You are on page 1of 20

VRF System Selection Report

VRF System Selection Report


Project Name :HACIENDA 17 PUNTA CANA
Region :LA_MMA
Selection Mode :Cooling+Heating
Sales Engineer :
Company:
Address:
Phone No:
Order Date : 18/01/2023
Delivery required date : 18/01/2023
Client Name :
Post Code :
Tel :
Mail :

Update Date: 18/01/2023


Project Revision:
Global Selection Software version: 4.9.6
VRF System Selection Report

CONTENTS
LIMITS OF LIABILITY.............................................................................................................................................................................1
License Contract ................................................................................................................................................................................1
Reports...............................................................................................................................................................................................1
SYSTEM SELECTION ...........................................................................................................................................................................2
Outdoor Units .....................................................................................................................................................................................2
Indoor Units........................................................................................................................................................................................3
SYSTEM DESIGN ..................................................................................................................................................................................4
SYS1 ..................................................................................................................................................................................................4
Outdoor Units of the system ..........................................................................................................................................................4
Indoor Units of the system .............................................................................................................................................................4
SYS2 ..................................................................................................................................................................................................4
Outdoor Units of the system ..........................................................................................................................................................5
Indoor Units of the system .............................................................................................................................................................5
PIPING DESIGN.....................................................................................................................................................................................6
SYS1 ..................................................................................................................................................................................................6
Piping Diagram ..............................................................................................................................................................................6
SYS1 ..................................................................................................................................................................................................7
Piping Rules...................................................................................................................................................................................7
Refrigerant Load & Pipe size .........................................................................................................................................................7
Recommendation...........................................................................................................................................................................7
SYS2 ..................................................................................................................................................................................................8
Piping Diagram ..............................................................................................................................................................................8
SYS2 ..................................................................................................................................................................................................9
Piping Rules...................................................................................................................................................................................9
Refrigerant Load & Pipe size .........................................................................................................................................................9
Recommendation...........................................................................................................................................................................9
WIRING DESIGN .................................................................................................................................................................................10
SYS1 ................................................................................................................................................................................................10
Wiring Diagram ............................................................................................................................................................................10
SYS1 ................................................................................................................................................................................................11
Power Supply...............................................................................................................................................................................11
RCS link description ....................................................................................................................................................................11
SYS2 ................................................................................................................................................................................................11
Wiring Diagram ............................................................................................................................................................................11
SYS2 ................................................................................................................................................................................................12
Power Supply...............................................................................................................................................................................12

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report
RCS link description ....................................................................................................................................................................12
Central Controller .............................................................................................................................................................................13
H-Link2 communication line description ......................................................................................................................................13
EQUIPMENT LIST AND INFORMATION.............................................................................................................................................14
Outdoor Units ...................................................................................................................................................................................14
Indoor Units......................................................................................................................................................................................14
Accessories .................................................................................................................................................................................14
Branch Kit.........................................................................................................................................................................................14
Multikit..........................................................................................................................................................................................14
CH Box.............................................................................................................................................................................................14
Field Providing .................................................................................................................................................................................14
Piping Materials ...........................................................................................................................................................................14
Refrigerant ...................................................................................................................................................................................15
Appendix –Equipment list for SYS2......................................................................................................................................................16
Field Providing .............................................................................................................................................................................16
Appendix –Equipment list for SYS1......................................................................................................................................................16
Field Providing .............................................................................................................................................................................17

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

LIMITS OF LIABILITY

License Contract
By using the Global VRF Selection Software, you agree to abide by the terms of this End User License Agreement.
This software is not intended to provide highly accurate or certifiable results taking into account all the factors involved
in complex or sophisticated installations.
YORK makes no warranties regarding the accuracy of the results obtained from the use of this software.
In fact, this software is not able to take into account all the site-specific factors that may influence the proper
functioning of the selected device (e.g. piping or wiring lengths on site, third party AHU, geometry of the piping
network, operating temperatures…).
It may also contain technical inaccuracies or errors, and improvements or modifications may be made to the software
by YORK at any time without prior notice.
This software is not intended to replace a thorough evaluation by a professional of the HVAC field.
Accordingly, you are advised not to rely solely on the reports produced by the software to select the appropriate
equipment.

Reports
The report is the result of the information transferred and input by the User of the Global VRF Selection Software.
YORK assumes no kind of liability regarding the pre-existing data and information in the Software, as well as the data
and information input by the User, and in particular in relation to:
1. The static part of the Software including the information required to carry out the calculations corresponding to each
project through preset parameters; this information merely includes the parameters for the preparation of the report in
line with the model designed by and with the knowledge of YORK, without this implying any kind of guarantee for the
user regarding the precision and reliability of the results of the report.
2. The dynamic part of the Software, which is the result of the information input by the User in correspondence with
the said parameters; the User is on all accounts exclusively liable for the accuracy of the information being input in the
Software.
3. The failure to include any legal aspects that may correspond or be required according to current laws.
The Software and the issuing of this report are merely informative tools to assist the User in the planning and
implementation of a project.

