Read carefully the installation instructions before starting the cable preparation.
Check if all the components listed on the bill of material are in the kit.
1. CABLE PREPARATION (fig. n. 1 and n. 2)
1.1 Train the cable in final position and cut it properly to connect to the electrical system.
1.2 Remove the outer jacket according to the CABLE JACKET REMOVAL LENGTH " A " (shown on the table according to the
voltage).
1.3 Fix the metallic protective covering (armour) at approx 40 mm from the outer jacket edge by some laps of copper wire. Remove
the armour near the copper wire.
1.4 Roughen the outer jacket for 50 mm.
WARNING: The ELCOMASTIC 83 tape must be applied stretching up to reduce the original width to the half, about.
1.5 Apply two halflapped layers of ELCOMASTIC 83 tape on the outer jacket edge for a tract of 30 mm from the edge.
CABLE WITH WIRE SHIELD
1.6 Don’t cut the wires of the metallic shield, but turn back completely on the outer jacket and fix them on to the cable at 50 mm
(lower tape edge) from the outer jacket edge, by some laps of PVC tape ELCOPLAST 51.
Joint and twist the wires of the metallic shield together in order to obtain a strand-shape conductor.
CABLE WITH TAPE SHIELD
1.7 Remove the tape shield, leaving them exposed for a length of 25 mm from armour edge.
1.8 Fix on the exposed tapes of the metallic shield the ground copper braid, tinned side, with the costant force spring. Fix the
ground copper braid on to the cable at 50 mm (lower tape edge) from the outer jacket edge, by some laps of PVC tape
ELCOPLAST 51.
--------------------------------------
1.9 Fix the wires of metallic shield or the ground copper braid on the armour with the costant force spring.
1.10 Apply, to the end of the wire shield opportunely shaped or to the end of ground copper braid, the low voltage lug and crimp it
with appropriate tools.
1.11 Remove the cable semiconductor (if necessariy use appropriate tool) leaving exposed 55 mm from the armour edge for cable
with wire shield, or for 30 mm from the shield edge for cable with tape shield.
1.12 Remove the primary insulation in such a way to expose the conductor of a cable for a length corresponding to the lug depth +
5 mm. Pay attention do not damage the conductor.
1.13 Apply a suitable medium voltage lug, orient it correctly, and crimp it with a suitable tools, remove sharp or point of a crimping
product and, at least fill up by a mastic eventual hole.
1.14 If necessary, smooth the insulation surface, to be sure that all semiconducting traces are removed, using the supplied
abrasive cloth without touching the semiconductive layer.
1.15 Clean the cable insulation by the cleaning tissue, starting from the top end toward the semiconductor, if necessary clean also
the cable semiconductor without touching the primary insulation previously cleaned.
ELCOTERM TES - 1284/EZ ÷ 3684/EZ Page 2/4 Drawing Nº 862/EZ ELCOTERM TES - 1284/EZ ÷ 3684/EZ Page 3/4 Drawing Nº 862/EZ
ACCESSORIES FOR ELECTRICAL CABLES
Installation instruction
HEAT SHRINKABLE
OUTDOOR TERMINATION
for
single core
plastic or rubber insulated cable
with armour and
wire or tape shield
Highest voltage 12 to 36 kV
Code
DRAWING N° MP11185
Drawn Rev. Approved
ELCOTERM TES - 1284 ÷ 3684 Page 4/4 Drawing Nº 862 ELCOTERM TES - 1284 ÷ 3684 Page 1/4 Drawing Nº 862