SHD 200 Technical Datasheet

Control unit for 4…20 mA/HART® field devices


• Second 4…20 mA current output for any HART® variable
• 2 configurable relays with various functionalities
• Different user-configurable measuring pages for all 4…20 mA and HART® signals

The documentation is only complete when used in combination with the relevant
documentation for the sensor.

© KROHNE 06/2022 - 4007932902 - TD SHD 200 R02 en


CONTENTS SHD 200

1 Product features 3

1.1 Control unit for 4…20 mA / HART field devices................................................................ 3

2 Technical data 4

2.1 Technical data................................................................................................................... 4


2.2 Dimensions ....................................................................................................................... 6

3 Installation 8

3.1 General notes on installation ........................................................................................... 8


3.2 Intended use ..................................................................................................................... 8
3.3 Pre-installation requirements ......................................................................................... 9
3.4 Opening the housing....................................................................................................... 10
3.5 Wall mounting ................................................................................................................ 12
3.5.1 Plastic housing...................................................................................................................... 12
3.5.2 Aluminium housing ............................................................................................................... 13

4 Electrical connections 14

4.1 Connection diagram overview ........................................................................................ 14


4.2 Connecting the field device cable .................................................................................. 16
4.3 Connecting the second current output .......................................................................... 17
4.4 Connecting the relay outputs ......................................................................................... 18
4.5 Connecting the external HART adapter ......................................................................... 19
4.6 Power supply .................................................................................................................. 20
4.7 Connecting the SHD 200 for use in an active 4...20 mA current output ........................ 21

5 Notes 23

2 www.krohne.com 06/2022 - 4007932902 - TD SHD 200 R02 en


SHD 200 PRODUCT FEATURES 1

1.1 Control unit for 4…20 mA / HART field devices


The SHD 200 is a unit for control and monitoring of process parameters in various industry
applications. It is suitable to be connecting to all loop-powered field devices with 4…20 mA
current output and/or HART® communication. The SHD 200 exceeds the functionality of an
ordinary display. It features different customer-specific measurement pages displaying up to 4
different values for detailed process monitoring (incl. trend graph and summary page). For
improved process control, the control unit comes with two freely programmable relays for
status, system alert and limit switch as well as a second current output for any HART® variable
(e.g. temperature in pH and conductivity measurements). In addition, it offers the possibility of
commissioning OPTIBAR pressure transmitters and OPTIWAVE level transmitters. Connecting a
HART® handheld, the SHD 200 provides access to all sensor functions including calibration.

Figure 1-1: SHD 200 plastic housing


1 High-brightness LEDs for NAMUR NE 107 status signalisation
2 Display
3 Operation keys
4 Cable glands

Highlights
• Control unit for 4…20 mA/HART® field devices
• 2 wire, loop-powered device
• Second 4…20 mA current output for any HART® variable
• 2 configurable relays for status output, limit switch, system alarm, cleaning control, error
current or alert functionality acc. to USP<645>
• Different user-configurable measuring pages for all 4…20 mA and HART® signals, trend
graph and summary page
• Commissioning of OPTIBAR pressure transmitters and OPTIWAVE level transmitters
• Full access to all sensor functions including calibration possible by connecting a HART®
handheld
• Status signalisation by 5 LEDs according to NAMUR NE 107
• Robust plastic or aluminium housing (IP66/67)

06/2022 - 4007932902 - TD SHD 200 R02 en www.krohne.com 3


2 TECHNICAL DATA SHD 200

2.1 Technical data


• The following data is provided for general applications. If you require data that is more
relevant to your specific application, please contact us or your local sales office.
• Additional information (certificates, special tools, software,...) and complete product
documentation can be downloaded free of charge from the website (Downloadcenter).

Measuring system
Measuring principle The measuring principle depends on the used field device(s), for further information
refer to the field device manual(s).
Measuring range The measuring range depends on the used field device(s), for further information
refer to the field device manual(s).

