Professional Documents
Culture Documents
TABLE OF CONTENTS
Introduction The introduction of high performance Redistributors share the same mechanical
Liquid distributors are used in packed tower packings in the early 1980s design characteristics as distributors, but
towers above each bed of packing. accentuated design deficiencies of they also include gas riser covers and pos-
distributors available at the time. In sibly wall wipers to collect all liquid raining
The liquid distributor is located response, Saint-Gobain NorPro introduced down from the packing above. The ques-
above the bed, usually 6 to 8 in. distributors with attributes designed to tion of when to redistribute liquid is not
[150 – 200 mm] above the packing. correct these deficiencies. These attributes easy to answer.
This provides sufficient space for the gas are well-understood by us and have been
to disengage from the bed before it There are four reasons to have more than
incorporated in NorPro™ Intalox® one bed of packing in a tower: feed
passes through the distributor. distributors. introduction, liquid cross-mixing, distribu-
An ideal distributor possesses the We offer two major categories of tion correction and product side-draws.
following attributes, each with a specific liquid distributors to meet the requirements Introduction of a feed (liquid or vapor) into
effect on the overall performance of a of specific applications. In determining a tower with packing above and below
packed tower: which category to choose, it is necessary nearly always requires a split in the beds
■ Uniform liquid distribution to know how sensitive the tower perform- for a redistributor.
■ Resistance to plugging or fouling ance is to distribution uniformity. Will a An important factor to keep in mind with
slight variation of distribution quality the introduction of an external feed is that
■ Proper turndown capability significantly affect the tower performance? of mixing (homogenization of composition
■ Low gas pressure drop As a rule: or temperature). Mixing of liquid should be
■ Minimal distributor height to allow ■ NorPro Intalox distributors… considered when:
more packed bed heights
Used primarily for distillation ■ A tower has deep beds or;
■ Cross-mixing capability services, typically where a high- ■ A feed is sub-cooled more than
efficiency packing (IMTP® random 30° F [17° C] or;
packing, Intalox® wire gauze or ■ A feed composition differs from the
Intalox® structured packing) is used.
internal flow
Deep beds of any type of packing
require Intalox® distributors to Cross-mixing is an optional feature on
maximize performance. most of our trough-type redistributors. By
eliminating the need for liquid collection in
■ NorPro traditional distributors…
a separate collector plate, the cross-mixing
Used for most absorption, stripping, option saves equipment and frees tower
and heat transfer services. Services space for more packing.
where a traditional packing (Pall Based on our operating experience, a
rings, Hy-Pak® packing, Intalox® conservative rule-of-thumb to use when
saddles, Raschig rings, etc…) is determining maximum depth is: A packed
used will usually use these less bed should be no higher than 15 times
costly distributors. the tower diameter and contain less than
20 theoretical stages. With proper
attention to initial distribution uniformity,
bed depths may be greater. However, we
do not recommend exceeding this limit
without consulting a Saint-Gobain NorPro
technical representative.
A-1
LIQUID DISTRIBUTORS
Distribution Quality Saint-Gobain NorPro developed a The significance of our distribution quality
Perfect liquid distribution could be defined distributor rating system for quantifying rating system is that the distributor rating
as providing equal liquid rate per unit area distribution quality, or performance. We correlates with tower performance.
of the packed bed surface. Many practical rate distribution uniformity as a percent- A tower containing deep beds of high-
factors restrict the achievement of this. age, where 100% indicates ideal uniform efficiency packing is sensitive to liquid
distribution and low percentage ratings distribution quality, whereas a tower
Liquid can be applied by sprays, weirs, or indicate that parts of the tower receive
orifices. Sprays can almost totally wet the containing shallow beds of a traditional
a liquid flow significantly different from packing is less sensitive to distribution
surface of a packed bed, but the point-to- other parts.
point flow variation is high. Weir distribu- quality.
tors provide discrete streams but flow For more information regarding our
variation is difficult to control. Orifice rating system, request a copy of the
distributors direct liquid to packing in publication, “Liquid and Gas Distribution
discrete streams. “Perfection” requires an in Commercial Packed Towers.”
infinite number of streams each of equal
flow. However, orifice size, fouling
considerations, and mechanical construc- TOWER PERFORMANCE CORRELATES WITH DISTRIBUTION QUALITY
tion details prevent high unit area point
count from being achieved.
