Professional Documents
Culture Documents
SHAFT CP
X1
GUARD W
S Z
HD
5.0 (127)
K K K
STANDARD* OPTIONAL* OPTIONAL ENGINE MODEL X1 WIDTH
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND 40.06 30
VMFP-06HT
(1018) (762)
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
VMFP-T6HT 40.06 31.13
PUMP SIZE HY
SUCTION
VMFP-L6HR
-T6HT (1018) (791)
DISCH MODEL CASE POWER S W X Z CP YY ZZ HD -06HT -L6HR VMFP-T6HR
BORE SERIES -T6HR
3 481 10 4 2 4.5 13.5 10 4.5 24 11 1.25 16 20.5 20
(114) (343) (254) (114) (610) (279) (406) (521) (508)
3 492 10A 4 NA 5.5 16.5 10 5.5 29.19 10 .75 16 17.63 NA
(140) (419) (254) (140) (741) (254) (406) (448)
4 481 11A/C 5 3 5 14.5 11.25 5 26 12.75 1.25 16 19.5 19
(127) (368) (286) (127) (660) (324) (406) (495) (483)
4 492 10 6 N/A 6.5 16.88 10.25 6.5 29.88 11 .75 18 17.12 16.63
(165) (429) (260) (165) (759) (279) (457) (435) (422)
4 491 11A/C 6 N/A 6.88 16.63 11.25 7.13 29.75 14 .75 19 17.38 16.88
(175) (422) (286) (181) (756) (356) (483) (441) (429)
5 481 11B/C 6 4 5.5 16 11.25 5.5 28.5 13.25 1.25 16 18 17.5
/D (140) (406) (286) (140) (724) (337) (406) (457) (445)
5 492 10 8 N/A 8 20 12.5 7 35.5 13 1 21 14 13.5
(203) (508) (318) (178) (902) (330) (533) (356) (343)
6 481 11HH 8 4A 8.63 18.13 10 8.63 32.88 15 1.25 23 15.88 15.38
(219) (461) (254) (219) (835) (381) (584) (403) (391)
6 481 14HH 8 5A 7.5 20.44 15 7.5 36.75 17 1.25 23 13.56 13.06
(191) (519) (381) (191) (933) (432) (584) (344) (332)
6 491 12A 6 N/A 6.88 16.63 20.5 7.13 29.75 14 1 19 17.38 16.88
(175) (422) (521) (181) (756) (356) (483) (441) (429)
6 492 10 10 N/A 9 20.63 13 7.5 36.75 15 1 23 13.38 12.88
(229) (524) (330) (191) (933) (381) (584) (340) (327)
* Pump sizes 6-481-11HH & 6-481-14HH are furnished as standard with 125# suction flange and 250# discharge flange.
NOTES
1. All dimensions are in inches (mm).
2. Dimensions may vary ± 3/8" (9).
3. Not for construction purposes unless certified.
4. The drive shaft is not designed to operate at 0°. The engine crankshaft must be parallel offset 0.2 ± 0.1
inch above the pump shaft and may be parallel offset from the pump shaft .02 inch laterally. Refer to the
engine manual for alignment instructions.
5. Pump suction and discharge flanges are ANSI Standard flat face.
6. Refer to individual engine dimension print for reference point used to determine overall engine length.
7. Left hand (CCW) rotation is not available.
AURORA MODEL 485 Section 913 Page 207
TWO STAGE FIRE PUMPS Date February 2005
Supersedes Section 913 Page 207
CLARKE VMFP-06HT, -T6HT, -L6HR & -T6HR Dated November 2001
DIESEL DRIVE
51.75 (1314)
APPROX (SEE NOTE 6) WIDTH
10.0 DISCHARGE CL
(254) CP
SHAFT
W ZZ PIPE TAP
GAP
BOTH SIDES
SHAFT M
GUARD HZ X1
1/2 PUMP CL
PIPE TAP
SUCTION DISCHARGE
S Z
HD
5.0 (127)
K K
STANDARD OPTIONAL
125# SUCTION FLANGE 250# SUCTION AND
250# DISCHARGE FLANGES DISCHARGE FLANGES
PUMP SIZE
SUCTION
HY HY
VMFP-T6HT
DISCH MODEL CASE POWER M S W X Z CP YY ZZ HD VMFP-06HT VMFP-L6HR HZ
BORE SERIES VMFP-T6HR
5 485 12 5 4A 6.63 7 20.88 13 7 35.38 13 1-1/4 19 13.25 12.77 1.38
(168) (178) (530) (330) (178) (899) (330) (483) (337) (324) (35)
6 485 12 6 5A 7.5 8 22.88 14 8 38.5 14 1-1/4 20 11.25 10.77 1.63
(191) (203) (581) (356) (203) (978) (356) (508) (286) (274) (41)
NOTES
1. All dimensions are in inches (mm).
2. Dimensions may vary ± 3/8" (9).
3. Not for construction purposes unless certified.
4. The drive shaft is not designed to operate at 0°. The engine crankshaft must be parallel offset 0.2 ± 0.1
inch above the pump shaft and may be parallel offset from the pump shaft .02 inch laterally. Refer to the
engine manual for alignment instructions.
