TOP WIRING INTERCONNET BATTERY CABINET WEIGHT AND CENTER OF GRAVITY (INSTALLED)
57 [2.2 ]
A ASSEMBLY / BATTERY CABINET REF (FLOOR MOUNTING) A
WEIGHT
A B C
kg (lbs)
TOP-WIRING
INTERCONNECT 128S 325 [12.8] 263.8 [10.4] 1027.5 [40.5] 482 [1063]
CONDUIT ACCESS

(ACCESS AREA:
136S 325 [12.8] 263.8 [10.4] 1027.5 [40.5] 500 [1102]
600 [23.6] X
155 [6.1]) SECURE CABINET TO FLOOR
465 410
[18.3 ] [16.1 ] WITH M16 OR 5/8" BOLTS
B (4X CORNERS) B
** CUSTOMER SUPPLIED ** PACKAGED RACK DIMENSIONS
PALLET PALLET OVERALL
529
WIDTH DEPTH HEIGHT
[20.8 ]
1110 [43.7] 1130 [44.5] 2190 [86.2]
650
TOP-WIRING [25.6 ]
INTERCONNECT
INTER-CABINET POWER
C
ASSEMBLY FRONT VIEW ASSEMBLY SIDE VIEW WIRING ACCESS REAR VIEW PRODUCT SPECIFICATIONS C
* FIELD INSTALLED *
VENTILATION (BOTH SIDES)
DC VOLTAGE BATTERY
BATTERY
OUTPUT, NAMEPLATE
CABINET MODEL
V (NOMINAL) kWh
128S1P 486.4 V 32.6 kWh
INTER-CABINET CONTROL 136S1P 516.8 V 34.6 kWh
WIRING ACCESS
(BOTH SIDES)
D D
TOP WIRING INTERCONNECT
ASSEMBLY
128S1P P-103003835
136S1P P-103003836

E E
"B" HEAT OUTPUT: 567 BTU

2281
[89.8 ]
2055
[80.9 ]

F F
NOTES
1. THE SYSTEM MUST BE INSTALLED ON A LEVEL FLOOR SURFACE
SUITABLE FOR COMPUTER OR ELECTRONIC EQUIPMENT.
2. THE SYSTEM MUST BE INSTALLED IN A TEMPERATURE AND HUMIDITY
CONTROLLED INDOOR AREA FREE OF CONDUCTIVE CONTAMINANTS.
"C" 3. AMBIENT TEMPERATURE RANGE 18-28degC [64-83degF],
RELATIVE HUMIDITY: 5%-95% NON-CONDENSING.
4. WEIGHT: WEIGHTS DO NOT INCLUDE CUSTOMER WIRING.
G 5. MINIMUM 914mm [36"] FRONT ACCESS NEEDED FOR SERVICING. G
6. VENTILATION IS BY MEANS OF NATURAL CONVECTION
7. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL
ELECTRIC CODES.
8. POWER HOOKUP TO UPS: POSITIVE, NEGATIVE, GROUND.
9. SPECIFICATIONS ARE SUBJECT TO CHANGE.
10. ALL DIMENSIONS ARE IN MILLIMETERS [INCHES].
THIRD ANGLE PROJECTION

METRIC
NAME (PART NUMBER):

P-110000740
REVISION: 03

"A"
H 530
DESCRIPTION: SAMSUNG UL9540a BATTERY CABINET SITE PLAN SIZE: A2 H
SEE NOTES FOR TOLERANCES
[20.9 ] MULE_V 18-NOV-2019 STATE: Release 1:10
650 ORIGINATED BY: SCALE:
DIM ARE IN MM (INCHES) AFTER PLATING
INTERPRET DIM AND TOL PER ASME
[25.6 ] MODIFIED BY: M. Kabade 14-AUG-2020 Y14.5-2018 ECO: ECO-191361 SHEET: 1 OF 3
EATON CORPORATION - CONFIDENTIAL AND PROPRIETARY. NOTICE TO PERSONS RECEIVING THIS DOCUMENT AND/OR TECHNICAL INFORMATION
THIS DOCUMENT, INCLUDING THE DRAWING AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL AND IS THE EXCLUSIVE PROPERTY OF EATON CORPORATION, AND IS MERELY ON LOAN AND SUBJECT TO RECALL
BY EATON AT ANY TIME. BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT BE USED IN ANY MANNER ADVERSE TO THE INTERESTS OF EATON
AND THAT NO PORTION OF THIS DOCUMENT MAY BE COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR WRITTEN CONSENT OF EATON. IN THE CASE OF CONFLICTING CONTRACTUAL PROVISIONS, THIS
NOTICE SHALL GOVERN THE STATUS OF THIS DOCUMENT. © 2019 Eaton Corporation - All Rights Reserved.