Design
Construction A typical measuring system consists of:
• SHD 200
• HART® capable field device
• Field device cable
Communication protocol  HART® 5

Display and user interface


Graphic display LC display
256 x 128 pixel
Operating elements 4 push buttons for operator control of the unit without opening the housing.
Operating menu The operation menu consists of:
Measuring mode: 6 pages (5 measurement pages and 1 status page)
Menu mode: variety of main and submenus that allows to customise the device
according to the demands of the measuring point.
Operating and display languages English, German, French, Italian, Spanish, simplified Chinese
Units HART® units and customer specific units

Operating conditions
Temperature
Ambient -20...+70°C / -4...+158°F
Note: the manufacturer strongly recommends to protect the unit from external heat
sources such as direct sunlight as higher temperatures reduce the life cycle of all
electronic components!
Storage -30...+70°C / -22...+158°F
Altitude  2000 m / 6561.68 f

Other conditions
Humidity RH4...100% rH
(IEC 60721-3-4:1995 Class 4K4)
Ingress protection IP66/ IP67
acc. to IEC 60529:

4 www.krohne.com 06/2022 - 4007932902 - TD SHD 200 R02 en


SHD 200 TECHNICAL DATA 2

Installation conditions
Weight Approx. 413 g / 0.91 lb for plastic housing
Approx. 855 g / 1.89 lb for aluminium housing
Installation Wall mounting; assure a vertical mounting orientation
Wall or pipe mounting with weather protection cover

Materials
Housing Aluminium
Plastic (Polycarbonate)
Cable glands 3xM16x1.5
2xM12x1.5
Material: Polyamid

Electrical connections
Power supply 20...30 VDC, loop powered from 4...20 mA signal input; Voltage drop max. 4V at 4 mA
and 2V at 20 mA
System requirements 250  loop resistance for HART® communication.
Note: In most Ex isolation amplifiers the 250 Ohm resistor is already integrated.
Current output 12...30 VDC; 4...20 mA signal output (passive)
Relays Two solid state relays working as status output, limit switch, system alarm,
cleaning control, error current or alert functionality acc. to USP<645>
• The relay contacts are electrically isolated from each other and from all other
circuits
• The output stages of the status outputs/limit switches behave like relay contacts
• Possible conditions: NO (normally open) or NC (normally closed)
Connection values:
• Maximum voltage = 30 V
• Maximum load current = 75 mA up to 55°C and 50 mA above 55°C
• Max on resistance = 10 Ohm

Approvals and certifications


CE
The device meets the essential requirements of the EU directives. The CE marking indicates the conformity of the
product with the union legislation applying to the product and providing for CE marking.
For full information of the EU directives and standards and the approved certifications, please refer to the EU
declaration on the website of the manufacturer.
Hazardous areas
ATEX ATEX II 2 G Ex ia IIC T4 Gb
IECEX IECEx ia IIC T4 Gb
QPS QPS Ex ia IIC T4 Gb / Class I, Zone 1 AEx ia IIC T4 Gb
UKEX UKEX II 2 G Ex ia IIC T4 Gb
Other approvals and standards
NAMUR recommendation NE 6, NE 21, NE 43, NE 53, NE 107
Shock resistance IEC 60721-3-4 class 4M4
Vibration resistance IEC 60721-3-4 class 4M4
IEC 61298-3 low vibration control room

06/2022 - 4007932902 - TD SHD 200 R02 en www.krohne.com 5


2 TECHNICAL DATA SHD 200

2.2 Dimensions
Plastic housing

Figure 2-1: Dimensions plastic housing

Dimensions [mm] Weight [g]


a b c d
Wall mounted 80 151 60 105 413
Table 2-1: Dimensions plastic housing in mm

Dimensions [inch] Weight [pound]


a b c d
Wall mounted 3.15 5.94 2.36 4.13 0.91
Table 2-2: Dimensions plastic housing in inch

6 www.krohne.com 06/2022 - 4007932902 - TD SHD 200 R02 en


SHD 200 TECHNICAL DATA 2

Aluminium housing

Figure 2-2: Dimensions aluminium housing

Dimensions [mm] Weight [g]


a b c d
Wall mounted 86 159 60 111 855
Table 2-3: Dimensions aluminium housing in mm

Dimensions [inch] Weight [pound]


a b c d
Wall mounted 3.39 6.26 2.36 4.37 1.89
Table 2-4: Dimensions aluminium housing in inch

06/2022 - 4007932902 - TD SHD 200 R02 en www.krohne.com 7


3 INSTALLATION SHD 200

3.1 General notes on installation


Inspect the packaging carefully for damages or signs of rough handling. Report damage to the
carrier and to the local office of the manufacturer.

Do a check of the packing list to make sure that you have all the elements given in the order.

Look at the device nameplate to ensure that the device is delivered according to your order.
Check for the correct supply voltage printed on the nameplate.

3.2 Intended use


For devices used in hazardous areas, additional safety notes apply; please refer to the Ex
documentation.

