BDM63DD Foreword

Three Phase Four Wires DIN Rail Energy Meter.Four Modules


Thank you for purchasing the EASTRON SDM630D DIN rail three phase
four wire energy meter. The EASTRON SDM630D energy meter is the
EASTRON most advanced type electronic kWh meter available at the market. With
the EASTRON product range we have introduced a large scale of energy
meters on the market suitable for 110V AC to 400V AC (50 or60Hz).
Besides the normal energy meters we also developed our own pre-paid
meters with chip card, chip card re-loaders and a complete PC management
control system. For more information on other product please contact
our sales department at sales@eastrongroup.com
Although we produce the EASTRON SDM630D meter according to
IEC 62053-21 and our quality inspection is very accurate there might
always be a possibility that your product shows a fault or failure for which
we do apologize. Under normal conditions your product should give you
years of benefit and pleasure. In case there is a problem with the energy
meter you should contact your dealer immediately. All energy meters are
sealed with a special seal. Once this seal is broken there is no possibility
to claim for warranty. Therefore NEVER open an energy meter or break
the seal of the energy meter. The warranty time is 24 months, after
installation, and only valid for construction faults.

Technical Data

Safety Instructions Performance criteria


Operating humidity 3 75%
Storage humidity S 95%
Information for your own safety Operating temperature -25°C-+50°C
Storage temperature -30°C-+70°C
This manual does not contain all of the safety measures for operation of
International standard IEC 62053-21
the equipment(module,device),because special operating conditions,
Accuracy class 1
and local code requirements or regulations may necessitate further
Protection against penetration
measures. However.it does contain information which must be read
of dust and water IP51
for your personal safety and to avoid material damages.This information
Insulating encased meter of
is highlighted by a warning triangle and is represented as follows,
protective class II
depending on the degree of potential danger.
Specifications
Warning
Nominal voltage(Un) 230V/400VAC(3-)
A | \ This means thatfailure to observe theinstruction canresult in
death, serious injury or considerable material damage. Operational voltage
Insulation capabilities
161/279V-300/520VAC

• Caution - AC voltage withstand 4KV for 1 minute


This means hazard of electric shock and failure to take the - Impulse voltage withstand 6KV-1.2uS

A necessary safety precautions will result in death,serious injury


or considerable material damage.
Basic current (lb)
Maximum rated current (Imax)
Operational current range
10A
100A
0.4% Ib-lmax
• Qualified personnel Over current withstand 20lmax for 0.01s
Operation of the equipment (module, device) described in this manual Operational frequency range 50Hz±10%
may only be performed by qualified personnel. Qualified personnel in Internal power consumption s2W/10VA/phase
this manual means person who are authorized to commission, start Test output flash rate (PULSE LED) 400imp/kWh
up, ground and label devices,systems and circuits according to safety Test pulse output rate (pins 8 & 9) 400imp/kWh
and Regulatory standards.
' Basic errors
• Useforthe intended purpose With balanced loads
The equipment (device, module) may only be used for the application 0.05lbCos9 = 1 ±1.5%
specified in the catalogue and the user manual,and only be connected 0.1lbCoscp = 0.5L ±1.5%
with devices and components recommended and approved by EASTRON. Cos(p = 0.8C ±1.5%
0.1lb-lmaxCos(p = 1 ±1.0%
• Proper handling 0.2lb - ImaxCosv = 0.5L ±1.0%
The prerequisites for perfect, reliable operation of the product are proper Cos«p = 0.8C ±1.0%
transport, proper storage, installation and assembly, as well as proper With single phase load
operation and maintenance. When operating electrical equipment, certain 0.1lb-lmaxCosq>= 1 ±2.0%
parts of this equipment automatically carry dangerous voltages. Improper 0.2lb - ImaxCosep = 0.5L ±2.0%
handling can therefore result in serious injuries or material damage.
♦ Use only insulating tools.
♦ Do not connect while circuit is live (hot).
♦ Place the meter only in dry surroundings.
♦ Do not mount the meter in an explosive area or expose the meter
to dust, mildew and insects. Dimensions
♦ Make sure the used wires are suitable for the maximum current of
this meter.
♦ Make sure the AC wires are connected correctly before activating
the current/voltage to the meter.
♦ Do not touch the meter connecting clamps directly with your bare
hands, with metal, blank wire or other material as you may get an
electrical shock.
♦ Make sure the protection cover is placed after installation.
♦ Installation, maintenance and reparation should only be done by
qualified personnel.
♦ Never break the seals and open the front cover as this might influence
the functionality of the meter, and will avoid any warranty.
♦ Do not drop, or allow physical impact to the meter as there are high
precision components inside that may break. Height 100mm
Width 76mm
Depth 66mm
Weight 0.3Kg(net)