1 2 3 4 5 6 7 8 9 10 11 A2
1 2 3 4 5 6 7 8 9 10 11 12 Page: 2 of 3

**NOTE:
A CUSTOMER SUPPLIED WIRING, TOP INTERCONNECT ASSEMBLY 1. EACH TYPE S BATTERY SYSTEM REQUIRES A MINIMUM OF ONE AC CIRCUIT A
TO PROVIDE AUXILIARY POWER TO THE SYSTEM BMS.
RECOMMENDED MINIMUM WIRE SIZE FOR 75 deg C COPPER RECOMMENDED 2. FOR 400-500 VAC UPS APPLICATIONS, THE BATTERY CABINET IS WIRED DIRECTLY TO A 400-500 VAC SOURCE.
STRANDED WIRE TORQUE 3. FOR LOWER VOLTAGE APPLICATIONS 100-240 VAC, THE BATTERY CABINET IS WIRED DIRECTLY TO A
100-240 VAC SOURCE.
BATTERY WIRES 3/0 AWG (2X PER POLE) 519 IN-LB
4. THESE CIRCUITS MUST BE PROVIDED FROM THE CUSTOMER'S ELECTRICAL DISTRIBUTION AND
GROUND WIRES 3/0 AWG 519 IN-LB SHOULD BE PROTECTED BY A LISTED 15A DEVICE (CIRCUIT BREAKER OR FUSE),
CONTROL WIRES (TB1)
WITH A RECOMMENDED WIRE SIZE OF 14 AWG.
18 AWG 5 IN-LB
5. SOURCE 1 (REQUIRED) SHALL BE PROVIDED FROM THE UPS OUTPUT DISTRIBUTION; SOURCE 2 (OPTIONAL)
AC AUX POWER (TB2)
14 AWG 10 IN-LB
SHALL BE PROVIDED FROM THE UPS BYPASS INPUT.
B (2 SOURCES)** 6. FOR PARALLEL BATTERY CABINETS, THE AC SOURCES CAN BE PROVIDED TO ONLY THE "MASTER" CABINET B
TOP WIRING KIT AND FROM THERE TO THE PARALLEL CABINETS USING THE SUPPLIED INTERCONNECT HARNESSING.

TOP WIRING
NOTE: INTERCONNECT ASSEMBLY
TERMINAL BLOCK (TB-1)
RECOMMEND 3/0 COMPRESSION LUG
THOMAS & BETTS CATALOG# 54265
C CONTROL WIRING TO UPS (TB1) C

TB1-1 MCCB NORMALLY OPEN

TB1-2 MCCB COMMON

TB1-3 MAJOR ALARM NORMALLY OPEN

TB1-4 MAJOR COMMON

TB1-5 MINOR ALARM NORMALLY OPEN GROUNDING HOLES


TB1-6 MINOR COMMON 1.75" SPACING
D TERMINAL BLOCK D
INPUT, OPEN BREAKER,
TB-1
TB2-7
CONTACT CLOSE >3 SEC
DC(+) TERMINAL BLOCK
TB1-8
GND, OPEN BREAKER, TB-2
CONTACT CLOSE >3 SEC DC(-)

TB1-9 NOT USED

TB1-10 NOT USED


E E
SCALE 3:2

TERMINAL BLOCK (TB-2)

F F
AC AUX POWER 400-500 VAC 100-240 VAC DC BUS JUMPERS
(TB2) SOURCE SOURCE TO SWITCHGEAR
TB2-1 SOURCE 1 L1 SOURCE 1 L1

TB2-2 SOURCE 1 L2 SOURCE 1 L2 OR N

TB2-3 SOURCE 1 L3 NOT USED


FRONT SEE DETAIL A
DETAIL A
TB2-4 SOURCE 1 PE SOURCE 1 PE
SCALE 1:4
G TB2-5 SOURCE 2 L1 SOURCE 2 L1 **COVER AND BUS BAR INSULATORS G
REMOVED FOR CLARITY**
TB2-6 SOURCE 2 L2 SOURCE 2 L2 OR N TOP WIRING INTERFACE BOX
NOT USED ASSEMBLY
TB2-7 SOURCE 2 L3

TB2-8 SOURCE 2 PE SOURCE 2 PE 480 VAC UPS


P-103003825
APPLICATIONS
*14 AWG AC AUXILIARY POWER
SHOULD BE PROTECTED BY A LISTED 15A BREAKER OR 208/220 VAC UPS THIRD ANGLE PROJECTION
P-103003826
METRIC
NAME (PART NUMBER):

APPLICATIONS P-110000740
REVISION: 03
FUSE.

