finish Nikaloy
-F Flange Only
-2 Satin Finish Bronze Top FLANGE STANDARD ON 4” -X AND 6” SIZES.
-WF Wide Flange *
-2-SD Special-Duty Satin Finish (not available on Cl)
Bronze Top FOR OUTLET TYPE SPECIFY -X, -Y or -Z
-CFC Carpet Cleanout Flange
-2-SQ Square Top, TYPE NO. PIPE SIZE A B C* D X Y LBS.
Cover
Satin Finish Bronze 55002 2 6 3-3/4 7-1/2 5-9/16 2-3/4 4-1/4 15
OUTLETS:
-2-12 Cover Recessed for Tile, 55003 3 6 3-3/4 7-1/2 5-9/16 2-3/4 4-1/4 15
Satin Finish Bronze -X Inside Caulk Outlet
55004 4 6 3-3/4 7-1/2 5-9/16 2-3/4 4-1/4 16
-2-13 Terrazzo Tile Cover, -Y Hub Outlet w/Gasket, 2”-4”
55004-X 4 7-1/2 4-1/4 9-3/16 7 2-5/8 4-5/16 18
Satin Finish Bronze -Z No-Hub Outlet
55005-Z 5 6 3-3/4 7-1/2 5-9/16 2-3/4 4-1/4 16
-SS Stainless Steel Top 55006-Z 6 7-1/2 4-1/4 9-3/16 7 2-5/8 4-5/16 18
PIPE SIZE
188
WARNING: Cancer and Reproductive Harm - www.p65warnings.ca.gov ▼ Product Illustration follows.
2.8 Water Heater
NOTICE: This water heater is designed for use in a commercial application and the installation and maintenance
! of it should be performed by qualified, licensed service personnel. If the foregoing assumption is not appropri-
ate, then we recommend that you obtain and retain our Residential Use & Care Manual.
! CALIFORNIA PROPOSITION 65 WARNING: This product contains chemicals known to the State of California to
cause cancer, birth defects or other reproductive harm.
R
ESE
ESE
cator to desired setting.See Operation Section of this
R
T
HI LOW
VERY
170°
MED
0°
13 TURN OFF
POWER
15 0
140° °
BEFORE
Safety and energy conservation are factors to be considered NOTE: When this water heater is supplying general purpose
when setting the water temperature on the thermostat. The hot water requirements for use by individuals, a
most energy efficient operation will result when the thermostatically controlled mixing valve for reducing point of
temperature setting is the lowest that satisfies the needs use water temperature is recommended to reduce the risk of
consistent with the application. scald injury. Contact a licensed plumber or the local plumbing
authority for further information.
2
Introduction
! WARNING FOR THE BOOSTER MODELS
Read and Review this entire Manual with special em- A minimum clearance of 18 inches (457mm) on the right
phasis on the Installation Section (Pages 3 - 6) and side of the Booster model is required for removal of the
Operation Section (Pages 7 - 8) prior to any installa- heating element(s) when required for service or inspec-
tion work.
tion.
LOCAL INSTALLATION REGULATIONS—This water heater
must be installed in accordance with these instruc- Four eparate 5/16-18 threaded openings are provided on
tions, local codes, utility company requirements, and/ the top, rear and bottom panels, so the heater may be
or in the absence of local codes, the latest edition of the bolted to a horizontal or vertical surface. If installed on
American National Standard / National Electrical Code. a counter top, or stacked vertically in multiples, insert
A copy of which can be purchased from the National Fire bolts and/or washers in bottom threaded openings to
Protection Association, 1 Batterymarch Park, Quincy, MA
02269 as booklet NFPA 70. provide a minimum 1/4” (6mm) clearance so door hinges
will not bind.
LOCATION
A. The water heater should be installed in a clean, dry Factory designed accessories available for the Booster
location as close as practical to the area of greatest hot square model are: six inch adjustable stainless steel legs
water demand. Long hot water lines should be insulated and a bracket kit for slide in “under counter” mounting or
to conserve water and energy. The water heater and wall mounting of the water heater.
water lines should be protected from exposure to freez-
ing temperatures. DO NOT install the water heater in an
outdoor, unprotected area. D. RESTAURANT INSTALLATION:
If the water heater is to be installed in a restaurant, or
B. The water heater should not be located in an area other location where NSF International listing is required,
where leakage of the tank or connections will result in it must be weather sealed to the floor, a raised base, or
damage to the area adjacent to it or to lower floors of shelf so that seepage cannot accumulate under it; or ele-
the structure. When such areas cannot be avoided, it vated to provide at least (6) inches (152mm) of clearance
is recommended that a suitable catch pan, adequately from the floor.
drained, be installed under the water heater.
NOTE: Auxiliary catch pan installation MUST conform the The standard legs supplied with the Booster models
applicable local codes. provide the six (6) inches (152mm) of clearance in accor-
dance with NSF International requirements.
C. FOR THE TANK TYPE MODELS, the minimum dis-
tance to provide adequate clearance for protection of For the Tank Type models, a factory designed sealing kit
combustible material is 0 inches (0 mm) from jacket and is available from the distributor or store where the water
18 inches (457mm) from access door. However, additional
clearance for accessibility to permit inspection and ser- heater was purchased. When installed according to the
vicing such as removing heating elements or checking instructions supplied with the kit, these heaters will meet
controls must be provided. All models are approved for the NSF International requirements.
installation on combustible flooring.
Installation
! WARNING 2. THERMAL EXPANSION — Determine if a check valve
The manufacturer’s warranty does not cover any exists in the inlet water line. It may have been installed
damage or defect caused by installation, or attach- in the cold water line as a separate back flow preventer,
ment or use of any special attachment such as ener- or it may be part of a pressure reducing valve, water
gy saving devices (other than those authorized by the meter or water softener. A check valve located in the
manufacturer) into, onto, or in conjunction with the cold water inlet line can cause what is referred to as a
water heater. The use of such unauthorized devices ”closed water system”. A cold water inlet line with no
may shorten the life of the water heater and may en- check valve or back flow prevention device is referred to
danger life and property. The manufacturer disclaims as an ”open” water system.
any responsibility for such loss or injury resulting
from the use of such unauthorized devices. As water is heated, it expands in volume and creates
an increase in the pressure within the water system.
1. INSPECT SHIPMENT—for possible damage. The man- This action is referred to as ”thermal expansion”. In an
ufacturer’s responsibility ceases upon delivery of goods ”open” water system, expanding water which exceeds
to the carrier in good condition. Any claims for dam- the capacity of the water heater flows back into the city
age, shortage in shipments, or nondelivery must be filed main where the pressure is easily dissipated.
immediately against carrier by consignee. A ”closed water system”, however, prevents the
Refer to Fig. 1 for installation with commercial dish- expanding water from flowing back into the main supply
washer to provide hot water for sanitizing rinse. Note: line, and the result of ”thermal expansion” can create
Adjust the pressure reducing valve to the dishwasher a rapid, and dangerous pressure increase in the water
manufacturer’s recommended pressure (usually between heater and system piping. This rapid pressure increase
15 and 25 psi) (103-172kPa), with water flowing to the can quickly reach the safety setting of the relief valve,
dishwasher. causing it to operate during each heating cycle. Thermal
3
Installation
Dishwasher Shut-off
Valve
Water Inlet
Legs
Check Valve Relief Valve
Circulation Return Line 6” Air Gap (152mm) Discharge Line
Open Drain
expansion, and the resulting rapid, and repeated expan- If a recirculation line is installed, the return connection
sion and contraction of components in the water heater should be made to a tee close to the inlet connection
and piping system can cause premature failure of the on the water heater. A check valve should always be
relief valve, and possibly the heater itself. Replacing the installed in the recirculation line to prevent cold water
relief valve will not correct the problem! from entering.
The suggested method of controlling thermal expan- Factory designed Equa-Flow Manifolds, and jacketed,
sion is to install an expansion tank in the cold water insulated storage tanks are available.
line between the water heater and the check valve. The 3. WATER CONNECTIONS—This heater may be con-
expansion tank is designed with an air cushion built nected individually in multiples with others, or with an
in that compresses as the system pressure increases, external hot water storage tank. It may also be used to
thereby relieving the over pressure condition and elimi- boost the temperature of preheated water.
nating the repeated operation of the relief valve. Other
methods of controlling thermal expansion are also avail- Inlet and outlet water connections are clearly marked
able. Contact your installing contractor, water supplier, next to the connections on the heater. Use only clean,
or plumbing inspector for additional information regard- new galvanized steel, copper or approved plastic for
ing this subject. pipe for water connections. Local codes shall govern
Hot Outlet Storage Tank Temperature & Pressure Relief Valve
Storage Tank Refer to Local Codes
Temperature & Pressure Relief Valve Temperature & Pressure Relief Valve
(Not visible in this view) Discharge Pipe to suitable open drain
Refer to Local Codes
Return Outlet
2”
Optional Return Outlet
(51mm)
Thermal
Expansion Tank
(If Required)
Recirculation Loop
Branch Circuit from Cold Water Inlet
Electrical Distribution Panel Check Valve
Shut-off Valve
NOTES:
Vacuum Relief Valve 1.) Heater’s Outlet Piping must have
(If required by local codes) upward slope, otherwise use
Circulator.
Air Gap 6” (152mm)
Temperature & Pressure Relief Valve(s) 2.) If vertical tank is used, follow same
Discharge Pipe(s) to suitable open drain layout.
Recirculation Loop
Storage Tanks
Shut-off Valve
Temperature & Pressure Relief Valve
(Not visible in this view)
Refer to Local Codes Recirculator
Manifolds
Circulator
Control
(Optional*)
Air Gap
6” (152mm)
Circulator*
* Circulator may be wired to run con-
tinuously without the control
Vacuum Relief Valve
(Not visible in this view) Temperature & Pressure Relief Valve(s)
If required by local codes Discharge Pipe(s) to suitable open drain
Figure 3. — Typical Forced Circulation Tank System with factory supplied jacketed and insulated storage tanks.
5
Recommended Over Current Protection
208 240 277 480
Rating
P
h Voltage Copper Aluminum Copper Aluminum Copper Aluminum Copper Aluminum
kW a
s
e Wire EMT Wire EMT Wire EMT Wire EMT Wire EMT Wire EMT Wire EMT Wire EMT
208 240 277 480
Gauge Conduit** Gauge Conduit** Gauge Conduit** Gauge Conduit** Gauge Conduit** Gauge Conduit** Gauge Conduit** Gauge Conduit**
6
1 220 190 165 95 4/0 2 300MCM 2 1/2 3/0 2 250MCM 2 2/0 1 1/2 4/0 2 3 1 1 1 1/4
36
3 125 110 NA 55 1 1 1/2 2/0 2 2 1 1/4 1/0 2 NA NA NA NA 6 1 4 1 1/4
1 275 235 205 120 300MCM 2 1/2 500MCM 2 1/2 250MCM 2 350MCM 2 1/2 4/0 2 250MCM 2 1 1 1/4 1/0 1 1/2
45
3 160 140 NA 70 2/0 2 4/0 2 1/2 1/0 2 3/0 2 NA NA NA NA 4 1 1/4 3 1 1/4
Installation
1 325 285 245 145 400MCM 2 1/2 600MCM 3 300MCM 2 1/2 500MCM 2 1/2 250MCM 2 350MCM 2 1/2 1/0 1 1/2 3/0 2
54
3 190 165 NA 85 3/0 2 250MCM 2 1/2 2/0 2 4/0 2 1/2 NA NA NA NA 4 1 1/4 2 1 1/4
1 360 315 275 160 500MCM 2.5 700MCM 3 400MCM 2.5 500MCM 2.5 300MCM 2 1/2 500MCM 2 1/2 2/0 1 1/2 4/0 2
60
3 210 180 NA 90 4/0 2.5 300MCM 2.5 3/0 2 4/0 2.5 NA NA NA NA 4 1.25 3 1.25
1 NA NA NA NA NA NA NA NA NA NA NA NA 300MCM 2.5 600MCM 3 3/0 2 250MCM 2
72
3 250 220 NA 110 250MCM 2.5 350MCM 2.5 4/0 2.5 300MCM 2.5 NA NA NA NA 2 1.25 1/0 2
81 3 NA NA NA 125 NA NA NA NA NA NA NA NA NA NA NA NA 2/0 2 4/0 2 1/2
1 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA
108
3 NA NA NA 170 NA NA NA NA NA NA NA NA NA NA NA NA 2/0 2 NA NA
* Table 1 - Minimum Branch Circuit and Wire Sizing Guide. Based on N.E.C. ANSI/NFPA 70 - 2002; Article 422.10(A); Article 240.6(A); Annex C Table C1 (EMT); Table 310.16
(Based on 75 C Type THW wire).
** Conduit size based on NEC Code, Annex C Table C1 Maximum Number of Conductors or Fixture Wires in Electrical Metallic Tubing (EMT); 3 wires for single phase; 4 wires
for 3 phase.
Installation
WARNING 7. GROUNDING—
Tank MUST be full of water before power is turned ! CAUTION
on. Heating elements WILL BE DAMAGED if ener-
The presence of water in the piping and water
gized for even a short time while tank is dry. The
water heater’s warranty does not cover damage or heater does not provide sufficient conduction for a
failure resulting from operation with an empty or ground. Nonmetallic piping, dielectric unions, flex-
partially empty tank. (Reference is made to the lim- ible connections, Etc.., can cause the water heater
ited warranty for complete terms and conditions.) to be electrically isolated.
cator to desired setting.See Operation Section of this taken shortly after the thermostat(s) cycle off during a
Manual for details. period of little or no use.
BEFORE
VERY
SERVICING
170°
120°
0°
13 15 0
! DANGER
140° °
8
Operation
TO RESET HIGH TEMPERATURE LIMIT CONTROL:
There is one thermostat that controls all heating ele-
ments. It is located behind the removable pad of glass
fiber insulation in the control compartment. ! WARNING
1 60°F (71°C) MODELS: Be certain the power supply to the water heater is turned
A djust thermostat dial pointer, with a small screwdriver, “OFF” before attempting to reset the Limit Control.
to the desired water temperature setting (refer to Fig.
4). THERMOSTAT PROTECTIVE COVER SHOULD NOT N OTE: Allow the water in the tank to cool before reset-
BE REMOVED. The thermostat is adjustable from a ting the High Temperature Limit Control.
“LOW” to “HI” setting. An approximate water tem-
perature of 130° F (54°C) is accomplished when the O n Surface Mounted Thermostat models, press the red
temperature dial pointer is in the “MED” position. Each “RESET” button located above the thermostat (refer to
mark above and below the “MED” position indicates an Fig. 4). The thermostat protective cover SHOULD NOT
approximate 10° F (6°C) change in water temperature. be removed.
R eplace insulation, close access door and turn power O n Immersion Thermostat models, the reset button is
”ON”, and the water heater is operational. located on the outside of the control enclosure near
N OTE: A thermometer(s) installed at or near the outlet the thermostat(s) dial(s).
of the water heater and/or storage tank(s) will result in
the most accurate outlet water temperature measure- 3. EMERGENCY INSTRUCTIONS —
ment.
! WARNING
180°F (82°C) GALLON MODELS:
A djust thermostat dial pointer, with a small screwdriver, If the water heater has been subjected to flood, fire, or
to the desired water temperature setting (refer to Fig. physical damage, turn off power and water to water heat-
4). THERMOSTAT PROTECTIVE COVER SHOULD NOT er. Do not operate the water heater again until it has been
BE REMOVED. The thermostat is adjustable from a thoroughly checked by qualified service personnel.
“LOW” to “HI” setting. An approximate water tem-
perature of 150° F (66°C) is accomplished when the 4. LONG TIME SHUT-DOWN — If the water heater is to
temperature dial pointer is in the “MED” position. Each remain idle for an extended period of time (60 days or
mark above and below the “MED” position indicates an more), the power and water to the water heater should
approximate 10° F (6°C) change in water temperature. be turned off to conserve energy. The water heater and
Replace insulation, close access door and turn power piping should be drained if they might be subjected
”ON”, and the water heater is operational. to freezing temperatures. It is recommended that
N OTE: A thermometer(s) installed at or near the outlet the water heater’s operation and controls should be
of the water heater and/or storage tank(s) will result in checked by qualified service personnel, before putting
the most accurate outlet water temperature settings. it in service again.
9
Maintenance
Properly maintained, this water heater will provide years
of dependable, trouble free service. It is strongly sug- ! DANGER
gested that a regular routine maintenance program be Before manually operating the relief valve, make certain
established and followed by the owner. It is further rec- no one will be exposed to the danger of coming in con-
ommended that a periodic inspection of the relief valve tact with the hot water released by this valve. The water
and electrical controls be made by service personnel may be hot enough to create a SCALD hazard. The water
qualified in electric appliance repair. released should be directed to a suitable drain to prevent
injury or damage.
! CAUTION
NOTE: If the temperature and pressure relief valve on
Make certain all power to the water heater is turned the water heater discharges periodically, this may be
“OFF” before performing any maintenance or inspection due to thermal expansion in a “closed” water system.
work on this water heater. Contact the water supplier or local plumbing inspec-
tor on how to correct this. DO NOT plug the relief valve
1. ELECTRICAL CONNECTIONS — Periodic inspection outlet.
of all electrical connections at the service terminal
block, fuse holders, contactors, thermostats and ele- 5. TANK — Good maintenance requires that the tank
ments should be performed to make certain all con- be cleaned of deposits. Unless the water supply is very
nections are tight. If the electrical supply leads used soft (0 to 5 grains hardness), scale or lime deposits will
are aluminum, particular attention should be given to accumulate in the tank. Hard water scale is deposited
the branch circuit connections at the heater’s termi- at an increasingly high rate in proportion to increased
nal block. It is advisable to retighten the field terminal water temperature, and accumulation of these deposits
connections of aluminum conductors may reduce efficiency and shorten the life of the water
twenty-four hours after the water heater was first heater.
placed in service. Torque specs are marked on the ter-
minal block. CLEANING THE TANK:
N OTE: On surface mounted thermostat models, make The water heater is not supplied with a clean-out pro-
certain insulation is carefully replaced and tucked in vision on the tank. To remove accumulated deposits
before placing heater in operation. Also check the from the tank, it is suggested that a few gallons of
thermostat to be certain that it is located in its bracket water be drained from the water heater’s tank through
and making good contact with the surface of the tank. the drain valve every month to remove those deposits.
2. FUSES — Any replacement fuses should be of the If chemical lime dissolving cleaners are preferred, cau-
same UL Class and type as the originals. The amp rat- tiously follow the instructions supplied with the clean-
ing of the element circuit fuses may be reduced on er. DO NOT use a muriatic or hydrochloric acid (HCl)
those models not having high amperage elements. based cleaner.
3. HEATING ELEMENTS — The life of elements can be 6. ANODE ROD INSPECTION — This water heater is
extended in hard water areas by removing the scale equipped with an anode rod designed to prolong the
build up. Cleaning can be accomplished by scraping or life of the glass lined tank. The anode is slowly con-
soaking in a de-scaling solution. Care should be taken sumed cathodically, thereby eliminating or minimizing
so the protective plating is not damaged by scraping corrosion of the glass lined tank.
or dissolved by excessive soaking.
Water sometimes contains a high sulfate and/or min-
eral content and together with the cathodic protection
! CAUTION process can produce a hydrogen sulfide or rotten egg
odor in the heated water. Chlorination of the water
supply should minimize the problem.
Be certain all power to the water heater is turned “OFF”
and tank has been completely drained before removing T he anode rod(s) should be removed from the water
elements for cleaning. heater’s tank for periodic inspection. Replace the
W henever an element is removed from the tank for anode(s) when more than 6” (152mm) of core wire is
cleaning or replacement, a new gasket should be in- exposed at either end of the rod.
stalled to prevent a possible water leak. Refer to parts
information in this manual for replacement gasket in- I f overhead clearance is not sufficient to allow installa-
formation. The elements are easily unscrewed with a tion of a rigid rod of original length, segmented rods in
1-1/2” socket wrench. both standard and resistor versions are available.
4. RELIEF VALVE — The Temperature and Pressure Re- N OTE: Do not remove the anode rod from the water
lief Valve must be free to operate properly. Check op- heater’s tank, except for inspection and/or replace-
eration (at least once a year) by lifting the handle fully ment, as operation with the anode rode removed will
and allowing several gallons of water to flush through shorten the life of the glass lined tank and exclude
the discharge line. Make certain the discharged water warranty coverage.
is directed to a suitable drain.
10
Maintenance
7. SEASONAL OPERATION — If the water heater is to NOTE: Refer to “Hydrogen Gas Caution” in Safety Pre-
remain idle for an extended period of time (60 days cautions Section on page 8.
or more) the power to the heater should be turned
off. The water heater and piping should be drained if 8. GENERAL— Periodic cleaning of the equipment
they might be subjected to freezing temperatures. It is recommended. Turn off power to heater. Remove
is recommended that the water heater’s operation is any lint or dust that may block the free passage of air
thoroughly checked (by qualified personnel) before it is through the control compartment. DO NOT allow com-
placed back in service. bustible materials such as newspapers, rags or mops
to accumulate near the water heater.
Replacement Parts
The following Parts are required for Normal Maintenance 2. Quantity of each part required.
for all Models:
3. Complete model number and name of the water
SP21949 1 1/2” Socket Wrench for Element Head heater.
SP6708 Element Gasket
4. Serial Number of water heater
All other Parts can be ordered by providing the following
information: 5. Specify the voltage and KW rating.
1. Description of Part(s), such as: 6. Address Parts orders to your distributor or dealer.
Thermostat(s)*
Thermostat / High Temp Limit Assembly*
High Temperature Limit* ! CAUTION
Control Transformer* * For your safety, DO NOT attempt repair of Thermostats,
Heating Element (Include wattage and voltage) High Limit Controls or any other control component.
Anode Rod(s) Refer repairs to qualified service personnel.
Or other parts as required*
11
Wiring Diagram:
Surface Mounted Thermostat Models
-G Models
SINGLE PHASE CONNECTIONS 3 & 6 Element Models Only
3
15
6 CONNECTED TO
3
! D TERMINAL 1 ON
FIELD THERMOSTAT
480
277
240
208
120
120
WIRING
ALL RED
C
BLOCK 17
2
14
5
2 3 AMP
B
R CLASS G FUSES
ALL BLACK
16
1
13 BLK
4 C
GRD 1
A
BLK
BL BL BL
L H K G
BL
N I M J
W W W W
13 14 15 1 2 3 4 5 6 16 17 18 CONNECTED TO
BLK
BLK
BLK
BLK
BLK
BLK
RATED VOLTAGE
R
CONTACTORS ON TRANSFORMER
R R R R
COPPER
CONDUCTORS ! D
R
F !
R
BLK
BLK
BLK
BLK
BLK
BLK
19 20 21 7 8 9 10 11 12 22 23 24
30 AMP
CLASS G FUSE BLOCKS
FUSES
19 24 THERMOSTAT
20 22
ELEMENTS 21 23
8 10
9 11 ! THERMOSTAT AND HIGH LIMIT CONTROLS
OPERATE AT INCOMING LINE VOLTAGE.
7 12
NOTE:
THIS WATER HEATER MAY BE SUPPLIED BY A BRANCH CIRCUIT HAVING OVER 300 VOLTS BETWEEN
CONDUCTORS, PROVIDED THE SYSTEM HAS A GROUND NEUTRAL AND NO CONDUCTOR IS OVER
3 0 0 V O LT S TO G R O U N D .
12
Wiring Diagram:
Surface Mounted Thermostat Models
-G Models
9 Element Configuration Only
30
CONTROL
3
15
6
3
CONNECTED TO
FIELD ! D TERMINAL 1 ON
480
277
240
208
120
120
29
C
WIRING ALL RED 26 THERMOSTAT
BLOCK 17
2
14
5
2 3 AMP
B
R CLASS G FUSES
ALL BLACK
28
25
16
1
13 BLK
4 C
GRD 1
A
BLK
BL BL BL BL BL
Q L H K P G
BL
S N R I M R J
W W W W W W
25 26 27 13 14 15 1 2 3 4 5 6 16 17 18 28 29 30 ! D
R
CONTACTORS CONNECTED TO
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
RATED VOLTAGE
R R R R R R ON TRANSFORMER
37 38 39 43 44 45 49 50 51 40 41 42 46 47 48 52 53 54
F !
35 AMP 37 38 39 43 44 45 49 50 51 40 41 42 46 47 48 52 53 54
R
CLASS G
FUSES
FUSE BLOCKS
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
31 32 33 19 20 21 7 8 9 10 11 12 22 23 24 34 35 36 THERMOSTAT
!
33 35
THERMOSTAT AND HIGH LIMIT CONTROLS
ELEMENTS 31 36 OPERATE AT INCOMING LINE VOLTAGE.
32 34
19 24
20 22
21 23
8 10
NOTE:
9 11 To insure proper thermostat response,
7 12 be sure to replace insulation pad tightly
over elements after servicing.
NOTE:
THIS WATER HEATER MAY BE SUPPLIED BY A BRANCH CIRCUIT HAVING OVER 300 VOLTS BETWEEN
CONDUCTORS, PROVIDED THE SYSTEM HAS A GROUND NEUTRAL AND NO CONDUCTOR IS OVER
3 0 0 V O LT S TO G R O U N D .
13
Wiring Diagram:
Immersion Thermostat Models
-G Models
1 Element Configuration
CONTROL
TRANSFORMER
SINGLE PHASE CONNECTIONS
CONNECTED TO
480
277
240
208
120
120
! F RATED VOLTAGE ON
C
FIELD TRANSFORMER
ALL RED
WIRING
BLOCK 2 3 AMP
B
R CLASS G FUSES
!
ALL BLACK
D
GRD R
C
1 BLK
A
BLK
G
BL
H
W
D !
1 2 R
BLK
CONTACTORS
R
COPPER
CONDUCTORS
30 AMP
CLASS G ! F
R
FUSES
FUSE BLOCKS
LIMIT
BLK
7 8 E !
R
THERMOSTAT
ELEMENTS 7 8
NOTE:
THIS WATER HEATER MAY BE SUPPLIED BY A BRANCH CIRCUIT HAVING OVER 300 VOLTS BETWEEN
CONDUCTORS, PROVIDED THE SYSTEM HAS A GROUND NEUTRAL AND NO CONDUCTOR IS OVER
3 0 0 V O LT S TO G R O U N D .
14
Wiring Diagram:
Immersion Thermostat Models
-G Models
3 & 6 Element Configurations Only
Up to 30 Amp Fuses
CONTROL
TRANSFORMER
SINGLE PHASE CONNECTIONS
480
277
240
208
120
120
CONNECTED TO
3
15
!
C
F
6
RATED VOLTAGE ON
3
FIELD TRANSFORMER
WIRING
ALL RED
BLOCK 17
2
14
5
2 3 AMP
CLASS G FUSES
ALL BLACK
B
16 R
D
1
13 R
4 A C
BLK BLK
GRD 1
BL BL BL
L H K G BL
N I M J
W W W W
! D R
13 14 15 1 2 3 4 5 6 16 17 18
CONTACTORS
BLK
BLK
BLK
BLK
BLK
BLK
R R R R
COPPER
CONDUCTORS
30 AMP
CLASS G LIMIT
FUSES
! F R
FUSE BLOCKS
BLK
BLK
BLK
BLK
BLK
BLK
19 20 21 7 8 9 10 11 12 22 23 24
! E R
19 24 THERMOSTAT
20 22
ELEMENTS 21 23
8 10
9 11
! THERMOSTAT AND HIGH LIMIT CONTROLS
OPERATE AT INCOMING LINE VOLTAGE.
7 12
NOTE:
THIS WATER HEATER MAY BE SUPPLIED BY A BRANCH CIRCUIT HAVING OVER 300 VOLTS BETWEEN
CONDUCTORS, PROVIDED THE SYSTEM HAS A GROUND NEUTRAL AND NO CONDUCTOR IS OVER
3 0 0 V O LT S TO G R O U N D .
15
Wiring Diagram:
Immersion Thermostat Models
-G Models
3 & 6 Element Configurations Only
35 Amp Fuse
CONTROL
TRANSFORMER
SINGLE PHASE CONNECTIONS
480
277
240
208
120
120
CONNECTED TO
3
15
!
C
F
6
RATED VOLTAGE ON
3
FIELD TRANSFORMER
WIRING
ALL RED
BLOCK 17
2
14
5
2 3 AMP
CLASS G FUSES
ALL BLACK
B
16 R
D
1
13 R
4 A C
BLK BLK
GRD 1
BL BL BL
L H K G BL
N I M J
W W W W
! D R
13 14 15 1 2 3 4 5 6 16 17 18
CONTACTORS
BLK
BLK
BLK
BLK
BLK
BLK
R R R R
LIMIT
25 26 27 28 29 30 31 32 33 34 35 36
35 AMP 25 26 27 28 29 30 31 32 33 34 35 36
! F R
CLASS G
FUSES FUSE BLOCKS
! E R
BLK
BLK
BLK
BLK
BLK
BLK
19 20 21 7 8 9 10 11 12 22 23 24
THERMOSTAT
19 24
20 22
ELEMENTS 21 23
8 10
9 11
! THERMOSTAT AND HIGH LIMIT CONTROLS
OPERATE AT INCOMING LINE VOLTAGE.
7 12
NOTE:
THIS WATER HEATER MAY BE SUPPLIED BY A BRANCH CIRCUIT HAVING OVER 300 VOLTS BETWEEN
CONDUCTORS, PROVIDED THE SYSTEM HAS A GROUND NEUTRAL AND NO CONDUCTOR IS OVER
3 0 0 V O LT S TO G R O U N D .
16
Wiring Diagram:
Immersion Thermostat Models
-G Models
9 Element Configuration Only
30
CONTROL
SINGLE PHASE CONNECTIONS
27
3
15
6
3
CONNECTED TO
480
277
240
208
120
120
D
FIELD 29
!
C
WIRING HIGH LIMIT
ALL RED
26
BLOCK 2
17
14
5
2 3 AMP
CLASS G FUSES
ALL BLACK
28
25 B
16 R
1
13
GRD 4 A
BLK
C
BLK
1
CONNECTED TO
RATED VOLTAGE ON
TRANSFORMER
BL BL BL BL BL
Q L H K P G
BL
S N I M R J
W W W W W W
D !
25 26 27 13 14 15 1 2 3 4 5 6 16 17 18 28 29 30 R
CONTACTORS
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
R R R R R R
LIMIT
37 38 39 43 44 45 49 50 51 40 41 42 46 47 48 52 53 54
37 38 39 43 44 45 49 50 51 40 41 42 46 47 48 52 53 54 F ! R
R E !
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
31 32 33 19 20 21 7 8 9 10 11 12 22 23 24 34 35 36
FUSE BLOCKS
35 AMP THERMOSTAT
CLASS G 33 35
FUSES 31 36
32 34
19 24 ! THERMOSTAT AND HIGH LIMIT CONTROLS
OPERATE AT INCOMING LINE VOLTAGE.
20 22
21 23 ELEMENTS
8 10
9 11
7 12
NOTE:
T H I S WAT E R H E AT E R M AY B E S U P P L I E D B Y A B R A N C H C I R C U I T H AV I N G O V E R 3 0 0 V O LT S B E T W E E N
CONDUCTORS, PROVIDED THE SYSTEM HAS A GROUND NEUTRAL AND NO CONDUCTOR IS OVER
3 0 0 V O LT S T O G R O U N D .
17
Wiring Diagram:
Immersion Thermostat Models
with Staging
3 Stage
-GS Models
30
SINGLE PHASE CONNECTIONS 27
3
15
6 TRANSFORMER
FIELD 29
3
! D CONNECTED TO
WIRING HIGH LIMIT
ALL RED
480
277
240
208
120
120
26
C
BLOCK 17
2
14
5
2 3 AMP
CLASS G FUSES
ALL BLACK
28
25 B
16 R
1
13
4 A C
BLK BLK
GRD 1
G
BL
Y
BL
V
BL
BL
H
S N I M R J
W W W W W W
25 26 27 13 14 15 1 2 3 4 5 6 16 17 18 28 29 30 CONTACTORS D !
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
R
R
R R R R R R LIMIT
X
BL
37 38 39 43 44 45 49 50 51 40 41 42 46 47 48 52 53 54 U
! BL
37 38 39 43 44 45 49 50 51 40 41 42 46 47 48 52 53 54
F 3 R
R E !
2 W
BL
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
31 32 33 19 20 21 7 8 9 10 11 12 22 23 24 34 35 36 1
FUSE BLOCKS
35 AMP
CLASS G THERMOSTATS
FUSES 33 35 CONNECTED TO
31 36 RATED VOLTAGE ON
TRANSFORMER
32 34
19 24
ELEMENTS 20 22
21 23
8 10
9 11
7 12
NOTE:
THIS WATER HEATER MAY BE SUPPLIED BY A BRANCH CIRCUIT HAVING OVER 300 VOLTS BETWEEN
CONDUCTORS, PROVIDED THE SYSTEM HAS A GROUND NEUTRAL AND NO CONDUCTOR IS OVER
3 0 0 V O LT S TO G R O U N D .
18
Wiring Diagram:
Immersion Thermostat Models
with Staging
2 Stage
-GS Models
CONTROL
SINGLE PHASE CONNECTIONS
18
3
6
3
! D CONNECTED TO
480
277
240
208
120
120
HIGH LIMIT
C
ALL RED
17
FIELD 14
WIRING
2
5
BLOCK 2
3 AMP
CLASS G FUSES
ALL BLACK
16 B
13 R
1
4
1 A C
BLK BLK
GRD
BL V
BL
H G
BL
N I M J
W W W W
D !
R
13 14 15 1 2 3 4 5 6 16 17 18
CONTACTORS
BLK
BLK
BLK
BLK
BLK
BLK
K
R
R R R R BL
! F
R
BLK
BLK
BLK
BLK
BLK
BLK
U
BL
LIMIT
19 20 21 7 8 9 10 11 12 22 23 24
43 44 45 49 50 51 40 41 42 46 47 48
CLASS G E !
FUSES R
2
BLK
BLK
BLK
BLK
BLK
BLK
20 21 8 9 11 12 23 24
THERMOSTATS
19 7 10 22
1
FUSE BLOCKS
CONNECTED TO
19 24 RATED VOLTAGE ON
TRANSFORMER
20 22
21 23
8 10
ELEMENTS
9 11
7 12
19
Wiring Diagram:
Immersion Thermostat Models
-G Models
42
39
30
FIELD 27
WIRING 18
3
BLOCK 15
6 CONTROL
3 CONNECTED TO TRANSFORMER
RATED VOLTAGE
41 ON TRANSFORMER
38
SINGLE PHASE CONNECTIONS
29
GROUND 26
480
277
240
208
120
120
ALL RED
C
17
2
14
5
2
D CONNECTED TO
40 HIGH LIMIT
37
28
ALL BLACK
25 3 AMP
16 CLASS G
1
FUSES
13
4
B R D R
1
A BK C BK
U Q L H K P T G
W W W W W W W BL
W S N I M R V J
BL BL BL BL BL BL BL W
D
37 38 39 25 26 27 13 14 15 1 2 3 4 5 6 16 17 18 28 29 30 40 41 42 R
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
R
R
R
R
R R R R R R R R
F
R
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72
LIMIT
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
R
R
43 44 45 31 32 33 19 20 21 7 8 9 10 11 12 22 23 24 34 35 36 46 47 48
44 46 FUSE 35 AMP
BLOCKS CLASS G THERMOSTAT E
FUSES R
45 47
43 48
33 35
31 36
32 34
ELEMENTS 19 24
20 22
21 23
8 10 THERMOSTAT AND HIGH LIMIT CONTROLS
9 11 OPERATE AT INCOMING LINE VOLTAGE
7 12
NOTE:
THIS WATER HEATER MAY BE SUPPLIED BY A BRANCH CIRCUIT HAVING OVER 300 VOLTS BETWEEN
CONDUCTORS, PROVIDED THE SYSTEM HAS A GROUND NEUTRAL AND NO CONDUCTOR IS OVER
3 0 0 V O LT S TO G R O U N D .
20
Wiring Diagram:
Immersion Thermostat Models
4 Stage
-GS Models
42
39
30
FIELD 27 CONTROL TRANSFORMER
3
WIRING 18
BLOCK 15
6
3
41
THREE PHASE CONNECTIONS
38 CONNECTED TO
29 RATED VOLTAGE
ALL RED
SINGLE PHASE CONNECTIONS
480
277
240
208
120
120
26 ON TRANSFORMER
C
2
17
14
GROUND 5
2
40
37 CONNECTED TO
D
ALL BLACK
28 HIGH LIMIT
25
1
16 3 AMP
13 CLASS G
4 FUSES
1
B R DR
A BK C
BK
DD BL
Y BL
V BL
H
BL
G
BL
D
AA S N I M R BB J R
W W W W W W W W
37 38 39 25 26 27 13 14 15 1 2 3 4 5 6 16 17 18 28 29 30 40 41 42 K
BL
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
R
R
R
R
F
CC
BL
R R R R R R R R
X LIMIT
BL
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72
U
52 54 67 68 69 70 71 72 BL 4
49 50 51 53 55 56 57 58 59 60 61 62 63 64 65 66
Z
3 BL
W
2 BL
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
R
R
43 44 45 31 32 33 19 20 21 7 8 9 10 11 12 22 23 24 34 35 36 46 47 48
35 AMP
44 46 FUSE
CLASS G E
BLOCKS R
FUSES 45 47
43 48 1
33 35
31 36
THERMOSTATS
32 34
19 24
ELEMENTS
20 22
21 23
8 10
THERMOSTAT AND HIGH LIMIT CONTROLS
9 11
OPERATE AT INCOMING LINE VOLTAGE
7 12
NOTE:
THIS WATER HEATER MAY BE SUPPLIED BY A BRANCH CIRCUIT HAVING OVER 300 VOLTS BETWEEN
CONDUCTORS, PROVIDED THE SYSTEM HAS A GROUND NEUTRAL AND NO CONDUCTOR IS OVER
3 0 0 V O LT S TO G R O U N D .
21
Wiring Diagram:
Immersion Thermostat Models
-G Models
42
39
30
FIELD 27
WIRING 18
BLOCK 3 15
6 CONTROL
3 CONNECTED TO TRANSFORMER
RATED VOLTAGE
41 ON TRANSFORMER
38
SINGLE PHASE CONNECTIONS
29
GROUND 26
480
277
240
208
120
120
ALL RED
C
17
2
14
5
2
D CONNECTED TO
40 HIGH LIMIT
37
28
ALL BLACK
25 3 AMP
16 CLASS G
1
FUSES
13
4
B R D R
1
A BK C BK
U Q L H K P T G
W W W W W W W BL
W S N I M R V J
BL BL BL BL BL BL BL W
D
37 38 39 25 26 27 13 14 15 1 2 3 4 5 6 16 17 18 28 29 30 40 41 42 R
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
R
R
R
R
R R R R R R R R
F
R
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72
LIMIT
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
R
R
43 44 45 31 32 33 19 20 21 7 8 9 10 11 12 22 23 24 34 35 36 46 47 48
44 46 FUSE 35 AMP
BLOCKS CLASS G THERMOSTAT E
FUSES R
45 47
43 48
33 35
31 36
32 34
ELEMENTS 19 24
20 22
21 23
8 10 THERMOSTAT AND HIGH LIMIT CONTROLS
9 11 OPERATE AT INCOMING LINE VOLTAGE
7 12
NOTE:
THIS WATER HEATER MAY BE SUPPLIED BY A BRANCH CIRCUIT HAVING OVER 300 VOLTS BETWEEN
CONDUCTORS, PROVIDED THE SYSTEM HAS A GROUND NEUTRAL AND NO CONDUCTOR IS OVER
3 0 0 V O LT S TO G R O U N D .
22
Wiring Diagram:
Immersion Thermostat Models
4 Stage
-GS Models
42
39
30
FIELD 27 CONTROL TRANSFORMER
3
WIRING 18
BLOCK 15
6
3
41
THREE PHASE CONNECTIONS
38 CONNECTED TO
29 RATED VOLTAGE
ALL RED
SINGLE PHASE CONNECTIONS
480
277
240
208
120
120
26 ON TRANSFORMER
C
2
17
14
GROUND 5
2
40
37 CONNECTED TO
D
ALL BLACK
28 HIGH LIMIT
25
1
16 3 AMP
13 CLASS G
4 FUSES
1
B R DR
A BK C
BK
DD BL
Y BL
V BL
H
BL
G
BL
D
AA S N I M R BB J R
W W W W W W W W
37 38 39 25 26 27 13 14 15 1 2 3 4 5 6 16 17 18 28 29 30 40 41 42 K
BL
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
R
R
R
R
F
CC
BL
R R R R R R R R
X LIMIT
BL
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72
U
52 54 67 68 69 70 71 72 BL 4
49 50 51 53 55 56 57 58 59 60 61 62 63 64 65 66
Z
3 BL
W
2 BL
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
BK
R
R
43 44 45 31 32 33 19 20 21 7 8 9 10 11 12 22 23 24 34 35 36 46 47 48
35 AMP
44 46 FUSE
CLASS G E
BLOCKS R
FUSES 45 47
43 48 1
33 35
31 36
THERMOSTATS
32 34
19 24
ELEMENTS
20 22
21 23
8 10
THERMOSTAT AND HIGH LIMIT CONTROLS
9 11
OPERATE AT INCOMING LINE VOLTAGE
7 12
NOTE:
THIS WATER HEATER MAY BE SUPPLIED BY A BRANCH CIRCUIT HAVING OVER 300 VOLTS BETWEEN
CONDUCTORS, PROVIDED THE SYSTEM HAS A GROUND NEUTRAL AND NO CONDUCTOR IS OVER
3 0 0 V O LT S TO G R O U N D .
23
24
7. Division 23- Heating, ventilating and Air Conditioning
(HVAC)
Content
HVAC OU CONDITION UNIT SAFETY SWITCH HVAC IU CONDITION UNIT SAFETY SWITCH
Out Door Air OU-101 OU-101 In Door Air IU-101 OU-101
Out Door Air OU-102 OU-102 In Door Air IU-102 OU-102
Out Door Air OU-103 OU-103 In Door Air IU-103 OU-103
Out Door Air OU-104 OU-104 In Door Air IU-104 OU-104
Out Door Air OU-105 OU-105 In Door Air IU-105 OU-105
Out Door Air OU-106 OU-106 In Door Air IU-106 OU-106
HVAC OU CONDITION UNIT SAFETY SWITCH HVAC IU CONDITION UNIT SAFETY SWITCH
Out Door Air OU-201 OU-201 In Door Air IU-201 OU-201
Out Door Air OU-202 OU-202 In Door Air IU-202 OU-202
Out Door Air OU-203 OU-203 In Door Air IU-203 OU-203
Out Door Air OU-204 OU-204 In Door Air IU-204 OU-204
Out Door Air OU-205 OU-205 In Door Air IU-205 OU-205
Out Door Air OU-206 OU-206 In Door Air IU-206 OU-206
Out Door Air
Condition Unit 0U-106
Safety Switch OU-106 In Door Air
Condition Unit IU-102 On Door Air In Door Air
Safety Switch OU-102 Condition Unit 0U-104 Condition Unit 0U-106
Out Door Air Safety Switch OU-104 Safety Switch OU-106
Condition Unit 0U-104
Safety Switch OU-104
REF.
REF.
REF.
REF.
REF.
REF.
REF.
REF.
REF.
REF.
REF.
Out Door Air
Condition Unit 0U-106
Safety Switch OU-106
®
Ceiling Exhaust and Inline Fans 1
Prepare the fan
Ductwork
Check ductwork to see if the fan’s discharge requires
rotation from horizontal to vertical discharge.
Airflow
Airflow
Fan Rotation
To rotate from horizontal to vertical discharge
A-Models Only
1 2
Insert plastic duct tab into SP-A box slots. Rotate plastic SP-A duct adapter (PN 473388)
until the screw tabs meets SP-A box.
Screw Tabs
Plastic SP-A Plastic SP-A Plastic SP-A
Duct Adapter Tabs Duct Adapter (PN 473388) Duct Adapter (PN 473388)
3
Install screws provided to secure discharge.
Screw holes
Sheet Metal Screw #10x3/8
Phillips Head (PN 415838)
®
Ceiling Exhaust and Inline Fans 3
Discharge Installation SP/CSP-B 50-200 Models
1 2
Insert SP-B box scroll tab into SP-B box Rotate plastic SP-B duct adapter (PN 474433)
scroll slots. until the two SP-B mounting tabs fully engage
into the two SP-B box mounting slots.
SP-B
Box Scroll Tabs
SP-B
Box Mounting Slots
SP-B
Box Scroll Slots
SP-B
Box Mounting Tabs
3
OPTIONAL
Align the pins on the TR 6x4 adaptor to the
duct pin hole on the SP-B 6-inch duct. Push
until the adaptor snaps into place.
TR 6x4 Pin
SP-B
Plastic Duct Pin Hole
SP-B
6-inch
TR 6x4 Plastic Duct
(PN 473324) (PN 474433)
SP-A200, A250, A290, A390 121⁄8 x 141⁄4 121⁄4 x 143⁄8 the same direction as the
AIRFLOW
SP-A700 233⁄4 x 113⁄4 241⁄8 x 121⁄4 wheel (2) is recommended.
SP-A410, A510, A710, A780 14 ⁄4 x 18 ⁄8
3 3
147⁄8 x 187⁄16 Ductwork turning opposite
SP-A900, A1050, A1410, the wheel direction (3) will
143⁄4 x 24 147⁄8 x 241⁄8
A1550 cause turbulence and back
SP-B 50 - 200 141⁄8 x 113⁄4 143⁄8 x 121⁄4 pressure resulting in poor
performance.
NOTE
4. Slide ductwork over the fan’s discharge collar and
Model SP-A 50-90 are standard with a round duct. securely attach it with sheet metal screws.
Should Model SP-A 110-190 require a round duct,
Model RDC (Round Duct Connector) may be ordered Make sure the screws do not interfere with damper
from Greenheck for field installation. operation. Check damper to make sure it opens freely.
®
Ceiling Exhaust and Inline Fans 5
Attach the Grille Fig. 8
Incorrect
SP/CSP models shown are
UL and cUL listed E 33599
®
Ceiling Exhaust and Inline Fans 7
Typical Installation
INSULATION*
(Place around and over Fan Housing.) ROOF CAP*
(with built-in damper)
FAN HOUSING
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck’s Centrifugal Ceiling and Cabinet Exhaust Fans AMCA Publication 410-96, Safety Practices for Users and
catalog provides additional information describing the Installers of Industrial and Commercial Fans, provides
equipment, fan performance, available accessories, and additional safety information. This publication can be
specification data. obtained from AMCA International, Inc. at www.amca.org.
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
8 474680 • SP/CSP, Rev. 3, February 2015 Copyright 2015 © Greenheck Fan Corporation
7.3 Single Zone Inverter Mini Split Cooling SPEC 2.9.2
MO D E L:
LI012CI-180V432 LI012CO-180V432
LI012CI-180P432 LI012CO-180P432
LI018CI-180P432 LI018CO-180P432
LI024CI-180P432 LI024CO-180P432
LI012HI-180V432 LI012HO-180V432
LI012HI-180P432 LI012HO-180P432
LI018HI-180P432 LI018HO-180P432
LI024HI-180P432 LI024HO-180P432
Thank you for selecting LENNOX air conditioners.Please read this manual
carefully before operation and keep it for further reference.
Content
Operation Notices
Precautions............................................................................................................ 1
Parts name ............................................................................................................ 9
Screen Operation Guide
Buttons on remote controller ............................................................................... 11
Introduction for icons on display screen .............................................................. 11
Introduction for buttons on remote controller .......................................................12
Function introduction for combination buttons ..................................................... 15
Operation guide ................................................................................................... 17
Replacement of batteries in remote controller ..................................................... 17
Emergency operation .......................................................................................... 18
Maintenance
Clean and maintenance....................................................................................... 18
Malfunction
Malfunction analysis ............................................................................................ 21
Installation Notice
Installation dimension diagram ............................................................................ 25
Safety precautions for installing and relocating the unit ...................................... 26
Tools for installation ............................................................................................. 27
Selection of installation location .......................................................................... 27
Requirements for electric connection .................................................................. 28
Installation
Installation of indoor unit...................................................................................... 29
Installation of outdoor unit.................................................................................... 35
Vacuum pumping................................................................................................. 38
Leakage detection................................................................................................38
Check after installation ........................................................................................ 39
Test and operation
Test operation ...................................................................................................... 39
Attachment
......................................................................... 40
Pipe expanding method ................................................................................... 42
This appliance is not intended for use by persons (including children) with reduced physical, sensory
or mental capabilities or lack of experience and knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
If it needs to install, move or maintain the air conditioner, please contact dealer or local service center
to conduct it at first. Air conditioner must be installed, moved or maintained by appointed unit. Otherw-
ise, it may cause serious damage or personal injury or death.
Explanation of Symbols
WARNING
1
Precautions
WARNING
2
Precautions
WARNING
Attachment
Installation must be performed by qualified professionals.
Otherwise, it may cause personal injury or damage.
Must follow the electric safety regulations when installing
the unit.
According to the local safety regulations, use qualified
power supply circuit and circuit break.
Do install the circuit break. If not, it may cause malfunction.
An all-pole disconnection switch having a contact separation
of at least 3mm in all poles should be connected in fixed
wiring.
Including an circuit break with suitable capacity, please
note the following table.Air switch should be included
magnet buckle and heating buckle function, it can protect
the circuit-short and overload.
Air Conditioner should be properly grounded. Incorrect
grounding may cause electric shock.
Don't use unqualified power cord.
Make sure the power supply matches with the
requirement of air conditioner.Unstable power supply or
incorrect wiring or malfunction. Please install proper power
supply cables before using the air conditioner.
Properly connect the live wire, neutral wire and
grounding wire of power socket.
Be sure to cut off the power supply before proceeding
any work related to electricity and safety.
3
Precautions
WARNING
4
Precautions
WARNING
FCC WARNING
FCC STATEMENT
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions :
5
Precautions
FCC STATEMENT
6
Precautions
IC STATEMENT
IC STATEMENT
8
Parts Name
Indoor Unit
air inlet
panel
aux.button
horizontal louver
air outlet
F
C
H OH OHU HORU ORU UR R
ONOFF
H HOONOFF
HOONOFF
UHOUONOFF
RHOUROURURR
ONOFF
ONOFF
ONOFF
ONOFFONOFF
remote control
Outdoor Unit
air inlet
Connection wire
air outlet
NOTICE:
Actual product may be different from above graphics, please refer to actual
products.
9
Parts Name
Display
temp.
indicator Power LED color indicator:
receiver Green-status-ON.
window Red -status-OFF.
Red-R-Heat Mode- R
(only for heating model)
Green-G-Dry Mode- G
temp.
indicator
Power LED color indicator:
receiver Green-status-ON.
window Red -status-OFF.
Mode LED color indicator:
W R O
White-W-Cool Mode-
W
Red-R-Heat Mode- R
(only for heating model)
Orange-O-Dry Mode- O
Display content or position may be different from above graphics, please refer to actual
products.
10
Buttons on remote controller
1 ON/OFF button
2 - button
F 3 + button
C
HOUR 4 MODE button
ONOFF
5 FAN button
1 /
6 SWING button
2 3
7 I FEEL button
8 / button
4 5 9 SLEEP button
6 7 10 TEMP button
8 9 11 TIMER-ON button
10 11 12 CLOCK button
12 13 13 TIMER-OFF button
14 16 14 TURBO button
15 15 LIGHT button
16 X-FAN button
11
Introduction for buttons on remote controller
Note:
● This is a general use remote controller, it could be used for the air conditioners
with multifunction; For some function, which the model doesn't have, if press
the corresponding button on the remote controller that the unit will keep the
original running status.
● After putting through power, air conditioner will give out a sound and operation
indicator " " is ON (red indicator). You can operate the air conditioner through
the remote controller.
● At ON status, after each pressing button on remote controller, the signal icon " "
1 ON/OFF button
Press this button to turn on the unit. Press this button again to turn off the unit.
2 - button
Press this button to decrease set temperature. Holding it down above 2 seconds
rapidly decreases set temperature. In AUTO mode, set temperature is not
adjustable.
3 + button
Press this button to increase set temperature. Holding it down above 2 seconds
rapidly increases set temperature. In AUTO mode, set temperature is not
adjustable.
4 MODE button
Each time you press this button, a mode is selected in a sequence that goes from
AUTO, COOL, DRY, FAN, and HEAT*, as the following:
AUTO COOL DRY FAN HEAT*
After energization, AUTO mode is defaulted. In AUTO mode, the set temperature
will not be displayed on the LCD, and the unit will automatically select the suitable
operation mode in accordance with the room temperature to make indoor room
comfortable. (As for cooling only unit, it won’t have any action when it receives the
signal of heating operation.)
12
Introduction for buttons on remote controller
5 FAN button
This button is used for setting Fan Speed in the sequence that goes from AUTO,
, , to , then back to Auto.
Auto
6 SWING button
Press this button to set up &down swing angle, which circularly changes as below:
OFF
This remote controller is universal. If any command , or is sent out, the unit
will carry out the command as
indicates the guide louver swings as:
7 I FEEL button
Press this button to turn on I FEEL function. The unit automatically adjust tempera-
ture according to the sensed temperature. Press this button again to cancel I FEEL
function.
8 / button
Press this button to achieve the on and off of healthy and scavenging functions in
operation status. Press this button for the first time to start scavenging function;
LCD displays " ". Press the button for the second time to start healthy and
scavenging functions simultaneously; LCD displays " " and " ". Press this
button for the third time to quit healthy and scavenging functions simultaneously.
Press the button for the fourth time to start healthy function; LCD display " ".
Press this button again to repeat the operation above. (This function is applicable
to partial of models)
9 SLEEP button
Press this button to go into the SLEEP operation mode. Press it again to cancel
this function. This function is available in COOL, HEAT (Only for models with
heating function) mode to maintain the most comfortable temperature for you.
13
Introduction for buttons on remote controller
10 TEMP button
Press this button can see indoor set temperature, indoor ambient temperature or
outdoor ambient temperature on indoor unit’s display. Temperature is set circularly
by remote controller as below:
no display
11 TIMER-ON button
Press this button to initiate the auto-ON timer. To cancel the auto-timer program,
simply press this button again.
After press of this button, disappears and "ON" blinks. 00:00 is displayed for
ON time setting. Within 5 seconds, press + or - button to adjust the time value.
Every press of either button changes the time setting by 1 minute. Holding down
either button rapidly changes the time setting by 1 minute and then 10 minutes.
Within 5 Seconds after setting, press TIMER ON button to confirm.
12 CLOCK button
Press CLOCK button, blinking. Within 5 seconds, pressing + or - button adjusts
the present time. Holding down either button above 2 seconds increases or
decreases the time by 1 minute every 0.5 second and then by 10 minutes every
0.5 second. During blinking after setting, press CLOCK button again to confirm the
setting, and then will be constantly displayed.
13 TIMER-OFF button
Press this button to initiate the auto-off timer. To cancel the auto-timer program,
simply press the button again. TIMER OFF setting is the same as TIMER ON.
14
Introduction for buttons on remote controller
14 TURBO button
Press this button to activate / deactivate the Turbo function which enables the
unitto reach the preset temperature in the shortest time. In COOL mode, the unit
will blow strong cooling air at super high fan speed. In HEAT mode, the unit will
blow strong heating air at super high fan speed.
15 LIGHT button
Press LIGHT button to turn on the display's light and press this button again to turn
off the display's light. If the light is turned on, is displayed. If the light is turned
off, disappears.
16 X-FAN button
Pressing X-FAN button in COOL or DRY mode, the icon is displayed and the
indoor fan will continue operation for 2 minutes in order to dry the indoor unit even
though you have turned off the unit.
After energization, X-FAN OFF is defaulted. X-FAN is not available in AUTO, FAN
or HEAT mode.
15
Function introduction for combination buttons
Combination of "TEMP" and "CLOCK" buttons:
About Energy-saving Function
Press "TEMP" and "CLOCK" simultaneously in COOL mode to start energy-saving
function. Nixie tube on the remote controller displays "SE". Repeat the operation to
quit the function.
WIFI Function
Press "MODE" and "TURBO" button simultaneously to turn on or turn off WIFI
function. When WIFI function is turned on, the " " icon will be displayed on
remote controller; Long press "MODE" and "TURBO" buttons simultaneously for
10s, remote controller will send WIFI reset code and then the WIFI function will be
turned on. WIFI function is defaulted ON after energization of the remote controller.
● This function is only available for some models.
16
Operation guide
1. After putting through the power, press "ON/OFF" button on remote controller to
turn on the air conditioner.
2. Press "MODE" button to select your required mode: AUTO, COOL, DRY, FAN,
HEAT.
3. Press "+" or "-" button to set your required temperature. (Temperature can’t be
adjusted under auto mode).
4. Press "FAN" button to set your required fan speed: auto, low, medium and high
speed.
5. Press "SWING" button to select fan blowing angle.
NOTICE
● During operation, point the remote control signal sender at the receiving
window on indoor unit.
● The distance between signal sender and receiving window should be no
more than 8m, and there should be no obstacles between them.
17
Emergency operation
air conditioner. When the air conditioner is turned on, it will operate under
auto mode.
panel
aux. button
WARNING:
Use insulated object to press the auto button
■ Do not wash the air conditioner with water to avoid electric shock.
18
Clean and maintenance
Open panel
1 Pull out the panel to a certain
3 ● Use dust catcher or water to
4
panel cover tightly.
WARNING
■ The filter should be cleaned every three months. If there is much dust in the
operation environment, clean frequency can be increased.
■ After removing the filter, do not touch fins to avoid injury.
■ Do not use fire or hair dryer to dry the filter to avoid deformation or fire hazard.
Clean and maintenance
Malfunction analysis
General phenomenon analysis
Please check below items before asking for maintenance. If the malfunction still
can’t be eliminated, please contact local dealer or qualified professionals.
Malfunction analysis
Phenomenon Check items Solution
Malfunction analysis
Phenomenon Check items Solution
Malfunction analysis
Error Code
● When air conditioner status is abnormal, temperature indictor on indoor unit will
C5
F0
F1
F2
Note:
service.
WARNING
■ When below phenomenon occurs, please turn off air conditioner and discon-
for service.
● Power cord is overheating or damaged.
● There’s abnormal sound during operation.
● Air switch trips off frequently.
● Air conditioner gives off burning smell.
● Indoor unit is leaking.
Installation dimension diagram
At least 15cm
Space to the wall
At least 15cm
At least 15cm
Space to the wall
cm
00
st3 n
At least 250cm
lea uc
tio
At str
b
heo
ot
c et
S pa
o
Ab
50cm Above
00
m
0c
Drainage pipe
25
Safety precautions for installing and relocating the unit
To ensure safety, please be mindful of the following precautions.
Warning
When installing or relocating the unit, be sure to keep the refrigerant
circuit free from air or substances other than the specified refrigerant.
Any presence of air or other foreign substance in the refrigerant circuit will cause
system pressure rise or compressor rupture, resulting in injury.
When installing or moving this unit, do not charge the refrigerant which
is not comply with that on the nameplate or unqualified refrigerant.
Otherwise, it may cause abnormal operation, wrong action, mechanical
malfunction or even series safety accident.
When refrigerant needs to be recovered during relocating or repairing the
unit, be sure that the unit is running in cooling mode.Then, fully close the
valve at high pressure side (liquid valve).About 30-40 seconds later, fully
close the valve at low pressure side (gas valve), immediately stop the unit
and disconnect power. Please note that the time for refrigerant recovery
should not exceed 1 minute.
If refrigerant recovery takes too much time, air may be sucked in and cause
pressure rise or compressor rupture, resulting in injury.
During refrigerant recovery, make sure that liquid valve and gas valve are
fully closed and power is disconnected before detaching the connection pipe.
If compressor starts running when stop valve is open and connection pipe is not
yet connected, air will be sucked in and cause pressure rise or compressor
rupture, resulting in injury.
When installing the unit, make sure that connection pipe is securely
connected before the compressor starts running.
If compressor starts running when stop valve is open and connection pipe is not
yet connected, air will be sucked in and cause pressure rise or compressor
rupture, resulting in injury.
Prohibit installing the unit at the place where there may be leaked corrosive
gas or flammable gas.
If there leaked gas around the unit, it may cause explosion and other accidents.
Do not use extension cords for electrical connections. If the electric wire
is not long enough, please contact a local service center authorized
and ask for a proper electric wire.
Poor connections may lead to electric shock or fire.
Use the specified types of wires for electrical connections between the
indoor and outdoor units. Firmly clamp the wires so that their terminals
receive no external stresses.
Electric wires with insufficient capacity, wrong wire connections and insecure
wire terminals may cause electric shock or fire.
Tools for installation
1 Level meter 2 Screw driver 3 Impact drill
4 Drill head 5 Pipe expander 6 Torque wrench
7 Open-end wrench 8 Pipe cutter 9 Leakage detector
10 Vacuum pump 11 Pressure meter 12 Universal meter
13 Inner hexagon spanner 14 Measuring tape
Note:
● Please contact the local agent for installation.
● Don't use unqualified power cord.
Requirements for electric connection
Safety precaution
1. Must follow the electric safety regulations when installing the unit.
2. According to the local safety regulations, use qualified power supply circuit and
circuit break.
3. Make sure the power supply matches with the requirement of air conditioner.
Unstable power supply or incorrect wiring or malfunction. Please install proper
power supply cables before using the air conditioner.
4. Properly connect the live wire, neutral wire and grounding wire of power socket.
5. Be sure to cut off the power supply before proceeding any work related to
electricity and safety.
6. Do not put through the power before finishing installation.
7. If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
8. The temperature of refrigerant circuit will be high, please keep the interconnec-
tion cable away from the copper tube.
9. The appliance shall be installed in accordance with national wiring regulations.
10.Installation must be performed in accordance with the requirement of NEC
and CEC by authorized personnel only
Grounding requirement
1. The air conditioner is the first class electric appliance. It must be properly
grounding with specialized grounding device by a professional. Please make
sure it is always grounded effectively, otherwise it may cause electric shock.
2. The yellow-green wire in air conditioner is grounding wire, which can't be used
for other purposes.
3. The grounding resistance should comply with national electric safety regulations.
4. The appliance must be positioned so that the plug is accessible.
5. An all-pole disconnection switch having a contact separation of at least 3mm in
all poles should be connected in fixed wiring. For models with a power plug,
make sure the plug is within reach after installation.
Installation of indoor unit
Step one: choosing installation location
rm it with the client.
QE:
Wall Wall
Mark in the middle of it Level meter
Space Space
to the to the
wall wall
above above
150mm 150mm
Left Right
Φ70mm Φ70mm
Rear piping hole Rear piping hole
2. Open a piping hole with the diameter of Φ55 or Φ70 on the selected outlet pipe
position.In order to drain smoothly, slant the piping hole on the wall slightly
downward to the outdoor side with the gradient of 5-10°.
Installation of indoor unit
Indoor outdoor
Note:
● Pay attention to dust prevention and
take relevant safety measures when
opening the hole.
● The plastic expansion particles are
5-10° Φ70/Φ55
not provided and should be bought
locally.
3. Adjust the torque force by referring to the following sheet. Place the open-end
wrench on the pipe joint and place the torque wrench on the union nut. Tighten
the union nut with torque wrench.
Installation of indoor unit
open-end Hex nut diameter Tightening torque (N.m)
wrench Φ6 15~20
union nut Φ 9.52 30~40
Φ 12 45~55
torque wrench pipe Φ 16 60~65
Φ 19 70~75
indoor pipe
4. Wrap the indoor pipe and joint of con-
nection pipe with insulating pipe, and
then wrap it with tape. insulating pipe
wiring cover
Installation of indoor unit
3. Remove the wire clip; connect the power connection wire to the wiring terminal
09K 12K (for some model): 18K 24K (for some model):
N(1) 2 3 N(1) 2 3
L1 L2
N(1) 2 3 N(1) 2 3 L1 L2 G
Outdoor unit connection
Outdoor unit connection
N(1) 2 3
installation.