JIAXING EASTRON ELECTRONIC INSTRUMENTS CO., LTD.


Add: No.1369 Chengnan Road, Nanhu, Jiaxing, Zhejiang, 314001, China
Tel: +86-573-83698881 /83698882 Fax: +86-573-83698883
Email :sa les@eastrongroup.com Web:www.eastrongroup.com
Installation Operation

♦ We recommend that the connecting wire which is used to connect the Consumption indication
meter to the outside circuit should be sized according to local codes On the SDM630D's front panel, there are four LEDs, in which top three
and regulations for the capacity of the circuit breaker or over current LEDs are for three phase voltage and the other one is impulse indication
device used in the circuit. for active energy measurement. The constant of the impulse is shown
♦ An external switch or a circuit-breaker should be installed on the inlet on the nameplate of the meter.
wire, which will be used as a disconnection device for the meter. And
there it is recommended that the switch or circuit-breaker is near the Reading the meter
meter so that it is more convenience for the operator. The switch or The SDM630D energy meter is equipped with 6+1 LCD display, which
circuit-breaker should comply with the specifications of the buildings is used as recording consumption and can't be reset to zero.
electrical design and all local regulations.
Pulse output
♦ The meter has to be installed against a wall which is fire resistant.
♦ The meter has to be installed in a good ventilated and dry place. SDM630D DIN rail energy meter is equipped with a pulse output which
♦ The meter has to be installed in a protection box when placed in is fully separated from the inside circuit. That generates pulses in
dangerous or dusty environment. proportion to the measured energy. They are test pulse output (pins
♦ The meter can be installed and used after being tested and sealed with 9 &10). Usually, the test pulse output is used as testing accuracy or reading
a letter press printing. purpose in close quarters.
♦ The meter can be installed on a 35mm DIN rail or direct on a meter board The test pulse output is a polarity dependant, passive transistor output
with screws. requiring an external voltage source for correct operation. For this
♦ The meter should be installed in an available height so that it is easy external voltage source, the voltage (Ui) should be 5-27V DC, and the
to read. maximum input current (Imax) should be 27mA DC. To connect the
♦ When the meter is installed in an area with frequent surges due to e.q. impulse output, connect 5-27V DC to connector 9 (anode), and the
thunderstorms, welding machines, inverters etc, protect the meter with signal wire (s) to connector 10 (cathode). The meter pulse is indicated
Surge Protection Devices. on the front panel.
♦ After finishing installation, the meter must be sealed to prevent tampering.
♦ Wiring of the wires should be done in accordance with the underneath
connection diagram.

Wiring Diagram

4> i l \sojv 1
1 ♦"
® © ®cf®6

j£ cJ V.J ©
1/5 la IN/OUT
1 t i i i i
2/6 lb IN/OUT
LI L2 L3 N 3/7 Ic IN/OUT
4 Neutral wire
8/9 Test pulse output contact

Installation Diagram

JIAXING EASTRON ELECTRONIC INSTRUMENTS CO., LTD.


Add: No.1369 Chengnan Road, Nanhu, Jiaxing, Zhejiang, 314001, China
Tel: +86-573-83698881 /83698882 Fax: +86-573-83698883
Emai I:sa les@eastrongroup.com Web: www.eastrongroup.com