Centrifugal Exhaust Fans:
Roof Upblast and Sidewall
• CUBE, CUE, CWB, CW, USGF, and S-CUBE models are listed for Greenheck Fan Corporation certifies that the Models
electrical (UL/cUL 705) File no. E40001 CUBE, CUE, CWB, CW, USGF, and S-CUBE fans shown
• CUBE, CUE, CWB, CW, and USGF models are listed for grease removal herein are licensed to bear the AMCA Seal. The ratings
(UL/cUL 762) File no. MH11745 shown are based on tests and procedures performed in
• S-CUBE and USGF models are listed for Emergency Smoke Control accordance with AMCA Publication 211 and Publication
Systems (UL/cUL Listed for 500˚F (260˚C) for 4 hours and 1,000˚F (538˚C) 311 and comply with the requirements of the AMCA
for 15 minutes) File no. MH17511 Certified Ratings Program. The certified ratings for Models
CUBE, CUE, CWB, CW, USGF, and S-CUBE are shown on
*UL/cUL is optional and must be specified pages 18 to 81.
Model Comparison
Mounting Application Drive Type Performance
High Temperature
General/Clean Air
Contaminated Air
Maximum Static
Spark-Resistant
in. wg (Pascals)
Volume Range
(above 200°F )
cfm (m3/hr)
Roof Curb
Pressure
Direct
Wall
Belt
200 - 30,000 5.0
CUBE (340-50,970) (1245)
70 - 6,400 3.0
CUE (119-10,874) (747)
70 - 6,400 3.0
CW (119-10,874) (747)
3
Codes and Certifications
Applications: General Clean Air
Codes and Certifications deterioration or damage that would cause the fan
to operate unsafely plus grease flare-up tests.
UL 705 - Power Ventilators Greenheck products with UL 762 include most
Intended to assure the buyer of the safety of centrifugal roof upblast and centrifugal sidewall
electrical components and connections within power fans, utility fans and housed centrifugal fans.
ventilators and duct fans. Limited to fans connected
to permanently installed wiring that meet NFPA 70
AMCA Certified Ratings Program
Ensures that all data is accurate. The 211 seal for air
and the National Electric Code. Tests under this
performance certifies that the fan has been tested
standard relate to extremes of current, temperature,
to the appropriate AMCA standards in a licensed
fuses, motor windings, bearing temperatures, and
test facility and that the air performance displayed in
water that a fan could be subject to.
catalogues and selection software is accurate. The
UL Power Ventilators for Smoke 311 seal for air and sound performance certifies that
Control Systems the fan has been tested to the appropriate AMCA
Ventilators or duct fans have been investigated sound standards in a licensed facility and that the
with respect to their operation during exposure sound performance displayed in catalogues and
to elevated temperatures. Installed as part of a selection software is accurate. The AMCA Certified
smoke control system and in accordance NFPA Ratings Program is designed to ensure that the
92A and 92B. Requirements also include UL 705 products perform as stated and that a third-party
and if applicable UL 793. Meets the IRI and SBCCI organization has verified all published data for
“Standard Fire Prevention Code” requirements. accuracy and consistency.
UL 762 - Power Ventilators for Restaurant NFPA 96
Exhaust Appliances Standard for Ventilation Control and Fire Protection
UL 762 is for exhausting grease in the airstream of Cooking Operations. This standard outlines
as found in restaurant or kitchen applications. the appropriate installation methods and required
Basic testing is the same as for UL 705 and equipment to ensure a safe and effective kitchen or
additional testing includes operating the fan in cooking installation of HVAC equipment.
a high temperature airstream without warpage,
4
Applications:
Seismic and Vari-Green Motor
Seismic Applications
Models CUBE, CUE, S-CUBE, USGF
The International Building Code has been adopted
on the state and local level throughout most of the
fifty states. The adoption of this code has resulted in
the adherence of buildings, along with electrical and
mechanical components to new previsions in the
code. In particular, there is an emphasis on seismic
compliance. As an industry leader, Greenheck
introduces the first seismic compliant centrifugal
roof exhaust fan available for general clean air
applications. Seattle, WA, 03/05/01 -- Damage in Pioneer Square from the 02/28 earthquake.
FEMA/Photo by: Liz Roll/FEMA News Photo
Greenheck offers products certified for the worst
plausible seismic event that would be found on the the requirements of ASCE 7-05 Minimum Design
IBC Spectral Response Map. Models CUBE, CUE, Loads for Buildings and Other Structures and the
S-CUBE, and USGF are rated for all soil site classes International Building Code.
A-F, which allows Greenheck to provide a seismic
ventilation solution regardless of the location. How Can Greenheck Provide a Seismic
Solution?
Rigorous Testing
While adhering to rigorous testing standards,
• Third-party FEA (Finite Element Analysis) by
Greenheck Fan Corporation is striving to provide a
licensed Professional Engineers
comprehensive selection of equipment to address
• Tested in Accordance with ICC ES AC-156 the HVAC industry’s seismic needs. The offerings
acceptance criteria cover all soil site classes. For the simplification
State P.E. Calculations of the submittal process, the consulting engineer
simply needs to specify seismic compliant
Models have been reviewed by state licensed equipment.
Professional Engineers to ensure they conform to
5
Applications: Emergency Smoke
Control, Restaurant and High Grease
Texas Department The certifications can be viewed on the Texas Department of Insurance Windstorm web
of Insurance site under TDI number RV-42.
Each of the Greenheck models have been subjected to extensive testing procedures.
Certified The CUBE, CUE and USGF have been certified by an independent third party to the ASTM
Independent E-330 Static Pressure Difference Standard, Florida Building Code Test Protocols TAS-202
Third-Party Testing Static Pressure Difference and TAS-201 Large Missile Impact. All tests are video taped for
documentation of test method and results.
All Greenheck high wind models have been analyzed using Computational Fluid Dynamics
Computational (CFD). CFD is computer software designed to simulate the flow of high speed (150 mph)
Fluid Dynamics winds over the surface of objects. The software records the force profile exerted on the
(CFD) fan, so it can be utilized in Finite Element Analysis (FEA).
Utilizing the results from CFD analysis Greenheck can accurately predict the stress,
Finite Element strain, and deflection resulting from high wind loads. Greenheck high wind units have
Analysis (FEA) been proven to withstand 150 mph winds through Finite Element Analysis utilizing
CFD results.
7
Applications: Severe-Duty Roof Curbs
for High Wind and Hurricane
8
Standard Construction
Features
CUE CW
Standard Construction Features CUBE CWB
USGF S-CUBE
9
Standard Construction
Features
Windband
Motor Cooling
Vibration Isolation
Curb Cap
Mounting Holes
Models CUBE and CUE
Galvanized
Mounting
Plate
Internal
Models Supports
Galvanized
CUBE Birdscreen
and CUE SD Curb required
Models CWB & CW
Dual Drives
Bearing Plate
Lifting Points
Hinged Curb
NEMA-3R
Cap with
Cables
Clean-Out PermatectorTM
Port Coating
Hinged Base
The following chart shows which options and accessories are available on Greenheck’s
roof upblast and sidewall exhaust fans.
Coatings — Wide variety of coatings and colors are Baked Enamel Decorative Coatings are
available for decorative to protective applications. heat cured enamels applied either as
wet paints or electrostatic powders.
Primer is applied at the factory to allow
Customers can choose from 16 standard
PRIMER
for final finish in the field. Not available
decorative colors or color match any color.
on model USGF.
Note: colors are subject to change. See
Permatector™ is our standard coating. Performance Coatings for Commercial &
Typically used for applications that
TM
PERMATECTOR
Industrial Fans brochure for more details.
require corrosion resistance in indoor
and outdoor environments.
Hi-Pro Polyester is resistant to salt
HI-PRO
POLYESTER water, chemical fumes and moisture in
more corrosive atmospheres. Typically
used for applications that require
superior chemical resistance, excellent
abrasion and outdoor UV protection. This
coating exceeds protective qualities of
Air Dried Heresite and Air Dry Phenolic.
12
8 or 12 in. Wiring by 8 - 24 in.
4 in. (102 mm)
(203 to 305 mm) Others Damper 1/2 in. (13 mm) (203 - 610 mm)
From Curb Edge
Wiring by GPF or SD Curb
Others
Roof Deck Roof Deck
Recommended Damper
Duct and
Factory Wired
Mounting Recommended Motor to
All CUBE, CUE, CWB and CW, exhaust fans are designed for
Bolt Hole
Circle
Duct and
Damper Size
Disconnect
Factory Wired
• Installation must include Motor to Models CUBE and CUE
a means for inspecting, Disconnect
ventilation, system designers must be aware of national, 1/2 in. (13 mm)
4 in. (102
From Curb
disconnect
mm)
through the
Edge
8 - 24 in.
(203 - 610 mm)
Wiring by breather tube
state, and local codes and guidelines
others governing these Factory wired
Wiring by
Others
GPF or SD Curb
Recommended
• When roofing materials extend to the top of the curb, roof 1¼ in. (32 mm) Duct and
Liquid Tight
Damper Size
Flexible Conduit
1¼ in. (32 mm)
curbs should be 1.5-inches (¾-inch on a side) less than the Minimum 8 in.
Recommendedby Others
Roof Opening
unit curb cap to allow for roofing and flashing. (203 mm)
data pages.
• Installation must include a means for inspecting, cleaning Recommended
Models S-CUBE
• Exhaust fans used in emergency smoke applications must
have external wiring. (Wiring must not be installed in the
airstream).
13
Typical Installations
by Application
Minimum Height
NEMA-3R
24 in. curb
Disconnect
Wall Grease
Trap Welded Duct factory wired
by others. Grease
External Wiring from motor to Trap
Minimum of disconnect
Liquid Tight
18 in. ( 457 mm)
Flexible Conduit through the
above roof deck breather tube
by Others
Mounting External Wiring per NFPA (Optional)
Bolt Hole Liquid Tight Minimum 40 in.
Welded Duct Roof Deck External Wiring
Circle Flexible Conduit (1016 mm)
by Others Liquid Tight
Recommended by Others Discharge Height Roof Deck
Flexible Conduit
Roof Opening
by Others
Recommended
Roof Opening Minimum Height
24 in. curb
Grease
Trap Welded Duct
Models CUBE & CUE External Wiring
by others.
Minimum of
Fire Wrapped InstallationFlexible
Liquid Tight
18 in. ( 457 mm)
Conduit
above roof deck
by Others
External Wiring per NFPA
Liquid Tight
Flexible Conduit Roof Deck
by Others
Recommended
Models CWB & CW Roof Opening
14
Severe-Duty Curbs Anchoring:
for Hurricane and Seismic Fans
Roof Truss
5-inch (127 mm)
Mounting Flange Center fasteners
Outside Flange on flange
15
Severe-Duty Curbs Anchoring:
for Hurricane and Seismic Fans
Metal/
Seismic Models Hurricane Square Dimensions Concrete Wood
Steel
CUE CUBE *USGF Fan Curb Roof Outside
Fasteners Per Side
Size Size Size Cap Opening Flange
060 - 075 17 (432) 101/2 (267) 26 (660) 5 5 5
080 - 095 19(483) 121/2 (318) 28 (711) 5 5 5
098 - 131 098 - 131 19 (483) 141/2 (368) 28 (711) 5 5 5
141 - 161 141 - 161 22 (559) 181/2 (470) 31 (787) 5 5 5
Reinforcement Brackets
140 - 160 26 (660) 181/2 (470) 33 (838) 5 5 5
are not required for
180 - 200 30 (762) 201/2 (521) 37 (940) 7 Seismic Rating
7 7
180 - 200 180 - 200 30 (762) 201/2 (521) 39 (991) 7 7 7
220 - 240 34 (864) 261/2 (673) 43 (1092) 7 7 7
300 40 (1016) 321/2 (826) 49 (1245) 7 7 9
360 46 (1168) 381/2 (978) 55 (1397) 7 7 9
Fastener
4204 in. (102 mm) 52 (1321) 441/2 (1130) 61 (1549) 1/4 in.7 (6 mm) fastener
7 minimum
9
from curb edge
480 H-GPF501/2
58 (1473) or (1283) 67 (1702) 5/16 in.
