You are on page 1of 8

Remote Terminal Units

Plug & play feeder-level automation

RightBox Series RTUs

RTU/RB4.0 Series
Unmatchable “RightBox” series

With Codesys support

Future ready
vendor-agnostic RTU
with ongoing protocol
support

Any other future open source protocol that uses


RS485 or TCP port is provided free of cost for
the period of at least five years.
Enabling SCADA with across assets

Automate your operations


for your electrical
networks
Applications and Features

Supporting number of
application with varied
business logic
Product Line
RTU/ RB 4.1

DIN rail mounted base module RTU/ RB 4.1


• ABS plastic housing
• 2x serial port (RS485)
• 1x Ethernet interface (10/100BaseT)
• Power supply 85-305 V AC (DC modules available on request)
• With connection interface to RTU/ RB 4.1 x
I/O-extension modules (upto 128 I/Os)
• Enhanced diversity antenna for signal strength
• Battery buffered real time clock
• Wall mounted option available

RTU/ RB 4.2

DIN rail mounted base module RTU/ RB 4.2


• Stainless Steel non-corrosive housing
• 2x serial port (RS485), extendable
• 1x Ethernet interface (10/100BaseT)
• USB configuration interface
• Power supply 12-48 V DC or 85-305 V AC
• With connection interface to RTU/ RB 4.2x
I/O-extension modules (upto 256 I/Os)
• Battery buffered real time clock
• Wall mounted option available

Additional Modules
Part Number Modules
RB 4.x1 Rs485 - for any serial communication (set of 2)
RB 4.x2 RS232 - for serial and optical communication
RB 4.x3 Ethernet 10/100 Base T (set of 4); Gigabit Ethernet optional
RB 4.x4 Universal Serial Bus
RB 4.x5 CAN Bus
RB 4.x6 4x Analog Input
RB 4.x7 4x Analog Output
RB 4.x8 8x Analog Input
RB 4.x9 8x Analog Output
RB 4.x10 8x Digital Input
RB 4.x11 8x Digital Output
RB 4.x12 4/4 Hybrid Analog IOs
RB 4.x13 4/4 Hybrid Digital IOs
Product Specifications

Supply voltage (85 - 305VAC, 120 - 370VDC) Or (24 VAC) Or (19-72 VDC)
Power consumption 3W for the base module
Storage Temp -40 °C to +85 °C
Operation Temp -20 °C to +70 °C
Humidity Max. 95% RH non-condensing
IP Class IP20, IP55

Programming
Remotely programmable Enabled without static IP
Over-the-air firmware update Enabled mode/ compulsory enabled mode

Remote variable change Enabled


Remote logic change Enabled

Communication ports
Port A: RS232 2400-57600 bps, Serial
Port B: RS485 2400-57600 bps, 2-wire, asynchronous, screw terminal
Port C: RS485 2400-57600 bps, 2-wire, asynchronous, screw terminal
Port D: Ethernet TCP/IP, 10Base-T, RJ45
Port E: Secured USB For data reconciliation/ programming only
Extendable ports As per requirements

Controller Specs
Memory Storage Extendable upto 16GB
Processor Arm Cortex, 1.2GHz
RAM 1GB
Edge Compute Enabled to run data enabled complex compute algorithms
like PID
Power saving for idle state DVFS (Dynamic Voltage and Frequency Scaling) on the core
voltage; hot standby
Extension modules Extendable I/O units - upto 256 I/O (4 20mA, 0-10V, 0-1V)
Communication channel 2G, 3G, 4G (with fallback) – dual mode (single SIM with future
provisioning), GSM, NB-IoT, Ethernet, Wi-fi
Modem Qualcomm 9207 based modem; with extended QMI interface

Security
Remote updates ISO27001 Cybersecurity compliant
Data Encryption All levels enabled (data at rest, data in communication)
Audit trails Available for all changes
Cybersecurity Specifications

S. No. Features
1 Confidentiality

1.a Confidentiality and integrity of Must be enabled


data
1.b Access control Must have a third field along with Username/ password

2 Hardware/ Controller security

2.a Physical security Password protected

2.b Update mechanism Over the air without any shutdowns

2.c Local data on hardware Encrypted

2.d Remote hardware access Must be enabled without physical connection

3 Communication security

3.a Client and backend server HTTPS

3.b Hardware and application services Additional encryption other than default https

3.c Application and cloud services Transport Layer Security (TLS)

4 Security: Data at rest

4.a User credentials Encrypted

4.b PII (personally identifiable) data At least SHA-512 encryption

4.c Database, backups and all logs Real-time encryption/ decryption of every database backup

4.d Access to cloud data Only allowed IP addresses

5 Recovery method implementation Point-in-Time-Restore data backups

6 Permissions to access application Role based and defined


features
7 Auditing

7.a Audit Trails Must have audit trails

7.b Audit Requirements Must record who accessed which data

7.c Customer's user log Maintained for one year including IP addresses

8 Data destruction (storage media Base layer must assure data destruction
dismission)
Feeders | Substation | Automation