● For the air conditioner without plug, an circuit break must be installed in the line.
The circuit break should be all-pole parting and the contact parting distance
should be more than 3mm.
Installation of indoor unit
Step eight: bind up pipe
1. Bind up the connection pipe, power connection pipe drain hose
band
cord and drain hose with the band.
indoor and
outdoor power cord
indoor unit gas
pipe
wall pipe
sealing gum
lower hook of
wall-mounting frame
Note:
● Do not bend the drain hose too excessively in order to prevent blocking.
Installation of outdoor unit
Note:
joint.
● For the unit with cooling capacity of 2300W
~5000W, 6 expansion screws are needed;
for the unit with cooling capacity of 6000W
~8000W, 8 expansion screws are needed;
for the unit with cooling capacity of 10000W
at least 3cm above the floor
~16000W, 10 expansion screws are needed.
Installation of outdoor unit
Step four: connect indoor and outdoor pipes
1. Remove the screw cap of valve and 3. Tighten the union nut with torque
aim the pipe joint at the bellmouth of wrench by referring to the sheet
pipe. below.
union nut
1. Remove the wire clip; connect the power connection wire and signal control
wire (only for cooling and heating unit) to the wiring terminal according to the
color; fix them with screws.
09、12K: 09、12K(for some model):
N(1) 2 3 N(1) 2 3 L N
L1 L2
N
L2 L
L1 POWER
POWER
N(1) 2 3
N(1) 2 3
L2
green white red black white green L1
(yellow- (blue) black (brown) (brown) (blue) (yellow-
green) green) POWER
Finish
conduit
L1 L2 N(1) 2 3
Installation of outdoor unit
2. Fix the power connection wire and signal control wire with wire clip (only for
cooling and heating unit).
Note:
● Never cut the power connection wire to prolong or shorten the distance.
Drain connecter
Hose (available drain holes
commercially, drain holes
inner dia. 16mm)
Fig.1
Vacuum pumping
Use vacuum pump
Leakage detection
1. With leakage detector:
Check if there is leakage with leakage detector.
2. With soap water:
If leakage detector is not available, please use soap water for leakage detection.
Apply soap water at the suspected position and keep the soap water for more
than 3min. If there are air bubbles coming out of this position, there's a leakage.
Check after installation
Test operation
1. Preparation of test operation
● The client approves the air conditioner.
● Specify the important notes for air conditioner to the client.
2. Method of test operation
● Put through the power, press ON/OFF button on the remote controller to start
operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and HEAT to check
whether the operation is normal or not.
● If the ambient temperature is lower than 16℃ , the air conditioner can’t
start cooling.
Configuration of connection pipe
1. Standard length of connection pipe
● 5m, 7.5m, 8m.
2.Min. length of connection pipe is 3m.
3.Max. length of connection pipe.
5000Btu/h 24000Btu/h
15 25
(1465W) (7032W)
7000Btu/h 28000Btu/h
15 30
(2051W) (8204W)
9000Btu/h 36000Btu/h
15 30
(2637W) (10548W)
12000Btu/h 42000Btu/h
20 30
(3516W) (12306W)
18000Btu/h 48000Btu/h
25 30
(5274W) (14064W)
4. The additional refrigerant oil and refrigerant charging required after prolonging
connection pipe
● After the length of connection pipe is prolonged for 10m at the basis of
standard length, you should add 5ml of refrigerant oil for each additional 5m
of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis
of liquid pipe):
Additional refrigerant charging amount = prolonged length of liquid pipe ×
additional refrigerant charging amount per meter
● Basing on the length of standard pipe, add refrigerant according to the
requirement as shown in the table. The additional refrigerant charging amount
per meter is different according to the diameter of liquid pipe. See the
following sheet.
Configuration of connection pipe
Additional refrigerant charging amount for R22, R407C, R410A and R134a
Φ6 Φ9.52 or Φ12 15 20
Pipe expanding method
Note:
Improper pipe expanding is the main cause of refrigerant leakage. Please expand
the pipe according to the following steps:
A: Cut the pipe E: Expand the port
● Expand the port with expander.
the distance of indoor unit and
outdoor unit. hard
mold
● Cut the required pipe with pipe cutter. expander
pipe
pipe
pipe cutter
Split Air Conditioner
OWNER'S MANUAL
GREE AIR CONDITIONERS
Model A:
GWHD09ABNK3A1B
GWHD12ABNK3A1B
Model B:
GWHD09ABNK3A1C
GWHD12ABNK3A1C
Thank you for choosing GREE air conditioner for correct operation, please
read this owner's manual carefully before operating the unit and keeps
66129924019 it carefully for consultation.
8. Division 26- Electrical
Content
1.6 Storage
1.7 Operation
1.12 Troubleshooting
Schedule of Operation and Maintenance Data Package for General
Electrical System
Note: The following instructions are provide for proper and safe maintenance of the 12 Plex
Phase I electrical system. Read theses instructions before start any operation or maintenance.
Make sure you have the proper personal protective equipment before you start any operation or
maintenance. Only qualified persons can make operation and maintenance in the electrical
system.
Prestart, startup operation only applies at any time on daylight, but make sure:
1.2.1 Close the load break cutout with its respective tool.
1.2.2 The ON/OFF switch main panels “S” has to be on the OFF Position.
1.2.3 “Insulation resistance test” (600 Volts wiring test) has to be done on the Power
Center. Both parts AC Circuit.
1.2.4 Confirm the transformer open circuit voltage is between 208-120 Vac.
1.2.5 Close doors the transformer and panels.
This procedure can be done at any time, to shut down the panels:
The term qualified personnel is defined hare as individual who thoroughly understand the
equipment and its safe operation, maintenance and repair.
Qualified personnel are physically capable of performing the required tasks, familiar with all
relevant safety rules and regulations and have been trained to safely install, operate, maintain
and repair the equipment. It is the responsibility of the company operating this equipment to
ensure that its personnel meet these requirements. Always use required personal protective
equipment (PPE) and follow safe electrical work practices.
1.6 Storage
If equipment is to be stored prior to installation, it must be protected from the weather and kept
free of condensation and dust. Failure to follow this instruction can result in injury or equipment
damage.
1.7 Operation
Read the follow instructions carefully before start any operation procedure:
1.7.1 Only qualified personnel, physically capable of operating the equipment and with no
impairments in their judgment or reaction time, should operate this equipment.
1.7.2 Read all system component manuals before operating this equipment. A thorough
understanding of system components and their operation will help you operate the
system safely and efficiently.
1.7.3 Before starting this equipment, check all safety interlocks, fire- detection systems, and
protective device such as panels and covers. Make sure all devices are fully functional.
Do not deactivate or bypass automatic safety interlocks or locked-out electrical
disconnects or pneumatic valves.
1.7.4 Protect equipment with safety device with safety devices as specified by applicable
safety regulations.
1.7.5 If safety devices must be removed for installation, install them immediately after the
work is completed and check them for proper functioning.
1.7.6 Route electrical wiring along a protected path. Make sure they will not be damaged by
moving equipment.
1.7.7 Never operate equipment with a known malfunction.
1.7.8 Do not attempt to operate or service electrical equipment if standing water is present.
1.7.9 Use this equipment only in the environments for which is rated. Do not operate this
equipment in humid, flammable, or explosive environments.
1.7.10 Never touch exposed electrical connections on equipment while the power is ON.
1.10.1 Allow only qualified personnel to perform maintenance troubleshooting, and repair
tasks.
1.10.2 Only persons who are properly trained and familiar with airfield solutions equipment
are permitted to service this equipment.
1.10.3 Disconnect and lock out electrical power.
1.10.4 Always use safety devices when working on this equipment.
1.10.5 Follow the recommended maintenance procedures in the product manuals.
1.10.6 Do not service or adjust any equipment unless another person trained in first aid and
CPR is present.
1.10.7 Connect all disconnected equipment ground cables and wires after servicing equipment.
1.10.8 Ground all conductive equipment
1.10.9 Use only approved replacement parts.
1.10.10 Using unapproved parts or making unapproved modifications to equipment may avoid
agency approvals and create safety hazards.
1.10.11 Check interlocks system periodically to ensure their effectiveness.
1.10.12 Use tools with insulated handles when working with electrical equipment.
1.12 Troubleshooting
Three-Phase
Pad-Mounted Transformers
STANDAR
For more information contact your local GE Sales Representative or visit our website at www.prolecge.com
Phone: Toll free 1 800-437-7653 (US & Canada) / +52 (81) 8030-2341 (Mexico) / Fax: +52 (81) 8030-2323 or 2325
3PPMTR-1011-02
8.2.1 South Wire Conductor
SIMpull THHN®
Copper THHN Wire & Cable
600 Volts. Copper Conductor. Thermoplastic Insulation/Nylon Sheath, Heat, Moisture, Gasoline and Oil
Resistant II. All Sizes Rated Both THHN and either THWN (sizes 14, 12, and 10 AWG) or THWN-2 (sizes 8
AWG and larger). Also Rated MTW and AWM (See Below). SIMpull® Technology for Easier Pulling.
APPLICATIONS
Southwire® SIMpull THHN® copper conductors are primarily used in conduit and cable trays for services,
feeders and branch circuits in commercial or industrial applications as specified in the National Electrical
Code. Voltage for all applications is 600 volts. SIMpull THHN® copper conductors are designed to be
installed without application of a pulling lubricant.
These conductors have multiple ratings. Depending upon the product application, allowable temperatures
are as follows:
• THHN or T90 Nylon- Dry locations not to exceed 90° C
• THWN-2- Wet or dry locations not to exceed 90° C or locations not to exceed 75°C when exposed
to oil
• THWN- Wet locations not to exceed 75° C or dry locations not to exceed 90° C or locations not
to exceed 75° C when exposed to oil
• TWN75- Wet locations not to exceed 75° C
• MTW- Wet locations or when exposed to oil at temperatures not to exceed 60° C or dry locations
not to exceed 90° C (with ampacity limited to that for 75° C conductor temperature per NFPA 79)
• AWM- Dry locations not to exceed 105° C only when rated and used as appliance wiring material
CONSTRUCTION
Southwire® SIMpull THHN® copper conductors are made with soft drawn copper. Sizes 14 through 4/0 AWG use a
combination-unilay stranding while 250 kcmil and larger sizes use a compressed copper stranding. The wire is
covered with a tough heat and moisture resistant PVC insulation with an overall nylon jacket utilizing SIMpull®
Technology. Available in black, white, red, blue, purple, green, yellow, orange, brown, and gray. Also available in
striped configurations. Some colors are subject to economic order quantity. Marked as THHN in all sizes. Also
marked as THWN-2 in sizes 8 AWG and larger or marked as THWN in sizes 14, 12, and 10 AWG. Marked sunlight
resistant in sizes 2 AWG and larger. Sizes 14, 12, and 10 AWG are available with SIMpull® Technology only in
SIMpull BARREL™ cable drum or SIMpull® CoilPAK™ configurations.
Conductor Approx. Allowable Ampacities+
Insulation Jacket Nominal Net Wt.
Standard
Size (AWG Thickness Thickness O.D. Per
No. of strands (mils) 60°C 75°C 90°C Package
or kcmil) (mils) (mils) 1000'
(lbs.)
14* 1 15 4 102 15 15 15 15 AC
12* 1 15 4 119 23 20 20 20 AC
10* 1 20 4 150 36 30 30 30 AC
14* 19 15 4 109 16 15 15 15 AC
12* 19 15 4 128 24 20 20 20 AC
10* 19 20 4 161 38 30 30 30 AC
8 19 30 5 213 63 40 50 55 ABCD
6 19 30 5 249 95 55 65 75 ABCD
4 19 40 6 318 152 70 85 100 ABCD
3 19 40 6 346 189 85 100 115 ABCD
2 19 40 6 378 234 95 115 130 ABCD
1 19 50 7 435 299 110 130 145 ABCD
1/0 19 50 7 474 372 125 150 170 ABCD
2/0 19 50 7 518 462 145 175 195 ABCD
3/0 19 50 7 568 575 165 200 225 ABCD
4/0 19 50 7 624 718 195 230 260 ABCD
250 37 60 8 694 851 215 255 290 ABCD
300 37 60 8 747 1012 240 285 320 ABC
350 37 60 8 797 1174 260 310 350 ABC
400 37 60 8 842 1334 280 335 380 ABC
500 37 60 8 926 1655 320 380 430 ABCD
600 61 70 9 1024 1987 350 420 475 ABC
750 61 70 9 1126 2464 400 475 535 BC
1000 61 70 9 1275 3257 455 545 615 C
* Sizes 14, 12, and 10 AWG are available with SIMpull® Technology only in SIMpull® Barrel or CoilPAK® configurations. Standard put ups
vary from the ones shown on this chart for standard 14-10 AWG THHN. Package
+Allowable ampacities shown are for general use as specified by the 2014 Edition of the National Electrical Code Sections 310.15 and Codes:
240.4(D). A - 2500' Reel
Unless the equipment is marked for use at higher temperatures the conductor shall be limited to the following per NEC 110.14(C): B - 1000' Reel
60° C - When terminated to equipment for circuits rated 100 amperes or less or marked for 14 - 1 AWG conductors.
C - 500' Spool
75° C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
D - 5000' Reel
90° C - THHN dry locations and THWN-2 wet or dry locations for ampacity adjustment purposes using NEC section 310.15.
8.2 Division 26 20 00- Interior Distribution System
Disconnect Switch 30 AMP, SPEC 2.8.2
800A and 1200A non-double throw safety switches also use the C nomenclature
1
Note: This information is provided for interpreting numbers. It should not be used to build product numbers.
3
Heavy Duty Safety Switches
GE’s Type TH heavy duty safety switches are designed for commercial and industrial applications where safety, high performance
and continuity of service are essential. Heavy duty switches are available in 30-1200 amps, 600 Vac, 600 Vdc maximum, fusible
and non-fusible units, and in NEMA Type 1 (indoor), Type 3R (outdoor), Type 4/4X (water and dust-tight, corrosion resistant), and
Type 5/12 (drip and dust-tight) enclosures. When used with Class R or J fuses, 30-600 amp switches have a UL Listed short-circuit
rating of 200,000 rms symmetrical amps. Switches rated 800-1200 amps use Class L fuses and have a UL Listed short circuit
rating of 100,000 rms symmetrical amps. GE’s heavy duty safety switches are UL Listed as service entrance equipment when
installed in accordance with the National Electrical Code.
Features
1 Highly visible ON/OFF label
5
2 Donut handle ideal for hook stick operation
and accepts 3 padlocks in the OFF position
6
Heavy Duty Safety Switches (continued)
Non-Fusible
Product Number Horsepower Rating DC Hp
Amperage NEMA NEMA Single- Three- Single- Three- Single- Three-
NEMA 250 Vdc
N
Rating Type 1 Type 3R Phase Phase Phase Phase Phase Phase
Type 5, 12
Indoor Outdoor 240 Vac Standard 480 Vac Standard 600 Vac Standard Standard
Non-Fusible / 3 Pole / 3 Wire / 240V / 50/60 Hz
N
30 THN3321 3 10 5
Non-Fusible / 3 Pole / 3 Wire / 600V / 50/60 Hz
N THN33612 THN3222R THN3361J2, 3
30 TH3361RF4 3 10 7.5 20 10 30 5
TH3361RF24
THN32222 THN3362R THN3362J2, 3
N
60 10 20 20 50 25 60 10
THN3362RF4
100 THN33632 THN3363R THN3363J 2,3
20 40 30 75 40 100 20
200 THN33641,2 THN3364R THN3364J3 30 60 50 125 50 150 40
400 THN33651 THN3365R THN3365J 125 250 350 50
600 THN33661 THN3366R THN3366J 200 400 500 50
800 TC36367
1200 TC36368
Non-Fusible / 6 Pole / 6 Wire / 600V / 50/60 Hz
30 THN6661 3 7.5 15 10 20 5
60 THN6662 10 20 30 25 50 10
100 THN6663 15 30 60 40 75 20
200 THN6664 15 50 125 50 150 40
Type 1 Enclosure: 200-600 Amp devices available factory reversed for
1 3
Available with Viewing Window. Add "W" suffix.
bottom feed. Add "B" suffix. 4
Farm switch with oversize Type 3R enclosure and vertical hinge. See page 27
2
Available with Copper Lug. Add "CL" suffix for dimensions.
6
Class L fuses are only applicable when used with 800 and 1200A Type TC safety switches.
7
Unless otherwise noted.
800A and 1200A non-double throw safety switches also use the C nomenclature
1
Note: This information is provided for interpreting numbers. It should not be used to build product numbers.
3
Heavy Duty Safety Switches
GE’s Type TH heavy duty safety switches are designed for commercial and industrial applications where safety, high performance
and continuity of service are essential. Heavy duty switches are available in 30-1200 amps, 600 Vac, 600 Vdc maximum, fusible
and non-fusible units, and in NEMA Type 1 (indoor), Type 3R (outdoor), Type 4/4X (water and dust-tight, corrosion resistant), and
Type 5/12 (drip and dust-tight) enclosures. When used with Class R or J fuses, 30-600 amp switches have a UL Listed short-circuit
rating of 200,000 rms symmetrical amps. Switches rated 800-1200 amps use Class L fuses and have a UL Listed short circuit
rating of 100,000 rms symmetrical amps. GE’s heavy duty safety switches are UL Listed as service entrance equipment when
installed in accordance with the National Electrical Code.
Features
1 Highly visible ON/OFF label
5
2 Donut handle ideal for hook stick operation
and accepts 3 padlocks in the OFF position
6
Heavy Duty Safety Switches (continued)
Non-Fusible
Product Number Horsepower Rating DC Hp
Amperage NEMA NEMA Single- Three- Single- Three- Single- Three-
NEMA 250 Vdc
N
Rating Type 1 Type 3R Phase Phase Phase Phase Phase Phase
Type 5, 12
Indoor Outdoor 240 Vac Standard 480 Vac Standard 600 Vac Standard Standard
Non-Fusible / 3 Pole / 3 Wire / 240V / 50/60 Hz
N
30 THN3321 3 10 5
Non-Fusible / 3 Pole / 3 Wire / 600V / 50/60 Hz
N THN33612 THN3222R THN3361J2, 3
30 TH3361RF4 3 10 7.5 20 10 30 5
TH3361RF24
THN32222 THN3362R THN3362J2, 3
N
60 10 20 20 50 25 60 10
THN3362RF4
100 THN33632 THN3363R THN3363J 2,3
20 40 30 75 40 100 20
200 THN33641,2 THN3364R THN3364J3 30 60 50 125 50 150 40
400 THN33651 THN3365R THN3365J 125 250 350 50
600 THN33661 THN3366R THN3366J 200 400 500 50
800 TC36367
1200 TC36368
Non-Fusible / 6 Pole / 6 Wire / 600V / 50/60 Hz
30 THN6661 3 7.5 15 10 20 5
60 THN6662 10 20 30 25 50 10
100 THN6663 15 30 60 40 75 20
200 THN6664 15 50 125 50 150 40
Type 1 Enclosure: 200-600 Amp devices available factory reversed for
1 3
Available with Viewing Window. Add "W" suffix.
bottom feed. Add "B" suffix. 4
Farm switch with oversize Type 3R enclosure and vertical hinge. See page 27
2
Available with Copper Lug. Add "CL" suffix for dimensions.
6
Class L fuses are only applicable when used with 800 and 1200A Type TC safety switches.
7
Unless otherwise noted.
CVM-C10
INSTRUCTION MANUAL
(M001B01-03-20A)
CVM-C10
2 Instruction Manual
CVM-C10
SAFETY PRECAUTIONS
Follow the warnings described in this manual with the symbols shown below.
DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a specific point.
If you must handle the unit for its installation, start-up or maintenance, the following
should be taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well as damage
to the unit. In particular, handling with voltages applied may result in electric shock, which may
cause death or serious injury to personnel. Defective installation or maintenance may also
lead to the risk of fire.
Read the manual carefully prior to connecting the unit. Follow all installation and maintenance
instructions throughout the unit’s working life. Pay special attention to the installation stan-
dards of the National Electrical Code.
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can
result in injury or damage to the unit and /or installations.
CIRCUTOR, SA reserves the right to modify features or the product manual without prior notification.
DISCLAIMER
CIRCUTOR, SA reserves the right to make modifications to the device or the unit specifica-
tions set out in this instruction manual without prior notice.
CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device
specifications and the most updated manuals.
www.circutor.com
Instruction Manual 3
CVM-C10
CONTENTS
SAFETY PRECAUTIONS��������������������������������������������������������������������������������������������������������������������������������������� 3
DISCLAIMER����������������������������������������������������������������������������������������������������������������������������������������������������������3
CONTENTS�������������������������������������������������������������������������������������������������������������������������������������������������������������4
REVISION LOG�������������������������������������������������������������������������������������������������������������������������������������������������������6
1.- VERIFICATION UPON RECEPTION����������������������������������������������������������������������������������������������������������������� 7
2.- PRODUCT DESCRIPTION�������������������������������������������������������������������������������������������������������������������������������� 7
3.- DEVICE INSTALLATION����������������������������������������������������������������������������������������������������������������������������������� 9
3.1.- PRIOR RECOMMENDATIONS������������������������������������������������������������������������������������������������������������������ 9
3.2.- INSTALLATION���������������������������������������������������������������������������������������������������������������������������������������� 10
3.3.- CVM-C10-FLEX: ROGOWSKI SENSORS����������������������������������������������������������������������������������������������� 10
3.4.- DEVICE TERMINALS������������������������������������������������������������������������������������������������������������������������������� 12
3.4.1.- LIST OF TERMINALS, CVM-C10-ITF, CVM-C10-MC AND CVM-C10-mV MODELS�������������������� 12
3.4.2.- LIST OF TERMINALS, CVM-C10-ITF-IN AND CVM-C10-MC-IN MODELS.���������������������������������� 13
3.4.3.- LIST OF TERMINALS, CVM-C10-FLEX MODEL��������������������������������������������������������������������������� 14
3.5.- CONNECTION DIAGRAM������������������������������������������������������������������������������������������������������������������������ 15
3.5.1.- MEASURING THREE-PHASE NETWORKS WITH A 4-WIRE CONNECTION, CVM-C10-ITF
AND CVM-C10-mV MODEL.��������������������������������������������������������������������������������������������������������������������� 15
3.5.2.- MEASURING THREE-PHASE NETWORKS WITH A 4-WIRE CONNECTION, CVM-C10-ITF-IN
MODEL.������������������������������������������������������������������������������������������������������������������������������������������������������ 16
3.5.3.- MEASURING THREE-PHASE NETWORKS WITH A 4-WIRE CONNECTION CVM-C10-MC
MODEL.������������������������������������������������������������������������������������������������������������������������������������������������������ 17
3.5.4.- MEASURING THREE-PHASE NETWORKS WITH A 4-WIRE CONNECTION CVM-C10-MC-IN
MODEL.������������������������������������������������������������������������������������������������������������������������������������������������������ 18
3.5.5.- MEASURING THREE-PHASE NETWORKS WITH A 4-WIRE CONNECTION, CVM-C10-FLEX
MODEL������������������������������������������������������������������������������������������������������������������������������������������������������� 19
3.5.6.- MEASURING THREE-PHASE NETWORKS WITH A 3-WIRE CONNECTION, CVM-C10-ITF AND
CVM-C10-mV MODEL. ������������������������������������������������������������������������������������������������������������������������������ 20
3.5.7.- MEASURING THREE-PHASE NETWORKS WITH A 3-WIRE CONNECTION, CVM-C10-MC
MODEL. ����������������������������������������������������������������������������������������������������������������������������������������������������� 21
3.5.8.- MEASURING THREE-PHASE NETWORKS WITH A 3-WIRE CONNECTION, CVM-C10-FLEX
MODEL������������������������������������������������������������������������������������������������������������������������������������������������������� 22
3.5.9.- MEASURING THREE-PHASE NETWORKS WITH A 3-WIRE CONNECTION AND TRANSFOR
MERS WITH AN ARON CONNECTION, CVM-C10-ITF AND CVM-C10-MC MODELS. �������������������������� 23
3.5.10.- MEASURING TWO-PHASE NETWORKS WITH A 3-WIRE CONNECTION, CVM-C10-ITF,
CVM-C10-MC AND CVM-C10-mV MODELS.������������������������������������������������������������������������������������������� 24
3.5.11.- MEASURING TWO-PHASE NETWORKS WITH A 3-WIRE CONNECTION, CVM-C10-ITF-IN
AND CVM-C10-MC-IN MODELS.��������������������������������������������������������������������������������������������������������������� 25
3.5.12.- MEASURING TWO-PHASE NETWORKS WITH A 3-WIRE CONNECTION, CVM-C10-FLEX
MODEL.������������������������������������������������������������������������������������������������������������������������������������������������������ 26
3.5.13.- MEASURING SINGLE-PHASE NETWORKS, PHASE TO PHASE, WITH A 2-WIRE CONNEC-
TION, CVM-C10-ITF, CVM-C10-MC AND CVM-C10-mV MODELS.�������������������������������������������������������� 27
3.5.14.- MEASURING SINGLE-PHASE NETWORKS, PHASE TO PHASE, WITH A 2-WIRE CONNEC-
TION, CVM-C10-FLEX MODEL.��������������������������������������������������������������������������������������������������������������� 28
3.5.15.- MEASURING SINGLE-PHASE NETWORKS, PHASE TO NEUTRAL, WITH A 2-WIRE CON-
NECTION, CVM-C10-ITF, CVM-C10-MC AND CVM-C10-mV MODELS.������������������������������������������������� 29
3.5.16.- MEASURING SINGLE-PHASE NETWORKS, PHASE TO NEUTRAL, WITH A 2-WIRE CON-
NECTION, CVM-C10-FLEX MODEL.��������������������������������������������������������������������������������������������������������� 30
4.- OPERATION����������������������������������������������������������������������������������������������������������������������������������������������������31
4.1.- MEASURING PARAMETERS������������������������������������������������������������������������������������������������������������������ 32
4.2.- KEYBOARD FUNCTIONS������������������������������������������������������������������������������������������������������������������������ 33
4.3.- DISPLAY��������������������������������������������������������������������������������������������������������������������������������������������������� 35
4.3.1. cos φ - PF (POWER FACTOR) BAR����������������������������������������������������������������������������������������������� 35
4.3.2. ANALOGUE BAR����������������������������������������������������������������������������������������������������������������������������� 36
4.3.3. OTHER SYMBOLS ON THE DISPLAY�������������������������������������������������������������������������������������������� 36
4.4.- LED INDICATORS����������������������������������������������������������������������������������������������������������������������������������� 37
4.5.- OPERATION PROFILES������������������������������������������������������������������������������������������������������������������������� 37
4.5.1. ANALYZER PROFILE����������������������������������������������������������������������������������������������������������������������� 37
4.5.2. e3 PROFILE������������������������������������������������������������������������������������������������������������������������������������� 41
4.5.3. USER������������������������������������������������������������������������������������������������������������������������������������������������ 44
4 Instruction Manual
CVM-C10
4.6.- HARMONICS�������������������������������������������������������������������������������������������������������������������������������������������� 44
4.7.- INPUTS����������������������������������������������������������������������������������������������������������������������������������������������������� 45
4.8.- OUTPUTS������������������������������������������������������������������������������������������������������������������������������������������������� 45
4.9.- PROGRAMMING�������������������������������������������������������������������������������������������������������������������������������������� 46
4.9.1. PRIMARY VOLTAGE������������������������������������������������������������������������������������������������������������������������ 47
4.9.2. SECONDARY VOLTAGE������������������������������������������������������������������������������������������������������������������ 48
4.9.3. PRIMARY CURRENT����������������������������������������������������������������������������������������������������������������������� 48
4.9.4. SECONDARY CURRENT ( MODEL CVM-C10-ITF)������������������������������������������������������������������������ 49
4.9.5. PRIMARY NEUTRAL CURRENT ( MODELS: CVM-C10-ITF-IN AND CVM-C10-MC-IN)�������������� 49
4.9.6. SECUNDARY NEUTRAL CURRENT (MODEL CVM-C10-ITF-IN)�������������������������������������������������� 50
4.9.7. NUMBER OF QUADRANTS������������������������������������������������������������������������������������������������������������ 50
4.9.8. MEASUREMENT CONVENTION����������������������������������������������������������������������������������������������������� 50
4.9.9. TYPE OF INSTALLATION���������������������������������������������������������������������������������������������������������������� 51
4.9.10. MAXIMUM DEMAND INTEGRATION PERIOD������������������������������������������������������������������������������ 51
4.9.11. DELETING MAXIMUM DEMAND��������������������������������������������������������������������������������������������������� 52
4.9.12. SELECTING THE OPERATION PROFILE������������������������������������������������������������������������������������� 52
4.9.13. BACKLIGHT, TURNING ON THE BACKLIT DISPLAY����������������������������������������������������������������� 54
4.9.14. SELECTING THE Cos φ - PF BAR ON THE DISPLAY���������������������������������������������������������������� 54
4.9.15. DELETING MAXIMUM AND MINIMUM VALUES�������������������������������������������������������������������������� 55
4.9.16. DELETING ENERGY VALUES������������������������������������������������������������������������������������������������������� 55
4.9.17. SELECTING THE RANGE OF ENERGIES������������������������������������������������������������������������������������ 55
4.9.18. ACTIVATING THE HARMONICS DISPLAY SCREEN.������������������������������������������������������������������ 56
4.9.19. kgC02 CARBON EMISSION RATIO OF GENERATED ENERGY������������������������������������������������� 56
4.9.20. kgC02 CARBON EMISSION RATIO OF CONSUMED ENERGY��������������������������������������������������� 57
4.9.21. COST RATIO OF GENERATED ENERGY������������������������������������������������������������������������������������� 57
4.9.22. COST RATIO OF CONSUMED ENERGY�������������������������������������������������������������������������������������� 58
4.9.23. PROGRAMMING ALARM 1 (RELAY 1)����������������������������������������������������������������������������������������� 59
4.9.24. PROGRAMMING ALARM 2 (RELAY 2)����������������������������������������������������������������������������������������� 64
4.9.25. PROGRAMMING ALARM 3 (DIGITAL OUTPUT T1)��������������������������������������������������������������������� 64
4.9.26. PROGRAMMING ALARM 4 (DIGITAL OUTPUT T2)��������������������������������������������������������������������� 66
4.9.27. OPERATING MODE OF DIGITAL INPUT 1����������������������������������������������������������������������������������� 67
4.9.28. OPERATING MODE OF DIGITAL INPUT 2����������������������������������������������������������������������������������� 67
4.9.29. RS-485 COMMUNICATIONS: PROTOCOL����������������������������������������������������������������������������������� 67
4.9.30. LOCKING THE PROGRAMMING�������������������������������������������������������������������������������������������������� 71
4.10.- COMMUNICATIONS������������������������������������������������������������������������������������������������������������������������������� 73
4.10.1. CONNECTIONS������������������������������������������������������������������������������������������������������������������������������ 73
4.10.2. PROTOCOL������������������������������������������������������������������������������������������������������������������������������������ 74
4.10.3. MODBUS COMMANDS������������������������������������������������������������������������������������������������������������������ 75
4.10.4. BACnet PROTOCOL���������������������������������������������������������������������������������������������������������������������� 85
4.10.5. MAPA PICS������������������������������������������������������������������������������������������������������������������������������������� 86
5.- TECHNICAL FEATURES�������������������������������������������������������������������������������������������������������������������������������� 89
6.- MAINTENANCE AND TECHNICAL SERVICE������������������������������������������������������������������������������������������������ 93
7.- GUARANTEE���������������������������������������������������������������������������������������������������������������������������������������������������93
8.- CE CERTIFICATE��������������������������������������������������������������������������������������������������������������������������������������������94
Instruction Manual 5
CVM-C10
REVISION LOG
Table 1: Revision log.
Date Revision Description
04/14 M001B01-03-14A Initial Version
Changes in the following sections:
06/14 M001B01-03-14B
3.4 - 4.9 - 4.10 - 5
Changes in the following sections:
06/14 M001B01-03-14C
4.9.5 - 4.9.6 - 4.10.2.1
Changes in the following sections:
11/14 M001B01-03-14D
4.9.21 - 4.9.23 - 4.10.2 - 4.10.3 - 5
Changes in the following sections:
11/14 M001B01-03-14E
3.3.2 - 3.4.2 - 3.4.8 - 4.5 - 4.9 - 4.10.3.1
Changes in the following sections:
01/15 M001B01-03-15A
2 - 3.3.- 3.4- 4.1- 4.9.4 -4.9.28 - 4.10 - 4.10.3.2 - 5
Changes in the following sections:
10/15 M001B01-03-15B 4.2 - 4.5.1 - 4.5.3 - 4.6 - 4.7 - 4.9 - 4.9.1 - 4.9.9 - 4.9.12 -
4.9.22.- 4.9.24 - 4.10.5
Changes in the following sections:
12/15 M001B01-03-15C
3.2.- 4.- 4.3.1.- 4.9.- 4.10.3.6. - 4.10.4.- 4.10.5.- 5.
Changes in the following sections:
07/16 M001B01-03-16A
4.9.23
Changes in the following sections:
02/17 M001B01-03-17A
2.- 3.3. - 3.4. - 3.5. - 4.7. - 4.8. - 4.9.- 4.10.3.6. - 4.10.3.7 - 5
Changes in the following sections:
07/17 M001B01-03-17B
5. - 8.
Changes in the following sections:
10/17 M001B01-03-17C
3.3 - 5.
Changes in the following sections:
06/18 M001B01-03-18A 2. - 3.4.2. - 3.5. - 4.1. - 4.5.1. - 4.5.3. - 4.8. - 4.9.5. - 4.9.23. -
4.10.3.1. - 4.10.3.7.2. - 4.9.25. - 4.9.26.- 4.10.3.7.13. - 5.
Changes in the following sections:
01/19 M001B01-03-19A
3.3.
Changes in the following sections:
02/19 M001B01-03-19B
5.
Changes in the following sections:
05/19 M001B01-03-19C
4.5.1. - 4.10.3.7.
Changes in the following sections:
10/19 M001B01-03-19D
2. - 4.3. - 4.4.
Changes in the following sections:
04/20 M001B01-03-20A
4.10.3.3. - 5.
Note: Devices images are for illustrative purposes only and may differ from the actual device.
6 Instruction Manual
CVM-C10
The CVM-C10 device measures, calculates and displays the main electrical parameters of the
following networks: single-phase, two-phase, with and without neutral, balanced three-phase,
with ARON measurements or unbalanced. The measurement will be taken in RMS with the
three AC voltage inputs and three current inputs.
There are 6 versions of the device, depending on the type of current input:
- 3 keys that allow you to browse between the various screens and program the device.
- 3 indicator LEDs: CPU, ALARM and KEY.
- LCD display, displays all parameters,
Instruction Manual 7
CVM-C10
- 2 digital inputs, used to select the tariff or detect the logic state of external signals.
- 2 digital outputs, fully programmable.
(Not available in the CVM-C10-ITF-IN, CVM-C10-MC-IN and CVM-C10-FLEX models)
- 2 alarm relays, fully programmable (Not available in the CVM-C10-FLEX model)
- RS-485 Communications, with two serial protocols: MODBUS RTU© and BACnet.
8 Instruction Manual
CVM-C10
In order to use the device safely, it is critical that individuals who handle it follow
the safety measures set out in the standards of the country where it is being used,
use the necessary personal protective equipment, and pay attention to the vari-
ous warnings indicated in this instruction manual.
The power supply plug must be disconnected and measuring systems switched off before
handling, altering the connections or replacing the device. It is dangerous to handle the device
while it is powered.
Also, it is critical to keep the cables in perfect condition in order to avoid accidents, personal
injury and damage to installations.
The manufacturer of the device is not responsible for any damage resulting from failure by the
user or installer to heed the warnings and/or recommendations set out in this manual, nor for
damage resulting from the use of non-original products or accessories or those made by other
manufacturers.
If an anomaly or malfunction is detected in the device, do not use it to take any measure-
ments.
Inspect the work area before taking any measurements. Do not take measurements in danger-
ous areas or where there is a risk of explosion.
Disconnect the device from the power supply (device and measuring system
power supply) before maintaining, repairing or handling the device's connections.
Please contact the after-sales service if you suspect that there is an operational
fault in the device.
Instruction Manual 9
CVM-C10
3.2.- INSTALLATION
The device will be installed on a panel (92+0.8 x 92+0.8 mm panel drill hole, in compliance with DIN
43700). All connections are located inside the electric panel.
Terminals, opening covers or removing elements can expose parts that are haz-
ardous to the touch while the device is powered. Do not use the device until it is
fully installed.
The device must be connected to a power circuit that is protected with gl (IEC 269) or M type
fuses with a rating of 0.5 to 2 A. It must be fitted with a circuit breaker or equivalent device, in
order to be able to disconnect the device from the power supply network.
The power and voltage measuring circuit must be connected with cables that have a minimum
cross-section of 1mm2.
The secondary line of the current transformer will have a minimum cross-section of 2.5 mm2.
The temperature rating of insulation of wires connected to the device will be at minimum 62ºC.
The CVM-C10-FLEX model measures currents using flexible sensors, based on the Rogowski
coil principle.
The flexibility of the sensor allows it to measure an alternating current irrespective of the posi-
tion of the conductor.
CIRCUTOR has a Rogowski sensor model that can be used with the CVM-C10-FLEX: FLEX-
MAG.
Table 3 shows the connection of the sensors and Table 2 the maximum position error.
A ± 1%
B
B A ± 3%
10 Instruction Manual
CVM-C10
Shield
Común / Common
Instruction Manual 11
CVM-C10
2 3 4 5 6 7 8 9 10 11 12
1 13
OUTPUTS
S0- S0+ S0+
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
Rc R2 R1 Tc T2 T1
GND
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
14 15 16 17 18 19 20 21 22 23
12 Instruction Manual
CVM-C10
2 3 4 5 6 7 8 9 10 11
1 12
OUTPUTS
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
Rc R2 R1 S2 S1
LN
GND
P2 P1
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
13 14 15 16 17 18 19 20 21 22
Instruction Manual 13
CVM-C10
2 3 4 5 6
1 7
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
GND
Ph-Ph Ph-N
520V ~ 300V ~ FLEX-MAG (100mV~ )
8 9 10 11 12 13 14 15 16 17
14 Instruction Manual
CVM-C10
Measurement system:
Power
Supply
OUTPUTS
S0- S0+ S0+
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
Rc R2 R1 Tc T2 T1
GND
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
b a
a b
A B A B
S1 S2
L1
P1 P2
S1 S2
L2
P1 P2
S1 S2
L3 P1 P2
LOAD
N
Figure 4: Three-Phase measuring with a 4-wire connection, CVM-C10-ITF and CVM-C10-mV model.
Instruction Manual 15
CVM-C10
Measurement system:
Power
Supply
OUTPUTS
RS485 INPUTS
POWER SUPPLY A(+) B(-)
A I1 I2
Rc R2 R1 S2 S1
LN
GND
P2 P1
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
b a
a b
A B A B
S1 S2
L1
P1 P2 S1 S2
L2
P1 P2 S2
S1
L3
P1 P2
S1 S2
LOAD
N
P1 P2
16 Instruction Manual
CVM-C10
Measurement system:
Power
Supply
OUTPUTS
S0- S0+ S0+
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
Rc R2 R1 Tc T2 T1
GND
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
Grey/Pink
Green/White
Red/Blue
Brown/Green
VL1 VL2 VL3
VL1 VL2 VL3 N
b a
a b
A B A B
L1
1P1
1P2
L2
2P1
2P2
L3
3P1
3P2
LOAD
N
Instruction Manual 17
CVM-C10
Measurement system:
Power
Supply
OUTPUTS
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
Rc R2 R1 S2 S1
LN
GND
P2 P1
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
Grey/Pink
Green/White
Red/Blue
Brown/Green
VL1 VL2 VL3
VL1 VL2 VL3 N
b a
a b
A B A B
L1
1P1
1P2
L2
2P1
2P2
L3
3P1
3P2
S1 S2
LOAD
N P1 P2
18 Instruction Manual
CVM-C10
Measurement system:
Power
Supply
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
GND
Ph-Ph Ph-N
300V ~ FLEX-MAG (100mV~ )
520V ~
VL1 VL2 VL3 N L1 L2 L3 LN C SHLD
L1
L2
L3
LOAD
N
Instruction Manual 19
CVM-C10
Measurement system:
Power
Supply
OUTPUTS
S0- S0+ S0+
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
Rc R2 R1 Tc T2 T1
GND
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
b a b
a
A B A B
S1 S2
L1
P1 P2 S1 S2
L2 P1 P2 S1 S2
LOAD
L3
P1 P2
Figure 9: Three-Phase measuring with a 3-wire connection, CVM-C10-ITF and CVM-C10-mV model.
20 Instruction Manual
CVM-C10
Measurement system:
Power
Supply
OUTPUTS
S0- S0+ S0+
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
Rc R2 R1 Tc T2 T1
GND
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
Grey/Pink
Green/White
Red/Blue
Brown/Green
VL1 VL2 VL3
VL1 VL2 VL3 N
b a
a b
A B A B
L1
1P1
1P2
L2
2P1
2P2
LOAD
L3
3P1
3P2
Instruction Manual 21
CVM-C10
Measurement system:
Power
Supply
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
GND
Ph-Ph Ph-N
520V ~ 300V ~ FLEX-MAG (100mV~ )
L1
L2
LOAD
L3
22 Instruction Manual
CVM-C10
Measurement system:
Power
Supply
OUTPUTS
S0- S0+ S0+
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
Rc R2 R1 Tc T2 T1
GND
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
b a
(1)
a b
A B A B
S1 S2
L1
P1 P2
L2
S1 S2
LOAD
L3 P1 P2
Figure 12: Three-Phase measuring with a 3-wire connection and transformers with an ARON connection, CVM-C10-
ITF and CVM-C10-MC and models.
(1)
Note: Do not connect MC current transformers to ground.
CVM-C10-ITF model:
The transformer secondary value must be 5A or 1A
CVM-C10-MC model:
The MC transformer secondary value is set to 0.250 A (fixed value)
Instruction Manual 23
CVM-C10
Measurement system:
Power
Supply
OUTPUTS
S0- S0+ S0+
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
Rc R2 R1 Tc T2 T1
GND
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
VL1 N VL2
VL1 VL2 N
b a b (1)
a
A B A B
S1 S2
L1
P1 P2 S1 S2
L2 P2
P1
LOAD
N
Figure 13: Measuring Two-Phase Networks with a 3-wire connection, CVM-C10-ITF, CVM-C10-MC and CVM-C10-mV
models.
(1)
Note: Do not connect MC current transformers to ground.
CVM-C10-ITF model:
The transformer secondary value must be 5A or 1A
CVM-C10-MC model:
The MC transformer secondary value is set to 0.250 A (fixed value)
CVM-C10-mV model:
The transformer secondary value must be 0.333 V
24 Instruction Manual
CVM-C10
Measurement system:
Power
Supply
OUTPUTS
RS485 INPUTS
POWER SUPPLY A(+) B(-)
A I1 I2
Rc R2 R1 S2 S1
LN
GND
P2 P1
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
VL1 N VL2
VL1 VL2 N
(1)
b a
a b
A B A B
S1 S2
L1 P1 P2
S1 S2
L2 P1 P2
LOAD S1 S2
N P1 P2
Figure 14: Measuring Two-Phase Networks with a 3-wire connection, CVM-C10-ITF-IN and CVM-C10-MC-IN models.
(1)
Note: Do not connect MC current transformers to ground.
CVM-C10-ITF-IN model:
The transformer secondary value must be 5A or 1A
CVM-C10-MC-IN model:
The MC transformer secondary value is set to 0.250 A (fixed value)
Instruction Manual 25
CVM-C10
Measurement system:
Power
Supply
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
GND
Ph-Ph Ph-N
520V ~ 300V ~ FLEX-MAG (100mV~ )
VL1 N VL2
VL1 VL2 N
b a L1 L2 LN
a b C
SHLD
A B A B
L1
L2
LOAD
N
Figure 15: Measuring Two-Phase Networks with a 3-wire connection, CVM-C10-FLEX model.
26 Instruction Manual
CVM-C10
Measurement system:
Power
Supply
OUTPUTS
S0- S0+ S0+
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
Rc R2 R1 Tc T2 T1
GND
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
VL1 VL2
VL1 VL2
(1)
a b
A B
S1 S2
L1 P1 P2
LOAD
L2
Figure 16: Measuring Single-Phase Networks, phase to phase, with a 2-wire connection, CVM-C10-ITF, CVM-C10-MC
and CVM-C10-mV models.
(1)
Note: Do not connect MC current transformers to ground.
CVM-C10-ITF model:
The transformer secondary value must be 5A or 1A
CVM-C10-MC model:
The MC transformer secondary value is set to 0.250 A (fixed value)
CVM-C10-mV model:
The transformer secondary value must be 0.333 V
Instruction Manual 27
CVM-C10
Measurement system:
Power
Supply
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
GND
Ph-Ph Ph-N
520V ~ 300V ~ FLEX-MAG (100mV~ )
VL1 VL2
VL1 VL2
L1
a b C
SHLD
A B
L1
LOAD
L2
Figure 17: Measuring Single-Phase Networks, phase to phase, with a 2-wire connection, CVM-C10-FLEX model.
28 Instruction Manual
CVM-C10
Measurement system:
Power
Supply
OUTPUTS
S0- S0+ S0+
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
Rc R2 R1 Tc T2 T1
GND
Ph-Ph Ph-N
520V ~ 300V ~ P1 P2 P1 P2 P1 P2
L1 L2 L3
VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
VL1 N
VL1 N
(1)
a b
A B
S1 S2
L1
P1 P2
LOAD
N
Figure 18: Measuring Single-Phase Networks, phase to neutral, with a 2-wire connection, CVM-C10-ITF, CVM-C10-MC
and CVM-C10-mV models.
(1)
Note: Do not connect MC current transformers to ground.
CVM-C10-ITF model:
The transformer secondary value must be 5A or 1A
CVM-C10-MC model:
The MC transformer secondary value is set to 0.250 A (fixed value)
CVM-C10-mV model:
The transformer secondary value must be 0.333 V
Instruction Manual 29
CVM-C10
Measurement system:
Power
Supply
RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2
GND
Ph-Ph Ph-N
520V ~ 300V ~ FLEX-MAG (100mV~ )
VL1 VL2 VL3 N L1 L2 L3 LN C SHLD
VL1 N
VL1 N
a b L1 C
SHLD
A B
L1
LOAD
N
Figure 19: Measuring Single-Phase Networks, phase to neutral, with a 2-wire connection, CVM-C10-FLEX model.
30 Instruction Manual
CVM-C10
4.- OPERATION
The measurement convention is configured in the setup menu, see “4.9.8. Measurement con-
vention”.
Capacitive Inductive
180º 0º
Inductive Capacitive
Single-phase Three-phase Single-phase Three-phase
k k k k
k k k k
k k
-90º
Generation Consumption
Power Power
Operation in the 4 quadrants (Q1, Q2, Q3, Q4) cos φ values in the receiver operating mode (Q1,Q4)
Q
0+ Q1
Q2 Q1
cos φ > 0
P<0 Q>0 PF < 0 P>0 Q>0 PF > 0
Capacitive Inductive
+1
+1
Capacitive P
Inductive
cos φ > 0
P<0 Q<0 PF < 0 P>0 Q<0 PF > 0
Q4 0+ Q4
Q3
Instruction Manual 31
CVM-C10
Operation in the 4 quadrants (Q1, Q2, Q3, Q4) cos φ values in the receiver operating mode (Q1,Q4)
Q
0- Q1
Q2 Q1
cos φ < 0
P<0 Q>0 PF > 0 P>0 Q>0 PF < 0
Capacitive Inductive
-1
+1
Capacitive P
Inductive
cos φ > 0
P<0 Q<0 PF < 0 P>0 Q<0 PF > 0
Q4 0+ Q4
Q3
32 Instruction Manual
CVM-C10
The CVM-C10 has 3 keys that allow you to browse between the various screens and program
the device.
Instruction Manual 33
CVM-C10
Next screen
Line jump.
34 Instruction Manual
CVM-C10
4.3.- DISPLAY
The device has a backlit LCD display showing all the parameters listed in Table 3.
The display is divided into four areas (Figure 23):
The area with data per phase displays the instantaneous, maximum and minimum
values of each phase being measured or calculated by the device.
The total data area displays the totals of the values being measured or calculated by
the device.
Cos φ - PF Bar, displays the value of the system's Cos φ or power factor in real time.
This bar displays the value of the installation's cos φ or power factor in real time.
The parameter that will be displayed is selected on the programming menu. (“4.9.14. Selecting
the Cos φ - PF bar on the display”)
Note: This bar will not be displayed in the IEC and IEEE measurement conventions.
Instruction Manual 35
CVM-C10
The maximum system demand reached, i.e., the maximum power value
reached since the device was started, expressed as a percentage.
This value is displayed with the icon .
The value and the maximum and minimum values are reset. (“4.9.15. Deleting maximum
and minimum values”)
Example: Figure 25 shows that the installation performance is 50% and that the maximum de-
mand of the system is 80%.
Type of installation
The type of installation to which the device is connected can be selected on the program-
ming menu, (“4.9.9. Type of installation”). The selected type is shown on the top left of
the display.
36 Instruction Manual
CVM-C10
The CVM-C10 has 3 operation profiles. The display screens will be opened for the correspond-
ing profile:
Instruction Manual 37
CVM-C10
The device displays 11 different screens for the analyzer profile (Table 12) and the voltage and
current harmonics, up to the 31st order harmonic, for each one of the lines, L1, L2 and L3.
(“4.6.- HARMONICS”)
The inst symbol on the bottom of the screen indicates that the values being displayed are of
the instantaneous type.
Table 12: Analyzer profile screens.
Current L1 (A)
Current L2 (A)
Current L3 (A)
Neutral Current (A)(2)
(2)
Not available for the and
installation types.
38 Instruction Manual
CVM-C10
Instruction Manual 39
CVM-C10
Cos φ L1 (cos φ)
Cos φ L2 (cos φ)
Cos φ L3 (cos φ)
Cos φ III (cos φ)
Also displayed on these screens are:
Maximum values
To see the maximum values of the screen being displayed, press the key for 2 seconds.
These are displayed for 30 seconds. The max symbol is shown on the display (Figure 28)
The maximum and minimum values are reset on the programming menu. (“4.9.15. Deleting
maximum and minimum values”)
Minimum values
To see the minimum values of the screen being displayed, press the key for 2 seconds.
These are displayed for 30 seconds. The min symbol will be displayed (Figure 29)
The maximum and minimum values are reset on the programming menu. (“4.9.15. Deleting
maximum and minimum values”)
40 Instruction Manual
CVM-C10
Maximum Demand
The device calculates the maximum demand of the following:
• Current
• Three-Phase Active Power.
• Three-Phase Apparent Power.
• Three-Phase Inductive Reactive Power
• Three-Phase Capacitive Reactive Power
This value can be displayed on the display screen of the parameter by pressing the and
keys at the same time. The dem symbol appears on the display (Figure 30)
Figure 30: Analyzer profile screen displaying the maximum demand values.
Press keys or to stop displaying the maximum demand values.
The maximum demand values are reset on the programming menu: “4.9.11. Deleting maximum
demand”
The device has a system for detecting the incorrect direction of rotation of the voltages. In other
words, if each of the voltages has been correctly connected to the appropriate terminal, L1 to
terminal VL1, L2 to terminal VL2 and L3 to terminal VL3.
If there is an error in the direction of rotation, the icons L1, L2 and L3 flash on the display.
The device has a RS-485 communications parameter, which indicates whether an incorrect di-
rection of rotation has been detected(“4.10.3.7. Detection of incorrect direction of rotation.”)
Note: The detection of the direction of rotation is only enabled for measurement systems:
Three-phase network measurement (4-3Ph, 3-3Ph y 3-ArOn) and two-phase network measure-
ment with 3-wire connection (3-2Ph).
Instruction Manual 41
CVM-C10
4.5.2. e3 PROFILE
This profile is identified with the e3 symbol on the bottom of the screen (Figure 31).
42 Instruction Manual
CVM-C10
Symbols T1, T2 and T3 on the display indicate the three tariffs available on the device.
The corresponding symbol flashes to indicate the selected tariff.
Instruction Manual 43
CVM-C10
4.5.3. USER
This profile is identified with the user symbol on the bottom of the screen (Figure 32).
This profile displays the screens selected in the programming menu (“4.9.12. Selecting the op-
eration profile”).
Note: If you have not selected the display of any screen, the device will restart and display the
Phase-Neutral Voltage screen by default.
The voltage and current harmonics are also displayed, up to the 31st order harmonic, for each
of the lines, L1, L2 and L3 (“4.6.- HARMONICS.”)
4.6.- HARMONICS
The device can display the voltage and current harmonics, up to the 31st order harmonic, for
each one of the lines, L1, L2 and L3.
The display of these can be deactivated using the programming menu (“4.9.18. Activating the
harmonics display screen.”).
Press the key on the last profile screen to show all operation profiles on the harmonics
display screens.
44 Instruction Manual
CVM-C10
4.7.- INPUTS
The CVM-C10 has two digital inputs (terminals 12 and 13 on Figure 1, Figure 2 and Figure 3)
that can be programmed to operate as a logic or tariff selection input.
If configured as a logic input, the device displays the status of that input.
See “4.9.27. Operating mode of digital input 1” and “4.9.28. Operating mode of digital input 2”
The selected tariff can be determined in accordance with the status of the inputs, as shown in
Table 14.
Table 14: Selecting the tariff in accordance with the input status.
IN1, Input 1 IN2, Input 2
Tariff
Logic input Tariff selection Logic input Tariff selection
x x T1
x 0 T1
x 1 T3
0 x T1
1 x T2
0 0 T1
0 1 T3
1 0 T2
1 1 T1
4.8.- OUTPUTS
Two alarm relays (terminals 3, 4 and 5, as shown in Figure 1, Figure 2 and Figure 3),
fully programmable, see “4.9.23. Programming alarm 1 (Relay 1)” and “4.9.24. Program-
ming alarm 2 (Relay 2)”
Instruction Manual 45
CVM-C10
4.9.- PROGRAMMING
When on reaching the last point on the programming menu (“4.9.30. Locking the pro-
gramming”) the key is pressed
At any point in the programming, by pressing the key or pressing for 3 sec-
onds.
If the device is RESET before validation or no key is pressed for 30 seconds, the configuration
will not be stored in the memory.
The home screen of the menu indicates whether the menu is locked or not:
UnLOC
When you enter the programming menu you can view and modify
the programming. Icon on the display indicates that the unit
is not locked.
LOC
When you enter the programming you can view the programming
but not modify it. Icon indicates the locking status.
The following screen will be displayed if the programming menu is locked, LOC:
46 Instruction Manual
CVM-C10
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
If the password is correct, the icon will change its status to not locked .
If you do not enter the password or it is incorrect, you can open the programming menu but it
cannot be modified.
The programming menu is unlocked for a short period of time and it will be locked again when
you exit the device's menu.
To permanently unlock the device, select the programming parameter “4.9.30. Locking the
programming”
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum
programming value.
Instruction Manual 47
CVM-C10
Note: The ratio is the relation between the primary and the secondary.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum
programming value.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the remaining values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
48 Instruction Manual
CVM-C10
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum
programming value.
Note: The ratio is the relation between the primary and the secondary.
Press key to browse the two possible options for the current
transformer secondary (1A or 5A).
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the remaining values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum
programming value.
Instruction Manual 49
CVM-C10
Press key to browse the two possible options for the current
transformer secondary (1A or 5A).
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
50 Instruction Manual
CVM-C10
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Instruction Manual 51
CVM-C10
The programmed value will be deleted if the entered value is higher than the maximum
programming value.
Note: Programming the value 0 disables the calculation of the maximum demand.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
52 Instruction Manual
CVM-C10
The following screen is displayed if you have selected the user profile:
Press key for 3 seconds to edit the selection. The prog icon
will be displayed on the bottom of the screen.
the display screens are those that were stored in previous programming
settings of the device. (In the case of new devices, these will be the same as those of
the analyzer profile)
, the display screens are selected.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press key for 3 seconds to edit the selection. The prog icon
will be displayed on the bottom of the screen.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
This programming step is repeated for each one of the 18 screens of the device.
Instruction Manual 53
CVM-C10
The time that the Backlight will stay lit (in seconds) is
programmed on this screen after the last keystroke on the unit .
Press key for 3 seconds to edit the backlight value. The prog
icon will be displayed on the bottom of the screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing
digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Note: The value 00 indicates that the backlight will stay permanently lit.
Press key to access the next programming step.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
54 Instruction Manual
CVM-C10
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
AUTO The device displays the kWh and MWh. When the energy value reaches 999999kWh,
the device automatically selects the MWh range.
SHORT The device only displays the KWh. When the energy value reaches 999999kWh, the
device resets the measurement to 0kWh.
To validate the modification of the range of energies, delete the energy values first.
To do so, press the validation key for 3 seconds; the energy value deletion screen will be
displayed. Select YES to delete the energy values; the device will go back to the energy range
selection screen.
Instruction Manual 55
CVM-C10
To complete the validation, press the key for 3 seconds; the prog icon will disappear from
the display.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing
digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
Press key to browse the different tariffs.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum
programming value.
56 Instruction Manual
CVM-C10
The emission ratio of the 3 tariffs of the device, T1, T2 and T3, is programmed on this screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing
digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum
programming value.
The cost per kWh of electricity of the three tariffs of the unit is
calculated on this screen.
Press key for 3 seconds to edit the cost ratio selection. The
prog icon will be displayed on the bottom of the screen.
To enter or modify the value, press the key repeatedly,
increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
Instruction Manual 57
CVM-C10
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum
programming value.
The cost per kWh of electricity of the three tariffs of the unit is
calculated on this screen.
Press key for 3 seconds to edit the cost ratio selection. The
prog icon will be displayed on the bottom of the screen.
To enter or modify the value, press the key repeatedly,
increasing the value of the flashing digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum
programming value.
58 Instruction Manual
CVM-C10
To enter or modify the value, press the key repeatedly, increasing the value of the flashing
digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
When you enter the code of a variable on the display, the symbols for that variable will be
activated.
Set the value to 00 if you do not wish to program a variable.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press key to access the next programming step.
Instruction Manual 59
CVM-C10
In addition, there are some parameters (Table 16) that refer to the three phases at the same
time (OR function). If you have selected one of these variables, the alarm will be activated when
any of the three phases meets the programmed conditions.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
In the case of some parameters (Table 17), you can modify the position of the decimal point.
To do so, press key after modifying the last digit and the decimal point will start flashing.
Press key repeatedly to modify the position of the decimal point.
When the decimal point is in the desired position, press the key to end the programming,
pressing now the key we can set a positive or negative value.
Note: Pay special attention when programming the Generation Power (displayed with negative
values).
60 Instruction Manual
CVM-C10
Example: If you wish to enter a generation power alarm with limits between 2 kW and 1 kW,
program the following as the maximum value : - 1 kW and the following as the minimum
value : - 2 kW.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press key to access the next programming step
Note: Pay special attention when programming the Generation Power (displayed with negative
values).
Example: If you wish to enter a generation power alarm with limits between 2 kW and 1 kW,
program the following as the maximum value : - 1 kW and the following as the minimum
value : - 2 kW.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press key to access the next programming step.
Instruction Manual 61
CVM-C10
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press key to access the next programming step.
62 Instruction Manual
CVM-C10
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Note: If the device is reset, the status of alarms is deleted and all alarms will return to the
programmed standby status, provided that the condition that triggered them has been resolved.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Instruction Manual 63
CVM-C10
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Note: Configuration parameters not available for the CVM-C10-FLEX, CVM-C10-ITF-IN and
CVM-C10-MC-IN models.
Press key for 3 seconds to edit the code selection. The prog icon will be displayed on the
bottom of the screen.
To enter or modify the value, press the key repeatedly, increasing the value of the flashing
digit.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
When you enter the code of a variable on the display, the symbols for that variable will be
activated.
Set the value to 00 if you do not wish to program a variable.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press key to access the next programming step
64 Instruction Manual
CVM-C10
If you have selected a parameter from Table 12 the subsequent programming steps are the
same as for alarm relay 1, see (“4.9.23. Programming alarm 1 (Relay 1)”)
If you have selected a parameter from Table 18, the subsequent programming steps are:
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
The programmed value will be deleted if the entered value is higher than the maximum
programming value.
Instruction Manual 65
CVM-C10
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Note: Configuration parameters not available for the CVM-C10-FLEX, CVM-C10-ITF-IN and
CVM-C10-MC-IN models.
66 Instruction Manual
CVM-C10
Logic input
Tariff selection.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Logic input
Tariff selection.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press key to access the next programming step.
Note: The device will restart after exiting the setup menu if the RS-485 communications
parameters have been modified.
Instruction Manual 67
CVM-C10
Transmission speed
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Peripheral number
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Parity
no parity
68 Instruction Manual
CVM-C10
even parity.
odd parity.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press key for 3 seconds to edit the bit number selection. The
prog icon will be displayed on the bottom of the screen.
Press key to browse the two options: 7 or 8 bits.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Instruction Manual 69
CVM-C10
Transmission speed
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Device ID
Press the key for 3 seconds to edit the value. The prog icon
will be displayed on the bottom of the screen.
To enter or modify the value, press the key repeatedly,
increasing the value of the flashing digit.
When the desired value is shown on the screen, press the key to go to the next digit and
modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press key to access the next programming step.
70 Instruction Manual
CVM-C10
MAC
Press the key for 3 seconds to edit the value. The prog icon
will be displayed on the bottom of the screen.
To enter or modify the value, press the key repeatedly,
increasing the value of the flashing digit.
When the desired value is shown on the screen, press the key to go to the next digit and
modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press key to access the next programming step.
When you enter the programming menu you can view and modify the programming. Icon
on the display indicates the permanently locked status.
When you enter the programming you can view the programming but not modify it. Icon
indicates the locking status. Enter the password to modify the programming values.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press the key to enter the password for locking and unlocking the programming:
Instruction Manual 71
CVM-C10
On this screen you enter the password for locking and unlocking
the programming.
When the desired value is shown on the screen, move onto the next digit by pressing the key
to modify the other values.
If you press the key after changing the last digit, it will jump back to the first digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
This value may only be modified through communications. See “4.10.3.8.17. Password
configuration.”
Press the key to exit the setup menu.
Note: The device will restart after exiting the setup menu if the RS-485 communications
parameters have been modified.
72 Instruction Manual
CVM-C10
4.10.- COMMUNICATIONS
The protocol and configuration parameters are selected in the setup menu. (“4.9.29. RS-485
communications: Protocol”)
4.10.1. CONNECTIONS
The RS -485 cable must be wired with twisted pair cable with mesh shield (minimum 3 wires),
with a maximum distance between the CVM-C10 and the master device of 1200 metres.
A maximum of 32 CVM-C10 devices can be connected to this bus.
PC
RS-232
USB
Ethernet
Profibus
...
RS-485
RS-485
A (+)
B (-)
S
OUTPUTS OUTPUTS
S0- S0+ S0+ S0- S0+ S0+
RS485 INPUTS RS485 INPUTS
POWER SUPPLY A(+) B(-) I1 I2 POWER SUPPLY A(+) B(-) I1 I2
Rc R2 R1 Tc T2 T1 Rc R2 R1 Tc T2 T1
GND GND
L1 L2 L3 L1 L2 L3
VL1 VL2 VL3 N VL1 VL2 VL3 N S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2
Instruction Manual 73
CVM-C10
4.10.2. PROTOCOL
In the Modbus protocol, the CVM-C10 device uses the RTU (Remote Terminal Unit) mode.