SD curb 7 (8 mm) recommended
7 9
See table for fastener quantities
All dimensions in inches (millimeters). *The outside flange dimension shown above is for the GPF curbs. Subtract 2 inches (51mm) if the SD Curb is
being used.
16
ModelHeader
Page Number Code
The Model number system is designed to completely identify the fan. The correct code letters must
be specified to designate belt or direct drive. The remainder of the model number is determined by
the size and performance.
CUBE - 240 XP - 5 or A
Motor HP (Belt Drive only)
4 = 1/4 10 = 1 30 = 3
Configuration 3 = 1/3 15 = 11/2 50 = 5
5 = 1/2 20 = 2 75 = 71/2
CUBE - Belt Drive Roof Mounted Fan Size 7 = 3/4
CUE - Direct Drive Roof Mounted 060 through 480
CWB - Belt Drive Wall Mounted Motor RPM (Direct Drive only)
CW - Direct Drive Wall Mounted Wheel Pressure Level A = 1725 D = 1550
USGF - Belt Drive Roof Mounted B = 1140 E = 1050
HP - High-Pressure C = 860 G = 1300
S-CUBE - Belt Drive Roof Mounted XP - Extended High-Pressure
Emergency Smoke Control (Belt Drive Only)
17
Roof Upblast - Belt Drive
Size-098: CUBE
247⁄8 1.0
1/4 RPM
E
(632) hp
V
HP
CUR
Density 0.075 lb/ft3
200 0.8
EM
YST
Static Pressure in. wg
Static Pressure Pa
IS S
17
*281⁄4 25
150 0.6
F TH
(718)
173⁄8
TO
15
(441) 10
L EF
100 0.4
12
HE
95
OT
TT
10
13/4 (44) 80
C
50 0.2
LE
19 86
SE
5
OT
(483) N 65
DO 0
0 0.0
0 200 400 600 800 1000 1200
cfm
0 500 1000 1500 2000
3
m /hr
CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Roof Opening = 141/2 x 141/2 (368 x 368) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.040 (1.0) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 58 lb (26 kg)
18
Roof Upblast - Belt Drive
Size-101: CUBE • S-CUBE
247⁄8 1.4
(632) 1/ RPM
1/ 3
RVE
4 hp HP
300 1.2 hp
Density 0.075 lb/ft3
CU
TEM
250 1.0
YS
Static Pressure Pa
*28 ⁄4
IS S
1
18
20
(718)
TH
200 0.8
17 ⁄8
3
OF
16
20
(441)
T
EF
150 0.6
EL
14
30
TH
TO
100 0.4
12
40
13/4 (44)
CT
10
LE
50
SE
19 50 0.2
86
NO
T
(483) 0
DO
0 0.0
0 200 400 600 800 1000 1200 1400 1600
cfm
0 500 1000 1500 2000 2500
3
m /hr
CUBE • S-CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Roof Opening = 141/2 x 141/2 (368 x 368) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.040 (1.0) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 58 lb (26 kg)
19
Roof Upblast - Belt Drive
Size-101HP: CUBE • S-CUBE
247⁄8 3.0
E
700 RPM
CURV
(632) 1/2 h
p HP
2.5 Density 0.075 lb/ft3
M
600 1/3 h
YSTE
p
HIS S
500 2.0 25
Static Pressure Pa
1/4 h
*281⁄4 p 80
OF T
(718)
17 ⁄8
3 400 23
1.5 40
EFT
(441)
20
80
HE L
300
1.0 18
OT
20
TT
200
13/4 (44) 15
L EC
60
19 0.5
13
SE
100 00
(483)
T
NO
0 0.0 DO
0 200 400 600 800 1000 1200
cfm
0 500 1000 1500 2000
3
m /hr
CUBE • S-CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Roof Opening = 141/2 x 141/2 (368 x 368) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.040 (1.0) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 58 lb (26 kg)
20
Roof Upblast - Belt Drive
Size-121: CUBE • S-CUBE
247⁄8 1.8
RPM
(632)
RVE
400 1.6 HP
1/
Density 0.075 lb/ft3
2h
CU
p
1/
350 1.4
3h
TEM
1/
4h
p
Static Pressure in. wg
YS
p
300 1.2
Static Pressure Pa
IS S
*281⁄4
(718) 17
TH
250 1.0 25
173⁄8
OF
(441)
FT
200 0.8 15
LE
00
E
TH
150 0.6 13
00
TO
11
T
13/4 (44) 100 0.4
C
00
LE
SE
19 T 90
(483)
50 0.2 NO 68
0
DO 5
0 0.0
0 300 600 900 1200 1500 1800 2100
cfm
0 500 1000 1500 2000 2500 3000 3500
3
m /hr
CUBE • S-CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Roof Opening = 141/2 x 141/2 (368 x 368) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.040 (1.0) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 66 lb (30 kg)
21
Roof Upblast - Belt Drive
Size-131: CUBE • S-CUBE
1.6
247⁄8
(632) RPM
1/
350 1.4 HP
2
E
hp
URV
Density 0.075 lb/ft3
1/
3
1/
MC
hp
4
300 1.2
hp
STE
Static Pressure in. wg
*281⁄4 250 1.0
SY
16
Static Pressure Pa
45
(718)
HI S
14
17 ⁄8
3
50
FT
200 0.8
(441)
TO
12
EF
150 0.6 50
EL
10
TH
100 50
0.4
TO
13/4 (44)
CT
85
LE
0
19 50 0.2
SE
T 65
(483) NO 0
DO
0 0.0
0 300 600 900 1200 1500 1800 2100 2400
cfm
0 500 1000 1500 2000 2500 3000 3500 4000
3
m /hr
CUBE • S-CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Roof Opening = 141/2 x 141/2 (368 x 368) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.040 (1.0) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 66 lb (30 kg)
22
Roof Upblast - Belt Drive
Size-140: USGF only
Size-141: CUBE • S-CUBE
287⁄8 2.0
RPM
1
(733)
hp
VE
HP
CUR
Density 0.075 lb/ft3
1/
2
400
3/
hp
4
T EM
1.5
hp
1/
Static Pressure in. wg
17
3
25
SY S
1/
hp
Static Pressure Pa
4
*293⁄4
hp
300
HI S
(756)
15
193⁄8
FT
1.0 10
TO
(492)
EF
200 12
EL
80
TH
TO
0.5 10
13/4 (44) 50
CT
100
LE
22 82
SE
T 0
(559) NO 59
DO 0
26 0 0.0
0 400 800 1200 1600 2000 2400 2800 3200
(660)
Size-140: USGF cfm
0 1000 2000 3000 4000 5000
3
m /hr
23
Roof Upblast - Belt Drive
Size-140HP: USGF only
Size-141HP: CUBE • S-CUBE
287⁄8 3.0
1/ 3/
700 2 4 RPM
(733) hp
E
hp
URV
1/ HP
3
hp
2.5 Density 0.075 lb/ft3
MC
600
STE
1/ 21
S SY
500 2.0 hp
Static Pressure Pa
*29 ⁄4
3
18
THI
(756) 60
193⁄8 400
OF
1.5
(492) 16
T
20
LEF
300
HE
1.0 13
T
80
TO
200
13/4 (44) 11
CT
40
LE
0.5
22 89
SE
100
5
(559)
OT
N
26 DO
0 0.0
(660) 0 300 600 900 1200 1500 1800
Size-140HP: USGF cfm
0 500 1000 1500 2000 2500 3000
3
m /hr
24
Roof Upblast - Belt Drive
Size-160: USGF only
Size-161: CUBE • S-CUBE
1.8
287⁄8
RPM
(733)
400 1.6 HP
3/
1
4
RVE
Density 0.075 lb/ft3
hp
hp
1/
CU
350 1.4
2
hp
1/
EM
3
Static Pressure in. wg
13
hp
300 1.2
ST
1/
Static Pressure Pa
90
*293⁄4
SY
hp
(756) 12
IS
250 1.0 50
193⁄8
TH
11
OF
(492) 200 0.8 20
FT
99
LE
150 0.6 0
E
TH
86
TO
0
13/4 (44) 100 0.4
T
73
EC
0
22
EL
50 0.2 S
T
(559) NO
DO
26 0 0.0
0 500 1000 1500 2000 2500 3000 3500 4000
(660)
Size-160: USGF cfm
0 1000 2000 3000 4000 5000 6000
3
m /hr
25
Roof Upblast - Belt Drive
Size-160HP: USGF only
Size-161HP: CUBE • S-CUBE
287⁄8 2.5
600 3/ RPM
(733) 4
hp HP
RVE
1/ 1
hp Density 0.075 lb/ft3
2
CU
500 2.0 hp
1/
TEM
3
hp
16
YS
90
1/
Static Pressure Pa
*29 ⁄4
3 400 4
IS S
1.5 hp 15
(756) 10
TH
19 ⁄8
3
13
OF
(492) 300 40
T
EF
1.0 11
EL
70
TH
200
10
TO
00
13/4 (44)
CT
0.5 82
LE
100 5
22
SE
NO
T
(559)
DO
26 0 0.0
0 500 1000 1500 2000 2500 3000
(660)
Size-160HP: USGF cfm
0 1000 2000 3000 4000 5000
3
m /hr
26
Roof Upblast - Belt Drive
Size-160XP: USGF only
Size-161XP: CUBE
287⁄8 3.5
3/ 1-
4 1/ RPM
CURVE
(733) 800 hp 2
hp HP
1
3.0 hp Density 0.075 lb/ft3
1/
YSTEM
700 2
hp
2.5
THIS S
Static Pressure Pa
25
*29 ⁄4
3
23
(756) 500 2.0 30
F
EFT O
193⁄8 21
35
(492) 400
19
1.5
HE L
40
17
TO T
300 45
1.0 15
50
E CT
13/4 (44) 200
SE L
22 0.5
100
T
NO
(559)
O
D
0 0.0
26 0 400 800 1200 1600 2000 2400 2800
(660)
Size-160XP: USGF cfm
0 500 1000 1500 2000 2500 3000 3500 4000 4500
3
m /hr
CUBE USGF
All dimensions in inches (millimeters). *May be
Damper Size = 16 x 16 (406 x 406) Roof Opening = 181/2 x 181/2 (470 x 470) greater depending on motor. ^Weight shown is
Roof Opening = 181/2 x 181/2 (470 x 470) Windband Thickness = 0.051 (1.3) largest cataloged Open Drip-Proof motor. For
Windband Thickness = 0.051 (1.3) Motor Cover Thickness = 0.040 (1.0) specification information and image of each model,
please see pages 82-87.
Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6)
Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 131 lb (59 kg)
^Approximate Unit Weight = 87 lb (39 kg)
27
Roof Upblast - Belt Drive
Size-180: CUBE • USGF
2.5
353⁄8 600 RPM
(899)
1-
HP
2
1/
RVE
hp
Density 0.075 lb/ft3
2
hp
CU
2.0
1
hp
M
Static Pressure in. wg
STE
14
Static Pressure Pa
1/
3/
400 95
SY
*285⁄8
4
1.5
hp
hp
HE
(727)
13
FT
21 10
1/
1/ p
TO
4
3
(553)
h
hp
EF
1.0 11
40
EL
200
TH
97
TO
0
13/4 (44)
CT
0.5 80
LE
0
SE
30
63
NO
T
(762)
0
DO
0 0.0
0 1 2 3 4 5 6
cfm X 1000
0 2 4 6 8 10
3
m /hr X 1000
28
Roof Upblast - Belt Drive
Size-180HP: CUBE • USGF
353⁄8 3.5
2 RPM
(899) 800 hp
HP
RVE
1-
3.0 1/
2
hp Density 0.075 lb/ft3
CU
700 1
hp
TEM
2.5
S
16
Static Pressure Pa
SY
*28 ⁄8
5 1/ 3/ 85
2 4
hp hp
HIS
(727) 500 2.0
21 15
FT
1/ 00
3
TO
(553) 400 hp
1.5 13
EF
1/ 25
EL
4
300 hp
TH
11
1.0 50
TO
13/4 (44) 200
T
97
C
5
LE
30
SE
0.5
100 T 79
(762) NO 5
DO
0 0.0
0 700 1400 2100 2800 3500 4200 4900
cfm
0 1000 2000 3000 4000 5000 6000 7000 8000
3
m /hr
CUBE USGF
All dimensions in inches (millimeters). *May be
Damper Size = 18 x 18 (457 x 457) Roof Opening = 201/2 x 201/2 (521 x 521) greater depending on motor. ^Weight shown is
Roof Opening = 201/2 x 201/2 (521 x 521) Windband Thickness = 0.051 (1.3) largest cataloged Open Drip-Proof motor. For
Windband Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) specification information and image of each model,
Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) please see pages 82-87.
Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 190 lb (86 kg)
^Approximate Unit Weight = 126 lb (57 kg)
29
Roof Upblast - Belt Drive
Size-200: CUBE • S-CUBE • USGF
353⁄8 2.0
1-
RPM
E
(899)
URV
1/
2
HP
hp
hp
Density 0.075 lb/ft3
C
3/
1
400
TEM
hp
hp
1.5
12
SYS
Static Pressure in. wg
10
Static Pressure Pa
1/
*28 ⁄8
HIS
5
2
1/
300
hp
3
(727)
T
10
hp
60
OF
21 1.0
FT
1/
(553)
LE
92
hp
200 0
HE
OT
78
0
TT
0.5
13/4 (44)
C
100
LE
64
0
SE
30 50
T
O
N 0
(762) DO
0 0.0
0 1 2 3 4 5 6 7
cfm X 1000
0 2 4 6 8 10
3
m /hr X 1000
30
Roof Upblast - Belt Drive
Size-200HP: CUBE • USGF
353⁄8 3.5
RPM
3
(899) 800
hp
HP
RVE
1-
3.0
1/
Density 0.075 lb/ft3
CU
2
700
hp
hp
M
2.5
STE
Static Pressure in. wg
600
1
Static Pressure Pa
SY
hp
*28 ⁄85
16
HIS
500 2.0
00
21 (727)
FT
1/
3/
2
14
(553)
TO
hp
hp
400
20
1.5
EF
12
50
EL
300 10
TH
1.0 80
TO
200 91
13/4 (44)
CT
0
LE
0.5
SE
30 100 T 74
(762) NO 0
DO
0 0.0
0 1 2 3 4 5 6 7
cfm X 1000
0 2 4 6 8 10
3
m /hr X 1000
CUBE USGF
All dimensions in inches (millimeters). *May be
Damper Size = 18 x 18 (457 x 457) Roof Opening = 201/2 x 201/2 (521 x 521) greater depending on motor. ^Weight shown is
Roof Opening = 201/2 x 201/2 (521 x 521) Windband Thickness = 0.051 (1.3) largest cataloged Open Drip-Proof motor. For
Windband Thickness = 0.064 (1.6) Motor Cover Thickness = 0.040 (1.0) specification information and image of each model,
Motor Cover Thickness = 0.040 (1.0) Curb Cap Thickness = 0.064 (1.6) please see pages 82-87.
Curb Cap Thickness = 0.064 (1.6) ^Approximate Unit Weight = 213 lb (97 kg)
^Approximate Unit Weight = 142 lb (64 kg)
31
Roof Upblast - Belt Drive
Size-220: CUBE
423⁄4 2.0
(1086) RPM
1-
2
1/
HP
hp
2
hp
Density 0.075 lb/ft3
E
RV
400
3/
CU
4
1.5
1
hp
hp
Static Pressure in. wg
EM
Static Pressure Pa
ST
*337⁄8
1/
SY
300
2
(860)
hp
HIS
251/2
95
1.0
FT
1/ 1/4
(648)
5
3
TO
hp hp
200
85
F
0
LE
75
E
TH
0
0.5
TO
13/4 (44)
65
100
0
T
EC
34 L
55
SE
0
(864) OT
ON
45
D
0
0 0.0
0 1 2 3 4 5 6 7 8
cfm X 1000
0 2 4 6 8 10 12
3
m /hr X 1000
CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 24 x 24 (610 x 610) depending on motor. ^Weight shown is largest
Roof Opening = 261/2 x 261/2 (521 x 521) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.064 (1.6) information and image of each model, please see
Motor Cover Thickness = 0.051 (1.3) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 174 lb (79 kg)
32
Roof Upblast - Belt Drive
Size-220HP: CUBE
423⁄4 3.0
(1086) 700 RPM
VE
3
HP
CUR
hp
2
Density 0.075 lb/ft3
hp
2.5
600
EM
1-
YST
1
1/
hp
Static Pressure in. wg
2
hp
12
500 2.0
S
Static Pressure Pa
*337⁄8
40
HIS
3/
(860)
11
FT
4
251/2
30
hp
400
TO
10
1/
1.5
(648)
2
10
LEF
hp
300 89
HE
0
1.0
T
TO
77
200 0
13/4 (44)
CT
65
LE
0.5 0
34
SE
100
T
(864)
O
N
DO
0 0.0
0 1 2 3 4 5 6 7 8
cfm X 1000
0 2 4 6 8 10 12
3
m /hr X 1000
CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 24 x 24 (610 x 610) depending on motor. ^Weight shown is largest
Roof Opening = 261/2 x 261/2 (673 x 673) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.064 (1.6) information and image of each model, please see
Motor Cover Thickness = 0.051 (1.3) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 174 lb (79 kg)
33
Roof Upblast - Belt Drive
Size-240: CUBE • S-CUBE
423⁄4 1.6
2
hp RPM
(1086) 1
VE
350 1.4 3/ hp HP
4
CUR
hp Density 0.075 lb/ft3
1-
1/
2
EM
300 1.2 hp
1/
T
2
SYS
hp
Static Pressure Pa
*337⁄8 250 1.0
93
HIS
0
(860) 1/
T
251/2 3
82
hp
OF
200 0.8
0
(648) 72
FT
1/ 0
LE
150 0.6 4
hp
E
62
TH
0
O
100 0.4
T
13/4 (44)
CT
52
0
LE
34 41
SE
50 0.2 0
T
(864) NO
DO
0 0.0
0 1 2 3 4 5 6 7 8 9
cfm X 1000
0 2 4 6 8 10 12 14
3
m /hr X 1000
CUBE • S-CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 18 x 18 (457 x 457) depending on motor. ^Weight shown is largest
Roof Opening = 201/2 x 201/2 (521 x 521) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.064 (1.6) information and image of each model, please see
Motor Cover Thickness = 0.040 (1.0) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 142 lb (64 kg)
34
Roof Upblast - Belt Drive
Size-240HP: CUBE
423⁄4 3.0
RPM
3
(1086) 700
hp
HP
Density 0.075 lb/ft3
RVE
2.5
2
600
hp
CU
1-
1/
EM
2
12
1
500 2.0
hp
hp
ST
30
*337⁄8
Static Pressure Pa
SY
(860) 20
3/
H IS
251/2 400
4
1.5 10
hp
FT
(648) 00
O
1/
300
FT
88
2
hp
0
LE
1.0
E
TH
200 76
0
13/4 (44)
TO
63
T
0.5
C
34 5
LE
100
SE
(864) T
NO
DO
0 0.0
0 1 2 3 4 5 6 7 8
cfm X 1000
0 2 4 6 8 10 12
3
m /hr X 1000
CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 24 x 24 (610 x 610) depending on motor. ^Weight shown is largest
Roof Opening = 261/2 x 261/2 (673 x 673) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.064 (1.6) information and image of each model, please see
Motor Cover Thickness = 0.051 (1.3) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 175 lb (79 kg)
35
Roof Upblast - Belt Drive
Size-240XP: CUBE
423⁄4 6
E
1400 RPM
CURV
(1086)
3
2
hp
HP
hp
5 Density 0.075 lb/ft3
STEM
1200
1-
1/
2
Static Pressure in. wg
IS SY
hp
1000 4
Static Pressure Pa
*337⁄8 21
H
65
hp
(860)
OF T
251/2 800
19
3
3/
LEFT
(648) 40
4
hp
600 17
30
TH E
1/
2
2 15
hp
T TO
400 20
13/4 (44) 13
C
10
ELE
1
34 200 11
00
TS
(864)
NO
O
0 0 D
0 500 1000 1500 2000 2500 3000 3500 4000 4500
cfm
0 2000 4000 6000
3
m /hr
CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 24 x 24 (610 x 610) depending on motor. ^Weight shown is largest
Roof Opening = 261/2 x 261/2 (673 x 673) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.064 (1.6) information and image of each model, please see
Motor Cover Thickness = 0.051 (1.3) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 175 lb (79 kg)
36
Roof Upblast - Belt Drive
Size-300: CUBE • S-CUBE
50 2.5
600 RPM
(1270) HP
5
Density 0.075 lb/ft3
RVE
hp
2.0
CU
3
hp
EM
Static Pressure in. wg
ST
Static Pressure Pa
1-
400
2
*36
1/
hp
SY
90
hp
1.5
5
(914)
hp
H IS
29
79
3/
1/
(737)
OF
5
4
2
hp
hp
FT
1.0
LE
68
5
1/
200
E
3
TH
hp
TO
57
13/4 (44)
5
0.5
CT
LE
40
46
E
5
S
(1016) N OT
35
DO
5
0 0.0
0 3 6 9 12 15
cfm X 1000
0 5 10 15 20 25
3
m /hr X 1000
CUBE • S-CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 30 x 30 (762 x 762) depending on motor. ^Weight shown is largest
Roof Opening = 321/2 x 321/2 (826 x 826) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.080 (2.0) information and image of each model, please see
Motor Cover Thickness = 0.051 (1.3) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 313 lb (142 kg)
37
Roof Upblast - Belt Drive
Size-300HP: CUBE
50 3.0
700 RPM
(1270)
HP
5
hp
3
VE
Density 0.075 lb/ft3
hp
2.5
UR
600
MC
1-
1/
Static Pressure in. wg
STE
2
2
500
hp
2.0
Static Pressure Pa
hp
10
*36
SY
45
(914)
IS
1
3/
94
29
TH
400
hp
4
0
1.5
hp
OF
(737)
82
FT
1/
300
0
2
LE
hp
1.0
70
TH
0
200
TO
13/4 (44)
58
CT
0
0.5
LE
40 100
SE
46
(1016) T
NO
0
DO
0 0.0
0 2 4 6 8 10 12
cfm X 1000
0 2 4 6 8 10 12 14 16 18 20
3
m /hr X 1000
CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 30 x 30 (762 x 762) depending on motor. ^Weight shown is largest
Roof Opening = 321/2 x 321/2 (826 x 826) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.080 (2.0) information and image of each model, please see
Motor Cover Thickness = 0.051 (1.3) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 313 lb (142 kg)
38
Roof Upblast - Belt Drive
Size-300XP: CUBE
50 5
1200
RVE
RPM
(1270)
5
3
HP
hp
hp
M CU
2
Density 0.075 lb/ft3
hp
1000 4
YSTE
1-
Static Pressure in. wg
1/
16
HIS S
2
Static Pressure Pa
90
*36 800
hp
3 15
(914)
OF T
10
29
1
hp
600
T
(737) 13
LEF
30
3/
4
2
HE
hp
11
50
OT
400
T
97
13/4 (44)
CT
0
1
LE
40 200 79
SE
0
(1016)
T
NO
O
0 0 D
0 1 2 3 4 5 6 7 8 9
cfm X 1000
0 5 10 15
3
m /hr X 1000
CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 30 x 30 (762 x 762) depending on motor. ^Weight shown is largest
Roof Opening = 321/2 x 321/2 (826 x 826) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.080 (2.0) information and image of each model, please see
Motor Cover Thickness = 0.051 (1.3) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 313 lb (142 kg)
39
Roof Upblast - Belt Drive
Size-360: CUBE • S-CUBE
585⁄8 2.0
(1489) RPM
HP
RVE
5
Density 0.075 lb/ft3
hp
hp
hp
400
CU
1.5
EM
Static Pressure in. wg
1-
1
1/
ST
Static Pressure Pa
hp
2
*391⁄8
hp
SY
300
(994)
HIS
293⁄8
69
3/
T
1.0
0
(746)
OF
hp
62
FT
200
0
1/
LE
2
hp
54
TH
0
0.5
TO
13/4 (44)
46
100
0
EC
46
EL
38
S
T
0
(1168) NO
30
DO
0
0 0.0
0 4 8 12 16 20
cfm X 1000
0 10 20 30
3
m /hr X 1000
CUBE • S-CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 36 x 36 (914 x 914) depending on motor. ^Weight shown is largest
Roof Opening = 381/2 x 381/2 (978 x 978) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.080 (2.0) information and image of each model, please see
Motor Cover Thickness = 0.064 (1.6) pages 82-87.
