You are on page 1of 3

10049-9-V06-MUSG-00153 003

GMD3681633 B

Mohamed Farag
2009/11/23 , 01:38:40 PM
Provide 50 X 25 mm reducer.
The connection on Owner side
is 25 mm

DN40

40

Relocate the flow element to upstream of the strainer

Relocate this drain line between the


flow element and the strainer

The strainer shall be a Y-type strainer with


blow-off valve as per Contract requirment.
Same comments as previous sheet