Initial No. of
Address Function CRC
Register Registers
0A 04 0000 0002 70B0
Response:
Note: Every Modbus frame has a maximum limit of 20 variables (40 logs).
Initial
Address Function Value CRC
Register
0A 05 0834 FF00 CEEF
74 Instruction Manual
CVM-C10
Instruction Manual 75
CVM-C10
76 Instruction Manual
CVM-C10
Instruction Manual 77
CVM-C10
78 Instruction Manual
CVM-C10
The device’s Modbus function does not check whether the variables recorded are within the
correct margins, they are only checked when they are read from the EEPROM. So if any
parameter is recorded with an incorrect value the device will be configured with its default
value.
The Modbus configuration will not take effect until the device is reset.
Instruction Manual 79
CVM-C10
4.10.3.8.4.Measurement convention
Table 31: Modbus memory map: Measurement convention.
Measurement convention
Configuration variable Address Valid data margin Default value
0: Circutor
Measurement convention 2B86 1: IEC 0
2: IEEE
80 Instruction Manual
CVM-C10
Instruction Manual 81
CVM-C10
82 Instruction Manual
CVM-C10
Note: Configuration parameters not available for the CVM-C10-FLEX , CVM-C10-ITF-IN and
CVM-C10-MC-IN models.
Table 40: Modbus memory map: Programming alarms 3 and 4.
Programming alarms 3 and 4
Address Default
Configuration variable Valid data margin
Relay 1 Relay 2 value
Kilowatts per impulse 2B0C-2B0D 2B16-2B17 0.001 - 999.999 kWh 0
Variable code 2B10 2B1A Table 18 0
Pulse width 2B11 2B1B 10 - 500 ms 100 ms
We can also read the status of the digital inputs when they are in logic mode:
Table 42: Modbus memory map: Status of the digital inputs (Logic state mode)
Status of digital inputs
Variable Address Default value
Status of digital inputs 4E20 -
Instruction Manual 83
CVM-C10
4.10.3.8.16. Communications
Table 46: Modbus memory map: Communications
Communications
Default
Configuration variable Address Valid data margin
value
0 : Modbus
Protocol 2742 0
1: Bacnet
Modbus and BACnet: Peripheral number 2743 0 - 255 1
Modbus : Transmission speed 2744 0: 9600 - 1:19200 0
0: No parity
Modbus : Parity 2745 1: Odd parity 0
2: Even parity
0 : 8 bits
Modbus : Data bits 2746 0
1: 7 bits
0 : 1 stop bit
Modbus : Stop bits 2747 0
1: 2 stop bits
BACnet: Device ID 2EE0- 2EE1 0- 999999 -
BAcnet: MAC 2EE2 0- 255 2
These variables allow you to lock or unlock access to the programming menu, and also allow
you to change the password code. The password code may only be changed through this com-
mand.
The device does not need you to enter the old password in order for it to record the new one; it
records the new one directly without any verification.
Table 47: Modbus memory map: Password configuration
Password
Configuration variable(12) Address Valid data margin Default value
Password value (13)
2B70 0 - 9999 1234
0: Unlock
Lock-Unlock 2B71 0
1: Lock
(12)
You must program all the variables at the same time.
(13)
The password value is read and written in hexadecimal.
84 Instruction Manual
CVM-C10
BACnet is a communications protocol for Building Automation and Control NETworks. This
protocol replaces the proprietary communications of each device, making it a set of common
communication rules that enables the complete integration of the building automation and
control devices of different manufacturers.
The device features BACNet MS/TP communications, following the specifications of ANSI/
ASHRAE 135 (ISO 16484-5).
Using a RS485 connection, the device can connect to a BACnet and include all of the objects
and services defined in the attached PICS map (Protocol Implementation Conformance
Statement). ( “4.10.5. PICS MAP”)
The default speed is 9600 bps and the MAC is 2 (node number), and can be changed on the
configuration screen or by entering the BaudRate and MAC_Address variables. The identifier
(Device_ID) can be changed on the configuration screen using the writing property over the
variable or through the Device_ID variable.
Instruction Manual 85
CVM-C10
PICS
Vendor Name: CIRCUTOR
Product Name: CVM-C10
Product Model Number: 0116
Application Software Version: 1.0
Firmware Revision: 0.7.1
BACnet Protocol Revision: 10
Product Description:
Electrical energy meter
Which of the following device binding methods does the product support? (check one or more)
x Recive Who-Is, send I-Am (BIBB DM-DDB-B)
x Recive Who-Has, send I-Have (BIBB DM-DOB-B)
Standard Object Types Supported:
Properly Identifier
Object_Name max 32 characters
86 Instruction Manual
CVM-C10
Instruction Manual 87
CVM-C10
88 Instruction Manual
CVM-C10
DC Power supply
Rated voltage 105 ... 272 V ± 10% 23 ... 109 V ± 10% (14)
Consumption 2 ... 6 W 3.5 ... 3 W
Installation category CAT III 300 V
(14)
Only available for references M5591100F0000, M5592100F0000, M5592100F0V00, M5594200F00000 and
M5596100F0000.
Voltage measurement circuit
Rated voltage (Un) 300 V Ph-N, 520 V Ph-Ph
Voltage measurement margin 5 ... 120% Un
Frequency measurement margin 45 ... 65Hz
Input impedance 440 kΩ
Min. voltage measurement (Vstart) 15 V
Installation category CAT III 300 V
Instruction Manual 89
CVM-C10
90 Instruction Manual
CVM-C10
User interface
Display LCD Custom COG
Keyboard Capacitive, 3 keys
LED 3 LED
Environmental features
Operating temperature -5ºC... +45ºC
Storage temperature -10ºC ... +50ºC
Relative humidity (non-condensing) 5 ... 95%
Maximum altitude 2000 m
IP21
Protection degree (20)
Front panel: IP51 (IP64 with accessory)
(20)
This pollution degree hasn’t been tested by UL.
Mechanical features
Dimensions ( Figure 35) 96.7x96.7x62.5 mm
Weight 330 gr
Surround Self-extinguishing V0 plastic
Attachment Panel
Standards
Safety of electronic measuring units UNE EN 61010: 2010
Electromagnetic compatibility (CEM). Part 6-3: Generic standards.
Emission standard for residential, commercial and light industry en- UNE EN 61000-6-3:2007
vironments.
Electromagnetic compatibility (CEM). Part 6-1: Generic standards. Im-
UNE EN 61000-6-1:2007
munity in residential, commercial and light industry environments
Coordination of the insulation of units installed in low voltage sys-
IEC 664:2007
tems (networks).
VDE 0110
Test for flammability of plastic materials for parts in devices and
UL 94
appliances
Electromagnetic compatibility (EMC). Generic standards. Immunity
BS EN 61000-6-2
for industrial environments
Electromagnetic compatibility (EMC). Generic standards. Emission
BS EN 61000-6-4
standard for industrial environments
Safety requirements for electrical equipment for measurement, con-
UL/CSA 61010-1 3rd edition
trol, and laboratory use - Part 1: General requirements
Instruction Manual 91
CVM-C10
60.9 96.7
10.9 50
2.5
91.8
96.7
Figure 35: Dimensions of the CVM-C10.
92 Instruction Manual
CVM-C10
8.- CE CERTIFICATE
94 Instruction Manual
CVM-C10
Instruction Manual 95
CVM-C10
96 Instruction Manual
CVM-C10
Instruction Manual 97
CIRCUTOR, SA
Vial Sant Jordi, s/n
08232 -Viladecavalls (Barcelona)
Tel.: (+34) 93 745 29 00 - Fax: (+34) 93 745 29 14
www.circutor.com central@circutor.com
8.4 GFCI Receptacle, SPEC 2.9.2
What to do when
your GFCI trips
GFCIs are important safety tools that help protect people from shock or
electrocution. Even though the latest models have their own self-test feature,
it’s still important to test them monthly and perform a visual inspection to be sure
they’re in good condition.
Your GFCI is designed to trip when it detects a ground fault, which occurs when current
flows along an unintended path such as through water or a person.
- Test your GFCIs monthly by pressing the ‘TEST’ and ‘RESET’ buttons on the face
of the device.
- P
erform a simple visual inspection to be sure they’re in good condition. If the plug
connection is loose or the outlet is discolored or warm, replace the GFCI immediately.
- Look at appliances or cords that were plugged into the GFCI at the time of the trip,
as well as any devices plugged into outlets downstream of the GFCI. Check for
damage like frayed wires or faulty devices.
If there’s an obvious cause for the trip, you should unplug the device as it may be faulty
and causing the GFCI to trip. If the GFCI continues to trip, or if the reason for the trip is not
obvious, it’s time to contact an electrician.
GFCI Trips
GFCI
Outlet
TS-111020-dp
1. What is a GFCI? 2. The GFCI's features
! CAUTION
A GFCI receptacle is different from FRONT VIEW BACK VIEW Screw (terminal) colors:
conventional receptacles. In the event of a LINE
• To prevent severe shock or electrocution Receptacle Green = grounding terminal
ground fault, a GFCI will trip and quickly stop Hot terminal (Brass or Black):
always turn the power OFF at the service the flow of electricity to prevent serious injury. Silver = WHITE terminals
Connection for the LINE
panel before working with wiring. Outlet cable's black wire Brass or Black = HOT terminals
Definition of a ground fault:
• Use this GFCI with copper or copper- LINE
Instead of following its normal safe path, A yellow sticker
clad wire. Do not use it
Installing and with aluminum wire.
electricity passes through a person's body to
reach the ground. For example, a defective
RESET
button:
covers the LOAD
terminals. Do not
White terminal (Silver):
Connection for the LINE
FOLLOW INSTRUCTIONS
LIGNE
SUIVEZ INSTRUCTIONS
Receptacle
A GFCI receptacle does NOT protect against
TEST MENSUEL
TEST MONTHLY
RESET
because if the GFCI trips it will shut TEST LOAD
WHITE WIRE
RESET
FIL BLANC
HOT WIRE
FIL ACTIF
circuit overloads, short circuits, or shocks. For
down the equipment. example, you can still be shocked if you touch button: TEST
TEST LOAD White terminal (Silver):
bare wires while standing on a non-conducting See step 8 Hot terminal Connection for the LOAD
• For installation in damp or wet locations, cable's white wire
surface, such as a wood floor. (Brass or Black):
the GFCI receptacle must be Listed and Outlet LOAD
marked as Weather Resistant (WR) NOTE: Connection for CHARGE
GFCI's contain a lockout feature that will prevent the LOAD cable's
Please read this leaflet • For installation in wet locations, protect RESET if: Self-Ground black wire
completely before getting started. the GFCI receptacle with a cover plate or • There is no power being supplied to
Clip
outlet box hood suitable for wet locations the GFCI.
that will keep both the receptacle and Back wire holes Grounding Terminal (Green):
• The GFCI is miswired due to reversal of
plug face dry. the LINE and LOAD connections.
Mounting Connection for bare
Green/Red Status
Bracket copper or green wire
• The GFCI cannot pass its internal test, Indicator Light
• Must be installed in accordance with
indicating that it may not be able to provide
national and local electric codes.
protection in the event of a ground fault.
PK-93792-10-00-2B AR0088
3. Should you install it? 4. LINE vs. LOAD 5. Turn the power OFF 6. Identify cables/wires Procedure: box with two (2) cables (4-6 wires):
Placement in circuit:
(a) Detach one cable's white wire and hot The GFCI's place in the circuit determines if
Installing a GFCI receptacle can be more A cable consists of 2 or 3 wires. Plug an electrical device, such as a lamp or Important: it protects other receptacles in the circuit.
wires from the receptacle and cap each
complicated than installing a conventional radio, into the receptacle on which you are DO NOT install the GFCI receptacle in an one separately with a wire connector.
receptacle. Cable Wires working. Turn the lamp or radio ON. Then, go electrical box containing (a) more than four (4) Sample circuit:
Make sure that they are from the same
to the service panel. Find the breaker or fuse wires (not including the grounding wires) or cable.
Make sure that you: that protects that receptacle. Place the breaker (b) cables with more than two (2) wires (not
in the OFF position or completely remove the including the grounding wire). Contact a A B C
fuse. The lamp or radio must turn OFF. (b) Re-install the receptacle in the electrical LINE LINE LINE
•
Understand basic wiring principles and qualified electrician if either (a) or (b) are true.
box, attach faceplate, then turn the power
techniques ON at the service panel. Service
LINE cable: If you are replacing an old receptacle, pull it out Panel
• Can interpret wiring diagrams Delivers power from the service panel (breaker of the electrical box without disconnecting the
(c) Determine if power is flowing to the
panel or fuse box) to the GFCI. If there is only wires.
receptacle. If so, the capped wires are the LOAD LOAD
• Have circuit wiring experience one cable entering the electrical box, it is the LOAD wires. If not, the capped wires are
LINE cable. This cable should be connected to • If you see one cable (2-3 wires), it is the the LINE wires.
the GFCI's LINE terminals only. LINE cable. The receptacle is probably in
• re prepared to take a few minutes to test
A position C (see diagram to the right). Placing the GFCI in position A will also
your work, making sure that you have wired (d) Turn the power OFF at the service panel, provide protection to "load side"
LOAD cable: Remove the receptacle and go to step 7A.
the GFCI receptacle correctly label the LINE and LOAD wires, then receptacles B and C. On the other hand,
Delivers power from the GFCI to another remove the receptacle.
Next, plug in and turn ON the lamp or radio at • If you see two cables (4-6 wires), the placing the GFCI in position C will not
receptacle in the circuit. This cable should be
the receptacle's other outlet to make sure the receptacle is probably in position A or B provide protection to receptacles A or B.
connected to the GFCI's LOAD terminals only.
(see diagram to the right). Follow steps a-e (e) Go to step 7B. Remember that receptacles A, B, and C
The LOAD terminals are under the yellow power is OFF at both outlets. If the power is not
OFF, stop work and call an electrician to of the procedure to the right. can be in different rooms.
sticker. Do NOT remove the sticker at this time.
complete the installation.
Procedure:
7. Connect the wires (choose A or B)... only after reading other side completely (a) This GFCI is shipped from the factory in the tripped condition and cannot be reset until it is wired
A: One Cable (2 or 3 wires) entering the box OR B: Two cables (4 or 6 wires) entering the box correctly and power is supplied to the device. Plug a lamp or radio into the GFCI (and leave it plugged RESET
in). Turn the power ON at the service panel. Ensure that the GFCI is still in the tripped condition
RESET
TEST
by pressing the TEST button. If the lamp or radio is OFF, and the GFCI will not reset, go to the TEST
Grounding LINE cable brings LINE cable brings power to the GFCI Troubleshooting section as the Line and Load connections are reversed.
connection to power to the GFCI Grounding connection (b) Press the RESET button fully and release. If the Status Indicator Light turns Green and the lamp or
box (if box has a to box (if box has a White radio is ON, the GFCI has been installed correctly. If the Status Indicator Light turns or continuously
grounding terminal) White grounding terminal) blinks Red, or the GFCI cannot be reset, go to the Self-Test Operation section.
Yellow
sticker (c) If you installed your GFCI using step 7B, plug a lamp or radio into surrounding receptacles to see which
remains one(s), in addition to the GFCI, lose power when you press the GFCI TEST button. Place a "GFCI RESET
RESET
Wire in place PROTECTED OUTLET" sticker on every receptacle that lost power, then press the RESET button to T EST
Wire
TEST
Connector reset the GFCI. DO NOT plug life saving devices into any of the receptacles that lost power.
to cover Connector Black LINE
the LOAD
LIGNE (d) Press the TEST button (then RESET button) every month to assure proper operation. If the Status
Black
WHITE WIRE
Indicator Light does not turn Green when the RESET button is depressed and then released, or the
FIL BLANC
HOT WIRE
FIL ACTIF
LINE
LIGNE terminals
GFCI cannot be reset, it must be replaced.
WHITE WIRE
FIL BLANC
Electrical Black
HOT WIRE
FIL ACTIF
LOAD
CHARGE
Electrical Box TROUBLESHOOTING
White
Box LOAD
CHARGE
Turn the power OFF and check the wire connections against the appropriate wiring diagram in step 7A or 7B. Make sure that RESET
RESET
there are no loose wires or loose connections. If the Status Indicator Light is not ON and the device is unable to reset this TEST
TEST
LOAD cable feeds could be a result of no power available. Start the test from the beginning of step 8 if you rewired any connections to the GFCI.
power to other
receptacle(s) SELF-TEST OPERATION
• A Self-Test GFCI receptacle has all the features of a conventional GFCI receptacle. In addition, this receptacle tests itself periodically to confirm
About Wire Connections: the GFCI electronics are functional. The Status Indicator Light will be solid green when the GFCI is powered from Line side and working correctly.
About Wire Connections: Back Wire: • Self-Test Indications: If the Status Indicator Light is solid or flashing RED a problem may exist. Press the TEST button to trip the GFCI. If unable
Side Wire: Back Wire: Side Wire: 5/8" (1.6 cm) to Reset, replace the GFCI. NOTE: The status indicator may flash Red at power "ON" and Reset.
3/4" (1.9 cm) Wire
3/4" (1.9 cm) 5/8" (1.6 cm) Wire
Wire Wire Self Test Cat. No. Description LIMITED 2 YEAR WARRANTY AND EXCLUSIONS
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product
GFNT1 15A-125VAC, 60Hz Non-Tamper Resistant GFCI at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper
use for two years from the purchase date. Leviton’s only obligation is to correct such defects by repair
For Back wire -
LINE
LIGNE
For Side wire - GFNT2 20A-125VAC, 60Hz Non-Tamper Resistant GFCI or replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty
For Side wire - For Back wire - Insert bare wire fully and
WHITE WIRE
FIL BLANC
excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty
HOT WIRE
FIL ACTIF
LINE
Loop clockwise 2/3 of the is void if this product is installed improperly or in an improper environment, overloaded, misused, opened,
Loop clockwise 2/3 of the Insert bare wire fully LIGNE
tighten terminal clamp on GFTR1 15A-125VAC, 60Hz Tamper Resistant GFCI
way around screw abused, or altered in any manner, or is not used under normal operating conditions or not in accordance
WHITE WIRE
conductor ONLY
HOT WIRE
FIL ACTIF
LOAD GFTR2 20A-125VAC, 60Hz Tamper Resistant GFCI with any labels or instructions. There are no other or implied warranties of any kind, including
CHARGE merchantability and fitness for a particular purpose, but if any implied warranty is required by the
clamp on conductor GFWR1 15A-125VAC, 60Hz Weather Resistant GFCI applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for
ONLY LOAD
CHARGE
a particular purpose, is limited to two years. Leviton is not liable for incidental, indirect, special, or
GFWR2 20A-125VAC, 60Hz Weather Resistant GFCI consequential damages, including without limitation, damage to, or loss of use of, any equipment,
lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided
GFWT1 15A-125VAC, 60Hz Weather/Tamper Resistant GFCI herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
GFWT2 20A-125VAC, 60Hz Weather/Tamper Resistant GFCI For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only)
1 800 405-5320 (Canada Only) www.leviton.com
Connect the LINE cable wires to the LINE terminals: GFRBF 20A-125VAC, 60Hz Blankface GFCI
Connect the LINE cable wires to the LINE terminals: • The white wire connects to the WHITE terminal (Silver) SmartlockPro is a Trademark of Leviton Manufacturing Co., Inc. registered in the United
All devices rated 20A feed-through States, Canada, Mexico and China.
• The white wire connects to the WHITE terminal (Silver) • The black wire connects to the HOT terminal (Brass or Black)
• The black wire connects to the HOT terminal (Brass or Black) Connect the LOAD cable wires to the LOAD terminals:
• Remove the YELLOW sticker to reveal the LOAD terminals FCC STATEMENT
Connect the grounding wire (only if there is a grounding wire): This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
• For a box with no grounding terminal (diagram not shown): Connect • The white wire connects to the WHITE terminal (Silver) designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio
the LINE cable's bare copper (or GREEN) wire directly to the • The black wire connects to the HOT terminal (Brass or Black) frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television
grounding terminal on the GFCI receptacle. Connect the grounding wires (only if there is a grounding wire): reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the
• For a box with a grounding terminal (diagram shown above): Connect • Connect a 6-inch bare copper (or GREEN) 12 or 14 AWG wire to the grounding terminal on the following measures:
• Reorient or relocate the receiving antenna.
a 6-inch bare copper (or GREEN) 12 or 14 AWG wire to the grounding GFCI. If the box has a grounding terminal, also connect a similar wire to the grounding terminal • Increase the separation between the equipment and receiver.
terminal on the GFCI. Also connect a similar wire to the grounding on the box. Connect the ends of these wires to the LINE or LOAD cable's bare copper (or • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
GREEN) wire using a wire connector. If these wires are already in place, check the connections. • Consult the dealer or an experienced radio/TV technician for help.
terminal on the box. Connect the ends of these wires to the LINE
cable's bare copper (or GREEN) wire using a wire connector. Complete the installation: IC STATEMENT
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not
If these wires are already in place, check the connections. • Fold the wires into the box, keeping the grounding wire away from the WHITE and HOT cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
Complete the installation: terminals. Screw the receptacle to the box and attach the faceplate.
• Fold the wires into the box, keeping the grounding wire away from the • Go to step 8. This product is covered by U.S. Patent Nos. 6,040,967; 6,246,558**; 6,282,070; 6,381,112; 6,437,953; 6,646,838; 6,657,834; 6,788,173; 6,864,766**; 6,944,001; 7,336,458; 7,355,117*;
WHITE and HOT terminals. Screw the receptacle to the box and attach 7,400,479; 7,463,124**; 7,697,252; 7,737,809**; 7,764,151**; 7,820,909*; 7,868,719†; 7,907,371; 8,004,804; 8,054,595; 8,130,480; 8,242,362*; 8,587,914**; 8,599,522; 8,944,859; 9,053,886 and
the faceplate. 8. Test your work corresponding foreign patents (*applies only to Cat. Nos. GFTR1, GFTR2, GFWT1 & GFWT2, †applies only to Cat. Nos. GFTR2 & GFWT2, **does not apply to Cat. No. GFRBF).
• Go to step 8. Why perform this test? FOR CANADA ONLY
• If you miswired the GFCI it may not prevent personal injury or death due to a ground fault
(electrical shock). For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada Ltd to the
attention of the Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
• If you mistakenly connect the LINE wires to the LOAD terminals, the GFCI will not reset and will
not provide power to either the GFCI receptacle face or any receptacles fed from the GFCI. © 2018 Leviton Mfg. Co., Inc. PK-93792-10-00-2B AR0088
GFNT2-RI
20 Amp, 125 Volt Receptacle/Outlet, 20 Amp Feed-Through, Self-test SmartlockPro
Slim GFCI, black test button and red reset button, Residential/Commercial applications,
back and side wired, heavy duty, wallplate/faceplate and self grounding clip included -
Ivory
Technical Information
Product Features Grounding Screw : Plated Steel
Amperage : 20 A Line Contacts : Brass Triple-Wipe .031
Thick
At Rated Voltage : 1 HP
Notes : Wallplate Sold Separately
Color : Ivory Brand : SmartlockPro
Product ID : Ratings are permanently
Color : Ivory marked on device
Feature : Self-Test Terminal Accom. : 14-10 AWG
UPC Code : 078477714638 Fed Spec WC-596 : Yes Terminal ID : Brass-Hot, Green-Ground,
Country Of Origin : China Grade : Residential/Commercial Silver-Neutral
Specification Grade Terminal Screws : Plated Steel
Grounding : Self-Grounding Yoke : Zinc-Plated Steel
NEMA : 5-20R NEMA : 5-20R
Mechanical Specifications
Pole : 2
Amperage : 20 A
Standards and Certifications :
UL/CSA, NEMA WD6 Body Material : Polycarbonate
Strap Material : Galvanized Steel Brand : SmartlockPro
Available Colors :
Tamper Resistant : No Color : Ivory
Termination : Back & Side Face Material : Thermoplastic
Trip Level : Class A, 5mA plus or minus Feature : Self-Test
White 1mA Fed Spec WC-596 : Yes
Type : Standard Duplex Grade : Residential/Commercial
Voltage : 125 VAC Specification Grade
Wallplate : Included Grounding : Self-Grounding
Warranty : 2-Year Limited NEMA : 5-20R
Wire : 3 Notes : Wallplate Sold Separately
Pole : 2
AC Horsepower Ratings
Product ID : Ratings are permanently
At Rated Voltage : 1 HP marked on device
Dielectric Voltage : Withstands Standards and Certifications :
1250VAC per UL 943 and CSA-C22.2 UL/CSA, NEMA WD6
No. 144.1-06
Strap Material : Galvanized Steel
Short Circuit Current Rating : 10KA
Tamper Resistant : No
Temperature Rise : Max 30C after 100
cycles OL at 150 percent rated current Terminal Accom. : 14-10 AWG
Terminal ID : Brass-Hot, Green-Ground,
Electrical Specifications Silver-Neutral
Dielectric Voltage : Withstands Termination : Back & Side
1250VAC per UL 943 and CSA-C22.2
No. 144.1-06 Torque Range : 14 – 18 in.-lbs
Operating Temperature : -35C to +66C Trip Level : Class A, 5mA plus or minus
1mA
Short Circuit Current Rating : 10KA
Type : Standard Duplex
Temperature Rise : Max 30C after 100
cycles OL at 150 percent rated current Voltage : 125 VAC
Warranty : 2-Year Limited
Environmental Specifications
Wire : 3
Body Material : Polycarbonate
Clamps : Brass Standards and Certifications
Face Material : Thermoplastic ANSI : C-73
Grounding Screw : Plated Steel CSA C22.2 No. 42 : Yes
Line Contacts : Brass Triple-Wipe .031 CSA-C22.2 No. 144.1-06 : File LR-
Thick 57811
Notes : Wallplate Sold Separately Fed Spec WC-596 : Yes
Operating Temperature : -35C to +66C MIL-SPEC : A-A-55459-SB
Terminal Screws : Plated Steel NOM : Yes
Yoke : Zinc-Plated Steel UL 943 : File E48380
UL498 : Yes
Material Specifications
Body Material : Polycarbonate
Clamps : Brass
Face Material : Thermoplastic
- Provides continuous ground fault protection – detects and trips on actual ground
- Auto adapts and shifts to more frequent testing if potential problem is detected
- Status Indicator Light provides simple, intuitive feedback on power and protection
- Patented Lockout Action prevents reset if GFCI is damaged and cannot respond
to a ground fault
- Reduced depth makes it easier to install in any electrical box, even shallow ones
- Terminals allow for easy wiring options – back and side wire capable
- External back wire clamps provide visual indication of proper wire seating
and over-voltages
- Compatible with all Decora devices and wallplates; available in select Decora
colors
Leviton's line of Heavy-Duty Industrial Grade Receptacles are available with a number
of wiring options and features. These heavy-duty receptacles are engineered for fine
appearance and top performance in demanding commercial and institutional
applications using a durable, thermoplastic face and impact-resistant construction.
Technical Information
AC Horsepower Ratings Strap Material : Zinc-Plated Steel
At Rated Voltage : 1 HP Terminal Screws : Brass 10-32
Technical Information
AC Horsepower Ratings Toggle : Polycarbonate
HP Rating : 1HP-120V 2HP-240V Mechanical Specifications
Electrical Specifications Product ID : Ratings are permanently
marked on device
Amperage : 20 A
Terminal Accom. : 14-#10 AWG back
Dielectric Voltage : Withstands 1500V
Color : Ivory wired; #14-#12 AWG side wired
for 1 minute
Terminal ID : Brass-Hot Black-Hot
Endurance : 50,000 cycles minimum White-Neutral Green-Gnd
Grounding : Self-Grounding
UPC Code : 078477239896 Termination : Back or Side Wire
Overload UL20 Test : 100 cycles of OL Torque Range : 12-14 inch pounds
Country Of Origin : United States at 4.8 times rated current
Temperature Rise : Maximum 30 Product Features
degress C rise Color : Ivory
Available Colors : Voltage : 120/277 VAC Device Type : Toggle Switch
Environmental Specifications Function : Single-Pole
Flammability : Rated V-2 per UL 94 Grade : Extra Heavy-Duty Industrial
Specification Grade
Brown Ebony Gray Operating Temperature : -40°C to 65°C
Standards and Certifications
Material Specifications
ANSI : C-73
Base Material : Thermoplastic
CSA C22.2 No. 111 : File #152105
Color : Ivory
Light Almond Red White NEMA : WD-1 & WD-6
Contact Material : Silver Alloy
NOM : 057
Cover Material : Thermoplastic
RoHS : Compliant
Ground Clips : Brass
UL Fed Spec WS896E : File #E7458
Grounding Screw : Brass 8-32
UL Standard : UL 20
Strap Material : .048” Thick Galvanized
Steel Warranty : 10-Year Limited
Terminal Screws : Brass 8-32
Leviton Manufacturing Co., Inc.
201 North Service Road, Melville, NY 11747
Telephone: +1-800-323-8920 · FAX: +1-800-832-9538 · Tech Line (8:30AM-7:30PM E.S.T. Monday-Friday):
+1-800-824-3005
1. COUPER LE COURANT.
OPTION B
2. Défoncer le joint d'étanchéité selon le modèle approprié de prise. Vis
3. Préparer la prise pour l'installation du couvercle. Prise avec disjoncteur de fuite de terre –
jeter les plaques d'adaptateur. Prise ronde jusqu'à 40 mm (1-9/16 po)- retirer les sections
défonçables de l'arrière du couvercle. Retirer le cercle intérieur de l'adaptateur rond pour OPTION A
interrupteur. Trou de serrure
4. Monter la plaque sur la boîte. Note : Placer la plaque avec les charnières au sommet, en Ensemble
prise/boîte
veillant à ce que la porte soit fixée à la plaque avant l'installation. (non fourni)
Option A : Fixation de la plaque à l'aide des vis de la prise.
Fixer la prise à la boîte en insérant (sans les serrer) les vis de la prise dans la boîte. Trou rond PLAQUE
Défoncer deux trous de vis dans le joint et poser le joint sur les têtes des vis et contre la *Voir NOTE sur le D'ADAPTATEUR
face de boîte. Visser les vis jusqu'à ce que les têtes dépassent de la surface du joint de disjoncteur de fuite
à la terre
9,5 mm (3/8 po). Pousser les broches de l'adaptateur dans le joint et la prise. Placer les PLAQUE
TROUS DE SERRURE du couvercle sur les vis et mettre à l'équerre le couvercle sur la
boîte (voir illustration). Serrer les vis pour fixer la plaque.
Utiliser une pince à
Option B : Fixation de la plaque à l'aide des vis de montage (fournies) becs pointus pour les Adaptateur
sections défonçables Pousser les
duplex broches dans
Fixer fixer la prise à la boîte. Défoncer le joint avec les quatre vis. Placer le joint sur la
prise et contre la face de la boîte. Pousser les broches de l'adaptateur dans le joint et le joint.
la prise. Bien fixer la plaque sur la boîte à l'aide des quatre vis.
5. Poser du calfeutrant ou du scellant autour de la plaque si elle est installée sur une surface
irrégulière comme un parement en brique ou en bois.
*NOTE sur le disjoncteur de fuite à la terre :
6. REMETTRE LE COURANT! autre installation de disjoncteur de fuite à la terre
(sans image). Vérifier que le disjoncteur de fuite à Prise simple ou
la terre est bien fixé à la boîte. Retirer le centre du adaptateur d'interrupteur
© 2008 Thomas & Betts Memphis, TN. joint et le poser sur le disjoncteur de fuite à la TA04208 A
Tous droits réservés. www.tnb.com terre. Insérer les (2) vis (fournies) par les trous Page 2 of 4
RONDS du couvercle dans les trous filetés du
disjoncteur de fuite à la terre. Serrer les vis.
Voir étape 4A.
CKMUV ADVERTENCIA El paquete incluye:
Conjunto de la cubierta,
Español
¡RIESGO ELÉCTRICO! empaquetadura, 2 adaptadores
¡DESCONECTE LA ELECTRICIDAD! y 4 tornillos
Los tornillos del tomacorriente
Cubierta Code Keeper ® para lugares húmedos deben extenderse 3/8” desde
la cara de la empaquetadura
Instrucciones de instalación para montar la cubierta
¡Sólo para montaje vertical! PUERTA EMPAQUETADURA
1. DESCONECTE LA ELECTRICIDAD.
OPCIÓN B
2. Retire el modelo de tomacorriente apropiado de la empaquetadura. Tornillos
5. Use masilla o sellante alrededor de la placa cuando la instale en una superficie irregular como *NOTA sobre GFCI: Instalación con interruptor de
revestimiento de ladrillo o madera. falla a tierra alternativo - GFCI (no ilustrada). Verifique
que el GFCI esté asegurado firmemente a la caja.
6. CONECTE LA ELECTRICIDAD. Retire el centro desde la junta y colóquelo sobre el Tomacorriente simple
GFCI. Inserte (2) tornillos (suministrados) a través de o
los agujeros CIRCULARES en la cubierta en los
© 2008 Thomas & Betts Memphis, TN. orificios roscados del GFCI. Apriete los tornillos. adaptador interruptor TA04208 A
Todos los derechos reservados. www.tnb.com Siga los pasos indicados en 4A. Pág. 3 de 4
TA04208 A Page 4 of 4
8.8 DIVISION 26 51 00- Interior Light Ceiling Fan Fixture
Type F SPEC 2.1
PARTS GUIDE
20
123
24 28
18
114 32
106 108 110
33
129
63
98
51
55 53
136
76
80
#
# in Parts List Included Accessories / Accesorios incluidos
# en Lista de partes
Pre-installed Parts / Partes preinstaladas
Spare Parts Bag
Bolsa de partes de repuesto
26
81 140
Hardware drawn to scale
For your convenience, you may receive extra fasteners.
Materiales dibujado a escala
Para su comodidad, es posible que reciba sujetadores extra.
MODEL #
59241 59242
MODELO #
DRAWING #
K5655-01 K5655-02
Hunter Fan Company • 7130 Goodlett Farms Parkway #400 • Memphis, TN 38016 • www.HunterFan.com • 98000-03-414 • 04-14-16 • ©2016
Table of Contents www.HunterFan.com 1.888.830.1326
PA G E
PA G E
PA G E
PA G E
We are proud of our work and
appreciate the opportunity to Hanging the Fan Wiring Canopy Blades
supply you with the best ceiling fan
available anywhere in the world.
PA G E
PA G E
PA G E
PA G E
Save your receipt for proof of purchase.
Operation,
Switch Housing Light Kit Remote Control Maintenance & Cleaning Troubleshooting
? ?
13 14 16 17 ? 19
PA G E
PA G E
PA G E
PA G E
PA G E
1
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
What to Expect with Your Installation www.HunterFan.com 1.888.830.1326
3
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Ceiling Plate www.HunterFan.com 1.888.830.1326
Bumper
r
owe
rnP
Tu
OFF
4
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Top Housing www.HunterFan.com 1.888.830.1326
Top Housing
Canopy
Trim Ring
Adapter
Adapter
Thread the wires through the Place the top housing onto the Rest the trim ring on the top Place the canopy on the top
top housing. motor housing so that the holes housing. housing. Ensure all four screw
in the top housing lineup with holes line up with the screw
the holes in the motor housing holes in both the top housing
and the adapter. and the adapter.
5
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Top Housing (continued) www.HunterFan.com 1.888.830.1326
CUT
STRIP
3/8”
&
(not to scale)
8”
Grounding
Top Housing Screw
Screws
Install the top housing screws. Install The wires can be cut, but leave at
the grounding screw in the smaller least 8” extending from the top of
screw hole. These screws can be found the canopy.
in the hardware bag.
8” 3/8”
6
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Hanging the Fan www.HunterFan.com 1.888.830.1326
Ceiling
Plate Hook
Ceiling
Plate
Hook
Raise the fan and align the slots in the Place the slots over the ceiling plate
canopy with the hooks on the ceiling plate. hooks to hang the fan.
Note: To hang the fan, you must tilt the
canopy to an almost vertical position so that
the canopy slots sit on the ceiling plate hooks.
Receiver
(grounding)
green/yellow stripe
Using an orange
wire connector from
the hardware
bag, connect the
3 grounding wires
(green, green/
yellow stripe, or bare
copper) coming
green
from the ceiling and
ceiling plate.
E
FR
AT
OM PL
CEILING
Turn the splices upward and push them carefully back through the hanger bracket
into the outlet box. Spread the wires apart, with the grounded wires on one side of
Refer to CAUTION c.1 on pg. 2 the outlet box and the ungrounded wires on the other side of the outlet box.
8
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
www.HunterFan.com 1.888.830.1326
RECEIV OM CEILING
OM ER
FR FR
Using the orange wire connectors Using the orange wire connectors
yellow
blue
(ungrounded)
black
white (grounded)
from the remote control hardware bag: from the hardware bag:
OM FAN
FR
• Connect the yellow wire from • Connect the black (ungrounded)
the receiver to the black wire wire from the ceiling to the black
from the fan. wire from the receiver.
white
• Connect the blue wire from the • Connect the white (grounded)
receiver to the blue wire (or wire from the ceiling to both the
possibly black with white stripe black white wire from the receiver and
blue
black
white
wire) from the fan. the white wire from the fan.
FR
FRO OM ER
M FA N RECEIV
Turn the splices upward and push them carefully back through the hanger bracket
into the outlet box. Spread the wires apart, with the grounded wires on one side of
Refer to CAUTION c.1 on pg. 2 the outlet box and the ungrounded wires on the other side of the outlet box.
9
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Canopy www.HunterFan.com 1.888.830.1326
Ceiling
Plate Hooks
Canopy
Screw
Screw Canopy
Holes Screw
Swing the fan up to align the canopy Hold the canopy up with the screw Partially install a canopy screw, found
screw holes with the mounting holes on holes aligned. Partially install two in the hardware bag, between the
the ceiling plate. canopy screws, found in the ceiling plate hooks. When all the holes
Note: The slots in the canopy must hardware bag, into the holes opposite are properly aligned, securely tighten all
remain engaged while swinging the the ceiling plate hooks. three canopy screws.
canopy for alignment.
10
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Canopy (continued) www.HunterFan.com 1.888.830.1326
Canopy
Trim Ring
11
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Blades www.HunterFan.com 1.888.830.1326
12
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Switch Housing www.HunterFan.com 1.888.830.1326
Screw two housing assembly screws from Feed the wire plug through the center Insert the third screw, found in the
the hardware bag halfway into the hole of the upper switch housing, then hardware bag, into place and then tighten
motor housing. It does not matter which wrap keyhole slots around the screws and all three screws.
two screw holes you choose. twist counterclockwise.
Screw two housing assembly screws from Connect the plugs from the upper Install the third switch housing screw.
the hardware bag halfway into the and lower switch housings. Make sure Tighten all three screws securely.
upper switch housing. It does not matter to line up the colored markings on
which two screw holes you choose. the connectors.Wrap light kit keyhole
slots around the screws and twist
counterclockwise.
Tab
Notch
Install a bulb into each of the sockets. Lift the globe and align the notches in the
When necessary, replace with bulbs of the globe with the tabs in the light kit. Attach
same type and wattage. the glass bowl to the light kit by twisting it
clockwise until it snaps into place.
15
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Remote Control www.HunterFan.com 1.888.830.1326
er
Pow
Switch Cover Plate rn
Tu
ON
Battery
Door
Phillips CONGRA
Head Removed Rocker- Style YOU’RETULATIONS!
Screw Tabs Plate DONE!
To access the battery compartment, remove To install the transmitter cradle, remove the
the small Phillips head screw that secures the two screws holding the switch cover plate. Do
battery door to the transmitter assembly. The not remove the cover plate. Orient the cradle
battery should be installed with the positive by lining up the two mounting holes with
(+) side up. Replace with a CR2032 battery those on the cover plate. Insert and tighten
when necessary. the screws. Do not over tighten. See next page for fan
Note: For rocker-style cover plates, break off operation instructions.
the tabs by pushing outward.
16
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Operation, Maintenance, & Cleaning www.HunterFan.com 1.888.830.1326
Medium
Speed
Fan High
Off Speed
Light
Low Reverse
Speed Switch
To turn on fan, press a fan speed button. The remote transmitter should already be paired To switch the direction of air flow, move the
Speeds range from off (0) to high (3). Quickly to the receiver and ready to use. reverse switch to the opposite position. You
press the Light button to turn the lights off Note: If your need to pair your remote, turn fan will need to remove the glass to do so.
and on. Hold the Light button to raise and power off and back on at the wall switch. Within 3
dim the light level. minutes, press and hold both the Fan Off button
and the High button for 4 seconds to pair the
remote. To prevent faulty operation, please
ensure all other ceiling fans within range are
turned off at the wall switch while pairing.
17
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Operation, Maintenance, & Cleaning (continued) www.HunterFan.com 1.888.830.1326
Safe-Exit
The Safe-Exit Program gives you about thirty
seconds of light when you turn the lights off
to exit the room before the lights go out. To
use Safe-Exit:
Changing the bulbs - carefully When cleaning the fan, use soft brushes
remove the globe. Unscrew bulbs or cloths to prevent scratching. Cleaning
and replace with bulbs of the same products may damage the finishes.
wattage. Reinstall the globe.
18
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Troubleshooting www.HunterFan.com 1.888.830.1326
Fan doesn’t work Excessive wobbling Noisy operation Lights dim when turned on or
• Make sure power switch is on. • Tighten all of the blade and • Tighten the blade and blade do not turn on at all.
blade iron screws until they iron screws until they are snug. • Make sure the wattage of the
• Pull the pull chain to make sure are snug. light bulbs installed matches
it is on. • Check to see if any of the the specifications on the light
• Turn the power off, support blades are cracked. If so, replace sockets.
• Push the motor reversing switch the fan carefully, and check all of the blades.
firmly left or right to ensure that that the hanger ball is
it is engaged. properly seated.
• Check the circuit breaker to • Use the provided balancing
ensure the power is turned on. kit and instructions to balance
the fan.
• Make sure the blades spin freely.
19
M0115-01 • 02/11/16 • © 2016 Hunter Fan Company
Article Information Sheet
Product name: Lithium Manganese Dioxide Button Cell Printing date: 05-Aug-2019
1. DOCUMENT INFORMATION
Product name: Lithium Manganese Dioxide Button Cell
Model: CR2032
Issue Date: 05-Aug-2019
2. COMPANY INFORMATION
Company name(China) DONGGUAN TUOBU ELECTRONIC CO., LTD
Address: No.A, Building6, BinheRoad, TianxinQuarter, HuangjiangTown, Dongguan,
Guangdong
E-mail: FREEGOBATTERY@126.COM
Telephone: +86-755-25867899
3. ARTICLE INFORMATION
Description Lithium Manganese Dioxide Button Cell
Use Lithium Primary/Metal Batteries
Brand ----
Image
4. ARTICLE CONSTRUCTION
IMPORTANT NOTE: The battery should not be opened or burned. Exposure to the ingredients contained within or
their combustion products could be harmful.
Chemical name CAS No. Concentration%
Manganese Dioxide 1313‐13‐9 32.8
Lithium 7439‐93‐2 2.04
Iron 7439‐89‐6 52.78
Propylene carbonate 108‐32‐7 4.13
1,3-Dioxolane 646-06-0 4
Lithium perchlorate 7791‐03‐9 4.25
-- Page 1 / 4 --
Article Information Sheet
Product name: Lithium Manganese Dioxide Button Cell Printing date: 05-Aug-2019
-- Page 2 / 4 --
Article Information Sheet
Product name: Lithium Manganese Dioxide Button Cell Printing date: 05-Aug-2019
lithium batteries, such as warehouses, lithium batteries should be isolated from unnecessary
combustibles.
Handling Avoid mechanical and electrical abuse. Do not short circuit or install incorrectly. Batteries
may rupture or vent if disassembled, crushed, recharged or exposed to high
temperatures. Install batteries in accordance with equipment instructions.
Spills of Large Quantities Notify spill personnel of large spills. Irritating and flammable vapors may be released from
Batteries (unpackaged) leaking or ruptured batteries. Spread batteries apart to stop shorting. Eliminate all
ignition sources. Evacuate area and allow vapors to dissipate. Clean-up personnel should
wear appropriate PPE to avoid eye and skin contact and inhalation of vapors or fumes.
Increase ventilation. Carefully collect batteries and place in appropriate container for
disposal. Remove any spilled liquid with absorbent material and contain for disposal.
8. DISPOSAL CONSIDERATIONS
Dispose of used (or excess) batteries in compliance with federal, state/provincial and local regulations. Do not
accumulate large quantities of used batteries for disposal as accumulations could cause batteries to short-circuit. Do not
incinerate. In countries, such as Canada and the EU, where there are regulations for the collection and recycling of
batteries, consumers should dispose of their used batteries into the collection network at municipal depots and
retailers. They should not dispose of batteries with household trash.
9. Transport information
The transportation of primary lithium cells and batteries is regulated by the International Civil Aviation Organization,
International Air Transport Association, International Maritime Dangerous Goods Code and the US Department of
Transportation. The batteries must meet the following criteria for shipment: 1. Air shipments must meet the
requirements listed in Special Provision A45 of the International Air Transport Association Dangerous Goods Regulations.
2. Meet the requirements for the US Department of Transportation listed in 49 CFR 173.185. 3. The transport of
primary lithium batteries is prohibited aboard passenger aircraft. Refer to the Federal Register December 15, 2004
(Hazardous Materials; Prohibited on the Transportation of Primary Lithium Batteries and Cells Aboard Passenger
Aircraft; Final Rule)
Lithium batteries shipped as "Lithium batteries", "Lithium batteries packed with equipment", or "Lithium batteries
contained in equipment" may not be classified as "Dangerous Goods" when shipped in accordance with "special
provision A45 of IATA-DGR" or "special provision 188 of IMO-IMDG Code"
(a) UN number 3480&3481
(b) UN Proper shipping name LITHIUM ION BATTERIES (including lithium ion polymer
batteries) or;
LITHIUM ION BATTERIES CONTAINED IN EQUIPMENT or
LITHIUM ION BATTERIES PACKED WITH EQUIPMENT (including
lithium ion polymer batteries)
(c) Transport hazard class(es) 9
(d) Packing group (if applicable) IA
(e) Marine pollutant (Yes/No) No
(f) Transport in bulk (according to Annex II of No information available.
MARPOL 73/78 and the IBC Code)
-- Page 3 / 4 --
Article Information Sheet
Product name: Lithium Manganese Dioxide Button Cell Printing date: 05-Aug-2019
-- Page 4 / 4 --
8.9 Lighting Type “A” Spec 2.2 Luminaires
Note: RX Series LED Luminaire has been discontinued. RXL Series Luminaire is the new product
from General Electric which will replace the discontinued product line of RX Series.
Lumination™ LED Luminaires
Project name _________________
Date ________________________
RX Series Downlights Type ________________________
RX820835MV-PUBLISH.IES
ZONAL LUMEN SUMMARY COEFFICIENTS OF UTILIZATION
RC 80% 70% 50% 30% 10% 0%
Zone Lumens
RW 70% 50% 30% 10% 70% 50% 30% 10% 50% 30% 10% 50% 30% 10% 50% 30% 10% 0%
0-10° 88.00 0 119 119 119 119 116 116 116 116 111 111 111 106 106 106 102 102 102 100
10-20° 250.24 1 111 107 103 100 108 105 102 99 101 98 96 97 95 93 93 92 90 88
20-30° 373.80 2 102 96 90 85 100 94 88 84 90 86 82 87 83 80 84 81 79 77
30-40° 437.77 3 95 86 79 73 92 84 78 72 81 76 71 79 74 70 76 72 69 67
40-50° 408.07 4 87 77 69 63 85 76 68 63 73 67 62 71 66 61 69 64 61 59
50-60° 273.31 5 81 70 62 56 79 68 61 55 66 60 55 65 59 54 63 58 54 52
60-70° 110.22 6 75 63 55 49 73 62 55 49 61 54 49 59 53 48 57 52 48 46
70-80° 45.22 7 70 58 50 44 68 57 49 44 55 49 44 54 48 43 53 47 43 41
80-90° 12.64 8 65 53 45 40 64 52 45 39 51 44 39 50 44 39 49 43 39 37
90-100° 0.02 9 61 49 41 36 60 48 41 36 47 40 36 46 40 35 45 39 35 34
100-110° 0.03 10 57 45 38 33 56 45 37 33 44 37 32 43 37 32 42 36 32 31
110-120° 0.06
120-130° 0.11 NOTE: Floor Cavity Reflectance : 20%
130-140° 0.16 ZONAL LUMEN SUMMARY LUMINANCE DATA (CANDELA/m2) POLAR GRAPH
140-150° 0.18
Zone Lumens % of Fixture Gamma 0° 45° 90° 932
150-160° 0.17
160-170° 0.12 0-20° 338.25 16.90 45° 266136 266196 266346 699
170-180° 0.04 0-30° 712.05 35.60 55° 188753 188759 188889
0-40° 1149.82 57.50 466
65° 86295 86220 86354 2
0-60° 1831.2 91.60 75° 58284 58366 58407 233
0-80° 1986.64 99.30 85° 43727 44376 45714
0-90° 1999.28 100.00
Product Specifications: 1
www.gelighting.com
GE and the GE Monogram are trademarks of the General Electric Company. All other trademarks are the property
of their respective owners. Information provided is subject to change without notice. All values are design or typical
values when measured under laboratory conditions. GE Lighting is a business of the General Electric Company.
© 2016 GE.
IND191 (Rev 05/26/16)
Installation Guide
IND259 | A-1028951
WARNING / AVERTISSEMENT
RISK OF ELECTRIC SHOCK RISQUES DE DÉCHARGES ÉLECTRIQUES
• Turn power off before inspection, installation or removal. • Coupez l’alimentation avant d’inspecter, installer ou déplacer le luminaire.
• Properly ground electrical enclosure. • Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISK OF FIRE RISQUES D’INCENDIE
• Follow all NEC and local codes. • Respectez tous les codes NEC et codes locaux.
• Use only UL approved wire for input/output connections. • N’utilisez que des fils approuvés par UL pour les entrées/sorties de connexion.
Minimum size 18 AWG (0.75mm2). Taille minimum 18 AWG (0.75mm2).
• Do not install insulation within 3 inches (76 mm) of luminaire top. • Maintenir une distance de 76 mm (3 pouces) entre le luminaire et l’isolant.
Provided Components
The components have been properly packed to avoid damage during transit. Inspect the components to confirm there is no physical
damage. Do not install damaged components.
Option A: Mount fixture by attaching hanger bars to T-Grid Adjust fixture height to be flush with ceiling and tighten
4 ceiling (BH3 SKU 94890) 5 mounting bracket wing nuts.
Option B: Mount fixture with 1.2” EMT conduit (not supplied)
2
Lumination® RC/LRC/RXLRX Series Installation Guide
RC/LRC-Series Mounting
(RX-Series skip to step 15. LRXR and LRXG - Series, skip to step 18.
Open RC/LRC PSU box cover, disconnect AC conduit. Remove AC conduit wire from PSU box knockout hole using
6 flat head screwdriver.
3
Lumination® RC/LRC/RXLRX Series Installation Guide
Place PSU box onto frame next to unused Take the provided safety tether and loop one
8 junction box and secure with U-bracket by 9 end of the tether around the L-bracket.
tightening wing nut.
Place PSU box onto frame next to unused Plug together the light fixture to the driver
10 junction box and secure with U-bracket by 11 enclosure with the supplied quick connects and
tightening wing nut. assemble the connector housing once finished.
Cut cable tie on light fixture Align the fixture so that two of the three springs are on each
12 13 side of the L-bracket. This is necessary in order to make
sure that when the springs release, the L-bracket does not
interfere and prevent the springs from making contact with
the top of the ceiling for proper support.
4
Lumination® RC/LRC/RXLRX Series Installation Guide
RX Series Mounting
Connect AC line to existing junction box. Connect conduit fitting to the existing junction box. Connect the black,
15 white, and green/yellow wires of the input leads to the black, white and green AC line wires using UL Listed twist-
on wire connectors and close the junction box (see wiring diagram).
Connect the two quick connectors and reassemble Load springs into an upright position by twisting
16 the connector box. 17 the springs upware. Carefully insert the fixture into
the frame hole. Ensure fixture is secure.
5
Lumination® RC/LRC/RXLRX Series Installation Guide
www.gecurrent.com/dimming
Note:
For 1000/650lm luminaires, the default lumen output is 1000lm. Push the switch up to activate the 650lm setting.
For 4000/3000lm luminaires, the default lumen output is 4000lm. Push the switch up to activate teh 3000lm setting.
6
Lumination® RC/LRC/RXLRX Series Installation Guide
20 Adjusting CCT
(for compatible fixtures only)
7
Lumination® RC/LRC/RXLRX Series Installation Guide
22
Note: Applicable only to 10in and 12 in Fixtures Connect the two quick connectors and reas-
21 Affix the hook of the safety tether onto the bracket of semble the connector box.
the frame kit.
23
Load springs into an upright position by twisting
the springs upward a. Carefully insert the fixture
24 Once installed, LRX Gimbal downlight’s light
engine can be rotated up to 359° horizontally
into the hole of the rough-in frame. Verify that and tilted up to 35° vertically.
the reflector trim is flush to the ceiling.
Note: it is recommended to use gloves while
handling and adjusting the Gimbal light engine
to prevent dirt and oils from contaminating the
surface of the luminaire.
www.gecurrent.com
© 2020 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the
General Electric Company and are used under license. Information provided is subject to change without
notice. All values are design or typical values when measured under laboratory conditions.
IND259 (Rev 12/18/20) A-1028951
Installation Guide
IND300 | A-1098951
WARNING / AVERTISSEMENT
RISK OF ELECTRIC SHOCK RISQUES DE DÉCHARGES ÉLECTRIQUES
• Turn power off before inspection, installation or removal. • Coupez l’alimentation avant d’inspecter, installer ou déplacer le luminaire.
• Properly ground electrical enclosure. • Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISK OF FIRE RISQUES D’INCENDIE
• Follow all NEC and local codes. • Respectez tous les codes NEC et codes locaux.
• Use only UL approved wire for input/output connections. • N’utilisez que des fils approuvés par UL pour les entrées/sorties de connexion.
Minimum size 18 AWG (0.75mm2). Taille minimum 18 AWG (0.75mm2).
• Do not install insulation within 3 inches (76 mm) of luminaire top. • Maintenir une distance de 76 mm (3 pouces) entre le luminaire et l’isolant.
Luminaire Installation
Before installation, verify that the existing junction
box and bracket are metal construction, designed
similarly to Illustration 1A.
1
Ensure that the power to the unit is turned off. Use Remove existing lamps, fixture and ballast. Leave
proper lockout/tagout procedures. 2 wiring in junction box. Verify that the AC supply line
is provided with a ground wire connected to the
luminaire.
2
Lumination® LRX Series Installation Guide
Disassemble the quick disconnection box (con- Connect conduit end with input leads to existing
3 nector box) and unplug the two quick connec- 4 junction box and make the proper connections.
tors inside. Make all electrical connections using twist-on wire
connectors. Securely close the junction box.
Optional Dimmer: When connecting a dimming Note: Phase cut dimmers must be wired to the power feed
controller, low-voltage dimming wires must route “hot” line (L). For 0-10V and phase cut dimming compatibility,
through a separate knockout. Connect the violet please visit:
(dimming +) and gray (dimming -) wires to the
violet and gray fixture wires. www.gecurrent.com/dimming
3
Lumination® LRX Series Installation Guide
Note:
For 1000/650lm luminaires, the default lumen output is 1000lm. Push the switch up to activate the 650lm setting.
For 4000/3000lm luminaires, the default lumen output is 4000lm. Push the switch up to activate teh 3000lm setting.
6 Adjusting CCT
(for compatible fixtures only)
Note: Note: The cover of the CCT switch can be used as a tool
For 2700K/3000K/3500K, default output CCT is 3000K. for switching CCT settings more easily.
Push switch up to activate 2700K, push the switch
down to activate 3500K.
For 3500K/4000K/5000K, default output CCT is 4000K.
Push switch UP to select 3500K or DOWN to select
5000K
4
Lumination® LRX Series Installation Guide
7 Firmly connect the two quick connectors and 8 Load springs into an upright position by
reassemble the connector box. twisting the springs upward a. Carefully insert
the fixture into the hole of the rough-in frame.
Verify that the reflector trim is flush to the
ceiling.
www.gecurrent.com
© 2020 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the
General Electric Company and are used under license. Information provided is subject to change without
notice. All values are design or typical values when measured under laboratory conditions.
IND300 (Rev 12/18/20) A-1028591
8.10 Lighting Type B and C, SPEC 2.2 Luminaires
BLWP
With multiple mounting options, easy installation, and controls configurations, the BLWP is an excellent
choice for renovation and new construction.
CONSTRUCTION — BLWP enclosure components are die-formed for dimensional consistency. For 2'
and 4' product, hinged door frame allows easy access to electrical components and mounting locations
without having to remove additional parts. For 8' product, suspension aircraft cables allow easy access
to electrical components and mounting locations without having to remove additional parts. Available
in three paint finishes: white (pre-paint), painted after fabrication white, and natural aluminum. 2', 4' and 8' Lengths
Diffusers are extruded from impact modified acrylic for increased durability. Optional polycarbonate
lens available for additional impact resistance, as well as Tamper Proof screws.
OPTICS — Volumetric illumination is achieved by creating an optimal mix of light to walls, partitions
and vertical and horizontal work surfaces – rendering the interior space, objects and occupants in a
more balanced, complimentary luminous environment. High performance extruded acrylic diffusers
conceal LEDs and efficiently deliver light in a volumetric distribution. Five diffuser choices available -
curved and square designs with ribbed, a smooth frosted finish, and a smooth polycarbonate finish.
ELECTRICAL — Long-life LEDs, coupled with high-efficiency drivers, provide superior quantity
and qualityof illumination for extended service life. 80% LED lumen maintenance at 60,000 hours TM
ORDERING INFORMATION Lead times will vary depending on options selected. Consult with your sales representative. Example: BLWP4 40L ADP GZ10 LP840
NOTE: ‡ indicates option value has ordering restrictions. Please reference the Option Value Ordering Restictions chart on the next page. Options are sorted alphanumerically.
BLWP
Commercial Indoor: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2018-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/13/21
Page 2 of 13
BLWP Low Profile LED Wraparound
‡ Option Value Ordering Restrictions
Option value Restriction
347 Not available with E10WLCP, EL7L, EL14L, BGTD or BLWP4 > 85L/ 85LHE.
BLWPCR, BLWPCRDNA, BLWP8CR, BLWP8CRDNA Cannot be used to continuous row mount 4' fixtures with 8' fixtures.
BGTD Not available with JOT sensor options or emergency battery options. Must specify voltage. Requires BSE labeling, voltage specific. Consult factory for options.
Example: BGTD BSE10.
DIM10, DIM50 Not available with NLTAIR2 or JOT sensor option. Requires occupancy control. Must be ordered with nLight Wired or Individual Control sensor option.
EL7L, EL14L Only available on BLWP8, 8ft length version of this fixture, in lumen packages 140L or less.
FAO EZ1 driver required. Not available with USPOM, FAO or lumen packages > 6000LM. FAO is not available with other integrated controls options and restricts the
use of external dimming controls. See chart on page 5 for additional details.
GLR, GMF Must specify voltage. 120 or 277, with GLR and GMF fusing.
GZ1, GZ10 Not available with any Control or Sensor options except JOT & JOTVTX15
JOT, JOTVTX15 Not available with SLD, NLIGHT, NLTAIR2, NOC, USPOM or FAO. Available only on 4' versions with ADPT and ADMST trim options; not available with > 72L or
72LHE lumen packages.
Lumens Approximate lumen output. For high Efficiency, all versions may not achieve 130+ LPW including 90CRI and versions with integral sensor trim. Refer to
photometry on www.acuitybrands.com. See QPL for latest DLC listings.
MSD7ADCX, MSDPDT7ADCX Must select Lens/Diffuser type with Trim Rings. Not available with nLight interface. 0-10V wires are not accessible via access plate.
N80EMG, N100EMG Requires a connection to existing nLight network. Power is provided from a separate NLIGHT enabled fixture or external power pack.
NES7, NESPDT7, NES7ADCX, NESPDT7ADCX Must select Lens/Diffuser type with Trim Rings. Requires N80, N80EMG, N100, or N100EMG. Only available with EZ1 driver.
NLTAIR2 Must select nLight wireless control. Not available with JOT or JOTVTX15
NOC Not available with JOT sensor options. Can only be ordered in conjunction with EZ1, NLTAIR2, RES7/RES7PDT. Occupancy sensor disabled at factory but can be
re-enabled upon commissioning.
PDSM, PDSMT Not available with HE (high efficiency) performance package on BLWP2 and BLWP4 only.
PLR__, PLR1LVG Not available with BLWP2. PLR1LVG is not available with Controls options or nLight interface.
QMB Not available with BLWP2 (2') or BLWP8 (8') fixture.
RES7, RES7PDT, RIO, RES7EM, RES7PDTEM, RIOEM Must select Lens/Diffuser type with Trim Rings. Requires EZ1 and NLTAIR2 to be specified. Only available with 60L or lower lumen packages on the BLWP4. Only
available with 100LHE/80L lumen packages or lower on the BLWP8.
SLD Not available with any nLight Interface or Control options. Cannot be used with PLR1LVG
TRS Accessory BLWP TRS T15 BIT available to be ordered with this option. See Accessories section page 3. Order as separate item.
Non-Configurable BLWP:
Stock/MTO Ci code Catalog Description UPC Lumens Wattage LPW Color Temperature Voltage Pallet QTY
*264V2M BLWP2 20L ADP LP835 191848282045 1942 17 117 3500 K 120-277 80
*264V2L BLWP2 20L ADP LP840 191848282038 1973 17 119 4000 K 120-277 80
*264CH0 BLWP2 33L ADP LP835 191848080825 3332 30 112 3500 K 120-277 80
MTO
*264CH1 BLWP2 33L ADP LP840 191848080832 3345 30 112 4000 K 120-277 80
*264CH2 BLWP2 40L ADP LP835 191848080849 3923 37 105 3500 K 120-277 80
*264CH4 BLWP2 40L ADP LP840 191848080856 4117 37 110 4000 K 120-277 80
*264V2K BLWP4 30L ADP LP835 191848282021 3065 25 123 3500 K 120-277 70
*264V2H BLWP4 30L ADP LP840 191848281994 3114 25 125 4000 K 120-277 70
*264CH5 BLWP4 40L ADP LP835 191848080863 4391 35 127 3500 K 120-277 70
STOCK
*264CH6 BLWP4 40L ADP LP840 191848080870 4263 35 123 4000 K 120-277 70
*264CH7 BLWP4 48L ADP LP835 191848080900 5137 40 129 3500 K 120-277 70
*264CH8 BLWP4 48L ADP LP840 191848080917 5205 40 131 4000 K 120-277 70
BLWP
Commercial Indoor: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2018-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/13/21
Page 3 of 13
BLWP Low Profile LED Wraparound
BLWP
Commercial Indoor: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2018-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/13/21
Page 4 of 13
BLWP Low Profile LED Wraparound
2' Version Replacement Lens 4' Version Replacement Lens 8' Version Replacement Lens
*264F5E DBLWP24 ADP *264F69 DBLWP48 ADP *2543CE DBLWP96 ADP
*264F5F DBLWP24 SDP *264F6E DBLWP48 SDP *2543CG DBLWP96 SDP
*264F5H DBLWP24 ADSM *264F6F DBLWP48 ADSM *2543CJ DBLWP96 ADSM
*264F5J DBLWP24 SDSM *264F6G DBLWP48 SDSM *2543CM DBLWP96 SDSM
*264F5L DBLWP24 ADPT *264F6H DBLWP48 ADPT *2543CN DBLWP96 ADPT
*264F5P DBLWP24 SDPT *264F6K DBLWP48 SDPT *2543CP DBLWP96 SDPT
*264F5U DBLWP24 ADSMT *264F6L DBLWP48 ADSMT *2543CR DBLWP96 ADSMT
*264F5W DBLWP24 SDSMT *264F6N DBLWP48 SDSMT *2543CS DBLWP96 SDSMT
*264F66 DBLWP24 PDSM *264F6W DBLWP48 PDSM *2543CW DBLWP96 PDSM
*264F67 DBLWP24 PDSMT *264F6X DBLWP48 PDSMT *2543CX DBLWP96 PDSMT
JOT Wireless
BLWP
Commercial Indoor: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2018-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/13/21
Page 5 of 13
BLWP Low Profile LED Wraparound
nLight Platform
H N H N H N
BLWP Series
Simple as 1,2,3
1. Install the nLight® AIR fixtures with embedded smart sensor
2. Install the wireless battery-powered wall switch
3. With CLAIRITY app, pair the fixtures with the wall switch
and if desired, customize the sensor settings for the desired
outcome nLight AIR rPODBA Mobile Device
H N H N H N
CAT5e
BLWP Series
Simple as 1,2,3
1. Install the nLight® Wired fixtures with embedded control
2. Install the nLight Wired wall switch
3. Connect the fixtures using standard CAT5e cables and the devices
will automatically discover each other and work (plug and play) nLight Wired nPODMA
BLWP
Commercial Indoor: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2018-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/13/21
Page 6 of 13
BLWP Low Profile LED Wraparound
Basic nLight Zone
Sensor Options
Automatic Occupancy Sensing nLight Wired nLight AIR
Option
Dimming Photocell PIR PDT Networking Networking
MSD7ADCX X X
MSDPDT7ADCX X X
NES7 X X
NES7ADCX X X X
NESPDT7 X X
NESPDT7ADCX X X X
RES7 X X X
RES7PDT X X X X
Sequence of
SEQUENCE OFOperation
OPERATION Sequence of
SEQUENCE OFOperation
OPERATION
MOTION NO MOTION MOTION MOTION NO MOTION MOTION
MAX MAX
LIGHT LEVEL
The Space Motion The Space Motion
MIN MIN
LIGHTS ON 17.5 MIN 2.5 MIN AT LIGHTS OFF LIGHTS ON LIGHTS ON 7.5 MIN 2.5 MIN AT LIGHTS OFF LIGHTS ON
TIME DELAY A 1% LEVEL TIME DELAY A 1% LEVEL
*The presetting on the automatic dimming photocell is 5fc. *The presetting on the automatic dimming photocell is 5fc.