Responsibility for the use of the measuring devices with regard to suitability, intended use and
corrosion resistance of the used materials against the measured fluid lies solely with the
operator.

If the device is not used according to the operating conditions (refer to chapter "Technical data"),
the intended protection could be affected.

This device is a Group 1, Class A device as specified within CISPR11. It is intended for use in
industrial environment. There may be potential difficulties in ensuring electromagnetic
compatibility in other environments, due to conducted as well as radiated disturbances.

The manufacturer is not liable for any damage resulting from improper use or use for other than
the intended purpose.

The SHD 200 is a control unit for 4...20 mA/HART® field devices. The intended use is process
control by using the relays, the second current output and the NAMUR NE 107 signalisation by
LEDs for the HART® parameters of the connected field device. The device has been constructed
for indoor and outdoor use below the maximum altitude of 2000 m / 6562 ft.

8 www.krohne.com 06/2022 - 4007932902 - TD SHD 200 R02 en


SHD 200 INSTALLATION 3

3.3 Pre-installation requirements


Always note the following items to ensure a proper and safe installation:
• Make sure that there is adequate space to the sides.
• Protect the device from direct sunlight.
• The device installed in control cabinets require adequate cooling, e.g. by fan or heat
exchanger.
• Do not expose the device to intense vibration.
• Use assembly materials and tools in compliance with the applicable occupational health and
safety directives (assembly materials and tools are not part of the scope of delivery).
• Do not make any mechanical modifications to the device. This can result in the loss of proper
functionality, as well as the rights under the device warranty.
• The device must not be heated by radiated heat (e.g. exposure to the sun) to a electronics
housing surface temperature above the maximum permissible ambient temperature. If it is
necessary to prevent damage from heat sources, a heat protection (e.g. sun shade) has to be
installed.

The device must be suitable for the temperature specified (including chemical resistance).

Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.

06/2022 - 4007932902 - TD SHD 200 R02 en www.krohne.com 9


3 INSTALLATION SHD 200

3.4 Opening the housing


Clean and grease all threads each time you open the housing. Use only resin-free and acid-free
grease. Before closing the cover, ensure that the housing gasket is properly fitted, clean and
undamaged.

All installation works on the electrical connections and mounting require to open the housing:

Opening the plastic housing

Figure 3-1: Opening the plastic housing

• Put a small flat tool (e.g. screwdriver) into the right hinge lock and open the device 1.
• Lift up the housing 2.
i Now you have access to the electronic compartment and the possibility to mount the device
on a wall.

10 www.krohne.com 06/2022 - 4007932902 - TD SHD 200 R02 en


SHD 200 INSTALLATION 3

Opening the aluminium housing

Figure 3-2: Opening the aluminium housing

• Pull only the right hinge lock the side 1.


• Loosen the 2 torx screws (TX20) with a torx screwdriver 2.
• Lift up the housing 3.
i Now you have access to the electronic compartment and the possibility to mount the device
on a wall.
• For closing the housing again, use the 2 torx screws with a torque of 1,5 Nm.

06/2022 - 4007932902 - TD SHD 200 R02 en www.krohne.com 11


3 INSTALLATION SHD 200

3.5 Wall mounting


Always note the following items to ensure a proper and safe installation:

• Make sure that there is adequate space to the sides.


• The device must not be heated by radiated heat (e.g. exposure to the sun) to a electronics
housing surface temperature above the maximum permissible ambient temperature. If it is
necessary to prevent damage from heat sources, a heat protection (e.g. sun shade) has to be
installed.
• Units installed in control cabinets require adequate cooling, e.g. by fan or heat exchanger.
• Do not expose the unit to intense vibration.
• Use assembly materials and tools in compliance with the applicable occupational health and
safety directives (assembly materials and tools are not part of the scope of delivery).

Installation, assembly, start-up and maintenance may only be performed by appropriately


trained personnel. The regional occupational health and safety directives must always be
observed.

A mounting system with a minimum load force of 0.1 kN (for example FISCHER type UX10)
suitable for the background has to be applied.

3.5.1 Plastic housing

Figure 3-3: Wall mounting of the plastic housing

1 Mark the holes with a suitable pen 1.


2 Drill the 4 holes and fasten the device securely to the wall 2.

For outdoor mounting, we recommend the optional weather protection cover XGSH010000 for
wall and pipe mounting. For more flexibility and convenient mounting, we recommend wall
mounting brackets XGSH010020 for plastic housing.

