First Pole to Clear Factor- Calculation & Significance Topics

Power System
Power System Protection
Electrical Machines

First Pole to Clear Factor of a Circuit Breaker is the ratio of power frequency recovery voltage DC Machine

across the first pole to clear the arc to the normal phase to ground voltage when all the three Measurement and Instrumentation

poles of breaker are open. It is denoted as kpp. If Vcb be the recovery voltage across the first AC Circuit
Digital Electronics
pole of CB and Vph be the phase to ground voltage then
Electrical Drives
Power Electronics
First Pole to Clear Factor = Vcb / Vph
EM Theory

The value of kpp depends on the system grounding. For system with non-effectively neutral
https://electricalbaba.com/first-pole-to-clear-factor/ 1/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts

Motor Control Parts - Place


Your Order Online
Ad High-Quality Contact Kits, Motor
Ad
Starters & More From Various Popular…
chartercontact.com

Learn more

earthing, kpp = 1.5 while for system with effectively neutral earthing, kpp = 1.3

Let us now understand the concept of first pole to clear factor in detail. We know that a
circuit breaker is used to make or break circuit or part of circuit in power system. Since the
power system is mostly inductive in nature, therefore the current flowing in the network is
lags the voltage. This definitely means that whenever the voltage is zero, current is at its peak
and when voltage is at its peak, current is zero. In circuit breaker, the basic philosophy used
to break the circuit current is to open the breaker contacts at natural current zero. But the
three phases current are separated from each other by an angle of 120 degree. This means
that the natural zero of the three phases will take place at three different points of time.
Figure below shows the current interruption for an assumed fault.
Recent Posts

A Case Study on LBB Protection Logic


Single Phase Half Wave Controlled Rectifier
Phase Control of SCR – Definition, Explanation
and Advantage
Firing Angle of SCR Explained
Natural or Line Commutation- Principle with
Circuit Diagram

https://electricalbaba.com/first-pole-to-clear-factor/ 2/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts

As clear from the figure, the current of Y phase first comes to zero at 53.5 ms followed by R
and B phases (phase current first coming to natural zero is dependent on the time of
occurrence of fault). This means that first Y pole will be opened and then R and B pole of
breaker. When Y poles opens in response to any fault, the remaining two poles are closed.
This gives rise to high recovery voltage across the breaker contacts when compared with
phase to ground voltage when all the three poles are open.

Build Custom Cable


Assemblies
Ad Get custom cable assemblies
Ad
shipped to you in 5 days! Start building…
SV Microwave

Open

Let us consider a three phase fault as shown in figure below. The figure shows the simplified
Subscribe to our mailing list and get
equivalent circuit of effectively earthed neutral with three phase fault without involving
interesting stuff and updates to your email
earth. When the very first pole (here it is assumed that R pole opens first) interrupts the
inbox.
fault, the symmetry of the system is lost and the system goes into a pure a phase to phase
fault condition. Due to this, the voltage of short circuit point shifts.
Your Email Please

https://electricalbaba.com/first-pole-to-clear-factor/ 3/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts

I consent to my submitted data being


collected via this form*

SUBSCRIBE NOW

we respect your privacy and take protecting it


seriously

The power frequency recovery voltage across the first opening pole i.e. R pole (assumed) is
nothing but the difference between the source side voltage and network side voltage. In our
case, this will be different between the source side voltage Ua and network side voltage Vp
(voltage at short circuit point). Thus,

VR = Recovery Voltage across the first opening pole

= Ua – Vp …………..(1)

From the symmetry of the system when the system goes into pure phase to phase fault, the
voltage at the short circuit point will be average of the Ub and Uc. The phasor diagram is
shown below.

https://electricalbaba.com/first-pole-to-clear-factor/ 4/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts

Vp = (phasor sum of Ub and Uc) / 2

= 0.5Ub

But magnitude of Ua, Ub and Uc are same, hence

Vp = 0.5Ua

Therefore from (1),

VR = Ua + 0.5Ua

= 1.5Ua

Hence from the definition,

First Pole to Clear Factor, kpp = 1.5Ua / Ua

= 1.5

Thus we see that, value of first pole to clear factor for effectively gounded neutral system
with ungrounded fault is 1.5.

https://electricalbaba.com/first-pole-to-clear-factor/ 5/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts

For three phase to earth faults with effectively earth neutral, the value of kpp depend on the
positive sequence and zero sequence reactance. The value of kpp for such condition is given
as

kpp = 3 / [(X1 / X0) + 2]

where X1 = Positive Sequence Reactance

X0 = Zero Sequence Reactance

For grounded system as is the case with transmission line, the ratio of (X1 / X0) is 1/3 and
therefore the value of first pole to clear factor is 1.3.

Significance of First Pole to Clear Factor:

First Pole to Clear Factor is basically the impact of system grounding on the Transient
Recovery Voltage (TRV). Apart from system grounding, TRV depends on many other factors.
All the three poles of circuit breaker can never open simultaneously; therefore first pole to
clear factor must be taken care for the design of breaker. The dielectric strength of breaker
must be sufficient enough to sustain the TRV across the first pole to clear the fault.

 March 23, 2018  admin  Power System  No Comment  first pole to clear factor

«Auto Transfer System – Basic Concept Calculation of Restriking Voltage»

https://electricalbaba.com/first-pole-to-clear-factor/ 6/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts

2019's Best Concept of Cutest Bras for Transient


Bikinis Neutral Grounding Women Over 50 Recovery Voltage
(TRV
Ad Bikini Clearance Sales electricalbaba.com Ad Intimates & More electricalbaba.com

Electrician - Symmetrical Fault Working Principle Power System


Electrical and Short Circuit of Residual Archives
Contractor kVA Voltage…
Ad jmbesol.com electricalbaba.com electricalbaba.com electricalbaba.com

Leave A Reply

Your email address will not be published. Required fields are marked *

 Comment

https://electricalbaba.com/first-pole-to-clear-factor/ 7/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts

 Name *

 Email *

 Website

 Notify me when new comments are added.

Post Comment

This site uses Akismet to reduce spam. Learn how your comment data is processed.

Electrical Concepts © 2020 | Theme: Optimize ↑

About Us | Contact Us | Downloads | List of downloadable generalized specification just for you. | Privacy Policy |

https://electricalbaba.com/first-pole-to-clear-factor/ 8/8

You might also like