Curb Cap Thickness = 0.080 (2.0)
^Approximate Unit Weight = 440 lb (200 kg)
40
Roof Upblast - Belt Drive
Size-360HP: CUBE only
3.0
585⁄8
700 RPM
(1489)
7-
HP
1/
RVE
2
5
Density 0.075 lb/ft3
hp
hp
2.5
600
CU
TEM
Static Pressure in. wg
3
hp
hp
500 2.0
Static Pressure Pa
YS
86
*391⁄8
5
S
1-
IS
(994)
78
1/
TH
400
293⁄8
0
1.5
hp
OF
(746)
69
T
0
300
EF
1
hp
EL
1.0
60
TH
0
200
TO
13/4 (44)
51
T
0
EC
0.5
EL
46 100 S
42
T
NO
0
(1168)
DO
0 0.0
0 3 6 9 12 15 18
cfm X 1000
0 5 10 15 20 25 30
3
m /hr X 1000
CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 36 x 36 (914 x 914) depending on motor. ^Weight shown is largest
Roof Opening = 381/2 x 381/2 (978 x 978) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.080 (2.0) information and image of each model, please see
Motor Cover Thickness = 0.064 (1.6) page 82-87.
Curb Cap Thickness = 0.080 (2.0)
^Approximate Unit Weight = 440 lb (200 kg)
41
Roof Upblast - Belt Drive
Size-360XP: CUBE only
585⁄8 6
E
5
RPM
7-
(1489) 1400
CURV
hp
1/
HP
2
hp
5 Density 0.075 lb/ft3
M
1200
hp
YSTE
Static Pressure in. wg
14
S
1000 4 90
Static Pressure Pa
THIS
*391⁄8
hp
(994) 13
40
T OF
293⁄8 800
1-
3
1/
(746)
LE F
2
11
hp
80
600
THE
1
10
hp
2 20
TO
400
13/4 (44)
CT
86
0
LE
1
46
SE
200 70
0
T
(1168)
NO
0 0 DO
0 2 4 6 8 10 12
cfm X 1000
0 5 10 15 20
3
m /hr X 1000
CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 36 x 36 (914 x 914) depending on motor. ^Weight shown is largest
Roof Opening = 381/2 x 381/2 (978 x 978) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.080 (2.0) information and image of each model, please see
Motor Cover Thickness = 0.064 (1.6) page 82-87.
Curb Cap Thickness = 0.080 (2.0)
^Approximate Unit Weight = 440 lb (200 kg)
42
Roof Upblast - Belt Drive
Size-420: CUBE • S-CUBE
653⁄8 2.0
7- RPM
(1661) 1/
E
5 2
URV
2 hp hp HP
hp 3
hp Density 0.075 lb/ft3
C
400
EM
1.5
T
Static Pressure in. wg
SYS
1-
1/
Static Pressure Pa
*443⁄4 2
hp
HIS
300
(1137)
FT
35 ⁄4
1 60
1.0 0
TO
(895) 1
hp 52
EF
0
200
EL
44
1/ 3/ 5
TH
2 4
hp hp
O
37
TT
0.5
13/4 (44) 0
C
100
LE
29
52
SE
5
T
(1321) 22
O
N 0
DO
0 0.0
0 4 8 12 16 20 24 28
cfm X 1000
0 10 20 30 40
3
m /hr X 1000
CUBE • S-CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 42 x 42 (1067 x 1067) depending on motor. ^Weight shown is largest
Roof Opening = 441/2 x 441/2 (1130 x 1130) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.080 (2.0) information and image of each model, please see
Motor Cover Thickness = 0.064 (1.6) pages 82-87.
Curb Cap Thickness = 0.100 (2.5)
^Approximate Unit Weight = 578 lb (262 kg)
43
Roof Upblast - Belt Drive
Size-480: CUBE • S-CUBE
743⁄16 1.8
RPM
(1884) 7- HP
400 1.6 1/
RVE
2 Density 0.075 lb/ft3
3 5 hp
2 hp hp
CU
350 1.4 hp
EM
Static Pressure in. wg
ST
300 1.2
Static Pressure Pa
1-
*481⁄8
SY
1 1/
hp 2
hp
HIS
(1222) 250 1.0
49
36
0
OF
(914) 200 0.8
3/
4
42
hp
EF
0
EL
150 0.6 1/
TH
36
2
hp
0
TO
13/4 (44) 100 0.4
C T
30
LE
0
58
SE
50 0.2 T
NO
24
(1473)
0
DO
18
0
0 0.0
0 5 10 15 20 25 30
cfm X 1000
0 5 10 15 20 25 30 35 40 45 50
3
m /hr X 1000
CUBE • S-CUBE
All dimensions in inches (millimeters). *May be greater
Damper Size = 48 x 48 (1219 x 1219) depending on motor. ^Weight shown is largest
Roof Opening = 501/2 x 501/2 (1283 x 1283) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.080 (2.0) information and image of each model, please see
Motor Cover Thickness = 0.064 (1.6) pages 82-87.
Curb Cap Thickness = 0.100 (2.5)
^Approximate Unit Weight = 675 lb (306 kg)
44
Roof Upblast - Direct Drive
Sizes-060 and 065: CUE
90
0.35
80
Static Pressure Pa
131/2 70 06
0- 06
(343) 0.25 D 5-
11 ⁄8
3 60 D
(289) 50 0.20 06
0- 06
G 5-
40 G
0.15 06
06 5-
E
30 0-
13/4 (44) E
0.10
20
17
(432) 0.05
10
0 0.00
0 40 80 120 160 200 240 280
cfm
0 50 100 150 200 250 300 350 400 450
3
m /hr
CUE
All dimensions in inches (millimeters). *May be greater
Damper Size = 8 x 8 (203 x 203) depending on motor. ^Weight shown is largest
Roof Opening = 101/2 x 101/2 (267 x 267) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.051 (1.3) pages 82-87.
Curb Cap Thickness = 0.051 (1.3)
^Approximate Unit Weight = 29 lb (13 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
45
Roof Upblast - Direct Drive
Sizes-070 and 075: CUE
183⁄8 0.5
120
(467) RPM
Density 0.075 lb/ft3
100 0.4
07
0-
Static Pressure Pa
131/2 80
0.3 07
(343) 5-
113⁄8 07 D
60 0-G
(289)
07
0.2 5-
G
07
40 0-E
07
13/4 (44) 5-
E
0.1
17 20
(432)
0 0.0
0 50 100 150 200 250 300 350 400 450
cfm
0 200 400 600
3
m /hr
CUE
All dimensions in inches (millimeters). *May be greater
Damper Size = 8 x 8 (203 x 203) depending on motor. ^Weight shown is largest
Roof Opening = 101/2 x 101/2 (267 x 267) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.051 (1.3) pages 82-87.