12 www.krohne.com 06/2022 - 4007932902 - TD SHD 200 R02 en


SHD 200 INSTALLATION 3

3.5.2 Aluminium housing

Figure 3-4: Wall mounting of the aluminium housing

1 Mark the holes with a suitable pen 1.


2 Drill the 4 holes and fasten the device securely to the wall 2.

For outdoor mounting, we recommend the optional weather protection cover XGSH010000 for
wall and pipe mounting. For more flexibility and convenient mounting, we recommend wall
mounting brackets XGSH010030 for aluminium housing.

06/2022 - 4007932902 - TD SHD 200 R02 en www.krohne.com 13


4 ELECTRICAL CONNECTIONS SHD 200

4.1 Connection diagram overview

1 3 5 6 7

U2 U1
+ - S Sens+ Sens- + + - UR1+ UR1- UR2+ UR2-
2 4

J K FE S A1 B1 A2 B2 C D E F G H I
SENSOR SHIELD

250:
FUNC. EARTH

SENSOR+

SENSOR-

RELAY1+

RELAY2+
RELAY1-

RELAY2-
LOOP2+

LOOP1+

LOOP1+
LOOP2-

LOOP1-
HART+

HART-

Figure 4-1: Connection diagram overview


1 Terminals for loop 2
2 Terminal for functional earth
3 Terminals for sensor connection
4 Terminals for external HART-Modem / external HART-adapter
5 Terminals for loop 1: Connect D and E when the power supply has an internal resistor or C and E to use the internal
resistor of this device. You must not connect C and D at the same time!
6 Terminals for relay 1
7 Terminals for relay 2

The device is equipped with an internal HART® access for the NonEx-version (A2 and B2) that
offers the opportunity to access the field device via HART® handheld or HART® modem.

14 www.krohne.com 06/2022 - 4007932902 - TD SHD 200 R02 en


SHD 200 ELECTRICAL CONNECTIONS 4

U2

+
- 1

U1

+
- 3

UR1

+
- 4

UR2

+
- 5

J K FE S A1 B1 A2 B2 C D E F G H I
250 :
SENSOR SHIELD
FUNC. EARTH

SENSOR+

SENSOR-

RELAY1+

RELAY2+
RELAY1-

RELAY2-
LOOP2+

LOOP1+

LOOP1+
LOOP2-

LOOP1-
HART+

HART-

Figure 4-2: Connection example with a 2-wire field device


1 Power supply for loop 2. Used for second 4...20 mA output and/or NE107 LEDs and backlight.
2 Connected field device, e.g. SMARTPAT PH.
3 Power supply for loop 1. Main loop for operating the device, in this case with usage of internal resistor.
4 Power supply for relay 1
5 Power supply for relay 2

06/2022 - 4007932902 - TD SHD 200 R02 en www.krohne.com 15


4 ELECTRICAL CONNECTIONS SHD 200

4.2 Connecting the field device cable


When connecting the power supply, always note the safety regulations of the current state of the
art. To avoid fatal injuries, destruction or damage of the device or measuring errors, also note
the following items:
• Cables may only be connected when the power is switched off.
• Always keep the housing of the device well closed if you do not perform any installation
works. The function of the housing is to protect the electronic equipment from dust and
moisture.
• Check the nameplate and assure that the power supply meets the voltage of the device. The
device is loop powered and operates in the range of 20...30 VDC with a voltage drop < 4 V. If
the power supply is below 20 VDC the device and field device will not work. If the power supply
is above 30 VDC the device and field device sensor may be damaged/destroyed.

Do not use the integrated 250 Ohm HART® resistor of the device, when using an Ex isolation
amplifier of third-party with integrated 250 Ohm HART® resistor.

S Sens+ Sens-
U2+ U2- S Sens+ Sens- U1+ U1- UR1+ UR1- UR2+ UR2-

J K FE S A1 B1
1 A
A2 B2 C D E F G H I
SHIELD

S A1 B1
FUNC. EARTH

SENSOR+

SENSOR-

SENSOR SHIELD
RELAY1+

RELAY2+
SENSOR

RELAY1-

RELAY2-
LOOP2+

LOOP1+

LOOP1+
LOOP2-

LOOP1-
HART+

HART-
SENS

SENS

SENSOR+

SENSOR-

Figure 4-3: Connecting the field device cable

The cable glands installed by the manufacturer are designed for a cable diameter of 3...6,5 mm
for M12 and 5...10 mm for M16. If you are using cables with a larger diameter than 3...6,5 mm for
M12 and 5...10 mm for M16, you must replace the manufacturer’s cable glands with suitable
ones. The operator is responsible for the correct sealing of cable glands.

