HEALTH, SAFETY & ENVIRONMENTAL INFORMATION

Exceptional risks relating to the works associated with this drawing are identified below.

Construction
No specific risks identified

Operation & Maintenance


No specific risks identified

Decommision & Demolition


No specific risks identified
HIGH MAST

BOLLARD FILLED WITH The above information is offered as guidance and assumes works are carried out by competent parties working where applicable
35N/MM2 CONCRETE INFILL to an appropriate Method Statements. The list of Risks/Hazards is not exhaustive and reference should be made to the relevant
CDM Risk Assessment documentation and Pre-Construction information.
REV:
01.C02 BOLLARD FILLED WITH GENERAL NOTES
35N/MM2 CONCRETE INFILL
REV: © 2022 IDOM
01.C02
1. This drawing has been prepared for the use of IDOM's client. It may not be used, modified, reproduced or relied
FOR HML FOUNDATION DETAILS 150mm Ø X 8mm HOLLOW STEEL BOLLARD, HOT upon by third parties except as agreed by IDOM or as required by law. IDOM accepts no responsibility and
REFER TO DRAWING DIPPED, GALVANISED, ETCH PRIMED. denies any liability whatsoever to any party that uses and relies on this drawing without IDOM's written consent.
P102658-IDM-AER-400000-DWG-Z-301690 PAINTED AND PRIMED GREY
2. The use of any proprietary products shown on this drawing or in any associated specifications is based solely on
1000 the data made available to IDOM by the manufacturer and/or supplier, and IDOM has made no detailed check
900 900 of the proprietary aspects of that product which remain the sole liability of the manufacturer and/or product
PROPOSED BOLLARD SET IN supplier. All proprietary products must be installed in accordance with the manufacturer's requirements.
EARTHING PIT 1200 500 X 500 X 500mm BASE WITH MIN
POWER SUPPLY 50N/mm2 NON SHRINK GROUT. 3. If this drawing has been received electronically it is the recipient's responsibility to print the document to the
JOINT JOINT
correct scale.

4. Do not scale from this drawing. Use dimensions where provided on this and related plans, sections and details.
500
Varies
5. All dimensions are in metres unless stated otherwise.

6. This drawing is to be read in conjunction with all other relevant drawings and specifications.
Varies 50mm BLINDING
UNDER PAD BASE 7. Existing infrastructure is based on an amalgamation/combination of; topographical surveys, aerial surveys,
partially completed services investigations, historical record drawings, design drawings and as-built drawings
Varies provided by LLA, in varying states of readiness and reliability.
500
8. No liability is accepted by IDOM for any discrepancy, omission or deviation and the actual existing infrastructure
must be verified and established on site by the contractor before the commencement of the works.

9. Design is based, on EASA-CS-ADR-DSN (European Aviation Safety Agency - certification specifications and
guidance material for aerodromes design) Issue 6 as instructed by LLA. Other requirements have been applied
PROTECTION BOLLARD REV:
as instructed or approved by LLA.
500 SCALE 1:25 01.C02
Dimension in mm.
NOTES

1V:1H 300
1. High mast lighting to be installed in accordance to manufacturer’s instructions.

4800 mm COPPER 2. For foundation details refer to drawing number P102658-IDM-AER-400000-DWG-Z-301690.


1V:1H BONDED EARTH
3. Bollards to be installed when there is a risk to be strike by GSE vehicles. For bollard location details, refer to
MINIMUM 75mm THICK BLINDING ELECTRODE drawing P102658-IDM-AER-4X0000-DWG-Z-301600.
DUCT CAST INTO CONCRETE
LAYER GRADE 15/40

REV:
01.C02

SECTION 30000
HIGH MAST LAYOUT
SCALE 1:25
Dimension in mm.

PROPOSED BOLLARD SET IN 500 X 500 X 500mm


BASE WITH MIN 50N/mm2 NON SHRINK GROUT.

3152
EARTHING PIT - PT205
REV: 300x300mm
01.C02

1 x 50 Ø

1000mm
CLEARANCE MIN.
3000mm LUMINAIRE
CRADLE CLEARANCE TO EARTHING PIT

01.C02 Revised to Include Protection Details 21/12/22

01.C01 Issued for Construction 18/11/22


3148
Rev Description Date
REV: ISSUED/ REVISION
01.C02
LV)
0Ø( HIGH MAST LIGHTING Drawn By: Checked By: Approved:
1x15 NM JS HE

REV: Consultant:
01.C02 POWER SUPPLY
1000mm RYEBRIDGE
CLEARANCE MIN. BOLLARD FILLED WITH Unit 4, Barratt Industrial Park, Airport Way
POWER SUPPLY 35N/MM2 CONCRETE INFILL LU2 9NH Luton
Phone +44 158 245 15 25
www.ryebridgeconstruction.com
EARTHING PIT

Consulting, Engineering,
REV: 300 Architecture
01.C02 Av. Monasterio de El Escorial, 4
BOLLARD FILLED WITH 28049 Madrid (Spain)
35N/MM2 CONCRETE INFILL Phone +34 91 444 11 50
www.idom.com

TO EARTHING PIT Project Title:


PLAN
P102658-IDM-AER-400000-DWG-Z-301680.dwg

HIGH MAST LIGHTING FOR HML FOUNDATION DETAILS PROJECT CURIUM PHASE 2
SCALE 1:25 REFER TO DRAWING
Dimension in mm. P102658-IDM-AER-400000-DWG-Z-301690 1100 STAGE 4 DESIGN

Drawing Title:
High Mast Lighting & FEGP
SECTION C-C SHOWING GENERAL ARRANGEMENT Standard Details - HML Infrastructure
SCALE 1:25
Dimension in mm.

Scale: Sheet: A1 Date: Project S4


1:25 18/11/22 Status:

Drawing Nº: P102658-IDM-AER- 400000-DWG-Z-301680 REV: 01.C02