The effect of liquid distribution quality on tower
Intalox distributors aim toward performance is shown by these actual results:
“perfection”:
20
(a) Orifices are laid out on a triangular 20
pattern, (preferred) or on a square 18 Stages Per Bed With
pattern, uninterrupted by gas System Base HETP
Actual Stages Per Bed of Packing
A-2
LIQUID DISTRIBUTORS
Point Count Cross Flow V-shaped weirs are less prone to blockage
The number of distribution points per unit As the liquid rate on a distributor is than orifices; orifices in a side wall are
area has an influence on the efficiency of increased, its cross flow capability and its generally less prone to blockage than
the uppermost part of a packed bed. primary (pre) distribution system become orifices in the bottom of a distributor;
When using larger packings, with relatively more important. orifices protected by an orifice strainer are
low efficiency, the effect of the number of less prone to blockage by a particulate
The cross flow capability of a distributor material than unprotected orifices. Orifice
distribution points is insignificant. However, reflects its ability to balance liquid from one
the effect can be considerable when using strainers are not recommended in systems
part of the distributor to another. It is that tend to coat surfaces.
smaller, high-efficiency packings. important to balance liquid on all gravity-
Saint-Gobain NorPro has established fed distributors. However, at high specific NorPro Intalox distributors with bottom
guidelines for Intalox distributors with high- liquid rates the liquid cross flow capacity orifices are not normally recommended for
performance packings as shown below. must be large to correct for system orifice sizes of 0.25 in. [6 mm] or less due
imperfection. to their fouling propensity. Intalox distribu-
In practice, a lower number of distribution tors designed with weirs may have flow
points per unit area may be the only way of The primary distribution of liquid into a variation outside the high-performance
achieving acceptable orifice diameters. distributor has been shown to have a range.
The number of distribution points per unit significant effect on overall distributor
performance. It is important that the feed The list below ranks the fouling resistance
area can be designed as required; of the various metering arrangements at
however, mechanical considerations system meters flow to one or more
appropriate points without excessive any given flow rate (most resistant - top,
usually limit the number to about to least - bottom):
18.6 pts/ft2 [200 pts/m2]. turbulence or horizontal velocity. This is
achieved by use of feed pipes and/or ■ “V” weir/spray
parting boxes. The design of the primary ■ Slotted weir
distribution system becomes increasingly
complex as the specific liquid rate and the ■ Side wall orifice with orifice strainer
column diameter increase. ■ Side wall orifice
Fouling ■ Bottom orifice with orifice strainer
If a distributor is to perform correctly it is ■ Bottom orifice
important that metering devices (orifices or
weirs) do not become fouled, since fouling Orifice strainers can protect a distributor
significantly reduces packing performance. from fouling with particulate matter such as
wall/pipe scale. Each orifice’s flow passes
There are several mechanisms of through a higher-surface-area strainer
distributor fouling: polymerization, before approaching the metering orifice.
sedimentation, coking, scale, debris, etc. However, orifice strainers are not effective
All precautions to eliminate fouling outside when fouling material pastes, coats or
the column should be adopted since sticks to metal. Other effective methods of
external strainers are far easier to clean protecting distributors from fouling include
than distributors. Regardless, the using sidewall orifices (positioned up
distributor should be considered for its from the bottom of the distributor) or
degree of fouling resistance. using weirs.
A-3
LIQUID DISTRIBUTORS
Operating Range
EFFECT OF OPERATING RANGE
A distributor will generally give its best
performance at liquid rates close to 100%
Figure 2
of design flow, with the performance
deteriorating as the liquid rate is reduced.
At 100% design flow, NorPro Intalox
distributors usually give a flow variation at
any point of the distributor of better than
±5% and at minimum rates better than
±8%. This will generally give an operating
range of 2:1 for a single-level orifice Traditional Distributors Flooded
Distributors
Flow Variation
distributor. If the minimum rate specifica-
tion is such that a wider flow variation can
be accepted, then a wider operating range
is possible. Increased
Flow
NorPro “traditional” distributors operate Variation
with much higher flow variations over a
typically broader range of operations than
Intalox distributors. Intalox Distributors
Intalox
Figure 2 shows the flow variation for the Distributors
Criteria Design Range
flow through a single-level orifice. The use
of a multi-level orifice enables the flow
100%
variation for the Intalox distributor to be Turndown
Design
Turnup
maintained over a very wide operating
range. % Liquid Load
9.3 2)
ft (8
P TS/ P T S/M
an operating range of 60 to 120% of the 30 7.4 2 0
t (6
P TS/f
5.6
design flow, the approximate orifice size is
(m3/h•m2)
20 50
indicated in Figure 3.