5. Pump suction and discharge flanges are ANSI Standard flat face.
6. Refer to individual engine dimension print for reference point used to determine overall engine length.
7. Left hand (CCW) rotation is not available.
Section 913 Page 208
Date February 2005
Supersedes Section 913 Page 208
Dated November 2001
S Z
HD
6 (152)
K K K
STANDARD * OPTIONAL* OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
S Z
HD
6 (152)
K K K
(127)
HB
48.8 (1240)
CP 30.1 (765)
(SEE NOTE 6)
DISCHARGE CL
W
M
HZ ZZ PIPE TAP
PUMP CL 45.0 (1143) FAR SIDE
1/2
SHAFT PIPE TAP YY X
GUARD
SEE NOTE 4
SUCTION DISCHARGE
S Z
HD
6 (152)
K K
STANDARD OPTIONAL
125# SUCTION AND 250# SUCTION AND
250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
NOTES
1. All dimensions are in inches (mm).
2. Dimensions may vary ± 3/8" (9).
3. Not for construction purposes unless certified.
4. The drive shaft is not designed to operate at 0° angle. The
engine crankshaft is to be parallel offset .35 ± .15 above the
pump shaft. The engine crankshaft may be parallel offset from
the pump shaft .35 right or left. Refer to the engine manual for
alignment instructions.
5. Pump suction and discharge flanges are ANSI Standard flat face.
6. Refer to individual engine dimension print for reference point
used to determine engine overall length.
7. Left hand (CCW) rotation not available.
AURORA MODEL 481 Section 913 Page 213
SINGLE STAGE FIRE PUMPS Date June 2007
CLARKE JU6H-UF30/32/34, -UF50/52/54/58/60/62/68/84, Supersedes Section 913 Page 213
-UFDO/D2, -UFG8, -UFMO/M2/M8 Dated April 2006
DIESEL DRIVE
C WIDTH
(SEE NOTE 6)
CP
1/2 NPT
ZZ NPT
W 45.75 (1162) FAR SIDE
GUARD
YY X
SEE NOTE 4 SUCTION DISCHARGE
S Z
HD
6 (152)
K
HB
K K
STANDARD* OPTIONAL* OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
CP
CL DISCHARGE
W
ZZ NPT
GUARD 45.75 (1162) FAR SIDE
M
HZ
YY X
SEE NOTE 4 SUCTION DISCHARGE
S Z
HD
6 (152)
(6) – 1 (25) x 2 (51) SLOTS CL PUMP HY 1 (25) 30 (762)
HF1 HF1 5 32 (813)
(127)
HB
STANDARD OPTIONAL
125# SUCTION AND 250# SUCTION AND
❑PUMP SIZE
250# DISCHARGE FLANGE
❑ DISCHARGE FLANGES
SUCTION
DIESEL DRIVE
C
WIDTH
(SEE NOTE 6)
CP
1/2 NPT
ZZ NPT
W 45.75 (1162) FAR SIDE
GUARD
YY X
SEE NOTE 4 SUCTION DISCHARGE
S Z
HD
6 (152)
K K K
STANDARD * OPTIONAL OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND ENGINE MODEL C WIDTH
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES JU6H-UF30 61.06 29.64
PUMP SIZE -UF32, -UF34 (1551) (753)
SUCTION
-UF50, -UF52
DISCH MODEL CASE S W X Z CP YY ZZ HB HD HF1 HY
BORE -UF54, -UF58
-UFDO, -UFD2
4 491 14C 6 6.88 17.63 13 8.38 31.69 15.25 3/4 98 20 44 22.38
-UFG8, -UFM0
(175) (448) (330) (213) (805) (387) (2489) (508) (1118) (568) -UFM2, -UFM8
4 492 18 5 9.5 18.38 14 9.5 33.25 14 3/4 98 22 44 21.63 JU6H-UF60 62.80 31.74
(241) (467) (356) (241) (845) (356) (2489) (559) (1118) (549) -UF62, -UF68 (1595) (806)
5 491 14A 8 8.25 17.63 13.5 9.75 31.69 17.25 1 98 23 44 22.38 -UF84
(210) (448) (343) (248) (805) (438) (2489) (584) (1118) (568)
5 491 18A 8 8.13 18.88 15 10.63 33.38 18.75 1 98 23 44 21.13
(207) (480) (381) (270) (848) (476) (2489) (584) (1118) (537)
5 492 18 6 10 21 14 10 37.13 14 1 98 23 44 19
(254) (533) (356) (254) (943) (356) (2489) (584) (1118) (483)
6 491 12A 6 6.88 16.63 20.5 7.13 29.69 14 1 98 23 44 13.38
(175) (422) (521) (181) (754) (356) (2489) (584) (1118) (340)
6 491 14C 10 9.38 20.13 13.25 10 35.88 18 1 98 25 44 19.88
NOTES
(238) (511) (337) (254) (911) (457) (2489) (635) (1118) (505) 1. All dimensions are in inches (mm).
6 491 18C 10 9.38 20.13 16 11.75 35.88 20 1 98 25 44 19.88 2. Dimensions may vary ± 3/8" (9).
(238) (511) (406) (298) (911) (508) (2489) (635) (1118) (505) 3. Not for construction purposes unless certified.
