EARTH ELECTRODE RESISTANCE TEST CERTIFICATE

CURRENT EDITION OF THE I.E.E. REGULATIONS

CUSTOMER:

Proprietary Earth Tester:

Test Procedure: Alternating Current Method, ACV=500V

Earthing Arrangement: 3x30m Tapes/Standard Conductors & 4 Test Rods

Test Equipment Used: Earth Resistance Meter with 4 poles


Manufacturer Type: ZM
Serial No. 3207086

Measurement:

Site Location: Earth Bar No.1 (see the plan attached)


Measured earth electrode resistance REB2 = 1.5 Ω
Site Location: Earth Bar No.2 (see the plan attached)
Measured earth electrode resistance REB2 = 1.3 Ω
Site Location: Earth Bar No.3 (see the plan attached)
Measured earth electrode resistance REB2 = 1.45 Ω
Site Location: Earth Bar No.4 (see the plan attached)
Measured earth electrode resistance REB2 = 1.6 Ω
Site Location: Earth Bar No.5 (see the plan attached)
Measured earth electrode resistance REB2 = 1.3 Ω
Site Location: Earth Bar No.6 (see the plan attached)
Measured earth electrode resistance REB2 = 1.3 Ω

Weather condition: Temperature 15°C, Ground Humidity 70%