10 25
8 20
6 15
5
4 10
3
2 5
1
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
A-4
INTALOX DISTRIBUTORS
A-5
MODEL 106/107 INTALOX PAN DISTRIBUTOR/REDISTRIBUTOR
■ Diameters 10 - 36 in.
CONSTRUCTION DETAILS DESIGN OPTIONS
[250 – 900 mm]
■ Orifices in base The Models 106/107 are available in any ■ Orifice strainers
weldable sheet metal. Carbon steel is not ■ Expandable and gasketed wall
■ Liquid rates above 2 gpm/ft 2
assistance.
Model 107
18"
[450]
A-6
MODEL 116/117 INTALOX DECK DISTRIBUTOR/REDISTRIBUTOR
Model 117
A-7
MODEL 126/127 INTALOX TROUGH DISTRIBUTOR/REDISTRIBUTOR
Model 127
20"
14" [500]
[350]
A-8
MODEL 136/137 INTALOX PAN OR TROUGH DISTRIBUTOR/REDISTRIBUTOR
■ Diameters greater than 10 in. The resistance to fouling of this distributor The Model 136/137 rests on an annular
[250 mm] is higher than that of deck-type distributors ring or is suspended from beams or clips.
■ Side-wall orifices because it features a debris collection zone All joints are gasketed. See Section G for
below the sidewall orifices. Weirs can be ledge and material requirements.
■ High turndown ratio used as an alternative to orifices in high All distributors and redistributors include
■ Standard liquid rates between 0.3 fouling systems. However, flow variation overflow orifices which help prevent
and 12 gpm/ft2 [0.75 – 30 m3/h•m2] will be outside normal Intalox parameters. distributor flooding during liquid surges.
The Model 136 Intalox distributor and For single-phase liquid feeds to the The standard design for a Model 137
Model 137 Intalox redistributor are for distributor, a feed pipe or a feed pipe/ redistributor includes a weld-on wall wiper
towers greater than 10 in. [250 mm] ID parting box combination is required to on the vessel wall and gas riser covers to
with liquid rates between 0.3 and control feed velocity to the troughs. collect and redistribute liquid raining down
12 gpm/ft2 [0.75 - 30 m3/h•m2] where Two-phase liquid-vapor feeds require use from above.
fouling protection and/or high turndown is of a flashing feed device to adequately
required. Special designs can handle liquid separate phases and assure proper liquid
rates from 0.08 to 0.3 gpm/ft2 feed velocity. Refer to “Liquid/Vapor Feed
Devices,” Section B, for selection
DESIGN OPTIONS
[0.2 - 0.75 m3/h•m2]; for these cases, the
Model 120 strainer basket should be assistance.
considered to protect the small flow ■ Cross-mixing capability (in towers
orifices. Special designs can also handle CONSTRUCTION DETAILS greater than 55 in. [1400 mm] ID)
liquid rates above 12 gpm/ft2 [30 m3/h•m2]. ■ Orifice strainers
The Models 136/137 are usually The Models 136/137 are available in any
weldable sheet metal. Carbon steel is not ■ Leveling screws
constructed as pans for diameters below
30 inches [750 mm] and as troughs for recommended except for very high liquid ■ Expandable and gasketed wall wiper
diameters above 30 inches [750 mm]. The rates where orifice corrosion will not (small Model 137)
standard turndown for a single sidewall significantly affect distribution quality. ■ Non-standard point count
orifice is 2:1; however, the turndown Thermoplastic construction is available,
(See Page A-3)
range can be extended by using two or although such construction reduces
three orifices at different levels of the same distribution quality.
Model 136
discharge point. Turndown ratios up
to 10:1 are achievable. The liquid from
each discharge point is conducted into
the lower vapor velocity region below the
distributor troughs. This results in low
entrainment levels.
A
B
Standard design passes through 18 in.
[450 mm] nominal manway.
Model 137
20"
[500]
14"
[350]
A-9
MODEL 166 INTALOX TROUGH DISTRIBUTOR
B
Standard design passes through 18 in.
[450 mm] nominal manway.
Hd
A-10
MODEL 186 INTALOX TROUGH DISTRIBUTOR
Hd
A-11
TRADITIONAL DISTRIBUTORS FOR ABSORPTION, STRIPPING, OR HEAT TRANSFER
A-12
MODEL 845 PAN DISTRIBUTOR
1 9/16" [40]
7" - 11"
[178 - 279]
A-13
MODEL 798 PAN DISTRIBUTOR
■ Diameters 12 to 48 in.
