Dimensions and installation conditions for HMH 24kV

Wall and Ceiling clearance

For substations provide


➢ A minimum rear-wall clearance of 70 mm (Recommended 150mm)
➢ A minimum lateral-wall clearance of 70 mm (Recommended
300mm)
➢ A minimum ceiling clearance of 70 mm (Recommended 150mm).

Figure 1 Wall and Ceiling clearance for HMH 24kV

**Please follow the cable manufacturer catalog to A and R.

1
Installation of the substation for internal arc withstand for
HMH 24kV

When there is a requirement for installations with protection against


internal arc faults, refer to the following diagrams.

Figure 2 Installation of the substation for internal arc withstand for HMH 24kV

2
Dimensions and installation conditions for HMH 36kV

Wall and Ceiling clearance

For substations provide


➢ A minimum rear-wall clearance of 70 mm (Recommended 150mm)
➢ A minimum lateral-wall clearance of 70 mm (Recommended
300mm)
➢ A minimum ceiling clearance of 70 mm (Recommended 150mm).

Figure 3 Wall and Ceiling clearance for HMH 36kV

**Please follow the cable manufacturer catalog to A and R.

3
Installation of the substation for internal arc withstand for
HMH 36kV

When there is a requirement for installations with protection against


internal arc faults, refer to the following diagrams.

Figure 4 Installation of the substation for internal arc withstand for HMH 36kV