H DESCRIPTION: SAMSUNG UL9540a BATTERY CABINET SITE PLAN SIZE: A2 H


SEE NOTES FOR TOLERANCES
SCALE 1:1 ORIGINATED BY: MULE_V 18-NOV-2019
DIM ARE IN MM (INCHES) AFTER PLATING
STATE: Release SCALE: 1:20
INTERPRET DIM AND TOL PER ASME
MODIFIED BY: M. Kabade 14-AUG-2020 Y14.5-2018 ECO: ECO-191361 SHEET: 2 OF 3
EATON CORPORATION - CONFIDENTIAL AND PROPRIETARY. NOTICE TO PERSONS RECEIVING THIS DOCUMENT AND/OR TECHNICAL INFORMATION
THIS DOCUMENT, INCLUDING THE DRAWING AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL AND IS THE EXCLUSIVE PROPERTY OF EATON CORPORATION, AND IS MERELY ON LOAN AND SUBJECT TO RECALL
BY EATON AT ANY TIME. BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT BE USED IN ANY MANNER ADVERSE TO THE INTERESTS OF EATON
AND THAT NO PORTION OF THIS DOCUMENT MAY BE COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR WRITTEN CONSENT OF EATON. IN THE CASE OF CONFLICTING CONTRACTUAL PROVISIONS, THIS
NOTICE SHALL GOVERN THE STATUS OF THIS DOCUMENT. © 2019 Eaton Corporation - All Rights Reserved.

1 2 3 4 5 6 7 8 9 10 11 A2
1 2 3 4 5 6 7 8 9 10 11 12 Page: 3 of 3

DC + DC - DC + DC -
A A

DC BREAKER DC BREAKER

B
+ 128S UL9540a
- + - B
MODULE 1 136S UL9540a MODULE 1
MODULE 16 CONFIGURATION MODULE 17 CONFIGURATION
- BATTERY CABINET
ONE LINE
+ - BATTERY CABINET +
ONE LINE

+ - + -
MODULE 15 MODULE 2 MODULE 16 MODULE 2
C - + - + C

+ - + -
MODULE 14 MODULE 3 MODULE 15 MODULE 3
- + - +
D
+ - + - D

MODULE 13 MODULE 4 MODULE 14 MODULE 4


- + - +
+ - + -
MODULE 12 MODULE 5 MODULE 13 MODULE 5
E
- + - + E

+ - + -
MODULE 11 MODULE 6 MODULE 6
MODULE 12
- + - +
F
+ - + - F

MODULE 10 MODULE 7 MODULE 11 MODULE 7


- + - +
+ - + -
MODULE 9 MODULE 8 MODULE 8
MODULE 10
G
- + - + G

+MODULE 9
- METRIC
THIRD ANGLE PROJECTION
NAME (PART NUMBER):

P-110000740
REVISION: 03

H DESCRIPTION: SAMSUNG UL9540a BATTERY CABINET SITE PLAN SIZE: A2 H


SEE NOTES FOR TOLERANCES
ORIGINATED BY: MULE_V 18-NOV-2019
DIM ARE IN MM (INCHES) AFTER PLATING
STATE: Release SCALE: NTS

INTERPRET DIM AND TOL PER ASME


MODIFIED BY: M. Kabade 14-AUG-2020 Y14.5-2018 ECO: ECO-191361 SHEET: 3 OF 3
EATON CORPORATION - CONFIDENTIAL AND PROPRIETARY. NOTICE TO PERSONS RECEIVING THIS DOCUMENT AND/OR TECHNICAL INFORMATION
THIS DOCUMENT, INCLUDING THE DRAWING AND INFORMATION CONTAINED THEREON, IS CONFIDENTIAL AND IS THE EXCLUSIVE PROPERTY OF EATON CORPORATION, AND IS MERELY ON LOAN AND SUBJECT TO RECALL
BY EATON AT ANY TIME. BY TAKING POSSESSION OF THIS DOCUMENT, THE RECIPIENT ACKNOWLEDGES AND AGREES THAT THIS DOCUMENT CANNOT BE USED IN ANY MANNER ADVERSE TO THE INTERESTS OF EATON
AND THAT NO PORTION OF THIS DOCUMENT MAY BE COPIED OR OTHERWISE REPRODUCED WITHOUT THE PRIOR WRITTEN CONSENT OF EATON. IN THE CASE OF CONFLICTING CONTRACTUAL PROVISIONS, THIS
NOTICE SHALL GOVERN THE STATUS OF THIS DOCUMENT. © 2019 Eaton Corporation - All Rights Reserved.

1 2 3 4 5 6 7 8 9 10 11 A2

You might also like