ETP08

Electronic Transmitter for Pressure and Level

The ETP08 is a series of pressure


transmitters with a wide range of
connections to suit most applications.
The transmitters can measure liquids,
gases, vapours and can be used for
hydrostatic level measurements in open
tanks.
ETP08 is durable against overload. In
most pressure ranges, the transmitter
can withstand overloads three to four
times its maximum, nominal value and
will withstand even higher momentary
pressure surges.
ETP08 is a directly connected
transmitter with no pressure
transmission. This does away with
various problems, such as temperature
drift, which is normally experienced
with transmitters relying upon pressure
transmission. Since ETP08 does not use
a pressure transmission device, it offers
very high temperature stability.
The ETP08 transmitters are stable
with regard to temperature drift and
long term use and intended for two-wire
4–20 mA connection.

ETP08 has the following features:

● Direct connection with no pressure


seal, which eliminates temperature
drift and offers a robust solution.
● Can be used in applications with high
media temperatures, up to 150 °C.
● Several connection possibilities
offers a freedom of choice for
adaptation to each application.
● Simple to install, calibrate and
maintain.
● Well-proven construction, approved
for EExia, DNV and CE.
● Enclosure offers protection against
the ingress of dust and water to IP66.
● Durable against media with solid
particles.
Outline
Transmitter Threaded Threaded with Flange Hygienic Hygienic Removable during
size extended connection clamping screw operation, extend-
Ø 70 diaphragm connection connection ed diaphragm

91.5

151 169.5
165
179.5 179/182

R½"

17/19
35
R1½" Ø 72/90 Ø 50.5
Ø 55
/64
Ø 40
Ø 96/127 266

All measurements are given in mm where nothing else is stated. Ø60

Type Threaded Threaded Flange Hygienic Hygienic Removable


with connections clamping screw during
extended connections connections operation,
diaphragm extended
diaphragm
Connection R½" ext. R1½" 50 80 Clamp 38 Rd 60-6 Welded
or external mm mm ISO2852, DIN405 flange or
NPT ½" ext. O-ring Viton / 2" / 3" clamp 51 or DIN11851 compres-
and DRD or Varivent DN50/40 sion flange
¼" int.
Diaphragm material1
Hastelloy C Yes Yes Yes Yes Yes Yes Yes
Tantalum – Yes2 Yes2 Yes2 – – Yes2
Stainless steel, 1.4462 Yes Yes Yes Yes – – Yes
Pressure range
0–14 kPa Yes Yes Yes Yes Yes Yes –
0–35 kPa Yes Yes Yes Yes Yes Yes Yes
0–100 kPa Yes Yes Yes Yes Yes Yes Yes
0–200 kPa Yes Yes Yes Yes Yes Yes Yes
0–1 MPa Yes Yes Yes Yes Yes Yes Yes
0–2 MPa Yes Yes Yes Yes Yes Yes Yes
0–10 MPa Yes – – – – – –
0–15 MPa Yes – – – – – –
Design
Atmospheric pressure Yes Yes Yes Yes Yes Yes Yes
Absolute pressure Yes2 Yes2 Yes2 Yes2 Yes2 Yes2 Yes2
DNV-approval Yes Yes Yes Yes Yes Yes Yes
Accessories
Installation kit P 110301 – – – – –
Welding stud – 435 802 01 – – – –
2" adapter (ext.) – R1½" – 435 826 01 – – – –
Slip-on flange, ∅ 80 mm:
PN40 DIN2656, 1.4435 – – 495 673 01 – – –
PN10 DIN2656, 1.4435 – – 498 080 301 – – –
Slip-on flange, ∅ 50 mm:
PN40 316L/1.4404 – – 498 081 402 – – –
PN10 316L/1.4404 – – 498 081 401 – – –
PN6 316L/1.4404 – – 498 081 403 – – –
Clamp ring 38 – – – 495 695 01 – –
Clamp welding stud 38 – – – 495 693 01 – –
Clamp gasket 38 EPDM – – – 495 694 01 – –
Hygienic, extended
diaphragm, clamp 38 – – – 498 026 901 – –
Welding stud 60 mm – – – – – 498 036 801
Compression flange DN80 – – – – – 498 036 901
Ball valvet Fage 1866 490 571 501
Ball valvePN63, DN32 – – – – – P123001
Display 498 090 001 498 090 001 498 090 001 498 090 001 498 090 001 498 090 001
1. Material in other media related parts is stainless steel 1.4435.
2. Not available with pressure range 0–14 and 0–35 kPa.