6 492 15 8 8.75 22.5 15.5 8.75 40.25 15 1 98 23 44 17.5 4. The drive shaft is not designed to operate at 0° angle.
(222) (572) (394) (222) (1022) (381) (2489) (584) (1118) (445) The engine crankshaft is to be parallel offset .35 ± .18
8 491 14A 12 10.75 20.5 16 10.75 36.63 22 1 98 28 44 19.5 above the pump shaft. The engine crankshaft may be
(273) (521) (406) (273) (930) (559) (2489) (711) (1118) (495) parallel offset from the pump shaft .35 right or left.
8 491 18A 12 10.75 23.75 16 12.5 41.5 22 1 98 28 44 16.25 Refer to the engine manual for alignment instructions.
(273) (603) (406) (318) (1054) (559) (2489) (711) (1118) (413) 5. Pump suction and discharge flanges are ANSI Standard
8 492 15 10 9.25 22.5 17 9.25 40.25 17 1 98 25 44 17.5 flat face.
(235) (572) (432) (235) (1022) (432) (2489) (635) (1118) (445) 6. Refer to individual engine dimension print for reference
point used to determine “C” dimension.
7. Left hand (CCW) rotation not available.
CP ZZ NPT
FAR SIDE
1/2 NPT
50.13
W (1273)
GUARD YY X
SUCTION DISCHARGE
S Z
HD
6 (152)
K K
HB
K
STANDARD OPTIONAL OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
69.88 (1775)
WIDTH
(SEE NOTE 6)
CP
W DISCH.
CL 50.13
PUMP M (1273)
CL HZ YY X
SUCTION DISCHARGE
S Z
HD
6 (152)
STANDARD OPTIONAL
NOTES
1. All dimensions are in inches (mm).
2. Dimensions may vary ± 3/8" (9).
3. Not for construction purposes unless certified.
4. The drive shaft is not designed to operate at 0° angle. The
engine crankshaft is to be parallel offset .35 ± .15 above the
pump shaft. The engine crankshaft may be parallel offset from
the pump shaft .35 right or left. Refer to the engine manual for
alignment instructions.
5. Pump suction and discharge flanges are ANSI Standard flat face.
6. Refer to individual engine dimension print for reference point
used to determine engine overall length.
7. Left hand (CCW) rotation not available.
Section 913 Page 219
Date November 2008
Supersedes Section 913 Page 219
Dated April 2006
51.10 (1298)
(SEE NOTE 6)
WIDTH
SEE NOTE 4
CP
W X1
1/2
COUPLING PIPE YY X
GUARD TAP
S Z
HD
10
K K K
STANDARD OPTIONAL OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
51.10 (1298)
(SEE NOTE 6)
WIDTH
SEE NOTE 7
CP
W X1
1/2
COUPLING PIPE YY X
GUARD TAP
S Z
HD
10 (254)
HF1 HF1 HM HJ HE HJ
(6) HH DIA. HOLES FOR FOUNDATION BOLTS HY HA
HB
K K K
STANDARD * OPTIONAL OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
NOTES
1. All dimensions are in inches (mm).
2. Dimensions may vary ± 3/8" (9).
3. Not for construction purposes unless certified.
4. Pump suction and discharge flanges are ANSI Standard flat face.
5. Flange ratings are either 125# or 250# and must be specified for each order submittal.
6. Refer to individual engine dimension print for reference point used to determine overall engine length.
7. Coupling gap is approximately 3.63 (92).
8. Left hand (CCW) rotation is not available.
STANDARD 125# SUCTION AND OPTIONAL 125# SUCTION FLANGE, OPTIONAL 250#SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
CASE POWER
DISCH MODEL SUCTION S W X Z CP YY ZZ HB HD HF HF1 HY
BORE SERIES
8 18 16 8 32 18 1.25 108 26 98 49 22
6 481 18B/C 8 5
(203) (457) (406) (203) (813) (457) (32) (2743) (660) (2498) (1245) (559)
9.5 21.88 18 9.5 38 21 2 108 27 98 49 18.13
8 481 21 10 6B
(241) (556) (457) (241) (965) (533) (51) (2743) (686) (2489) (1245) (461)
13.5 21.88 18 13.5 38 22 2 108 33 98 49 18.13
10 481 18 12 6B
(343) (556) (457) (343) (965) (559) (51) (2743) (838) (2489) (1245) (461)
12.25 24.31 20 12.25 42.94 24 2 108 33 98 49 15.69
10 481 18D 12 7A
(311) (617) (508) (311) (1091) (610) (51) (2743) (838) (2489) (1245) (399)
15 25.25 18 15 43.88 23 2 118 33 108 54 24.75
12 481 18A 14 7
(381) (641) (457) (381) (1115) (584) (51) (2997) (838) (2743) (1372) (629)
NOTES:
1. All dimensions are in inches and may vary ± 3/8” (10 MM)
2. Not for construction purposes unless certified.
3. The driveshaft is not designed to operate at 0* angle. The engine crankshaft is to be parallel offset 0.35 ± 0.18 inch
above the pump shaft. The engine crankshaft may be parallel offset from the pump shaft 0.35 inch right or left.