16 www.krohne.com 06/2022 - 4007932902 - TD SHD 200 R02 en


SHD 200 ELECTRICAL CONNECTIONS 4

4.3 Connecting the second current output

U2+ U2-
U2+ U2- S Sens+ Sens- U1+ U1- UR1+ UR1- UR2+ UR2-

J K F
FE S A1 B1 A2 B2 C D E F G H I
SENSOR SHIELD

J K
FUNC. EARTH

SENSOR+

SENSOR-

RELAY1+

RELAY2+
RELAY1-

RELAY2-
LOOP2+

LOOP1+

LOOP1+
LOOP2-

LOOP1-
HART+

HART-

A
LOO

LOO

LOOP2+

LOOP2-
Figure 4-4: Connection of second current output

The second current output can be either used as current output for any HART® variable or as
power supply for backlight and LEDs for NAMUR NE 107 signalisation if supported by field device
(field device must support extended command 523: Read Condensed Status Mapping Array).

06/2022 - 4007932902 - TD SHD 200 R02 en www.krohne.com 17


4 ELECTRICAL CONNECTIONS SHD 200

4.4 Connecting the relay outputs


The device has two solid state relays that can work as status output, system alarm,
cleaning control or limit switch:
• The relay contacts are electrically isolated from each other and from all other circuits.
• The output stages of the status outputs / limit switches behave like relay contacts.
• Possible conditions: NO (normally open) or NC (normally closed).

Connection values:
• Maximum Voltage = 30 V
• Maximum Load Current = 75 mA up to 55°C and 50 mA above 55°C
• Max On resistance = 10 Ohm

UR1+ UR1 UR2+ UR2-


U2+ U2- S Sens+ Sens- U1+ U1- UR1+ UR1- UR2+ UR2-

J K FE S A1 B1 A2 B2 C D E F G H I

F G H I
SENSOR SHIELD
FUNC. EARTH

SENSOR+

SENSOR-

RELAY1+

RELAY2+
RELAY1-

RELAY2-
LOOP2+

LOOP1+

LOOP1+

RELAY2
LOOP2-

LOOP1-
LOOP1
HART+

RELAY
HART-

A
R

RELAY1+

RELAY2+
RELAY1-

RELAY2-

Figure 4-5: Connecting the relay outputs

18 www.krohne.com 06/2022 - 4007932902 - TD SHD 200 R02 en


SHD 200 ELECTRICAL CONNECTIONS 4

4.5 Connecting the external HART adapter


The external HART® adapter is an optional feature that offers the opportunity to access the field
device without opening the housing.

Figure 4-6: External HART adapter

U2+ U2- S Sens+ Sens- U1+ U1- UR1+ UR1- UR2+ UR2-

J K FE S A1 B1 A2 B2 C D E F G H I

A2 B2
SENSOR SHIELD
FUNC. EARTH

SENSOR+

SENSOR-

RELAY1+

RELAY2+
RELAY1-

RELAY2-
LOOP2+

LOOP1+

LOOP1+
LOOP2-

LOOP1-
HART+

HART-

A
HAR

HAR

HART+

HART-

Figure 4-7: Connection of the external HART® adapter


1 Open the housing.
2 Remove the middle M16 cable gland and screw the HART® adapter.
3 Connect the HART® adapter to connections A2 and B2.

Consider that the cap needs to be closed for a protection of the electronics parts.

06/2022 - 4007932902 - TD SHD 200 R02 en www.krohne.com 19


4 ELECTRICAL CONNECTIONS SHD 200

4.6 Power supply


To avoid fatal injuries as well as destruction or damage of the device assure a correct installation
before switching on the power. This includes:
• The device is mechanically safe, mounting and power connection comply with the regulations.
• The electrical terminal compartments must be secured, i.e. the housing has to be closed and
the screws have to be tightened.
• The electrical operating data of the power supply comply with the requirements of the device.

Observe without fail the local occupational health and safety regulations.
Any work done on the electrical components of the measuring device may only be carried out by
properly trained specialists.

When connecting the power supply, always note the safety regulations of the current state of the
art. To avoid fatal injuries, destruction or damage of the device or measuring errors, also note
the following items:
• Cables may only be connected when the power is switched off.
• Always keep the housing of the device well closed if you do not perform any installation
works. The function of the housing is to protect the electronic equipment from dust and
moisture.
• Check the nameplate and assure that the power supply meets the voltage of the device. The
device is loop powered and operates in the range of 20...30 VDC with a voltage drop < 4 V. If
the power supply is below 20 VDC the device and field device will not work. If the power supply
is above 30 VDC the device and field device sensor may be damaged/destroyed.

