An earth electrode resistance test was conducted on 6 earth bars using an alternating current method with a 500V test voltage. Earth resistances between 1.3 and 1.6 ohms were measured using an earth resistance meter with 4 poles. The test was performed with 3 tapes of 30m each and 4 test rods under 15°C temperature and 70% humidity conditions.
An earth electrode resistance test was conducted on 6 earth bars using an alternating current method with a 500V test voltage. Earth resistances between 1.3 and 1.6 ohms were measured using an earth resistance meter with 4 poles. The test was performed with 3 tapes of 30m each and 4 test rods under 15°C temperature and 70% humidity conditions.
An earth electrode resistance test was conducted on 6 earth bars using an alternating current method with a 500V test voltage. Earth resistances between 1.3 and 1.6 ohms were measured using an earth resistance meter with 4 poles. The test was performed with 3 tapes of 30m each and 4 test rods under 15°C temperature and 70% humidity conditions.
Test Procedure: Alternating Current Method, ACV=500V
Earthing Arrangement: 3x30m Tapes/Standard Conductors & 4 Test Rods
Test Equipment Used: Earth Resistance Meter with 4 poles
Manufacturer Type: ZM Serial No. 3207086
Measurement:
Site Location: Earth Bar No.1 (see the plan attached)
Measured earth electrode resistance REB2 = 1.5 Ω Site Location: Earth Bar No.2 (see the plan attached) Measured earth electrode resistance REB2 = 1.3 Ω Site Location: Earth Bar No.3 (see the plan attached) Measured earth electrode resistance REB2 = 1.45 Ω Site Location: Earth Bar No.4 (see the plan attached) Measured earth electrode resistance REB2 = 1.6 Ω Site Location: Earth Bar No.5 (see the plan attached) Measured earth electrode resistance REB2 = 1.3 Ω Site Location: Earth Bar No.6 (see the plan attached) Measured earth electrode resistance REB2 = 1.3 Ω
Weather condition: Temperature 15°C, Ground Humidity 70%