Discuss the desirable attributes of Power system protection (RSSSSE) in brief and justify how they are contrary
to each other.
Determine the ratio error and hence the ratio correction factor for a CT with turns ratio 500:5, secondary
leakage impedance of 0.01+j0.1 Ω, magnetizing impedance of 4.0+j15Ω and having burden as follows:
a. 1Ω
b. j2Ω