Do not use the integrated 250 Ohm HART® resistor of the device, when using an Ex isolation
amplifier of third-party with integrated 250 Ohm HART® resistor.

The device and the field device require a minimum operating voltage of 20 VDC. The power
supply is provided via the 2-wire interface (4...20 mA).

U1+ U1-
U2+ U2- S Sens+ Sens- U1+ U1- UR1+ UR1- UR2+ UR2-

J K FE S A1 B1 A2 B2 C D E F G H I
SENSOR SHIELD

C D E
FUNC. EARTH

SENSOR+

SENSOR-

RELAY1+

RELAY2+
RELAY1-

RELAY2-
LOOP2+

OOP1+

LOOP1+

RELAY1
LOOP2-

LOOP1-
HART+

HART-

LOOP

LOOP

LOOP1+

LOOP1+

LOOP1-

Figure 4-8: Connection of the power supply

20 www.krohne.com 06/2022 - 4007932902 - TD SHD 200 R02 en


SHD 200 ELECTRICAL CONNECTIONS 4

4.7 Connecting the SHD 200 for use in an active 4...20 mA current output
To avoid fatal injuries as well as destruction or damage of the device assure a correct installation
before switching on the power. This includes:
• The device is mechanically safe, mounting and power connection comply with the regulations.
• The electrical terminal compartments must be secured, i.e. the housing has to be closed and
the screws have to be tightened.
• The electrical operating data of the power supply comply with the requirements of the device.

Observe without fail the local occupational health and safety regulations.
Any work done on the electrical components of the measuring device may only be carried out by
properly trained specialists.

When connecting the power supply, always note the safety regulations of the current state of the
art. To avoid fatal injuries, destruction or damage of the device or measuring errors, also note
the following items:
• Cables may only be connected when the power is switched off.
• Always keep the housing of the device well closed if you do not perform any installation
works. The function of the housing is to protect the electronic equipment from dust and
moisture.
• Check the nameplate and assure that the power supply meets the voltage of the device. The
device is loop powered and operates in the range of 20...30 VDC with a voltage drop < 4 V. If
the power supply is below 20 VDC the device and field device will not work. If the power supply
is above 30 VDC the device and field device may be damaged/destroyed.

Do not use the integrated 250 Ohm HART® resistor of the device, when using an Ex isolation
amplifier of third-party with integrated 250 Ohm HART® resistor.

06/2022 - 4007932902 - TD SHD 200 R02 en www.krohne.com 21


4 ELECTRICAL CONNECTIONS SHD 200

+ -

U2+ U2- S Sens+ Sens- U1+ U1- UR1+ UR1- UR2+ UR2-

J K FE S 1 A
A1 B1 A2 B2 C D E F G H I
C D E
SENSO SHIELD
FUNC. EARTH

SENSOR+

SENSOR-

RELAY1+

RELAY2+
SENSOR

RELAY1-

RELAY2-
LOOP2+

OOP1+

LOOP1+

RELAY1
LOOP2-

LOOP1-
LOOP1
HART+

HART-

LOOP
SENS
ENS

LOOP1+

LOOP1+

LOOP1-
S Sens+ Sens-

S A1 B1
Sensor Shield

Sensor+

Sensor-

+
-

Figure 4-9: Connection for use in an active 4...20 mA current output


1 Connection to process control system (passive input)
2 Active current output of field device

Connect output + from field device to SENSOR - and output - from field device to SENSOR +.

For information on connecting the second current output refer to Connecting the second current
output on page 17 , connecting the relays refer to Connecting the relay outputs on page 18 and
connecting the external HART adapter refer to Connecting the external HART adapter on page
19.

22 www.krohne.com 06/2022 - 4007932902 - TD SHD 200 R02 en


SHD 200 NOTES 5

06/2022 - 4007932902 - TD SHD 200 R02 en www.krohne.com 23


KROHNE – Products, Solutions and Services
• Process instrumentation for flow, level, temperature, pressure measurement
and process analytics
• Flow metering, monitoring, wireless and remote metering solutions
• Engineering, commissioning, calibration, maintenance and training services
© KROHNE 06/2022 - 4007932902 - TD SHD 200 R02 en - Subject to change without notice.