Curb Cap Thickness = 0.051 (1.3)
^Approximate Unit Weight = 29 lb (13 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
46
Roof Upblast - Direct Drive
Sizes-080 and 085: CUE
21 0.7
RPM
(533) 160 Density 0.075 lb/ft3
0.6
140 08
5-
08 D
0.5 0-
Static Pressure Pa
133⁄8
(340) 100 0.4 08
111/2 08 5-
G
0-
(292) G
80
0.3
0
60 08 85-E
0-E
0.2
13/4 (44) 40
19 0.1
(483) 20
0 0.0
0 100 200 300 400 500 600
cfm
0 200 400 600 800 1000
3
m /hr
CUE
All dimensions in inches (millimeters). *May be greater
Damper Size = 10 x 10 (254 x 254) depending on motor. ^Weight shown is largest
Roof Opening = 121/2 x 121/2 (318 x 318) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.051 (1.3) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 40 lb (18 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
47
Roof Upblast - Direct Drive
Size-090: CUE
21 0.8
RPM
(533) 180
0.7 Density 0.075 lb/ft3
160
0.6
Static Pressure Pa
D
133⁄8 120
0.5
(340)
111/2 100 0.4 09
0-
(292) G
80
0.3
09
0-
60 E
13/4 (44) 0.2
40
19
0.1
(483) 20
0 0.0
0 100 200 300 400 500 600 700 800 900
cfm
0 200 400 600 800 1000 1200 1400
3
m /hr
CUE
All dimensions in inches (millimeters). *May be greater
Damper Size = 10 x 10 (254 x 254) depending on motor. ^Weight shown is largest
Roof Opening = 121/2 x 121/2 (318 x 318) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.051 (1.3) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 40 lb (18 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
48
Roof Upblast - Direct Drive
Size-095: CUE
21 0.8
RPM
(533) 180 Density 0.075 lb/ft3
0.7
160
0.6
Static Pressure Pa
151⁄4 0.5
09
120
5-
(387)
D
13 ⁄8
3
100 0.4
(340) 09
5-
80 G
0.3
60 09
5-
0.2 E
13/4 (44)
40
19 0.1
(483) 20
0 0.0
0 200 400 600 800 1000 1200
cfm
0 200 400 600 800 1000 1200 1400 1600 1800 2000
3
m /hr
CUE
All dimensions in inches (millimeters). *May be greater
Damper Size = 10 x 10 (254 x 254) depending on motor. ^Weight shown is largest
Roof Opening = 121/2 x 121/2 (318 x 318) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.051 (1.3) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 40 lb (18 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
49
Roof Upblast - Direct Drive
Size-098 and 101: CUE
247⁄8 1.4
RPM
(632) Density 0.075 lb/ft3
300 1.2
250 1.0
Static Pressure Pa
*28 ⁄4
1
10
1-
(718) 200 0.8
A
173⁄8
(441)
150 0.6
cfm
0 500 1000 1500 2000 2500
3
m /hr
CUE
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Roof Opening = 141/2 x 141/2 (368 x 368) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.040 (1.0) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 53 lb (24 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
50
Roof Upblast - Direct Drive
Sizes-121 and 131: CUE
1.8
247/8
RPM
(632)
400 1.6 Density 0.075 lb/ft3
350 1.4
Static Pressure Pa
12
*281/4
1-
A
(718)
13
250 1.0
1-
173/8
A
(441) 200 0.8
150 0.6
12
13/4 (44)
1-
100 0.4
13
12
19
1-
1-
50 0.2
B
C
(483)
13
1-
C
0 0.0
0 400 800 1200 1600 2000 2400
cfm
0 500 1000 1500 2000 2500 3000 3500 4000
3
m /hr
CUE
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Roof Opening = 141/2 x 141/2 (368 x 368) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.040 (1.0) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 64 lb (29 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
51
Roof Upblast - Direct Drive
Sizes-141, 141HP, 161 and 161HP:
CUE
287⁄8 2.8
(733) RPM
Density 0.075 lb/ft3
600 2.4
161
HP
2.0
-A
Static Pressure Pa
16
*29 ⁄4
3
1-
A
14
(756) 400 1.6
14
1H
19 ⁄8
3
1-
P-
A
A
(492)
1.2
16
141-B
16
1H
200 0.8
1-
P-
B
13/4 (44)
B
141-C
22 0.4
16
(559)
1-
C
0 0.0
0 1000 2000 3000 4000 5000
cfm
0 2000 4000 6000 8000
3
m /hr
CUE
All dimensions in inches (millimeters). *May be greater
Damper Size = 16 x 16 (406 x 406) depending on motor. ^Weight shown is largest
Roof Opening = 181/2 x 181/2 (470 x 470) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.051 (1.3) information and image of each model, please see
Motor Cover Thickness = 0.040 (1.0) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 90 lb (41 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
52
Roof Upblast - Direct Drive
Sizes-180, 180HP and 200:
CUE
353⁄8 3.5
RPM
(905) 800 Density 0.075 lb/ft3
3.0
700
18
2.5
0H
Static Pressure Pa
*285⁄8
P-
A
(524) 500 2.0
21
(533)
400
1.5
18 200
0-B -B
300
1.0
13/4 (44)
200 200
18 -C
30 0-C
0.5
(762) 100
0 0.0
0 1000 2000 3000 4000 5000 6000 7000
cfm
0 2000 4000 6000 8000 10000
3
m /hr
CUE
All dimensions in inches (millimeters). *May be greater
Damper Size = 18 x 18 (457 x 457)
depending on motor. ^Weight shown is largest
Roof Opening = 201/2 x 201/2 (521 x 521) cataloged Open Drip-Proof motor. For specification
Windband Thickness = 0.064 (1.6) information and image of each model, please see
Motor Cover Thickness = 0.040 (1.0) pages 82-87.
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 142 lb (64 kg)
CFM 4850 4732 4613 4493 4353 4215 4078 3740 3265 2695
180HP-A 2 1725 BHP 1.77 1.84 1.92 1.99 2.06 2.12 2.18 2.23 2.25 2.16
Sones 30 29 28 27 26 26 25 24 23 21
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
53
Sidewall - Belt Drive
CWB-098
*281⁄4 1.0
(718) 1/4 RPM
E
hp
V
HP
CUR
Density 0.075 lb/ft3
200 0.8
EM
YST
Static Pressure in. wg
Static Pressure Pa
IS S
17
25
150 0.6
F TH
TO
193⁄4 15
10
247⁄8
L EF
(502)
16 ⁄8
7
(632) 100 0.4
12
HE
(429) 95
OT
TT
10
80
C
50 0.2
LE
86
SE
5
OT
N 65
DO 0
0 0.0
0 200 400 600 800 1000 1200
cfm
0 500 1000 1500 2000
3
m /hr
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Damper Frame Size = 14 x 14 (356 x 356) cataloged Open Drip-Proof motor. For specification
Wall Opening = 121/2 x 121/2 (318 x 318) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 58 lb (26 kg)
54
Sidewall - Belt Drive
CWB-101
*281⁄4 1.4
(718) 1/ RPM
1/ 3
RVE
4 hp HP
300 1.2 hp
Density 0.075 lb/ft3
CU
TEM
250 1.0
YS
Static Pressure Pa
IS S
18
20
TH
200 0.8
OF
16
193⁄4
20
T
247⁄8
EF
(502) 150 0.6
167⁄8
EL
(632)
14
30
(429)
TH
TO
100 0.4
12
40
CT
10
LE
50
SE
50 0.2
86
NO
T
0
DO
0 0.0
0 200 400 600 800 1000 1200 1400 1600
cfm
0 500 1000 1500 2000 2500
3
m /hr
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Damper Frame Size = 14 x 14 (356 x 356) cataloged Open Drip-Proof motor. For specification
Wall Opening = 121/2 x 121/2 (318 x 318) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 58 lb (26 kg)
55
Sidewall - Belt Drive
CWB-101HP
*281⁄4 3.0
E
(718) 700 RPM
CURV
1/2 h HP
p
2.5 Density 0.075 lb/ft3
M
600 1/3 h
YSTE
p
HIS S
500 2.0 25
Static Pressure Pa
1/4 h
p 80
OF T
400 23
1.5 40
193⁄4
EFT
(502) 24 ⁄8
7
20
80
HE L
167⁄8 (632) 300
(429) 1.0 18
OT
20
TT
200
15
L EC
60
0.5
13
SE
100 00
T
NO
O
0 0.0 D
0 200 400 600 800 1000 1200
cfm
0 500 1000 1500 2000
3
m /hr
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Damper Frame Size = 14 x 14 (356 x 356) cataloged Open Drip-Proof motor. For specification
Wall Opening = 121/2 x 121/2 (318 x 318) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 58 lb (26 kg)
56
Sidewall - Belt Drive
CWB-121
*281⁄4 1.8
(718) RPM
RVE
400 1.6 HP
1/
Density 0.075 lb/ft3
2h
CU
p
1/
350 1.4
3h
TEM
1/
4h
p
Static Pressure in. wg
YS
p
300 1.2
Static Pressure Pa
IS S
17
TH
250 1.0 25
OF
19 ⁄4
3
FT
247⁄8 200 0.8 15
(502)
LE
00
167⁄8 (632)
E
TH
(429) 150 0.6 13
00
TO
11
T
100 0.4
C
00
LE
SE
T 90
50 0.2 NO 68
0
DO 5
0 0.0
0 300 600 900 1200 1500 1800 2100
cfm
0 500 1000 1500 2000 2500 3000 3500
3
m /hr
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Damper Frame Size = 14 x 14 (356 x 356) cataloged Open Drip-Proof motor. For specification
Wall Opening = 121/2 x 121/2 (318 x 318) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 66 lb (30 kg)
57
Sidewall - Belt Drive
CWB-131
*281⁄4 1.6
(718) RPM
1/
350 1.4 HP
2
E
hp
URV
Density 0.075 lb/ft3
1/
3
1/
MC
hp
4
300 1.2
hp
STE
Static Pressure in. wg
250 1.0
SY
16
Static Pressure Pa
45
HI S
14
50
FT
193⁄4 200 0.8
TO
(502) 24 ⁄8
7
12
167⁄8
EF
(632) 150 0.6 50
EL
(429)
10
TH
100 50
0.4
TO
CT
85
LE
0
50 0.2
SE
T 65
NO 0
DO
0 0.0
0 300 600 900 1200 1500 1800 2100 2400
cfm
0 500 1000 1500 2000 2500 3000 3500 4000
3
m /hr
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Damper Frame Size = 14 x 14 (356 x 356) cataloged Open Drip-Proof motor. For specification
Wall Opening = 121/2 x 121/2 (318 x 318) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 66 lb (30 kg)
58
Sidewall - Belt Drive
CWB-141
*293⁄4 2.0
(756) RPM
1
hp
VE
HP
CUR
Density 0.075 lb/ft3
1/
2
400
3/
hp
4
T EM
1.5
hp
1/
Static Pressure in. wg
17
3
25
SY S
1/
hp
Static Pressure Pa
4
hp
300
HI S
15
FT
10
221⁄8 1.0
TO
(562) 28 ⁄8
7
EF
193⁄8 (733) 200 12
EL
(492) 80
TH
TO
0.5 10