Refer to the engine manual for alignment instructions.
4. Suction and discharge flanges are ANSI Standard flat face.
5. Refer to individual engine dimension print for reference point used to determine this dimension.
6. Left hand (CCW) rotation not available.
Section 913 Page 224 AURORA 491 & 492 FIRE PUMPS
Date June 2007 CLARKE MODEL JX6H-UF30, -UF40,
Supersedes Section 913 Page 224
Dated April 2006
-UF50, -UF60 & UF70 DIESEL ENGINES
STANDARD 125# SUCTION AND OPTIONAL 125# SUCTION FLANGE, 250# OPTIONAL 250# SUCTION AND
DISCHARGE FLANGES DISCHARGE FLANGE DISCHARGEFR FLANGES
PUMP SIZE
CASE
DISCH MODEL SUCTION S W X Z CP YY ZZ HB HD HF HF1 HY
BORE
9.38 20.13 16 11.75 35.88 20 1 108 28 98 49 19.88
6 491 18C 10
(238) (511) (406) (298) (911) (508) (25) (2743) (711) (2489) (1245) (505)
9.38 22.63 18 12.13 39.25 22 1 108 28 98 49 17.38
6 491 19A 10
(238) (575) (457) (308) (997) (559) (25) (2743) (711) (2489) (1245) (441)
8 491 18A 12 12.50 20.5 16 12.50 36.63 22 1 108 30 98 49 19.5
(273) (521) (406) (273) (930) (599) (25) (2743) (762) (2489) (1245) (495)
13.5 28.63 20 15 51.5 25 1 118 33 108 54 21.38
8 492 24 12
(343) (727) (508) (381) (1308) (635) (25) (2997) (838) (2743) (1372) (543)
13 25.56 23 14.25 44.56 25 1 108 31 98 49 14.44
10 491 20 16
(330) (649) (584) (362) (1132) (635) (25) (2743) (787) (2489) (1245) (367)
11.5 22.56 21 11.5 45.81 21 1 118 31 108 54 24.44
10 492 18 12
(292) (649) (533) (292) (1164) (533) (25) (2997) (787) (2743) (1372) (621)
NOTES:
1. All dimensions are in inches and may vary ± 3/8” (10 MM)
2. Not for construction purposes unless certified.
3. The driveshaft is not designed to operate at 0* angle. The engine crankshaft is to be parallel offset 0.35 ± 0.18 inch
above the pump shaft. The engine crankshaft may be parallel offset from the pump shaft 0.35 inch right or left.
Refer to the engine manual for alignment instructions.
4. Suction and discharge flanges are ANSI Standard flat face.
5. Refer to individual engine dimension print for reference point used to determine this dimension.
6. Left hand (CCW) rotation not available.
Section 913 Page 225
Date April 2006
Supersedes Section 913 Page 225
Dated February 2005
K K K
"F" 1 (25) DIA HOLES RIGHT HAND PUMP ONLY
BASE HB HA HE HF HF1 HD F
M 72 28 26 48 NA 26 4
(1827) (711) (660) (1218) (660)
M1 78 28 26 54 NA 28 4
(1980) (711) (660) (1371) (711)
M2 78 28 26 54 NA 29-1/2 4
(1980) (711) (660) (1371) (749)
M3 78 28 26 54 NA 32 4
(1980) (711) (660) (1371) (812)
M4 78 28 26 54 NA 26 4
(1980) (711) (660) (1371) (660)
Section 913 Page 230 AURORA MODEL 481, 491 & 492
Date March 2009 SINGLE STAGE FIRE PUMPS
Supersedes Section 913 Page 324 3306B–DIT & DITA CATERPILLAR DIESEL ENGINE
Dated June 2007
DRIVE
C APPROX
WIDTH
SEE NOTE 4
CP ZZ PIPE TAP
FAR SIDE
W
X1
COUPING
GUARD YY
1/2 (12) X
PIPE TAP
S Z
HD
K K
RIGHT HAND PUMP ONLY
K
STANDARD * OPTIONAL OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
X1
COUPING
GUARD YY
1/2 (12) X
PIPE TAP
S Z
HD
K K K
"F" 1 (25) DIA HOLES RIGHT HAND PUMP ONLY
STANDARD * OPTIONAL OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND ENGINE MODEL C X1 WIDTH
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES 3406B-DIT 78-3/4 36-1/2 42
PUMP SIZE (1997) (924) (1066)
SUCTION
C APPROX
WIDTH
SEE NOTE 4
CP ZZ PIPE TAP
FAR SIDE
W
X1
COUPING
GUARD YY
1/2 (12) X
PIPE TAP
S Z
HD
K K K
"F" 1 (25) DIA HOLES RIGHT HAND PUMP ONLY
STANDARD * OPTIONAL OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
NOTES
1. All dimensions are in inches.
2. Dimensions may vary ± 3/8" (9).
3. Not for construction purposes unless certified. * Standard flanges for 10-491-20 are 125# suction, 250 # discharge
4. Coupling Gap will vary with engine and pump model.
5. Suction & discharge flanges ANSI Standard flat face.
6. Refer to individual engine dimension print for reference point
used to determine “C” dimension.