9 FT Mounting H N H N H N
5.5 18
4.6 15
3.7 12
2.7 9
1.8 6 BLWP Series
0.9 3
0m 0 ft Simple as 1,2,3
0.9 3
1.8 6 1. Install the nLight® AIR fixtures with embedded smart sensor
2.7 9 2. Install the wireless battery-powered wall switch
3.7 12
4.6 15 3. With CLAIRITY PRO app, pair the fixtures with the wall switch and if
5.5 18 desired, customize the sensor settings for the desired outcome
BLWP
Commercial Indoor: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2018-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/13/21
Page 7 of 13
BLWP Low Profile LED Wraparound
MOUNTING INFORMATION
For unit or row installation; surface or suspend mounting. Accessory Images
Note: 2' and 8' configurations not available with QMB accessory.
Stem Suspension
Individual installation — Two single-stem hangers required.
8 7 6 5 4 3 2
REVISIONS
NOTES: REV. ECR# DESCRIPTION
XX XX XXXXX
1. Note: 2' configurations with emergency option cannot be stem mounted.
DIMENSIONS
All dimensions are inches (centimeters) unless otherwise noted.
CABLE HANGER
ATTACHMENT HOLES
ENDPLATE
24.00(61) 48.00(122)
21.54(55) 45.54(116)
Quick Mount(QMB) 43.50(111)
19.50(50) 3.75(10)
q 3.75(10) (Optional) q
5.30(14)
ENDPLATE
DETAIL A SCREW
5.30(14) A
8' DIMENSIONS
BLWP
Commercial Indoor: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2018-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/13/21
Page 8 of 13
BLWP Low Profile LED Wraparound
PHOTOMETRICS
BLWP2 33L ADP LP835, 3332 delivered lumens, test no. ISF 37666, tested in accordance to IESNA LM-79.
180°
Coefficients of Utilization
pf 20%
90°
CP Summary pc 80% 70% 50% Zonal Lumen Summary
80° 0° 90 pw 70%50%30% 50%30%10% 50%30%10% Zone Lumens % Lamp % Fixture
0° 1024 1024 0 117 117 117 114 114 114 107 107 107 0° - 30° 790 23.7 23.7
200
5° 1009 1027 1 106 100 96 97 93 89 92 88 85 0° - 40° 1286 38.6 38.6
15° 962 982 2 96 87 79 84 78 72 79 74 69 0° - 60° 2278 68.4 68.4
400 60°
25° 867 910 3 87 76 67 74 66 59 70 63 57 0° - 90° 3096 92.9 92.9
35° 745 809 4 79 67 58 65 57 50 62 54 49 90° - 120° 184 5.5 5.5
RCR
600 45° 604 694 5 73 60 51 58 50 43 55 48 42 90° - 130° 210 6.3 6.3
55° 456 567 6 67 54 45 52 44 38 50 42 37 90° - 150° 233 7.0 7.0
800 65° 303 436 7 62 49 40 48 39 33 45 38 32 90° - 180° 236 7.1 7.1
40° 75° 158 309 8 58 44 36 43 35 30 41 34 29 0° - 180° 3332 100.0 100.0
1000 85° 36 202 9 54 41 32 40 32 27 38 31 26
0° 20° 90 0 161 10 51 38 30 37 29 24 35 28 24
0° 90°
BLWP2 40L ADP LP835, 3923 delivered lumens, test no. ISF 37668, tested in accordance to IESNA LM-79.
180°
Coefficients of Utilization
pf 20%
90°
CP Summary pc 80% 70% 50% Zonal Lumen Summary
80° 0° 90 pw 70%50%30% 50%30%10% 50%30%10% Zone Lumens % Lamp % Fixture
200 0° 1210 1210 0 117 117 117 114 114 114 107 107 107 0° - 30° 932 23.8 23.8
5° 1190 1219 1 106 100 96 97 93 89 92 88 85 0° - 40° 1519 38.7 38.7
400 15° 1130 1178 2 96 87 80 84 78 72 80 74 69 0° - 60° 2687 68.5 68.5
60°
25° 1019 1100 3 87 76 67 74 66 60 70 63 58 0° - 90° 3646 92.9 92.9
600 35° 870 990 4 80 67 58 65 57 50 62 55 49 90° - 120° 215 5.5 5.5
RCR
BLWP4 40L ADP LP835, 4391 delivered lumens, test no. ISF 37596, tested in accordance to IESNA LM-79.
180°
Coefficients of Utilization
pf 20%
90°
CP Summary pc 80% 70% 50% Zonal Lumen Summary
80° 0° pw 70%50%30% 50%30%10% 50%30%10% Zone Lumens % Lamp % Fixture
200 0° 1324 0 117 117 117 114 114 114 107 107 107 0° - 30° 1028 23.4 23.4
5° 1321 1 106 100 95 97 93 89 92 88 85 0° - 40° 1681 38.3 38.3
400 15° 1274 2 96 87 79 84 77 72 79 74 69 0° - 60° 2991 68.1 68.1
60°
25° 1180 3 87 76 67 74 66 59 70 63 57 0° - 90° 4082 93.0 93.0
600
35° 1043 4 79 67 58 65 57 50 62 54 49 90° - 120° 249 5.7 5.7
RCR
BLWP4 48L ADP LP835, 5137 delivered lumens, test no. ISF 37597, tested in accordance to IESNA LM-79.
180°
Coefficients of Utilization
pf 20%
90°
CP Summary pc 80% 70% 50% Zonal Lumen Summary
80° 0° 90 pw 70%50%30% 50%30%10% 50%30%10% Zone Lumens % Lamp % Fixture
0° 1528 1528 0 117 117 117 114 114 114 107 107 107 0° - 30° 1188 23.1 23.1
300
5° 1517 1528 1 105 100 95 97 93 89 91 88 84 0° - 40° 1944 37.8 37.8
15° 1447 1488 2 95 86 79 84 77 71 79 73 69 0° - 60° 3464 67.4 67.4
600 60°
25° 1311 1398 3 87 75 67 73 65 59 69 62 57 0° - 90° 4754 92.5 92.5
35° 1129 1267 4 79 67 57 65 56 50 61 54 48 90° - 120° 308 6.0 6.0
RCR
BLWP
Commercial Indoor: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2018-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/13/21
Page 9 of 13
BLWP Low Profile LED Wraparound
PHOTOMETRICS
BLWP8 40L ADP LP835, 4113 delivered lumens, test no. ISF 37290P226.
180°
Coefficients of Utilization
pf 20%
90°
CP Summary pc 80% 70% 50% Zonal Lumen Summary
80° 0° 90 pw 70%50%30% 50%30%10% 50%30%10% Zone Lumens % Lamp % Fixture
200 0° 1263 1263 0 117 117 117 114 114 114 107 107 107 0° - 30° 979 23.8 23.8
5° 1246 1263 1 106 100 95 97 93 89 92 88 85 0° - 40° 1593 38.7 38.7
400 15° 1197 1223 2 96 87 79 84 77 72 79 74 69 0° - 60° 2811 68.4 68.4
60°
25° 1083 1134 3 87 76 67 74 66 59 70 63 57 0° - 90° 3825 93.0 93.0
600 35° 928 1011 4 79 67 58 65 57 50 62 54 49 90° - 120° 233 5.7 5.7
RCR
45° 750 871 5 73 60 51 58 50 43 55 48 42 90° - 130° 263 6.4 6.4
800
55° 558 722 6 67 54 45 52 44 38 50 42 37 90° - 150° 286 7.0 7.0
1000 65° 378 564 7 62 49 40 48 39 33 45 38 32 90° - 180° 288 7.0 7.0
40° 75° 200 410 8 58 44 36 43 35 30 41 34 29 0° - 180° 4113 100.0 100.0
1200 85° 57 278 9 54 41 32 40 32 27 38 31 26
0° 20° 90 9 221 10 51 38 30 37 29 24 35 28 24
0° 90°
BLWP8 60L ADP LP835, 6033 delivered lumens, test no. ISF 37290P386.
180°
Coefficients of Utilization
pf 20%
90°
CP Summary pc 80% 70% 50% Zonal Lumen Summary
80° 0° 90 pw 70%50%30% 50%30%10% 50%30%10% Zone Lumens % Lamp % Fixture
300 0° 1853 1853 0 117 117 117 114 114 114 107 107 107 0° - 30° 1437 23.8 23.8
5° 1827 1853 1 106 100 95 97 93 89 92 88 85 0° - 40° 2336 38.7 38.7
600 15° 1756 1794 2 96 87 79 84 77 72 79 74 69 0° - 60° 4124 68.4 68.4
60°
25° 1588 1664 3 87 76 67 74 66 59 70 63 57 0° - 90° 5611 93.0 93.0
900 35° 1361 1483 4 79 67 58 65 57 50 62 54 49 90° - 120° 342 5.7 5.7
RCR
PLR
products mounted in continuous rows. 1, 2, 3 and 4-lamp fixtures. PLR22 (2-circuit) and PLR33 (3-circuit) crossover harness switches
hot circuit serving next fixture in row. Reduces fixture types on job for alternating circuit applications (see example below.)
Easy one-step installation, saves up to 35% on labor costs. Expanded switching flexibility helps save energy.
Rows can be 50% longer with two-circuit systems. Polarized, lock-together nylon connectors prevent miswiring in the field. #12
THHN conductor, rated 600V, 90°C. White neutral wire included. Grounding accomplished by fixture in-row connectors.
CSA certified systems available with up to 2 circuits. G ground required.
Advanced 3-Circuit Plug-In
Note: Specifications subject to change without notice.
ORDERING INFORMATION Lead times will vary depending on options selected. Consult with your sales representative.
BLWP
Commercial Indoor: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2018-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/13/21
Page 10 of 13
BLWP Low Profile LED Wraparound
Constant Lumen Management BLWP PERFORMANCE DATA 24
Enabled by the embedded nLight control, the BLT actively
tracks its run-time and manages its light source such that Lumen Package Lumens Input Watts LPW
constant lumen output is maintained over the system life.
Referred to as lumen management, this feature eliminates BLWP2 8L ADP LP830 825 7 118
the energy waste created by the traditional practice of BLWP2 8L ADP LP835 855 7 122
over-lighting.
BLWP2 8L ADP LP840 868 7 124
BLWP2 8L ADP LP850 893 7 128
Without Lumen Management With Lumen Management
Energy is wasted and light level is inconsistent. BLWP2
Energy is saved and light 20L ADP
level remains LP830
consistent. 1876 17 110
100% 30W 100% BLWP2 20L ADP LP835 30W 1942 17 114
POWER INPUT
Saved Energy BLWP2 20L ADP LP840 1973 17 116
BLWP2 20L POWER ADP LP850 2029 17 119
LIGHT OUTPUT
LIGHT OUTPUT
POWER INPUT
POWER INPUT
INPUT
LIGHT BLWP2 33L ADP LP830 3180 30 107
OUTPUT
BLWP2 33L ADP LP835 3332 30 112
Wasted Energy
BLWP2 LIGHT33L ADP
OUTPUTLP840 3345 30 112
80% 24W 80% 24W
0 10 20
THOUSAND OPERATING HOURS
30 40 50 0 10 BLWP2
THOUSAND OPERATING HOURS
20 33L ADP
30 LP850 40 50 3440 30 115
BLWP2 40L ADP LP830 3914 37 105
ement With Lumen Management BLWP2 40L ADP LP835 3923 37 105
consistent. Energy is saved and light level remains consistent. BLWP2 40L ADP LP840 4117 37 110
30W 100% 30W
BLWP2 40L ADP LP850 4234 37 113
R INPUT
Saved Energy BLWP2 48L ADP LP830 4772 44 109
BLWP2 48L ADP LP835 4940 44 112
LIGHT OUTPUT
POWER
POWER INPUT
POWER INPUT
INPUT
HT
PUT BLWP2 48L ADP LP840 5019 44 114
BLWP2 48L ADP LP850 5162 44 118
24W 80%
LIGHT OUTPUT
24W
BLWP4 15L ADP LP830 1372 11 126
30 40 50 0 10 20
THOUSAND OPERATING HOURS
30 40 50
BLWP4 15L ADP LP835 1420 11 129
BLWP4 15L ADP LP840 1443 11 131
How to Estimate Lumens in Emergency Mode BLWP4 15L ADP LP850 1484 11 135
Use the formula below to estimate the delivered lumens BLWP4 20L ADP LP830 1985 16 124
in emergency mode
Estimated Lumens = 1.25 x P x LPW BLWP4 20L ADP LP835 2055 16 128
P = Ouput power of emergency driver. P = 10W for BLWP4 20L ADP LP840 2088 16 131
E10WLCP option. BLWP4 20L ADP LP850 2147 16 134
LPW = Lumen per watt rating of the luminaire. LPW
information available in Performance Data section. BLWP4 30L ADP LP830 2960 25 118
BLWP4 30L ADP LP835 3065 25 123
BLWP4 30L ADP LP840 3114 25 125
BLWP4 30L ADP LP850 3203 25 128
BLWP4 40L ADP LP830 4027 35 115
BLWP4 40L ADP LP835 4391 35 125
BLWP4 40L ADP LP840 4236 35 121
BLWP4 40L ADP LP850 4357 35 124
BLWP4 48L ADP LP830 4948 40 124
BLWP4 48L ADP LP835 5137 40 129
BLWP4 48L ADP LP840 5205 40 131
BLWP4 48L ADP LP850 5353 40 134
BLWP4 60L ADP LP830 6059 49 123
BLWP4 60L ADP LP835 6273 49 127
BLWP4 60L ADP LP840 6373 49 129
BLWP4 60L ADP LP850 6555 49 133
BLWP4 72L ADP LP830 7088 59 121
BLWP4 72L ADP LP835 7338 59 125
BLWP4 72L ADP LP840 7455 59 127
BLWP4 72L ADP LP850 7668 59 131
BLWP4 85L ADP LP830 7972 68 117
BLWP4 85L ADP LP835 8253 68 121
BLWP4 85L ADP LP840 8385 68 123
BLWP4 85L ADP LP850 8624 68 127
BLWP4 100L ADP LP830 9316 85 110
BLWP4 100L ADP LP835 9645 85 114
BLWP4 100L ADP LP840 9799 85 116
BLWP4 100L ADP LP850 10079 85 119
BLWP
Commercial Indoor: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2018-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/13/21
Page 11 of 13
BLWP Low Profile LED Wraparound
BLWP PERFORMANCE DATA (continued)
Lumen Package Lumens Input Watts LPW
BLWP2 8LHE ADP LP830 851 8 106
BLWP2 8LHE ADP LP835 881 8 110
BLWP2 8LHE ADP LP840 895 8 112
BLWP2 8LHE ADP LP850 921 8 115
BLWP2 20LHE ADP LP830 1932 16 120
BLWP2 20LHE ADP LP835 2000 16 125
BLWP2 20LHE ADP LP840 2032 16 127
BLWP2 20LHE ADP LP850 2090 16 130
BLWP2 33LHE ADP LP830 3272 26 127
BLWP2 33LHE ADP LP835 3388 26 131
BLWP2 33LHE ADP LP840 3442 26 133
BLWP2 33LHE ADP LP850 3540 26 137
BLWP2 40LHE ADP LP830 3991 32 126
BLWP2 40LHE ADP LP835 4132 32 130
BLWP2 40LHE ADP LP840 4198 32 131
BLWP2 40LHE ADP LP850 4318 32 136
BLWP2 48LHE ADP LP830 4881 39 126
BLWP2 48LHE ADP LP835 5053 39 130
BLWP2 48LHE ADP LP840 5134 39 132
BLWP2 48LHE ADP LP850 5280 39 136
BLWP4 15LHE ADP LP830 1375 11 125
BLWP4 15LHE ADP LP835 1424 11 129
BLWP4 15LHE ADP LP840 1447 11 132
BLWP4 15LHE ADP LP850 1488 11 135
BLWP4 20LHE ADP LP830 1985 16 124
BLWP4 20LHE ADP LP835 2055 16 128
BLWP4 20LHE ADP LP840 2088 16 131
BLWP4 20LHE ADP LP850 2147 16 134
BLWP4 30LHE ADP LP830 3012 24 126
BLWP4 30LHE ADP LP835 3118 24 131
BLWP4 30LHE ADP LP840 3168 24 133
BLWP4 30LHE ADP LP850 3258 24 137
BLWP4 40LHE ADP LP830 4181 33 127
BLWP4 40LHE ADP LP835 4329 33 132
BLWP4 40LHE ADP LP840 4398 33 134
BLWP4 40LHE ADP LP850 4524 33 137
BLWP4 48LHE ADP LP830 5033 39 130
BLWP4 48LHE ADP LP835 5211 39 135
BLWP4 48LHE ADP LP840 5294 39 137
BLWP4 48LHE ADP LP850 5445 39 141
BLWP4 60LHE ADP LP830 6280 47 133
BLWP4 60LHE ADP LP835 6502 47 137
BLWP4 60LHE ADP LP840 6606 47 140
BLWP4 60LHE ADP LP850 6795 47 144
BLWP4 72LHE ADP LP830 7303 56 129
BLWP4 72LHE ADP LP835 7561 56 134
BLWP4 72LHE ADP LP840 7682 56 136
BLWP4 72LHE ADP LP850 7901 56 140
BLWP4 85LHE ADP LP830 8567 69 124
BLWP4 85LHE ADP LP835 8869 69 129
BLWP4 85LHE ADP LP840 9011 69 131
BLWP4 85LHE ADP LP850 9268 69 134
BLWP4 100LHE ADP LP830 9898 80 124
BLWP4 100LHE ADP LP835 10247 80 128
BLWP4 100LHE ADP LP840 10411 80 130
BLWP4 100LHE ADP LP850 10708 80 134
Notes
24 For ADP lens only, for additional lens options refer to photometry on www.acuitybrands.com.
BLWP
Commercial Indoor: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2018-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/13/21
Page 12 of 13
BLWP Low Profile LED Wraparound
BLWP8 PERFORMANCE DATA BLWP8 HE PERFORMANCE DATA
Lumen Package Lumens Input Watts LPW Lumen Package Lumens Input Watts LPW
BLWP8 40L ADP LP830 3953 30 131 BLWP8 40LHE ADP LP830 3953 30 133
BLWP8 40L ADP LP835 4113 30 136 BLWP8 40LHE ADP LP835 4113 30 139
BLWP8 40L ADP LP840 4107 30 136 BLWP8 40LHE ADP LP840 4160 30 140
BLWP8 40L ADP LP850 4246 30 141 BLWP8 40LHE ADP LP850 4246 30 143
BLWP8 60L ADP LP830 5799 47 122 BLWP8 60LHE ADP LP830 5942 46 128
BLWP8 60L ADP LP835 6034 47 127 BLWP8 60LHE ADP LP835 6183 46 133
BLWP8 60L ADP LP840 6107 47 130 BLWP8 60LHE ADP LP840 6254 46 135
BLWP8 60L ADP LP850 6229 47 132 BLWP8 60LHE ADP LP850 6383 46 137
BLWP8 80L ADP LP830 7643 63 121 BLWP8 80LHE ADP LP830 7820 59 132
BLWP8 80L ADP LP835 7952 63 126 BLWP8 80LHE ADP LP835 8136 59 137
BLWP8 80L ADP LP840 8035 63 127 BLWP8 80LHE ADP LP840 8230 59 139
BLWP8 80L ADP LP850 8210 63 130 BLWP8 80LHE ADP LP850 8400 59 142
BLWP8 100L ADP LP830 9628 82 118 BLWP8 100LHE ADP LP830 9723 74 132
BLWP8 100L ADP LP835 10017 82 123 BLWP8 100LHE ADP LP835 10117 74 138
BLWP8 100L ADP LP840 10133 82 124 BLWP8 100LHE ADP LP840 10233 74 139
BLWP8 100L ADP LP850 10342 82 127 BLWP8 100LHE ADP LP850 10445 74 142
BLWP8 140L ADP LP830 13265 120 111 BLWP8 140LHE ADP LP830 13491 104 129
BLWP8 140L ADP LP835 13802 120 115 BLWP8 140LHE ADP LP835 14037 104 135
BLWP8 140L ADP LP840 13961 120 116 BLWP8 140LHE ADP LP840 14198 104 136
BLWP8 140L ADP LP850 14249 120 119 BLWP8 140LHE ADP LP850 14492 104 139
BLWP8 180L ADP LP830 17781 147 121 BLWP8 180LHE ADP LP830 17245 130 133
BLWP8 180L ADP LP835 18501 147 126 BLWP8 180LHE ADP LP835 17943 130 138
BLWP8 180L ADP LP840 18714 147 127 BLWP8 180LHE ADP LP840 18150 130 140
BLWP8 180L ADP LP850 19101 147 130 BLWP8 180LHE ADP LP850 18525 130 143
BLWP8 200L ADP LP830 18563 156 119 BLWP8 200LHE ADP LP830 19587 144 136
BLWP8 200L ADP LP835 19314 156 124 BLWP8 200LHE ADP LP835 20380 144 141
BLWP8 200L ADP LP840 19537 156 125 BLWP8 200LHE ADP LP840 20615 144 143
BLWP8 200L ADP LP850 19941 156 128 BLWP8 200LHE ADP LP850 21041 144 146
Notes
24 For ADP lens only, for additional lens options refer to photometry on www.acuitybrands.com.
BLWP
Commercial Indoor: One Lithonia Way, Conyers, GA 30012 Phone: 800-705-SERV (7378) www.lithonia.com © 2018-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 04/13/21
Page 13 of 13
8.11 Lighting Type WL, SPEC 2.2 Luminaires
Type
Buy American
Hit the Tab key or mouse over the page to see all interactive elements.
Introduction
The WDGE LED family is designed to meet
specifier’s every wall-mounted lighting need in
D2 a widely accepted shape that blends with any
Specifications architecture. The clean rectilinear design comes
in four sizes with lumen packages ranging from
Depth (D1): 5.5"
1,200 to 25,000 lumens, providing true site-wide
Depth (D2): 1.5"
H solution.
Height: 8"
WDGE1 delivers up to 2,000 lumens with a soft,
Width: 9"
non-pixelated light source, creating a visually
Weight:
(without options)
9 lbs comfortable environment. The compact size of
W D1 WDGE1, with its integrated emergency battery
backup option, makes it an ideal over-the-door
wall-mounted lighting solution.
Ordering Information EXAMPLE: WDGE1 LED P2 40K 80CRI VF MVOLT SRM PE DDBXD
WDGE1 LED P1 27K 2700K 80CRI VF Visual comfort forward throw MVOLT Shipped included
P2 30K 3000K 90CRI VW Visual comfort wide 347 2 SRM Surface mounting bracket
35K 3500K ICW Indirect Canopy/Ceiling Washer bracket (dry/damp locations only)5
40K 4000K Shipped separately
50K 1 5000K AWS 3/8inch Architectural wall spacer
PBBW Surface-mounted back box (top, left, right conduit entry) Use when
there is no junction box available.
Options Finish
E4WH 3 Emergency battery backup, Certified in CA Title 20 MAEDBS (4W, 0°C min) DDBXD Dark bronze DDBTXD Textured dark bronze
PE 4 Photocell, Button Type DBLXD Black DBLBXD Textured black
DS Dual switching ( comes with 2 drivers and 2 light engines; see page 3 for details) DNAXD Natural aluminum DNATXD Textured natural aluminum
DMG 0-10V dimming wires pulled outside fixture (for use with an external control, ordered separately) DWHXD White DWHGXD Textured white
BCE Bottom conduit entry for back box (PBBW). Total of 4 entry points. DSSXD Sandstone DSSTXD Textured sandstone
Accessories NOTES
Ordered and shipped separately. 1 50K not available in 90CRI. 4 PE not available with DS.
WDGEAWS DDBXD U WDGE 3/8inch Architectural Wall Spacer (specify finish) 2 347V not available with 5 Not qualified for DLC. Not
E4WH, DS or PE. available with E4WH.
WDGE1PBBW DDBXD U WDGE1 surface-mounted back box (specify finish) 3 E4WH not available with
PE or DS.
One Lithonia Way • Conyers, Georgia 30012 • Phone: 1-800-705-SERV (7378) • www.lithonia.com WDGE1 LED
COMMERCIAL OUTDOOR
© 2019-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 03/17/21
Performance Data
Lumen Output
Lumen values are from photometric tests performed in accordance with IESNA LM-79-08. Data is considered to be representative of the configurations shown,
within the tolerances allowed by Lighting Facts. Contact factory for performance data on any configurations not shown here.
Performance System 27K (2700K, 80 CRI) 30K (3000K, 80 CRI) 35K (3500K, 80 CRI) 40K (4000K, 80 CRI) 50K (5000K, 80 CRI)
Dist. Type
Package Watts Lumens LPW B U G Lumens LPW B U G Lumens LPW B U G Lumens LPW B U G Lumens LPW B U G
VF 1,120 112 0 0 0 1,161 116 0 0 0 1,194 119 0 0 0 1,227 123 0 0 0 1,235 123 0 0 0
P1 10W
VW 1,122 112 0 0 0 1,163 116 0 0 0 1,196 120 0 0 0 1,229 123 0 0 0 1,237 124 0 0 0
VF 1,806 120 1 0 0 1,872 125 1 0 0 1,925 128 1 0 0 1,978 132 1 0 0 1,992 133 1 0 0
P2 15W
VW 1,809 120 1 0 0 1,876 125 1 0 0 1,929 128 1 0 0 1,982 132 1 0 0 1,996 133 1 0 0
One Lithonia Way • Conyers, Georgia 30012 • Phone: 1-800-705-SERV (7378) • www.lithonia.com WDGE1 LED
COMMERCIAL OUTDOOR
© 2019-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 03/17/21
Photometric Diagrams To see complete photometric reports or download .ies files for this product, visit the Lithonia Lighting WDGE LED homepage.
Tested in accordance with IESNA LM-79 and LM-80 standards.
LEGEND
0.25 fc
0.5 fc
1.0 fc
3.0 fc
MH = 8ft
Grid = 8ft x 8ft
WDGE1 LED P2 40K 80CRI VW WDGE1 LED P2 40K 80CRI VF
8' MH
8'
15'
1.0 fc avg.
0.1 fc min.
26'
Grid = 10ft x 10ft
Driver1 Driver2
One Lithonia Way • Conyers, Georgia 30012 • Phone: 1-800-705-SERV (7378) • www.lithonia.com WDGE1 LED
COMMERCIAL OUTDOOR
© 2019-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 03/17/21
Mounting, Options & Accessories
One Lithonia Way • Conyers, Georgia 30012 • Phone: 1-800-705-SERV (7378) • www.lithonia.com WDGE1 LED
COMMERCIAL OUTDOOR
© 2019-2021 Acuity Brands Lighting, Inc. All rights reserved. Rev. 03/17/21
Nambe of Product Brand Code Item
Light Fixture for Installation Commercial Electric TM 54194201
under cabinet SKU#1003580970
PRODUCT SPECIFICATIONS
1.71in Power 11 W
SURfACE MOUNT
PRODUCT DESCRIPTION
These photocontrols install on standard outdoor light fixtures and electrical boxes with 1/2"-14 NPSM thread or 7/8" knock-out
holes for dusk-to-dawn ON/OFF control of outdoor lighting.
FEATURES
Mechanical bimetal switch with Cadmium Sulfide photocell
Delay feature prevents unwanted OFF switching
Gray plastic housing
1/2"-14 NPSM threaded stem
Washer gasket and locking nut included
#18 AWG, 9" wire leads
APPLICATIONS
Outdoor Lighting Control
TECHNICAL DATA
General
Model Number K4121C
Description Stem Mount Thermal Photocontrol, 120 V
Brand Intermatic
Control Specifications
Sensor Time Delay 30 sec to 90 sec
Fail Mode ON
Activation On 1 to 5 fc
Activation Off 3 to 15 fc
Dimensions
Product Height (in) 3
Technical specifications and other information are subject to change without notice. Images can vary from original. © 04/20/2021 1/3
Photocontrol - K4121C
Material Specifications
Cover Color Gray
Load Ratings
Magnetic Ballast Range(s) 8.3 A, 1000 VA
Electrical Specifications
Wiring Option Wire leads
Packaging
Shipping Weight (lbs) 0.21
Environmental Specifications
Temperature (operation) -40°C..70°C
UL Standard UL773
Technical specifications and other information are subject to change without notice. Images can vary from original. © 04/20/2021 2/3
Photocontrol - K4121C
ACCESSORIES
Technical specifications and other information are subject to change without notice. Images can vary from original. © 04/20/2021 3/3
Photo Controls
Stem Mounting, Thermal Type – K4100 Series
This series features single and multivolt models in both stem mount and stem mount with a swivel. All models
are equipped with a light level slide adjustment and provide a 1/2"-14 threaded stem. A washer gasket and
locking nut are packaged with each photo control. Models with “M” suffix have heavy duty die cast housings.
Model K4251 and K4253 have photo eye located on top and are designed for spot/flood type fixtures.
Size – K4100 Series - 1-9/16" (4.0 cm) Square, 3" (7.6 cm) Long;
K4200 Series - 1/2"-14 threaded swivel, 1-9/16" (4.0 cm) Square, 5-1/2" (14.0 cm) Long;
Model K4236 - 5-3/4" (14.6 cm) High, 3" (7.6 cm) Diameter.
K4423M
K4251
22 WEATHERPROOF • ENERGY CONTROLS • PROFESSIONAL LIGHTING • POOL & SPA • SURGE PROTECTION • CONSUMER
K4200 Series
Photo Controls
Project:
Location:
K4200 Series Product Type:
Stem and Swivel Mounting Contact/Phone:
The K4200 Series Photo Controls feature stem and swivel mounting,
with thermal-type controls. Thermal-type photo controls, which are Model #:
available in single or multi-voltage models, provide dusk-to-dawn
lighting control and a delay action, which eliminates loads switching
OFF due to car headlights, and lightning. The thermal-type controls
feature a cadmium sulfide photocell and a sonic-welded polycarbonate
case and lens to seal out moisture. The design utilizes a dual
temperature compensating bi-metal and composite resistor for reliable
long life operation over ambient temperature extremes.
Features
• Cadmium sulfide photocell
• Sonic welded polycarbonate housing and lens to seal out moisture
• Delay action eliminates load switching OFF due to car
headlights, and lightning
• 6" leads
• K4251 and K4253 Models are designed for spot/flood type fixtures
• Controls come with a washer gasket and locking nut
K4235, K4236
Energy Controls
K4200 Series
Tungsten Tungsten Ballast
Model Number Ballast (VA) Volts AC Agency Listing
(Watts) (Amps) (Amps)
K4221C 1800 1000 15 8.3 120 UL
K4223C** 3100-4150 1700-2300 15 8.3 208-277 CSA, C/US
K4227 5205 2880 15 8.3 347 CSA, C/US
K4235* 7200 4000 15 8.3 480
K4236C 1800-4150 1000-2300 15 8.3 120-277 UL, CSA
K4251 1800 1000 15 8.3 120 CSA, C/US
K4253** 3100-4150 1700-2300 15 8.3 208-277 CSA, C/US
*Not Agency certified
**Title 20 Listed Model
Specification
The photo control shall provide automatic switching for outdoor lighting loads. The control shall be a thermal design with
built-in delay to ensure that the controlled lighting does not switch off due to ambient light or light striking the photocell.
The photo control shall have a rating of 1800 Watts and 15 Amps tungsten and 1800 Watts and 8.3 Amps ballast based
on agency testing at 50% power factor for ballast loads. The photo control shall provide switching for nominal voltage
fixtures of 120 Volts ±10% to accommodate fluctuations in supply voltage. The photo control mounting shall be the stem
and swivel type with all necessary mounting hardware and instructions. The photo control housing shall be constructed
of high impact polycarbonate. The photo control components shall consist of a resistor, dual temperature compensating
bi-metal blades, snap action contact blades, chemically treated/polymer encapsulated cadmium sulfide photocell and
silver alloy contacts to ensure reliable operation. The photo control shall be 100% factory tested for function within
specified light levels. The photo control shall be agency certified (unless otherwise noted) and tested accordingly. The
photo control shall function over temperature range of -40°F to 158°F (-40°C to 70°C). The photo control shall be
Intermatic model K4221C(See Model Numbers Listed).
Diagrams
Photo Control
Nut and
neoprene
washer
1/2" nipple
Photo Control
Energy Controls
8.13 Lighting Contactor
GE Lighting Contactors
Coil
30A 60A 100A 200A 300A
Options Voltage Catalog List Price Catalog List Price Catalog List Price Catalog List Price Catalog List Price
Number Adder, Number Adder, Number Adder, Number Adder, Number Adder,
Digits GO-10MB Digits GO-10MB Digits GO-1 0MB Digits GO-10MB Digits GO-1 0MB
24 24D $165.00 24D $165.00 24D $165.00 24D $165.00 24D $165.00
120 02D 165.00 02D 165.00 02D 165.00 02D 165.00 02D 165.00
2 Control Circuit Fuses
208 23D 165.00 23D 165.00 23D 165.00 23D 165.00 23D 165.00
240 030 165.00 03D 165.00 03D 165.00 03D 165.00 03D 165.00
277 13D 165.00 13D 165.00 130 165.00 130 165.00 13D 165.00
480 040 165.00 040 165.00 040 165.00 040 165.00 040 165.00
208 82S 202.00 82S 275.00 62S 420.00 48S 510.00 40S 578.00
CRT 1 Secondary
240 03S 202.00 03S 275.00 03S 420.00 03S 510.00 03S 578.00
277 61S 202.00 61 S 275.00 61S 420.00 61 S 510.00 61S 578.00
120 Volt Secondary
480 04 S 202.00 £4S 275.00 04S 420.00 04 S 510.00 04S 578.00
CPT 1 Secondary 208 82T 367.00 827 440.00 62T 585.00 48T 675.00 40T 743.00
Fuse and 2 240 03T 367.00 031 440.00 03T 585.00 03T 675.00 03T 743.00
Primary Fuses 277 61T 367.00 61 T 440.00 61T 585.00 -61T 675.00 61T 743.00
1 20 Volt Secondary 480 04T 367.00 04T 440.00 04T 585.00 04T 675.00 04T 743.00
6-10 1999 Issue Prices and data subject to change without notice
U-
GE Lighting Contactors
GE Fastrac™ Program items are printed in red type. CR360L Electrically Held Contactors
Application 600 Volts Maximum 50/60 Hertz
300 Amperes Maximum
These CR360L magnetic
electrically held lighting
contactors are specifically Schematic Diagram
rated for 30-, 60-, 100-, 200-,
and 300-ampere tungsten-,
fluorescent-, mercury arc-, and
sodium-lamp loads. They are FOR
available open or enclosed. I [CONNECTIONS
| REFER TO
' FIGURE A
They may be controlled by a I I FIGURE B
I j OR
remote push button, toggle, or I I FIGURE C
Open 60-Amp Electrically ^elector switch or other pilot ( IF USED)
Held Lighting Contactor device.
WIRE "A1
Ratings
Open or enclosed ratings are 30-, 60-, 100-, 200-, and 300-ampere,
ac full-load current.
Maximum AC Voltage Rating ON-OFF
__L. BLACK
1
Lighting Load Line Load T f WHITE 2
Tungsten 480 480 RED
Ballast: Fluorescent Mercury, Sodium, e.g. 600 600
FIGURE A
PUSH BUTTON
DC Tungsten Rating
Contactor Size, No. Poles in Series for: M-LINE CONTACTOR
Continuous Ampere Rating 1 2 5 V Maximum 250V Maximum I - INDICATING LIGHT
D - MAINTAINING CONTACT PILOT DEVICE
30 2 3
60 2 4 Typical Schematic Diagram For
100-300 2 2
CR360L Lighting Contactor
Ordering Directions
Order by complete catalog number. Select rating and enclosure from Table O. Select coil voltage from Table O. For additionally
modified enclosed forms, use Tables ©, O, O, and 0. Note: Coils will be connected line-to-line unless otherwise specified. Complete
Catalog Number must contain 15 digits.
O OOF© 0 o e +o $
CR360L I I +o
#NO
| |
Pilot Pilot Aux.
$
Enclosure Control Circuit Option
Poles Device Light Contacts
+© $
CR360L 312 02A D A Z +o $
+o $
Example: 30-ampere, three-pole lighting contactor in a NEMA Type 1 enclosure with a 480/120 Volt $
CPT, 2 primary, 1 secondary fuse, standard-duty on/off push button with holding interlock.
Prices and data subject to change without notice 1999 Issue 6-9
9. Division 27- Communications
Content
9.1 Jack Connector, SPEC 2.5.1
1-800-Belden1
General Description:
CAT6+ Modular Jack, RJ45, KeyConnect style, Blue (TIA 606)
Usage (Overall)
Suitable Applications: IBDN System 2400, 3600 and 4800, TIA Category 6+, ISO Class E, 1000 BASE-T
Related Parts: Compatible with KeyConnect Faceplates, Adapters, Boxes and Patch Panels
Materials
Materials:
Description Type Material
Front Connection Lead Frame Copper Allow with 50u inch Gold over Nickel
Rear Connection IDC Copper Allow with Nickel Plating
Connector Body Plastic - UL940V-0
Color
Color: Blue (TIA 606)
Wiring Scheme
Wiring Scheme: T568A/B
Weight
Weight: 0.014 lbs.
Included Parts
Included Parts: 1 T-Bar
Packaging
Packaging: Individually packaged in a plastic bag. Standard pack of 50 units.
Page 1 of 3 10-19-2017
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
Suitability
Suitability - Indoor: Yes - Indoor
Notes (Overall)
Notes: Please see Installation Guide PX103329
Product Family
Part Number List:
Item Number Color
AX101318 Gray
AX101319 Almond
AX101320 Elec. White
AX101321 Black
AX101322 Orange (TIA 606)
AX101323 Red (TIA 606)
AX101324 Yellow (TIA 606)
Page 2 of 3 10-19-2017
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
Page 3 of 3 10-19-2017
9.2 Patch Panel, SPEC 2.4.4
NEW-27777XX
Ordering Information
NEW-980634X
Features:
Jacket
Standards ANSI/EIA/TIA 568-C.2 &
ISO/IEC 11801, IEEE 802.3af, UL
Insulation 568.C.2 - Local Area Network Cable
Verified for Transmission
Performance, UL ANSI 444 -
Communication Cables
Conductor CMR Rated
4- Balanced Pairs, 23 AWG
Unshielded Twisted-pair construction
Rip Cord Applications: Voice, Fax, T1, ISDN,
10BASE-T, 100BASE-TX,
100BASE-T4, 100VG-AnyLan,
ATM-25, ATM-51, ATM-155,
1000BASE-T
High density twisted pairs (up to 51.7
– 65.2 per inch)
Construction of Balanced Pair in
differential mode
Size 23AWG
Material HD-PE
Blue / White-Blue
Brown / White-Brown
Min.: 0.53mm
Thickness
Max. Avg: 0.57mm
ANSI/EIA/TIA 568-C.2 & ISO/IEC 11801, IEEE 802.3af, UL 568.C.2 - Local Area
Standards: Network Cable Verified for Transmission Performance, UL ANSI 444 - Communication
Cables
Electrical Characteristics:
Ordering Information:
Part Number Description
NEW-9806341 CAT-6 CMR 23AWG 4-pair UTP Cable 1000ft, Gray
NEW-9806342 CAT-6 CMR 23AWG 4-pair UTP Cable 1000ft, Blue
PRODUCT SPECIFICATIONS
41080-xxP
APPLICATION FEATURES
41080-xxP
Single-Gang QuickPort Wallplates accept QuickPort • Color-matched wallplate screws
connectors to support multimedia applications with 1, • Fits within minimum rectangular NEMA openings and
2, 3, 4, or 6 ports. Use where a one-piece, single-gang, accommodates low-voltage box eliminators for a flush mount
economical flush-mount housing is desired. Available in • Compatible with all individual QuickPort connectors
six colors (white, light almond, ivory, grey, brown, and • Individual port configurability allows specification flexibility
black) with color-matched screws. • Narrow module width allows high port density in a small area
DESIGN CONSIDERATIONS
• Fits single-gang back boxes, or four-square boxes with
appropriate user-provided reducer
• Put blanks in unused ports for future expansion
• Specify port identification method (colored modules, designation
labels, and custom silk-screening available/to identify ports,
use different colored connectors for each application or Leviton
pre-printed Port Designation Labels (41080-LEB)
STANDARDS COMPLIANCE
• cULus Listed (UL 1863 & CAN/CSA-C22.2 No. 182.4)
• ANSI/TIA-568-C.0
PHYSICAL SPECIFICATIONS
SPECIFICATION Dimensions: See page two
The wallplate housing shall be a one-piece, single-gang Materials: High-impact, durable, fire-retardant plastic rated
flush-mount style that fits standard NEMA openings, UL 94V-0
or four-square boxes with reducer. It should provide 1, Capacity: Available in 1-, 2-, 3-, 4-, and 6-port versions
2, 3, 4, or 6 ports. Must be able to accept all Leviton Mounting: Color-matched screws
QuickPort connectors. It must be made of high-
impact, fire-retardant plastic rated UL 94V-0, and be COUNTRY OF ORIGIN
cULus Listed, and compliant with ANSI/TIA-568-C.0 USA
specifications. The wallplate shall accommodate low-
voltage box eliminators for a flush mount. WARRANTY INFORMATION
For a copy of Leviton product warranties, visit
www.leviton.com/warranty.
Page 1 of 2
tel 1
-800-824-3005
Europe India / SAARC Mexico Middle East & Africa South Korea
tel +1-425-486-2222
T +33.6.8869.1380 T +971.4.886.4722 T +52.55.5082.1040 T +971.4.886.4722 T +82.2.3273.9963
appeng@leviton.com
E infoeurope@leviton.com E infoindia@leviton.com E lsamarketing@leviton.com E lmeinfo@leviton.com E infokorea@leviton.com
www.leviton.com
Copyright © 2015 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice. Revised July 2015
PRODUCT SPECIFICATIONS
41080-xxP
ELECTRONIC FILES
For CAD files, typical specs, or technical drawings (.DXF, .DWG), visit www.leviton.com.
41080-xxP
4.53"
4.53 4.53"
4.53 4.53"
4.53
2.77"
2.77 2.77"
2.77 2.77"
2.77
.25" .25" .25"
.45"
.45 .45"
.45 .45"
.45
41080-4xP 41080-6xP
4.53"
4.53 4.53"
4.53
2.77"
2.77 2.77"
2.77
.25" .25"
.45"
.45 .45"
.45
PART NUMBERS
Description WHITE LT. ALMOND IVORY GREY BROWN BLACK
® 41080-1WP 41080-1TP 41080-1IP 41080-1GP 41080-1BP 41080-1EP
Single-Gang QuickPort Wallplate, 1 Port
Single-Gang QuickPort Wallplate, 2 Ports 41080-2WP 41080-2TP 41080-2IP 41080-2GP 41080-2BP 41080-2EP
Single-Gang QuickPort Wallplate, 3 Ports 41080-3WP 41080-3TP 41080-3IP 41080-3GP 41080-3BP 41080-3EP
Single-Gang QuickPort Wallplate, 4 Ports 41080-4WP 41080-4TP 41080-4IP 41080-4GP 41080-4BP 41080-4EP
Single-Gang QuickPort Wallplate, 6 Ports 41080-6WP 41080-6TP 41080-6IP 41080-6GP 41080-6BP 41080-6EP
tel 1
-800-824-3005 Europe India / SAARC Mexico Middle East & Africa South Korea
tel +1-425-486-2222 T +33.6.8869.1380 T +971.4.886.4722 T +52.55.5082.1040 T +971.4.886.4722 T +82.2.3273.9963
appeng@leviton.com E infoeurope@leviton.com E infoindia@leviton.com E lsamarketing@leviton.com E lmeinfo@leviton.com E infokorea@leviton.com
www.leviton.com
Copyright © 2015 Leviton Manufacturing Co., Inc. All rights reserved. Subject to change without notice. Revised July 2015
9.5 Coaxial Module Connector, SPEC 2.1.2
ANSI/TIA-568-C Y UL 1863
9.6 Coaxial Cable, SPEC 2.1.1
General
Braid Coverage 60 % + 40 %
Cable Type Series 6
Packaging Type Box
Construction Materials
Jacket Material PVC
Black A6QS-BVV-BOX
Jacket Color Neutral A6QS-BVVN-BOX
White A6QS-BVVW-BOX
Bonded APA foil + 60 % aluminum braid
Shield Materials + non-bonded APA foil + 40 % aluminum braid
Dielectric Material Foam PE
Inner Conductor Material Copper-clad steel wire
Dimensions
Cable Length 1000 ft 305 m
Diameter Over Jacket 0.295 in 7.49 mm
Jacket Wall Thickness 0.030 in 0.76 mm
Diameter Over Tape 0.186 in 4.72 mm
Diameter Over Dielectric 0.177 in 4.49 mm
Diameter Inner Conductor 0.0403 in 1.024 mm
Length 20.5 in 520 mm
Box Width 10.6 in 270 mm
Height 20.5 in 520 mm
Total Weight 39 lbs 17.5 kg
Electrical Specifications
Operating Frequency Band 5 to 1525 MHz
Impedance 75 Ohms
Velocity 85 %
DC Loop Resistance 36.9 Ohms / kft 121 Ohms / km
Dielectric Strength 1500 V
Jacket Spark Test Voltage (rms) 2500 V
Attenuation @ 68°F (20 °C)
Freq. (MHz) db / 100 ft db / 100 m Freq. (MHz) db / 100 ft dB / 100 m
5 0.58 1.90 500 4.66 15.29
55 1.60 5.25 550 4.90 16.08
211 3.05 10.00 600 5.10 16.73
250 3.30 10.82 750 5.65 18.54
270 3.37 11.04 870 6.11 20.04
300 3.55 11.64 1000 6.55 21.49
330 3.74 12.26 1125 6.95 22.80
350 3.85 12.63 1218 7.21 23.66
400 4.15 13.61 1525 8.09 26.54
450 4.40 14.43
Standards Conformance
RoHS
Applicable SCTE 74 2011
UL / ETL Listings CATV, CM, NEC 830 BM
Specifications subject to change without notice. Visit www.pctintl.com/patents for a list of USA and
international patents. 1PreP, Innovation for the Last Mile, MoCSY, MOGO, Copper Guard, Corrosion Guard, PCT,
PCT International, Predator, TRITON and Z-Wire are trademarks, registered and otherwise, of PCT International, Inc.
Description
PPC EX6 PLUS Universal Compression Connectors for RG6 series cable are up to SCTE standards providing a
secure watertight connection and excellent pull strength with effortless installation.
Installers are faced with the problem of identifying old unmarked 60% through Quad Shield Series 6 cable, and
having to guess which connector is the best match. This results in unnecessary service calls due to the use of
the wrong connector/cable match. The unique patented design of the EX® body achieves true universality on
60% through Quad Shield for PE, and PVC jackets for RG6 series cable.
Specifications
• Bandwidth: 0 MHz to 3 GHz
• Impedance: 75 Ohms
• Return Loss: Minimum -30 dB to 3 GHz
• Insertion Loss: Less than .10 dB to 3 GHz
• Operating Voltage: 90 V (at 60 Hz continuous AC)
• Operating Temperature: -40°F to +140°F ( -40°C to +60°C)
• Cable Retention: 45 lbs (20.41 kg) minimum
• Meets or exceeds all SCTE Specifications
PPC-EX6PLUS
Multicom, Inc.
Ph: 407-331-7779
www.multicominc.com Toll Free: 800-423-2594
Fax: 407-339-0204
Email: multicom@multicominc.com
Specifications subject to change without notice © Multicom, Inc. 2017
Multicom and the Multicom logo are registered trademarks of Multicom, Inc.
10. Division 28 31 76- Fire Alarm Control and Mass
Notification Panel
Content
10.1 Fire Alarm Control Unit and Mass Notification Control Unit SPEC 2.11
- Silent Knight Fire Alarm Control and Mass Notification Panel 6820 EVS
-Ditek Voice, Data and Signaling Circuit Modular Surge Protection DTK-
2MHLP
-Wiring 2x16 AWG Unshielded FPLR for Speaker and SLC CON 666581
This system meets NFPA requirements for operation at 0-49º C/ This system contains static-sensitive components. Always
32-120º F and at a relative humidity 93% ± 2% RH (non-condens- ground yourself with a proper wrist strap before handling any cir-
ing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the sys- cuits so that static charges are removed from the body. Use static
tem's standby batteries and the electronic components may be suppressive packaging to protect electronic assemblies removed
adversely affected by extreme temperature ranges and humidity. from the unit.
Therefore, it is recommended that this system and its peripherals Units with a touchscreen display should be cleaned with a dry,
be installed in an environment with a normal room temperature of clean, lint free/microfiber cloth. If additional cleaning is required,
15-27º C/60-80º F. apply a small amount of Isopropyl alcohol to the cloth and wipe
Verify that wire sizes are adequate for all initiating and indicating clean. Do not use detergents, solvents, or water for cleaning. Do
device loops. Most devices cannot tolerate more than a 10% I.R. not spray liquid directly onto the display.
drop from the specified device voltage. Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
Precau-D2-11-2017
FCC Warning
WARNING: This equipment generates, uses, and can radi- Canadian Requirements
ate radio frequency energy and if not installed and used in This digital apparatus does not exceed the Class A limits for
accordance with the instruction manual may cause interfer- radiation noise emissions from digital apparatus set out in
ence to radio communications. It has been tested and found the Radio Interference Regulations of the Canadian Depart-
to comply with the limits for class A computing devices pur- ment of Communications.
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such Le present appareil numerique n'emet pas de bruits radio-
interference when devices are operated in a commercial electriques depassant les limites applicables aux appareils
environment. Operation of this equipment in a residential numeriques de la classe A prescrites dans le Reglement sur
area is likely to cause interference, in which case the user le brouillage radioelectrique edicte par le ministere des
will be required to correct the interference at his or her own Communications du Canada.
expense.
eVance®, Honeywell®, Silent Knight®, and SWIFT® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks
of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation.
©2020. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
NOTE: The system can support a maximum of 16 Intelligent Power modules, either the 5895XL or 5496, in any combination.
Term Description
SLC Signaling line circuit
Module The term module is used for all hardware devices except for SLC addressable devices and notification
appliances. This includes the 6820 or 6820EVS panel itself and the built-in power supply. It also refers
to any (optional) 5815XL or 6815 SLC expansion modules.
Input Point An addressable sensing device, such as a smoke or heat detector or a contact monitor device.
Input Zone A protected area made up of input points.
Output Point A notification point or circuit for notification appliances. Relay circuits and auxiliary power circuits are
(or “Output Circuit”) also considered output points.
Output Group (OPG) A group of output points. Operating characteristics are common to all output points in the group.
Output (or “Cadence”) Pattern The pattern that the output will use, for example, Constant, March Code, ANSI 3.41. Applies to zones
and special system events. See “Cadence Patterns” on page 181 for additional information.
Mapping Mapping is the process of specifying which outputs are activated when certain events occur in the
system. Section “Mapping Overview” on page 89 explains mapping in detail.
EVS Emergency Voice System.
Common Communication Link Up to 17 panels can be linked. Consist of any combination of 17 panels of these model numbers:6700,
6808, 6820, or 6820EVS. For reporting purposes only. Not a peer-to-peer networked system.
SWIFT Smart Wireless Integrated Fire Technology
WARNING: This Device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions:
! (1) This device may not cause radio interference, and
(2) This device must accept any interference received, including interference that may cause undesired operation
CAUTION: To ensure proper operation, this equipment must be installed according to the enclosed installation instructions. To verify that
! the equipment is operating properly and can successfully report an alarm, this equipment must be tested immediately after installation, and
periodically thereafter, according to the enclosed test instructions.
CAUTION: IN ORDER FOR “ALARM DIALING EQUIPMENT” TO BE ABLE TO SEIZE THE PHONE LINE TO REPORT AN ALARM OR
OTHER EVENT WHEN OTHER CUSTOMER EQUIPMENT (TELEPHONE, ANSWERING SYSTEM, COMPUTER MODEM, ETC.)
CONNECTED TO THE SAME LINE IS IN USE, “ALARM DIALING EQUIPMENT” MUST BE CONNECTED TO A PROPERLY INSTALLED
RJ31X JACK. THE RJ31X JACK MUST BE CONNECTED IN SERIES WITH, AND AHEAD OF, ALL OTHER EQUIPMENT ATTACHED TO
THE SAME PHONE LINE. SERIES INSTALLATION OF AN RJ31X JACK IS DEPICTED IN THE FIGURE BELOW. IF YOU HAVE ANY
QUESTIONS CONCERNING THESE INSTRUCTIONS, YOU SHOULD CONSULT YOUR TELEPHONE COMPANY OR A QUALIFIED
INSTALLER ABOUT INSTALLING THE NECESSARY JACK AND ALARM DIALING EQUIPMENT FOR YOU.
Rating Earth
Terminal Label Description Ground
Voltage Current Faults
B SBUS IN Used for Class A installations 0Ω
A
+
-
B EXT. Comm Cellular Connection input 0Ω
A
+ 55 mA, 100 mA
-
N.C. RELAY 1 General Purpose Relay 1 24 VDC 2.5 A, resistive N/A
C
N.O.
N.C. RELAY 2 General Purpose Relay 2 24 VDC 2.5 A, resistive N/A
C
N.O.
N.C. TROUBLE Trouble Relay 24 VDC 2.5 A, resistive N/A
C
N.O.
SC- L1 SLC terminals 32 VDC 150 mA 0Ω
SC+ SLC OUT
AC Power
Input
NAC
Circuits
Flexput
Relays
Trouble
Relay
SBUS
In/Out
Standby Alarm
Device # of Devices Current per Device
Current Current
Addressable SLC Module
SK-MONITOR Standby/Alarm: .375 mA mA mA
SK-MINIMON mA mA
SK-PULL-SA mA mA
SK-PULL-DA mA mA
SK-MONITOR-2 Standby/Alarm: .75 mA mA mA
SK-MONITOR-10 Standby/Alarm: 3.5 mA mA mA
SLC Standby: .375 mA mA
Alarm: .375 mA mA
SK-CONTROL
Aux Pwr Standby: 1.7 mA mA
Alarm: 7 mA mA
SLC Standby: 2.25 mA mA
Alarm: 2.25 mA mA
SK-CONTROL-6
Aux Pwr Standby: 8 mA mA
Alarm: 20 mA mA
SK-RELAY Standby/Alarm: .255 mA mA mA
SK-RELAY-6 Standby/Alarm: 1.45 mA mA mA
Standby: 1.3 mA mA
SK-RELAYMON-2
Alarm: 24 mA mA
Aux Pwr Standby 12mA mA
SK-ZONE Alarm 90mA mA
SLC Standby/Alarm .27mA mA mA
Aux Pwr Standby 50mA mA
SK-ZONE-6 Alarm 270mA mA
SLC Standby/Alarm 2mA mA mA
SLC Modules
Standby: .5mA mA
Aux Pwr
B200SR-WH / IV Intelligent sounder base Alarm: 35mA mA
SLC Standby .3mA mA
Standby: .5mA mA
Aux Pwr
B200S-WH / IV Intelligent sounder base Alarm: (high vol) 35mA mA
SLC Standby .3mA mA
B200SR-LF-WH / IV Low Frequency sounder Standby: 1mA mA
Aux Pwr
base Alarm: 125mA mA
Standby .55mA mA
B200S-LF-WH / IV Low Frequency sounder Aux Pwr
Alarm (high vol) 140mA mA
base
SLC Standby .30mA mA
B224RB-WH / IV Relay Base Standby/Alarm: .5mA mA mA
RTS151/151 KEY Alarm: 7.5mA mA
RA100Z Alarm: 10mA mA
SLC Isolator Devices
SK-ISO (Isolator Module) (100 max/loop) Standby/Alarm: .45 mA mA mA
B224BI / IV Isolator Base Standby/Alarm: .5 mA mA mA
Accessories Modules
6815 SLC Expander (63 max.) Standby/Alarm: 78mA mA mA
(16 max.) Standby: 25mA mA
6860 Remote LCD Annunciator
Alarm: 50mA mA
Standby: 20mA mA
5860 Remote LCD Annunciator
Alarm: 25mA mA
Standby: 20mA mA
6855 Remote LCD Annunciator
Alarm: 25mA mA
5824 Serial/Parallel I/O Module (4 max.) Standby/Alarm: 45mA mA mA
Table 3.2 Current Draw Worksheet for SK SLC Devices (Continued)
Standby Alarm
Device # of Devices Current per Device
Current Current
5895XL Power Supply (16 max.) Standby/Alarm: 10mA mA mA
5496 NAC Expander Standby/Alarm: 10mA mA mA
5865-4 LED Annunciator (8 max.) Standby: 35mA mA
(with reset and silence switches) Alarm: 145mA mA
Standby: 35mA mA
5865-3 LED Annunciator
Alarm: 145mA mA
Standby: 35mA mA
5880 I/O Module
Alarm: 200mA mA
(32 max.) Standby: 0mA mA
5883 Relay Interface Alarm: 220mA mA
(22 mA per relay)
EVS-50W or EVS-125W Audio Amplifier (8 max.) Standby: 10mA mA
with/without EVS-CE4 Alarm: 10mA mA
(8 max.) Standby: 52mA mA
EVS-INT50W Internal Amplifier Alarm @ 25V: 275mA mA
Alarm @ 70V: 310mA mA
(1 max.) Standby: 70mA mA
EVS-VCM Voice Control Module
Alarm: 100mA mA
(5 max.) Standby: 10mA mA
EVS-SW24 Switch Expander
Alarm: 25mA mA
EVS-LOC Local Operating Console (includes (4 max.) Standby: 100mA mA
6860, RVM & SW-24) Alarm: 150mA mA
EVS-100W 100W amplifier ( max.) Standby/Alarm: 10mA mA mA
EVS-100WBU backup daughter card ( max.) Standby/Alarm: 10mA mA mA
Total System Current
Network Cards
SK-NIC Network Interface Card (1 Max.) Standby/Alarm: 21mA mA mA
SK-FML Fiber Optic Multi Mode (1 Max.) Standby/Alarm: 53mA mA mA
SK-FSL Fiber Optic Single Mode (1 Max.) Standby/Alarm: 79mA mA mA
Wireless Modules
Max current using ext supply 40mA mA mA
WSK-WGI Wireless Gateway
Max current SLC Power 24mA mA mA
Auxiliary Devices4 Refer to devices manual for current rating.
(1 max.) Standby: 93mA mA
IPDACT-2 IP Communicator
Alarm: 136mA mA
(1 max.) Standby: 98mA mA
IPDACT-2UD IP Communicator
Alarm: 155mA mA
Standby: 55mA mA
CELL-MOD/CELL-CAB-SK
Alarm: 100mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Auxiliary Devices Current
Notification Appliance Circuits Refer to device manual for current rating.
24 VDC One input circuit: 15mA mA
5495/5499 Power Supply
Both input circuits: 30mA mA
Alarm: mA mA
Alarm: mA mA
Alarm: mA mA
Alarm: mA mA
Notification Appliances Current mA
Total current ratings of all devices in system (line A + line B + C) mA mA
Table 3.2 Current Draw Worksheet for SK SLC Devices (Continued)
Standby Alarm
Device # of Devices Current per Device
Current Current
Total current ratings converted to amperes (line D x .001): A A
Number of standby hours: H
Multiply lines E and F. Total standby AH AH
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H
Multiply lines E and H. Total alarm AH AH
Add lines G and I.5 AH
Multiply by the Derating Factor x 1.25
Total ampere hours
required
Table 3.2 Current Draw Worksheet for SK SLC Devices (Continued)
1. The FACP can only support 5 devices with LED’s on. This current draw has been added to the panels alarm current.
2. The SK-DUCT housing contains a vacant mount for a SK-RELAY (sold separately). The current draw for the SK-RELAY is
calculated by increasing the SK-RELAY row of the calculation sheet by, one, for each SK-RELAY used with an SK-DUCT.
3. SK-BEAM-T draws a maximum of 500mA from Auxiliary power only when the Test feature is used. This should be
considered when determining auxiliary power capacity but not calculated into the current requirements for day-to-day
operation.
4. If you use door holders, you do not need to consider the door holder current for alarm/battery standby, because the power is
removed during that time. However, during normal operation, the door holders draw current must be included in the 6.0A total
current that can be drawn from the panel.
5. Use the next size battery with a capacity greater than required.
6. Total does not include isolator devices or accessory bases.
3.7.3 Current Draw Worksheet for SD SLC Devices
Use Table 3.3 to determine current requirements during alarm/battery standby operation when SD SLC devices are installed. You can
install up to 127 SD devices per loop.5
Standby Alarm
Device # of Devices Current per Device
Current Current
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from battery) 1 Standby: 190 mA 190 mA
Alarm: 250 mA 250 mA
Addressable SLC Devices
SD500-AIM Standby/Alarm: .55 mA1 mA mA
SD500-MIM mA mA
SD500-PS mA mA
SD500-ARM mA mA
SD505-HEAT mA mA
SD505-PHOTO mA mA
SD500-ANM Aux. Pwr Standby: 8 mA mA
Alarm: 60 mA mA
SLC Standby/Alarm: .55 mA mA mA
SD500-SDM SLC Standby/Alarm: .55 mA mA
Aux. Pwr Standby: 20 mA mA
Alarm: 106 mA mA
SLC Accessory Bases
SD505-6RB Standby/Alram: .082 mA mA mA
SD505-6SB Aux. Pwr Standby: 1 mA mA
Alarm: 32 mA mA
SLC Standby/Alarm .082 mA mA mA
SD505-DUCTR Aux. Pwr Standby: 20 mA2 mA
Alarm: 62 mA2 mA
SLC Standby/Alarm: .5 mA mA mA
SD505-DTS-K None, included with SD505-DUCTR worst case.