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
1 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

SYSTEM SELECTION

Outdoor Units
Model
Pictures Description Quantity Components
Identification
-

Commercial VRF HP, -


JTOH160VPERBS1 1
JTOH-BS1 -
-

JTOH160VPERBS1
Specifications
Power supply 220V/3Ph/60Hz
Cooling 12.8Ton
Nominal capacity
Heating 14.2Ton
EER
COP
SEER
SCOP
Sound power dB(A)
Height 1,675mm
Dimensions Width 1,210mm
Depth 765mm
Net Weight 305kg

Model
Pictures Description Quantity Components
Identification
-

Commercial VRF HP, -


JTOH120VPERBS1 1
JTOH-BS1 -
-

JTOH120VPERBS1
Specifications
Power supply 220V/3Ph/60Hz
Cooling 9.5Ton
Nominal capacity
Heating 10.7Ton
EER
COP
SEER
SCOP
Sound power dB(A)
Height 1,675mm
Dimensions Width 950mm
Depth 765mm
Net Weight 205kg

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
2 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

Indoor Units
No Room
Indoor Unit Nominal Cap. (Ton) Control
Accessories
Picture Ident. Description - Model Cool Heat Picture Model Gp
MEDIA High Static Ducted JCWA10NEG
4.6 5.1
ROOM JTDH160H0NB0AQ Q
DININ
G
ROOM
High Static Ducted JCWA10NEG
& 4.6 5.1
JTDH160H0NB0AQ Q
COLD
KITCH
EN
GREA
High Static Ducted JCWA10NEG
T 4.6 5.1
JTDH160H0NB0AQ Q
ROOM
MAST
ER High Static Ducted JCWA10NEG
3.2 3.7
BEDR JTDH112H0NB0AQ Q
OOM
FAMIL
Medium Static Ducted JCWA10NEG
Y 2.0 2.4
JTDM071H0NB0AQ Q
ROOM
GUES
T Medium Static Ducted JCWA10NEG
1.8 2.1
BEDR JTDM063H0NB0AQ Q
OOM 3
GUES
T Medium Static Ducted JCWA10NEG
1.8 2.1
BEDR JTDM063H0NB0AQ Q
OOM 2
GUES
T Medium Static Ducted JCWA10NEG
1.8 2.1
BEDR JTDM063H0NB0AQ Q
OOM 1

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
3 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

SYSTEM DESIGN

SYS1

Working Condition Outdoor (Air) Indoor (Air)

27.0 °C DB
Cooling 35.0 °C DB
19.6 °C WB (50% RH)
7.0 °C DB
Heating 20.0 °C DB
3.1 °C WB (51% RH)
Note:
- Actual capacity takes into account all correction factors, including defrosting in heating mode.
- Each Indoor unit’s temperature condition might be different. Software uses minimum wet bulb temperature of indoor for
system cooling process and uses maximum dry bulb temperature of indoor for system heating process.

Outdoor Units of the system

Outdoor Unit (SYS1) Connect. Rate (%) Cooling Capacity (Ton) Heating Capacity (Ton)
Ref + Description Ident. Actual Max Nominal Actual Required Nominal Actual Required
Commercial VRF HP, JTOH-BS1
113 120 - 12.8 - - 13.4 -
JTOH160VPERBS1
Total - 12.8 - - 13.4 -

Indoor Units of the system

Indoor Unit (SYS1) Sound Pressure Air Flow Cooling Capacity (Ton) Heating Capacity (Ton)
Ref + Description Ident. dB(A) Speed m³/min Actual Sensible Required Actual Required
Total 12.8 9.2 0.0 13.4 0.0
MEDIA 38.0
High Static Ducted JTDH160H0NB0AQ 41 High 4.3 3.1 0.0 4.5 0.0
ROOM
DINING 38.0
ROOM
High Static Ducted JTDH160H0NB0AQ & COLD 41 High 4.3 3.1 0.0 4.5 0.0
KITCHE
N
GREAT 38.0
High Static Ducted JTDH160H0NB0AQ 41 High 4.3 3.1 0.0 4.5 0.0
ROOM

SYS2

Working Condition Outdoor (Air) Indoor (Air)

27.0 °C DB
Cooling 35.0 °C DB
19.6 °C WB (50% RH)
7.0 °C DB
Heating 20.0 °C DB
3.1 °C WB (51% RH)
Note:
- Actual capacity takes into account all correction factors, including defrosting in heating mode.
- Each Indoor unit’s temperature condition might be different. Software uses minimum wet bulb temperature of indoor for
system cooling process and uses maximum dry bulb temperature of indoor for system heating process.

