Professional Documents
Culture Documents
6
CONTROLLED RECTIFIERS
a. To present the power circuit topologies and the control possibilities of the
single-phased controlled rectifiers
b. To present simple applications that can be included in control systems.
3. THEORETICAL SUPPORT:
The circuit arrangement is shown in figure 6.1.a with two controlled (T1,T2) and two
uncontrolled (d1,d2) rectifiers. For resistive or resistive-inductive load the average of the load
voltage computed by equation :
2 2 1 cosα 1 cosα
V Va 0,9 V
0 π 2 2 a
The r.m.s. output voltage equation is :
V
0 r.m.s.
V
0
π α 0,5
π
V
a
(6.3.2.)
The output voltage V0(t), besides the D.C. components V0 contains also high order
harmonics whose amplitudes and phases depend in the first line on the delay phase-angle () .
The harmonics have to be smoothed (”filtered” ) to obtain a quasi-ideal (A.C.-D.C.) converter
with a “pure” (D.C.) output voltage .
The output current depend on delay angle () and on the load –character, figure
6.3.1.b .(iOR: resistive load , IORL: resistive- inductive load ). On the A.C. side the current ia(t)
is also harmonics–rich and disturbs the main line. This is the main problem of the usual
rectifiers that are using the delay-angle control strategy .
The circuit topology is presented in figure 6.2.a. The load current will be transferred from
thyristors (T1 ;T2) during the positive half-cycle to thyristors (T3 ;T4) in the negative half-
cycle . The advantages of the full controlled converter can be fully exploited only by
inductive resistive load with ( τ L L L R L ). Figure 6.2.b shows the voltage and current for
LL (L) as an idealized limit case. The average output voltage is :
2 2
V cosα V 0,9 cosα V
0 π a a
as in figure 6.2.d.
If (LL >>), the load current is constant and the rectifiers is in continuous conduction mode
of operation :
i 0 t I 0 V0 R L .
For pure resistive load (LL=0) results the load time constant ( τ L L L R L 0 ). The average
output voltage was given by the equation:
1 cosα
V 0,9 V
0 2 a
while for pure inductive load (RL=0)and
τ L LL R L
It results
V 0 0,9cosα V
a.
The two boundary static characteristic of the rectifying circuits are shows in figure 6.2.d and
results that, for inductive load and for 2 , the average output voltage can be negative. In
practice, this is possible only if the load is “active”, containing are external (equivalent)
power supply (eb) as we will see further.
For α 0 π 2 , V 0 I 0 0 and the convertor operates as rectifier. The electrical power flows
from the supply to the load. The operating point ( V 0 , I 0 ) is placed in the first quadrant figure
6.2.c.
Figure 6.2. Single-phase full-wave controlled converter
For α π 2 and an active load figure 6.3 (eb, ZL) the average of the output voltage ( V 0 )
is negative. The converter operates as inverter in the fourth quadrant. The local current can be
controlled by changing the delay angle () ” beyond 2 “. The converter can operate only if
e 2 V . When the converter is operated as inverter and accidentally the A.C. voltage
b a
disappears, the load current i0(t) can not be more controlled by angle (), being given by the
equation: i e R . This is practically a short-circuit and this situation must be avoided .
0 b L
eb
4. EXPERIMENT PROCESS:
Figure 4.