50
CT
100
LE
82
SE
T 0
NO 59
DO 0
0 0.0
0 400 800 1200 1600 2000 2400 2800 3200
cfm
0 1000 2000 3000 4000 5000
3
m /hr
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 15 x 15 (381 x 381) depending on motor. ^Weight shown is largest
Damper Frame Size = 17 x 17 (432 x 432) cataloged Open Drip-Proof motor. For specification
Wall Opening = 151/2 x 151/2 (394 x 394) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 84 lb (38 kg)
59
Sidewall - Belt Drive
CWB-141HP
*293⁄4 3.0
3/
1/ 4 RPM
(756) 700 2 hp
E
hp
URV
1/ HP
3
hp
2.5 Density 0.075 lb/ft3
MC
600
STE
1/ 21
S SY
500 2.0 hp
Static Pressure Pa
18
THI
60
400
OF
22 ⁄8
1 1.5
16
T
287⁄8 20
LEF
(562)
193⁄8 (733) 300
HE
(492) 1.0 13
T
80
TO
200
11
CT
40
LE
0.5
89
SE
100
5
OT
N
DO
0 0.0
0 300 600 900 1200 1500 1800
cfm
0 500 1000 1500 2000 2500 3000
3
m /hr
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 15 x 15 (381 x 381) depending on motor. ^Weight shown is largest
Damper Frame Size = 17 x 17 (432 x 432) cataloged Open Drip-Proof motor. For specification
Wall Opening = 151/2 x 151/2 (394 x 394) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 84 lb (38 kg)
60
Sidewall - Belt Drive
CWB-161
*293⁄4 1.8
(756) RPM
400 1.6 HP
3/
1
4
RVE
Density 0.075 lb/ft3
hp
hp
1/
CU
350 1.4
2
hp
1/
EM
3
Static Pressure in. wg
13
hp
300 1.2
ST
1/
Static Pressure Pa
90
SY
hp
12
IS
250 1.0 50
TH
221⁄8 11
OF
(562) 287⁄8 200 0.8 20
FT
193⁄8 (733) 99
LE
(492) 150 0.6 0
E
TH
86
TO
0
100 0.4
T
73
EC
0
EL
50 0.2 S
T
NO
DO
0 0.0
0 500 1000 1500 2000 2500 3000 3500 4000
cfm
0 1000 2000 3000 4000 5000 6000
3
m /hr
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 15 x 15 (381 x 381) depending on motor. ^Weight shown is largest
Damper Frame Size = 17 x 17 (432 x 432) cataloged Open Drip-Proof motor. For specification
Wall Opening = 151/2 x 151/2 (394 x 394) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 87 lb (39 kg)
61
Sidewall - Belt Drive
CWB-161HP
*293⁄4 2.5
(756) 600 3/ RPM
4
hp HP
RVE
1/ 1
hp Density 0.075 lb/ft3
2
CU
500 2.0 hp
1/
TEM
3
hp
16
YS
90
1/
Static Pressure Pa
400 4
IS S
1.5 hp 15
10
TH
13
OF
22 ⁄8
1
300 40
287⁄8
T
(562)
EF
19 ⁄8
3
(733) 1.0 11
EL
70
(492)
TH
200
10
TO
00
CT
0.5 82
LE
100 5
SE
NO
T
DO
0 0.0
0 500 1000 1500 2000 2500 3000
cfm
0 1000 2000 3000 4000 5000
3
m /hr
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 15 x 15 (381 x 381) depending on motor. ^Weight shown is largest
Damper Frame Size = 17 x 17 (432 x 432) cataloged Open Drip-Proof motor. For specification
Wall Opening = 151/2 x 151/2 (394 x 394) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 85 lb (39 kg)
62
Sidewall - Belt Drive
CWB-180
*285⁄8 2.5
600 RPM
(727)
1-
HP
2
1/
RVE
hp
Density 0.075 lb/ft3
2
hp
CU
2.0
1
hp
M
Static Pressure in. wg
STE
14
Static Pressure Pa
1/
3/
400 95
SY
2
4
1.5
hp
hp
HE
13
FT
10
1/
1/ p
273⁄4
TO
4
3
h
35 ⁄8
hp
3
(705)
EF
1.0 11
25 (899) 40
EL
(635) 200
TH
97
TO
0
CT
0.5 80
LE
0
SE
63
NO
0
DO
0 0.0
0 1 2 3 4 5 6
cfm X 1000
0 2 4 6 8 10
3
m /hr X 1000
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 17 x 17 (432 x 432)
depending on motor. ^Weight shown is largest
Damper Frame Size = 19 x 19 (483 x 483) cataloged Open Drip-Proof motor. For specification
Wall Opening = 171/2 x 171/2 (445 x 445) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 126 lb (57 kg)
63
Sidewall - Belt Drive
CWB-180HP
*285⁄8 3.5
(727) 2 RPM
800 hp
HP
RVE
1-
3.0 1/
2
hp Density 0.075 lb/ft3
CU
700 1
hp
TEM
2.5
S
16
Static Pressure Pa
SY
1/ 3/ 85
2 4
hp hp
HIS
500 2.0
15
FT
1/ 00
273⁄4 3
TO
400 hp
(705) 35 ⁄8
3
1.5 13
EF
25 1/ 25
(899)
EL
4
(635) 300 hp
TH
11
1.0 50
TO
200
T
97
C
5
LE
SE
0.5
100 T 79
NO 5
DO
0 0.0
0 700 1400 2100 2800 3500 4200 4900
cfm
0 1000 2000 3000 4000 5000 6000 7000 8000
3
m /hr
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 17 x 17 (432 x 432) depending on motor. ^Weight shown is largest
Damper Frame Size = 19 x 19 (483 x 483) cataloged Open Drip-Proof motor. For specification
Wall Opening = 171/2 x 171/2 (445 x 445) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 126 lb (57 kg)
64
Sidewall - Belt Drive
CWB-200
*285⁄8 2.0
(727)
1-
RPM
E
URV
1/
2
HP
hp
hp
Density 0.075 lb/ft3
C
3/
1
400
TEM
hp
hp
1.5
12
SYS
Static Pressure in. wg
10
Static Pressure Pa
1/
HIS
2
1/
300
hp
3
T
10
hp
60
OF
273⁄4 1.0
FT
1/
35 ⁄8
3
LE
(705) 92
hp
25 200 0
(899)
HE
(635)
OT
78
0
TT
0.5
C
100
LE
64
0
SE
50
T
O
N 0
DO
0 0.0
0 1 2 3 4 5 6 7
cfm X 1000
0 2 4 6 8 10
3
m /hr X 1000
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 17 x 17 (432 x 432) depending on motor. ^Weight shown is largest
Damper Frame Size = 19 x 19 (483 x 483) cataloged Open Drip-Proof motor. For specification
Wall Opening = 171/2 x 171/2 (445 x 445) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 142 lb (64 kg)
65
Sidewall - Belt Drive
CWB-200HP
*285⁄8 3.0
(727) 700 RPM
2 HP
hp
E
Density 0.075 lb/ft3
RV
2.5 1-
600 1
CU
hp 1/
2
hp
EM
Static Pressure in. wg
3/
ST
500 2.0
Static Pressure Pa
4
hp
SY
HIS
400 1/ 14
00
FT
2
273⁄4 1.5 hp 12
TO
35 ⁄8
3 70
(705)
25
EF
(899) 300 11
35
EL
(635) 1.0
TH
10
200 05
TO
87
T
5
EC
0.5
EL
100 S 74
T 0
NO
DO
0 0.0
0 1 2 3 4 5 6
cfm X 1000
0 2 4 6 8 10
3
m /hr X 1000
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 17 x 17 (432 x 432) depending on motor. ^Weight shown is largest
Damper Frame Size = 19 x 19 (483 x 483) cataloged Open Drip-Proof motor. For specification
Wall Opening = 171/2 x 171/2 (445 x 445) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 142 lb (64 kg)
66
Sidewall - Belt Drive
CWB-220
*337⁄8 2.0
(860) RPM
1-
2
1/
HP
hp
2
hp
Density 0.075 lb/ft3
E
RV
400
3/
CU
4
1.5
1
hp
hp
Static Pressure in. wg
EM
Static Pressure Pa
ST
1/
SY
300
2
hp
HIS
31 ⁄4
95
1 1.0
FT
1/ 1/4
5
4225⁄32
3
(794)
TO
hp hp
28 ⁄8
3
200
85
(1087)
0
LE
(721)
75
E
TH
0
0.5
TO
65
100
0
T
EC
L
55
SE
0
OT
ON
45
D
0
0 0.0
0 1 2 3 4 5 6 7 8
cfm X 1000
0 2 4 6 8 10 12
3
m /hr X 1000
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 20 x 20 (508 x 508) depending on motor. ^Weight shown is largest
Damper Frame Size = 22 x 22 (559 x 559) cataloged Open Drip-Proof motor. For specification
Wall Opening = 201/2 x 201/2 (521 x 521) information and image of model, please see page 84.
Windband Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.051 (1.3)
^Approximate Unit Weight = 174 lb (79 kg)
67
Sidewall - Belt Drive
CWB-220HP
*337⁄8 2.5
2
600 hp RPM
(860)
VE
HP
CUR
1-
1/ Density 0.075 lb/ft3
2
2.0 hp
EM
3/ 1
4
YST
hp hp
Static Pressure Pa
SS
400 1/ 85
1.5 2
THI
hp 10
00
OF
311⁄4 91
0
FT
(794) 4225⁄32
LE
82
28 ⁄8
3
(1087) 1.0 5
E
TH
(721) 200 74
0
O
TT
65
0
EC
0.5
L
SE
T
O
N
DO
0 0.0
0 1 2 3 4 5 6 7
cfm X 1000
0 2 4 6 8 10
3
m /hr X 1000
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 20 x 20 (508 x 508) depending on motor. ^Weight shown is largest
Damper Frame Size = 22 x 22 (559 x 559) cataloged Open Drip-Proof motor. For specification
Wall Opening = 201/2 x 201/2 (521 x 521) information and image of model, please see page 84.
Windband Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.051 (1.3)
^Approximate Unit Weight = 174 lb (79 kg)
68
Sidewall - Belt Drive
CWB-240
*337⁄8 1.6
2
(860) hp RPM
1
VE
350 1.4 3/ hp HP
4
CUR
hp Density 0.075 lb/ft3
1-
1/
2
EM
300 1.2 hp
1/
T
2
SYS
hp
Static Pressure Pa
250 1.0
93
HIS
0
1/
T
3
82
hp
OF
311⁄4 200 0.8
0
42 ⁄32 72
FT
25
(794) 1/ 0
283⁄8
LE
(1087) 150 0.6 4
hp
E
(721) 62
TH
0
O
100 0.4
T
CT
52
0
LE
41
SE
50 0.2 0
T
NO
DO
0 0.0
0 1 2 3 4 5 6 7 8 9
cfm X 1000
0 2 4 6 8 10 12 14
3
m /hr X 1000
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 20 x 20 (508 x 508) depending on motor. ^Weight shown is largest
Damper Frame Size = 22 x 22 (559 x 559) cataloged Open Drip-Proof motor. For specification
Wall Opening = 201/2 x 201/2 (521 x 521) information and image of model, please see page 84.
Windband Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.051 (1.3)
^Approximate Unit Weight = 175 lb (79 kg)
69
Sidewall - Belt Drive
CWB-240HP
*337⁄8 2.5
600 RPM
(860)
1-
2
1/
HP
hp
VE
2
hp
Density 0.075 lb/ft3
UR
2.0
MC
1
hp
STE
Static Pressure in. wg
Static Pressure Pa
SY
400
3/
10
4
1.5
HIS
70
hp
FT
98
1/
31 ⁄4 0
2
1
TO
hp
4225⁄32 90
(794) 0
EF
283⁄8 (1087) 1.0
EL
81
(721) 0
TH
200
72
TO
0
CT
0.5 63
5
LE
SE
T
NO
DO
0 0.0
0 1 2 3 4 5 6 7
cfm X 1000
0 2 4 6 8 10
3
m /hr X 1000
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 20 x 20 (508 x 508) depending on motor. ^Weight shown is largest
Damper Frame Size = 22 x 22 (559 x 559) cataloged Open Drip-Proof motor. For specification
Wall Opening = 201/2 x 201/2 (521 x 521) information and image of model, please see page 84.