7. Left hand rotation not available.
AURORA MODEL 481, 491 & 492 Section 913 Page 233
SINGLE STAGE FIRE PUMPS Date February 2005
Supersedes Section 913 Page 327
3412–DIT & DITA CATERPILLAR Dated April 2003
DIESEL ENGINE DRIVE
C APPROX
WIDTH
SEE NOTE 4
CP ZZ PIPE TAP
FAR SIDE
W
X1
COUPING
GUARD YY
1/2 (12) X
PIPE TAP
S Z
HD
K K K
STANDARD * OPTIONAL OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
NOTES
1. All dimensions are in inches.
2. Dimensions may vary ± 3/8" (9).
* Standard flanges for 10-491-20 are 125# suction, 250 # discharge 3. Not for construction purposes unless certified.
4. Coupling Gap will vary with engine and pump model.
5. Suction & discharge flanges ANSI Standard flat face.
6. Refer to individual engine dimension print for reference point
used to determine “C” dimension.
7. Left hand rotation not available.
Section 913 Page 234 AURORA MODEL 485 & 495
Date February 2005 TWO STAGE FIRE PUMPS
Supersedes Section 913 Page 328
Dated November 2001 3208–DINA & DIT CATERPILLAR DIESEL
ENGINE DRIVE
C APPROX CP
DISCHARGE
SEE NOTE 4 W WIDTH
ZZ NPT
M NEAR SIDE†
HZ
COUPLING PUMP
GUARD 1/2 (12)
PIPE TAPS X1
YY X
S Z
HD
SUCTION DISCHARGE
10 (254)
K K
STANDARD* OPTIONAL* ONE ON NEAR SIDE FOR OTHER PUMPS.
125# SUCTION FLANGE, 250# SUCTION AND
250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
NOTES
1. All dimensions are in inches (mm).
2. Dimensions may vary ± 3/8" (10).
3. Not for construction purposes unless certified.
4. Coupling Gap will vary with engine and pump model.
5. Suction & discharge flanges ANSI Standard flat face.
6. Refer to individual engine dimension print for reference point
used to determine “C” dimension.
7. Left hand rotation not available.
AURORA MODEL 485 & 495 Section 913 Page 235
TWO STAGE FIRE PUMPS Date February 2005
Supersedes Section 913 Page 329
3306B–DIT & DITA CATERPILLAR DIESEL Dated November 2001
ENGINE DRIVE
C APPROX CP
DISCHARGE
SEE NOTE 4 W WIDTH
ZZ NPT
M NEAR SIDE†
HZ
COUPLING PUMP
GUARD 1/2 (12)
PIPE TAPS X1
YY X
S Z
HD
SUCTION DISCHARGE
10 (254)
K K
STANDARD OPTIONAL
125# SUCTION FLANGE 250# SUCTION AND
250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
BASE HB HA HE HF HF1 HD F HY
E 93 29 27 69 NA 25-1/4 4 8-1/2
(2360) (736) (685) (1751) (641) (216)
E4 115 29 27 91 45-1/2 28 6 16
(2919) (711) (660) (2310) (1155) (711) (406)
NOTES
1. All dimensions are in inches.
2. Dimensions may vary ± 3/8" (9).
3. Not for construction purposes unless certified.
4. Coupling Gap will vary with engine and pump model.
5. Suction & discharge flanges ANSI Standard flat face.
6. Refer to individual engine dimension print for reference point
used to determine “C” dimension.
7. Left hand rotation not available.
Section 913 Page 236 AURORA MODEL 495
Date February 2005 TWO STAGE FIRE PUMPS
Supersedes Section 913 Page 330
Dated November 2001 3406B–DIT & DITA CATERPILLAR DIESEL
ENGINE DRIVE
C APPROX CP
DISCHARGE
SEE NOTE 4 W WIDTH
ZZ NPT
M NEAR SIDE†
HZ
COUPLING PUMP
GUARD 1/2 (12)
PIPE TAPS X1
YY X
S Z
HD
SUCTION DISCHARGE
10 (254)
PUMP SIZE
SUCTION
BASE HB HA HE HF HF1 HD F HY
O2 114 33 31 90 45 28-1/4 6 16
(2893) (838) (787) (2284) (1142) (717) (406)
NOTES
1. All dimensions are in inches.
2. Dimensions may vary ± 3/8" (9).
3. Not for construction purposes unless certified.
4. Coupling Gap will vary with engine and pump model.
5. Suction & discharge flanges ANSI Standard flat face.
6. Refer to individual engine dimension print for reference point
used to determine “C” dimension.
7. Left hand rotation not available.
AURORA MODEL 481 PUMPS Section 913 Page 237
SINGLE STAGE FIRE PUMPS Date February 2005
Supersedes Section 913 Page 341
EDWARDS RADIATOR DIESEL DRIVE Dated May 2004
C APPROX.