2
Transmitter Types The transmitter is clamped between Removable During Operation
standard flange rings. The transmitter This transmitter is intended for liquid
Threaded
fits slip-on flanges of the ANSI or DIN media, even when viscous or fibre-rich.
The threaded version with connection to
type. The extended diaphragm has direct
a ½" thread is intended for clean media.
For transmitters with flange contact with the medium without the
At a media temperature higher than
connection, the type of flange has to be use of a pocket.
+80 °C, a water pocket tube is used to
stated at order. The transmitter can be exchanged
prevent too high a temperature at the
ETP08 with a 50 mm/2" flange and during operation and comprises three
sensor.
six holes, for use with MWP10, is parts; the transmitter, a ball valve and a
The threaded connection is normally
available upon request. welded flange/compression flange. This
sufficient to keep the transmitter in
place. The transmitter can be supported compression flange is designed to fit an
Hygienic Clamp Connected ANSI or DIN 80 mm flange and may be
and reinforced with an installation kit,
A clamp connected transmitter is used installed to measure levels according to
for specific conditions or wall
when special hygiene requirements are the hydrostatic principle.
installation.
needed, such as those in the
pharmaceutical industry. The design
Threaded with Extended
meets ISO 2852 and the transmitter is Temperature Range
Diaphragm
easy to install and remove. The diagram below is applicable for all
This version with connection to a 1 ½"
If clamp 38 connection is not transmitters except transmitters with ½"
thread is intended for fibre-rich and
available, the optional clamping ring, connection.
viscous media. The extended front
connector piece and gasket ring may be
diaphragm is in direct contact with the
used. Connection details for clamp 51 is
media without the use of a pocket. Ambient temperature
available upon request but not kept in
An optional adapter is available for
stock. 0
connection to a 2" thread and an
optional welded sleeve for R1 ½". There 0
Hygienic Screw Connected
are no additional requirements on the Permitted
A screw connected transmitter giving a
installation. The transmitter may also be temperature range
hygienic connection e.g. used in the
connected inside a threaded R1 ½"
Food Industry. The exposed diaphragm
cylinder, such as a pipe sleve or cut-off
has direct contact with the media which 0
valve 80 150
makes it possible for the transmitter to
Media temperature at the diaphragm
measure even viscous liquid media,
Flange Connected
without getting silted up. Approvals
A flange connected transmitter is
The transmitter is installed in Connections with code 7, 8, 9, A,
intended for level measurement in open
accordance with the RD 60-6 D, E and V are 3A approved.
tanks with liquid media even when
connection of SMS 1146, DIN 405 and
viscous or fibre-rich. The risk of
DIN 11851. The transmitter is screwed ETP08 has approvals for DNV, Ghost
blockage is eliminated by the large area
to the connector. and EExia.
of the exposed diaphragm.

Order Codes
See the outline for permitted combinations.

ETP08-XXXX

Material of diaphragm Connection Span min./max. Design


and related parts 1 = R ½" external 1 = 1.68–14 kPa 0 = Atmospheric pressure
3 = Stainless steel 2 = NPT ½" external 2 = 4.2–35 kPa 2 = Absolute pressure
1.4462/1.4435 3 = R 1 ½" external 3 = 12.0–100 kPa 4 = Atmospheric pressure
4 = Hastelloy C-276 4 = 80 mm/3" 4 = 24.0–200 kPa and DNV-approval
/stainless steel 316L, 5 = 50 mm/2" 5 = 0.12–1 MPa 6 = Absolute pressure and
1.4435 6 = Removable during operation 6 = 0.24–2 MPa DNV-approval
5 = Tantalum/stainless steel 7 = 40 mm/DIN11851 7 = 1.2–10 MPa
316L, 1.4435 8 = Rd 60-6 8 = 1.8–15 MPa
9 = Clamp 38
A = Clamp 51
B = House M3. Rd 60-6
C = 1 ½" RJT
D = DRD Connection
E = 50 mm/DIN11851
V = Varivent 2"

Ordering example: Threaded transmitter R ½" external with pressure range 0–65 kPa for atmospheric pressure will have
order code: ETP08-4130 with calibrated measuring range 0–65 kPa.
Note 1: The desired type of flange must be stated when ordering ETP08-44X0 and -45X0.
Note 2: Verify pressure range for actual type as in table on previous page, when defining pressure range 1–8.