SD505-DUCT None, included with detector current.
SLC Isolator Devices
SD500-LIM (100 max/loop) Standby/Alarm .092 mA mA mA
SD505-6IB
Accessories Modules
5815XL SLC Loop Expander (63 max.) Standby/Alarm: 55 mA mA mA
Table 3.3 Current Draw Worksheet for SD SLC Devices
Standby Alarm
Device # of Devices Current per Device
Current Current
6860 Remote LCD Annunciator. (16 max.) Standby: 25 mA mA
Alarm: 50 mA mA
5860 Remote LCD Annunciator. Standby: 20 mA mA
Alarm: 25 mA mA
6855 Remote LCD Annunciator Standby: 20 mA mA
Alarm: 25 mA mA
5824 Serial/Parallel Printer Interface (4 max.) Standby/Alarm: 45 mA mA mA
5895XL Power Supply (16 max.) Standby/Alarm: 10 mA mA mA
5496 NAC Expander Standby/Alarm: 10 mA mA mA
5865-4 LED Annunciator Module (8 max.) Standby: 35 mA mA
(with reset and silence switches) Alarm: 145 mA mA
5865-3 LED Annunciator Module Standby: 35 mA mA
Alarm: 145 mA mA
5880 LED I/O Module Standby: 35 mA mA
Alarm: 200 mA mA
5883 Relay Interface (32 max.) Standby: 0 mA mA
Alarm: 220 mA mA
(22 mA per relay)
EVS-50W or EVS-125W Audio Amplifier (8 max.) Standby: 10 mA mA
with/without EVS-CE4 Alarm: 10 mA mA
EVS-INT50W Internal Amplifier (8 max.) Standby: 52 mA mA
Alarm @ 25V: 275 mA mA
Alarm @ 70V: 310 mA mA
EVS-VCM Voice Control Module (1max.) Standby: 70 mA mA
Alarm: 100 mA mA
EVS-SW24 Switch Expander (5 max.) Standby: 10 mA mA
Alarm: 25 mA mA
EVS-LOC Remote Command Unit (4 max.) Standby: 100 mA mA
(includes 6860, RVM & SW-24) Alarm: 150 mA mA
EVS-100W 100W Amplifier (8 max.) Standby/Alarm: 10 mA mA mA
EVS-100WBU backup daughter card (8 max.) Standby/Alarm: 10 mA mA mA
A Total System Current
Network Cards
SK-NIC Network Interface Card (1 Max.) Standby/Alarm: 21 mA mA mA
SK-FML Fiber Optic Multi Mode (1 Max.) Standby/Alarm: 53 mA mA mA
SK-FSL Fiber Optic Single Mode (1 Max.) Standby/Alarm: 79 mA mA mA
Auxiliary Devices3 Refer to devices manual for current rating.
IPDACT-2 IP Communicator (1 max.) Standby: 93 mA mA
Alarm: 136 mA mA
IPDACT-2UD IP Communicator (1 max.) Standby: 98 mA mA
Alarm: 155 mA mA
CELL-MOD/CELL-CAB-SK Standby: 55 mA mA
Alarm: 100 mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
B Auxiliary Devices Current
Notification Appliance Circuits Refer to device manual for current rating.
5495/5499 Power Supply 24 VDC One input circuit: 15 mA mA
Both input circuits: 30 mA mA
Alarm: mA mA
Alarm: mA mA
Alarm: mA mA
Alarm: mA mA
C Notification Appliances Current mA
D Total current ratings of all devices in system (line A + line B + C) mA mA
E Total current ratings converted to amperes (line D x .001): A A
F Number of standby hours: H
Table 3.3 Current Draw Worksheet for SD SLC Devices (Continued)
Standby Alarm
Device # of Devices Current per Device
Current Current
G Multiply lines E and F. Total standby AH AH
H Alarm sounding period in hours. (For example, 5 minutes = .0833 hours) H
I Multiply lines E and H. Total alarm AH AH
J Add lines G and I.4 AH
Multiply by the Derating Factor x 1.25
Total ampere hours
required
Table 3.3 Current Draw Worksheet for SD SLC Devices (Continued)
1. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
2. If you use 24 VDC aux power only, and no standby or alarm current for the battery calculation if you use 24 VAC, 120 VAC or 240
VAC.
3. If you use the door holders, you do not need to consider the door holder current for the alarm/battery standby, because the power is
removed during that time.
However, during normal operation, the door holder’s draw current must be included in the 6.0A total current that can be drawn from
the panel.
4. Use the next size battery with a capacity greater than required.
5. The total does not include the Isolator devices or accessory bases.
3.7.4 Maximum Battery Standby Load
Tables 3.4 and Table 3.5 show the standby load calculations for the 6820 / 6820EVS panels based on 24 and 90 hours of standby. The
standby load calculations of line D in the Current Draw Calculation Worksheet must be less than the number shown in Table 3.4 and
Table 3.5 for the selected battery size, standby hour and alarm time. The numbers below have a built-in 20% derating factor for the bat-
tery amp-hour capacity.
WARNING: Honeywell Silent Knight does not support the use of batteries smaller than those listed in Table 3.4 and Table 3.5. If you use
! a battery too small for the installation, the system could overload the battery resulting in the installation having less than the required 24
hours standby power. Use Table 3.4 and Table 3.5 to calculate the correct battery amp hour rating needed for your installation. It is
recommended that you replace batteries every five years.
14.50" 20"
24.75"
26.5"
6820 6820EVS
Figure 4.2 120 VAC Power Connection for the 6820 or 6820EVS
4.3 Battery Power
The batteries must be sealed lead acid type. Before connecting the batteries to the FACP, make certain that the interconnect cable
between the batteries is not connected. Do not connect the battery jumper cable until the system is completely installed. Observe polarity
when connecting the batteries.
The control panel battery charge capacity is 7.0 to 35 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as
per your current load calculation (see Section 3.7).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating. It is recommended that you
replace the batteries every five years.
To Control Panel
Black
Red
Battery Jumper
(P/N 140694)
Shipped With Panel
• If mounting onto drywall the accessory cabinet must be mounted onto 3/4-inch plywood. This is necessary because the weight of
the batteries inside the accessory cabinet could cause the cabinet to pull away from the drywall.
• When mounting on concrete, especially when moisture is expected, attach a piece of ¾” plywood to the concrete surface and
then attach the RBB cabinet to the plywood.
• If you use the battery cable extenders provided (P/N 140643), mount the RBB cabinet no more than 18" away from the main
control panel cabinet. This placement will ensure that the battery cables reach the battery terminals.
Cabinet
Mounting Holes
Figure 4.5 Splicing Control panel Battery Cable to RBB Battery Cable Extenders
3. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4.6.
RBB Cabinet
Cover Screws
Conduit
Coupler
Conduit
+ - + -
RBB Cabinet
Cover Screws
Figure 4.6 Battery Connections in the RBB Cabinet
NOTE: Figure 4.6 is an example of how the wire connections can be routed. However, any other cabinet knock-outs (on either the main
control panel or the RBB cabinet), that are not previously being used may be utilized to connect conduit between the two cabinets
4. Connect battery leads to the backup battery terminals. See Figure 4.6.
Observe the proper polarity to prevent damage to the batteries or the control panel.
5. Insert the RBB cover screws into the cover mounting holes. See Figure 4.6.
Screw the cover screw ¾ of the way into the cover mounting hole.
6. Align the cover plate mounting keyhole over the cover mounting screws. See Figure 4.7.
Cover Plate
Mounting Keyholes
Figure 4.7 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment
7. Slide the cover into place and tighten the cover mounting screws. See Figure 4.7.
4.4 SBUS Wiring
This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class A and B).
4.4.1 Calculating Wiring Distance for SBUS Modules
The following instructions will guide you in determining the type of wire and the maximum wiring distance that can be used with the
control panel SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the control panel, it is necessary to calculate the total worst
case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual
worst case currents for each module. The individual worst case values are shown in the table below. .
NOTE: The total worst case current draw on a single SBUS cannot exceed 1 amp. If a large number of accessory modules are required,
and the worst case current draw will exceed the 1 amp limit, then the current draw must be distributed using 5895XL Power Expanders.
Each 5895XL Power Expander provides an additional SBUS, with an additional 1 amp of SBUS current. Wiring distance calculations are
done separately for each 5895XL, and separately for the control panel itself.
NOTE: Refer to Table 3.2 is using SK Devices and Table 3.3 if using SD SLC devices for maximum number of each type of device that can
be used per system.
After calculating the total worst case current draw, Table 4.2 specifies the maximum distance the modules can be located from the panel
on a single wire run. The table ensures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for
heavier wire gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used.
The formula used to generate this chart is shown in the note below.
Wiring Distance: SBUS Modules to Panel
Total Worst Case
22 Gauge 18 Gauge 16 Gauge 14 Gauge
Current Draw (amps)
0.100 1852 ft. 4688 ft. * 6000 ft. * 6000 ft.
0.200 926 ft. 2344 ft. 3731 ft. 5906 ft.
0.300 617 ft. 1563 ft. 2488 ft. 3937 ft.
0.400 463 ft. 1172 ft. 1866 ft. 2953 ft.
0.500 370 ft. 938 ft. 1493 ft. 2362 ft.
0.600 309 ft. 781 ft. 1244 ft. 1969 ft.
0.700 265 ft. 670 ft. 1066 ft. 1687 ft.
0.800 231 ft. 586 ft. 933 ft. 1476 ft.
0.900 206 ft. 521 ft. 829 ft. 1312 ft.
1.000 (Max) 185 ft. 469 ft. 746 ft. 1181 ft.
Table 4.2 Wire Distances Per Wire Gauge Using Copper Wire
:
NOTE: The following formulas were used to generate the wire distance chart.
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
• 370 feet maximum using 22 Gauge wire
• 938 feet maximum using 18 Gauge wire
• 1493 feet maximum using 16 Gauge wire
• 2362 feet maximum using 14 Gauge wire
Caution
For proper system
supervision, do not use
looped wire under terminals
marked A, B, +, and - of the
SBUS device connectors.
Break wire runs to provide
supervision of connections.
Supervised
Power-Limited
Figure 4.8 SBUS Class A Wiring
Supervised
Power Limited
The 5860 comes from the factory fully assembled. You must disassemble it for mounting. To disassemble the annunciator, use a 5/64 hex
wrench to remove the set screws, located on the bottom of the annunciator bezel. (See Figure 4.12 for location of the set screws).
Supervised
Power Limited
Mounting Holes
Figure 4.17 Back Box Mounting Holes
2. Remove knockout holes as needed for wires. See Figure 4.18 for backbox knockout locations
Wire Knockouts
Wire Knockouts
Wire Knockouts
Back Box
Mounting Holes
Supervised
Power Limited
Flush Mounting
This section of the manual describes flush mounting. Follow these steps to flush mount the 6860
1. The back box dimensions are 9¼” W x 8 3/8” H. The minimum depth required is 2". The back box can be mounted prior to the
complete installation of the 6860 using any of the mounting holes shown in Figure 4.23.
Mounting Holes
Mounting Holes
Figure 4.23 Back Box Mounting Holes
2. Remove knockout holes as needed for wires. See Figure 4.24 for backbox knockout locations.
Wire Knockouts
Wire Knockouts
Wire Knockouts
4. Attach the annunciator and door assembly to back box as shown in Figure 4.25 using the supplied screws.
Back Box
Mounting Holes
4. Place the trim ring over the back box as shown in Figure 4.27.
Supervised
power limited
2. Mount the 5815XL in the 6820 cabinet, the 5895XL cabinet, or the 5815RMK remote mounting kit. Use the standoffs located under
the control panel board assembly and secure with screws provided with the 5815XL. For additional information, also see Model
5895XL Installation Instructions (P/N 151142) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
3. Connect the 5815XL to the control panel. (See Section 4.8.1.)
4. Use on-board DIP switches to select an SBUS ID#. (See Section 4.13.1).
5. The new 5815XL module must be added to the system through programming. JumpStart will add the module automatically (see
Section 8.1). You can also add it manually (see Section 9.2.2). Select a name, if desired.
6. You are now ready to connect SLC devices to the 5815XL (see Section 9.5.1).
Figure 4.29 is a drawing of the 5815XL board, showing the location of terminals and DIP switches.
DIP Switch
Supervised
Power Limited
2. Mount the 6815 in the 6820 cabinet, the 5895XL cabinet, or the 5815RMK remote mounting kit. Use the standoffs located under
the control panel board assembly and secure with screws provided with the 6815. For additional information, also see Model
5895XL Installation Instructions (P/N 151142) or 5815RMK Remote Mounting Kit Installation Instructions (P/N 151391).
3. Connect the 6815 to the control panel. (See Section 4.8.1.)
4. Use on-board DIP switches to select an SBUS ID#. (See Section 4.13.1).
5. The new 6815 module must be added to the system through programming. JumpStart will add the module automatically (see
Section 8.1). You can also add it manually (see Section 9.2.2). Select a name, if desired.
6. You are now ready to connect SLC devices to the 6815 (see Section 9.5.1).
Supervised
Power Limited
3. Use the DIP switches on the back of the 5824 board to assign an ID# to the 5824 (see Section 4.13.1).
4. Configure the 5824 device through programming. See Section 4.10.1.
5. Connect a printer to the 5824 as shown in Figure 4.33.
Supervised
Power Limited
Option Choices
Baud Rate: 75 - 19200
Data Bits: 5-8
Stop Bits: .5, 1, 2
Parity: None, Even, Odd
SBUS Address
DIPs
SBUS Connection
Supervised
Power Limited
NOTE: The circuit connected to “Open Collector Output” (last pin on P1) must be current limited so that no more than 100mA of current is
allowed to flow into the open collector transistor.
Supervised
4.7k Ω EOL
NOTE: This manual uses “5865” when referring to aspects of the 5865-3 and 5865-4 that are common to both models.
Supervised
Power Limited
Attach 5865 to a
standard 3- or 4-gang
electrical box.
Cover Plate
The 5865 ships with a set of zone description labels that can be inserted into the 5865 board assembly. These labels can be used in a type-
writer or can be written by hand. Slide the labels under the plexiglass as shown in Figure 4.42. The LEDs will show through the label
when illuminated.
Supervised
power limited
UL Listed
EOL 4.7 kΩ
Supervised
power limited
Maximum Impedance
per circuit is 50W
Supervised
power-limited
Note:
Flexput circuit 5
4.7 kΩ EOL used as an example.
Either Flexput circuit
5 or 6 could be used.
Figure 4.47 Two-Wire Class B Smoke Detector
Installing 2-Wire Class A Smoke Detectors
To install a Class A two-wire smoke detector, wire as shown in Figure 4.48.
Supervised
power limited
Air Products
PAM-2
Model 160150
Supervision
Module
Supervised
power limited
Air Products
PAM-2 Model
160150
Supervision
Module
4.7 kΩ EOL
Max. Impedance: 1.5Ω
notification wiring
supervised
power limited
supervised
power limited
Resettable Power
Resettable power is typically used to power beam detectors, flame detectors and conventional 4-wire smoke detectors. For circuits
selected as Resettable, 24-volt power is always present at the terminals unless a system reset occurs. If a system reset occurs, power is
disconnected from the terminals for 30 seconds, then re-applied.
Sounder Sync Power
Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is intended for use with B200S sounder bases.
4.17 On-Board Relays (Conventional)
The control panel has two built-in programmable relays and a built-in trouble relay. All relays are Form C rated at 2.5 A @ 24 VDC.
NOTE: The NC contact is relay contact that is closed when the panel has power and there are no trouble conditions
4.18.3 Using the Addressable Relay Module for City Box Connection
Wire the SK-Relay as shown in Figure 4.56.
Must be in
Conduit
2’ cable
Class B wiring
Class A Wiring
Data
Network
NOTE: The SK-NIC provides a common communications link for 6820/6820EVS. These panels cannot be linked together for peer-to-peer
networking.
Class A wiring
Class A wiring
Class A wiring
Class A wiring
Figure 5.10 Twisted Pair and Fiber Optic Combination Wiring Example
The panel ID for each panel is set using DIP switch positions 1 through 5. See Figure 5.11 below for possible DIP switch settings.
NOTE: Profile 1 (Fire Fighter’s Key) the user name and access code can not be edited. Profile 2 (Installer) the user name and panel
functions can not be edited. Profile 3 (Multi-Site Installer) is defaulted with the Multi-Site access option, but the entire profile can be edited.
Edit Name
6. See Appendix for a list of available characters and their numeric designators.
7. Then press ENTER to finish.
Edit Access Code
8. Enter the new access code (minimum of 4 digits, maximum of 7 digit).
9. Press ENTER.
10. Enter code again. Press ENTER.
Panel Functions
11. Press the Up or Down arrow key to move through the list of available functions.
12. Then press right arrow to move to Y (yes) or N (no) selection column.
13. Press the Up or Down arrow key to select Y or N.
14. Press ENTER.
15. Repeat steps 12 through 15 until user profile is complete.
6.2.6 Communicator Options
Communicator options provides the configuration for reporting events to a central station.
1. From the Main Menu. select 6 for Network Programming.
2. Press 6 to enter Communicator Options Menu.
Communicator Assignments
Each panel on the 6820/EVS communication link system specifies which communicator is used for reporting. The communication link
capability of the linked system allows all panels to use the same communicator providing an economical solution for reducing the num-
ber of paths required for reporting purposes. A communicator is specified by panel number. The communication link will be used to
report events according to the communicator report table.
Communicator Miscellaneous
When using the SIA reporting format, the communicator sends information according to the SIA Reporting Type. The selections for this
option are:
1. PI Modifier (default)
2. Panel ID*
Receiver Configuration
The 6820/EVS system can report events to as many as 68 receivers. See Appendix for panel/receiver relationship numbers. Each
receiver is assigned a phone number and reporting format. Phone numbers can be up to forty digits long.
1. From the Main Menu.
2. Select 6 for Network Programming.
3. Press 6 to enter Communicator Options Menu.
4. Select 3 for Receiver Configuration.
5. Select Panel to Program and press ENTER.
6. Enter the receiver number that you want to report to. The receiver numbers available will correspond with what panel number you
entered. Receiver numbers are populated based on panel number and audited to allow only the 4 appropriate receivers. See
Appendix Appendix D: for receiver number
Available Format choices are listed in the Reporting Format table:
Reporting Format
Contact ID
SIA500
Ethernet
Cellular
eVance
UNUSED
SIA8
SIA20
System Event
Fire Alarm
Fire System Aux 1
Fire System Aux 2
Fire Zone Aux 1
Fire Zone Aux 2
Fire Pre Alarm
Emergency Communication 1
Emergency Communication 2
Emergency Communication 3
Emergency Communication 4
Emergency Communication 5
Emergency Communication 6
Emergency Communication 7
Emergency Communication 8
Fire Supervisory
System Alert 1-5
Trouble
Fire Interlock Release
Fire Interlock Alert
Custom Emergency Comm
Emergency Supervisory
CO Alarm
CO Supervisory
Table 6.3 Voice Command Mapping
7. Select whether a Message or Tone Only should be played. If Message is selected, choose the desired message for the command.
8. Select the tone to be played between messages. (High-Lo, ANSI Whoop, Cont. Whoop, ANSI, March Code, California, Steady,
Alert Tone, or No Tones).
NOTE: 520Hz tones are available when using EVS-VCM, EVS-INT50W or EVS-100W AMP’s. These include ANSI 520, Temp 4 520,
Steady 520. See Table A.6 for a list of compatible speakers.
9. Select how many times you want the message to repeat. (None, 1 - 14, or Continuous).
10. Select the initial delay time (0, 3, 4, 8, 12, 16, 20, 24, 28).
11. Select the inter-message delay time (4 to 32 seconds, in 4 second increments).
12. Select Y or N to allow message to continue to play after the MIC release.
13. Select Y or N to allow message to restart on a new activation.
6.4 Sync Network Options
If after making changes to network programming, the distribution of network options fail, the system will report a trouble of network
options out of sync. Use this menu to redistribute changed options to the rest of the network. The user will be required to choose a panel
to source the options from. Scroll down through the informational message and press ENTER to view the Select Source screen.
1. Enter the Installer Code. The panel will automatically go to the Main Menu.
2. Select 6 for Network Programming Menu.
3. Select 8 for Sync Network Options.
4. Select which panel to source the options from.
Send/Receive
Firmware Update
Communicator See Section 6.2.6
Select Panel Primary 0= unused
Assignments
Enable pi SIA Modifier See ,
Communicator
SIA Options "Communicator
Miscellaneous Include Panel ID in SIA Reporting Miscellaneous"
Receiver See , "Receiver
Network Select Panel Select Receiver Number Configuration"
Programming
(cont.) Contact ID
SIA500
SIA8
Receiver
Configuration SIA20
Receiver Format
eVance
Ethernet
Cellular
Communicator
Options UNUSED
Receiver Credentials
Panel
Report Alarms
Report Supervisory
Report Troubles
Report Events by
Point
See , "Communicator Reporting
Communicator Report Table Primary Receiver
Table"
Primary Account
Test Primary Account
Secondary Receiver
Secondary Account
Test Secondary
Account
NOTE: The control panel supports the use of either SK SLC devices or SD SLC devices. You cannot install both SLC device types on the
control panel.
SK Installation
Model Name/Description
Part Number Instruction PN
SK-PHOTO Photoelectric smoke detector
SK-PHOTO-T Photoelectric smoke detector with thermal (135°F)
I56-3426-00
SK-PHOTOR Photoelectric detector with remote test capability
SK-ACCLIMATE Multi criteria photoelectric smoke detector with thermal (135°F)
SK-BEAM Reflected beam smoke detector without test feature
I56-3433-00
SK-BEAM-T Reflected beam smoke detector with test feature
SK-DUCT Photoelectric duct smoke detector with extended air speed range I56-3432-00
SK-HEAT Fixed temperature thermal detector (135°F)
SK-HEAT-ROR Rate-of-rise thermal detector with 135° fixed temperature I56-3429-00
SK-HEAT-HT Fixed high temperature thermal detector (190°F)
SK-PULL-SA Addressable single action pull station I56-3446-00
SK-PULL-DA Addressable dual action pull station I56-3447-00
SK-ISO Fault isolator module I56-3445-00
SK-MONITOR Monitor module I56-3442-00
SK-MINIMON Mini monitor module I56-3444-00
SK-MONITOR-2 Dual input monitor module I56-3435-00
SK-MON-10 10 input monitor module I56-3443-00
SK-RELAY Addressable relay module I56-3438-00
SK-RELAY-6 Six relay control module I56-3439-00
SK-RELAYMON-2 Dual relay/monitor module I56-3735-00
SK-ZONE Addressable zone interface module I56-3440-00
SK-ZONE-6 Six zone interface module I56-3441-00
SK-CONTROL Supervised control module I56-3436-00
SK-CONTROL-6 Six circuit supervised control module I56-3437-00
SK-FIRE-CO CO Smoke Detector I56-3945-00
B210LP 6" mounting base I56-0595-00
B224BI-WH / IV 6" isolator base. White or Ivory I56-0725-00
B224RB-WH / IV 6" relay base. White or Ivory I56-3737-00
B200SR-WH / IV 6" temporal sounder base. White or Ivory I56-3392-00
B200S-WH / IV Intelligent Sounder Base. White or Ivory I56-3387-00
B501 4" mounting base I56-0357-00
B501-WHITE / IV / BL 4" mounting base. White, Ivory, or black I56-6527-00
B200SR-LF-WH/ IV Low Frequency Sounder Base. White or Ivory I56-4152-00
B200S-LF-WH / IV Low Frequency Sounder Base. White or Ivory I56-4151-00
SK-PHOTO-W Photoelectric smoke detector. White I56-6527-00
SK-PHOTO-R-W Photoelectric replacement smoke detector with remote test capability in DNR. White I56-6528-00
SK-PHOTO-T-W Photoelectric smoke detector with thermal (135°F) White I56-6530-00
SK Installation
Model Name/Description
Part Number Instruction PN
SK-HEAT-W Fixed temperature thermal detector (135°F). White I56-6529-00
SK-HEAT-ROR-W Rate-of-rise thermal detector with 135° fixed temperature. White I56-6529-00
SK-HEAT-HT-W Fixed high temperature thermal detector (190°F). White I56-6529-00
Color Guide: -IV = Ivory color, -BL = Black, -WH = White, -WHITE-White
NOTE: The control panel supports the use of either SD SLC devices or SK SLC devices. You cannot install both SLC device types on this
control panel.
SD Installation
Model Name/Description
Model Number Instruction PN
SD505-PHOTO Photoelectric smoke detector.
150955
SD505-HEAT Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C).
SD505-6AB 6" base
SD505-6IB 6" short circuit isolator base I56-3541-00
SD505-6RB 6" relay base I56-3542-00
SD505-6SB 6" sounder base I56-3540-00
SD505-DUCT Duct Smoke Detector. Duct Housing including the SD505- Analog Photoelectric Smoke Sensor. 1700-09882
Intake tubing for duct available in three lengths: SD505-T2 (2.5 foot); SD505-T5 (5 foot); SD505-
T10 (10 foot)
SD505-DUCTR Duct Detector housing with relay base. Duct housing with relay base including SD505- Analog 1700-09882
Photoelectric Smoke detector pre-installed
SD500-PS/-PSDA Single or dual action addressable pull station I56-3632-00
SD500-AIM Addressable input module (switch input), standard size, DIP switch configurable I56-3547-00
SD500-MIM Mini input monitor module (switch input), small size, DIP switch configurable.
SD500-ANM Addressable notification module I56-3544-00
SD500-ARM Addressable relay module DIP switch configurable. I56-3545-00
SD500-SDM Addressable smoke detector module. I56-3546-00
SD500-LIM Line isolator module. Fits in a double gang box. I56-3543-00
SD505-DTS-K Remote test switch & LED indicator for the SD505-DUCTR 1700-09882
Figure 7.1 Calculating wire run length for a simple out and back
When you use T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement must be met in addition
to the maximum distance requirements for the various wire gauges.
.
NOTE 1: Class A wiring also requires an isolator module as the first device on the in and the out loops.
NOTE 2: It is recommended to use the same wire gauge if there are multiple connections to the same terminal.
For more information regarding Gateway wiring instructions, see SWIFT manual LS10036-000SK-E.
7.10.1 Power Connections for the Gateway
The SK-WGI Wireless Gateway acts as a bridge between a group of wireless fire devices and a SLC loop on the 6820/EVS. It is powered
by the SLC loops or by a regulated, external 24 VDC UL listed power supply. See the SWIFT® Smart Wireless Integrated Fire Technol-
ogy Instruction Manual P/N LS10036-000SK-E for a list of available wireless devices, system setup, and operation
NOTE: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
NOTE: If you need to install a few devices after you have run JumpStart, you can install them manually or run JumpStart again at a later
time. JumpStart will keep user options, such as names, for devices already installed. Follow instructions in Section 9 for configuration
NOTE: Mapping cannot be programmed through annunciators and can only be programmed through HFSS Honeywell Fire Software
Suite.
Figure 8.4 Example of Zone Events Mapped to Output Groups and Patterns
Figure 8.5 Example of Zone Events Mapped to Output Groups and Patterns
NOTE: Mapping cannot be programmed through the on-board and remote annunciators. Mapping is only available through HFSS
Honeywell Fire Software Suite up/downloading software.
The following subsections describe programming basics, including a description of editing keys available for programming and how to
move through programming menus. Section 9 contains specific information about individual programming options.
To Press
Enter the number The corresponding number on the annunciator.
Enter numeric data The appropriate number on the annunciator.
Enter text (alphanumeric data) See Appendix for complete list of characters.
Select from a scrolling list Use the Up or Down arrow to move through the list of available options. When the option you want
to select is displayed, press ENTER.
No Accessory
PHOTO DUCT1,2,3,4,5
DCT RLY
No Accessory
SDR BAS
RLY BAS
SD and SK ACCLIMATE2,3,4
DETECTOR I-SdrBa
Devices on Internal
Point 1,2,3,4,5 (Intelligent
and External 6815 Enter Pt Select Sensor Sounder Base) Section 9.5
(cont.)
and External
No Accessory
5815XL (cont.)
SDR base
RLY base
HEAT-HT2,3,4
I-SdrBa
(Intelligent
Sounder Base)
No Accessory
SDR BAS
RLY BAS
PHOT-HEAT2,3,4
I-SdrBa
(Intelligent
Sounder Base)
BEAM2,3,4
SUP DET Same function as LATCH
1,2,3,4,5 DETECTOR NON-LATCH
Table 8.3 Programming Quick Reference List (Continued)
100 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Programming Overview Programming Menu Quick Reference
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 101
Programming Menu Quick Reference Programming Overview
Y or N *N
Monitor Line
*N
Answering Machine Bypass Y or N
Y or N *N
Phone Line Unused
IP Address
Subn Mask
Section Edit
Edit Ethernet SubNet
Ethernet
Default Gateway
DHCP Enable
75 sec, 90 Sec, 3 min, 5
Ethernet Supervise min, 1 hr, 24 hrs, 30 *5 Minutes
days, None
Section
Cellular Supervise 24Hrs, 30 days, none *24 Hours
Communication AlarmNet Timers AlarmNet
10 min, 15 min, 30
Options Timers
Minutes, 1 hr, 2 hrs, 4
Old Alarm Time *30 Minutes
hrs, 8 hrs, 12 hrs, 24hrs,
none
High
Dialing Low *High
Normal Section Phone
Phone Line Gains
Low Line Gains
System
Reporting Normal *Low
Options
cont High
Water Flow delay is the number
of seconds before a water flow
Water Flow Delay 0 - 90 Seconds *1 sec
alarm is generated. Section
Water Flow Delay
Alarm Verification time section
Alarm Verify 60 to 250 seconds *60 sec
Alarm Verify
Low AC Report Delay. Section
Low AC Report Time 0 - 30 hours *3 hrs
AC Report Delay
Time Options 50 Hz
Section Change AC Line
AC Freq: 60 Hz *60Hz
Frequency
Internal
AM/PM System Clock Format (AM/PM
or military). Section Clock
Clock Display Format *AM/PM
MIL Display Format (AM/PM or
Military)
4 hours Section Auto-Resound (4 or 24
Auto-resound *24 hours
24 hours hours)
Table 8.3 Programming Quick Reference List (Continued)
102 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Programming Overview Programming Menu Quick Reference
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 103
Section 9: Programming
This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses
these menu options in detail. All options described in this section can be performed using HFSS Honeywell Fire Software Suite.
NOTE: Internal devices and SK-NIC are not able to have their module ID edited.
104 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Programming Zone
Naming Modules
You can assign an English name to a system hardware module to make it easier to recognize on a display.
7. If you wish to edit the module’s name, press the ENTER on the modules name. Then press the number keys corresponding to the
character to select each character for the module’s name (or press the right arrow to bypass editing the name).
Press the right arrow to move to the next character.
NOTE: If you Add a Module that has not been physically connected, the panel will go into trouble after it reinitializes (when you exit the
Program Menu). When the new module is attached, the trouble will correct itself automatically.
9.3 Zone
Through the Zone option in the Program Menu, you can edit and view zone points. Selections made here affect all detectors and switches
in the zone. Up to 999 zones can be used in the system.
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 105
Zone Programming
NOTE 1: The B200S Sounder base provides the recommended CO cadence pattern.
NOTE 2: If the SLC protocol is changed from SD to SK series and the cadence is no longer valid for SK, the zone cadence will be set to
constant on.
Zone Number
Zone Name
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 107
Group Programming
9.4 Group
An output group is made up of output points that have been programmed to respond in the same way. Output groups simplify program-
ming because you only need to program the output characteristics that are common to all of the group points once, instead of program-
ming each individual point. Once you have defined the characteristics of output groups, you can assign each point to the appropriate
group. All valid output points are assigned to only one output group. Unused points are not assigned to any output group. Up to 999 out-
put groups can be defined.
9.4.1 Edit Group
In the Edit Group option, you can program the name of an output group (Section Edit Group Name) and change the properties of that
group. To edit a group, follow these steps:
1. Enter the Installer Code. The panel will automatically go the Main Menu.
2. Select 7 for the Program Menu.
3. Press 3 to enter the Group Menu.
4. Press 1 to edit the group.
5. Enter the number of the group you wish to edit, then press ENTER.
Edit Group Name
6. To edit the group name, press 1.
You can use words to display a descriptive name for a group.
Corresponding Corresponding
Key and LED Numbers Key and LED Numbers
108 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Programming Point
Silencing Options
The following silencing options are available for each output group.
Optional Timers Description
Silence Inhibit Timed Silence after Inhibit. If this option is selected, the output group must be audible for a programmed
number of minutes before it can be silenced. If the condition that caused the output to activate has not
cleared during the time-frame, the output can be silenced. If you select this option, select the timeframe in
the delay field. Range is 0-60 minutes.
Auto Silence Silenceable. The output group will automatically silence after the timer expires. Range is 0-60 minutes.
Auto Unsilence If this option is selected, the output group can be silenced for a programmed time-frame. If the condition that
caused the output to activate has not cleared during the time-frame, the output reactivates. If you select this
option, select the time-frame in the delay field. Range is 0-60 minutes.
Startup Delay When a alarm is generated, the Output group will not activate until the timer expires assuming the event is
still active. Range is 0-120 Seconds
Table 9.2 Silencing Options
9.4.2 View Group Points
1. Enter the Installer Code. The panel will automatically go to the Main Menu.
2. Select 7 for Panel Programming.
3. Press 3 to enter the Group Menu.
4. Press 2 to view the Group Points.
5. Enter the Group Number, then press ENTER.
7. Press the right arrow to the OPG and select YES or NO to select which output groups to include in the template.
9.5 Point
You may need to change characteristics of the individual input points (detectors and switches) even after using JumpStart. This section
explains how to change options for: type of point, latching/non-latching, silenceable/non-silenceable, zone assignment (input points),
detector accessory base options, group assignment (output points), and point name.
9.5.1 Point Programming For 5815XL Module
To program points on 5815XL Module, follow these steps:
1. Enter the Installer Code. The panel will automatically go to the Main Menu.
2. Select 7 for the Program Menu.
3. Press 4 to enter the Point Menu.
4. Press the Up or Down arrows to select the desired module. Refer to Section 8.5 Quick Reference Table for available choices. Press
ENTER.
5. Enter the number of the point you wish to edit, then press ENTER.
6. Select the type of device by pressing the Up or Down arrow key. Refer to Table 9.3 under the column heading “Type Selection” for
a list of choices.
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 109
Point Programming
110 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Programming Point
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 111
Point Programming
112 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Programming Point
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 113
Point Programming
114 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Programming Point
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 115
Point Programming
9.5.4 Point Programming for 5880, 5865, EVS-50W, EVS-INT50W, EVS-100W, EVS-125W and
EVS-CE4 Modules
To program 5880, 5865, EVS-50W, EVS-INT50W, EVS-100W, EVS-125W, or EVS-CE4 module points:
1. Enter the Installer Code. The panel will automatically display the Main Menu.
2. Select 7 for the Program Menu.
3. Press 4 to enter the Point Menu.
4. Press the Up or Down arrows to select the desired module. Refer to Section 8.5 for available choices. Then press ENTER.
Select a name
for the Point
116 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Programming System Options
Phone Lines
To access the phone lines screen:
1. Enter the Installer Code. The panel will automatically go to the Main Menu.
2. Select 7 for Panel Programming.
3. Select 5 for the System Options.
4. From the next menu, select 1 for Communication Options.
5. Select 2 for the Phone Lines.
6. Select Phone Line to be edited (1 or 2) by pressing the Up or Down arrow key, then press ENTER.
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 117
System Options Programming
118 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Programming System Options
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 119
System Options Programming
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)
NOTE: You must select 1-3 hours in UL central station installations and UL remote signaling installations.
You can adjust the number of hours before a low AC report will be sent to the central station.
To program the low AC report delay, follow these steps:
8. Enter the number of hours (0-30) before a low AC report will be sent to the central station, then press ENTER.
Change AC Line Frequency
The panel’s AC line frequency is selectable for 50, 60 Hz, or Internal. AC Frequency feature dictates how the control panel will calculate
the time based on the AC line frequency used in the installation site. The “Neither” option can be used in areas where the AC line fre-
quency is not dependable and you want the panel to calculate the time from the internal crystal. The internal crystal is not as accurate as
the AC power source and internal 60 Hz or 50 Hz should normally be selected. The panel defaults to the 60 Hz. selection.
To change the AC line frequency, continue programming from step 9 above:
9. Select 50, 60 or Intl by pressing the Up or Down arrow, then press ENTER.
120 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Programming System Options
NOTE: The “SYNC Strbs w/ Sil:” only functions with outputs that use a synchronized output pattern.
5. Press the Up or Down arrow to toggle this selection between Y (Yes) or N (No).
6. Press the right arrow or ENTER to make your selection and move to the next programming option.
Auto Display Event
When this feature is programmed Y (Yes), then the oldest un-acknowledge event will automatically display on the control panel and
remote annunciators, after there has been no activity on any system touchpad for two minutes.
7. Press the Up or Down arrow to toggle this selection between Y (Yes) or N (No).
8. Press the right arrow or ENTER to make your selection and move to the next programming option.
9.6.4 Daylight Savings Options
To edit Daylight Savings:
1. Enter the Installer Code. The panel will automatically access the Main Menu.
2. Select 7 for the Program Menu.
3. Select 5 for the System Options.
4. Select 6 for the Daylight Savings.
Automatic Daylight Savings Adjustment
The control panel has an automatic DST (Daylight Saving Time) adjustment feature. If this feature is not enabled (set to No), the Day-
light Saving Time change is not made to the system clock.
To enable or disable DST adjustment continue programming:
5. Select Y (enabled) or N (disabled) by pressing the Up or Down arrow, then press ENTER.
Daylight Saving Time Start and End
This option lets you adjust the week and month Daylight Saving Time (DST) starts and ends. For this feature to work, you must enable
(set to Yes) the Automatic Daylight Savings Adjustment option under Daylight Savings Options. The default values for the DST Start
and End are:
DST Start: The second Sunday in March
DST End: The first Sunday in November
To set the start and end for the Daylight Saving Time:
6. Press the Up or Down arrow to select the week (1st, 2nd, etc.) Daylight Saving Time starts, then press ENTER to make your
selection and move to the month setting.
7. Press the Up or Down arrow to select the month (January – December) Daylight Saving Time starts, then press ENTER to make
your selection and move to the DST End option.
8. Press the Up or Down arrow to select the week (1st, 2nd, etc.) Daylight Saving Time ends, then press ENTER to make your
selection and move to the month setting.
9. Press the Up or Down arrow to select the month (January – December) Daylight Saving Time ends, then press ENTER two times to
make your selection and exit.
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 121
JumpStart Auto-Programming Programming
5. Select each letter by pressing the Up or Down arrow, then press the right arrow to move to the next character.
6. When done, press ENTER to move to line two of the custom banner.
9.6.6 SLC Family
The 6820/6820EVS supports SD protocol SLC devices or SK protocol SLC devices. You must configure the 6820/6820EVS to accept
the protocol of the devices you are installing.
NOTE: You cannot mix SK and SD protocol SLC devices on the same panel
1. Enter the Installer Code. The panel will automatically access the Main Menu.
2. Select 7 for the Program Menu.
3. Select 5 for the System Options.
4. Press 8 for the SLC Family.
5. Press Up arrow to select the desired SLC device type.
6. Press ENTER to accept the displayed SLC device type.
NOTE: When changing SLC type from one protocol to another, the following message will appear.
NOTE 2: Message when changing from SD to SK: “SLC family will remove all 5815XL’s on the system”
122 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Programming Restore Defaults
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 123
Section 10: System Operation
Operation of the control panel is simple. Use the Menus to guide you step-by-step through the operations. This section of the manual is
an overview of the Operation Menus. Please read this entire section carefully before operating the control panel.
10.1 User and Installer Default Codes
Installer Code (factory-programmed as 123456).
Multi-site Installer Code (factory-programmed as 654321).
10.2 Annunciator Description
Figure 10.1 shows the annunciator that is part of the control panel board assembly for 6820.
124 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
System Operation Menu System
Text of
Internal Banner
Custom Banner
Example
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 125
Basic Operation System Operation
126 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
System Operation Basic Operation
NOTE: If any Alarm Verification Zones are used, the user will be asked if they want to disable the Alarm Verification during the Walk Test.
This occurs for either Walk Test option.
2. Select 3 for Walk Test-No Rpt.
Enter the time period you want the NAC circuit to be active for each alarm (06 to 180 seconds).
The LCD will display “WALK TEST STOPPED” on Line 1 and “ENTER = start test” on Line 3.
When you select this option, the Central Station Reporting is disabled while the test is in progress.
3. Select 4 for Walk Test-with Rpt.
Enter the time period you want the NAC circuit to be active for each alarm (06 to 180 seconds).
The LCD will display “WALK TEST STOPPED” on Line 1 and “ENTER = start test” on Line 3.
When you select this option, the Central Station Reporting will occur as normal during the Walk Test.
4. The panel generates a TEST report to the Central Station when the Walk Test begins. During a Walk Test, the panel’s normal fire
alarm function is completely disabled, placing the panel in a local trouble condition. All zones respond as 1-Count zones (respond
when a single detector is in alarm) during a Walk Test. Each alarm initiated during the Walk Test will be reported and stored in the
event history buffer.
5. To End the Walk Test, go to the Main Menu. Select 1 for the System Test. Then press 3 or 4. Press ENTER to end the Walk Test.
The system will reset. The panel will send a “TEST RESTORE” report to the Central Station.
If you do not end the Walk Test manually within four hours, it will end automatically. If an alarm or pre-alarm condition is occurring in
the system, you will not be able to enter the Walk Test.
NOTE: The panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to normal, the panel is
ready to go to the next device.
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 127
Basic Operation System Operation
NOTE 1: Alarm and trouble signals that have been silenced, but the detector remains un-restored, will un-silence every 4 or 24 hours
depending on user selection until the detector is restored.
NOTE 2: Multi-Site displays do not allow for silencing multiple sites. Pressing SILENCE will only locally silence the PZT built into the
annunciator.
NOTE 3: For EVS systems, pressing silence at an LOC will only prompt for which system they desire to reset. See Section 10.5.1.
NOTE 2: For EVS Systems, pressing reset at an LOC will prompt the user for which system they desire to reset. See Section 10.5.1.
Reset Communicator
This options allows the user to Reset the Communicator. The LCD will display:
“Resetting Communicator… Please Wait“
You will be returned to the Main Menu when the reset is complete.
The Communicator is not allowed to be reset when alarms or supervisories are active. Communicator reset is not allowed if any of the
following are active:
• Fire Alarm
• Fire Supervisory
• Fire Pre-Alarm
• CO Alarm
• CO Supervisory
• EVS Alarm
• EVS Supervisory
10.4.10 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA 72. Detectors are
sampled every three hours.
If sensitivity for a detector is not in compliance, the panel goes into trouble, generating a Calibration Trouble condition. A detector enters
a Calibration Maintenance state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
When a Calibration Trouble condition occurs, the central station receives a detector trouble report (“373” + Zone # for Contact ID for-
mat; “FT” + Zone # in SIA format).
To check sensitivity for an individual detector, follow the steps below.
1. From the Main Menu, press 2 for Point Functions.
2. Press 2 for Point Status.
3. Select the module where the point you want to check is located.
4. Enter the number of the point you want to check and press ENTER.
128 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
System Operation Basic Operation
A screen similar to those shown in Figure 10.5 will display for 6820 and Figure 10.6 for 6820EVS.
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 129
Event Priority System Operation
AlarmNet Info
1. Press 6 from the System Information Menu for AlarmNet Info.
2. Cell Strength: 0 to 100%
3. Status: Registered/Not Registered
AlarmNet Temporary PIN
Press 7 from the System Information menu for the AlarmNet Temporary PIN. This is used in case the FACP is replaced on the CCP.
10.5 Event Priority
This section goes over how event activations are handled by the control panel with regards to priority.
10.5.1 System Control
The 6820 or 6820EVS control panel integrates both a fire and emergency system into one. When the events are active from both sys-
tems, the control panel makes intelligent decisions to determine which system should be controlling outputs. This is called System Con-
trol. This manual will refer to the fire or emergency systems having System Control, this means that the system has an active alarm or
supervisory event that has a higher event priority than an active alarm or supervisory event from the other system. For this consideration,
the control panel looks at the highest priority event active on each system. When both systems are active, the system with control will
activate System Override. System Override is activated on the lower priority, non-System Control panel system (fire or emergency sys-
tem.)
10.5.2 System Override
System Override temporarily disengages output group activations from the system being overridden. This is done to not provide conflict-
ing messages and signaling and help with reducing confusion of the building occupants.
When output groups are supposed to be active but are not because System Control has activated System Override, they are re-activated
every 30 seconds for 2-3 seconds to indicate to the building occupants that there is still an event active. This will only occur when the
system with System Control is not using the output group. The System Override option is programmable for non-voice output groups on
a per output group basis through the panel output group programming menus and in HFSS Honeywell Fire Software Suite. In these
places the option is called Allow System Override and defaults to YES. It is also possible to not reactivate the output groups every 30
seconds when System Override is active on a per system basis. This option is programmable in HFSS Honeywell Fire Software Suite.
There are times when you would not want to allow System Override for an output group. For example: fire is programmed to an elevator
relay to bring the elevator to the bottom floor for fire only. If fire and EVS are active with EVS being the higher priority event, you still
need the elevator to move to the bottom floor and only audible and visual notification appliances must be overridden. In this case, the
output group assigned to the relay would be set to NO on the Allow System Override setting. See Section edit group properties.
130 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
System Operation Event Priority
NOTE 1: Status Points, Status Voice Aux 1, Status Voice Aux 2, and Background Music are contained within the System Status event
priority.
NOTE 2: All fire, emergency and system troubles are prioritized into the Trouble event priority
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 131
Operation Mode Behavior System Operation
132 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
System Operation Operation Mode Behavior
The communicator seizes control of the phone Press Down arrow to view the trouble. A screen
line and calls the central station. similar to this one displays.
The on-board annunciator sounds a loud,
pulsing beep in the sequence one second on,
nine seconds off.
SYSTEM TROUBLE LED flashes.
The LCD displays a screen similar to this one.
Press SILENCE and enter an access code (or
activate the key) to silence the annunciator.
Once the trouble condition has been fixed, the system
A system trouble condition
will restore itself automatically.
occurs.
Trouble
Touchpad PZT beeps. Press Down arrow to view the Prealarm. A screen
The LCD displays a screen similar to this one. similar to this one displays.
A single detector trips in a 2-
Count zone. (2-Count
Prealarm means two detectors must
trip before an alarm is
reported.)
All system operations are available in this mode.
All LEDs are on briefly then the LCD displays Menus are not available during the reset process.
The RESET button is
“RESET IN PROGRESS”. If the reset process
Reset pressed followed by a valid
completes normally, the date and time normal
code or rotation of the key.
mode screen displays.
Table 10.3 :Operation Mode Behavior
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 133
Releasing Operations System Operation
NOTE 2: An annunciator cannot be programmed as a multi-site display when it is associated with an VCM or RVM in a EVS system.
NOTE 3: Status Points, Status Voice Aux 1, Status Voice Aux 2, and Background Music are contained within the System Status event
priority.
NOTE 4: All fire, emergency and system troubles are prioritized into the Trouble event priority.
• Output Group 2 is created. Output Group 2 will be defaulted as a “Detector Alarm” output group for all releasing zones. NAC
[98:001] is assigned to Output Group 2.
• Output Group 3 is created. Output Group 3 will be defaulted as a “Interlock Release Alert” output group for all releasing zones.
NAC [98:002] is assigned to Output Group 3.
• Output Group 4 is created. Output Group 4 will be defaulted as “Interlock Release Alarm” output group for all releasing zones.
NAC circuit [98:003] is assigned to Output Group 4..
NOTE 1: The installer must define which input points will be used for detectors, manual release switches, or interlock/pressure switches.
NOTE 2: For manual release operation, Installer must use an FM approved/ UL listed releasing manual station
134 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
System Operation Releasing Operations
Model 7641-L8
Must Mounted
at the Solenoid
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 135
Releasing Operations System Operation
NOTE: Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.
Important!
Each Double Interlock Zone input requires at least one Interlock/pressure switch and at least one manual release switch.
136 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
System Operation Smoke Alarm Verification
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 137
Section 11: Emergency Voice System Operation
11.1 Overview
The EVS series control panels and accessories provide features to meet the requirements for Mass Notification Systems as described in
NFPA 72 and is compliant with the UL 2572 standard. EVS (Emergency Voice System) is integrated with the fire alarm and voice evac-
uation functions of the control panel. n a networked panel system, only one panel can be chosen to be the voice evacuation/EVS panel
for the site
There are two ways for activating EVS in the 6820EVS panel:
EVS Point Activations
EVS Point Activation involves using pre-determined EVS Alarm input points to activate EVS Alarm events. These events cause output
areas to activate based on mapping that is programmed into the system at installation. This is very similar to the traditional mapping that
the fire system has utilized to date.
Manual LOC Activations
Manual LOC Activation involves using the LOC EVS interface to activate EVS Events, choose output areas, and speak through a micro-
phone. These selections are not pre-determined and allow the user to make system functionality decisions when the event is actually hap-
pening. This requires the activation of Manual EVS State which bypasses EVS Point Activations. See section 11.2.3.
2. If Microphone Mode is active (see Section 11.2.3), the Select Keys will toggle which areas the microphone audio is distributed to
(also toggles the green Select Key LED).
138 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Emergency Voice System Operation LOC Functionality
NOTE: These are only active when the microphone PTT (Push To Talk) is engaged.
READY
EVS CONTROL
TO TALK
Select
LEDs
Message
Keys
Message
Select LEDs
Keys
NOTE: The lockout timer must be programmed to expire sometime, other than Never.
2. The user at the second LOC requests EVS Control from the LOC with EVS Control and that LOC grants the request. (See Section
11.2.7). If the EVS lockout timer expires while an EVS Control request is in progress, the system will automatically pass EVS
Control to the requesting LOC.
3. The user at the second LOC enters an access code with the EVS Super User profile option.
The LOC lockout timer can be set between immediate and 12 hours in increments of 1 second or it can be set to never expire. The default
setting is 30 seconds. The LOC lockout timer is restarted upon any key press at the LOC with EVS control. The LOC lockout timer is
cleared when EVS Control is relinquished.
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 139
LOC Functionality Emergency Voice System Operation
140 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Emergency Voice System Operation EVS Super User
NOTE: In order to perform an EVS reset, the display must be associated with the EVS-VCM / EVS-RVM.
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 141
Amplifier Programming Emergency Voice System Operation
NOTE: Background Music is only allowed to be mapped to circuit 8 of the EVS-100W amplifiers to ensure correct active supervision.
142 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Emergency Voice System Operation Using the Microphone
The screen will display “Adding module [#]...” for a few moments. You will be returned to the <New Module Type> screen where
you can select a name for the module if desired.
6. Add a compatible LCD Annunciator, if desired, to associate with each EVS-VCM or EVS-RVM
You must save changes when you exit the Program Menu or the new module(s) will not be added. For more information see section
9.2.2.
NOTE: If you Add a Module that has not been physically connected, the panel will go into trouble after it re-initializes (when you exit the
Program Menu). When the new module is attached, the trouble will restore automatically the next time you power up the system.
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 143
Recording Custom Messages Emergency Voice System Operation
11.7.5 Paging
If there are no active emergency or fire system events, the microphone at an LOC can be used for paging by following these steps:
1. Remove the microphone from its cradle.
2. Press the push-to-talk button on the microphone.
3. Use the Select Keys on the LOC to toggle the output areas to page to with the microphone (illuminates the green LEDs).
NOTE: The Ready to Talk LED will illuminate after an output area has been activated.
4. Speak into the microphone.
5. Release PTT button when finished.
Message
Key 1
Message
Select Keys Key 3
1-15
Message
Key 8
Key Function
EVS Message Key 1 Select message slot to record to
EVS Message Key 3 Start and stop recording from Aux Audio Input
EVS Message Key 8 Erase user message 1-15
Select Keys 1-15 Message slot 1-15
144 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Emergency Voice System Operation Recording Custom Messages
While in the Local Record mode, select keys 1-15. Use these keys to reference message slots 1-15. The associated green Select Key will
indicate that a message is currently programmed in the corresponding slot. When there is no message recorded (or the message is
erased), the associated green Select Key LED will be off. While recording a particular message, the Red Select Key will turn on until
recording is completed. The Select Key 1-15 will be used to playback a recorded message or to select a message slot to record to or
erase.
When in the Local Record mode, the EVS-VCM LEDs will function as follows:
Switch LED Active LED Status Meaning
Select Key 1-15 Green LED On Message is currently programmed in this slot
Select Key 1-15 Red LED On Message recording is in progress
Select Key 1-15 Green/Red LED Off/Off Message slot is empty
Select Key 1-15 Red LED Flashing Message is being played back or message is selected for
recording
Table 11.1 LED Functions During Programming
11.8.1 Recording Messages 1-15 Using Aux Audio Input
Recording messages from the Aux Audio Input enables you to load customized, pre-recorded messages into an EVS message location.
Follow these steps to record user message using Aux Audio Input:
1. Wire a speaker cable with 1/8” mini plug (Radio Shack Cat. No. 42-2454) to the Aux AUDIO GND and IN terminals. Refer to
Figure 11.5.
Plug in here
6. Select the amplifier and circuit for the audio to play through during programming. A user would generally pick the audio circuit that
is in closest proximity to them.
7. Press EVS Message Key 1 to enter the message slot selection mode. Then, press the Select Key 1-15 that corresponds to the
message slot that you wish to record to. The associated Select Key red LED will begin flashing, indicating that the message slot is
ready for recording.
8. Simultaneously press EVS Message Key 3 and start playing the audio source on the PC or laptop.
9. When the audio file from the PC is finished playing, press EVS Message Key 3 again to stop the recording. The Select Key green
LED will come on.
10. To playback the recorded message, press the Select Key 1-15 that was just recorded to.
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 145
Recording Custom Messages Emergency Voice System Operation
Press EVS
Message Key
1 to enter message
slot selection mode
Press EVS
Press Message Key 3
Select Key 2 to start and stop
to record recording from
Message to the Aux Audio
this slot Input
5. Select the amplifier and circuit for the audio to play through during programming. A user would generally pick the audio circuit that
is in closest proximity to them.
6. Press EVS Message Key 1 to enter the message slot selection mode. Then, press the Select Key 1-15 that corresponds to the
message slot that you wish to record to. The associated Select Key red LED will begin flashing, indicating that the message slot is
ready for recording.
7. Press the push-to-talk (PTT) button on the microphone and speak your message.
8. Release the PTT button on the microphone to save your message. The Select Key green LED for this location will turn on.
9. To playback the recorded message, press the Select Key 1-15 that was just recorded to.
10. If you are not satisfied with the recorded message, erase it (see Section 11.8.3) and then repeat steps 1 through 7.
146 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Emergency Voice System Operation Recording Custom Messages
Press
EVS Message
Key to enter
message slot
Press selection mode
Select Key 5
to record to
this message
slot
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 147
Recording Custom Messages Emergency Voice System Operation
VCM
148 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Section 12: Reporting
This section lists receivers that are compatible with this control panel, and the reporting codes sent by the control panel for SIA and Con-
tact ID formats.
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 149
Receivers Compatible with the Control Panel Reporting
150 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Reporting Receivers Compatible with the Control Panel
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 151
Receivers Compatible with the Control Panel Reporting
152 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Reporting Receivers Compatible with the Control Panel
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 153
Receivers Compatible with the Control Panel Reporting
154 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Reporting Receivers Compatible with the Control Panel
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 155
Receivers Compatible with the Control Panel Reporting
156 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Reporting Receivers Compatible with the Control Panel
158 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Reporting SIA – Panel Communicator:
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 159
Section 13: Testing and Troubleshooting
13.1 Troubleshooting
This section of the manual offers suggestions for troubleshooting hardware problems. Please read this section if you encounter a problem
when installing the control panel. If these suggestions do not solve your problem or if you encounter a problem that is not listed here,
contact Honeywell Silent Knight Technical Support at 800-446-6444 for assistance.
Common Problems
Problem Possible Cause / Suggested Actions
Trouble message "DBL ADDR" (Double An address has been assigned to more than one detector. Correct the address following the
Address) displays on LCD. procedure described in Section 7.9 if using SD devices or Section 7.7 if using SK devices.
Auxiliary power or notification circuits have Correct polarity. For notification and auxiliary power circuits: When in alarm or powered,
incorrect polarity. terminals labeled “X” are positive, terminals labeled “O” are negative.
Check hardware connections.
If devices are physically connected, make sure wiring is correct (see Section 7.8 if using SD
devices or Section 7.6 if using SK devices). For the main panel, the positive side of device
must be connected to terminal 34; the negative side must be connected to Terminal 33. For
5815XL devices, make sure the device connects to the 5815XL via the SLC OUT terminals.
There can be only one SLC loop on the main panel and on each 5815XL module. Do not
SLC devices are not being recognized connect devices to terminals labeled SLC IN.
(trouble message "Missing" displays). Make sure SLC devices have been addressed properly following the procedure described in
Section 7.9 if using SD devices or Section 7.7 if using SK devices.
For contact monitor modules, which are addressed using DIP switches, the DIP switch must
be set to the correct address before power is applied to the SLC loop. If this procedure is not
followed, the device will have an incorrect address.
Make sure correct polarity has been observed for SLC device wiring. See Section 7.8 if using
SD devices or 7.6 if using SK devices.
Check that SLC loop impedance is within the required range.
To measure impedance, use the following procedure:
1. Disconnect both wires from the terminal block at the panel (SLC devices can remain
connected).
SLC devices are not being recognized 2. Measure the impedance from positive to negative and from negative to positive. Both
(trouble message “Missing” displays on measurements should be greater than 500 K ohms. If the installation uses T-taps, test
the annunciator). each T-tap individually.
3. Temporarily connect the positive wire to the negative wire of the SLC loop at the point
farthest from the panel (SLC devices can remain connected).
4. Measure the impedance from positive to negative and from negative to positive wires that
were disconnected from the panel in step 1. Both measurements must be less than 50
ohms.
An earth ground fault occurs when the panel senses an unexpected flow of current from one or
more of its terminals to the earth connection (Terminal 2).
Isolate the wiring that is causing the fault by removing wiring connections one at a time until
The panel indicates a ground fault trouble the earth fault is no longer present. Pause at least five seconds after removing a wire before
condition (trouble message “GROUND removing the next one.
FAULT” displays). The panel will also go into ground fault if a computer is connected to the panel via a serial
cable attached to the panel’s 9-pin connector. This is a correct method for on-site
communication between a panel and a computer. Ignore the ground fault message in this
case. The trouble will clear automatically when you disconnect the computer from the cable
Check the status of the 5815XL green LED. If it flashes in the pattern .5 sec. on / .5 sec. off, it
is likely that the 5815XL has not been added to the system through programming. JumpStart
will add any 5815XLs connected to the panel. If you have already run JumpStart, 5815XLs can
be added manually (see Section 9.2.2).
Check that the correct ID for the 5815XL module has been set through the DIP switches.
5815XL module that has been physically
Assign ID#1 to the first 5815XL and ID#2 to the second 5815XL. See Section 4.13.1 for
connected to the panel but is not being
complete details.
recognized.
If the wiring between the 5815XL and the panel is correct, measure the voltage from 5815XL
Terminal (+) to Terminal (-). Voltage should be in the range 27.2-27.4V when AC power is
present.
If the green LED is not flashing, the likely cause is incorrect wiring from between the 5815XL
and the panel. See Section 4.8.1 for wiring details.
Table 13-1 Troubleshooting Conditions
160 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Testing and Troubleshooting Periodic Testing and Maintenance
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 161
Built-in Troubleshooting and Testing Tools Testing and Troubleshooting
NOTE: Once you exit, the system will resume normal operation.
NOTE: Once you exit, the system will resume normal operation.
162 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Testing and Troubleshooting Built-in Troubleshooting and Testing Tools
6 + I/O 5 - - 0 0
7 – 0 0 - -
9 – 0 0 - -
10 + NAC 3 - - 0 0
11 – 0 0 - -
12 + NAC 2 - - 0 0
13 – 0 0 - -
14 + NAC 1 - - 0 0
15 – 0 0 - -
17 A - - 0 0
SBUS Power 18 + 0 0 - -
19 - - - 0 0
21 A - - 0 0
SBUS Power 22 + 0 0 - -
23 - - - 0 0
34 S+ 0 0 - -
35 SC- SLC IN - - 0 0
36 S+ 0 0 - -
EXT. COMM B - - 0 0
A - - 0 0
+ 0 0 - -
– - - 0 0
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 163
Section 14: Installation Records
This section of the manual is for you to use if you wish to track of how points, zones, and groups have been programmed.
164 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Installation Records Detector and Module Point Record
Module Addr Zone / Group Description Module Addr Zone/ Group Description
On-board 70 On-board 110
On-board 71 On-board 111
On-board 72 On-board 112
On-board 73 On-board 113
On-board 74 On-board 114
On-board 75 On-board 115
On-board 76 On-board 116
On-board 77 On-board 117
On-board 78 On-board 118
On-board 79 On-board 119
On-board 80 On-board 120
On-board 81 On-board 121
On-board 82 On-board 122
On-board 83 On-board 123
On-board 84 On-board 124
On-board 85 On-board 125
On-board 86 On-board 126
On-board 87 On-board 127
On-board 88
Table 14.1 : Installation Record of Onboard Devices
Additional SLC Devices
Use the table below to record devices installed on additional 5815XLs. Make a copy of this page if additional pages are needed.
Zone /
Module Addr Description Module Addr Zone/ Group Description
Group
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 165
Detector and Module Point Record Installation Records
Zone /
Module Addr Description Module Addr Zone/ Group Description
Group
Use the table below to record devices installed on additional SLC expanders. Make a copy of this page if additional pages are needed.
Module Addr Zone / Group Description Module Addr Zone/ Group Description
166 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Appendix A: Compatible Devices
A.1 Notification Appliances
For proper operation, you must use polarized devices with a 4.7k ohm EOL resistor on each loop. All supervised notification appliances
used with the control panel must be polarized.
NOTE: Not all devices can use the Sync feature, be sure to check table below to ensure the device you have chosen will work with this
feature. This control is UL listed for panel wide Synchronization.
Table below lists notification appliances compatible with the fire alarm control panel. Appliances which can be synchronized indicate
the type of SYNC available in the columns marked Audio and Visual.
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 167
Notification Appliances Compatible Devices
168 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Compatible Devices Notification Appliances
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 169
Notification Appliances Compatible Devices
170 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Compatible Devices Notification Appliances
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 171
Notification Appliances Compatible Devices
172 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Compatible Devices Two Wire Detectors
6820/EVS
Identifier 24H
17.1 - 27.3
Operating voltage Range
VDC
NOTE 1: The maximum number of smoke detectors per zone is determined by both the current draw and the impedance of the smoke
detector. If too many smoke detectors are used on any zone, false alarms could occur.
NOTE 2: Do not mix different models of detectors on any zone; false alarms could occur
NOTE 3: Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum reset time of the smoke
detector
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 173
Two Wire Detectors Compatible Devices
174 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Compatible Devices Four-Wire Smoke Detectors/Devices (UL Listed)
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 175
Door Holders (UL Listed) Compatible Devices
Current
Manufacturer Model Type
(mA)
176 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Compatible Devices Compatible 520Hz Signaling Speakers
6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020 177
Appendix B: Editing Text Using the Built-In Programmer
This section contains tables of programmable characters that may be used for device, module, site, template, group, and zone names or
phone numbers. T9 style editing is used.
yz9 Spc0
YZ9 Spc0
1 [ ]1 2 ( )2 3 . ,3 4 : ;4
5 ’ "5 6 ? !6 7 ‘ /7 8 – +8
9 = -9 0 0 *&@ * #$ #
178 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Appendix C: Expanded Receiver/Panel Relationship
The available receiver number will correspond with what panel number you entered. Receiver numbers are populated based on panel
number and audited to allow only the 4 appropriate receivers. See Section 6.2.6.
