GE Fanuc IC694MDL940

http://www.pdfsupply.com/automation/ge-fanuc/rx3i-pacsystem/IC694MDL940

Rx3i PacSystem

Output module, relay 2 amp 16 point, non isolated. IC694M IC694MD


IC694MDL

919-535-3180
sales@pdfsupply.com
7

Output Module, Relay Output, N.O., 2 Amp, 16 Point: IC694MDL940


The 2 Amp Relay Output module, IC694MDL940, provides 16 normally–
1 2 3 4 5 6 7 8 open relay circuits for controlling output loads. The output switching
F capacity of each output is 2 Amps. The output points are in four groups
9 10 11 12 13 14 15 16
of four points each. Each group has a common power output terminal.
The relay outputs can control a wide range of load devices, such as:
IC694MDL940 motor starters, solenoids, and indicators. Power for the internal relay
Q1
circuits is provided by the +24 volt DC bus on the backplane. The user
Q2
must supply the AC or DC power to operate field devices.
Q3 Individual numbered LEDs show the ON/OFF status of each output point.
Q4 There are no fuses on this module. The red bands on the label show that
Q5 MDL940 is a high-voltage module.
Q6
This module can be installed in any I/O slot in an RX3i system.
Q7

Q8 Specifications: MDL940
Q9
Rated Voltage 24 volts DC, 120/240 volts AC (nominal - see
Q10 the following table for exceptions)
Q11 Operating Voltage 5 to 30 volts DC
Q12 5 to 250 volts AC, 50/60 Hz
Q13 Outputs per Module 16 (four groups of four outputs each)
Q14 Isolation:
Q15 Field to 250 VAC continuous;
Q16 Backplane and to 1500 VAC for 1 minute
Frame Ground
Point to Point 250 VAC continuous; 1500 VAC for 1 minute
Maximum Load 2 Amps pilot duty maximum per output
4 Amps maximum per common
Minimum Load 10mA
Maximum Inrush 5 Amps
On Response Time 15ms maximum*
Off Response Time 15ms maximum*
Power Consumption, 7mA from 5 volt bus on backplane
all outputs on 135mA from relay 24V bus on backplane
Refer to Appendix A for product standards and general specifications.
* When this module is used with DC power supply IC695PSD040 or PSD140, special
precautions should be taken because dropouts in the source voltage will be seen by
this module and may cause relay dropouts.

7-48 PACSystems™ RX3i System Manual – October 2005 GFK-2314C


7

Load Current Limitations: MDL940


Maximum Current
Operating for Load Type Typical Contact Life
Voltage Resistive Lamp or Solenoid * (Number of Operations)
24 to 120 VAC 2 Amps 1 Amp 300,000
24 to 120 VAC 1 Amp 0.5 Amp 500,000
24 to 120 VAC 0.1 Amp 0.05 Amp 1,000,000
240 VAC 2 Amps 1 Amp 150,000
240 VAC 1 Amp 0.5 Amp 200,000
240 VAC 0.1 Amp 0.05 Amp 500,000
24 VDC – 2 Amps 100,000
24 VDC 2 Amps 1 Amp 300,000
24 VDC 1 Amp 0.5 Amp 500,000
24 VDC 0.1 Amp 0.05 Amp 1,000,000
125 VDC 0.2 Amp 0.1 Amp 300,000

∗ Assumes a 7 ms time constant


Relay contact life, when switching inductive loads, will approach resistive load contact life if
suppression circuits are used. The following figures are examples of typical suppression circuits
for AC and DC loads. The 1A, 200V diode shown in the DC load suppression circuit is an
industry standard 1N4935. The resistor and capacitor shown for AC load suppression are
standard components.

Load Suppression Examples for Output Module IC694MDL940

AC Loads
MDL940 DC Loads .022 100 Ohms
MDL940
1A, 200V
600V 1/2W

Relay
Relay
Output
Load Coil Output
Load Coil
Comm

DC Supply
Comm
~
AC Source

GFK-2314C Chapter 7 Discrete Output Modules 7-49


7

Field Wiring: MDL940


Terminal Connection
1 Outputs 1 – 4 common (return)
2 Output 1
3 Output 2
4 Output 3
5 Output 4
6 Outputs 5 -8 common (return)
7 Output 5
8 Output 6
9 Output 7
10 Output 8
11 Outputs 9 - 12 common (return)
12 Output 9
13 Output 10
14 Output 11
15 Output 12
16 Outputs 13 – 16 common (return)
17 Output 13
18 Output 14
19 Output 15
20 Output 16

Module Circuits Terminals Field Wiring

Other
Circuits 1
2 Q1
3 Q2
LED 4 Q3
5 Q4
6
7 Q5
8 Q6
Relay N. O.
9 Q7
10 Q8
11
12 Q9
13 Q10
14 Q11
15 Q12
16
17 Q13
18 Q14
19 Q15
20 Q16

7-50 PACSystems™ RX3i System Manual – October 2005 GFK-2314C