3
Function Connection
ETP08 uses a piezo-resistive pressure
sensor which is connected to the
pressure of the medium via a capillary

tube and a diaphragm. Media pressure
applied to the diaphragm is transferred
via silicon oil to the pressure sensor. RY
The oil completely fills the cavity in the
sensor, the capillary tube and the cavity +
above the diaphragm, whichs means Test terminal 4–20 mA
that the diaphragm movement is very
small with pressure changes. The
capillary tube protects the pressure
sensor from transient pressure shocks.
To esure that the sensor has the
correct reference pressure, the rear side

S
is connected to ambient atmospheric
pressure, via a tube, designed in order
that air passes “cold surfaces” closest to Measuring 10F
the pressure connection of the span

ED
432

CB
transmitter. Any humidity in the air will

65
A
987
condense on these surfaces, the

Z
condensate runs out and the air
remaining in the tube remains dry. Switch
Additionally, the reference pressure
connection is designed to prevent Zero
flushing water from entering.
An electronic circuit converts the
sensor bridge circuit resistance change
to a 4–20 mA current signal. A test Cable connection and adjustment
terminal allows monitoring of the
output signal during operation without
Cable Connection Settings
1. Remove the cover of the transmitter Setting the Measuring Range
the need to disconnect the signal lines, Zero and span are set with switches and
to access the terminal chamber.
i.e. the measurement signal remains potentiometers, see figure.
2. Wire the transmitter cable through the
uninterrupted.
cable bushing Pg 11.
3. Connect the transmitter cable to the Setting the Time Constant
terminals marked S+ and S–. Max. The time constant of the transmitter is
cable area 2.5 mm2. selected with a jumper on the printed
Reference tube The transmitter is protected against circuit card. The time constant can be
incorrect polarity connection, however set to 0.1 sec or 3 sec.
the protection circuit is defeated when Use the long time constant when it is
the test terminal is used. necessary to suppress noise and
interference in the measuring signal.
Adjustment
Upon delivery, the transmitter is Switch Positions
adjusted according to the specific
Sensor requirements of the customer. Pos. Zero in % Span in %
Adjustments following installation, 0 -100 to -55 25 to 50
repairs, or to monitor the transmitter
1 -55 to -10 25 to 50
Middle settings, can be done as in 1–5 below.
tube Note that when installing, only the zero 2 -10 to +35 25 to 50
value is to be adjusted (as in 4 below). 3 +35 to +80 25 to 50
1. Connect the transmitter to power sup-
Capillary ply. 4 -100 to -55 50 to 100
tube 2. Put the switch in the position that cor- 5 -55 to -10 50 to 100
respond to desired calibration area, 6 -10 to +35 50 to 100
concering zero and measure range.
3. To measure the output signal, connect 7 +35 to +80 50 to 100
Diaphragm a low resistance (R < 6 Ω) ammeter to 8 -50 to -28 12 to 25
the test terminal. 9 -28 to -5 12 to 25
The pressure of the medium is 4. Connect the pressure which shall con-
transferred to the sensor via silicon stitute the minimum measuring value. A -5 to +18 12 to 25
oil relaying diaphragm movements. Adjust the zero value using the screw
The total volume of the silicone oil B +18 to +40 12 to 25
is only 0.25 ml. Z (zero) until the output signal has a
C -50 to -28 25 to 50
reading of 4.00 mA.
5. Connect the pressure which shall con- D -28 to -5 25 to 50
Principle figure stitute the maximum measuring value. E -5 to +18 25 to 50
Adjust the measuring span using the
screw S (span) until the output signal F +18 to +40 25 to 50
has a reading of 20.00 mA.
4
Changing Exchangeable
Transmitter 1
Warning

The transmitter cannot be removed 2


at high pressure due to the large 3
force required to push the
transmitter back into the valve 4
2
housing. The area affected by the
375 force is 7.5cm2. 5
2
6
3
The transmitter must not be pushed
3

266
in when the ball valve is closed.

The transmitter must be fully


1 1
extended before the ball valve is
operated.
7
The transmitter that is exchangeable
during operation is mounted in a welded Disassembling and assembling 8
flange or in a compression flange (1)
welded in the tank/tube. The valve is To disassemble the electronic unit, E, 9
threaded in the welded flange. The out of the casing, unscrew the two
transmitter is exchanged as follows: screws (3) alternately until E comes 10
1. Slacken carefully the flange nut (2). out of the casing.
Note: The transmitter will be pushed To assemble E into the casing, 11
out by high pressure. The gland nut lubricate the O-ring (7) and turn E to
(3) acts as the mechanical stopper. make the screws enter the threading in 12
2. Shut the ball valve, when the trans- the casing. Tighten the screws
mitter is fully extended. alternately. Be careful that the O-ring 13
3. Slacken the gland nut. The transmitter does not crush.
can now be replaced or inspected. 14
4. Check that the transmitter is clean and
that the sealing rings are undamaged 15
prior to re-assembly.
5. Assemble the new transmitter in the 16
reverse order.
17