Windband Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.051 (1.3)
^Approximate Unit Weight = 175 lb (79 kg)
70
Sidewall - Belt Drive
CWB-300
*36 1.8
(914) RPM
VE
400 1.6 HP
3
CUR
1-
Density 0.075 lb/ft3
hp
hp
1/
2
350 1.4
hp
TEM
Static Pressure in. wg
SYS
300 1.2
Static Pressure Pa
3/
hp
4
hp
IS
76
TH
250 1.0
5
OF
1/
383⁄8
68
50
hp
200
T
(975) 0.8
0
EF
3527⁄32 (1270)
EL
1/
60
(910)
0
150 0.6
TH
hp
52
TO
0
100 0.4
CT
44
LE
0
SE
50 0.2 T
35
NO
5
DO
0 0.0
0 2 4 6 8 10 12 14
cfm X 1000
0 2 4 6 8 10 12 14 16 18 20 22
3
m /hr X 1000
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 25 x 25 (635 x 635)
depending on motor. ^Weight shown is largest
Damper Frame Size = 27 x 27 (686 x 686) cataloged Open Drip-Proof motor. For specification
Wall Opening = 251/2 x 251/2 (648 x 648) information and image of model, please see page 84.
Windband Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.051 (1.3)
^Approximate Unit Weight = 313 lb (142 kg)
71
Sidewall - Belt Drive
CWB-300HP
*36 2.5
600 RPM
(914)
3
HP
hp
E
Density 0.075 lb/ft3
RV
1-
CU
2.0
1/
2
hp
2
hp
EM
Static Pressure in. wg
ST
Static Pressure Pa
1
400
SY
hp
88
1.5 5
HIS
1/
FT
80
3/
2
38 ⁄8
3 0
4
hp
TO
hp
(975) 50 71
EF
35 ⁄32
27
(1270) 1.0 5
EL
(910) 63
TH
200 0
TO
54
T
5
EC
0.5
46
EL
S 0
T
NO
DO
0 0.0
0 2 4 6 8 10
cfm X 1000
0 5 10 15
3
m /hr X 1000
CWB
All dimensions in inches (millimeters). *May be greater
Damper Size = 25 x 25 (635 x 635) depending on motor. ^Weight shown is largest
Damper Frame Size = 27 x 27 (686 x 686) cataloged Open Drip-Proof motor. For specification
Wall Opening = 251/2 x 251/2 (648 x 648) information and image of model, please see page 84.
Windband Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.051 (1.3)
^Approximate Unit Weight = 313 lb (142 kg)
72
Sidewall - Direct Drive
CW-060 and CW- 065
90
0.35
80
Static Pressure Pa
70 06
0- 06
0.25 D 5-
60 D
143/4
(375) 18 ⁄8
3
50 0.20 06
0- 06
113/4 (467) G 5-
40 G
(298) 0.15 06
06 5-
E
30 0-
E
0.10
20
0.05
10
0 0.00
0 40 80 120 160 200 240 280
cfm
0 50 100 150 200 250 300 350 400 450
3
m /hr
CW
All dimensions in inches (millimeters). *May be greater
Damper Size = 8 x 8 (203 x 203) depending on motor. ^Weight shown is largest
Damper Frame Size = 10 x 10 (254 x 254) cataloged Open Drip-Proof motor. For specification
Wall Opening = 201/2 x 201/2 (521 x 521) information and image of model, please see page 84.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.051 (1.3)
^Approximate Unit Weight = 26 lb (12kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
73
Sidewall - Direct Drive
CW-070 and CW-075
131⁄2 0.5
120
(343) RPM
Density 0.075 lb/ft3
100 0.4
07
0-
Static Pressure Pa
80
0.3 07
5-
07 D
143/4 60 0-G
(375) 18 ⁄8
3
07
113/4 (467) 0.2 5-
G
(298) 07
0-E
40
07
5-
E
0.1
20
0 0.0
0 50 100 150 200 250 300 350 400 450
cfm
0 200 400 600
3
m /hr
CW
All dimensions in inches (millimeters). *May be greater
Damper Size = 8 x 8 (203 x 203) depending on motor. ^Weight shown is largest
Damper Frame Size = 10 x 10 (254 x 254) cataloged Open Drip-Proof motor. For specification
Wall Opening = 81/2 x 81/2 (216 x 216) information and image of model, please see page 85.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.051 (1.3)
^Approximate Unit Weight = 26 lb (12 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
74
Sidewall - Direct Drive
CW-080 and CW-085
133⁄8 0.7
(340) RPM
160 Density 0.075 lb/ft3
0.6
140 08
5-
08 D
0.5 0-
Static Pressure Pa
100 0.4 08
08 5-
G
177⁄8 0-
G
(454) 21 80
0.3
15 (533) 0
(381) 60 08 85-E
0-E
0.2
40
0.1
20
0 0.0
0 100 200 300 400 500 600
cfm
0 200 400 600 800 1000
3
m /hr
CW
All dimensions in inches (millimeters). *May be greater
Damper Size = 10 x 10 (254 x 254) depending on motor. ^Weight shown is largest
Damper Frame Size = 12 x 12 (305 x 305) cataloged Open Drip-Proof motor. For specification
Wall Opening = 101/2 x 101/2 (267 x 267) information and image of model, please see page 85.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.051 (1.3)
^Approximate Unit Weight = 40 lb (18 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
75
Sidewall - Direct Drive
CW-090
133⁄8 0.8
(340) RPM
180
0.7 Density 0.075 lb/ft3
160
0.6
Static Pressure Pa
D
0.5
120
09
177⁄8 100 0.4 0-
G
(454) 21
15 (533) 80
0.3
(381) 09
0-
60 E
0.2
40
0.1
20
0 0.0
0 100 200 300 400 500 600 700 800 900
cfm
0 200 400 600 800 1000 1200 1400
3
m /hr
CW
All dimensions in inches (millimeters). *May be greater
Damper Size = 10 x 10 (254 x 254) depending on motor. ^Weight shown is largest
Damper Frame Size = 12 x 12 (305 x 305) cataloged Open Drip-Proof motor. For specification
Wall Opening = 101/2 x 101/2 (267 x 267) information and image of model, please see page 85.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.051 (1.3)
^Approximate Unit Weight = 40 lb (18 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
76
Sidewall - Direct Drive
CW-095
151⁄4 0.8
(387) RPM
180 Density 0.075 lb/ft3
0.7
160
0.6
Static Pressure Pa
0.5
09
120
5-
D
177⁄8 100 0.4
09
(454) 21 5-
G
15 (533) 80
0.3
(381)
60 09
5-
0.2 E
40
0.1
20
0 0.0
0 200 400 600 800 1000 1200
cfm
0 200 400 600 800 1000 1200 1400 1600 1800 2000
3
m /hr
CW
All dimensions in inches (millimeters). *May be greater
Damper Size = 10 x 10 (254 x 254) depending on motor. ^Weight shown is largest
Damper Frame Size = 12 x 12 (305 x 305) cataloged Open Drip-Proof motor. For specification
Wall Opening = 101/2 x 101/2 (267 x 267) information and image of model, please see page 85.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.051 (1.3)
^Approximate Unit Weight = 40 lb (18 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
77
Sidewall - Direct Drive
CW-098 and CW-101
*281⁄4 1.4
RPM
(718)
Density 0.075 lb/ft3
300 1.2
250 1.0
Static Pressure Pa
10
1-
200 0.8
A
193⁄4
(502) 247⁄8 150 0.6
167⁄8 (632)
(429)
100 0.4 098-B 10
1-
B
101-C
098-C
50 0.2
0 0.0
0 200 400 600 800 1000 1200 1400 1600
cfm
0 500 1000 1500 2000 2500
3
m /hr
CW
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Damper Frame Size = 14 x 14 (356 x 356) cataloged Open Drip-Proof motor. For specification
Wall Opening = 121/2 x 121/2 (318 x 318) information and image of model, please see page 85.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 53 lb (24 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
78
Sidewall - Direct Drive
CW-121 and CW-131
*281⁄4 1.8
(718) RPM
400 1.6 Density 0.075 lb/ft3
350 1.4
Static Pressure Pa
12
1-
A
13
250 1.0
1-
A
193⁄4
(502) 24 ⁄8
7 200 0.8
167⁄8 (632)
(429) 150 0.6
12
1-
100 0.4
13
12
1-
1-
50 0.2
B
C
13
1-
C
0 0.0
0 400 800 1200 1600 2000 2400
cfm
0 500 1000 1500 2000 2500 3000 3500 4000
3
m /hr
CW
All dimensions in inches (millimeters). *May be greater
Damper Size = 12 x 12 (305 x 305) depending on motor. ^Weight shown is largest
Damper Frame Size = 14 x 14 (356 x 356) cataloged Open Drip-Proof motor. For specification
Wall Opening = 121/2 x 121/2 (318 x 318) information and image of model, please see page 85.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 53 lb (24 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
79
Sidewall - Direct Drive
CW-141, CW-141HP, CW-161 and
CW-161HP
*293⁄4 2.8
(756) RPM
Density 0.075 lb/ft3
600 2.4
161
HP
2.0
-A
Static Pressure Pa
16
1-
A
14
400 1.6
14
1H
1-
P-
221⁄8
A
A
(562) 287⁄8 1.2
193⁄8 (733)
16
(492) 141-B
16
1H
200 0.8
1-
P-
B
B
141-C
0.4
16
1-
C
0 0.0
0 1000 2000 3000 4000 5000
cfm
0 2000 4000 6000 8000
3
m /hr
CW
All dimensions in inches (millimeters). *May be greater
Damper Size = 15 x 15 (381 x 381) depending on motor. ^Weight shown is largest
Damper Frame Size = 17 x 17 (432 x 432) cataloged Open Drip-Proof motor. For specification
Wall Opening = 151/2 x 151/2 (394 x 394) information and image of model, please see page 85.
Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 90 lb (41 kg)
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
80
Sidewall - Direct Drive
CW-180, CW-180HP and CW-200
*285⁄8 3.5
(524) RPM
800 Density 0.075 lb/ft3
3.0
700
18
2.5
0H
Static Pressure Pa
P-
A
500 2.0
273⁄4
(705) 35 ⁄8
3
400
25 (905) 1.5
200
(635) 18 -B
300 0-B
1.0
200 200
18 -C
0-C
0.5
100
0 0.0
0 1000 2000 3000 4000 5000 6000 7000
cfm
0 2000 4000 6000 8000 10000
3
m /hr
CW
All dimensions in inches (millimeters). *May be greater
Damper Size = 17 x 17 (432 x 432)
depending on motor. ^Weight shown is largest
Damper Frame Size = 19 x 19 (483 x 483) cataloged Open Drip-Proof motor. For specification
Wall Opening = 171/2 x 171/2 (445 x 445) information and image of model, please see page 85.
Windband Thickness = 0.064 (1.6)
Motor Cover Thickness = 0.040 (1.0)
^Approximate Unit Weight = 142 lb (64 kg)
CFM 4850 4732 4613 4493 4353 4215 4078 3740 3265 2695
CW-180HP-A 2 1725 BHP 1.77 1.84 1.92 1.99 2.06 2.12 2.18 2.23 2.25 2.16
Sones 30 29 28 27 26 26 25 24 23 21
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings
shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet
hemispherical sone levels.
81
PageDrive
Belt Specifications
Header
Model CUBE
Each fan shall bear a permanently affixed
manufacturer’s engraved metal nameplate
containing the model number and individual serial
number for future identification.
A leakproof fan housing shall be constructed with a
one-piece windband with an integral rolled bead for
added strength and shall be joined to the curb cap
with a continuously welded seam.
Fans shall be model CUBE, CUBE-HP or CUBE-XP
as manufactured by Greenheck Fan Corporation in
Schofield, Wisconsin, USA.
