First Pole to Clear Factor of a Circuit Breaker is the ratio of power frequency recovery voltage DC Machine
across the first pole to clear the arc to the normal phase to ground voltage when all the three Measurement and Instrumentation
poles of breaker are open. It is denoted as kpp. If Vcb be the recovery voltage across the first AC Circuit
Digital Electronics
pole of CB and Vph be the phase to ground voltage then
Electrical Drives
Power Electronics
First Pole to Clear Factor = Vcb / Vph
EM Theory
The value of kpp depends on the system grounding. For system with non-effectively neutral
https://electricalbaba.com/first-pole-to-clear-factor/ 1/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts
Learn more
earthing, kpp = 1.5 while for system with effectively neutral earthing, kpp = 1.3
Let us now understand the concept of first pole to clear factor in detail. We know that a
circuit breaker is used to make or break circuit or part of circuit in power system. Since the
power system is mostly inductive in nature, therefore the current flowing in the network is
lags the voltage. This definitely means that whenever the voltage is zero, current is at its peak
and when voltage is at its peak, current is zero. In circuit breaker, the basic philosophy used
to break the circuit current is to open the breaker contacts at natural current zero. But the
three phases current are separated from each other by an angle of 120 degree. This means
that the natural zero of the three phases will take place at three different points of time.
Figure below shows the current interruption for an assumed fault.
Recent Posts
https://electricalbaba.com/first-pole-to-clear-factor/ 2/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts
As clear from the figure, the current of Y phase first comes to zero at 53.5 ms followed by R
and B phases (phase current first coming to natural zero is dependent on the time of
occurrence of fault). This means that first Y pole will be opened and then R and B pole of
breaker. When Y poles opens in response to any fault, the remaining two poles are closed.
This gives rise to high recovery voltage across the breaker contacts when compared with
phase to ground voltage when all the three poles are open.
Open
Let us consider a three phase fault as shown in figure below. The figure shows the simplified
Subscribe to our mailing list and get
equivalent circuit of effectively earthed neutral with three phase fault without involving
interesting stuff and updates to your email
earth. When the very first pole (here it is assumed that R pole opens first) interrupts the
inbox.
fault, the symmetry of the system is lost and the system goes into a pure a phase to phase
fault condition. Due to this, the voltage of short circuit point shifts.
Your Email Please
https://electricalbaba.com/first-pole-to-clear-factor/ 3/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts
SUBSCRIBE NOW
The power frequency recovery voltage across the first opening pole i.e. R pole (assumed) is
nothing but the difference between the source side voltage and network side voltage. In our
case, this will be different between the source side voltage Ua and network side voltage Vp
(voltage at short circuit point). Thus,
= Ua – Vp …………..(1)
From the symmetry of the system when the system goes into pure phase to phase fault, the
voltage at the short circuit point will be average of the Ub and Uc. The phasor diagram is
shown below.
https://electricalbaba.com/first-pole-to-clear-factor/ 4/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts
= 0.5Ub
Vp = 0.5Ua
VR = Ua + 0.5Ua
= 1.5Ua
= 1.5
Thus we see that, value of first pole to clear factor for effectively gounded neutral system
with ungrounded fault is 1.5.
https://electricalbaba.com/first-pole-to-clear-factor/ 5/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts
For three phase to earth faults with effectively earth neutral, the value of kpp depend on the
positive sequence and zero sequence reactance. The value of kpp for such condition is given
as
For grounded system as is the case with transmission line, the ratio of (X1 / X0) is 1/3 and
therefore the value of first pole to clear factor is 1.3.
First Pole to Clear Factor is basically the impact of system grounding on the Transient
Recovery Voltage (TRV). Apart from system grounding, TRV depends on many other factors.
All the three poles of circuit breaker can never open simultaneously; therefore first pole to
clear factor must be taken care for the design of breaker. The dielectric strength of breaker
must be sufficient enough to sustain the TRV across the first pole to clear the fault.
March 23, 2018 admin Power System No Comment first pole to clear factor
https://electricalbaba.com/first-pole-to-clear-factor/ 6/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts
Leave A Reply
Your email address will not be published. Required fields are marked *
Comment
https://electricalbaba.com/first-pole-to-clear-factor/ 7/8
3/28/2020 First Pole to Clear Factor- Calculation & Significance | Electrical Concepts