(SEE NOTE 6)
EXHAUST WIDTH
RADIATOR DIESELS CONNECTION CP
REQUIRE ADDITIONAL
AIR FLOW FOR COOLING RADIATOR 1/2" NPT
W
SEE X1
NOTE 3
AIR FLOW
SUCTION DISCHARGE
S Z
SHAFT HD
GUARD
HY 1.36 (35) YY X
44.64 (1134) 44.64 (1134) ZZ PIPE TAP
FAR SIDE
(2) .75 (19) HOLES
RIGHT HAND PUMP ONLY
35.63 (905)
27.63 (702)
32.63 (829)
38 (965)
92 (2337)
K K K
STANDARD OPTIONAL OPTIONAL ENGINE MODEL HD C WIDTH X1
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND EMI 4041D 21.87 45.63 26.10 30.50
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES (555) (1159) (663) (775)
PUMP SIZE EMI 4050T 21.87 45.63 26.10 36.50
SUCTION
SUCTION DISCHARGE
S Z
SHAFT
HD
GUARD
HY 1.36 (35) YY X
44.64 (1134) 44.64 (1134)
ZZ PIPE TAP
FAR SIDE
(2) .75 (19) HOLES
35.63 (905)
27.63 (702)
32.63 (829)
RIGHT HAND PUMP ONLY
38 (965)
92 (2337)
K K K
STANDARD * OPTIONAL OPTIONAL ENGINE MODEL HD C X1 WIDTH
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND EMI 4041D 21.87 45.63 26.10 30.50
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES (555) (1159) (663) (775)
PUMP SIZE EMI 4050T 21.87 45.63 26.10 36.50
SUCTION
C APPROX.
(SEE NOTE 6) WIDTH
S Z
SHAFT
HD
GUARD
HY 1.36 (35) YY X
44.64 (1134) 44.64 (1134)
ZZ PIPE TAP
FAR SIDE
(2) .75 (19) HOLES
RIGHT HAND PUMP ONLY
27.63 (702)
32.63 (829)
35.63 (905)
38 (965)
92 (2337)
K K K
STANDARD OPTIONAL OPTIONAL ENGINE MODEL HD C WIDTH X1
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND EMI 4JB1H 22.52 46.87 23.63 33.00
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES (572) (1190) (600) (838)
PUMP SIZE EMI 4080DH 22.52 52.00 30.00 41.80
SUCTION
C APPROX.
(SEE NOTE 6) WIDTH
S Z
SHAFT
HD
GUARD
HY 1.36 (35) YY X
44.64 (1134) 44.64 (1134)
ZZ PIPE TAP
FAR SIDE
(2) .75 (19) HOLES
27.63 (702) RIGHT HAND PUMP ONLY
32.63 (829)
35.63 (905)
38 (965)
92 (2337)
K K K
STANDARD * OPTIONAL OPTIONAL ENGINE MODEL HD C X1 WIDTH
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND EMI 4JB1H 22.52 46.87 33.00 23.63
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES (591) (1190) (838) (600)
PUMP SIZE EMI 4080DH 22.52 52.00 41.80 30.00
SUCTION
CASE POWER
DISCH MODEL BORE SERIES S W X Z CP YY ZZ HY HD
5 3 5 14.5 11.25 5 26 12.75 1-1/4 25.25 24.63
(127) (368) (286) (127) (660) (324) (641) (626)
4 481 11A
491 11A/C 6 N/A 6.88 16.63 11.25 7.13 29.69 14 3/4 23.13 24.63
(175) (422) (286) (181) (754) (356) (588) (626)
4
NOTES
1. All dimensions are in inches (mm) and may vary ± 3/8" (9).
2. Not for construction purposes unless certified.
3. Suction and discharge flanges are ANSI Standard flat face.
4. Refer to individual engine dimension print for reference point used to determine engine overall length.
5. Left hand (CCW) rotation not available.
6. The drive shaft is not designed to operate at 0˚ angle. The endgine crankshaft is to be parallel offset 0.50 ±0.25 inch. The engine
crankshaft may be parallel offset from the pump shaft 0.50 inch right or left.
*Pump size 6-481-11HH is furnished as standard with 125# suction flange and 250# discharge flange.
Pump size 6-491-12A is available only with 125# suction flange and 250# discharge flange.
Section 913 Page 272 AURORA MODEL 485 PUMPS
Date July 2009 TWO STAGE FIRE PUMPS
Supersedes Section 913 Page 272
Dated June 2008 CUMMINS CFP33
DIESEL DRIVE
STANDARD OPTIONAL
CASE POWER
DISCH MODEL BORE SERIES S M W X Z CP YY ZZ HY HD
4 485 15 6 4A 5 7.13 18.88 13 6.5 31 13.5 1.25 27.98 24.63
(127) (181) (480) (330) (165) (787) (343) (711) (626)
5 485 15 6 5A 5.5 9.13 21.13 15 7.5 34.5 15.44 1.25 27.73 24.63
(140) (232) (537) (381) (191) (876) (392) (704) (626)
6 485 16/ 6 5 8-1/4 10-1/2 23-5/8 19 7-3/4 37-7/8 17 1.25 25.86 30.00
16B (210) (267) (600) (483) (197) (962) (432) (657) (762)
NOTES
1. All dimensions are in inches (mm) and may vary ± 3/8" (9).
2. Not for construction purposes unless certified.
3. Suction and discharge flanges are ANSI Standard flat face.
4. Refer to individual engine dimension print for reference point used to determine engine overall length.
5. Left hand (CCW) rotation not available.
6. The drive shaft is not designed to operate at 0˚ angle. The endgine crankshaft is to be parallel offset 0.50 ±0.25 inch. The engine
crankshaft may be parallel offset from the pump shaft 0.50 inch right or left.