Options and Accessories For Belt Drives
UL/cUL Listed
• Fans shall be Listed by Underwriters Laboratory
for UL/cUL 705 for all electrical components.
Spun aluminum exhaust fans shall be centrifugal • Fans shall be Listed by Underwriters Laboratory
belt-driven type. The fan wheel shall be centrifugal for UL/cUL 762 for all electrical components and
backward-inclined, constructed of aluminum and grease removal.
shall include a wheel cone carefully matched to the
inlet cone for precise running tolerances. Wheels Curb Extensions
shall be statically and dynamically balanced. The • Shall be mounted between roof curb and roof
fan housing shall be constructed of heavy-gauge mounted fans to meet NFPA requirements of 40
aluminum with a rigid internal support structure. The inches (1016 mm) minimum discharge above the
windband shall be welded to the one-piece curb cap roof when mounted on a minimum 8-inch (203 mm)
and on all sizes with UL/cUL 762. high roof curb.
Motors shall be heavy-duty ball bearing type, Grease Containers
carefully matched to the fan load, and furnished at • Drain connection shall be constructed of aluminum
the specified voltage, phase and enclosure. Drive and allow for single-point drainage of grease,
frame assembly shall be constructed of heavy- water or other residues.
gauge steel. • Grease trap shall include the drain connection and
Motors and drives shall be mounted on vibration shall be constructed from aluminum. The unit shall
isolators, out of the airstream where no steel-to- collect grease and water from the fan and extract
steel contact between rotating components and the the grease from the water for ease of grease
base shall occur. Fresh air for motor cooling shall be disposal.
drawn into the motor compartment through a ten- Easy Clean Options
square-inch tube free of discharge contaminants.
Motors and drives shall be readily accessible for • Hinge kit shall be constructed of heavy-gauge
maintenance. aluminum hinges and shall include hold-open
cables for field installation.
Precision ground and polished fan shafts shall be
mounted in permanently sealed, lubricated pillow • Non-stick wheel shall be constructed of aluminum
block ball bearings. Bearings shall be selected for a with a non-stick coating similar to Teflon® as
minimum L10 life in excess of 100,000 hours (L 50 life manufactured by DuPont™.
of 500,000 hours) at maximum cataloged operating • Clean-Out Port shall have
speed. Drives shall be sized for a minimum of 150% a hole on the outside of
of driven horsepower. Pulleys shall be of the cast the windband and a grease
type, keyed and securely attached to the wheel and repellent compression
motor shafts. rubber fit, allowing access
Motor pulleys shall be adjustable for final system to entire wheel for cleaning.
balancing. A disconnect switch shall be factory Windband Extension
installed and wired from the fan motor to a junction • Shall be constructed from
box installed within the motor compartment. A heavy-gauge aluminum
conduit chase shall be provided through the base to tube that raises the discharge an additional
the motor compartment for ease of electrical wiring. 36 inches (914 mm).
All fans shall bear the AMCA Sound and Air
Performance seal.
82
DirectHeader
Page Drive Specifications
Model CUE
83
PageDrive
Belt Specifications
Header
Model CWB
Motor pulleys shall be adjustable for final system
balancing. A disconnect switch shall be factory
installed and wired from the fan motor to a junction
box installed within the motor compartment. A
conduit chase shall be provided through the base
to the motor compartment for ease of electrical
wiring.
All fans shall bear the AMCA Sound and Air
Performance seal.
Each fan shall bear a permanently affixed
manufacturer’s engraved metal nameplate
containing the model number and individual serial
number for future identification.
A leakproof fan housing shall be constructed with
Spun aluminum exhaust fans shall be centrifugal a one-piece windband with an integral rolled bead
belt-driven type. The fan wheel shall be centrifugal for added strength. Fan shall be provided with a
backward-inclined, constructed of aluminum and mounting plate, which is attached and sealed to the
shall include a wheel cone carefully matched to the wall prior to locating the entire unit.
inlet cone for precise running tolerances. Wheels
shall be statically and dynamically balanced. The Fans shall be model CWB or CWB-HP as
fan housing shall be constructed of heavy-gauge manufactured by Greenheck Fan Corporation in
aluminum with a rigid internal support structure. Schofield, Wisconsin, USA.
The windband shall be welded to the one-piece
curb cap and on all sizes with UL/cUL 762. Options and Accessories For Belt Drives
Motors shall be heavy-duty ball bearing type, UL/cUL Listed
carefully matched to the fan load, and furnished at • Fans shall be Listed by Underwriters Laboratory
the specified voltage, phase and enclosure. Drive for UL/cUL 705 for all electrical components.
frame assembly shall be constructed of heavy-
• Fans shall be Listed by Underwriters Laboratory
gauge steel. Motors and drives shall be mounted
for UL/cUL 762 for all electrical components and
on vibration isolators, out of the airstream where no
grease removal.
steel-to-steel contact between rotating components
and the base shall occur. Fresh air for motor Easy Clean Options
cooling shall be drawn into the motor compartment • Non-stick wheel shall be constructed of aluminum
through a ten-square-inch tube free of discharge with a non-stick coating similar to Teflon® as
contaminants. Motors and drives shall be readily manufactured by DuPont™.
accessible for maintenance.
Precision ground and polished fan shafts shall be
mounted in permanently sealed, lubricated pillow
block ball bearings. Bearings shall be selected for a
minimum L10 life in excess of 100,000 hours (L 50 life
of 500,000 hours) at maximum catalogued operating
speed. Drives shall be sized for a minimum of 150%
of driven horsepower. Pulleys shall be of the cast
type, keyed and securely attached to the wheel and
motor shafts.
84
DirectHeader
Page Drive Specifications
Model CW
Each fan shall bear a permanently affixed
manufacturer’s engraved metal nameplate
containing the model number and individual serial
number for future identification.
A leakproof fan housing shall be constructed with
a one-piece windband with an integral rolled bead
for added strength. Fan shall be provided with a
mounting plate, which is to be attached and sealed
to the wall prior to locating the entire unit.
Fans shall be model CW or CW-HP as manufactured
by Greenheck Fan Corporation in Schofield,
Wisconsin, USA.
85
PageDrive
Belt Specifications
Header
Model USGF
Ultimate Steel Grease Fan
Precision ground and polished 1-inch minimum
diameter fan shafts shall be mounted in cast pillow
block lubricatable ball bearings. Bearings shall
be selected for a minimum L10 life in excess of
100,000 hours (L 50 life of 500,000 hours) at maximum
cataloged operating speed. Dual drives shall be
sized for a minimum of 150% of driven horsepower.
Pulleys shall be of the cast type, keyed and securely
attached to the wheel and motor shafts.
Motor pulleys shall be adjustable for final system
balancing. All fans shall have a dual belt and pulley
system. A NEMA-3R disconnect switch shall be
factory installed and wired from the fan motor
to a junction box installed outside the
motor compartment.
Spun steel exhaust fans shall be centrifugal All fans shall bear the AMCA Sound and Air
belt-driven type. Fan wheel shall be centrifugal Performance seal.
backward-inclined type. The wheel shall be Each fan shall bear a permanently affixed
constructed of steel and coated with a non- manufacturer’s engraved metal nameplate
stick coating similar to Teflon® as manufactured containing the model number and individual serial
by DuPont™. Wheel shall include a wheel cone number for future identification.
carefully matched to the inlet cone for precise Fans shall be Listed by Underwriters Laboratory for
running tolerances. Wheels shall be statically and UL/cUL 762 Listed for all electrical components and
dynamically balanced. grease removal.
The fan housing shall be constructed of 16-gauge Hinged base shall be constructed of heavy-gauge
galvaneal steel with a rigid internal support structure hinges and shall include hold-open cables for
and shall be leakproof. The fan housing shall be field installation.
constructed with a one-piece windband with an
integral rolled bead for added strength and shall Grease trap shall include the drain connection. The
be joined to the curb cap with a continuously unit shall collect grease and water from the fan and
welded seam. extract the grease from the water for ease of grease
disposal.
The fan windband shall have a Clean-Out Port, a
4-inch diameter hole on the outside of the fan’s Fans shall be model USGF as manufactured by
windband with a grease repellent compression Greenheck Fan Corporation in Schofield,
rubber fit, allowing access to entire wheel Wisconsin, USA.
for cleaning.
Motors shall be heavy-duty ball bearing type,
carefully matched to the fan load, and furnished
at the specified voltage, phase and enclosure.
Drive frame assembly shall be constructed of heavy-
gauge galvanized steel. Motors and drives shall be
mounted on heavy-duty true vibration isolators, out
of the airstream. Fresh air for motor cooling shall be
drawn into the motor compartment through a ten-
square-inch tube free of discharge contaminants.
Motors and drives shall be readily accessible
for maintenance.
86
PageDrive
Belt Header
Specifications
Model S-CUBE
Emergency Smoke Control
Precision ground and polished fan shafts shall be
mounted in permanently sealed, lubricated pillow
block ball bearings. Bearings shall be selected for
a minimum L10 life in excess of 100,000 hours
(L50 life of 500,000 hours) at maximum cataloged
operating speed.
Dual drives shall be sized for a minimum of 150%
of driven horsepower. Pulleys shall be of the cast
type, keyed and securely attached to the wheel and
motor shafts.
Motor pulleys shall be adjustable for final system
balancing. A NEMA-3R disconnect switch shall
be factory installed and wired from the fan motor
to a junction box installed outside the motor
compartment.
Spun aluminum exhaust fans shall be centrifugal
belt-driven type. The fan wheel shall be centrifugal All fans shall bear the AMCA Sound and Air
backward-inclined, constructed of steel and shall Performance seal.
include a wheel cone carefully matched to the Each fan shall bear a permanently affixed
inlet cone for precise running tolerances. Wheels manufacturer’s engraved metal nameplate
shall be statically and dynamically balanced. The containing the model number and individual serial
fan housing shall be constructed of heavy-gauge number for future identification.
aluminum with a rolled bead and a rigid internal
support structure. A leakproof fan housing shall Fans shall be Listed by Underwriters Laboratory
be constructed with a one-piece windband with an for UL/cUL 705 for electrical components and
integral rolled bead for added strength and shall be UL/cUL Listed for Emergency Smoke Control
joined to the curb cap with a continuously Systems [500°F (260°C) for 4 hours and 1,000°F
(538°C) for 15 minutes].
welded seam.
Motors shall be heavy-duty ball bearing type, Fans shall be model S-CUBE as manufactured
carefully matched to the fan load, and furnished by Greenheck Fan Corporation in Schofield,
at the specified voltage, phase and enclosure. Wisconsin, USA.
Drive frame assembly shall be constructed of
heavy-gauge steel. Motors and drives shall be
mounted on safety flange vibration isolators,
out of the airstream. Fresh air for positive motor
cooling shall be drawn into the motor compartment
through a ten-square-inch tube free of discharge
contaminants. Motors and drives shall be readily
accessible for maintenance.
87
Quick Delivery and Quick Build Programs
Our Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period
of one year from the purchase date. Any units or parts which prove defective during the warranty
period will be replaced at our option when returned to our factory, transportation prepaid. Motors are
warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck
prove defective during this period, they should be returned to the nearest authorized motor service
station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
Prepared to Support
specifications without notice. Green Building Efforts