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
4 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

Outdoor Units of the system

Outdoor Unit (SYS2) Connect. Rate (%) Cooling Capacity (Ton) Heating Capacity (Ton)
Ref + Description Ident. Actual Max Nominal Actual Required Nominal Actual Required
Commercial VRF HP, JTOH-BS1
112 120 - 9.3 - - 9.8 -
JTOH120VPERBS1
Total - 9.3 - - 9.8 -

Indoor Units of the system

Indoor Unit (SYS2) Sound Pressure Air Flow Cooling Capacity (Ton) Heating Capacity (Ton)
Ref + Description Ident. dB(A) Speed m³/min Actual Sensible Required Actual Required
Total 9.3 6.5 0.0 9.8 0.0
MASTE 27.0
R
High Static Ducted JTDH112H0NB0AQ 40 High 2.8 1.9 0.0 2.9 0.0
BEDRO
OM
FAMILY 16.0
Medium Static Ducted JTDM071H0NB0AQ 34 High 1.8 1.2 0.0 1.9 0.0
ROOM
GUEST 16.0
Medium Static Ducted JTDM063H0NB0AQ BEDRO 34 High 1.6 1.1 0.0 1.7 0.0
OM 3
GUEST 16.0
Medium Static Ducted JTDM063H0NB0AQ BEDRO 34 High 1.6 1.1 0.0 1.7 0.0
OM 2
GUEST 16.0
Medium Static Ducted JTDM063H0NB0AQ BEDRO 34 High 1.6 1.1 0.0 1.7 0.0
OM 1

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
5 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

PIPING DESIGN

SYS1

Piping Diagram

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
6 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

SYS1

Piping Rules

Project Max
Commercial VRF HP, JTOH-BS1 JTOH160VPERBS1 OK
m m
Total pipe length 55 1,000 
Maximum piping length (Actual length) 38 165 
Length Maximum piping length (Equivalent length) 44 190 
Maximum Piping Length between Multi-kit of 1st Branch and Each Indoor Unit 25 90 
Maximum Piping Length between Each Multi-kit and Each Indoor Unit 18 40 
Height Difference between (O.U. is Upper) 0 110 
Height Height Difference between (O.U. is Lower) 4 40 
Height Difference between Indoor Units 0 30 

IU connectable ( Min / recommended / Max) 3 1 / 16 / 26 


Connected Cap. (Min-Max) 113% 50% - 130% 

Refrigerant Load & Pipe size

Refrigerant Type: R410A


Commercial VRF HP, JTOH-BS1 JTOH160VPERBS1
kg

OU refrigerant load (Charge before shipment) 9.9

Installation Additional refrigerant load (OU + Piping) 6.2


Total 16.1

Recommendation

- If pipe size 1'' is not available in your country, please use 1''1/8 as replacement.

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
7 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

SYS2

Piping Diagram

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
8 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

SYS2

Piping Rules

Project Max
Commercial VRF HP, JTOH-BS1 JTOH120VPERBS1 OK
m m
Total pipe length 67 1,000 
Maximum piping length (Actual length) 45 165 
Length Maximum piping length (Equivalent length) 53 190 
Maximum Piping Length between Multi-kit of 1st Branch and Each Indoor Unit 32 90 
Maximum Piping Length between Each Multi-kit and Each Indoor Unit 10 40 
Height Difference between (O.U. is Upper) 0 110 
Height Height Difference between (O.U. is Lower) 4 40 
Height Difference between Indoor Units 0 30 

IU connectable ( Min / recommended / Max) 5 1 / 10 / 19 


Connected Cap. (Min-Max) 112% 50% - 130% 

Refrigerant Load & Pipe size

Refrigerant Type: R410A


Commercial VRF HP, JTOH-BS1 JTOH120VPERBS1
kg

OU refrigerant load (Charge before shipment) 7.2

Installation Additional refrigerant load (OU + Piping) 7.5


Total 14.7

Recommendation

- If pipe size 1'' is not available in your country, please use 1''1/8 as replacement.