AURORA MODEL 481 & 491 PUMPS Section 913 Page 273
SINGLE STAGE FIRE PUMPS Date April 2006
CUMMINS CFP39
DIESEL DRIVE
K K K
STANDARD* OPTIONAL* OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
CASE POWER
DISCH MODEL BORE SERIES S W X Z CP YY ZZ HY HD
6 N/A 6.88 17.63 13 8.38 31.69 15.75 1 22.11 25.81
(175) (448) (330) (213) (805) (400) (562) (656)
4 491 14C
NOTES
1. All dimensions are in inches (mm) and may vary ± 3/8" (9).
2. Not for construction purposes unless certified.
3. Suction and discharge flanges are ANSI Standard flat face.
4. Refer to individual engine dimension print for reference point used to determine engine overall length.
5. Left hand (CCW) rotation not available.
6. The drive shaft is not designed to operate at 0˚ angle. The endgine crankshaft is to be parallel offset 0.50 ±0.25 inch. The engine
crankshaft may be parallel offset from the pump shaft 0.50 inch right or left.
*Pump size 6-481-11HH and 6-481-14HH are furnished as standard with 125# suction flange and 250# discharge flange.
Pump size 6-491-12A is available only with 125# suction flange and 250# discharge flange.
Section 913 Page 274 AURORA MODEL 481 PUMPS
Date April 2006 SINGLE STAGE FIRE PUMPS
CUMMINS CFP59 & CFP6E
DIESEL DRIVE
K K K
STANDARD* OPTIONAL* OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
CASE POWER
DISCH MODEL BORE SERIES S W X Z CP YY ZZ HY HD
6 4 6.25 16 13.25 6.25 28.5 15 1.25 24.31 28
(159) (406) (337) (159) (724) (381) (617) (711)
5 481 15
NOTES
1. All dimensions are in inches (mm) and may vary ± 3/8" (9).
2. Not for construction purposes unless certified.
3. Suction and discharge flanges are ANSI Standard flat face.
4. Refer to individual engine dimension print for reference point used to determine engine overall length.
5. Left hand (CCW) rotation not available.
6. The drive shaft is not designed to operate at 0˚ angle. The endgine crankshaft is to be parallel offset 0.50 ±0.25 inch. The engine
crankshaft may be parallel offset from the pump shaft 0.50 inch right or left.
*Pump size 6-481-11HH & 6-481-14HH are furnished as standard with 125# suction flange and 250# discharge flange.
AURORA MODEL 485 & 495 PUMPS Section 913 Page 275
TWO STAGE FIRE PUMPS Date April 2006
K K
STANDARD OPTIONAL
125# SUCTION AND 250# SUCTION AND
DISCHARGE FLANGES DISCHARGE FLANGES
PUMP SIZE
SUCTION
CASE POWER
DISCH MODEL BORE SERIES S M W X Z CP YY ZZ HY HD
6 4A 5 7.13 18.88 13 6.5 31 13.5 1.25 28.56 28
(127) (181) (480) (330) (165) (787) (343) (725) (711)
4 485 15
NOTES
1. All dimensions are in inches (mm) and may vary ± 3/8" (9).
2. Not for construction purposes unless certified.
3. Suction and discharge flanges are ANSI Standard flat face.
4. Refer to individual engine dimension print for reference point used to determine engine overall length.
5. Left hand (CCW) rotation not available.
6. The drive shaft is not designed to operate at 0˚ angle. The endgine crankshaft is to be parallel offset 0.50 ±0.25 inch. The engine
crankshaft may be parallel offset from the pump shaft 0.50 inch right or left.
Section 913 Page 276 AURORA MODEL 491 & 492 PUMPS
Date March 2009 SINGLE STAGE FIRE PUMPS
Supersedes Section 913 Page 276
Dated April 2006 CUMMINS CFP59 & CFP6E
DIESEL DRIVE
K K K
STANDARD OPTIONAL OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
CASE
DISCH MODEL BORE S W X Z CP YY ZZ HY HD
6 6.88 17.63 13 8.38 31.69 15.25 3/4 22.69 28
(175) (448) (330) (213) (805) (387) (576) (711)
4 491 14C
NOTES
1. All dimensions are in inches (mm) and may vary ± 3/8" (9).
2. Not for construction purposes unless certified.
3. Suction and discharge flanges are ANSI Standard flat face.
4. Refer to individual engine dimension print for reference point used to determine engine overall length.
5. Left hand (CCW) rotation not available.
6. The drive shaft is not designed to operate at 0˚ angle. The endgine crankshaft is to be parallel offset 0.50 ±0.25 inch. The engine
crankshaft may be parallel offset from the pump shaft 0.50 inch right or left.
