Last Measurement Deviation Report

*********************************

Database: GPF.rbm
Area: Utlities - GPF
Report Date: 13-Jul-22 12:42

Reference Value is the PREVIOUS DATA

POINT POINT CURRENT REF ABS. % ALR


ID DESCRIPTION VALUE VALUE UNITS DELTA DEV. SYM
----- ----------------------------- ------- ----- ------- ------- ---- ---

P-348-02 F - Hot Oil Circulation Pump-F (13-Jul-22) PARM = OVERALL


MOH=Motor Outboard Horizontal 16.04 4.047 mm/Sec 11.99 296 %+#
MOV=Motor Outboard Vertical 5.875 3.884 mm/Sec 1.991 51 %
MOA=Motor Outboard Axial 4.621 7.113 mm/Sec -2.492 -35
MIH=Motor Inboard Horizontal 3.773 3.122 mm/Sec .652 21
MIV=Motor Inboard Vertical 6.112 4.604 mm/Sec 1.508 33
MIA=Motor Inboard Axial 6.051 3.347 mm/Sec 2.704 81 %
PIH=Pump Inboard Horizontal 3.705 2.336 mm/Sec 1.369 59 %
PIV=Pump Inboard Vertical 1.821 1.728 mm/Sec .093 5
PIA=Pump Inboard Axial 2.660 2.537 mm/Sec .124 5
POH=Pump Outboard Horizontal 3.127 2.458 mm/Sec .669 27
POV=Pump Outboard Vertical 1.912 2.301 mm/Sec -.389 -17
POA=Pump Outboard Axial 3.084 2.686 mm/Sec .398 15

----------------------------------------------------------------------------

% - Maximum Percentage Alarm


+ - Maximum Delta Alarm
# - Maximum Value Alarm

Remarks:-
Vibration trend increased.
Abnormal sound from motor.
Broken/Cracked rotor bars loose rotor bar joints.
Also need to check motor bearings.
Vibration values have sufficient severity to cause damage to the machine.