180 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Appendix D: Cadence Patterns
The cadence patterns shown in Appendix Appendix D: are available for use with the control panel.
181 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Notes
182 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer
warrants that the Products manufactured by it in its Northford, Connecticut facility
and sold by it to its authorized Distributors shall be free, under normal use and
service, from defects in material and workmanship for a period of thirty six months
(36) months from the date of manufacture (effective Jan. 1, 2009). The Products
manufactured and sold by Manufacturer are date stamped at the time of production.
Manufacturer does not warrant Products that are not manufactured by it in its
Northford, Connecticut facility but assigns to its Distributor, to the extent possible,
any warranty offered by the manufacturer of such product. This warranty shall be
void if a Product is altered, serviced or repaired by anyone other than Manufacturer
or its authorized Distributors. This warranty shall also be void if there is a failure to
maintain the Products and the systems in which they operate in proper working
conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY
AND ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH
RESPECT TO THE PRODUCTS, TRADEMARKS, PROGRAMS AND SERVICES
RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION,
INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR ANY
PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY
PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS
A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USES OF ITS
PRODUCTS.
This document constitutes the only warranty made by Manufacturer with respect to
its products and replaces all previous warranties and is the only warranty made by
Manufacturer. No increase or alteration, written or verbal, of the obligation of this
warranty is authorized. Manufacturer does not represent that its products will
prevent any loss by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion,
each part returned by its authorized Distributor and acknowledged by Manufacturer
to be defective, provided that such part shall have been returned to Manufacturer
with all charges prepaid and the authorized Distributor has completed Manufacturer's
Return Material Authorization form. The replacement part shall come from
Manufacturer's stock and may be new or refurbished. THE FOREGOING IS
DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A
WARRANTY CLAIM.
Warn-HL-08-2009.fm
183 6820 / 6820EVS Installation and Operation Manual P/N LS10144-001SK-E:D 3/24/2020
Honeywell Silent Knight
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
LS10144-001SK-E | D | 03/20
www.silentknight.com ©2020 Honeywell International Inc.
10.2 Radio Transmitter and Interface Panel SPEC 2.18.1
Features
Q Supports Fire and Mass Notification applications
Q Hardwire line or narrowband radio communication
with any D-21 system
– Narrowband radio is FCC certified for
narrowband operation and meets the requirements
of the NTIA (National Telecommunications and
Information Administration) Manual of
Regulations and Procedures for Federal
Frequency Management
Q Radio communication with the D-700
Q Provides eight onboard relay driver outputs and four
FM
supervised fire zone inputs that can be connected to a
APPROVED
fire alarm control panel
Q Optional Relay Board adds eight Form C relays
Q Relays provide automatic or manual control of local
or remote devices such as turning on pumps based on Ordering Information
timed events, input from a fire alarm control panel, or Part Number Description
manually activated from the D-21
227-600-xx BT-XF, 4–28 zones, narrowband radio; 20 inch
Q
Single-wide enclosure supports up to three expansion high x 12 inch wide x 4 inch deep single-wide
backplanes or two expansion backplanes and one enclosure; one 12 Ah battery; specify frequency
BT-X relay board; double-wide enclosure supports 227-601-xx BT-XF, 4–28 zones, narrowband radio; 20 inch
up to seven zone expansion backplanes or six high x 12 inch wide x 4 inch deep single-wide
NEMA 3R enclosure; one 12 Ah battery;
expansion backplanes and one BT-X relay board specify frequency
Q Each expansion backplane supports two fire
227-603-xx BT-XF, 4–60 zones, narrowband radio; 20 inch
expansion cards high x 25 inch wide x 4 inch deep double-wide
Q Each BT-X fire expansion card provides four zone enclosure; two 12 Ah batteries; specify
inputs that can be connected to a fire alarm control frequency
panel and eight relay driver outputs 227-605-00 BT-XHF, 4–28 zones, hardwire communication
via installed audio board; 20 inch high x 12 inch
Q
Onboard and expansion card status LEDs wide x 4 inch deep single-wide enclosure; one
Q
One selectable RS-422/RS-485 port 12 Ah battery
Q
RS-232 port 227-607-00 BT-XHF, 4–28 zones, hardwire communication
Q
115 or 230 Vac power monitored with automatic via installed audio board; 20 inch high x 12 inch
wide x 4 inch deep single-wide NEMA 3R
switch-over to backup battery power enclosure; one 12 Ah battery
Q Battery backup is provided with each BT-X unit. One
227-606-00 BT-XHF, 4–60 zones, hardwire communication
or two 12 volt batteries can be installed in each BT-X, via installed audio board; 20 inch high x 25 inch
depending on the power requirements of the wide x 4 inch deep double-wide enclosure; two
transceiver. 12 Ah batteries
Q
Self test, stuck transmitter disconnect, reset, 176-212-00 BT-X expansion backplane
acknowledge, and battery reconnect switches 176-206-00 BT-X fire expansion card provides 4 zone inputs
Q Local audible alert (2 per backplane) and 8 relay outputs
Q Real-time clock and calendar 176-208-00 Audio Board Kit for hardwire communication
Q
1/2 Mb of program memory 176-214-00 BT-X relay board with 8 onboard Form C relays
Q 1/2 Mb of non-volatile data storage 513-412-00 BT-X enclosure tamper switch kit
Q Factory Mutual approved
Batteries
Ordering Information
Part Number Description
Enclosure with Batteries
081-155-00 Two 12V / 18 Ah batteries in an 18-inch × 12-inch × 6-inch NEMA 1 battery enclosure for use with Monaco M-1 and
M-2 Panels, Vulcan 1, C-99A, and C-100A
081-156-00 Two 12V / 26 Ah batteries in an 18-inch × 12-inch × 6-inch (45.7 × 30.5 × 15.2 cm) red enclosure for use with Monaco
M-1 and M-2 Panels, Vulcan 1, C-99A, and C-100A
081-177-00 Two 12V / 40 Ah batteries in a 20-inch × 16-inch × 8-inch (50.8 × 40.6 × 20.3 cm) red enclosure for use with M-1 and
M-2 panels and Vulcan 1
081-182-00 Two 12V / 75 Ah batteries in a 10-inch x 22-inch x 8.5 inch (25.4 x 55.9 x 21.6 cm)
Enclosure With Batteries
081-172-00 20-inch × 16-inch × 6-inch deep NEMA 3R enclosure with four 12V / 18Ah batteries
Batteries Without Enclosures
400-603-00 6V / 1 Ah, 2-inch × 1.65-inch × 2.3-inch (5.1 × 4.2 × 5.6 cm), 0.6 lbs (0.3 kg), 0.187-inch × 0.032-inch tab
400-701-00 12V / 26 Ah, 6.89-inch × 6.54-inch × 4.92-inch (17.5 × 16.6 × 12.5 cm), 18.7 lbs (8.5 kg), 0.250-inch × 0.032-inch tab
400-703-00 12V / 1.2 Ah, 3.82-inch × 1.65-inch × 2.95-inch (19.5 × 4.7 × 7.5 cm), 1.3 lbs (1.4 kg), 0.187-inch × 0.032-inch tab
400-704-00 12V / 7.7 Ah, 5.95-inch × 2.58-inch × 3.95-inch (15.1 × 6.6 × 10 cm), 5.6 lbs (2.5 kg), 0.187-inch × 0.032-inch tab
400-716-00 12V / 75 Ah, 10.25-inch × 6.6-inch × 9.45-inch (26 × 16.8 × 24 cm), 39.7 lbs, nut & bolt terminals
400-717-00 12V / 100 Ah, 12-inch × 6.6-inch × 9.45-inch (30.5 × 16.8 × 24 cm), 50 lbs (22.7 kg), nut & bolt terminals
400-719-00 12V / 14 Ah, 8.5-inch × 2.75-inch × 5.5-inch (21.6 × 7 × 14 cm), 10.2 lbs (4.6 kg)
400-712-00 12V / 18 Ah, 7.22-inch × 3.34-inch × 6.7-inch (18.3 × 8.5 × 17 cm), 13.6 lbs (6.2 kg), 0.32-inch × 0.25-inch tab
400-713-00 12V / 12 Ah, 5.94-inch × 3.86-inch × 3.7-inch (15.1 × 9.8 × 9.4 cm), 9.0 lbs (4.1 kg), 0.250-inch × 0.032-inch tab
400-714-00 12V / 40 Ah, 7.72-inch × 6.42-inch × 6.85-inch (19.6 × 16.3 × 17.4 cm), 30.5 lbs (13.8 kg), nut & bolt terminals
Ordering Information
Tower Mount, P/N 199-014-01
Part Number Description
199-012-00 Adjustable 45–60 inches, heavy-duty, pair of
The antenna is engineered for eaves mounts. Use with up to 1.5-inch mast.
strength with Pre-Zinc tubing. Lag bolts included.
199-010-00 4-inch, pair of wall mounts. Lag bolts included.
It is pre-galvanized for long life, Use with up to 1.5-inch mast.
with baked aluminum paint.
199-011-00 7-inch, heavy-duty, pair of wall mounts. Lag
bolts included. Use with up to 1.75-inch mast.
Hardware is heat treated and
cadmium plated. Single bolt 199-008-00 3-foot, heavy duty, tripod mount. Use with up
holes make erection quick and to 1.75-inch mast.
easy. 199-013-00 Accessory pad kit for tripod mount. Includes
three pitch pads and six 2-inch by 1/4-inch lag
bolts.
199-014-01 Forty-two-foot antenna tower kit. Includes
three tower sections, a top section with
1.25-inch × 5-foot mast, one 12-inch
adjustable house bracket, one motor mount,
and all assembly hardware.
199-020-00 Tower section, 10-foot optional addition for
P/N 199-014-01
199-031-00 Spare tower top section
199-021-00 Tower 12-inch adjustable house bracket for
P/N 199-020-00
199-022-00 Tower hinged base for flat roof or ground
foundation. Towers must be bracketed or
guyed. For use with P/N 199-014-01.
199-023-00 Tower non-hinged base. For use with
P/N 199-014-01.
199-024-00 20–24 inch adjustable bracket for connecting
tower to building. Use with P/N 199-014-01.
199-025-00 24–33 inch adjustable bracket for connecting
tower to building. Use with P/N 199-014-01.
Installation Diagrams
Typical lightning arrestor installation where building grounding system is accessible and adequate
Notes
1. Lightning arrestor to be connected to
main building ground per NFPA 70 (NEC)
Article 810-21.
Control
MDP BT
Panel
See Note 1
Typical lightning arrestor installation where lightning risk is high or the building grounding system is questionable
Notes
1. If risk of lightning is high (refer to
Mast: 1 EMT or rigid conduit NFPA 78, Appendix I), or the building
grounding system is questionable, an
Lightning arrestor
auxiliary lightning grounding electrode
with enclosure is recommended. Refer to NFPA 70,
Article 250.
7 inch wall Coaxial cable
mounts 2. For complete installation details, refer
1 inch
to the installation manuals and applicable
ground codes and standards.
clamp Detail
Features
TrueAlarm® analog sensing provides digital
transmission of analog sensor values via
MAPNET II® or IDNet™, two-wire communications**
Fire alarm control panel provides:
x Individual sensitivity selection for each sensor
x Sensitivity monitoring that satisfies NFPA 72®
sensitivity testing requirements
x Peak value logging allowing accurate analysis for
sensitivity selection 4098-9714 TrueAlarm Photoelectric
Sensor Mounted in Base
x Automatic, once per minute individual sensor
calibration check that verifies sensor integrity
Description
x Automatic environmental compensation
x Display of sensitivity directly in percent per foot Digital Communication of Analog Sensing.
TrueAlarm analog sensors provide an analog
x Multi-stage alarm operation measurement that is digitally communicated to the host
x Ability to display and print detailed sensor control panel using Simplex addressable communications.
information in plain English language At the control panel, the data is analyzed and an average
Photoelectric smoke sensors: value is determined and stored. An alarm or other
abnormal condition is determined by comparing the
x Seven levels of sensitivity from 0.2% to 3.7% sensor’s present value against its average value and time.
Heat sensors:
Intelligent Data Evaluation. Monitoring each sensor’s
x Fixed temperature sensing average value provides a continuously shifting reference
x Rate-of-rise temperature sensing point. This software filtering process compensates for
environmental factors (dust, dirt, etc.) and component
x Utility temperature sensing aging, providing an accurate reference for evaluating new
Ionization smoke sensors: activity. With this filtering, there is a significant reduction
x Three levels of sensitivity; 0.5%, 0.9% and 1.3% in the probability of false or nuisance alarms caused by
shifts in sensitivity, either up or down.
For use with Simplex®:
x 4010, 4020, 4100, 4100U, and 4120 Series control Control Panel Selection. Peak activity per sensor is
stored to assist in evaluating specific locations. The alarm
panels set point for each TrueAlarm sensor is determined at the
x Universal Transponders and 2120 TrueAlarm CDTs host control panel, selectable as more or less sensitive as
equipped for MAPNET II operation the individual application requires.
Magnetic test feature Timed/Multi-Stage Selection. Sensor alarm set points
Functional and architecturally styled chamber can be programmed for timed automatic sensitivity
enclosure: selection (such as more sensitive at night, less sensitive
during day). Control panel programming can also provide
x Louvered design enhances smoke capture by directing multi-stage operation per sensor. For example, a 0.2%
flow to chamber level may cause a warning to prompt investigation while a
x Entrance areas are minimally visible when ceiling 2.5% level may initiate an alarm.
mounted Sensor Alarm and Trouble LED Indication. Each
Optional accessories include remote LED alarm sensor base’s LED pulses to indicate communications
indicator and output relays with the panel. If the control panel determines that a
UL listed to Standard 268 sensor is in alarm, or that it is dirty or has some other type
of trouble, the details are annunciated at the control panel
* Refer to page 4 for ULC listing status. These products have been approved by the and that sensor base’s LED will be turned on steadily.
California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California During a system alarm, the control panel will control the
Health and Safety Code. See CSFM Listings 7272-0026:218, 7271-0026:231, 7270-
0026:216, and 7300-0026:217 for allowable values and/or conditions concerning LEDs such that an LED indicating a trouble will return to
material presented in this document. It is subject to re-examination, revision, and pulsing to help identify the alarmed sensors.
possible cancellation. Accepted for use – City of New York Department of Buildings –
MEA35-93E. Additional listings may be applicable, contact your local Simplex product ** TrueAlarm analog sensors are protected by one or more of the following U.S. Patents:
supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. 5,155,468; 5,173,683; 5,400,014; 5,543,777; 5,710,541; D383,407; D388,352; D392,573.
are the property of Tyco Safety Products Westminster. MAPNET II and IDNet addressable communications designs are protected by U.S. Patent
No. 4,796,025.
S4098-0019-9 9/2003
TrueAlarm Sensor Bases and Accessories Description
Sensor Base Features TrueAlarm sensor bases contain integral addressable
electronics that constantly monitor the status of the
Base mounted address selection:
detachable photoelectric, ionization, or heat sensors. Each
x Address remains with its programmed location sensor’s output is digitized and transmitted to the system
x Accessible from front (dipswitch under sensor) fire alarm control panel every four seconds.
Automatic identification provides default sensitivity Since TrueAlarm sensors use the same base, different
when substituting sensor types sensor types can be easily interchanged to meet specific
Integral red LED for power-on (pulsing), or alarm or location requirements. This feature also allows intentional
trouble (steady on) sensor substitution during building construction. When
Locking anti-tamper design conditions are temporarily dusty, instead of covering the
Magnetically operated functional test smoke sensors (causing them to be disabled), heat sensors
Mounts on standard outlet box may be installed without reprogramming the control
panel. Although the control panel will indicate an
Sensor Bases incorrect sensor type, the heat sensor will operate at a
4098-9792, Standard sensor base default sensitivity providing heat detection for building
4098-9789, Sensor base with wired connections for:
protection at that location.
x 2098-9808 Remote LED alarm indicator or Mounting Reference
4098-9822 relay (unsupervised)
4098-9791, Sensor base with supervised relay driver
output (not compatible with 2120 CDT): Electrical Box Requirements: (boxes are by others)
Without relay: 4" octagonal or 4" square, 1-1/2" deep;
x Relay operation is programmable and can be manually single gang, 2" deep
operated from control panel With relay : 4" octagonal or 4" square, 1-1/2" deep,
x Use with remote mount 2098-9737 relay with 1-1/2" extension ring
x Also includes wired connections for remote LED 4" (102 mm) Square Box 4" (102 mm) Octagonal Box
alarm indicator or 4098-9822 relay Surface mount reference
TrueAlarm Bases
4098-9789, -9791, & -9792
2 S4098-0019-9 9/2003
TrueAlarm Sensors 4098-9714 Photoelectric Sensor
Features TrueAlarm photoelectric sensors use a stable, pulsed
Sealed against rear air flow entry infrared LED light source and a silicon photodiode
receiver to provide consistent and accurate low power
Interchangeable mounting
smoke sensing. Seven levels of sensitivity are available
EMI/RFI shielded electronics for each individual sensor, ranging from 0.2% to 3.7% per
Heat sensors: foot of smoke obscuration. Sensitivity is selected and
x Selectable rate compensated, fixed temperature monitored at the fire alarm control panel.
sensing with or without rate-of-rise operation The sensor head design provides 360° smoke entry for
x Spacing distance between heat sensors: optimum response to smoke from any direction. A built-in
screen keeps insects from entering the smoke chamber.
Fixed Temp. FM Spacing, Either Fixed
Setting
UL Spacing
Temperature Setting
Due to its photoelectric operation, air velocity is not
normally a factor, except for impact on area smoke flow.
15 ft x 15 ft (4.6 m) fixed
135° F (57.2° C) 60 ft (18.3 m)
temperature only;
4-7/8" (124 mm)
30 ft x 30 ft (9.2 m) fixed
155° F (68° C) 40 ft (12.2 m)
temperature with rate-of-rise
2-3/8"
(60 mm)
Application Reference
4098-9733 Heat Sensor with Base
Sensor locations should be determined only after careful
consideration of the physical layout and contents of the
WARNING: In most fires, hazardous levels of smoke area to be protected. Refer to NFPA 72, the National Fire
and toxic gas can build up before a heat detection Alarm Code®. On smooth ceilings, smoke sensor spacing
device would initiate an alarm. In cases where Life of 30 ft (9.1 m) may be used as a guide. For detailed
Safety is a factor, the use of smoke detection is highly application information, refer to 4098 Detectors, Sensors,
recommended. and Bases Application Manual (574-709).
3 S4098-0019-9 9/2003
!
255385
Rev. C3 0718
Printed in U.S.A.
© Copyright 2018 Federal Signal Corporation
!
!
!
1! TABLE!OF!CONTENTS!
!
Section! ! ! ! ! ! ! ! ! ! ! ! Page!
!
1! TABLE!OF!CONTENTS!....................................................................................................!3!
2! SAFETY!MESSAGE!.........................................................................................................!6!
3! GENERAL!DESCRIPTION!................................................................................................!9!
3.1! Model!Number!Descriptions!.....................................................................................!10!
3.2! Recommended!Cables.............................................................................................!10!
3.3! UVRI!Part!Locations:................................................................................................!11!
3.4! Initial!Configuration!..................................................................................................!13!
3.5! Programming!Methods!.............................................................................................!18!
3.6! Status!Monitoring!.....................................................................................................!18!
4! SPECIFICATIONS!..........................................................................................................!19!
4.1! Electrical!..................................................................................................................!19!
4.2! Power!Supply!...........................................................................................................!19!
4.3! Battery!......................................................................................................................!20!
4.4! Relay!Output!............................................................................................................!20!
4.5! Control!Board!(2005698901)!....................................................................................!20!
4.6! Controller!Front!Panel!Controls,!Jacks,!Switches!and!Indicators!.............................!21!
4.7! Motherboard!(2005320)!...........................................................................................!26!
4.8! Environmental!..........................................................................................................!28!
4.9! Physical!....................................................................................................................!28!
5! UVRI!OPERATION!.........................................................................................................!29!
5.1! Hardware!General!Description!.................................................................................!29!
5.2! Manual!Activation!.....................................................................................................!29!
5.3! Local!Public!Address................................................................................................!30!
5.4! Relay!Output!............................................................................................................!30!
5.5! Sensor!Inputs!...........................................................................................................!30!
5.6! Two9Way!Status!Monitoring!.....................................................................................!31!
5.7! Quiet!Test!................................................................................................................!32!
5.8! DC!Power!Supply!.....................................................................................................!32!
6! SYSTEM!PLANNING!......................................................................................................!33!
6.1! Control!Unit!..............................................................................................................!33!
7! INSTALLATION!...............................................................................................................!34!
7.1! UVRI!Controller!Installation!Reference!Drawings!....................................................!34!
7.2! General!Mounting!Guidelines!...................................................................................!37!
7.3! UVRI!Installation!Material!List!and!Installation!Guidelines!.......................................!37!
7.4! Installer!Supplied!UVRI!Electrical!Installation!Material!List!......................................!41!
7.5! Electrical!Connections..............................................................................................!42!
7.6! Remote!System!Sense!Input!...................................................................................!44!
7.7! Landline!Control!Connection!....................................................................................!45!
7.8! Ethernet!Connection!................................................................................................!45!
7.9! Antenna!Types!.........................................................................................................!45!
3!
!
7.10! Remote!Mounted!Magnetic!Base!Antenna!Installation.............................................!45!
8! PRE9OPERATION!CHECKOUT!AND!TEST!...................................................................!46!
8.1! Visual!Inspection!......................................................................................................!46!
8.2! Pre9Operation!Checkout!..........................................................................................!46!
8.3! Radio!Transceiver!Adjustment!Procedure!................................................................!47!
8.4! Control!and!Status!Monitoring!..................................................................................!48!
9! MAINTENANCE!..............................................................................................................!50!
9.2! Troubleshooting!.......................................................................................................!53!
10! OPTIONS!....................................................................................................................!54!
10.1! Radio!Control!...........................................................................................................!54!
10.2! Digital!Voice!Recording!............................................................................................!54!
10.3! Installation!of!User!Supplied!Radio!Receivers!.........................................................!54!
10.4! Model!UVRI9IP!.........................................................................................................!55!
11! Final!Assembly!Drawing!and!Parts!List!.......................................................................!60!
!
!
4!
!
TABLE!OF!FIGURES!
!
Figure!3.1!9!UVRI!Inside!View!................................................................................................!11!
Figure!3.2!9!UVRI!Parts!Layout!..............................................................................................!12!
Figure!4.1!9!Motherboard!Outline!Drawing!.............................................................................!27!
Figure!7.1!9!Typical!UVRI!Installation!Drawing!.......................................................................!34!
Figure!7.2!9!UVRI!Cabinet!Dimensional!Outline!Drawing!.......................................................!35!
Figure!7.3!9!UVRI!Wiring!Diagram!..........................................................................................!36!
Figure!7.4!9!UVRI!Remote!System!Sense,!Audio!Output!and!DC!Power!Connections!..........!44!
Figure!7.5!9!Relay!Output!.......................................................................................................!44!
Figure!8.1!9!Field!Test!Data!Sheet!.........................................................................................!49!
Figure!9.1!9!UVRI!Motherboard!Connections!.........................................................................!52!
Figure!9.2!9!UVRI!Battery!Location!and!Cover!Plate!Mounting!Screws!..................................!52!
Figure!11.1!9!UVRI!Final!Assembly!and!Parts!List!.................................................................!60!
5!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
2! SAFETY!MESSAGE!
It!is!important!to!follow!all!instructions!shipped!with!this!product.!This!device!is!to!be!
installed!by!trained!personnel!who!are!thoroughly!familiar!with!the!country!electric!codes!
and!will!follow!these!guidelines!as!well!as!local!codes.!
!
Listed!below!are!important!safety!instructions!and!precautions!you!should!follow.!
!
Important!Notice!
!
Federal!Signal!reserves!the!right!to!make!changes!to!devices!and!specifications!
detailed!in!the!manual!at!any!time!in!order!to!improve!reliability,!function!or!design.!The!
information!in!this!manual!has!been!carefully!checked!and!is!believed!to!be!accurateb!
however,!no!responsibility!is!assumed!for!any!inaccuracies!
!
PUBLICATIONS!
!
Federal!Signal!recommends!the!following!publications!from!the!Federal!Emergency!
Management!Agency!for!assistance!with!planning!an!outdoor!warning!system:!
!
•! The!“Outdoor!Warning!Guide”!(CPG!1917)!
•! “Civil!Preparedness,!Principles!of!Warning”!(CPG!1914)!
•! FEMA9REP91,!Appendix!3!(Nuclear!Plant!Guideline)!
•! FEMA9REP910!(Nuclear!Plant!Guideline)!
!
PLANNING!
!
•! If!suitable!warning!equipment!is!not!selected,!the!installation!site!for!the!siren!is!not!
selected!properly!or!the!siren!is!not!installed!properly,!it!may!not!produce!the!
intended!optimum!audible!warning.!Follow!Federal!Emergency!Management!Agency!
(FEMA)!recommendations.!
!
•! If!sirens!are!not!activated!in!a!timely!manner!when!an!emergency!condition!exists,!
they!cannot!provide!the!intended!audible!warning.!It!is!imperative!that!
knowledgeable!people,!who!are!provided!with!the!necessary!information,!are!
available!at!all!times!to!authorize!the!activation!of!the!sirens.!
!
•! When!sirens!are!used!out!of!doors,!people!indoors!may!not!be!able!to!hear!the!
warning!signals.!Separate!warning!devices!or!procedures!may!be!needed!to!
effectively!warn!people!indoors.!
!
•! The!sound!output!of!sirens!is!capable!of!causing!permanent!hearing!damage.!To!
prevent!excessive!exposure,!carefully!plan!siren!placement,!post!warnings,!and!
restrict!access!to!areas!near!sirens.!
!
6!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
•! Activating!the!sirens!may!not!result!in!people!taking!the!desired!actions!if!those!to!be!
warned!are!not!properly!trained!about!the!meaning!of!siren!sounds.!Siren!users!
should!follow!FEMA!recommendations!and!instruct!those!to!be!warned!of!correct!
actions!to!be!taken.!
!
•! After!installation,!service,!or!maintenance,!test!the!siren!system!to!confirm!that!it!is!
operating!properly.!Test!the!system!regularly!to!confirm!that!it!will!be!operational!in!
an!emergency.!
!
•! If!future!service!and!operating!personnel!do!not!have!these!instructions!to!refer!to,!
the!siren!system!may!not!provide!the!intended!audible!warning!and!service!
personnel!may!be!exposed!to!death,!permanent!hearing!loss,!or!other!bodily!injury.!
File!these!instructions!in!a!safe!place!and!refer!to!them!periodically.!Give!a!copy!of!
these!instructions!to!new!recruits!and!trainees.!Also!give!a!copy!to!anyone!who!is!
going!to!service!or!repair!the!siren.!
!
!
INSTALLATION!&!SERVICE!
!
•! Electrocution!or!severe!personal!injury!can!occur!when!performing!various!
installation!and!service!functions!such!as!making!electrical!connections,!drilling!
holes,!or!lifting!equipment.!Therefore!only!experienced!electricians!should!install!this!
product!in!accordance!with!national,!state!and!any!other!electrical!codes!having!
jurisdiction.!Perform!all!work!under!the!direction!of!the!installation!or!service!crew!
safety!foreman.!
!
•! The!sound!output!of!sirens!is!capable!of!causing!permanent!hearing!damage.!To!
prevent!excessive!exposure,!carefully!plan!siren!placement,!post!warnings!and!
restrict!access!to!areas!near!the!sirens.!Sirens!may!be!operated!from!remote!control!
points.!Whenever!possible,!disconnect!all!siren!power!including!batteries!before!
working!near!the!siren.!
!
•! After!installation!or!service,!test!the!siren!system!to!confirm!that!it!is!operating!
properly.!Test!the!system!regularly!to!confirm!that!it!will!be!operational!in!an!
emergency.!
!
•! If!future!service!personnel!do!not!have!these!warnings!and!all!other!instructions!
shipped!with!the!equipment!to!refer!to,!the!siren!system!may!not!provide!the!
intended!audible!warning!and!service!personnel!may!be!exposed!to!death,!
permanent!hearing!loss,!or!other!bodily!injury.!File!these!instructions!in!a!safe!place!
and!refer!to!them!periodically.!Give!a!copy!of!these!instructions!to!new!recruits!and!
trainees.!Also,!give!a!copy!to!anyone!who!is!going!to!service!or!repair!the!sirens.!
!
!
!
!
7!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
OPERATION!
!
Failure!to!understand!the!capabilities!and!limitations!of!your!siren!system!could!result!in!
permanent!hearing!loss,!other!serious!injuries!or!death!to!persons!too!close!to!the!
sirens!when!you!activate!them!or!to!those!you!need!to!warn.!Carefully!read!and!
thoroughly!understand!all!safety!notices!in!this!manual!and!all!operations9related9items!
in!all!instruction!manuals!shipped!with!equipment.!Thoroughly!discuss!all!contingency!
plans!with!those!responsible!for!warning!people!in!your!community,!company,!or!
jurisdiction.!
WARNING!
!
Read!and!understand!the!information!contained!
in!this!manual,!before!attempting!to!install!or!!
service!this!product.!
!
Pay!careful!attention!to!the!following!notices!located!on!the!equipment.!
!
A.!NOTICES!M!EXTERNALLY!PLACED!
!
!
!
!
!
B.!NOTICESMINTERNALLY!PLACED!
!
! ! !
8!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
3! GENERAL!DESCRIPTION!
!
The!UltraVoice!Remote!Interface!(UVRI)!provides!remote!control!and!status!monitoring!
of! Fire! Alarm! and! PA! systems! to! create! a! fully! integrated! indoor! and! outdoor! Mass!
Notification!System!when!used!with!the!Federal!Commander!Digital!Control!System.!The!
UVRI! has! a! built9in! radio! transceiver! interface,! an! RS232! port,! and! optional! ethernet,!
satellite,! and! telephone! line! interfaces! for! tying! into! communication! networks.! Built9in!
warning!tone!generation,!live!voice!and!up!to!8!minutes!of!local!digital!voice!storage!is!
included!in!all!models.!!
!
The! UVRI! is! housed! in! a! non9metalic! indoor/outdoor! NEMA4X! /! UL50! rated! enclosure!
suitable!for!wall!mounting.!
!
Features:!
•! 12VDC!Operation!
•! Seven!standard!warning!signals!
•! Single!tone,!Two9tone,!DTMF,!EAS!and!MSK!decoders!for!remote!siren!control!
•! Integrated!MSK!radio!modem!with!1289bit!encryption!over!radio!or!wire!!
•! Local!pushbutton!control!for!7!control!functions!
•! Local!microphone!input!
•! Up!to!8!minutes!of!digital!voice!storage!
•! Integrated!radio!modem!
•! RS232!port!
•! 29Tone!and!DTMF!decoders!
•! Radio!Transceiver!option!
•! Ethernet!interface!option!
•! 29Way!Satellite!option!
•! Scrolling!Message!Display!option!
•! Dedicated!telephone!line!option!
•! Programmable!radio!receiver!for!Low!Band,!VHF,!or!UHF!(optional)!
•! Windows®!based!siren!programming!software!(optional)!
•! Diagnostic!LEDs!
•! Quiet!Test!Diagnostics!–!Checks!tone!generator!with!20KHz!tone!
•! Remotely!adjustable!line!level!audio!output!
•! DPDT!10!amp!relay!output!
•! Battery!backup!with!built9in!power!supply/battery!charger!and!low!voltage!cutoff!
•! Activation!Test!–!Monitors!tone!generator!and!remote!contact!closure!input!
•! Stackable!siren!functions!enable!user!pre9defined!warning!scenarios!
•! Programmable!over!wireless!radio!channel!using!SFCDWARE!
•! NEMA4X!/!UL50!rated!enclosure!with!padlock!hasp!
9!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
3.1! Model!Number!Descriptions!
!
All!UVRI!models!are!set!up!for!29way!control!and!status!monitoring!using!the!Federal!
Commander!Digital!Control!system.!All!models!include!8!minutes!of!digital!voice!
storage.!Custom!digital!voice!recording!requires!a!model!DVR.!!
!
!
!CONTROLLER!OPTIONS!! !!!!!!!UVRI!MODEL!#!
NO!RADIO!(RF)! UVRI!
!UHF!BAND!Transceiver! UVRIU!
!HIGH!BAND!Transceiver! UVRIH!
Landline!Control! UVRI9LL!
Ethernet!Control! UVRI9IP!
Satellite!Control! UVRI9ISAT!
!
Option!Exclusions:!
!
The!UVRI9IP!and!UVRI9SAT!options!cannot!be!used!with!any!other!options!listed!above!
at!the!same!time.!
3.2! Recommended!Cables!
When!equipped!with!a!Vertex!Radio!(Model!VX92100)!in!your!two9way!RTUs,!Federal!
Signal!recommends!purchasing!the!following!cables!for!computer!programming:!
!
•! RIB!FIF912A!USB!interface!cable!
•! CT9104A!interface!cable!
Use!the!RIB!FIF912A!USB!cable!to!connect!to!your!computer.!Use!the!CT9104A!cable!
to!connect!from!the!RIB!FIF912A!USB!cable!to!the!radio.!
!
GENERAL!DESCRIPTION!
10!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
3.3! UVRI!Part!Locations:!
!
!
!
Figure!3.1!M!UVRI!Inside!View!
! !
GENERAL!DESCRIPTION!
11!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
! Power!Supply!
Transceiver!
Out!
120VAC!Sensor!Relay!
Fuses (240VAC!w/9240!option)!
!
AC!Input!
Local!Activation!Buttons!
Audio!Out!
OuytOut! Antenna!Bulkhead!
BiulBulkhead!
Relay!Output! Ground!
OupOutput! Lug!
!!!!! !
Figure!3.2!M!UVRI!Parts!Layout!
!
GENERAL!DESCRIPTION!
12!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
3.4! Initial!Configuration!
!
Each!modular!UVRI!controller!contains!the!following!configuration!parameters!that!must!
be! initially! configured.! Additional! programming! configuration! is! required! before! placing!
the! UVRI! into! service.! Refer! to! the! programming! software! reference! manual! for!
programming!information.!
!
1.! Unit!Type!
2.! RF!Frequency!
3.! Security!Key!
4.! 1289bit!Encryption!Key!
5.! Unit!Address!(see!below)!
6.! Configuration!Jumper!Settings!
!
3.4.1! Unit!Type!
!
The!UVRI!unit!type!is!used!to!tell!the!front9end!control!system!how!to!communicate!with!
the! UVRI.! This! is! configured! within! the! Federal! Commander! software! and! sent! to! the!
UVRI.!
!
3.4.2! RF!Frequency!
!
The!radio!transceiver!must!be!programmed!with!the!RF!frequency(s),!channel!spacing!
and!power!output!before!placing!into!service.!These!settings!will!be!pre9set!at!the!factory!
if!the!requirements!are!provided!with!the!order.`!
!
If! a! 19way! radio! receiver! is! used! with! the! UVRI,! the! RF!frequency! must! be! configured!
using!Federal!Signal!configuration!software!and!sent!to!the!UVRI!to!put!the!receiver!on!
the! correct! RF! frequency.! The! frequency! must! stay! within! the! correct! RF! band! for! the!
model!purchased.!The!receiver!will!need!re9alignment!if!the!frequency!is!changed!from!
the!factory!provided!setting.!!
!
3.4.3! Security!Key!!
!
The!Security!Key!is!a!unique!number!assigned!to!the!system!that!prevents!nearby!
systems!operating!on!the!same!RF!frequency!from!interfering.!Like!the!1289bit!
encryption!key,!the!Security!Key!is!programmed!during!the!flashing!of!the!
microprocessor!and!must!match!the!key!used!at!the!control!point.!All!sites!in!the!system!
must!use!the!same!security!key.!The!exception!is!a!key!value!of!65535!(the!default),!
defined!as!an!“open”!system!and!will!communicate!with!all!encoders!regardless!of!the!
encoder’s!key!setting.!
GENERAL!DESCRIPTION!
13!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
3.4.4! 128Mbit!Encryption!Key!
!
1289bit!data!encryption!provides!security!against!malicious!operation!or!monitoring.!The!
1289bit!key!is!programmed!during!the!flashing!of!the!microprocessor!and!must!match!
the!encoder!(SS2000+!or!SFCDWARE)!being!used!to!activate!the!unit.!A!key!value!of!
zero!disables!1289bit!encryption!and!must!be!used!if!the!encoder!does!not!support!1289
bit!encryption.!All!sites!in!the!system!must!use!the!same!encryption!key.!
!
3.4.5! Unit!Address!!
!
Site!Address!Switch:!
!
The!unit!address!sets!the!UVRI!site!number!and!is!used!to!numerically!identify!the!site!
within!the!system!network.!The!Unit!Address!is!a!three9digit!number!with!a!range!of!0019
1023.!The!unit!address!is!set!via!dip!switch!S1.!S1!Off!position!indicates!active!position.!
Add!binary!active!switch!positions!to!get!ID!address.!!
!
! !
Switch!! ! !
No.! 1! 2! 3! 4! 5! 6! 7! 8! 9! 10!
! !
Binary!! ! !
No.! 1! 2! 4! 8! 16! 32! 64! 128! 256! 512!
!!
Example:!The!illustration!above!shows!Switch!numbers!1,!2!&!3!in!the!active!position.!
The!switch!in!the!example!above!represents!the!binary!numbers!1,!2!&!4,!which!when!
added,!would!equal!unit!address!7.!
!
Note:!The!address!must!be!set!to!address!(one)!to!program!a!controller!board!to!program!
a! DTMF,! non9digital! unit.! When! the! programming! is! completed,! change! the! dip! switch!
setting!to!the!actual!site!address.!Programming!details!are!in!the!Commander!software!
manual.! The! site! address! is! stored! when! power! is! applied! to! the! controller.! If! the! site!
GENERAL!DESCRIPTION!
14!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
address!is!changed,!cycle!power!to!the!control!board!by!removing!the!connector!at!JP3!
on!the!motherboard!for!five!seconds.!
3.4.6! Control!Board!Configuration!Jumper!Settings!
!
JP12!9!Short!to!force!radio!Carrier!Detect!of!External!transceiver!1!
•! Jumper!out!=!Default!Setting!
!
!
JP9!9!External!Transceiver!#1!VOX!(Audio!level!dependent!Carrier!Detect)!
•! Jumper!OFF!=!VOX!Disabled!(Default!setting)!
•! Jumper!ON!=!Carrier!detect!in!<!20mS!when!received!audio!exceeds!15%!
deviation.!
!
!
JP10!9!Dual!receiver!priority!jumper:!
•! Jumper!"EXT"!side!to!give!external!receiver!#1!priority!
•! Jumper!"INT/EXT2"!side!to!give!on9board!receiver!or!external!receiver!#2!priority!!
•! Jumper!neither!side,!first!carrier!detect!has!priority!
! ! ! ! ! !
!
JP7!–!600!Ohm!Audio!Output!
•! Jumper!pins!2!and!3,!Output!radio!transmit!audio!(Default!Setting)!
•! Jumper!pins!1!and!2,!Output!siren!audio!
!
!
JP6!–!600!Ohm!Audio!Input!
•! Jumper!pins!2!and!3,!Input!audio!to!decoders!as!from!a!receiver!(Default!Setting)!
•! Jumper!pins!1!and!2,!Input!audio!to!Amps!when!600!Ohm!PTT!is!asserted.!
!
!
!
!
!
GENERAL!DESCRIPTION!
15!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
3.4.7! User!Programs!
!
The!UVRI!has!the!capacity!to!store!up!to!fifty!(50)!user!programs.!Each!user!program!
contains!the!following!elements:!
!
1)! Optional!DTMF!Activation!Code!!
2)! Optional!Two9Tone!Activation!Code!
3)! Optional!EAS!Event!Code!
4)! POCSAG!code!
5)! Digital!activation!Code!
6)! List!of!up!to!20!functions!
!
The!ability!to!assign!more!than!one!function!to!each!activation!code!or!user!program!is!a!
new! feature! not! previously! found! in! electronic! sirens.! This! allows! the! user! to! run! a!
sequence! of! functions! without! sending! additional! activation! commands,! greatly!
enhancing! flexibility! while! reducing! operator! involvement! and! communication! channel!
traffic.!!
!
3.4.8! Available!Functions:!!
!
Arm!
Disarm!
Report!
Master!Reset!
Cancel!
PA!Output!
Quiet!Test!
Low!Power!Mode!
Hi!Power!Mode!
Zone!A!(Not!used!with!UVRI)!
Zone!B!(Not!used!with!UVRI)!
Zone!C!(Not!used!with!UVRI)!
Zone!D!(Not!used!with!UVRI)!
Wail!
Pulsed!Wail!
Alt!Wail!
Steady!
Pulsed!Steady!
Alt!Steady!
Auxiliary!(Chime)!
Delay!
Digital!Voice!(19250)!
Amp/Audio!Zone!Control!(Not!used!with!UVRI)!
GENERAL!DESCRIPTION!
16!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
Power!
Report!
Record!PA!Message!
Play!Recorded!PA!Message!
RelayN!On!(Not!used!with!UVRI)!
RelayN!Off!(Not!used!with!UVRI)!
!
3.4.9! Low!Power!Mode,!Hi!Power!Mode!
!
This!causes!the!siren!to!operate!at!a!greatly!reduced!volume!level.!Upon!activation!of!a!
user!program,!the!siren!defaults!to!Hi!(normal)!volume!level.!This!command!must!follow!
an! ARM! command.! Reduced! volume! mode! will! remain! in! effect! for! all! subsequent!
functions!in!a!user!program!that!follow!the!Low9Power!function!or!until!a!Hi9Power!function!
occurs!or!an!ARM!command!is!sent.!
!
3.4.10!Delay!!
!
The!delay!function!causes!the!siren!to!pause!(wait)!for!2!9!512!seconds!before!starting!
the!next!function!of!the!user!program!currently!running.!When!selecting!the!delay!function,!
the!user!will!be!prompted!to!enter!the!desired!delay!time!in!seconds.!A!default!delay!of!4!
seconds!is!present!between!functions,!without!adding!a!delay.!
!
3.4.11!Power!Level!
!
The!Power!function!allows!the!user!to!control!the!volume!level.!The!volume!can!be!
adjusted!from!0!to!920!dB!in!1!dB!steps.!Reduced!volume!mode!will!remain!in!effect!for!
all!subsequent!functions!in!a!user!program!that!follow!the!Power!function,!or!until!
another!Power!function!occurs,!or!an!ARM!command!is!sent.
GENERAL!DESCRIPTION!
17!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
3.5! Programming!Methods!
!
There!are!two!methods!of!entering!and!reviewing!the!user!programming!information!in!an!
UltraVoice!electronic!siren!controller:!
!
1.! FSPWARE! Windows®! based! programming! software! for! 29tone! and! DTMF!
controlled!systems.!This!software!requires!a!direct!connection!between!the!siren!
and!the!computer’s!RS232!port.!
!
2.! SFCDWARE!Windows®!based!digital!control!and!status!monitoring!software.!This!
software!may!be!used!over!a!landline!or!wireless!radio!channel!as!well!as!over!an!
RS232!port.!!
!
Detailed!information!on!the!operation!of!the!Windows®!program!is!beyond!the!scope!of!
this!document!and!can!be!found!in!the!software’s!Help!file.!!
!
3.6! Status!Monitoring!
!
The!UVRI!monitors!various!diagnostic!conditions!for!reporting!back!to!a!central!monitoring!
station!using!optional!control!and!status!monitoring!hardware!and!software.!
!
3.6.1! Items!monitored!
Siren!Type!
Function!State!(code!running)!
Unit!ID!
Audio!A*!
Audio!B*!
Master!Current!/!Remote!System!Operation*!
Battery!Voltage!
Charger!
AC!Power!
Control!Box!Intrusion!
False!Alarm/Local!Activation*!
*Latched! Items! 99! remain! set! until! reception! of! a! Reset! command! or! another!
function!is!run.!
!
Status! information! is! transmitted! either! as! a! DTMF! or! FSK! data! string! over! the!
communications! channel! and! as! an! ASCII! string! over! the! RS232! port.! Report! back!
transmission!will!occur!when!one!of!two!conditions!exist:!
!
1.! Reception!of!a!REPORT!command!!!!!!or!
!
2.! One!of!the!asynchronous!status!conditions!changes!state.!
GENERAL!DESCRIPTION!
!
18!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
4! SPECIFICATIONS!
!
4.1! Electrical!!
!
Battery!Voltage! On!at!11.5!VDC!/!off!at!10!VDC,!
13.7!volts!(nom.)!
!
! Battery!Current! ! ! ! ! <!80!mA.!standby!current,!
! ! ! ! ! ! ! ! <!120!mA!during!a!function!
! ! ! ! ! ! ! ! <7A!during!radio!transmit!
! Stand!By!Time!(with!minimum!
59minute!full!signal!reserve)! ! ! Greater!than!24!hours!!
(With!radio!transceiver,!10!W,!
8!Tx!/!day)!
4.2! Power!Supply!
! !
! AC!Input! ! ! ! ! ! 889264!VAC,!50960!Hz,!!
! !
! Input!Current!(115/230!VAC)! ! ! 2.2/1.2!A!
! !
! DC!Output! ! ! ! ! ! 13.5916.5VDC!(14VDC!Nom.),!7A!
! !
! Immunity! ! ! ! ! ! IEC610009492,93,94,95,96,98,911!
! !
! Conducted/Radiated!EMI! ! ! ! EN55011/EN550229B,!FCC9B!
! !
! Terminal!Block!Wiring! ! ! ! 14922!AWG!
! !
! Terminal!Block!Torque! ! ! ! 191.4!Nm!torque!
SPECIFICATIONS!
!
19!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
4.3! Battery!
!
! Rating:! ! ! ! ! ! 12!V,!12!A/H!
! !
Type:! PowerSonic!PS129120l!Absorbed!
Glass!Matt!Valve!Regulated!Lead!
Acid!(AGM!9!VRLA)!
!
CAUTION:!!Substituting!batteries!may!be!hazardous!and!will!void!warranty.!!
Use!specified!batteries!only.!
!
4.4! Relay!Output!
!
Contacts!! ! ! ! ! ! DPDT,!28!VDC,!277!VAC,!10!A!!
4.5! Control!Board!(2005698M01)!
4.5.1! Serial!&!I2C!Ports!
!
! Serial!Port!Protocol! ! ! ! ! RS232C!1200,N,8,1!
! I2C!Port!Protocol! ! ! ! ! Philips!Standard!I2C!
4.5.2! Signaling!Formats!
!
! Number!of!codes! ! ! ! ! Up!to!50!activation!codes!maximum!
!
Number!of!Functions!allowed!stacked! ! Up!to!20!
! under!each!code! !
!
!
! Two9Tone!Sequential!or!Single!Tone! ! 282!Hz!9!3000!Hz!
0.5!sec!(A)!9!.25!sec!(B)!minimum!
to!8!sec!maximum!
!
! DTMF!! ! ! ! ! ! 3!to!12!digits!standard!
! ! ! ! ! ! ! ! 50!ms/50!ms!timing!or!greater!
FSK!
Baud!rate! ! ! ! ! 1200!bps!
Modem!type! ! ! ! ! MSK!(minimal!shift!key)!
Mark!frequency! ! ! ! 1200!Hz!
Space!frequency! ! ! ! 1800!Hz!
Error!checking! ! ! ! 16!bit!CRC!
SPECIFICATIONS!
!
20!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
EAS! ! ! ! ! ! ! AFSK,!520.83!baud
! Modem!Tones! ! ! ! 2083.3!Hz!and!1562.5!Hz!
!
POCSAG!
Supports!Binary!frequency!shift!keyed,!512!Baud!numeric!messages.!
!
4.6! Controller!Front!Panel!Controls,!Jacks,!Switches!and!Indicators!
!
4.6.1! Controls:!
!
DV!GAIN! Internal!Digital!Voice!Level!sufficient!to!drive!
TP3!or!TP4!into!clipping!
!
TX!GAINs! Transmitted!Audio!outputs!adjustable!from!!
50!mV!to!1!Vpp!
!
! EXTERNAL!REC!GAINs! Received!Audio!Level!inputs!300!mV!to!3!Vpp! !
! !
! MIC!GAIN! Local! PA! Level! range! sufficient! to! drive! amplifiers!
into!clipping!w/50!mV!nominal!input!level!
4.6.2! Jacks:!
! ! !
! MIC! ! ! ! ! 10!k!ohms!input!impedance,!! ! !
! ! ! ! ! ! 50!mV!nominal!input!level!
! ! !
! External!Transceivers! ! External!Transceiver!Connectors!Pins!!
Upper!and!Lower:!!!!
1!! RX!Audio!in,!300!mVpp!to!3!Vpp!!
2!! TX!Audio!out,!50!mVpp to!3!Vpp
3!! Carrier!Detect,!<!1!VDC!for!active!!
4!! PTT,!Active!low,!will!sink!500!mA!max.
5,7!! 8!VDC!for!Radio,!1.0!Amps!max.!!
6,8!! Ground,!1.5!Amps!max.!Current
!
! !
Serial!Port!9!Lower! ! ! 8!Pin!Serial!Port:!
2!! Digital!Receive!/!Serial!Port!Not!!!!
3!! TX!Data!!!!
4!! RX!Data!!!!
5!! Ground!!!
6!! SCK!Microcontroller!Programming!Line!!!
SPECIFICATIONS!
!
21!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
7!! Microcontroller!Reset
!
Serial!Port!9!Upper! ! ! 8!Pin!Auxiliary!Serial!Port:!
3! TX!Data!!!!
4!! RX!Data!!!!
5!! Ground!!!
!
! I2C! ! ! ! 5!volts!peak9to9peak!+/9!1!volt!input!! ! !
! ! ! ! ! 5!volts!DC!+/9!.2!volts!250!mA!!! ! ! !
! ! ! ! ! Ground!250!mA!maximum!sink! !
! !
4.6.3! Manual!Activation!Switches:! !
! ! ! ! ! QTY!8,!activate!with!a!hold!time!>0.50!seconds!
!
4.6.4! Indicators:!
!
! RXD! ! ! ! Receive!Serial!Data!&!receipt!of!! ! ! !
! ! ! ! ! radio!channel!modulation!
!
! TXD! ! ! ! Transmit!Serial!Data!&!DTMF!&!Digital!
!
! AUDIO!A! ! ! Audio!present!on!Channel!A!
!
! AUDIO!B! ! ! Audio!present!on!Channel!B!!
!
! ARM! ! ! ! Unit!Armed!indicator!
!
! PA! ! ! ! Public!Address!mode!indicator!
!
! CPU! ! ! ! Microprocessor!Heartbeat!
!
! CARRIER! ! ! RF!Carrier!indicator!on!w/carrier!present!
!
RECEIVE!LEVEL! ! 3!stage!LED!bar!graph!
!
SPECIFICATIONS!
!
22!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
4.6.5! Control!Unit!Connector!Configuration!
!
! Connectors!for!2005698M01!PCB!
! CONNECTOR!!!
DESIGNATION!!!!!!!!!!!!!!!! PURPOSE!!!!!!!! ! !
J2! ! ! ! Microphone!jack!
1! k!!input!impedance,!
50!mVP9P nominal!input!level.
!
! JP1! ! ! ! microSD!FLASH!card!holder!
1! NC!
2! Slave!Select!Not!
3! Master!Out!/!Slave!In!
4! Switched!3.3V!power!
5! Serial!Clock!
6! Ground!
7! Master!In!/!Slave!Out!
8! NC!
!
JP4! ! ! ! Options!Connector:!
! ! ! ! ! ! 1! microcontroller!Input!
! ! ! ! ! ! 2! Ground! !!
!
JP3! ! ! ! On9Board!Receiver!Module!Connector!Pins:!!!!
1!! Ground!
2!! +8!VDC!
3!! Clock!
4! Data!!!!
5!! Latch!Enable!
6!! Carrier!Detect!Not!
7!! De9Emphasized!Receive!Audio!
8!! Flat!Receive!Audio!
!
JP4! ! ! ! SINAD!Sensor!Input!Pins:!
! ! ! ! ! ! 1! Ground!
! ! ! ! ! ! 2! Sensor!Input!
!
JP5! ! ! ! Backplane!
48!pin!EPT!male!card!edge!connector!
!
JP6! ! ! ! 600!Ohm!Input!Configuration!Jumper!Pins:!!
293!!!!! 600!Ohm!audio!in!to!receiver!decoders!!!
192!!!!! Audio!from!600!Ohm!sent!to!Amps!
when!600!Ohm!PTT!is!closed!
!
SPECIFICATIONS!
!
23!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
JP7!! ! ! ! 600!Ohm!Output!Configuration!Jumper!Pins:!
! ! ! ! ! 192!! Output!siren!audio!
! ! ! ! ! ! 293! Output!radio!transmit!audio!
!
! JP8!! ! ! ! CTCSS!Connector!Pins:!!!!
1!! RX!Audio!in!!
2!! Ground!!!!
3!! 8!VDC!for!CTCSS!board!!!
4!! Audio!Switch!!!!
5!! TX!CTCSS!tone!
!
! JP9! ! ! ! Transceiver!#1!VOX!Jumper!
! ! ! ! ! ! Jumpered!to!use!VOX!for!Carrier!Detect!
!
JP10! ! ! ! Dual!receiver!priority!jumper!
Jumper!"EXT"!side!to!give!external!receiver!#1!priority!
! Jumper!"INT/EXT2"!side!to!give!on9board!receiver!or!
!external!receiver!#2!priority.!
! ! ! ! ! Jumper!neither!side,!first!carrier!detect!has!priority!
!
JP11! ! ! ! Jumpered!when!SINAD!option!is!used!
!
JP12! ! ! ! Short!to!force!Carrier!Detect!of!External!transceiver!1!
!
JP13! ! ! ! External!Transceiver!Connector!Pins!!
Upper!and!Lower:!!
1!! RX!Audio!in!
Receive!audio!level!for!300!m!VP9P!to!3!!
VP9P!to!make!1!VP9P!at!TP16!
2!! TX!Audio!out!
50!mVP9P!to!3!VP9P!
3!! Carrier!Detect!!
<!1!VDC!for!active!!
4!! PTT!!
Active!low,!will!sink!500!mA!max.
5,7!! 12!VDC!for!Radio!!
+/9!0.2!Volts,!1.0!Amps!max.!
6,8!! Ground!
1.5!Amps!max.!Current!capacity
!
!
!
!
!
!
SPECIFICATIONS!
!
24!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
P19Lower! ! ! 8!Pin!Serial!Port:!
2! Digital!Receive!/!Serial!Port!Not!
3!! TX!Data!!!!
4!! RX!Data!!!!
5!! Ground!!!
6!! SCK!Microcontroller!Programming!Line!!!
7!! Microcontroller!Reset
!
P19Upper! ! ! 8!Pin!Auxiliary!Serial!Port:!
3!! TX!Data!
4!! RX!Data!
5!! GND!!!! !
SPECIFICATIONS!
!
25!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
4.7! Motherboard!(2005320)!
!
JP1!–!Relay!Output!Control! ! ! 1!A,!30!VDC!
1!9!ground!
2!9!switched!10!9!15!Volts!! ! ! (Switches!on!when!a!function!is!active)!
!
JP2!9!Switched!Radio!Power!Output! ! 10!A,!30!VDC!
1!9!ground!
2!9!switched!10!9!15!Volts! (Switches!on!when!control!board!is!
operating!above!low!voltage!cutoff!point)!
JP3!–!12VDC!Power!Input!
1!9!ground!
2!9!11!9!15!Volts!
!
JP4!–!Audio!Signal!Output!
1!9!ground!
2!9!signal!
Output!voltage!Swing!! ! ! >4.5!V!Peak!to!Peak!
Maximum!Load! ! ! ! 2K!Ohms!
Total!Harmonic!Distortion! ! ! <!10%!w/!1KHz!Sine9wave!
!
JP5!–!Control!Board!Connection!
!
JP6!–!Sensor!Inputs!
1.! GND!
2.! Activation!Detect!(SPR#1)!
3.! GND!
4.! Intrusion!
5.! GND!
6.! Solar!
7.! GND!
8.! AC!
9.! GND!
10.!PTT!
11.!GND!
12.!Spare!(SPR#2)!
SPECIFICATIONS!
!
26!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
JP7!9!Audio!Channel!Select!Jumper!
•! Jumper!pins!1!&!2!to!select!channel!A!
•! Jumper!pins!2!&!3!to!select!channel!B!
!
JP8!9!Charger!Sense!Input!
! 1!9!ground!
! 2!9!charger!input!
!
Fuses!
! (F1)!Relay!Coil!at!JP1! ATO,!1!A,!32!VDC!
! (F2)!12!VDC!Radio!at!JP2! ATO,!10!A,!32!VDC!
!
!
!
!
Figure!4.1!M!Motherboard!Outline!Drawing!
SPECIFICATIONS!
!
27!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
4.8! Environmental!
!
! Operating!Temperature! ! ! 913°F!to!140°F!/!925°C!to!+60°C!
! Humidity! ! ! ! ! 0998%!non9condensing!
!
Notes:!
1.! The!UVRI!can!operate!throughout!this!temperature!range!provided!the!
battery!temperature!is!maintained!at!918°C!or!higher.!
2.! The!UVRI!housing!carries!a!NEMA!4X!/!UL50!rating!
!
4.9! Physical!
!
! Enclosure! ! ! ! ! 16"!x!15"!x!893/8"!(H!x!W!x!D)!
! 40.64!cm!x!38.1!cm!x!21.27!cm!
!
! Weight! ! ! ! ! 29.6!lb!/!13.43!kg!(including!battery)!
!
SPECIFICATIONS!
!
28!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
5! UVRI!OPERATION!
!
5.1! Hardware!General!Description
!
All!relay!control,!audio!generation!and!remote!communication!functions!are!handled!by!a!
single! microcontroller! board.! The! back9plane! (motherboard)! contains! connectors! and!
terminal!blocks!for!interconnection!to!other!system!components.!!
!
The! UVRI! receives! remote! control! signals! and! responds! to! the! Federal! Commander!
remote! monitoring! system! to! provide! live! and! recorded! voice,! warning! tones,! and! a!
remote!control!relay!contact!output.!The!UVRI!provides!a!contact!closure!to!activate!the!
remote!system!and!provide!an!audio!output!at!JP4!on!the!motherboard.!
!
Operation!is!supervised!and!status!information!is!transferred!back!to!the!control!station(s)!
via!one!or!more!available!communications!networks.!The!UVRI!monitors!the!audio!output!
level! and! the! Remote! Activation! input! on! the! motherboard! at! JP692! to! verify! proper!
operation.!Remote!Fire!Alarm!and!PA!systems!provide!a!contact!closure!across!JP691!
and!JP692!to!indicate!proper!operation.!
!
The!controller!can!be!powered!from!12VDC!and/or!120!or!240!VAC.!!
!
5.2! Manual!Activation!
!
The!manual!activation!switches!located!on!the!face!of!the!controller!are!used!to!manually!
activate!siren!functions.!
Function!Switch! Function!
FUNC1! Activates!Functions!under!code!1!
FUNC2! Activates!Functions!under!code!2!
FUNC3! Activates!Functions!under!code!3!
FUNC4! Activates!Functions!under!code!4!
FUNC5! Activates!Functions!under!code!5!
FUNC6! Activates!Functions!under!code!6!
FUNC7! Activates!Functions!under!code!7!
FUNC8! Reset!
FUNC5!&!FUNC7! Digital!Transmit!Deviation!tone!
!
NOTE:!At!any!time!during!a!sounding!function!the!"RESET"!button!may!be!pushed!to!
cause!the!unit!to!halt!all!output!immediately.!
UVRI!OPERATION!
!
29!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
5.3! Local!Public!Address!
!
The!operator!has!the!ability!to!give!local!Public!Address!(PA)!messages!using!the!model!
MNC9MC!microphone!provided.!PA!mode!can!be!entered!simply!by!pressing!the!push9
to9talk!(PTT)!button!on!the!MIC!while!the!MIC!is!plugged!into!the!¼"!receptacle!on!the!
front!panel.!The!PA!LED!will!be!lit!anytime!the!PTT!button!on!the!microphone!is!pressed.!
The!local!PA!volume!level!is!set!by!adjusting!the!MIC!GAIN!knob!located!directly!above!
the!MIC!jack.!
!
NOTE:!Local!PA!overrides!ALL!siren!functions!activated!either!remotely!or!locally.!
!
5.4! Relay!Output!
!
A!DPDT!relay!output!is!located!in!a!socket!at!the!bottom!of!the!control!cabinet.!This!relay!
closes!whenever!a!alert!tone,!digital!or!live!voice!message!is!active!and!can!be!used!to!
trigger!remote!devices.!!
!
5.5! Sensor!Inputs!
!
Terminal!block!JP6!on!the!motherboard!accepts!contact!closure!inputs.!These!inputs!are!
activated!by!a!short!to!“Common”.!
!
Sensor!Connections!
!
JP15! Function!
Terminal!
1! “Common”!
2! Remote!Activation!
“Spare!#1”!
3! “Common”!
4! “Intrusion”!
5! “Common”!
6! “Solar”!
7! “Common”!
8! “AC!Power”!
9! “Common”!
10! “600!PTT”!
11! “Common”!
12! “Spare!#2”!
!
!
UVRI!OPERATION!
30!
!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
5.5.1! Intrusion! !
! Alerts!the!controller!when!one!of!the!unit’s!doors!has!been!opened.!!
!
5.5.2! Solar:!Used!to!sense!operation!of!solar!power!system.!
! Jumper!JP15:!pins!5!to!6!and!to!enable!solar!sensing.!Solar!mode!latches!power!
sense!to!prevent!low!light!conditions!from!causing!failures.!For!solar!panel!test,!
initiate!a!reset,!and!then!a!poll.!Immediate!good!power!input!required!after!a!reset!
to!pass.!!
! Jumper!JP15!pins!7!to!8!AC!sense!is!required!if!solar!only!unit.!
!
5.5.3! Spare#1! !
Remote!system!operation!detect.!Shorting!this!input!verifies!that!the!remote!
system!is!active.!
!
5.5.4! Spare!#2!
Unused!inputs!for!special!functions.!
!!
5.5.5! AC!Power!!! !
Alerts!the!controller!when!the!AC!Power!has!failed.!Open!is!fail.!Closed!is!pass.!
!
5.5.6! 600!Ohm!PTT!!! !
Puts!the!unit!in!Local!PA!mode!for!input!of!external!audio.!Closed!is!active!
!
5.6! TwoMWay!Status!Monitoring!!
!
The!UVRI!uses!a!variety!of!sensors!in!the!UVRI!Series!Controller,!which!when!equipped!
with!a!two9way!radio,!allows!the!remote!unit!to!communicate!its!status!back!to!the!base!
station.!This!reduces!station!downtime!by!quickly!alerting!operating!personnel!to!potential!
problems!at!remote!units.!!
The!following!status!points!are!monitored:!
1.! AC!Power!(AC!sense!relay)!
2.! Battery!Voltage!(built!in)!
3.! Charger!Operation!(built!in)!
5.! Signal!A!!(built!in)!
6.! Signal!B!!(built!in)!
7.! Remote!System!Operation!(Motherboard!JP691&2)!!
8.! Intrusion!!
UVRI!OPERATION!
31!
!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
5.7! Quiet!Test!
!