AURORA MODEL 485 PUMPS Section 913 Page 277
TWO STAGE FIRE PUMPS Date July 2009
Supersedes Section 913 Page 277
CUMMINS CFP59 & CFP6E Dated June 2008
DIESEL DRIVE
STANDARD OPTIONAL
❑
PUMP SIZE
125# SUCTION AND
250# DISCHARGE FLANGES ❑ 250# SUCTION AND
DISCHARGE FLANGES
SUCTION
CASE POWER
DISCH MODEL BORE SERIES S M W X Z CP YY ZZ HY HD
4 485 15 5 3 5 7.13 18.88 13 6.5 31 13.5 1.25 28.56 28
(127) (181) (480) (330) (165) (787) (343) (725) (711)
5 485 15 6 4 5.5 9.13 21.13 15 7.5 34.5 15.44 1.25 28.31 28
(140) (232) (537) (381) (191) (876) (392) (719) (711)
6 485 12 6 5A 8 7.5 22.88 14 8 38.5 14 1.25 24.93 28
(203) (191) (581) (356) (203) (978) (356) (633) (711)
6 485 16/ 8 5 8.25 10.5 23-5/8 19 7.75 37-7/8 17 1.25 25.86 30
16B (210) (267) (600) (483) (197) (962) (432) (657) (762)
6 485 17A 8 5 7 11 24.5 16 9 38 16.5 1.25 26.81 28
(178) (279) (645) (406) (229) (965) (419) (681) (711)
NOTES
1. All dimensions are in inches (mm) and may vary ± 3/8" (9).
2. Not for construction purposes unless certified.
3. Suction and discharge flanges are ANSI Standard flat face.
4. Refer to individual engine dimension print for reference point used to determine engine overall length.
5. Left hand (CCW) rotation not available.
6. The drive shaft is not designed to operate at 0˚ angle. The endgine crankshaft is to be parallel offset 0.50 ±0.25 inch. The engine
crankshaft may be parallel offset from the pump shaft 0.50 inch right or left.
Section 913 Page 278 AURORA MODEL 481, 491 & 492 PUMPS
Date April 2006 SINGLE STAGE FIRE PUMPS
Supersedes Section 913 Page 278
Dated April 2006 CUMMINS CFP83 & CFP8E
DIESEL DRIVE
K K K
STANDARD OPTIONAL OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
CASE POWER
DISCH MODEL BORE SERIES S W X Z CP YY ZZ HY HD
8 N/A 8.13 18.88 15 10.63 31.38 18.75 1 21.44 28
(207) (480) (381) (270) (797) (476) (545) (711)
5 491 18A
NOTES
1. All dimensions are in inches (mm) and may vary ± 3/8" (9).
2. Not for construction purposes unless certified.
3. Suction and discharge flanges are ANSI Standard flat face.
4. Refer to individual engine dimension print for reference point used to determine engine overall length.
5. Left hand (CCW) rotation not available.
6. The drive shaft is not designed to operate at 0˚ angle. The endgine crankshaft is to be parallel offset 0.50 ±0.25 inch. The engine
crankshaft may be parallel offset from the pump shaft 0.50 inch right or left.
AURORA MODEL 485 & 495 PUMPS Section 913 Page 279
TWO STAGE FIRE PUMPS Date April 2006
K K
STANDARD OPTIONAL
125# SUCTION AND 250# SUCTION AND
DISCHARGE FLANGES DISCHARGE FLANGES
PUMP SIZE
SUCTION
CASE POWER
DISCH MODEL BORE SERIES S M W X Z CP YY ZZ HY HD
8 5 7 11 24.5 16 9 38 16.5 1.25 26.81 28
(178) (279) (622) (406) (229) (965) (419) (681) (711)
6 485 17A
NOTES
1. All dimensions are in inches (mm) and may vary ± 3/8" (9).
2. Not for construction purposes unless certified.
3. Suction and discharge flanges are ANSI Standard flat face.
4. Refer to individual engine dimension print for reference point used to determine engine overall length.
5. Left hand (CCW) rotation not available.
6. The drive shaft is not designed to operate at 0˚ angle. The endgine crankshaft is to be parallel offset 0.50 ±0.25 inch. The engine
crankshaft may be parallel offset from the pump shaft 0.50 inch right or left.
Section 913 Page 280 AURORA MODEL 481, 491, 492 PUMPS
Date February 2007 SINGLE STAGE FIRE PUMPS
CUMMINS CFP11E
DIESEL DRIVE
K K K
STANDARD OPTIONAL OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES
PUMP SIZE
SUCTION
CASE POWER
DISCH MODEL BORE SERIES S W X Z CP YY ZZ HY HD
6 481 20 8 5 8 18 15.75 8 32 18 1.25 21.6 30
(203) (457) (400) (203) (813) (457) (32) (549) (762)
10 N/A 9.38 20.13 16 11.75 35.88 20 1 19.47 30
(238) (511) (406) (298) (911) (508) (495) (762)
6 491 18C
NOTES
1. All dimensions are in inches (mm) and may vary ± 3/8" (9).
2. Not for construction purposes unless certified.
3. Suction and discharge flanges are ANSI Standard flat face.
4. Refer to individual engine dimension print for reference point used to determine engine overall length.
5. Left hand (CCW) rotation not available.
6. The drive shaft is not designed to operate at 0˚ angle. The endgine crankshaft is to be parallel offset 0.50 ±0.25 inch. The engine
crankshaft may be parallel offset from the pump shaft 0.50 inch right or left.