CONSTRUCTION DETAILS DESIGN OPTIONS
[300 – 1200 mm]
■ Liquid rates between 1 and 8 The Model 798 is available in any weldable ■ Corrosion allowance
gpm/ft2 [2.5 – 20 m3/h•m2] sheet metal. ■ One-piece construction in columns
■ Weir in riser This distributor is supported either by a full greater than 18 in. [450 mm] in
ledge or lugs. Gasketing is standard on diameter
The Model 798 “weir riser” distributor is
plates with flow rates less than
used for highly fouling services in towers
4 gpm/ft2 [10 m3/h•m2].
less than 48 in. [1200 mm] ID. Cylindrical
risers with “V” weirs are used as liquid This distributor is not recommended for
downcomers. A wide turndown range is liquid redistribution. Consider the
possible due to the weirs, which allow Model 817 instead.
greater flow as the liquid head increases.
However, maximum liquid flow is severely
limited by the gas flow since they compete
for the same passage.
For liquid-only feeds to the distributor, use
a feed pipe to control feed velocity. Two-
phase liquid-vapor feeds require a flashing
feed device to adequately separate phases Model 798
and assure proper liquid feed velocity.
Refer to “Feed Devices,” Section B for
more information.
1 9/16" [40]
3.9" - 5.5"
[100 - 140]
A-14
MODEL 816/817/916/917 DECK DISTRIBUTOR/REDISTRIBUTOR
Model 917
18"
[450]
Ask your Saint-Gobain NorPro
representative about other options
at the time of inquiry.
Midspans may be required in towers larger than 10 ft [3000 mm] ID.
A-15
MODEL 806 TROUGH DISTRIBUTOR
16 1/4" [413]
Model 806 distributor with triangular weirs Towers larger than 146 in. [3700 mm] ID may require midspans for
and three parting boxes. metal construction; the maximum span is smaller for other materials.
A-16
MODEL 1016/1017 TROUGH DISTRIBUTOR/REDISTRIBUTOR
Model 1016
Model 1017
18"
[450]
12"
[300]
A-17
MODEL 844 PIPE-ARM DISTRIBUTOR
Model 844
TOWER CENTERLINE
SUPPORT SADDLE
Ask your Saint-Gobain NorPro BY CUSTOMER
INTERIOR FLANGE
representative about other options BY CUSTOMER
A-18
MODEL 1044 SPRAY-TYPE LIQUID DISTRIBUTOR
Model 1044
B TOWER CENTERLINE
VARIES
WALL CLIP(S)
INTERIOR FLANGE BY CUSTOMER
BY CUSTOMER
A-19
FEED DEVICES
Obtaining desirable tower performance For liquid and vapor feed devices above a
requires the proper handling of liquid and distributor (Table II), the selection depends
vapor entering the column. The types of on the type of distributor, flow rates, type
feeds, or inlets, into a column can generally of flow at feed (flashing or suppressed),
be classified into four major categories: turndown necessary, column height
■ Liquid only (contains less than 1% needed for flashing vapor distribution and
volume vapor) mixing of the inlet liquid with the overhead
liquid. In all cases, separating the two
■ Liquid and vapor above a packed phases is a primary concern. Additional
bed (flashing or suppressed flash) pre-distribution (via parting boxes) may
■ Vapor only below a packed bed be required.
■ Reboiler returns
Selection criteria for each category of feed
device is unique. The following tables Table I
assist in selecting the proper equipment.
The selection of liquid-only feed devices, SELECTING A LIQUID ONLY FEED PIPE
which are required as pre-distributors, (Inlet is less than 1% volume vapor)
depends on the type of distributor and on
turndown needs. Among the factors Used With Turndown
Saint-Gobain NorPro considers in Model Type Distributor Ratio
designing a feed device are flow rate,
operating range, degree of sub-cooled 119 Intalox ≤ 2:1
liquid versus column size and temperature,
and whether mixing with overhead liquid 129 Intalox ≤10:1
is required.
Table II
Tower Size
Model Flow Region in. [mm]
Spray or
192* > 96 [2400]
Separated
B-1
Two factors must be considered in For those towers employing suppressed
choosing the proper device for a vapor vaporization reboilers, the pressure release
only feed below a packed bed (Table III). and flash should not occur at the tower
1. Kinetic energy of inlet vapor nozzle. The Model 144 suppressed flash
distributor is effective for these towers.