This!option!enables!acoustically!quiet!tests!to!be!performed!on!the!UVRI!control!and!the!
remotely! controlled! devices.! Quiet! Test! uses! a! 20! kHz! tone! to! quietly! test! the! tone!
generators!and!the!remote!amplifiers!(if!applicable).!To!perform!this!test!the!Quiet!Test!
must!be!programmed!under!one!of!the!activation!codes.!If!it!is!one!of!the!first!7!codes!
then! it! can! be! activated! manually! through! the! switches! on! the! front! panel! or! with! the!
remote!activation!inputs.!Normally!once!the!Quiet!Test!is!programmed!under!one!of!the!
activation!codes,!the!code!is!activated!over!the!radio!channel,!the!panel!switches,!or!with!
a!local!laptop!computer!running!SFCDWARE.!!
!
A.! Operation!
!
The!results!of!a!Quiet!Test!can!be!obtained!remotely!using!the!SS2000+!printout!or!the!
SFCDWARE! control! and! status! monitoring! software.! The! status! can! also! be! obtained!
locally! at! the! siren! site! with! a! portable! computer! running! SFCDWARE.! The! actual!
amplifier!voltage!and!current!are!monitored!with!Quiet!Test!providing!a!true!indication!of!
each!amplifier!and!load!performance.!
!
B.! Finding!Faults!
!
When!using!SFCDWARE,!the!controller!will!automatically!update!the!Quiet!Test!status!
each! time! a! new! Quiet! Test! is! run.! The! status! can! be! obtained! from! the! status! detail!
screen!and!from!the!Reports!menu.!
!
5.8! DC!Power!Supply!
!
A!13.5916.5VDC!(13.8VDC!Nom.),!7A!supply!provides!a!constant!voltage!current!limited!
charging!system!for!the!integrated!12V!battery!and!power!for!peripheral!equipment.!
!
UVRI!OPERATION!
32!
!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
6! SYSTEM!PLANNING!
!
6.1! Control!Unit!
!
Select!a!suitable!mounting!location!that!is!secure,!and!away!from!high!voltage!wiring!and!
high!power!RF!systems.!The!Control!Unit!can!be!mounted!indoors!or!outdoors!depending!
on!what!equipment!it!will!be!connected!to!as!long!as!the!unit!is!kept!within!the!operating!
temperature!limits.!
!
Refer! to! the! specification! section! to! obtain! the! weight! of! the! UVRI.! Insure! that! the!
mounting!surface!and!fasteners!can!safely!sustain!the!weight!of!the!assembly.!
!
In! order! to! reduce! the! possibility! of! introducing! noise! in! the! audio! path,! the! controller!
should!be!placed!as!close!as!possible!to!the!Fire!Alarm!or!remote!PA!system.!
!!
The!controller!should!be!located!out!of!the!reach!of!vandals.!The!controller!is!supplied!
with!padlock!hasps!that!will!accept!user!provided!padlocks!for!security.!
!
The!UVRI!requires!a!120!VAC!or!240!VAC!50960!Hz!power!source!to!power!the!UVRI!
and!charge!the!internal!12V!battery.!
!
Several! methods! can! be! used! to! activate! the! Control! Unit.! Plan! how! the! UVRI! will! be!
connected!to!the!antenna!system!or!wired!communications!network.!
!
If!radio!control!is!going!to!be!used,!consider!RF!coverage!and!antenna!placement!when!
selecting!a!suitable!location.!
!
SYSTEM!PLANNING!
33!
!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
7! INSTALLATION
!
WARNING!
!
Read!all!Safety!Notices!at!the!beginning!of!this!manual!before!installation.!
!
This!section!contains!reference!drawings!to!assist!with!installation.!A!list!of!typical!
installation!materials!required!may!be!obtained!by!reviewing!the!cabinet!mounting!
details!and!the!electrical!installation!material!list!below.!
!
7.1! UVRI!Controller!Installation!Reference!Drawings!
!
!
!
Figure!7.1!M!Typical!UVRI!Installation!Drawing!
INSTALLATION!
34!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
!
!
!
!
Figure!7.2!M!UVRI!Cabinet!Dimensional!Outline!Drawing!
INSTALLATION!
35!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
!
Figure!7.3!M!UVRI!Wiring!Diagram!
INSTALLATION!
36!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
7.2! General!Mounting!Guidelines!
!
These! general! installation! instructions! are! pertinent! to! all! installations.! Specific!
mounting! methods! and! required! installation! materials! are! described! in! the! next!
section.!
!
1.! There!are!four!cabinet!mounting!flanges!available!for!bolting!the!UVRI!to!a!flat!surface,!
(see!Figure'7.2).'!
!
2.! The!total!weight!of!the!UVRI!is!listed!in!the!specifications!section.!It!is!imperative!that!
the!mounting!surface!and!mounting!method!selected!can!safely!sustain!the!weight!of!
the!assembly.!!
!
3.! Prepare!the!mounting!surface!for!hanging!the!cabinet!by!predetermining!the!location!
of!the!mounting!holes.!The!cabinet!should!be!attached!to!a!wall!or!other!substantial!
vertical!surface!using!the!four!mounting!flanges.!Lag!bolt!the!cabinet!to!the!wall!using!
the!prepared!holes!and!anchors.!
!
4.! If!the!UVRI!model!being!installed!has!a!29way!radio,!ensure!the!radio!antenna!cable!
is!installed!before!applying!power!to!the!UVRI!to!avoid!damaging!the!radio.!
!
7.3! UVRI!Installation!Material!List!and!Installation!Guidelines!
!
The!following!material!lists!and!guidelines!describe!basic!installation!details!required!
to!install!the!UVRI!cabinet.!This!list!will!vary!depending!on!mounting!methods,!other!
options,!local!and!national!electrical!codes,!etc.!Therefore,!this!list!should!be!used!
as!a!reference!guideline!only.!!
!
Concrete!or!Filled!Cement!Block!
Wall!Mounting!Materials!
! ! !
Material! Purpose! Qty!
Description!
¼"!x!2"!Pin/Sleeve/! Anchor! !
Lock!Washer/Nut! Bolts! 4!
Style!Anchors!
INSTALLATION!
37!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
7.3.1! Concrete!or!Filled!Cement!Block!Wall!Mounting!Guidelines:!
!
1.! Mark!the!mounting!hole!locations!on!the!wall!for!the!cabinet.!
2.! Install!the!anchor!bolts!for!the!four!cabinet!corners!according!to!the!manufacturer’s!
instructions.!
3.! Mount!the!cabinet!to!the!wall.!
4.! Proceed!to!following!section.!
Note:'If'wall'is'not'straight,'use'shims'to'insure'enclosure'maintains'square'and'structural'
integrity.'
!
Hollow!Block!Wall!Mounting!Materials!
Material! ! !
Description! Purpose! Qty!
¼"!x!2"!Heavy!Duty! Anchor! !!4!
Toggle!Bolts! Bolts!
7.3.2! Hollow!Block!Wall!Mounting!Guidelines:!
!
1.! Mark!the!mounting!hole!locations!on!the!wall!for!the!cabinet.!
!
2.! Install! the! anchor! bolts! for! the! four! cabinet! corners! according! to! the! manufacturer’s!
instructions.!
!
3.! Mount!the!cabinet!to!the!wall.!
!
4.! Proceed!to!following!section.!
! !
INSTALLATION!
38!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
Wood!Stud!Wall!Mounting!
Materials!
Material! ! !
Description! Purpose! Qty!
¼"!x!1"!Lag! Backboard!&! 8!
bolts! cabinet!
mounting!bolts!!
2'!x!2'!x!¾"! Mounting! 1!
B/C!or!better! backboard!
plywood!
Construction! Mounting! 1!
adhesive!! backboard!
attachment!
7.3.3! Wood!Stud!Wall!Mounting!Guidelines:!
!
1.! Locate!the!wall!studs!for!attaching!the!mounting!backboard!to!the!wall.!The!backboard!
should!attach!to!at!least!two!studs.!
!
2.! Mark!the!wall!stud!location!on!the!mounting!backboard!and!drill!four!pilot!holes!for!the!
lag!bolts.!
!
3.! Apply!construction!adhesive!to!the!back!of!the!mounting!backboard.!
!
4.! Attach!the!mounting!backboard!to!the!wall!with!four!lag!bolts.!!
!
5.! Locate!the!mounting!position!of!the!cabinet!on!the!mounting!backboard.!
!
6.! Drill!pilot!holes!for!the!lag!bolts.!
!
7.! Mount!the!cabinet!to!the!mounting!backboard.!
!
8.! Proceed!to!the!following!section.!
! !
INSTALLATION!
39!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
Metal!Stud!Wall!Mounting!Materials!
Material! ! !
Description! Purpose! Qty!
¼"!x!2"!lag!bolts! Cabinet! 4!
mounting!
bolts!!
2'!x!¾"!x!2'!B/C!or! Mounting! 1!
better!plywood backboard!
#14!x!2"!metal! Backboard! 6!
stud!screws! mounting!
Construction! Backboard! 1!
adhesive!! mounting!
!
7.3.4! Metal!Stud!Wall!Mounting!Guidelines:!
!
1.! Locate!the!wall!studs!for!attaching!the!Mounting!Backboard!to!the!wall.!!
!
2.! Mark!the!wall!stud!location!on!the!mounting!backboard!and!drill!pilot!holes!for!the!#14!
metal!stud!screws.!Three!screws!should!be!placed!in!each!stud!evenly!spaced!apart.!
!
3.! Apply!construction!adhesive!to!the!back!of!the!mounting!backboard.!
!
4.! Attach!the!mounting!backboard!to!the!wall!with!#14!metal!stud!screws.!!
!
5.! Locate!the!mounting!position!of!the!cabinet!on!the!mounting!backboard.!
!
6.! Drill!pilot!holes!for!the!¼"!lag!bolts.!
!
7.! Mount!the!cabinet!to!the!mounting!backboard.!
!
8.! Proceed!to!the!following!section.!
!!
INSTALLATION!
40!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
7.4! Installer!Supplied!UVRI!Electrical!Installation!Material!List
!
Material!Description! ! ! Purpose! Qty!
30!amp/250V/!2!Pole!Solid! Optional!Electrical!Disconnect! 1!
Neutral/Fused!Disconnect!w/!
Ground!Kit/!NEMA!1!Rating/!
Lockable!Cover!Tang/!Lockable!
Operator!
10A!FRNR!Fuse! Fuses!For!120!V!Service! 1!
5A!FRNR!Fuse! Fuses!For!240!V!Service! 2!
12!9!14!AWG!White!Wire! AC!Neutral!from!disconnect! !8'!
12!9!14!AWG!Black!Wire! AC!Load!from!disconnect! !8'!
12!9!14!AWG!Green!Wire! Equipment!ground!from! !8'!
disconnect!
1/2”!Seal!Tight!Conduit!&!Fittings! Electrical!conduit!from!disconnect! Varies!
and!to!Fire!Panel/PA!System!
Metal!Ground!Bushings! Equipment!ground!connections! 2!
Screws,!appropriate!to!mounting! Disconnect!mounting! 4!
surface!
15!A!Breaker! Service!panel!breaker!serving!unit! 1!
INSTALLATION!
41!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
7.5! Electrical!Connections!
!
Make! all! electrical! connections! in! compliance! with! local! electrical! codes! and! NEC!
recommendations.! Disconnect! all!power! and!read! all! warnings! at! the!beginning! of! this!
manual!and!on!the!batteries!before!making!connections.!
7.5.1! Grounding!Requirements!
!
1.! The! UVRI! cabinet! must! be! properly! connected! to! an! earth! ground.! The! cabinet!
contains!an!external!¼"!ground!stud!for!making!this!connection.!!
2.! Externally! installed! antennas! require! a! dedicated! ground! to! either! a! ground! rod! or!
building!steel!below!grade!in!addition!to!the!UVRI!cabinet!ground.!
7.5.2! DIN!Rail!Terminal!Blocks!!
!
These!points!provide!a!convenient!location!for!making!the!AC!power!connections.!A!small!
screwdriver! must! be! pushed! into! the! square!opening! in! the! terminal! block! to! open! the!
contact!of!the!block.!With!the!wire!inserted,!the!block!will!clamp!the!wire!with!a!spring9
loaded!connection!when!the!screwdriver!is!removed!from!the!terminal!block.!
!
Each!terminal!block!accepts!bare!12914!AWG!wire.!The!terminal!blocks!are!labeled!L1!
and!L2.!!
!
7.5.3! 120!VAC!Electrical!Service!Wiring!
!
1.! Install!a!dedicated!15!A!circuit!breaker!in!an!existing!breaker!panel!or!install!a!new!
breaker!panel!if!necessary!for!the!UVRI.!
!
2.! Install!conduit!from!the!breaker!panel!to!the!½"!conduit!entrance!in!the!bottom!of!the!
UVRI.!
!
3.! Route!user9supplied!12914!AWG!wires!(1!black,!1!white,!1!green)!through!the!conduit!
from!the!UVRI!Cabinet!and!the!fused!breaker!panel.!
!
4.! Connect!the!white!neutral!wire!from!the!breaker!panel!neutral!to!the!DIN!rail!mounted!
terminal!block!labeled!L1!in!the!UVRI!control!cabinet.!
!!!
5.! Connect! the! black! line! wire! from! the! 15A! breaker! to! the! DIN! rail! mounted! terminal!
block!labeled!L2!in!the!UVRI!control!cabinet.!!
!
6.! Optionally,!connect!a!green!ground!wire!from!the!breaker!panel!earth!ground!to!the!
green!ground!block!in!the!UVRI!cabinet!or!run!a!ground!lead!from!the!external!1/4”!
ground!stud!on!the!UVRI!cabinet!to!earth!ground.!
INSTALLATION!
42!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
7.5.4! 240!VAC!Electrical!Service!Wiring!
!
1.! Install!a!dedicated!29pole!15A!breaker!in!an!existing!breaker!panel!or!install!a!new!
breaker!panel!if!necessary!for!the!UVRI.!
!
2.! Install!conduit!from!the!breaker!panel!to!a!conduit!entrance!in!the!bottom!of!the!UVRI.!
Ensure!the!conduit!is!adequately!grounded.!
!
3.! Route!user9supplied!12914!AWG!wires!(2!black,!1!green!9!optional)!through!the!conduit!
from! the! UVRI! Cabinet! and! the! fused! breaker! panel! (or! as! otherwise! specified! by!
code).!
!
4.! Connect!one!line!wire!from!the!15A!breaker!panel!to!the!DIN!rail!mounted!terminal!
block!labeled!L1!in!the!UVRI!control!cabinet.!
!!!
5.! Connect! the! other! line! wire! from! the! 15A! breaker! to! the! DIN! rail! mounted! terminal!
block!labeled!L2!in!the!UVRI!control!cabinet.!!
!
6.! Connect!a!green!ground!wire!from!the!breaker!panel!earth!ground!to!the!green!ground!
block!in!the!UVRI!cabinet!or!run!a!ground!lead!from!the!external!1/4”!ground!stud!on!
the!UVRI!cabinet!to!earth!ground.!
!
7.5.5! DC!Power!Connection!
!
The! battery! is! located! under! the! control! board! mounting! plate! and! is! pre9wired! to! the!
UVRI.!Connect!DC!power!to!the!UVRI!by!plugging!in!the!two!position!power!connector!at!
JP3!on!the!motherboard!as!shown!in!figure!7.5.!
!
7.5.6! Audio!Output!Connection!
!
Connect! the!audio! output! of! the! UVRI! to! the! audio! input! of! the! Remote!Fire! Alarm/PA!
System!at!JP4!on!the!motherboard!as!shown!in!figure!7.5!below.!Adjust!the!Audio!Output!
Level!potentiometer!to!the!desired!output!level.!The!pot!is!located!next!to!the!Audio!Signal!
Output!connector!(JP4).!
! !
INSTALLATION!
43!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
7.6! Remote!System!Sense!Input!
!
Connect!the!remote!system!sense!contact!closure!to!the!UVRI!to!JP6!on!the!motherboard!
as!shown!in!figure!7.5!below.!This!contact!is!used!by!the!UVRI!to!report!the!operational!
status!of!the!remote!system!
!
! ! Remote!System!Sense!!!Audio!Output!!!!!!!DC!Power!
!!!
!
Figure!7.4!M!UVRI!Remote!System!Sense,!Audio!Output!and!DC!Power!Connections!
!
7.6.1! Relay!Output!
!
The!relay!output!is!used!to!activate!the!remote!Fire!Alarm/PA!System!if!a!remote!
contact!closure!input!is!available!in!the!remote!system.!The!relay!can!also!be!used!to!
control!other!remote!devises!such!as!strobe!lights.!Two!sets!of!normally!open!and!
normally!closed!contacts!are!available!as!shown!in!the!figure!below.!
!
!
Figure!7.5!M!Relay!Output!
INSTALLATION!
44!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
7.7! Landline!Control!Connection!
!
If!the!UVRI9LL!wireline!control!option!is!used,!connect!the!telephone!wire!pair!from!the!
TB9LL!base!line!driver!to!the!Landline!Interface!module!located!in!the!control!cabinet!on!
manual!255377!for!further!installation!details.
!
!
top!of!the!control!board’s!protective!metal!cover.!Refer!to!the!Telco!Interconnect!System!
7.8! Ethernet!Connection!
!
If!the!UVRI9IP!Ethernet!control!option!is!used,!the!UVRI!Ethernet!module!will!be!located!
in!the!control!cabinet!on!top!of!the!control!board’s!protective!metal!cover.!Make!the!
Ethernet!connection!to!J1!on!the!UVRI!Ethernet!module.!Refer!to!the!Serial!to!Ethernet!
User’s!Guide!part!number!2005457!for!further!connection!details.!
!
The!UVRI!requires!an!IEEE!802.3,!10!Base9T,!half!duplex!connection!and!uses!ports!
16,887!(for!Codespear!TCP/IP)!and!port!80!(HTTP)!for!its!configuration!web!page.!
Ethernet!wire!runs!must!be!less!than!328!feet!from!the!nearest!network!switch.!
7.9! Antenna!Types!!
!
Determine!type!of!antenna!to!be!installed!if!a!wireless!RF!system!is!used:!
1.! Cabinet!Mounted!Magnetic!Base!
2.! Remote!Mounted!Magnetic!Base!
3.! Yagi!External!Antenna!Type!!!
4.! Omni!external!antenna!Type!
!
For!installation!instructions!on!the!Yagi!and!Omni!Antennas!go!to!the!Federal!Signal’s!
website.!
!
7.10! Remote!Mounted!Magnetic!Base!Antenna!Installation!
!
A! remote! magnetic!base! antenna!may! be! installed! in! buildings! that! a! known! good! RF!
signal!strength!inside!and!a!suitable!location!to!mount!the!antenna.!!
!
1.! Locate! a! suitable! location! for!the! antenna! that! is! away! from! any! electrical! devices,!
high! voltage! and! computer! wiring.! The! location! should! be! as! high! as! possible! and!
should!enable!the!antenna!mast!to!be!at!least!2!feet!away!from!any!grounded!metal!
objects.!
!
2.! Mount!the!antenna!to!a!flat,!secure!metal!structure!with!at!least!225!inches!square!
area!for!the!magnetic!mount!to!stick!to.!!
!
INSTALLATION!
45!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
8! PREMOPERATION!CHECKOUT!AND!TEST!
!
Warning!
!
The!following!procedures!should!be!performed!by!a!properly!trained!technician!to!
ensure!the!equipment!is!operating!properly.!
!
8.1! Visual!Inspection!
!
1.! Fill!out!the!Field!Test!Data!Sheet!at!the!end!of!this!section!to!document!the!following!
inspections! and! tests.! The! completed! document! should! be! kept! on! file! for! future!
reference.!
2.! Verify!all!connections!and!fasteners!are!tight.!
3.! Ensure!that!all!installation!debris!is!removed!from!the!cabinet.!
4.! Secure!all!wiring!with!wire9ties!to!provide!strain!relief!and!to!neatly!manage!the!wiring.!
5.! Verify!the!control!board!clock!LED!is!blinking.!
6.! Verify!the!power!supply!LED!is!on.!
!
8.2! PreMOperation!Checkout!
!
1.! Refer!to!Figure'7.4.!Measure!the!DC!voltage!across!the!DC!input!connector!on!the!
control!board.!The!voltage!must!be!at!least!11.5!VDC!to!turn!on!the!control!board.!
The!voltage!should!be!13.7VDC!when!AC!power!is!applied!to!the!UVRI.!!
!
2.! All!alert!signals!and!voice!messages!should!be!tested!at!this!time.!Verify!that!the!
correct!audio!is!heard!at!the!proper!volume!for!each!function.!The!Audio!A,!Audio!
B,!and!ARM!LEDs!should!light!during!each!function.!
PRE9OPERATION!CHECK9OUT!AND!TEST!
46!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
8.3! Radio!Transceiver!Adjustment!Procedure!!
!
Note:'This'procedure'previously'completed'at'factory.'Only'readjust'if'radio'reDalignment'
is'required'or'if'the'radio'is'being'installed'in'the'field.'
!
A.!Qualifications:!
!
Requires!a!properly!trained!Radio!Technician.!
!
B.!Equipment!Required:!
!
1.! Service!Monitor!
2.! Oscilloscope!
!
C.!Setup:!!
!
Connect!the!radio!to!the!service!monitor.!
!
D.!Receive!Audio!Adjustment!
!
1.!Using!service!monitor,!modulate!the!correct!RF!signal!into!the!receiver!with!a!1!kHz!
tone!at!3!kHz!deviation.!If!bandwidth!is!12.5,!then!modulate!at!1.5!kHz!deviation.!(If!using!
private!line,!add!0.75!kHz!private!line!deviation!to!the!signal.)!
!
2.! Adjust! the! level! at! TP16! (2005698! controller! card)! for! 1Vp9p! using! the! REC! gain!
adjustment!R105!(2005698!controller!card!front!panel).! !
!
E.!Transmit!Deviation!Adjustment!
!
1.! Simultaneously!press!buttons!5!&!7!on!the!2005698!controller!card.!This!will!cause!
the!controller!to!transmit!for!approximately!8!seconds.!
!
2.! Measure!the!deviation!level!using!service!monitor.!!
!
3.! Adjust! the! TX! level! (2005698! controller! card!front! panel)!for!3! kHz! deviation.! If! the!
bandwidth!is!12.5!kHz,!then!adjust!for!1.5!kHz!deviation!(If!using!private!line,!add!0.75!
kHz!private!line!deviation!to!the!signal.)!!!
!
Note,'slightly'higher'S/N'levels'can'be'obtained'by'increasing'the'RF'modulation'levels'
to'4'and'2'kHz'depending'on'the'channel'spacing'and'the'ability'of'the'radio'to'produce'
a'clean'sinewave'at'these'levels'without'limiting.'Do'not'exceed'these'deviation'levels.'
All'sites'in'the'system'should'be'set'to'the'same'modulation'level.'
!
PRE9OPERATION!CHECK9OUT!AND!TEST!
47!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
8.4! Control!and!Status!Monitoring!
!
1.! Use! The! Commander! Digital! System! (SFCDWARE)! to! verify! the! UVRI! has! been!
properly! configured! for! the! application.!Make! any!required! changes! prior! to! placing!
the!UVRI!into!service.!
!
2.! The!control!and!status!monitoring!features!should!be!tested!from!each!control!point.!
Test!each!control!function!and!all!status!indications!using!SFCDWARE.!Verify!each!
status!point!provides!the!proper!indication!of!both!pass!and!fail!conditions.!
! !
PRE9OPERATION!CHECK9OUT!AND!TEST!
48!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
!
UVRI!Field!Test!Data!!
Customer:!! ! ! ! ! !! Project!Number:!! ! ! ! ! ! Date:!! ! ! ! ! !
Contact!Person:!! ! ! ! ! ! Phone:!! ! ! ! ! ! Second!Phone:!! ! ! ! ! !
Radio!Shop:!! ! ! ! ! ! Contact:!! ! ! ! ! ! Phone:!! ! ! ! ! !
!
Siren!Type:!! ! ! ! ! ! S/N:!! ! ! ! ! ! Voltage:!! ! ! ! ! !
Controller!Type:!! ! ! ! ! ! Antenna:!Omni!! !!!!!Yagi! ! A/C!Service:!!!O.H. !
Cabinet!Mounted!! !! !! !!!!!!!!!!!!!!!!!!!!!!!U.G. !
! !!External!Mounted! !
CPU!Software:!! ! ! ! ! ! Program!file:!! ! ! ! ! ! SMV:!! ! ! ! ! !
!
!
Battery!Type:!! ! ! ! ! ! Model:!! ! ! ! ! ! Manufacturer:!! ! ! ! ! !
!
Sensor! State! Sensor!/!Output! State!
Intrusion!Sensor! Pass! !!!!!Fail! ! Audio!A/B!Sense! Pass! !!!!!Fail! !
Low!Battery! Pass! !!!!!Fail! ! Remote!System!Operation! Pass! !!!!!Fail! !
AC!Power!On! Pass! !!!!!Fail! ! Relay!Output! Pass! !!!!!Fail! !
AC!Power!Off! Pass! !!!!!Fail! ! Audio!Output! Pass! !!!!!Fail! !
Charger!Sense!! Pass! !!!!!Fail! ! ! !
!
! !
Wiring!Neatly!Dressed!in!Cabinet:!!Yes! ! Debris!removed!from!Control!Cabinet:!Yes! !
!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!No! ! !No! !
!
Antenna!connectors!sealed:!!Yes! ! !
! ! ! ! No! !
(Required!for!outdoor!antenna!installations)!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
! !
Tested!by:!! ! ! ! ! ! Date:!! ! ! ! ! !
Notes:!
!
!
!
!
!
!
!!!!!!
Figure!8.1!M!Field!Test!Data!Sheet
PRE9OPERATION!CHECK9OUT!AND!TEST!
49!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
9! MAINTENANCE!!
!
WARNING!
!
Service! and! maintenance! should! be! performed! by!qualified! personnel!familiar! with! the!
UVRI,! associated! controls,!and! power! sources! being! used! and! in! conjunction! with! the!
authorities!having!jurisdiction.!
!
The! sound! output!of! speakers! is! capable! of!causing! permanent! hearing! damage.! Use!
adequate!hearing!protection!and!avoid!excessive!exposure.!
!
!
!
If!you!are!experiencing!any!difficulties,!contact!Federal!Signal!Customer!Care!at:!!
800954897229!or!708953493400!extension!5822!or!Technical!Support!at:!800952493021!
or!708953493400!extension!7329!or!through!e9mail!at:!techsupport@fedsig.com.!For!
instruction!manuals!and!information!on!related!products,!visit:!http://www.fedsig.com/
!
Test!the!UVRI!for!proper!operation!at!least!once!a!month.!A!daily!test!at!noon,!curfew,!or!
other!selected!time!is!preferred.!This!not!only!enhances!the!usefulness!of!the!UVRI!and!
verifies! that! it! remains! ready! for! use! when! neededb! it! also! instills! confidence! in! the!
reliability!of!the!system.!
!
In! order! to! minimize! the! potential! for! a! failure,! annual! inspection! and! maintenance! is!
recommended.
MAINTENANCE!
50!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
GENERAL!MAINENANCE!
!
9.1.1! Signal!Operational!Check!
!
1.! Activate!each!of!the!signals!from!the!control!point!and!observe!the!signal!indicators!
on! the! control! module! and! the!remote! PA! system.! Verify! each! function! sounds! the!
correct!signal!at!the!proper!volume!level!for!the!application.!!
!
2.! Verify! that! the! system! status! is! reported! correctly! at! the! control! point.! Check! each!
status!point!to!verify!both!pass!and!fail!conditions!are!correctly!reported.!Verify!that!
the!relay!output!closes!with!each!function!activated.!
!
9.1.2! Battery!Inspection!!
1.! Remove!AC!power!and!measure!the!DC!voltage!across!the!DC!input!connector!on!
the!control!board.!This!voltage!should!be!above!12.75!VDC!if!the!battery!has!been!
charging!for!at!least!24!hours.!
!
2.! The! battery! will! typically! need! to! be! replaced! every! 395! years! depending! on! the!
application!environment.!The!battery!life!will!be!diminished!if!it!is!left!in!a!discharged!
state!for!prolonged!periods.!
!
3.! Maintain!or!replace!the!battery!as!recommended!by!its!manufacturerb!obey!local!or!
state!laws!governing!the!disposal!of!lead9acid!batteries.!
!
4.! Check!the!battery!terminals!for!corrosion.!Clean!and!grease!connectors!and!terminals,!
or!replace!if!necessary.!!
!
9.1.3! Battery!Replacement!
!
Remove!all!electrical!connections!from!the!motherboard!before!removing!the!battery.!
Remove!the!connectors!at!JP1,!JP2,!JP3,!JP4,!JP6,!and!JP8!on!the!motherboard.!!
!
The!battery!is!located!under!the!control!board!mounting!plate.!The!control!board!
mounting!plate!can!be!removed!by!loosening!the!four!screws!as!shown!below.
MAINTENANCE!
51!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
!
!
Figure!9.1!M!UVRI!Motherboard!Connections!
!
!
!
!
!
!
!
Figure!9.2!M!UVRI!Battery!Location!and!Cover!Plate!Mounting!Screws
MAINTENANCE!
52!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
9.2! Troubleshooting!
!
! PROBLEM! ACTION!
1.! NO!RADIO!DECODE! A.!Unit!is!not!programmed!to!recognize!that!
particular!code!sequence!(or)!Signal!is!not!
being!received!properly.!
!
B.!Verify!programming!is!correct.!Check!the!
received!audio!signal!quality!at!the!RX!test!
pin!on!the!front!of!the!control!board.!
2.! LOW!OUTPUT!FROM! Check!battery!voltage.!Also,!check!signal!
SPEAKERS! indicators!on!amplifiers!during!a!function.!If!
indicators!are!off,!remove!amplifier!for!
service.!
!
3.! FUNCTION!STOPS!BEFORE! Batteries!may!require!further!charging.!
NORMAL!TIME9OUT! Check!battery!voltage!under!load.!Check!
charger!output.!
!
4.! LOCAL!P.A.!FEEDS!BACK! Lower!P.A.!volume!using!knob!above!MIC!
connector.!
!
5.! LOCAL!P.A.!HAS!LITTLE!OR!NO! Hold!MIC!close!to!mouth.!Increase!PA!
OUTPUT! volume!using!knob!above!MIC!connector.!
!
6.! BATTERIES!NOT!HOLDING! Check!that!charger!fuses!are!intact!and!!!
CHARGE! check!charger!output.!
Load!!!Test!batteries.!
!
7.! RELAY!OUTPUT!ON! Check!that!the!relay!on!the!system!
MOTHERBOARD!DOESN’T! motherboard!is!operating!(indicated!by!LED!
OPERATE! D2).!Also!check!fuse!F1!on!motherboard!(20!
amp!slo9blow)!
8.! RADIO!P.A.!TAKES!TOO!LONG! Check!radio!for!proper!operation!of!squelch.!
TO!TIME!OUT! CD!LED!should!light!while!carrier!is!present.!
9.! LANDLINE!ACTIVATION!INPUTS! Verify!minimum!19!second!contact!closure!is!
DO!NOT!FUNCTION! applied!to!JP14!on!the!motherboard.!
!
! ! !
! ! ! ! ! !
NOTE:!For!additional!help!contact!the!FWS!Service!Dept.!at!(800)!52493021.!
!
MAINTENANCE!
53!
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
10! OPTIONS!!
!
10.1! Radio!Control!
!
The!UVRI!can!be!activated!by!a!radio!signal!when!the!optional!radio!transceiver!is!
incorporated!into!the!Control!Unit.!Activation!by!radio!control!has!the!advantage!that!
control!lines!are!not!required!between!the!control!site!and!the!UVRI.!Federal!Signal!
offers!the!controller!with!a!full!line!of!transceivers!built!in!which!cover!the!VHF!and!
UHF!bands.!
! ! ! ! !
10.2! Digital!Voice!Recording!
!
Four!minutes! of! digital! voice! storage! is! provided! as! a! standard! feature! with! the! UVRI.!
When! the! Digital! Voice! Recording! option! (model! DVR)! is! purchased,! the! UVRI! will! be!
factory! programmed! with! high! quality! voice! or! music! recordings! as! specified! by! the!
customer.!
!
Up! to! 250! individual! messages! may! be! programmed! into! the! UVRI.! Digital! Voice!
Messages! may! be! activated! remotely! or! via! the! control! panel! switches.! To! program!
activation!codes!with!Digital!Voice!Messages!under!them,!follow!the!instructions!in!the!
Commander!Digital!System!manual.!It!is!possible!to!assign!codes!to!the!functions!DIG!
VOICE!1!through!DIG!VOICE!250.!As!in!all!sounding!functions,!the!unit!must!first!be!sent!
the! ARM! command! followed! by! one! of! the! six! DIG! VOICE! commands! to! activate! the!
stored! message.! The! only! adjustment! available! on! the! Digital! Voice! PCB! is! a!
potentiometer,!which!adjusts!the!audio!output!level.!
!
10.3! Installation!of!User!Supplied!Radio!Receivers!!
CAUTION!
Improper! installation! of! radio! control! equipment! may! cause! the! Alert! and! Notification!
system! to!malfunction! or!operate! intermittently.! Installation!must! only! be! performed!by!
experienced!radio!technicians!who!have!thoroughly!read!this!manual.!
!
1.!TUNING!9!Tune!the!radio!receiver!to!the!manufacturer's!specifications.!
!
2.!POWER!9!Determine!the!radio!power!requirements.!The!ULTRAVOICE!control!panel!
provides!+12!VDC!on!the!RADIO!connector!on!the!front!panel,!as!shown!below.!
!
!
OPTIONS!
! ! 54! !
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
RADIO!Connector,!8!pin!MOD!jackb!
1.!Receive!Audio,!300mV!9!10Vp9p!
2.!Transmit!Audio,!50mV!9!3Vp9p!
3.!Carrier!Detect!9!active!low!
4.!PTT!
5.!+8!VDC!
6.!GND!
7.!+8!VDC!
8.!GND!
!
This! voltage! source! must! not! be! used! for! radios,! which! draw! more! than! 1.5! Amps! of!
current!in!transmit.!Use!both!grounds!and!both!+8!VDC!connections!for!current!handling.!
If! a! higher! current! output! is! required,! a! 24! VDC! –! 12! VDC! voltage! converter! must! be!
purchased.!This!converter!is!provided!with!the!UVRI!series!models.!Do!not!use!one!of!
the!12!VDC!batteries!to!run!the!radio!equipment.!
!
1.! AUDIO!–!The!ULTRAVOICE!controller!Receive!Audio!Input!should!be!connected!to!
the! de9emphasized! Audio! Output! of! the! radio.! Use! shielded! audio! grade! cable! and!
keep!wire!runs!as!short!as!possible.!The!Receive!Audio!level!can!vary!from!300!mV!
–!3Vp9p!unclipped.!
!
2.! The!Transmit!Audio!Output!is!adjustable!from!50!mV!9!3Vp9p.!
!
3.! C.D.!9!The!carrier!detect!signal!from!the!radio!must!pull!to!ground!when!active.!The!
radio! carrier! detect! signal! is! useful! for! controlling! live! PA.! When! the! C.D.! signal! is!
removed!from!the!controller!for!over!5!seconds,!the!controller!will!automatically!cancel!
the! P.A.! function! eliminating! the! need! to! broadcast! the! cancel! tones! over! the!
speakers.!
!
4.! PTT!–!The!PTT!output!pulls!to!ground!when!active!to!key!the!radio.!
!
5.! RX!and!TX!Audio!–!Adjust!the!RX!and!TX!Audio!levels!as!described!in!Section!6.!
!
10.4! Model!UVRIMIP!
!
The!UVRI9IP!combines!the!characteristics!of!a!UVRI!with!Serial!to!Ethernet!conversion!
capabilities.! This! allows! serial! devices! to! communicate! over! an! Ethernet! network! and!
provides!audio!decoding!of!digitized!audio!sent!over!the!network.!
!
The!converter!is!configured!with!its!own!fixed!IP!address!and!port!number.!When!packets!
of!data!are!received!over!the!Ethernet!port!that!are!addressed!to!the!board’s!IP!and!port!
number,!they!are!converted!to!serial!data!and!sent!out!over!the!serial!port.!Likewise,!any!
data!coming!into!the!serial!port!is!converted!to!TCP/IP!data!packets!and!sent!out!over!the!
!
OPTIONS!
! ! 55! !
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
Ethernet! port! to! the! server’s! IP! address.! The! unit! also! contains! a! digital! to! analog!
converter.! This! allows! specially! configured! incoming! data! packets! to! be! converted! to!
audio,!which!is!then!filtered!and!sent!out!over!a!600!ohm!audio!port.!
!
A.!Ethernet!Board!Specifications!
!
Electrical!
10.4.1!!
Input!Voltage!! 10.5!–!95!VDC!
Current!Draw! <150!mA!
!
Serial!Port!
!
Serial!Port!Protocol! !!RS232C,!N,!8,!1!
!!!!! !!baud!rate!!
! !!configurable!
!
Ethernet!Port!
!
Protocol! IEEE!802.3,!10!!
! Base9T!connection!
!
600!Ohm!Audio!Output!Port!
!
Protection! MOV!and!Transorb!!
! surge!protection!
Impedance!! 600!ohms!!
Audio!Output!Level! Adjustable!from!0.30!to!3.00!Vp9p,!
(917!dB!to!+2.7!dB)!into!600!Ohms!
!
*NOTE:!To!use!the!600!ohm!input!for!activation!receive!audio,!a!jumper!must!be!across!
pins!293!at!JP8.!JP8!is!located!on!the!main!controller!card.!Refer!to!section!‘600!Ohm!
Adjustment!Procedure!for!Communications’.!
!
Connectors!
!
JP1! 600!Ohm!Audio!Output!Port!
! Balanced!line!output!
!
JP2! JTAG!Emulation!port!
!
JP3! Audio!Output!Expanded!or!
! Flat!Selection!Jumper!
Jumper!pins!1!&!2!for!flat!audio!output!
! Jumper!pins!2!&!3!for!expanded!dynamic!range!audio!output!
!
!
OPTIONS!
! ! 56! !
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
JP4! RS232!Serial!Port!
!1!9!
!2!9!
! 3!9!Ground,!0.5!amps!maximum!current!capacity!
! 4!9!Radio!transmit!data!from!! PC,!standard!RS232!levels!
! 5!9!Radio!receive!data!to!PC!standard!RS232!levels!
! 6!9!Ground,!0.5!amps!maximum!current!capacity!
!
JP5! FLASH!Programming!and!Converter!Configuration!Port!
!1!9!
! 2!9!TX!Data,!standard!RS232!levels!
! 3!9!RX!Data,!standard!RS232!levels!
! 4!9!Ground!
! 5!9!Serial!Clock!input!for!FLASH!programming,!standard!RS232!levels!
! 6!9!Processor!Reset!Not!line,!used!in!programming!FLASH,!10K!pull9up!
!
JP6! 10.5M95!VDC!Power!Input!
!1!9!(9)!
!2!9!(+)!
!
JP7! Resets!board!back!to!factory!default!settings.!
!
J1! Ethernet!Network!Port!
! 1!&!2!9!Transmit!data!pair,!balanced!line!3!&!6!9!Receive!data!pair,!!
! balanced!line!
! 4,!5,!7,!8!9!AC!coupled!ground!
!
Indicators!
!
D1!9!CPU!Heartbeat!indicator,!green!
D2!9!Transmit!data!indicator,!red!
D3!9!Receive!data!indicator,!yellow!
D4!9!Power!indicator,!green!
!
Controls!
!
R1!–!600!ohm!audio!output!level!set!
!
Environmental!
!
Operating!Temp.! 930!°C!9!+65!°C!
Humidity! ! 09!95%!non9condensing!
!
!
OPTIONS!
! ! 57! !
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
Physical!
!
Dimensions! about!(H!x!W!x!L)!2"!x!4”!x!6.5"!
!
Weight! ! <!2!lb!!
!
!
Serial'to'Ethernet'Board'
!
B.!Network!Information!
!
Protocols!Supported!
!
•! TCP/IP!
•! UDP!(optional)!
•! XML!(optional)!
•! XMPP!(optional)!
!
IP!Ports!Used!
!
16,887!(Codespear!TCP/IP)!
80!(HTTP)!
3100!(optional!UDP!Serial!Over!IP)!
3101!(optional!UDP!Voice!Over!IP)!
!
IP!Address!
!
User!selectable!
!
!
OPTIONS!
! ! 58! !
Federal!Signal!UltraVoice!Remote!Interface!(UVRI)!
Installation,!Operation,!and!Service!Manual!
!
!
TOS/DSCP!(Type!of!Service)!
!
User!selectable!priority!level!
!
Bandwidth!Requirements!
!
Voice!Over!IP:!!150K!baud!per!Connection!
!
Siren!Activation:!!!50!bytes!per!connection!
!
Siren!Poll!Response:!!74!bytes!per!connection!
!
!
!
OPTIONS!
! ! 59! !
!
11" Final"Assembly"Drawing"and"Parts"List"
ITEM NO. PART NUMBER DESCRIPTION QTY.
4.00 22
1 103441 RES, WIREWND, 10 Ohm, 50W, 1% 1
2 115812 DIODE, SCHOTTKY, 80A, 30V 1 46
48
3 120896 TRANSFORMER, POWER SUPPLY, 15VDC, 7A 1
4.75
4 122378A SWITCH, INTRUSION, SPDT 1
5 131290-01 RELAY, 120VAC, 15A 1
6 131292 RELAY,12V,10A 1 C1 4.00
7 138182A SOCKET,RELAY,8 PIN 1 23
8 138212 IC SOCKET, TYCO, 8 PIN 1
9 139491-03 CONN,3 POS,BLZ 5.08 1 6.00
10 150A109 MISC ELEC, CABLE TIE, SELF LOCKING 1 B2 44
11 150A130 MISC ELEC, CABLE TIE MOUNT 1 B2
12 155193A BATTERY
13 1611511 LABEL, FEDERAL SIGNAL 1
14 1611639B-01 LABEL,WARNING, HIGH VOLTAGE 1
15 1612403A LABEL, GRND. SYMBOL 1 14
43
16 1612546A LABEL, WARNING, BATTERY 1
17 1613057 LABEL,RELAY COIL 1
18 1613058 LABEL,RELAY,OUTPUT 1
19 1613059 LABEL, CONTROL, UVRI 1 B3
20 1613060 LABEL, CONTROL, LED, UVRI 1 B3
21 1613062A LABEL,WARNING,AC VOLTAGE 1 62
22 1613066 LABEL,MODEL UVRI 1
23 161693A LABEL,FS LOGO 1
24 170347A ENCLOSURE, FIBERGLASS, UVRI 1
26 2005240 (1-way radio) PCB,1-WAY RADIO (SEE TABLE) 1 55
27 2005320-05 PCBA, UVRIU ADAPTER, STAND ALONE 1 4
28 2005457 PCBA, SERIAL TO ETHERNET CONVERTER 1 INSERT RIVETS
B5 FROM DIRECTION SHOWN
29 2005698-01 PCBA,UV+ CONTROLLER 1 B2 NOTE: OMIT RADIO AND MTG. BRACKETS ON
30 229218A BRKT.T,BLOCK END 2 16 UVRI-IP & UVRI-LL MODELS
31 229282A TERM BLOCK,1-POLE,35MM DIN 4 RADIO 61
60
32 229283A CAP,END,TERM BLK,1 P. 2
33 230286A STUD/STANDOFF, HEX, 6-32, NYLON, 2 37
28
34 255385 MANUAL, UVRI 1 53 42 60 B2 SECTION A-A
35 259338 WIRING DIA., UVRI 0 DETAIL K
36 288691A-03 ANTENNA,LIGHTNING PROT,POLYPHASER 1 58
37 288810A-03 DIN RAIL ALUM UNCOATED 3" LENGTH 1 B2 44
38 7000A345-16 SCREW,MACH,HEX HD,1/4-20 X 1" 1 A A
39 7000A404-08 SCREW, MACH, PAN HD., PHILLIPS, 6-32 5 B4 C2 8
*
40 7000A404-16 SCREW, MACH, 6-32, PAN HD, PHIL, STEEL, ZINC CHR 2 B3 C2
41 7000427-04 SCREW, MACH., PAN HEAD, PHILLIPS, 6-32 2 B3 C2 3
42 7000427-06 SCREW, MACH., PAN HEAD, PHILLIPS, 6-32 4 C2
44
43 7000A428-10 SCREW, MACH, 8-32, PAN HD, PHIL, SS, 7 C2 31
44 7000444A-05 SCREW,MACH,PHIL,4-40 X 5/16 9
45 7000A455-06 SCREW, MACH, 10-32, TRS HD, SLOT, SS, 4 47 43 30 COVER HOLE WITH TAPE
46 7011A152-06 #8 SHT.MTL.SCREW,S.S. 2 C C D
47 7058A045 NUT, KEPS, SS, 8-32 1
13 32
48 7058A047 NUT,MACH SCR,KEPS,10-32 2
49 7058050A NUT,MACH SCR,KEPS,1/4-20 2
50 7058053A NUT, KEPS, 4-40, , SS, 6 5
51 7072024 WASHER, FLT, 1/4, 11/16 OD, 0.078"/0.049" THK, SS, 2
B2 K
52 7072148 WASHER, FLT, .250 ID, .625 OD, 0.093" THK, NEOPRENE, 1 C1 39
53 7074077A WASHER, SPLT, M4, 7.55mm OD, 0.8mm THK, 4 21
54 7075A002 WASHER,EXT TTH, #6,.31 OD,0.02" THK,STL,TRIV CHROM 2 C2
55 7099219A RIVET, BLND, , 5/32 DIA HD, ALUM, 2 C4 NUT FROM 142122A
27
56 8009021A BRACKET, POLYPHASER 1 43 15
E E 44
57 8009030A CATCH,SNAP-ACTION 1
58 8609101 BACKPLATE ASSY, UVRI 1 C1
59 8609104-01 CHASSIS ASSY, PCB 1 C1
44 51
60 8609108 BRKT, RADIO MT, LEFT 1
43
61 8609108-01 BRKT, RADIO MT, RIGHT 1
62 8609115 BRKT, INTRUSION SWITCH 1 B3
63 8609117-01 DOOR ASSY., PCB COVER 1 1
64 8609118 COVER ASSY., PCB 1
65 85001560 TEST PROC.,UVRI 0 19
66 r42-02-13 NEOPRENE SPONGE,1/8" X 1/2" X 8" LG. 1
67 r42-02-13 NEOPRENE SPONGE,1/8" X 1/2" X 2" LG. 2 B2
68 T300210-10-023 TWIRE (SEE WIRING DIAGRAM) 1 11
69 139285-03 CONN, RECPT, .100 CENTERS (JP6, UVRI-IP ONLY) 1 C3
70 C300422-09-143 C-WIRE, BLK (JP6, POS. 1 & POS. 3, UVRI-IP ONLY) 1 C3 50 10
50 D
43
39
33
12
39
2
20
52
67 41 49
9 38 DETAIL B
44
17 63 56 B
55 50 51
45
SECTION E-E
54 18
7 40 64 43 36
47 6
24
NOTE: REPLACE POLYPHASER
50 WITH 231208 HOLE PLUG ON
MODEL NO. RADIO/PCB PART NO. DESCRIPTION UVRI-IP & UVRI-LL MODELS Tolerances Unless
Otherwise Specified SI NA
I ISION
UVRIH 19901665-02 VHF,VX-2100 C0 C5
Angles ------- 0.5
UVRIU 19901665-06 UHF,VX-2100 C0 C5 X.XX ---------- 0.015 Federal Signal Corporation
UVRI N/A NO RADIO MODEL X.XXX ---------- 0.005 2645 FEDERAL SIGNAL DRIVE - UNIVERSITY PARK,IL 60466
FINISH: MATERIAL DESCRIBED AND INFORMATION CONVEYED IS
UVRI-LL 2005548 PCB,LAND LINE PROPRIETARY TO FEDERAL SIGNAL CORPORATION, IS OR
N/A MAY BE THE SUBJECT OF PATENT APPLICATIONS, AND
SECTION UVRI-IP 2005457 PCB,SERIAL ETHERNET C5 SEE ECR #9210 2/23/18 MAF MAYNOT BE COPIED, DIVULGED TO OTHERS, OR USED
FOR MANUFACTURING WITHOUT CONSENT.
D-D C4 SEE ECR #6903 1/17/17 MAF
REMOVE BURRS, SHARP CORNERS AND EDGES
UNIT OF DRAWN BY:
MATERIAL: MJF CHKD. BY: SC SCALE AT D SIZE:
MEASURE
C3 SEE ECR #6702 12/14/16 MAF DATE: DATE:
N/A NONE
NOTE: REFER TO WIRING DIAGRAM NO. 259338 FOR WIRING PART NO'S. C2 SEE ECR #6103 9/7/16 MAF RF 1/20/10 1/21/10
C1 SEE ECR #6104 8/18/16 MAF NAME: DRAWING NUMBER:
SECTION C-C
66 C0
REV
SEE ECR #4142
CHANGE
9/1/15
DATE
MAF
BY
FINAL ASSY.,UVRI 8609105
!
!
Figure"11.1"8"UVRI"Final"Assembly"and"Parts"List"
60!
10.3 Batteries SPEC 2.10.1
PS-12350
FEATURES
12V 35.0 AH @ 20-hr. • Absorbent Glass Mat (AGM) technology for
12V 33.0 AH @ 10-hr. superior performance
Rechargeable Sealed Lead Acid Battery • Valve regulated, maintenance free spill proof construction
PS – General Purpose Series
• Power/volume ratio yielding excellent energy density
TERMINALS: (mm) • Rugged vibration and impact resistant ABS case
NB3: Heavy duty terminal posts with T6: Threaded insert with
and cover
nut and bolt fasteners 6mm stud fastener
16mm
• Gas recombination technology
APPROVALS
7mm
6mm
6mm
16mm
Battery
MO DE L PS-12350 NB
12 Volt 35.0 Amp. Hr. 1 Month 97%
R echarge able Sealed Lead-Acid Battery
D C power, constant voltage charge
3 Month 91%
6 Month 83%
C ycle use: 14.4 - 15.0V(20 C)
S tandby use: 13.5 - 13.8V(20 C )
Initial current: 10.5A MAX
Warn in g:
R isk of fire, explosion, or burns. 120350400211
Do not disassemble, heat above 60 C, or incinerate.
L: 7.72HEADQUARTERS
GLOBAL (196) W: 5.14 (131) H: 6.22 (158)EMEA
POWER-SONIC HT: 7.00 (176) Case ABS Plastic
(USA AND INTERNATIONAL EXCLUDING EMEA) (EMEA – EUROPE, MIDDLE EAST AND AFRICA)
Tolerances
Power-Sonic are +/- 0.04 in. (+/- 1mm)
Corporation and +/-
Smitspol 0.08
4, 3861 RSin. (+/- 2mm) for Power Sonic Chargers
Nijkerk, PSC-124000-PC
height
365 Cabela dimensions.
Dr Suite 300, All data subject to change without notice.
The Netherlands PSC-124000A-C
Reno, Nevada 89523 T NL: + 31 33 7410 700
USA T UK: + 44 1268 560 686
T: +1 619 661 2020 T FR: + 33 344 32 18 17
E: customer-service@power-sonic.com E: salesEMEA@power-sonic.com
Rev2: 08/20
To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website.
© 2018. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners.
All data subject to change without notice. E&O.E www.power-sonic.com
PS SERIES
PS-12350 12V 33.0 AH @ 20-hr.
12V 30.7 AH @ 10-hr.
LIFEAmbient
CHARACTERISTICS IN STAND-BY USE
necessary unless
Capacity Retention Ratio (%)
Percentage of capacity
necessary unless 100
Capacity Retention Ratio (%)
80
5oC Charging before 100% of capacity
Ambient Temperature 20˚C (68˚F)
available (Ah%)
use is necessary is required.
Percentage of capacity
80 (41oF) to help recover 80 100
5fulloCcapacity. Charging before
available (Ah%)
60 use is necessary 60
(41oF) to help recover 80
full capacity. Float Charging Voltage
60 o 40 60
30 C 2.25 - 2.30 V/Cell
o
40 C 20 C o
o
40 (104oF) (86 F) (68oF) Float Charging Voltage
o 20 40
40oC 30 C
o
20oC 2.25 - 2.30 V/Cell
0 40 (104oF) (86 F) (68oF) 0 20
0 2 4 6 8 10 12 14 16 18 20 0 1 2 3 4 5
0 0 Years
Standing
0 2 4Period
6 (Months)
8 10 12 14 16 18 20 0 1 2 3 4 5
Standing Period (Months) Years
CHARGING CHARGERS
Cycle Applications: Apply constant voltage charge at Power Sonic offers a wide range of chargers suitable
2.35v/c – 2.45v/c (14.1 – 14.7v for 12v Monobloc) at 20°C. for batteries with a variety of capacities.
Initial charging current should be set at less than 0.25C
Please refer to our website for more information on
Amps. Switch to float charge to avoid overcharging.
our switch mode and transformer type chargers.
“Float” or “Stand-By” Service: Apply constant voltage
Please contact our technical department for advice if
charge of 2.25v/c – 2.30v/c (13.5 to 13.8 volts for 12v
you have difficulty in locating a suitable charger.
Monobloc at 20°C. When held at this voltage, the battery
will seek its own current level and maintain itself in a fully
charged condition. FURTHER INFORMATION
Temperature Compensation: Charging Voltage for both Please refer to our website www.power-sonic.com
Cyclic and Standby applications should be regulated in for a complete range of useful downloads, such as
relation to ambient temperature. As temperature rises product catalogs, material safety data sheets (MSDS),
charging voltage should be reduced to prevent overcharge ISO certification, etc.
and increased as temperature falls to avoid undercharge.
For further charging information including temperature
compensation factors, see Power Sonic Technical Manual/
Power Sonic Charger specifications.
APPLICATIONS
• General purpose • Medical
• Emergency lighting • Fire and security
To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website.
© 2018. Power-Sonic Corporation. All rights reserved. All trademarks are the property of their respective owners.
All data subject to change without notice. E&O.E www.power-sonic.com
10.4 Smoke Sensor
SK-PHOTO and SK-PHOTO-T are plug-in type smoke sensors that combine
a photoelectric sensing chamber with addressable analog
communications. Point ID capability allows each detector’s address to be
set with rotary address switches, providing exact detector locations for
selective maintenance when chamber contamination reaches
unacceptable levels. SK-PHOTO (BASE INCLUDED)
The SK-PHOTOR is a remote test capable detector for use with the DNR/
DNRW duct smoke detector (not included).
COMPATIBILITY
SK-Photo, and SK-Photo-T are compatible with the following detector bases:
B210LP: 6” base (included)
B501: 2 wire base
B224RB: Relay base
B224BI: Isolator base
F E AT U R E S & B E N E F I T S
• Sleek, low-profile • Superior EMI • Detector transmits • Plug-in mounting • Listed for use in duct
design resistance for signal to indicate provides ease of applications
reliability maintenance is installation
• Base included • Rotary address
required
• Simple field cleaning • Tamper-proof feature switches for fast
• Reliable analog
for code compliance • Optional remote LED available on mounting installation
communications for
annunciator (System bases
trouble-free operation • Variety of mounting • UL Listed
Sensor ® PN RA100Z)
options to meet any
• Age resistant polymer • FM Approved
application
housing
• Dual LED indicators
• Dual electronic
for 360º visibility
thermistor design on
the SK-Photo-T
SK-PHOTO, SK-PHOTO-T and SK-PHOTOR Technical Specifications
For a complete listing of all
compliance approvals and
certifications, please visit
www.silentknight.com.
B200S/B200S-LF
Intelligent Sounder Base
The B200S sounder base series is designed for new and existing commercial dwelling unit applications. It offers
maximum flexibility in installation, configuration, and operation to meet or exceed UL 268 and UL 464
requirements.
For more information about the IntelliKnight system, or to locate your nearest source, please call
1-800-328-0103.
B200S/B200S-LF
The sounder base “listens in” to the communication
between the attached sensor head and the fire alarm
control panel (FACP) to adopt the same address as the
detector, but as a unique device type on the loop. The
FACP can then use that address to command an individual
sounder — or a group of sounders — to activate. In
addition, the FACP’s will enable custom tone patterns.
The B200S series sounder bases recognize the System
Sensor synchronization protocol. This enables it to be used
as a component of the general evacuation signal — along
with other System Sensor horns, horn strobes, and chimes
— when connected to a FACP output programmed as B200S-LF B200S
sounder base power.
The B200S-LF low frequency sounder base is designed to
meet the NFPA 72 sleeping space requirement to produce a
Compatibility
fundamental frequency of 520 Hz +/- 10% with a square The B200S series is compatible with the
wave or its equivalent. Studies show that a lower frequency, following SK-series detectors programmed for
centered around 520 Hz, is the most ideal to awaken System Sensor protocol (Firmware version of
sleeping occupants, even those with mild to severe hearing 13.0 or higher):
loss. • SK-Fire-CO Addressable Combination Fire and
Features CO Detector
• SK-Photo Photoelectric Smoke Detector and
• Addressability for maximum configuration flexibility
SK-Photo-T Photoelectric Smoke Detector with
• Supports Continuous, ANSI Temporal 3, ANSI Temporal 4,
and March Time tones Thermal
• Custom tone capability with some FACP models • SK-Acclimate Multicriteria Photoelectric Smoke
• Ability to synchronize with other System Sensor Detector
notification devices • SK-Ion Ionization Smoke Detector
• UL 268 and UL 464 compliant • SK-Heat Fixed Temperature Thermal Detector,
• Pre-wire mounting plate fits various junction box sizes SK -Heat-ROR Rate-of-Rise Detector with
• Uses a mechanical locking feature that prevents the Thermal, and SK-Heat-HT Fixed High
removal of the attached sensor head Temperature Thermal Detector
• No external relays and input modules needed to The B200S/B200S-LF are compatible with the
supervise the Aux power
following IntelliKnight FACP’s:
• 520 Hz +/– 10% square wave tone (B200S-LF )
5700
Installation 5808
The B200S series sounder bases can be mounted directly 5820XL
to 4” (10.16 cm) square, 4” (10.16 cm) octagon, 3 1/2” (8.9 5820XL-EVS
cm) octagon, single-gang or double-gang junction boxes.
P/N 351565 Rev A
© 2014 Honeywell International Inc.
INTELLIKNIGHT ACCESSORY
Model B200S/B200S-LF
Sounder Base
Wiring B200S/B200S-LF
Environmental
Operating Temperature: 32ºF – 120ºF (0ºC – 49ºC)
Humidity: 10% – 93% non-
condensing
I56-3442-000
7550 Meridian Circle, Maple Grove, MN 55369-4927
763-493-6455; 800-328-0103 Fax: 763-493-6475
SK-Monitor Module http://www.silentknight.com
Specifications
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 5.0 mA (LED on)
Average Operating Current: 375µA (group poll), 350 μA (direct poll), 600 μAmps (communication, IDC shorted)
EOL Resistance: 47K Ohms
Max. IDC wiring resistance: 1,500 Ohms
Maximum IDC Voltage: 11 Volts
Maximum IDC Current: 450µA
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10% to 93% Non-condensing
Dimensions: 41⁄2˝ H x 4˝ W x 11⁄4˝ D (Mounts to a 4˝ square by 21⁄8˝ deep box.)
Accessories: SMB500 Electrical Box
C1066-00
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power limited wiring only.
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in Figure 2.
C1067-00
Mounting
The SK-Monitor mounts directly to 4-inch square electrical boxes (see Figure
2). The box must have a minimum depth of 21⁄8 inches. Surface mounted elec-
trical boxes (SMB500) are available from Silent Knight.
SK-460-013 1 I56-3442-000
Figure 3. Typical 2-wire initiating circuit configuration, NFPA Style B OR SECURITY SYSTEMS:
NOTE: For UL Listed security installations, the SK-Monitor must be mounted within the control panel enclosure.
)–( )–(
TO NEXT FROM PANEL OR
DEVICE )+( )+( PREVIOUS DEVICE
MONITOR
ANY NUMBER OF UL LISTED CONTACT MODULE
CLOSURE DEVICES MAY BE USED. DO NOT MIX CONNECT MODULES TO LISTED COMPATIBLE
FIRE ALARM INTIATING, SUPERVISORY, OR CONTROL PANELS ONLY
SECURITY DEVICES ON THE SAME MODULE.
)–(
)+(
MONITOR
MODULE
ANY NUMBER OF UL LISTED CONTACT
CLOSURE DEVICES MAY BE USED. DO NOT MIX CONNECT MODULES TO LISTED COMPATIBLE
FIRE ALARM INTIATING, SUPERVISORY, OR CONTROL PANELS ONLY
SECURITY DEVICES ON THE SAME MODULE.
)–(
)+(
C0919-00
SK-460-013 2 I56-3442-000
©2009 Silent Knight
10.6 Local Operating Console (LOC), SPEC 2.11
EVS-LOC Local Operator Console outer hinge pins are for the door, the inner
hinge pins are for the dead front. See
The EVS-LOC Local Operator Console is a Figure 3.
combination EVS-RVM Remote Voice Module 2. Remove AC power and disconnect the
and its associated 6860 annunciator which is backup batteries from the main control
compatible with the Emergency Voice System. panel.
Note: Installation and wiring of this device must be done When mounting on interior walls, use
in accordance with NFPA 72 and local ordinances. appropriate screws such as #10 sheet rock or
concrete screw to anchor into plaster. When
mounting on concrete, especially when moisture
is expected, attach a piece of ¾” plywood to the
concrete surface and then attach the EVS-LOC
to the plywood.
Surface Mounting
The cabinet can be mounted on the wall surface
by using the mounting holes in the back of the
cabinet.
1. Mark and predrill holes in the wall for the
center top keyhole mounting bolts using the
dimensions in Figure 2.
2. Place backbox over the top screws, level
and secure.
3. Install remaining fasteners and tighten.
16”
Figure 1: EVS-LOC cabinet
Key Shaped Holes
Compatibility
26.5”
The EVS-LOC is compatible with the Honeywell
Silent Knight 5820XL-EVS or 6820EVS.
For more information refer to the FACP
Installation manual.
Bottom Mounting Holes
Electrical Ratings
FACP
Dead
Front
Figure 5: Wiring the to the FACP
Board Layout
SBUS Address
DIPs
SBUS
VBUS2
2¾”
Optional Accessory
Silent Knight® and Honeywell® are registered trademarks of Honeywell International, Inc.
Compatibility
PN LS10120-001SK-E Rev B
ECN 15-0176
1
EVS-INT50W Internal Amplifier Installation Instructions
EVS-VCM
FACP
EVS-INT50W
EVS-INT50W
LS10120-001SK-E Rev B
ECN 15-0176
2
EVS-INT50W Internal Amplifier Installation Instructions
@½ @1 18 16 14 12
Vrms Watts
W W AWG AWG AWG AWG
10 5 25Vrms 5W 3900 6200 9860 15680
70Vrms 25000 39700 63200 100520
20 10 25Vrms 10W 2125 3380 5375 8540
70Vrms 15200 24150 38400 61100
30 15 25Vrms 15W 1460 2320 3690 5870
70Vrms 11000 17500 27800 44200
40 20 25Vrms 20W 1100 1750 2780 4420
70Vrms 8500 13510 21500 34175
52 26 25Vrms 26W 760 1200 1920 3050
70Vrms 6100 9700 15400 24520
80 40 25Vrms 40W 550 875 1390 2200
Figure 5: DIP Switch 70Vrms 4100 6500 10360 16480
Once the ID number is set, you must add the 100 50 25Vrms 50W 450 715 1130 1800
EVS-INT50W to the system through 70Vrms 3500 5560 8850 14070
programming.
Note: EVS-INT50W is powered by a NAC. It will not be Note: The above table assumes a uniform distribution of
found using JumpStart AutoProgramming. the speakers, and that a max of 20% voltage drop
on the last speaker is allowed.