18

19
Spare Parts
Item Quantity Order number
1 Cover, complete 1 P104401
2 Switch rod, complete 1 P103701
3 Screw M4x50 A2-70 2 MC6S 4x50
4 O-ring 60.05 x 1.78 mm 1 P105002
5 Cable through-connection 1 495 266 04
6 Top, complete 1 P103001
7 O-ring 59.5 x 3 mm 1 P105001
8 O-ring 4.1 x 1.6 mm 5 015 083 202
9 Divider plate 1 P104201
10 Locking washer SS 1583 1 016 072 107
11 Spring 2 P109301
12 Spring 3 435 479 01
13 Nut ML6M4 2 016 034 312
14 Feed-through capacitor 2 495 262 02
15 Pillar screw 3 P109701
16 Potentiometer rod, complete 2 P103401
17 Printed circuit card 1 P104111
18 Jumper for time constant 1 P110701
19 Screw MRX-POZ M3 x 6 Fzb 3 495 469 01
Spare parts kit:
Items 3, 4, 7, 8, 11, 13, 15, 19 P109901

5
Technical Data

Type Electronic pressure transmitter Installation tolerance


for process control. Threaded connection Max. ±0.3 kPa when installation
Function Directly connected transmitter (1, 2) differs from adjustment position.
with no pressure transmission. Factory adjusted using vertical
Piezo-resistive pressure sensor centre line.
with a capillary tube. Other connections Max. ±0.7 kPa when installation
Operating range From absolute zero to 100% of (3, 4, 5, 6, 7, 8, 9, A) differs from adjustment position.
maximum pressure range value. Factory adjusted using horizontal
centre line.
Absolute pressure Available on certain connector
versions. Vibration tolerance
Measuring span Adjustable from 12 to 100% of Perpendicular to
the max. pressure range value. diaphragm surface Max. +0.3 kPa/G.
Zero point suppression Adjustable from –100 to 80% of Parallel to diaphragm
the max. pressure range value. surface Max. +0.02 kPa/G.
Overloading Vibration test The transmitter has passsed a
vibration test meeting the
14 kPa 250 kPa SS IEC 770.
35 kPa 250 kPa 10–60 Hz, amplitude 0.21 mm.
100 kPa 400 kPa 60–500 Hz, acceleration
200 kPa 400 kPa 19.6 m/s2.
1 MPa 3 MPa Repeatability Less than ±0.1% of measuring
2 MPa 3 MPa span.
10 MPa 15 MPa Deviation Less than ±0.2% of measuring
span (including non-linearities,
15 MPa 15 MPa hysteresis and repeatability).
Material ±0.5% for pressure area 4, 6 and
Diaphragm Refer to “Outline”. 8 at adjustments 50–100% of the
Related parts Stainless steel 1.4435. pressure area.
Housing Stainless steel 1.4306 and Installation Direct on the process line or
polyphenylesulfon (PPS).. using the installation kit.
Ambient temperature –20 to +80 °C Electrical connection Internal terminal block.
Time constant Switchable between 0.1 sec (as Wire area Max. 2.5 mm2
delivered) and 3 sec. Cable entry Pg 11 for 5–12 mm cable
Media temperature Refer to the relevant description. diameter.
Output signal 4–20 mA, two-wire connection. Protection class IP 66
Signal proportional to pressure. Intrinsic safety EExia IIC T4 approved
Max. current at overload 28 mA. Electrical interference Meets the EN 50081-1,
Supply voltage 9–55 V DC. EN 50082-2.
For intrinsic safety 9–30 V DC.
Weight
External series R kΩ = Supply voltage – 9
resistance 20 Threaded connection 650 g
Threaded connection
Series resistance with extended dia-
dependent Less than ±0.1%4. phragm 1040 g
Supply voltage Flange connection,
dependent Less than ±0.1%4. 50 mm 3490 g, incl. PN10 slip-on flange
80 mm 1890 g
Temperature tolerance In temperature range 0–55 °C at
max. measuring range: zero Hygienic clamping con-
point max. ±0.02% per °C for nection 650 g
pressure area 1 and 2. Hygienic screw con-
For other ±0.015% per °C. nections 1030 g
Measurement span max. Removable during
±0.025% per °C. operation,
transmitter 1060 g
ball valve 1250 g

4
The tolerance is valid for up to 30 V supply voltage. To be valid for higher volt-
age, an external resistor is demanded, reducing the voltage over the transmitter
to 24 V at 20 mA.

ABB Automation Technology Products AB Internet: www.abb.se


Instrumentation, 191 85 Sollentuna E-mail: instrumentation@se.abb.com
Customer Center: +46 (0)8 658 80 00

Specifications subject to change without notice. 0945en0209