The kinetic energy of the inlet vapor must
be considered in relation to the pressure
drop in the packed bed, the feed nozzle
arrangement and tower separation
requirements. Table III
2. Vapor composition
When the vapor is introduced between SELECTING VAPOR ONLY FEED DEVICES
packed beds, consider the degree of
Tower Size
mixing of the inlet vapor with the rising Model Typical Use in. [mm]
vapor. If a gross mismatch of composition
and/or temperature exists, mixing of the 194* Vapor Diffuser > 48 [1200]
two vapors optimizes packing perform-
ance above. 196 Vapor Diffuser > 48 [1200]
Specific equipment for vapor distribution (Reduces Flow Inertia)
may not be required if the pressure drop
198 Vapor Distributor > 17 [430]
in the packed bed is sufficient for proper (For Uniform Flow/Mixing)
vapor distribution.
796* Vapor Distributor > 48 [1200]
To determine the type of feed device
(for Uniform flow)
required for a reboiler return, the first step
is to consider the kinetic energy as 896 Vapor Distributor All
described above. After it is determined (for Uniform flow)
that vapor distribution is required, factors
to consider include feed nozzle size and
arrangement, pressure drop in the packed
bed, flow rates, tower size and type of
reboiler. Table IV
If vapor distribution equipment is needed
above reboiler return inlets, the Model 896 SELECTING REBOILER RETURN FEED DEVICES
is an effective distributor. Occasional (IF VAPOR DISTRIBUTION EQUIPMENT IS NEEDED)
exceptions are listed in Table IV.
Usual Alternate
Type Reboiler Model Models
B-2
MODEL 119/129 LIQUID ONLY FEED PIPE
Model 119 C
VARIES
B-3
MODEL 719/729 LIQUID ONLY FEED PIPE
Model 729
Model 719
VARIES
B-4
MODEL 755 FLASHING FEED GALLERY
Model 755
Hd Hn
B-5
MODEL 855 FLASHING FEED CHAMBER
Model 855
Hd
B-6
MODEL 955 FLASHING FEED PIPE
Model 955
TOWER I.D.
VARIES
B-7
MODEL 196 VAPOR DIFFUSER
Model 196
VARIES
B-8
MODEL 198 VAPOR DISTRIBUTOR
Model 198
B-9
MODEL 896 VAPOR DISTRIBUTOR PLATE
Hd
Ha
B-10
BED LIMITERS
When are bed limiters required? The Model 905 is a weighted plate used Bed Limiter Selection
Random Packing with ceramic or carbon tower packing to Bed limiters must maintain a high free area
prevent breakage. It is important to level for vapor/liquid passage and minimize
For metal and plastic random packings, the bed to assure packing contact with the
bed limiters are recommended when there interference with liquid distribution. With
hold-down plate over all areas. In addition Intalox distributors, non-interfering bed lim-
is the potential for sufficient vapor load to to handling vapor surges, weighted plates
fluidize the top of the bed. Generally, this iters such as the Models 103 and 133 are
are recommended when liquid rates are recommended. The Model 822 is specially
occurs during upset conditions, which are greater than 15 gpm/ft2 [35 m3/h•m2].
difficult to predict. designed for use on top of random pack-
Structured Packing ing with a spray distributor (Model 1044)
Use the table below for guidelines. above.
Bed limiters are recommended for use with
structured packing when there is the When laying out tower elevations, the bed
APPROXIMATE POINT OF FLUIDIZATION potential for packing displacement during limiter is not considered part of the packed
upset conditions. Retention of the top layer bed. The top of the packed bed is normally
Packing Wt. 5 10 15 20 25 is accomplished with the Model 133, six to eight in. [150 - 200 mm] from the
(lbs/ft3)
which may be attached to the distributor. distributor to allow for gas disengagement
∆P 0.96 1.92 2.9* 3.8* 4.8*
For towers with one-piece layers of pack- from the packed bed. The bed limiter
(in. WC/ft) ing, the Model 133 is typically integral with occupies this disengagement area.
the distributor to provide a means of sup- The table below summarizes the selection
*Pressure drop is difficult to predict in flood. port for and attachment to the distributor. criteria for any size tower. The support
Many columns with structured packing do method is given in reference to vessel wall
not need bed limiters. attachments. See the appropriate model
There are three basic ways to prevent description for further details.
upward movement of random packing:
bed limiters, anti-migration bars and
weighted plates.