Speaker Wiring Figure 6 illustrates how to wire speakers to the
control panel using Class B (Style Y) supervision.
Each EVS-INT50W supplies one circuit for speaker
connection. The speaker circuit can be supervised
and wired Class B (Style Y) or Class A (Style Z). The
speaker circuit is capable of 50 watts of power at 25
Vrms or 70.7 Vrms.
PN LS10120-001SK-E Rev B
ECN 15-0176
3
EVS-INT50W Internal Amplifier Installation Instructions
Model
Description
Number
SPSCW Ceiling High-Fidelity Speaker Strobe, White
SPSCWH Ceiling High-Fidelity Speaker Strobe, High
Candela, White
SPSCRH Ceiling High-Fidelity Speaker Strobe, High
Candela, Red
SPSCW- Ceiling High-Fidelity Speaker Strobe, Clear
CLR-ALERT Lens, ALERT, White
SPSCW-P Ceiling High-Fidelity Speaker Strobe, Plain,
White
SPSCWH-P Ceiling High-Fidelity Speaker Strobe, High
Candela, Plain, White
SPSR-P Wall High-Fidelity Speaker Strobe, Plain,
Figure 6:Class B (Style Y) Speaker Configuration Red
Figure 7 illustrates how to wire speakers to the SPSRH-P Wall High-Fidelity Speaker Strobe, High
control panel using Class A (Style Z) wiring. Candela, Plain, Red
SPSCWH-P Ceiling High-Fidelity Speaker Strobe, High
Candela, Plain, White
SPSW- Wall High-Fidelity Speaker Strobe, Amber
ALERT Lens, ALERT, White
SPSW- Wall High-Fidelity Speaker Strobe, Clear
CLR-ALERT Lens, ALERT, White
SPSW-P Wall High-Fidelity Speaker Strobe, Plain,
Red
SPSWH Wall High-Fidelity Speaker Strobe, High
Candela, White
SPSWH-P Wall High-Fidelity Speaker Strobe, High
Candela, Plain White
Figure 7: Class A (Style Z) Speaker Configuration
Model
Description
Number
SPR Wall High-Fidelity Speaker, Red
SPW Wall High-Fidelity Speaker, White
SPCR Ceiling High-Fidelity Speaker, Red
SPCW Ceiling High-Fidelity Speaker, White
SPSR Wall High-Fidelity Speaker Strobe, Red
SPSRH Wall High-Fidelity Speaker Strobe, High
Candela, Red
SPSW Wall High-Fidelity Speaker Strobe, White
SPSCR Ceiling High-Fidelity Speaker Strobe, Red
PN LS10120-001SK-E Rev B
ECN: 15-0176
4
10.8 Fire Alarm Mass Notification Speakers, SPEC
2.15.1
I56-5846-002
Selectable Output
Horn Strobes, Chime Strobes 3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
and Strobes – Ceiling Mount www.systemsensor.com
PRODUCT SPECIFICATIONS
Standard Operating Temperature: 32°F to 120°F (0°C to 49°C)
Humidity Range: 10 to 93% Non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage: Regulated 12VDC or regulated 24DC/FWR
Operating Voltage Range: 8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)
Operating Voltage with MDL3 Sync Module: 8.5 to 17.5V (12V nominal) or 16.5 to 33V (24V nominal)
Input terminal wire gauge: 12 to 18 AWG
1 I56-5846-002
10/02/2018
FIGURE 1. AUDIO SELECTOR FIGURE 2. CANDELA SELECTOR FIGURE 3. LIGHT OUTPUT - VERTICAL DISPERSION, CEILING TO WALLS
TO FLOOR
Percent of
Degrees*
Rating
0 100
5-25 90
A0486-00 30-45 75
50 55
A0518.00
60 45
TABLE 1. HORN TONES TABLE 2. CHIME TONES 65 35
Volume Volume 70 35
Pos Tone Pos Tone
Setting Setting 75 30
1 Temporal High 1 1 Second Chime High 80 30
2 Temporal Low 2 1 Second Chime Low 85 25
3 Non-Temporal High 3 ¼ Second Chime High 90 25
4 Non-Temporal Low 4 ¼ Second Chime Low A0468-00
3.1 KHz
5 High 5 Temporal Chime High
Temporal
FIGURE 4. LIGHT OUTPUT – FIGURE 5. VERTICAL
3.1 KHz
6 Low 6 Temporal Chime Low HORIZONTAL DISPERSION DISPERSION, WALL TO FLOOR
Temporal
3.1 KHz Degrees* Percent of Rating Degrees* Percent of Rating
7 High 7 5 Second Whoop High
Non-Temporal 0 100 0 100
3.1 KHz 5-25 90 5-30 90
8 Low 8 5 Second Whoop Low
Non-Temporal
30-45 75 35 65
50 55 40 46
TABLE 3. CEILING-MOUNT STROBE CURRENT DRAW (mA) 55 45 45 34
8-17.5 60 40 50 27
16-33 Volts
Candela Volts 65 35 55 22
DC DC FWR 70 35 60 18
15 87 41 60 75 30 65 16
30 153 63 86 NOTE: Products set at 15 and 30 80 30 70 15
75 - 111 142 candela automatically work on 85 25 75 13
95 - 134 164 either 12V or 24V power supplies. 90 25 80 12
115 - 158 191 The products are not listed for Compound 45
150 - 189 228 24 85 12
12V DC operation when set to any to the left
177 - 226 264 other candela settings. Compound 45
24 90 12
to the right
CURRENT DRAW AND AUDIBILITY RATINGS This is generated text for figtxt.
For the horn strobe, the current draw and audibility ratings for each setting is
listed in Table 4. For the chime strobe, the current draw and audibility ratings
for each setting is listed in Table 5. For the strobe, the current draw for each
setting is listed in Table 3.
A0467-00
A0469-00
*Tolerance of ±1 degree is permitted.
TABLE 4. CEILING--MOUNT HORN STROBE CURRENT DRAW (mA) AND SOUND OUTPUT (dBA)
2 I56-5846-002
10/02/2018
WIRING AND MOUNTING SHORTING SPRING FEATURE
All wiring must be installed in compliance with the National Electric Code System Sensor notification appliances come with a shorting spring that is pro-
and the local codes as well as the authority having jurisdiction. Wiring must vided between terminals 2 and 3 of the mounting plate to enable system con-
not be of such length or wire size which would cause the notification appli- tinuity checks after the system has been wired, but prior to installation of the
ance to operate outside of its published specifications. Improper connections final product. (See Figure 6.) This spring will automatically disengage when
can prevent the system from alerting occupants in the event of an emergency. the product is installed, to enable supervision of the final system.
Wire sizes up to 12 AWG (2.5 mm²) may be used with the mounting plate. The MOUNTING AND REMOVING APPLIANCE
mounting plate ships with the terminals set for 12 AWG wiring. 1. Attach mounting plate to junction box using two of the provided Philips
Make wire connections by stripping about 3/8"of insulation from the end of head screws. (See Figure 8.)
the wire. Then slide the bare end of the wire under the appropriate clamping 2. Connect field wiring according to terminal designations. (See Figures 6
plate and tighten the clamping plate screw. We provide a wire strip guide. See and 7.)
Figure 6 for wiring terminals and strip guide reference. 3. If the product is not to be installed at this point, use the protective dust
CAUTION cover to prevent contamination of the wiring terminals on the mounting plate.
Factory finish should not be altered: Do not paint! 4. To attach product to mounting plate:
a. Remove the protective dust cover.
CAUTION b. Hook the tabs on the top of the product housing into the grooves on mount-
Do not over tighten mounting plate screws; this may cause mounting plate ing plate.
to flex. c. Pivot the product into position to engage the terminals on the mounting
plate. Make sure that the tabs on the back of the product housing fully en-
FIGURE 6. WIRING TERMINALS, SHORTING SPRING, AND STRIP GUIDE gage with the mounting plate.
Shorting Spring
d. Hold product in place with one hand, and secure product by tightening the
single mounting screw in the front of the product housing.
Ceiling Models only: To remove product from the mounting plate, loosen the
captive mounting screw and press the locking button.
FIGURE 8. MOUNTING
WIRING TERMINALS
1. Negative (-). Line in and out
2. Positive (+). Line in and out
3. Positive (+). Line in and out
Strip Guide
A0475-01
SYSTEM WIRING
The 2-wire horn strobe, chime strobe and strobe only require two wires for
power and supervision. (See Figure 7.) Please consult your FACP manufac-
turer or power supply manufacturer for specific wiring configurations and
special cases.
FIGURE 7. 2-WIRE CIRCUIT
INPUT
FROM OUTPUT A0492-01
FACP TO
OR NEXT
PRIOR DEVICE
DEVICE OR EOL
+ +
– – Locking
A0367-02 button A0574-00
TABLE 5. CEILING-MOUNT CHIME STROBE CURRENT DRAW (mA) AND SOUND OUTPUT (dBA)
3 I56-5846-002
10/02/2018
TAMPER SCREW FIGURE 10. SURFACE MOUNTING ON CEILING
For tamper resistance, the standard captive screw may be replaced with a Torx SBBCRL/SBBCWL
screw (sold separately).
1. To remove the captive screw, back out the screw and apply pressure to the
back of the screw until it disengages from the housing. Replace with Torx
screw. (See Figure 9.)
FIGURE 9. TAMPER SCREW
T15 Torx
#6-32, 5/8"
SCREW-TMPR-50
A0494-02
A0493-01 FIGURE 11. CUT-OUTS FOR SPEAKER (SPK) AND STROBE (STR)
INSTALLING A SURFACE MOUNT BACK BOX
1. The ceiling surface mount back box may be secured directly to the wall
or ceiling. Use of grounding bracket with ground screw is optional. (See
Figure 10.)
2. The ceiling mount box can be used on ceiling horn strobe, chime strobe,
strobe as well as ceiling speaker and speaker strobe models. Use the STR cut-
outs for ceiling horn strobe, chime strobe and strobe installation needs. (See A0495-00
Figure 11.)
3. Threaded knockout holes are provided for the sides of the box for ¾ inch
and ½ inch conduit adapter. Knockout holes in the back of the box can be FIGURE 12. KNOCKOUT AND V500/V700 REMOVAL FOR SURFACE
used for ¾ inch and ½ inch rear entry. MOUNT BACK BOX
4. To remove the ¾ inch knockout, place the blade of a flat-head screwdriver Wire Mold Removal
along the outer edge and work your way around the knockout as you strike
the screwdriver. (See Figure 12.)
½ inch
NOTE: Use caution not to strike the knockout near the top edge of the or ¾ inch
surface mount back box.
5. V500 and V700 raceway knockouts are also provided. Use V500 for low
profile applications and V700 for high profile applications. A0465-01 A0466-01
WARNING
THE LIMITATIONS OF HORN/STROBES
The horn and/or strobe will not work without power. The horn/strobe gets its power The signal strobe may not be seen. The electronic visual warning signal uses an extremely
from the fire/security panel monitoring the alarm system. If power is cut off for any rea- reliable xenon flash tube. It flashes at least once every second. The strobe must not be
son, the horn/strobe will not provide the desired audio or visual warning. installed in direct sunlight or areas of high light intensity (over 60 foot candles) where the
The horn may not be heard. The loudness of the horn meets (or exceeds) current visual flash might be disregarded or not seen. The strobe may not be seen by the visually
Underwriters Laboratories’ standards. However, the horn may not alert a sound sleeper or impaired.
one who has recently used drugs or has been drinking alcoholic beverages. The horn may The signal strobe may cause seizures. Individuals who have positive photoic response to
not be heard if it is placed on a different floor from the person in hazard or if placed too visual stimuli with seizures, such as persons with epilepsy, should avoid prolonged exposure
far away to be heard over the ambient noise such as traffic, air conditioners, machinery to environments in which strobe signals, including this strobe, are activated.
or music appliances that may prevent alert persons from hearing the alarm. The horn The signal strobe cannot operate from coded power supplies. Coded power supplies
may not be heard by persons who are hearing impaired. produce interrupted power. The strobe must have an uninterrupted source of power in or-
NOTE: Strobes must be powered continuously for horn operation. der to operate correctly. System Sensor recommends that the horn and signal strobe always
be used in combination so that the risks from any of the above limitations are minimized.
FCC STATEMENT
System Sensor Strobes and Horn/Strobes have been tested and found to comply with the can radiate radio frequency energy and, if not installed and used in accordance with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are instruction manual, may cause harmful interference to radio communications. Operation
designed to provide reasonable protection against harmful interference when the equip- of this equipment in a residential area is likely to cause harmful interference in which
ment is operated in a commercial environment. This equipment generates, uses, and case the user will be required to correct the interference at his own expense.
SUPPLEMENTAL INFORMATION
I56-0002-002
Selectable Output Speaker Strobes 3825 Ohio Avenue, St. Charles, Illinois 60174
NOTICE: This manual shall be left with the owner/user of this equipment.
BEFORE INSTALLING FIRE ALARM SYSTEM CONSIDERATIONS
Please read the System Sensor Voice Evacuation Application Guide, which System Sensor also recommends installing fire alarm speakers in compliance
provides detailed information on speaker notification devices, wiring and with NFPA 72, ANSI/UL 1480 and NEC 760.
special applications. Copies of this manual are available from System Sensor.
SYSTEM DESIGN
NFPA 72 and NEMA guidelines should be observed. System Sensor also rec-
The system designer must make sure that the total current drawn by the de-
ommends installing fire alarm speakers in compliance with NFPA 72, ANSI/
vices on the loop does not exceed the current capability of the panel supply,
UL 1480 and NEC 760
and that the last device on the circuit is operated within its rated voltage. The
Important: The notification appliance used must be tested and maintained current draw information for making these calculations can be found in the
following NFPA 72 requirements. tables within this manual. For convenience and accuracy, use the voltage drop
GENERAL DESCRIPTION calculator on the System Sensor website (www.systemsensor.com).
System Sensor series of notification appliances offer a wide range of audible When calculating the voltage for the last device, it is necessary to consider
and visible devices for life safety notification. Our indoor speaker strobes the voltage drop due to the resistance of the wire. The thicker the wire, the
come with 7 field selectable candela setting. The strobe portion is designed smaller the voltage drop. Note that if Class A wiring is installed, the wire
to be used in 12 VDC, 24VDC, or 24V FWR (full wave rectified) systems. The length may be up to twice as long as it would be circuits that are not fault
speaker is designed to be used at either 25 or 70.7 volts, and operate at any tolerant. The total number of strobes on a single NAC must not exceed 69 for
one of four input power levels. Our speaker strobes are suitable for dry and 24 volt applications.
damp environments. These products are electrically backwards compatible
AVAILABLE CANDELA SETTINGS
with previous generation of System Sensor speaker strobes. With its low total
harmonic distortion, the System Sensor SPL series offers high fidelity sound System Sensor offers a wide range of candela settings for your life safety
output. needs. In order to select your candela output, adjust the slide switch on the
rear of the product to the desired candela setting on the selector switch. (See
Speakers Strobes are public mode notification appliances intended to alert oc- Figure 1.)
cupants of a life safety event. The speaker is listed to ANSI/UL 1480 (public
mode) and the strobe is listed to ANSI UL 1638 (public mode). The candela setting can also be verified by looking into the small window
on the front of the unit. See Tables 1 and 2 for candela settings for wall and
ceiling products. All products meet the light output profiles specified in the
appropriate UL Standards. (See Figures 2–4.)
1 I56-0002-002
12/10/2018
FIGURE 1. CANDELA SELECTOR FIGURE 4. LIGHT OUTPUT - VERTICAL DISPERSION, CEILING TO WALLS
TO FLOOR
Percent of
Degrees*
Rating
0 100
A0486-00 5-25 90
30-45 75
CURRENT DRAW AND AUDIBILITY RATINGS 50 55
For the strobe, the current draw for each setting is listed in Tables 1 and 2. 60 45
TABLE 1. WALL-MOUNT STROBE CURRENT DRAW (mA) 65 35
70 35
8-17.5
16-33 Volts 75 30
Candela Volts
80 30
DC DC FWR
85 25
15 88 43 60
90 25
30 143 63 83 NOTE: Products set at 15 and 30 A0468-00
75 - 107 136 candela automatically work on ei-
95 - 121 155 WIRING AND MOUNTING
ther 12V or 24V power supplies.
110 - 148 179 All wiring must be installed in compliance with the National Electric Code
The products are not listed for
and the local codes as well as the authority having jurisdiction. Wiring must
135 - 172 209 12V DC operation when set to any
not be of such length or wire size which would cause the notification appli-
185 - 222 257 other candela settings.
ance to operate outside of its published specifications. Improper connections
TABLE 2. CEILING-MOUNT STROBE CURRENT DRAW (mA) can prevent the system from alerting occupants in the event of an emergency.
8-17.5 Wire sizes up to 12 AWG (2.5 mm²) may be used with the mounting plate. The
16-33 Volts mounting plate ships with the terminals set for 12 AWG wiring.
Candela Volts
DC DC FWR Make wire connections by stripping about 3/8" of insulation from the end of
15 87 41 60 the wire. Then slide the bare end of the wire under the appropriate clamping
30 153 63 86 NOTE: Products set at 15 and 30 plate and tighten the clamping plate screw.
75 - 111 142 candela automatically work on See Figure 5 for wiring terminals and strip guide reference.
95 - 134 164 either 12V or 24V power supplies.
115 - 158 191 1. Connect the speaker. (See Figure 5.)
The products are not listed for 12V
150 - 189 228 DC operation when set to any other 2. There are two rotary switches on the back of the product. The first switch
177 - 226 264 candela settings. is used to select either 25 or 70.7 volts input and the second switch is used to
select the input power of ¼, ½, 1 or 2 watts. (See Figure 6.)
FIGURE 2. WALL LIGHT OUTPUT – FIGURE 3. VERTICAL FIGURE 5. WIRING DIAGRAM AND WIRING TERMINALS
HORIZONTAL DISPERSION DISPERSION, WALL TO FLOOR
Percent of Percent of
Degrees* Degrees*
Rating Rating
0 100 0 100
INPUT OUTPUT
5-25 90 5-30 90
(-) (-)
(+) To Next Device or EOL
30-45 75 35 65
From Amplifier (+)
50 55 40 46
55 45 45 34 (-) (-) To Next Device or EOL
From FACP (+) (+)
60 40 50 27
A0519-01
65 35 55 22
70 35 60 18
75 30 65 16 Wiring Terminals NOTE: Do not loop electrical wiring un-
80 30 70 15 1. Negative (-). Line in and out der terminal screws. Wires connecting
2. Positive (+). Line in and out the device to the control panel must be
85 25 75 13
3. Positive (+). Line in and out broken at the device terminal connec-
90 25 80 12
tion in order to maintain electrical su-
Compound 45
24 85 12 pervision.
to the left
Compound 45 FIGURE 6. SPEAKER WATTAGE AND VOLTAGE SETTINGS
24 90 12
to the right This is generated text for figtxt.
A0467-00
A0469-00
*Tolerance of ±1 degree is permitted.
A0419-01
2 I56-0002-002
12/10/2018
SHORTING SPRING FEATURE
System Sensor notification appliances come with a shorting spring that is pro- CAUTION
vided between terminals 2 and 3 of the mounting plate to enable system con- Do not over tighten mounting plate screws; this may cause mounting plate
tinuity checks after the system has been wired, but prior to installation of the to flex.
final product. (See Figure 7.) This spring will automatically disengage when
the product is installed, to enable supervision of the final system. FIGURE 8. WALL SPEAKER/STROBE
FIGURE 7. SHORTING SPRING
Strip Guide
WIRING TERMINALS
1. Negative (-). Line in and out
2. Positive (+). Line in and out
3. Positive (+). Line in and out
Shorting
Spring
A0499-02
CAUTION
A0521-02
Signal levels exceeding 130% rated signal voltage can damage the speaker.
Consequently, an incorrect tap connection may cause speaker damage. This
means that if a 25V tap is selected when a 70.7V amplifier is being used,
speaker damage may result. Therefore, be sure to select the proper taps for the
amplifier voltage/input power level combination being used.
3 I56-0002-002
12/10/2018
the top mounting holes for ceiling speaker and speaker strobe products. (See FIGURE 13. SURFACE MOUNT BACK BOX UP ARROW
Figure 14.)
3. Threaded knockout holes are provided for the sides of the box for conduit
adapter. Knockout holes in the back of the box can be used for rear entry.
4. To remove the conduit knockout, place the blade of a flat-head screwdriver
along the outer edge and work your way around the knockout as you strike
the screwdriver. (See Figure 15A.)
A0481-00
NOTE: Use caution not to strike the knockout near the top edge of the
surface mount back box. FIGURE 14. CEILING INSTALLATION WITH A SURFACE MOUNT BACK
5. V500 and V700 raceway knockouts are also provided. Use V500 for low BOX : KEY HOLE PATTERN
profile applications and V700 for high profile applications.
6. To remove the knockout, turn pliers up. (See Figure 15B.)
FIGURE 11. SURFACE MOUNTING ON WALL
A0505-00
FIGURE 15A AND 15B. KNOCKOUT AND WIRE MOLD REMOVAL FOR
SURFACE MOUNT BACK BOX
A0465-01 A0466-01
NOTE: Use caution not to strike the knockout near the top edge of the wall
version of the surface mount back box.
A0520-02
WARNING
THE LIMITATIONS OF SPEAKERS
Always make sure that the individual speakers are tested after installation per NFPA regu- ages. The speaker may not be heard if it is placed on a different floor from the person in
lations. The speakers may not be heard. The loudness of the speaker meets (or exceeds) hazard or if placed too far away to be heard over the ambient noise such as traffic, air
current Underwriters Laboratories’ standards. However, the speaker may not alert a conditioners, machinery or music appliances that may prevent alert persons from hearing
sound sleeper or one who has recently used drugs or has been drinking alcoholic bever- the alarm. The speaker may not be heard by persons who are hearing impaired.
FCC STATEMENT
System Sensor speakers have been tested and found to comply with the limits for a radio frequency energy and, if not installed and used in accordance with the instruction
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed manual, may cause harmful interference to radio communications. Operation of this
to provide reasonable protection against harmful interference when the equipment is equipment in a residential area is likely to cause harmful interference in which case the
operated in a commercial environment. This equipment generates, uses, and can radiate user will be required to correct the interference at his own expense.
SUPPLEMENTAL INFORMATION
Features:
• UL Listed for indoor and outdoor
applications
• Molded Self-Sealing Mounting
Bosses
• CSFM Listed
• Snap Latches for Easy
Installation of the Pull Station
SB-I/O
• Two Reinforced 1/2” NPT
Connector Outlets (One Plug
Included)
• Single-gang Electrical Box
Mounting Holes (Knockout)
Compatibility
The SB-I/O is compatible with the following pull sta-
• Four #10 x 1.00” Mounting
tions:
Screws Included
PS-DA
PS-SA
Pull Station BackBox
This document is not intended to be used for installation purposes. We MADE IN AMERICA
try to keep our product information up-to-date and accurate. We cannot P/N 350052
cover all specific applications or anticipate all requirements. All specifica- © 2008 Honeywell International Inc.
tions are subject to change without notice. For more information, contact
Silent Knight 7550 Meridian Circle Suite 100, Maple Grove, Mn 55369-
4927.
Phone: (800) 328-0103, Fax: (763) 493-6475.
10.10 Manual Station, SPEC. 2.14
Description
The SK-Pull-DA Addressable pull station is a non-coded, dual-action manual pull station
with a key-lock reset feature. It provides Silent Knight intelligent fire alarm control panels
(FACP) with one addressable alarm initiating input. The addressable module is housed inside
the pull station. The SK-Pull-DA is compatible with all Silent Knight intelligent panels that
use the Intelligent Device Protocol (IDP). Refer to the FACP Installation Manual to determine
P0252-03
if Intelligent Device Protocol is supported. The SK-Pull-DA meets the ADAAG controls
P0267-00
and operating mechanisms guidelines (section 4.1.3[13]), and the ADA requirement for a
5 lb. maximum pull force to activate the pull station. Operating instructions are molded into
the pull station handle along with Braille text. Molded Terminal numbers are also present. WARNING! Do not loop wiring under any
Conforms to ANSI/UL Standard 38. terminals. Break wire run to
maintain IDC supervision.
Ratings
Normal Operating Voltage: 24VDC.
Average Operating Current (LED Flash): 375 µA. CAUTION!
Maximum Operating Current (LED On): 5 mA. Do not detach the door of the pull station during installation. The door of the pull station
Temperature Range: 32°F – 120°F (0°C – 49°C). cannot be reattached to the backplate after the backplate has already been installed onto an
Relative Humidity Range: 10% - 93% non-condensing. electrical box.
Installation CAUTION!
The SK-PULL-DA Addressable pull station can be surface mounted to a SB-I/O surface Install the Silent Knight SK-PULL-DA addressable pull station in accordance with these
backbox or semi-flush mounted on a standard single-gang, double-gang or 4˝ (10.16 cm) instructions, applicable NFPA standards, national and local Fire and Electrical codes and
square electrical box. The optional BG-TR trim ring can be used if the SK-PULL-DA is to the requirements of the AHJ (Authority Having Jurisdiction). Regular testing of the devices
be semi-flush mounted. should be conducted in accordance with the appropriate NFPA standards. Failure to follow
these directions may result in failure of the device to report an alarm condition. Silent Knight
Operation
is not responsible for devices that have been improperly installed, tested or maintained.
To activate the dual-action pull station, push in and pull down on the handle. The word
‘ACTIVATED’ appears after the handle is pulled down. This will remain until the pull station ADA Compliance
is reset. The pull station includes one Single Pole, Single Throw (SPST) Normally Open For ADA compliance, if the clear floor space only allows forward approach to an object, the
(N/O) switch which closes upon activation of the pull station. maximum forward reach height allowed is 48 inches (121.92 cm). If the clear floor space
Resetting the Pull Station allows parallel approach by a person in a wheelchair, the maximum side reach allowed is
1. Insert the key into the lock and rotate 1/4 turn counterclockwise. 54 inches (137.16 cm).
2. Open the door until the handle returns to normal.
3. Close and lock the door.
NOTE: Closing the door automatically resets the switch to the ‘Normal’ position.
Opening the door will not activate or deactivate the alarm switch.
1 I56-3447-005
07-24
Setting the SK-PULL-DA Address
The SK-PULL-DA Addressable pull station is factory preset with address ‘00.’ Set the ad-
dress for the pull station by turning the rotary address switches on the addressable module
mounted inside the pull station. Only one device per address is allowed. Multiple modules
may not be set to the same address on the Signaling Line Circuit. Once the address is set,
record it in the space provided on the product ID label located inside the pull station.
15 0 0
14 1 1
13 2 2
12 3
3
11 4 4
3 2 1 4
10 5 5
9 8
9 8
7 6 7 6
TENS ONES
AL
RM
NO
ACT
IVAT
ED
P/N50997 REV-A LOOP ADDRESS
M
UL NOTIFIER
PRODUCT IDENTIFICATION
NBG-12
UL Approved
LISTED
Series
NON-CODEDLabel HereLABEL
AHDHDH
23424
FIRE ALARM BOX
14 15
0 REFER TO DOCUMENT
13
1
12
2
11 3
10 4
9 5
8 6
7
ADDRESS 0
15 0 1
14 1
13 2 2
12 3
Note – Opening the pull 3
station door will not activate 11 LOOP 4
or deactivate the alarm switch.
4
10 5 5
9 8
9 8
7 6 7 6
LED OPERATION
Alarm:
Steady RED
Normal:
Flash GREEN
Note: LED is
visible through
LED
translucent handle.
P0130-00
12 Clintonville Road
ROTARY ADDRESS SWITCHES Northford, CT 06472
203-484-7161
Fax: 203-484-7118
www.silentknight.com
Silent Knight® and Honeywell® are registered trademarks of Honeywell International, Inc. 2 I56-3447-005
©2017 Honeywell. 07-24
11.11 Surge Protector, SPEC 2.5
from the public switched telephone network or where the SPD is directly connected to the
INSTALLATION electronic device. Maximum protection will only be achieved if the SPD is properly installed.
Please read and follow the installation instructions carefully.
NOTICE: This SPD should be installed and grounded, by a licensed contractor, per the applicable
requirements of the NEC and the following instructions. These devices are only to be employed on
communication loop circuits which have been isolated from the Public Switched Telephone Network.
APPLICATION
DTK-MB10 base can be installed inside a 4”x4” electrical boxes and other locations where there is a space
constraint. This base is available as a 1 up array (standard) or 2 through 5 up array for multiple pair
terminations at one point of use. Specify DTK-2MB, 3MB, 4MB or 5MB for 2 through 5 up arrays.
DTK-2MHLPxxFWB surge module is for hardwired series installations for voltages ranging from 5-75 Volts
on circuits that operate at less than 1 Amp.
DTK-2MHLPxxBWB surge module is for hardwired series installations for voltages ranging from 5-75 Volts
on circuits that operate at less than 5 Amps.
DTK-2MHTP surge module is for hardwired series installations for dialer circuits and POTS lines for
communication circuits.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of the unit.
Improper installation voids the warranty.
MB BASE INSTALLATION
1. Turn off the power at the circuit to be protected before beginning installation.
2. Securely mount the snap track between the field wiring and your equipment to be protected. Use the two #8 screws
provided to fasten the snap track.
3. Connect ground to the ground terminal using a minimum of 14 AWG wire, make this conductor as short as possible.
Ground Resistance Rule: Max ground resistance is 25 Ohms, 5 Ohms or less is optimum.
This cannot be an assumed value and must be measured to assure proper grounding.
4. Connect the supply/field wiring to the UNPROTECTED side of the MB base. Connect the 1st pair to
position 1+ and 1- , than the 2nd pair to position 2+ and 2-.
5. Connect the equipment wiring to the PROTECTED side of the MB base. Connect the 1st pair to
position 1+ and 1- , than the 2nd pair to position 2+ and 2-.
6. Make sure the UNPROTECTED supply/field wiring and PROTECTED equipment wiring conductors do not occupy
the same space or conduits.
7. Make sure the wire distance from the base to protected equipment is about 3’ of conductor length. This can be a
coiled service loop if necessary.
MODULE INSTALLATION
Insert the module into the base making sure the polarizing keys in the block are aligned with the notches cut into
the edge card printed circuit board.
8. After all connections have been made and no hazards exist, restore power.
GROUNDING
EQUIPMENT
Pair 2 Pair 2
DTK-2MHLP BASE
Illustrations Page
DITEK Corporation
ONE DITEK CENTER
1720 Starkey Road
Largo, FL 33771
INSTALLATION 1.15
1.03
ED
CT
TE
O
PR
GND
E D
Snap Track
3.25 1+ CT
1- 2
+ 2 TE
- O
PR
UN
1.50
DTK-MB10
DTK-2MHLPxxFWB
DTK-2MHLPxxBWB
DTK-2MHTPWB
DTK-2MB DTK-4MB
DTK-3MB DTK-5MB
Drawn By: RMitchell 3-3-11 DITEK Technical Support Available 24/7 Doc # INT-100132-001
Revised By: RMitchell 6-14-16 1-888-472-6100 www.ditekcorp.com Part No. 191556 Rev. 4
INSTALL INSTRUCTIONS
DTK-120HW
This Surge Protective Device (SPD) is a high performance device, designed to provide protection
DITEK Corporation
ONE DITEK CENTER
1720 Starkey Road
for sensitive electronic loads connected to service panels, fire panels, or where the SPD is
Largo, FL 33771
directly connected to the electronic device. Maximum protection will only be achieved if the SPD
is properly installed.
INSTALLATION
Please read and follow the installation instructions carefully.
NOTICE: This SPD should be installed and grounded, by a licensed contractor, per the applicable
requirements of the NEC and the following instructions.
APPLICATION
Type 1 and Type 2 SPD for hardwired parallel installations on 120 VAC single phase branch circuits.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of
the unit. Improper installation voids the warranty.
Warning: No Serviceable Parts-Attention:Aucune pièce remplaçable ou réparable
For Use Only With A Flexible Conduit System Or Direct Connection To Panel
NOTE: Suitable for use on a circuit capable of delivering not more than 10,000 rms symmetrical
Amperes, when protected by a 20 Ampere circuit breaker rated 120 Volts minimum.
1. Turn off the power at the circuit breaker or main before beginning installation.
2. Remove front cover from the panel.
3. Remove 3/4" knockout on side of panel box.
4. Unscrew nut from unit.
5. Feed all wires and the DTK-120HW nipple through knockout hole then through nut,
tighten nut securing the unit.
8. For JUNCTION BOX INSTALLATION, refer to diagram #3. In this application, ensure the
DTK-120HW’s leads are as short as possible to the connection point. Use a 3-position barrier strip, or
ION
twist-on wire connectors for Line and Neutral conductors and a multi-position grounding bus bar for
Ground conductors. Barrier strip and connectors are not provided. Allow the unit reaction time by
maintaining no less than 3’ of conductor length between the connection point and the equipment it is
protecting.
9. After all connections have been made and no hazards exist, restore power.
NOTE: The LED must be on, if the LED is off then surge protection is compromised and the unit
must be replaced.
Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum.
This cannot be an assumed value and must be measured to assure proper grounding.
DITEK Corporation
ONE DITEK CENTER
Illustrations Page
1720 Starkey Road
Largo, FL 33771
Circuit Board
DTK-120HW
Connection Point
3’ Conductor Length
#12 AWG Minimum
Battery Battery
White Wire
Black wire
Green Wire
Ground Bus
White Wires
3’ Conduit Length
To Alarm Panel
White Wire
Green Wire
Green Wires
APPLICATION
Surge suppression for hardwired series installations on loop circuits or communication circuits in a
NEMA 4X enclosure.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of the unit.
Improper installation voids the warranty.
NEMA ENCLOSURE MOUNTING
Enclosure can be mounted directly on to a panel, frame, or other mounting surface through corner
mounting holes. Corner hole mounting is required to maintain the NEMA 4X rating.
Punch holes in the enclosure as necessary for conduit placement. Use liquidtight connectors
to maintain NEMA 4X rating.
DTK-2MHLP WIRING INSTRUCTIONS
1. Turn off the power at the circuit to be protected before beginning installation.
2. Connect ground to the ground terminal using a minimum of 14 AWG wire, make this conductor as short
as possible.
Ground Resistance Rule: Max ground resistance is 25 Ohms, 5 Ohms or less is optimum.
This cannot be an assumed value and must be measured to assure proper grounding.
3. Connect the supply/field wiring to the UNPROTECTED side of the MB base. Connect the 1st pair to
position 1+ and 1- , than the 2nd pair to position 2+ and 2-.
4. Connect the equipment wiring to the PROTECTED side of the MB base. Connect the 1st pair to
position 1+ and 1- , than the 2nd pair to position 2+ and 2-.
5. Make sure the UNPROTECTED supply/field wiring and PROTECTED equipment wiring conductors do
not occupy the same space or conduits.
6. Make sure the wire distance from the base to protected equipment is a minimum of 3’ of conductor
length. This can be a coiled service loop if necessary.
MODULE INSTALLATION
Insert the module into the base making sure the polarizing keys in the block are aligned with the
notches cut into the edge card printed circuit board.
7. After all connections have been made and no hazards exist, restore power.
GROUND WIRE
14AWG MINIMUM
SUPPLY/FIELD WIRE
OUTPUT
INPUT
TO EQUIPMENT
UNPROTECTED
3' MINIMUM
SUPPLY/FIELD WIRE
INPUT OUTPUT
UNPROTECTED UNPROTECTED PROTECTED TO EQUIPMENT
3' MINIMUM
UNPROTECTED PROTECTED
Drawn By: B. Aycock 5-19-16 DITEK Technical Support Available 24/7 Doc # INT-100093-001
Approved By: R. Mitchell 7-5-16 1-888-472-6100 www.ditekcorp.com Part No. 191522 Rev. 2
11.3 Wiring, SPEC. 2.19
M.R.
UNSHIELDED FIRE ALARM CABLE
ECOLGICAL
Telecom Cables
DESCRIPTION:
• Solid bare copper conductor 22, 18, 16 or 14 AWG APPLICATION:
• Semirigid PVC insulation Smoke detectors, burglar
• Insulated conductors are cabled in all constructions alarm, critical control circuits, power
• PVC jacket limited circuits.
• Rip-Cord
• FPLR Standard lengths of 1000 ft or 500 ft reels
or boxes.
SPECIFICATIONS
NEC 760 UL-1424 ETL Listed RoHS
Available In:
Condumex Wire and Cable 2590 114th Street, Suite 200 - Grand Prairie, TX 75050 - (800) 925-9473
8-04
8
RoHS
M.R.
UNSHIELDED FIRE ALARM CABLE
ECOLGICAL
Telecom Cables
DESCRIPTION:
• Solid bare copper conductor 22, 18, 16 or 14 AWG APPLICATION:
• Semirigid PVC insulation Smoke detectors, burglar
• Insulated conductors are cabled in all constructions alarm, critical control circuits, power
• PVC jacket limited circuits.
• Rip-Cord
• FPLR Standard lengths of 1000 ft or 500 ft reels
or boxes.
SPECIFICATIONS
NEC 760 UL-1424 ETL Listed RoHS
Available In:
Condumex Wire and Cable 2590 114th Street, Suite 200 - Grand Prairie, TX 75050 - (800) 925-9473
8-04
8
11.4 Boxes and Cover Plates, SPEC. 3.6
In ELECTRICAL MANUFACTURER
GARVIN
On
Unique
Stock! Since
1892
Time!
WHO WE ARE...
• Family-owned manufacturer of UL Listed
electrical, low voltage and lighting
products with 120 years of industry
experience.
Material: Steel
Material: Steel
52171-SDA IN USE
Material: Steel
52C1 IN USE
Part Std.
Number Description Similar Products or Special Features Pkg.
_________________________________________________________________________________________________
52C1 4” Square Blank Cover Thomas & Betts 52C1 Crouse Hinds TP472 50
Hubbell Raco 752 EGS Appleton 8465
52C1-RED 4” Square Blank Cover, Red Painted red for alarm and life safety circuits. 50
Hubbell Raco 911-8
52C1-GS 4” Square Blank Cover with Great for prefab boxes used with Garvin Industries’ dual access box! 50
10-32 Green Ground Screw Allows proper grounding of pre-installed devices on rings.
52C1-TOG 4” Square Blank Cover with Economical On/Off switch on 4” square flat cover. Great for HVAC and other 25
15 AMP Toggle Switch Installed appliances that require On/Off switching
52C1-VT 4” Square Blank, Gasketed Cover Thomas & Betts 52C1-VT Crouse Hinds TP850 25
with Captivated, 8-32 Box Screws Hubbell Raco 762 EGS Appleton
52C1-VTRED 4” Square Blank, Gasketed Cover with Painted red for alarm and life safety circuits. 25
Captivated, 8-32 Box Screws. Red Hubbell Raco 911-8
53C1-VT Double-Gasketed Flat Ring Creates “air tight” seal between existing Chicago plenum box and 25
extension ring being added.
52C6 4” Square Cover with Thomas & Betts 52C6 Crouse Hinds TP478 50
1/2” Knockout Hubbell Raco 753 EGS Appleton 8474
52C6-VTSS Stainless Steel Cover with Water resistant stainless steel gasketed cover with sealed 1/2” 50
1/2” Sealed Knockout conduit knockout. Great for damp locations or wash down areas.
629NG 4” Square Blank Cover with Flat blank steel cover, no gasket, steel plate only with captive 8-32 box screws. 50
Captivated 8-32 Box Screws
52C1-OCT 4” Square Cover with four Threaded 8-32 This conversion plate mounts on Octagon boxes and provides 4” square 25
Mounting Holes & Two Through Holes to mounting tabs for life safety and other low voltage devices.
Fit on 4” Octagon Boxes.
Harrington CF hand chain hoists give you a practical alternative thanks to an economical design using
fewer parts for trouble-free service. Outstanding durability is due to a die-cast aluminum body and
high-strength, heat-treated main pinion shaft and load gear. Pre-lubricated ball bearings, precision
machined gears, and Weston-style load brake make lifting smooth and easy while allowing long service
and low maintenance.
11
Load Weight
Chain for
Pull to Diameter Shipping Additional
Headroom Std. Lift (mm) x Net Weight One Foot
Cap. Product C Lift Load Overhaul Chain Weight Approx. of Lift
(Tons) Code (in) (ft) (lbs) Ratio Fall Lines (lbs) (lbs) (lbs)
Lighting System
Name of Product Catalog
Ceiling Fan Type F Hunter Dempsey 59242
Lumination LED RX General Electric RX610830MV
Lighting BLWP Lithonia Light GA 30012
Power System
Name of Product Catalog
GFCI Receptacle Leviton TS-111020-dp
20 Amp Receptacle Leviton GFNT2-I
Communication System
Name of Product Catalog
UTP Cable NEWLINK NEW-980634X
Single Gang QuickPort Leviton 41080-xxP
Module F type Nicle Plaed ICC 125268
Coaxial Cable MoCSY A6QS-BVV-BOX
Coaxial Type F Connector Multicom PPCEX6PLUS
APENDIX C
MAINTENANCE SCHEDULE LOG
MAINTENANCE SCHEDULE LOG
12 PLEX PHASE I
5.2 The warranty for Products shall expire one (1) year from first use or eighteen (18) months from delivery, whichever occurs
first, except that software is warranted for ninety (90) days from delivery. The warranty for Services shall expire one (1) year
after performance of the Service, except that software-related Services are warranted for ninety (90) days.
5.3 If Products or Services do not meet the above warranties, Buyer shall promptly notify Seller in writing prior to expiration of
the warranty period. Seller shall (i) at its option, repair or replace defective Products and (ii) re-perform defective Services. If
despite Seller’s reasonable efforts, a non-conforming Product cannot be repaired or replaced, or non-conforming Services
cannot be re-performed, Seller shall refund or credit monies paid by Buyer for such non-conforming Products and
Services. Warranty repair, replacement or re-performance by Seller shall not extend or renew the applicable warranty
period. Buyer shall obtain Seller’s agreement on the specifications of any tests it plans to conduct to determine whether a non-
conformance exists.
5.4 Buyer shall bear the costs of access for Seller’s remedial warranty efforts (including removal and replacement of systems,
structures or other parts of Buyer’s facility), de-installation, decontamination, re-installation and transportation of defective
Products to Seller and back to Buyer.
5.5 The warranties and remedies are conditioned upon (a) proper storage, installation, use, operation, and maintenance of
Products, (b) Buyer keeping accurate and complete records of operation and maintenance during the warranty period and
providing Seller access to those records, and (c) modification or repair of Products or Services only as authorized by Seller in
writing. Failure to meet any such conditions renders the warranty null and void. Seller is not responsible for normal wear and
tear.
5.6 This Article 5 provides the exclusive remedies for all claims based on failure of or defect in Products or Services, regardless
of when the failure or defect arises, and whether a claim, however described, is based on contract, warranty, indemnity,
tort/extra-contractual liability (including negligence), strict liability or otherwise. The warranties provided in this Article 5 are
exclusive and are in lieu of all other warranties, conditions and guarantees whether written, oral, implied or statutory. NO
IMPLIED OR STATUTORY WARRANTY, OR WARRANTY OR CONDITION OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE APPLIES.
Limited Lifetime Warranty
Hunter Fan Company grants this limited warranty to the original purchaser of this • ENERGY STAR® Rated Light Kits – Three-Year Limited Warranty
Hunter ceiling fan. This document can be found online at www.HunterFan.com. If your ENERGY STAR rated light kit (not including glass components)
Thank you for choosing Hunter! fails at any time within three years of the date of purchase due to a defect
in material or workmanship, as determined solely by Hunter, Hunter will
How Can Warranty Service Be Obtained? provide a replacement light kit free of charge.*
Proof of purchase is required when requesting warranty service. The original * If no replacement product/part can be provided for your fan, we will provide a comparable
purchaser must present a sales receipt or other document that establishes proof of or superior replacement product/part at the sole discretion of Hunter.
purchase. Hunter, at its sole discretion, may accept a gift receipt. To obtain service,
contact Hunter Fan Company online or by phone. What Does This Warranty NOT Cover?
www.HunterFan.com/Support/Contact-Us/ Labor Excluded. This warranty does not cover any costs or fees associated with the
1-888-830-1326 labor (including electrician’s fees) required to install, remove, or replace a fan or any
Please do not ship your fan or any fan parts to Hunter. Delivery will be refused. fan parts.
What Does This Warranty Cover? There is no warranty for light bulbs (except where otherwise noted); remote control
batteries; fans purchased or installed outside the United States; fans owned by
someone other than the original purchaser; fans for which proof of purchase has not
Motor – Limited Lifetime Warranty been established; fans purchased from an unauthorized dealer; ordinary wear and
If any part of your ceiling fan motor fails during your ownership of the fan due to tear; minor cosmetic blemishes; refurbished fans; and fans that are damaged due to
a defect in material or workmanship, as determined solely by Hunter, Hunter will any of the following: improper installation, misuse, abuse, improper care, failure to
provide you with a replacement fan free of charge.* The foregoing limited warranty follow Hunter instructions, accidental damage caused by the fan owner or related
applies only to the motor itself and does not apply to electronic controls – such parties, modifications to the fan, improper or incorrectly performed maintenance or
as remote control transmitters, remote control receivers, or capacitors – used in repair, improper voltage supply or power surge, use of improper parts or accessories,
conjunction with the motor. Such electronic control items are included in the one- failure to provide maintenance to the fan, or acts of God (e.g. flood).
year limited warranty below.
ORIGINAL PURCHASER’S SOLE AND EXCLUSIVE REMEDY FOR A CLAIM OF ANY
Other – One-Year Limited Warranty KIND WITH RESPECT TO THIS PRODUCT SHALL BE THE REMEDIES SET FORTH
HEREIN. HUNTER FAN COMPANY IS NOT RESPONSIBLE FOR CONSEQUENTIAL OR
Except as otherwise indicated throughout this warranty, if any part of your Hunter INCIDENTAL DAMAGES, DUE TO PRODUCT FAILURE, WHETHER ARISING OUT OF
ceiling fan fails at any time within one year of the date of purchase due to a defect BREACH OF WARRANTY, BREACH OF CONTRACT, OR OTHERWISE. Some States do
in material or workmanship, as determined solely by Hunter, Hunter will provide a not allow the exclusion or limitation of incidental or consequential damages, so the
replacement part free of charge.* above limitation or exclusion may not apply to you.
Light Kits – Warranty May Vary ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A
Light kits are included in the one-year limited warranty. However, you may qualify for PARTICULAR PURPOSE APPLICABLE TO THIS PRODUCT ARE LIMITED IN
additional warranty coverage if your fan includes one of the following: DURATION TO THE PERIOD OF COVERAGE OF THE APPLICABLE LIMITED
WARRANTIES SET FORTH ABOVE. Some States do not allow limitations on how long
• LED Light Kits – Three-Year Limited Warranty an implied warranty lasts, so the above limitation may not apply to you.
If your LED light kit module (not including glass components) or LED bulb
fails at any time within three years of the date of purchase due to a defect in How Does State Law Affect Warranty Coverage?
material or workmanship, as determined solely by Hunter, Hunter will
provide a replacement part free of charge.* This warranty gives you specific legal rights. You may also have other rights which vary
from state to state.
Applies to Lumination® LED Luminaires purchased from Current between August 1, 2020, and the date on which this Limited Warranty
document is later superseded.
WARRANTY: Subject to the terms and conditions specified in this Limited Warranty, Current Lighting Solutions, LLC (‘Current’), warrants
that Lumination® LED luminaires (“Product”) purchased directly from Current will be free from defects in material and workmanship
until the earlier of (i) five (5) years from the date of manufacture, and (ii) 22,000 hours of operation. Current does not warrant the
photoelectric controls, which are covered by the applicable warranty (if any) of the company that manufactured the photoelectric
controls.
REMEDY: If a Product fails to meet the warranty set forth above, then Current will, at its option, either (i) repair the defective Product, (ii)
provide a free replacement Product or replacement parts, F.O.B. Current’s warehouse, or (iii) refund the purchase price paid to Current
for the Product or replacement parts. Any replacement Product or part will be comparable in function, but may not be identical to the
original. The replacement or repaired Product is warranted for the remainder of the original warranty period. Current is not responsible
for labor and other costs associated with removal or reinstallation.
TERMS AND CONDITIONS: This Limited Warranty is VOID if Purchaser or the user fails to comply with any applicable instructions and
recommendations of Current; if any components are replaced with components of other manufacturers; or if the Product is operated
outside the specified electrical values or is subject to abnormal use or stress, including under/over voltage conditions, excessive
switching cycles, and operation in environmental conditions (e.g., ambient temperature) outside normal specified operating range.
Current shall not be responsible for any failure of Products that result from external causes, including, but not limited to, acts of God;
power surges that exceed product specification; improper power supply; fault or negligence of the Purchaser or user; improper or
unauthorized use, installation, handling, storage, maintenance, alteration or service; any abuse, misuse, abnormal use or use in violation
of any applicable standard, code or instructions for use in installations including those contained in the latest National Electrical Code
(NEC), the Standards for Safety of Underwriters Laboratory, Inc. (UL), Standards for the American National Standards Institute (ANSI), in
Canada, the Canadian Standards Association (CSA), Europe (CE), Australia (C-Tick); or any cause other than a defect in the material or
workmanship of the Product itself. Notwithstanding anything to the contrary in this Limited Warranty, the LED module of the Product
shall not be deemed to fail to meet the warranties above unless ten percent (10%) or more of the LEDs in the module do not light. This
limited warranty extends only to Purchaser, but Current will honor, under the terms of this Limited Warranty, valid warranty claims by
Purchaser arising from a failure to meet the above warranty when the Product has been resold in new condition and used only by the
original end user.
HOW TO MAKE A WARRANTY CLAIM: Current must issue a Return Material Authorization (RMA#) for all requests for warranty review.
To make a warranty claim, retain the failed Products and notify your Current sales or customer service representative in writing within
thirty (30) days of the failure. After contacting Current and receiving an RMA number, Purchaser shall promptly return the Product after
receiving instructions regarding if, when, and where to ship the Product. The Product must be returned within 10 days of receiving the
RMA number, and the shipping box must be clearly marked with RMA number. Failure to follow this procedure shall void this Limited
Warranty. Current reserves the right to examine all failed Product to determine the cause of failure and patterns of usage and shall be
the sole judge as to whether any Product is defective and covered under this Limited Warranty.
LIMITS OF LIABILITY: THE FOREGOING LIMITED WARRANTY CONSTITUTES THE SOLE AND EXCLUSIVE WARRANTY AND REMEDY
OF THE PURCHASER AND THE SOLE LIABILITY OF CURRENT FOR THE SPECIFIED LED LUMINAIRES AND IS IN LIEU OF ALL OTHER
WARRANTIES, WHETHER WRITTEN, ORAL, IMPLIED OR STATUTORY. NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE IS MADE OR IS TO BE IMPLIED. IN NO EVENT SHALL CURRENT BE LIABLE FOR ANY OTHER COSTS OR DAMAGES
INCLUDING LOST PROFITS, INDIRECT, INCIDENTAL, SPECIAL OR CONSEQUENTIAL DAMAGES.
© 2021 Current Lighting Solutions, LLC. All rights reserved. GE is a trademark of the General Electric Company and is used under license.
© 2020 Current Lighting Solutions, LLC | 1975 Noble Road | East Cleveland, OH 44112 | USA
P.O. Box 410
Schofield, WI 54476
Phone: 715.359.6171
www.greenheck.com
Greenheck Fan Corporation warrants its SP/CSP products to be free of any defect in material or
workmanship for a period of three years from the date of shipment. In the event of such a defect
during the warranty period, Greenheck Fan Corporation agrees, at its option, to either repair or
replace the defective product free of charge.
This warranty runs to the original purchaser of such SP/CSP products for a period of three years
from the date of shipment. Any product repaired or replaced under this warranty will, itself, be
warranted only for the remainder of the warranty period of the original product being repaired or
replaced.
All light bulbs are excluded under this limited warranty. Greenheck Fan Corporation is not
responsible for any removal, installation, or transportation cost.
In the case of any query in relation to unit operation or malfunction, please contact the
CIRCUTOR, SA Technical Support Service.
7.- GUARANTEE
CIRCUTOR guarantees its products against any manufacturing defect for two years after the
delivery of the units.
CIRCUTOR will repair or replace any defective factory product returned during the guarantee
period.
• No returns will be accepted and no unit will be repaired or replaced if it is not ac-
companied by a report indicating the defect detected or the reason for the return.
•The guarantee will be void if the units has been improperly used or the stora-
ge, installation and maintenance instructions listed in this manual have not been
followed. “Improper usage” is defined as any operating or storage condition con-
trary to the national electrical code or that surpasses the limits indicated in the
technical and environmental features of this manual.
• CIRCUTOR accepts no liability due to the possible damage to the unit or other
parts of the installation, nor will it cover any possible sanctions derived from a pos-
sible failure, improper installation or “improper usage” of the unit. Consequently,
this guarantee does not apply to failures occurring in the following cases:
- Overvoltages and/or electrical disturbances in the supply;
- Water, if the product does not have the appropriate IP classification;
- Poor ventilation and/or excessive temperatures;
- Improper installation and/or lack of maintenance;
- Buyer repairs or modifications without the manufacturer’s authorisation.
Instruction Manual 93
from state to state.
Garantía limitada de por vida This warranty gives you specific legal rights. You may also have other rights which vary
provide a replacement part free of charge.*
Hunter Fan Company otorga la siguiente garantía limitada al comprador original de este ventilador vidrio) falla en cualquier momento durante los siguientes tres años a partir la fecha How Does State Law Affect Warranty Coverage? in material or workmanship, as determined solely by Hunter, Hunter will
para techo marca Hunter: Este documento puede ser encontrado en Internet en de compra, debido a un defecto en los materiales o la mano de obra, conforme Hunter fails at any time within three years of the date of purchase due to a defect
www.HunterFan.com. ¡Gracias por elegir Hunter! lo determine a su arbitrio, Hunter le proporcionará un reemplazo de la pieza sin cargo the above limitation may not apply to you.
If your LED light kit module (not including glass components) or LED bulb
para usted.* ABOVE. Some States do not allow limitations on how long an implied warranty lasts, so
• LED Light Kits — Three-Year Limited Warranty
¿Cómo puede obtenerse un servicio cubierto en la garantía? * Si no le podemos brindar un producto o pieza de reemplazo igual para su ventilador, le proporcionaremos PERIOD OF COVERAGE OF THE APPLICABLE LIMITED WARRANTIES SET FORTH additional warranty coverage if your fan includes one of the following:
un producto o pieza de reemplazo comparable o superior, conforme el arbitrio de Hunter. PURPOSE APPLICABLE TO THIS PRODUCT ARE LIMITED IN DURATION TO THE Light kits are included in the one-year limited warranty. However, you may qualify for
Se requiere un comprobante de compra cuando solicite el servicio cubierto en la garantía. El ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR Light Kits — Warranty May Vary
comprador original debe presentar un recibo de compra u otro documento que compruebe su
compra. Hunter, a su arbitrio, puede aceptar un recibo de regalo. Para obtener servicio, póngase ¿Qué es lo que NO cubre esta garantía? above limitation or exclusion may not apply to you. free of charge.*
en contacto con Hunter Fan Company por internet o por teléfono. not allow the exclusion or limitation of incidental or consequential damages, so the or workmanship, as determined solely by Hunter, Hunter will provide a replacement part
La mano de obra está excluida. Esta garantía no cubre ningún costo u honorarios asociados con BREACH OF WARRANTY, BREACH OF CONTRACT, OR OTHERWISE. Some States do
www.HunterFan.com/Support/Contact-Us/ la mano de obra (incluyendo los honorarios del electricista) requeridos para instalar, retirar o INCIDENTAL DAMAGES, DUE TO PRODUCT FAILURE, WHETHER ARISING OUT OF
fan fails at any time within one year of the date of purchase due to a defect in material
1-888-830-1326 reemplazar un ventilador o cualquier pieza del mismo. HEREIN. HUNTER FAN COMPANY IS NOT RESPONSIBLE FOR CONSEQUENTIAL OR
Except as otherwise indicated throughout this warranty, if any part of your Hunter ceiling
Por favor no envíe a Hunter su ventilador ni ninguna de sus partes. Le entrega será rechazada.
Other — One-Year Limited Warranty
No hay garantía para lámparas/bombillas (excepto si se especifica lo contrario); las baterías KIND WITH RESPECT TO THIS PRODUCT SHALL BE THE REMEDIES SET FORTH
del control remoto; los ventiladores comprados o instalados fuera de los Estados Unidos; ORIGINAL PURCHASER’S SOLE AND EXCLUSIVE REMEDY FOR A CLAIM OF ANY motor. Such electronic control items are included in the one-year limited warranty below.
¿Qué es lo que cubre esta garantía? los ventiladores propiedad de otra persona distinta al comprador original; los ventiladores maintenance to the fan, or acts of God (e.g. flood). transmitters, remote control receivers, or capacitors – used in conjunction with the
cuyo comprobante de compra no haya sido presentado; los ventiladores comprados en un voltage supply or power surge, use of improper parts or accessories, failure to provide to the motor itself and does not apply to electronic controls – such as remote control
Motor — Garantía limitada de por vida distribuidor no autorizado; el desgaste por uso normal; imperfecciones cosméticas menores; to the fan, improper or incorrectly performed maintenance or repair, improper you with a replacement fan free of charge.* The foregoing limited warranty applies only
Si cualquier pieza de su ventilador para techo Hunter falla durante el tiempo que el ventilador ventiladores remanufacturados; y aquellos ventiladores que hayan sido dañados debido a instructions, accidental damage caused by the fan owner or related parties, modifications defect in material or workmanship, as determined solely by Hunter, Hunter will provide
sea de su propiedad, debido a un defecto en el material o en la mano de obra, conforme Hunter cualquiera de las siguientes causas: instalación inapropiada, mal uso, abuso, falta de cuidado, no following: improper installation, misuse, abuse, improper care, failure to follow Hunter If any part of your ceiling fan motor fails during your ownership of the fan due to a
lo determine a su arbitrio, le proporcionaremos un ventilador de remplazo sin costo para usted.* seguir las instrucciones de Hunter, daño accidental ocasionado por el propietario o personas cosmetic blemishes; refurbished fans; and fans that are damaged due to any of the Motor — Limited Lifetime Warranty
La garantía limitada anterior sólo aplica al motor y no aplica a controles electrónicos como relacionadas, modificaciones al ventilador, mantenimiento o reparación realizados inadecuada established; fans purchased from an unauthorized dealer; ordinary wear and tear; minor
trasmisores y receptores de control remoto, o los capacitores utilizados junto con el motor. Tales o incorrectamente, suministro de voltaje incorrecto o sobrecargas de energía, uso de partes o other than the original purchaser; fans for which proof of purchase has not been What Does This Warranty Cover?
controles electrónicos están incluidos en la garantía limitada de un año señalada abajo. accesorios inapropiados, no dar mantenimiento al ventilador, o desastres naturales (ej. inundación). batteries; fans purchased or installed outside the United States; fans owned by someone
Otros — Garantía limitada por un año LOS REMEDIOS ÚNICOS Y EXCLUSIVOS DEL COMPRADOR ORIGINAL PARA RECLAMOS There is no warranty for light bulbs (except where otherwise noted); remote control Please do not ship your fan or any fan parts to Hunter. Delivery will be refused.
A menos que se indique de otra manera a lo largo de esta garantía, si cualquier pieza de su DE CUALQUIER CLASE CON RESPECTO A ESTE PRODUCTO DEBEN SER LOS ESTABLECIDOS (including electrician’s fees) required to install, remove, or replace a fan or any fan parts.
ventilador de techo Hunter falla en cualquier momento durante el primer año desde la fecha de EN ESTE DOCUMENTO. HUNTER FAN COMPANY NO ES RESPONSABLE POR DAÑOS Labor Excluded. This warranty does not cover any costs or fees associated with the labor
1-888-830-1326
compra, debido a un defecto en los materiales o la mano de obra, conforme Hunter lo determine a EMERGENTES O INCIDENTALES, DEBIDO A LA FALLA DEL PRODUCTO, YA SEA QUE SURJA DE www.HunterFan.com/Support/Contact-Us/
su arbitrio, Hunter le proporcionará un reemplazo de la pieza sin cargo para usted.* UNA INFRACCIÓN A LA GARANTÍA, UNA INFRACCIÓN DEL CONTRATO O POR CUALQUIER Fan Company online or by phone.
OTRA CAUSA. Algunos estados no permiten la exclusión ni limitación de daños incidentales ni
What Does This Warranty NOT Cover?
Conjuntos de lámparas — La garantía puede variar emergentes, así que las limitaciones o exclusiones anteriores pueden no aplicarse a usted.
Hunter, at its sole discretion, may accept a gift receipt. To obtain service, contact Hunter
Los conjuntos de lámparas están incluidos en la garantía limitada de un año. Sin embargo, quizá must present a sales receipt or other document that establishes proof of purchase.
califique para una cobertura de garantía adicional si su ventilador incluye alguno de los siguientes CUALQUIER GARANTÍA IMPLÍCITA DE COMERCIABILIDAD O IDONEIDAD PARA UN comparable or superior replacement product/part at the sole discretion of Hunter. Proof of purchase is required when requesting warranty service. The original purchaser
elementos: PROPÓSITO EN PARTICULAR APLICABLE A ESTE PRODUCTO ESTÁ LIMITADA POR LA * If no replacement product/part can be provided for your fan, we will provide a
DURACIÓN DEL PERIODO DE COBERTURA DE LAS GARANTÍAS LIMITADAS APLICABLES How Can Warranty Service Be Obtained?
• Conjunto de lámparas LED — Garantía limitada de tres años ESTABLECIDAS ANTERIORMENTE. Algunos estados no permiten limitaciones sobre la duración
provide a replacement light kit free of charge.*
Si su módulo de conjunto de lámparas LED (no incluye componentes de vidrio) o de una garantía implícita, de modo que la limitación antes mencionada puede no aplicarse a usted.
in material or workmanship, as determined solely by Hunter, Hunter will
si la lámpara LED falla en cualquier momento durante los siguientes tres años a fails at any time within three years of the date of purchase due to a defect Thank you for choosing Hunter!
partir la fecha de compra, debido a un defecto en los materiales o la mano de obra, If your ENERGY STAR rated light kit (not including glass components) Hunter ceiling fan. This document can be found at www.HunterFan.com.
conforme Hunter lo determine a su arbitrio, Hunter le proporcionará un reemplazo ¿Cómo afecta la ley estatal a la cobertura de la garantía? • ENERGY STAR® Rated Light Kits — Three-Year Limited Warranty Hunter Fan Company grants this limited warranty to the original purchaser of this
de la pieza sin cargo para usted.*
Esta garantía le da dos derechos legales específicos. También usted puede tener otros derechos
• Conjunto de lámparas certificadas ENERGY STAR® — Garantía limitada de tres años que varían de un estado a otro.
Si su conjunto de lámparas certificadas ENERGY STAR® (no incluye componentes de
Limited Lifetime Warranty
Español
La información que se entreta a
Lea y guarde estas instrucciones ______________________________
Where Purchased
Limited Warranty
This product is subject to and covered by a limited warranty, a!copy!of!which!
can!be!found!at!www.fedsig.com/SSG9Warranty. A copy of this limited warranty
can also be obtained by written request to Federal Signal Corporation, 2645
Federal Signal Drive, University Park, IL 60484, email to info@fedsig.com or
call +1 708-534-3400.
www.fedsig.com
2!
APENDIX E
POINTS OF CONTACT FOR WARRANTY CALLS
Yeymi Donaire_______________
Email: eternascab@eterna.hn
Osvaldo Munguía
Email: omunguía@eterna.hn
APENDIX F
Door Access Code
C3789X
C2567X
C4790X
C2790X
Request the unique code of room doors to FLUOR Staff on charge to room’s
assignment.
12 Plex Housing
Phase I
Operation &
Maintenance
Manuals
May 2021