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
9 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

WIRING DESIGN

SYS1

Wiring Diagram

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
10 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

SYS1

Power Supply

Input power Max current


Model Power supply
kW A

JTOH160VPERBS1 220V/3Ph/60Hz 10.09 54.5

JTDH160H0NB0AQ 220V/1Ph/60Hz 0.4 1.9

RCS link description

- Minimum recommended section (up to 500 m): 2 x 0.75 mm² connected to earth at one point.
- Cable characteristics: non polar, twisted shielded pair of cable.
- One Remote Control Switch can control up to 16 Indoor Units as a maximum.
- Two Remote Control Switch can be connected in the same unit or unit group.
- The second one is a subsidiary remote control switch.

SYS2

Wiring Diagram

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
11 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

SYS2

Power Supply

Input power Max current


Model Power supply
kW A

JTOH120VPERBS1 220V/3Ph/60Hz 6.84 39

JTDH112H0NB0AQ 220V/1Ph/60Hz 0.31 1.4

JTDM071H0NB0AQ 220V/1Ph/60Hz 0.13 0.65

JTDM063H0NB0AQ 220V/1Ph/60Hz 0.13 0.65

RCS link description

- Minimum recommended section (up to 500 m): 2 x 0.75 mm² connected to earth at one point.
- Cable characteristics: non polar, twisted shielded pair of cable.
- One Remote Control Switch can control up to 16 Indoor Units as a maximum.
- Two Remote Control Switch can be connected in the same unit or unit group.
- The second one is a subsidiary remote control switch.

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
12 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

Central Controller

H-Link2 communication line description

- Minimum recommended section: 2 x 0.75 mm² connected to earth at one point. Shielding must be renewed every 300m.
- Transmitting wires: non polar, twisted shielded pair of cable.
- Maximum H-Link2 communication line length is 1000 m but can be increased until 5.000m using optional relay PSC-5HR.
- Several refrigerant systems can be connected together on a bus with H-LINK2 wiring using an open loop
- Maximum number of Outdoor Units is 64.
- Maximum number of Indoor Units is 160.
- Number of central controller: 0

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
13 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

EQUIPMENT LIST AND INFORMATION

Outdoor Units

Model & Components System Name Description Quantity

JTOH160VPERBS1 SYS1 Commercial VRF HP, JTOH-BS1 1


JTOH120VPERBS1 SYS2 Commercial VRF HP, JTOH-BS1 1

Indoor Units

Model Description Quantity

JTDH112H0NB0AQ High Static Ducted 1


JTDH160H0NB0AQ High Static Ducted 3
JTDM063H0NB0AQ Medium Static Ducted 3
JTDM071H0NB0AQ Medium Static Ducted 1

Accessories

Model Description Quantity

JCWA10NEGQ Remote Control Switch 8

Branch Kit

Multikit

Model Description Quantity

MW-NP452A3 Line branch kit 3


MW-NP282A3 Line branch kit 3

CH Box

Field Providing

Piping Materials

Pipe size(mm) Length


m

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
14 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report
Pipe size(mm) Length
m
1/2 33
3/8 89
5/8 77.5
3/4 4.5
7/8 7
1 20
1 1/8 13

Refrigerant

Quantity to be provided
Refrigerant Type
kg
R410A 13.6

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
15 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report

Appendix –Equipment list for SYS2


Category Model Description Quantity

Outdoor Units JTOH120VPERBS1 Commercial VRF HP, JTOH-BS1 1

Indoor Units JTDH112H0NB0AQ High Static Ducted 1


JTDM063H0NB0AQ Medium Static Ducted 3
JTDM071H0NB0AQ Medium Static Ducted 1

Accessory JCWA10NEGQ Remote Control Switch 5

MultiKit MW-NP452A3 Line branch kit 1


MW-NP282A3 Line branch kit 3

Field Providing

Pipe size(mm) Length

1/2 13
3/8 54
5/8 42.5
3/4 4.5
7/8 7
1 13

Quantity to be provided
Refrigerant Type
kg
R410A 7.5

Appendix –Equipment list for SYS1


Category Model Description Quantity

Outdoor Units JTOH160VPERBS1 Commercial VRF HP, JTOH-BS1 1

Indoor Units JTDH160H0NB0AQ High Static Ducted 3

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
16 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6
VRF System Selection Report
Category Model Description Quantity

Accessory JCWA10NEGQ Remote Control Switch 3

MultiKit MW-NP452A3 Line branch kit 2

Field Providing

Pipe size(mm) Length

1/2 20
3/8 35
5/8 35
1 7
1 1/8 13

Quantity to be provided
Refrigerant Type
kg
R410A 6.2

JOHNSON CONTROLS-HITACHI AIR CONDITIONING expresses no warranty or legal responsibility concerning the Project Name: HACIENDA 17 PUNTA CANA
17 accuracy or completeness of the data given and therefore the answers obtained by this software.
Global Selection Software version: 4.9.6