The bed limiter is the most common type. SELECTING A BED LIMITER
A bed limiter either sits directly on the
packing or is attached to the vessel wall.
Plate Packing
Attachment to the vessel wall increases Model Wall Construction Type of Construction
interference with the distribution pattern. Number Attachment Material Packing Material
The bed limiter acts as a screen to confine
the packing to the defined bed. 103 None; rests Metal Random Metal
on packing or Plastic or Plastic
Another method of retaining a bed of
random packing is through the use of 823 Attached to Metal Random Metal
anti-migration bars at the bottom of the support ring or Plastic or Plastic
distributor’s gas risers. Anti-migration bars
do not prevent the packed bed from 133 Attached to Metal Structured Metal
wall clips
becoming fluidized and unleveled, but they
do prevent packing from being blown up 822* Attached to Metal Random Metal
through the gas risers. The concern in the support ring or Plastic
use of anti-migration bars is the possibility 905* None; rests Metal Random Ceramic
of restricting vapor passage through the on packing or Carbon
gas risers. This could lead to liquid back-
cycling due to high vapor velocity, which *Contact Saint-Gobain NorPro for plate details
may flood the distributor. Hence, close
attention to process and internal design
parameters is recommended before using
anti-migration bars.
C-1
MODEL 823 BED LIMITER FOR RANDOM PACKING
Model 823
A B
3" - 5"
[75 - 125]
C-2
MODEL 103 NON-INTERFERING BED LIMITER FOR RANDOM PACKING
Model 133
C-3
SUPPORT PLATES
Saint-Gobain NorPro manufactures ■ A random-packed bed depth 818 support, and 804 multi-beam support.
support plates for random and structured includes the height of the support All are made of metals; the Models 818
tower packings. Regardless of the plate. A structured-packed bed and 804 are also available in thermoplastic.
packing, each plate incorporates several depth does not include the height The Models 819 and 1019 are both
critical design factors. First, the plate must of the support. available in FRP only.
physically support the packing under Where tower height is a premium, special Supporting a structured packing is
operating conditions. Second, it must have designs for support plates are available somewhat simpler than supporting
a high percentage of free area to allow to permit integral packing support random packing because the integral
unrestricted flow of downcoming liquid and and either vapor distribution or partial nature of the structured packing physically
upward flow of gas. Third, it must be easy liquid collection. allows support by an open grid. The major
to install. design criteria is minimization of the grid
Gas injection support plates are designed
There are several criteria for selecting a to provide separate passageways for gas cross-sectional area while providing
support plate: and liquid so both phases do not compete sufficient strength. The Model 134
■ Type of packing supported for the same opening. Unrestricted flow of support for structured packing is
(random or structured) both phases minimizes pressure drop available in metal only.
■ Process characteristics (corrosion, across the plate. This is done by providing All our support plates sit directly on an
gas inlets above the liquid head, preventing annular ring. The weight of the packed
packing material, temperature)
excess liquid build-up. The support plates bed is normally sufficient to keep the plate
■ Maximum design load supported are designed to retain the various packing in place. However, if extra restraint is
(bed depth, packing type and sizes while not restricting the capacity of needed, the plate can be clamped to its
material, liquid hold-up, material the packing. support ring.
build up in the bed and surge
Support plates for random packings
conditions)
include the Models 809 light-duty support,
Note: In cases where the column liquid
level rises above the vapor entry, the
support plates can be subjected to
exceptional forces.
Pressure drop calculations for our tower
packings include the pressure drop
through support plates of our design: No
extra pressure drop need be added for the
support plate. Support plates can be
designed to handle any liquid flow rate.
In both cases (pressure drop and liquid
rates), the packing is the limiting SELECTING A SUPPORT PLATE
factor in tower design.
Model Tower ID Type Packing Construction
Number in. [mm] Supported Material
Contact your local Saint-Gobain NorPro representative for applications outside the “standards”
shown in this brochure.
D-1
MODEL 818 GAS INJECTION SUPPORT PLATE
400 500 600 700 800 900 1000 1100 1200 Metal 5.5 26.9
300
Note: Standard heavy-duty
construction increases load Polypropylene 2.4 11.7
1250
250 capacity 1.25 times. Higher
temperatures and/or loads
Allowable Load
200
5 4 3 2 1
1000 CPVC 4.1 20.0
are possible.
(kg/m2)
(lb/ft2)
150 750
Note: Other materials are available.
100 500
50 250
0
12 18 24 30 36 42 48 A B
(inches)
Curve Plastic
1 PVC/CPVC @ 75° F [24° C] through 125° F [52° C]
2 Polypropylene @ 75° F [24° C]
3 Polypropylene @ 100° F [38° C]
4 Polypropylene @ 125° F [52° C] or
PVC/CPVC @ 150° F [66° C]
5 Polypropylene @ 150° F [66° C]
Model 818
D-2
MODEL 804 GAS INJECTION SUPPORT PLATE
200 1000
temperatures and/or loads
(kg/m2)
(lb/ft2)
Curve Plastic
1 PVC/CPVC @ 75° F [24° C] through 125° F [52° C]
2 Polypropylene @ 75° F [24° C]
3 Polypropylene @ 100° F [38° C]
4 Polypropylene @ 125° F [52° C] or
PVC/CPVC @ 150° F [66° C]
5 Polypropylene @ 150° F [66° C]
Model 804
D-3
MODEL 809 LIGHT DUTY SUPPORT PLATE
2000
representative for allowable
400
loads for other materials.
300 1500
200 1000
A B
100 500
0
6 12 18 24 30
(inches)
Model 809
1" - 1 1/2
[25 - 38]
D-4
MODEL 819/1019 FRP GAS INJECTION SUPPORT PLATE
300 1500
Allowable Load
1019
819
68° F [20° C]
250
(kg/m2)
(lb/ft2)
B
200 1000
150
100 500
50
0
18 24 30 36 42 48 54 60 66 72 78 84 90 96
(inches)
VARIES
D-5
MODEL 134 SUPPORT GRID
D-6
LIQUID COLLECTORS
Liquid collection from between packed The chevron style of the Model 633 makes
beds is frequently required. Liquid this design suitable for high vapor rates, as
collectors are used in three main are typical of vacuum applications.
circumstances: Applying chevrons in towers less than
■ Total draw-off of liquid to product or 31.5 in. [800 mm] ID is impractical. The
reboiler or pump-around/pump- deck-type Model 833 can be used in
down smaller diameter towers where the
Models 633 and 733 cannot. Deck-style
■ Partial draw-off of liquid with construction is versatile at handling high
overflow continuing down the tower liquid rates. However, thermoexpansion
■ Collection of liquid for mixing can present leakage problems for a large
deck-type collector. In these cases, the
Collector plates come in different design
trough-type Model 733 is recommended.
styles which meet the needs of specific
The troughs eliminate the need to seal the
applications. For example, chevron- and
collectors to a ledge. The collector plate’s
trough-style collector plates require less
liquid capacity can be varied by sump and
tower height than deck-style collectors and
riser design.
thus are better suited for applications
where packed height is limited. The table below is helpful in selecting
the appropriate model for various
applications.
E-1
MODEL 633 CHEVRON-TYPE LIQUID COLLECTOR
Model 633
Hd
E-2
MODEL 733 TROUGH LIQUID COLLECTOR
Model 733
Hd
Ha
E-3
MODEL 833 DECK LIQUID COLLECTOR
Model 833
Hd
Ha
E-4
LIQUID/LIQUID EXTRACTION
Packing is used in counter-current When the heavy phase (feed which enters
liquid/liquid contactors with special the top of the tower) is dispersed, the
internals to disperse one of the phases. Model 835 disperser plate is used above
Selection and arrangement of the internals the top bed. When multiple beds are
depends on which phase (light or heavy) is required, the Model 835 is also used to
continuous and which is dispersed. In all support the upper beds and collect and
cases, feed pipes directing the feed, light redisperse the heavy phase to the beds
and heavy, are recommended to control below. The bottom bed is supported by a
velocity. It is extremely important to conventional support plate (see Models
properly feed the dispersed phase to 804 or 818). The Model 835, although
the disperser plate. structurally different, is hydraulically
In contactors where the light phase (feed upside-down compared to the Model 834.
which enters the bottom of the tower) is In heavy phase dispersed contactors, the
dispersed, packed beds are supported by same bed depth recommendations apply
the Model 834 disperser support plate. In as with light-phase dispersement.
addition to supporting the packing, the It is generally recommended to disperse
plates allow proper dispersion or formation the phase with the higher flow rate to
of small droplets which rise through the generate maximum interfacial contact.
continuous phase. In breaking the The exception to this rule is when the
dispersed liquid into small droplets, higher volumetric flow rate phase has
the Model 834 provides maximum initial higher viscosity or preferentially wets the
contact area between the two phases. packing surface.
Because the droplets tend to coalesce in Surfactants may alter surface properties
the packing, beds are typically limited to a to the extent that the performance of a
depth of 6 to 8 ft [1.5 to 2.5 m]. Multiple liquid/liquid contactor cannot be
beds, each supported by a Model 834, are predicted.
recommended where a total of more than
8 ft [2.5 m] of packing is required.
Model Construction
Number Description Material Phase
F-1
MODEL 834 DISPERSER/SUPPORT PLATE
* These limits apply to the disperser plate capacity; packing capacity may limit operating capacity.
**Turndown of the continuous phase is unlimited.
Model 834
Ask your Saint-Gobain NorPro
representative about other options
at the time of inquiry.
F-2
MODEL 835 DISPERSER/SUPPORT PLATE
* These limits apply to the disperser plate capacity; packing capacity may limit operating capacity.
**Turndown of the continuous phase is unlimited.
Model 835
F-3
MODEL 644 DISPERSED-PHASE FEED PIPE
F-4
TYPICAL TOWER LAYOUT
Face of
Inlet Flange
6" [150] C
Hd
Feed Pipe
Hd Distributor Hn + 2" + Manway ID 4" [100]
2
6" [150] Hn
Bed Limiter Distributor Hd
Packed Bed
Bed Limiter 8" [200]
Bed Packed Bed
Depth
Hn = Dimension from the bottom
Bed
to the inlet nozzle center-line. Depth
Support Plate
Hd = Height of given model. Support Plate
12" [300]
For these dimensions, refer to Manway + 6" [150]
Wall Wiper individual item page.
Hd Feed Pipe
Redistributor 4" [100]
6" [150] Hn Redistributor Hd
Bed Limiter Hd
G-1
GENERAL DETAILS
If your ledge size is other than listed above, special consideration must be given Meets ASME code for lethal service
to the plate diameter and vessel tolerances.
G-2
MATERIALS OF CONSTRUCTION
G-3
SPECIAL TOWER INTERNALS
The following is a partial listing of models which are supplied by Saint-Gobain NorPro, but not specifically
covered in this brochure. For more information on these or other models contact your Saint-Gobain NorPro
representative.
Device Model
Distributors 120 Metal internal strainer baskets used to strain internal liquid flow to prevent
low flow liquid distributors and Intalox wire gauze packing from fouling.
146 Metal enclosed Intalox distributor used in clean systems with limited height.
176 Metal Intalox trough distributor with parting box and bottom orifices.
854 Metal in-bed distributor to distribute small quantities of liquid feed into a bed
without separating the random packed section.
Feed Devices 144 Metal suppressed flash vapor distributor which achieves vapor distribution
and vapor mixing in a flashing feed or reboiler return.
192 Metal vapor horn for atmospheric and vacuum crude towers.
194 Metal vane-style vapor inlet diffuser.
655 Metal two-phase feed pipe with shelter plates. Used in feeding collector
plates or distributors with parting box(es).
796 Metal gas distributing support plate used in low pressure (low liquid flow)
service where vapor distribution in a compact space is required.
Bed Limiters 822 Metal bed-limiter used with Model 1044 spray distributors to reduce spray
pattern interference at the top of the bed.
Support Plates 104 Metal non-interfering support plate that allows liquid to pass without diver-
sion, eliminating need for redistribution. Limited to short beds of packing.
1004 Metal gas injection type support plate for catalyst beds.
840 Metal gas injection type support plate used to divert liquid to feed a tray or
other device or to provide partial liquid draw-off.
Collector Plates 841 Metal in-bed collector/draw off of up to 3 to 5% of column liquid for flows up
to 26 gpm [6.0 m3/hr].
Miscellaneous 100 Metal support ledge for field attachment.
101 Metal support beam.
102 Metal support truss.
858 Metal in-bed wall wiper (Rosette type).
111 Metal anti-migration screen to separate different size packing in a single bed.
Also ask your Saint-Gobain NorPro representative about their line of ceramic tower internals. Saint-Gobain
NorPro provides a complete line of distributors and support plates in a high-strength Aludur® ceramic body.
G-4
OTHER PRODUCTS FOR REFINING, CHEMICAL AND PETROCHEMICAL PROCESSING
G-5
NOTES
Locations
w w w. i n t a l ox . c o m