IKAN Tray support Member size check

1/16/2020

Column size H 150x150 Column size H 150x150 Column size H 150x150 Column size H 200x200
Beam size C 100x50x5 Beam size C 100x50x5 Beam size C 125x65x6 Beam size C 125x65x6
Max Unity Ratio 0.997 Max Unity Ratio 0.223 Max Unity Ratio 0.551 Max Unity Ratio 0.563
Max Deflection 5.19mm / 6mm Max Deflection 0.24mm / 6mm Max Deflection 4.43mm / 6mm Max Deflection 5.10mm / 6mm
Remark Remark Remark Remark

Column size H 150x150 Column size H 150x150 Column size - Column size H 150x150
Beam size C 100x50x5 Beam size C 125x65x6 Beam size C 125x65x6 Beam size C 125x65x6
Max Unity Ratio 0.966 Max Unity Ratio 0.557 Max Unity Ratio 0.776 Max Unity Ratio 0.625
Max Deflection 5.93mm / 6mm Max Deflection 4.46mm / 6mm Max Deflection 4.08mm / 7mm Max Deflection 5.2mm / 13mm
Remark Remark Remark Remark Shear Connection
IKAN Tray support Member size check
1/16/2020

Column size H 150x150 Column size H 150x150 Column size Column size
Beam size C 100x50x5 Beam size C 100x50x5 Beam size Beam size
Max Unity Ratio 0.444 Max Unity Ratio 0.224 Max Unity Ratio Max Unity Ratio
Max Deflection 4.72mm / 4.5mm Max Deflection 2.11mm / 3mm Max Deflection Max Deflection
Remark Deflection N.G (0.22mm) Remark Remark Remark
1.0 Cable Tray Load (Del)

The cable tray loads given by the electric and instrument department are applied as follows :

TRAY LOAD
W900 140 kg/m
W600 85 kg/m
W300 65 kg/m

Electric Cable Tray Load


Number
Width Unit Weight (kN/m) Span Length (m) Applied Load (kN) Sub-Total
of rows
W900 1.40 6 8.40 kN 1 8.4 kN
W600 0.85 6 5.10 kN 1 5.1 kN
W300 0.65 6 3.90 kN 1 3.9 kN
2.0 Wind Load (W)

Wind loads are calculated in accordance with ASCE/SEI 7 and Design Criteria, 26071-100-3DR-000-00001.

2.1 Wind Load on Structural Coded Members

Wind Load on Structural Elements : Auto-Generated by 'STAAD Pro' for open structure.

The design wind force shall is based on ASCE/SEI 7 & Design Criteria, 26071-100-3DR-000-00001.
Wind Loading applied in longitudinal & transverse direction for the structure.

Design wind Force, F = qz x G x Cf x A - ASCE 7-10, section 29.5

where, qz : Velocity Wind Pressure evaluated at mean roof height (N/mm2)


G : Gust effect factor, 0.85
Cf : Force coefficient, Figure 29.5-1~3 of ASCE 7-10
for Structural member : 1.8
for Pipe : 0.7
for Cable tray : 2.0
A : Projected area

Wind velocity pressure, qz = 0.00256 x Kz x Kzt x Kd x V2 (psf)


= 0.613 x Kz x Kzt x Kd x V2 (N/m2)

where, Kz : Velocity pressure exposure coefficient evaluated at height z, Exposure category C


(Table 27.3-1 of ASCE 7-10)
Kzt : Topographic factor, 1 (Sec. 26.8.2 of ASCE 7-10)
Kd : Wind directionality factor, 0.85 (Table 26.6-1 of ASCE 7-10)
V : Basic wind speed, 35 m/sec

Height V V qz qz x G
Kz Kzt Kd
(ft) (m) (m/s) (mi/h) (psf) (kN/m2) (kN/m2)
0 0.0 0.85 1.00 0.85 35.00 78.30 11.34 0.543 0.462
15 4.6 0.85 1.00 0.85 35.00 78.30 11.34 0.543 0.462
20 6.1 0.90 1.00 0.85 35.00 78.30 12.01 0.574 0.488
25 7.6 0.94 1.00 0.85 35.00 78.30 12.54 0.600 0.510
30 9.1 0.98 1.00 0.85 35.00 78.30 13.07 0.626 0.532
40 12.2 1.04 1.00 0.85 35.00 78.30 13.87 0.664 0.564
50 15.2 1.09 1.00 0.85 35.00 78.30 14.54 0.696 0.592
60 18.3 1.13 1.00 0.85 35.00 78.30 15.07 0.721 0.613
70 21.3 1.17 1.00 0.85 35.00 78.30 15.61 0.747 0.635
80 24.4 1.21 1.00 0.85 35.00 78.30 16.14 0.772 0.656
90 27.4 1.24 1.00 0.85 35.00 78.30 16.54 0.791 0.672
100 30.5 1.26 1.00 0.85 35.00 78.30 16.81 0.804 0.683
120 36.6 1.31 1.00 0.85 35.00 78.30 17.47 0.836 0.711
140 42.7 1.36 1.00 0.85 35.00 78.30 18.14 0.868 0.738
160 48.8 1.39 1.00 0.85 35.00 78.30 18.54 0.887 0.754
180 54.9 1.43 1.00 0.85 35.00 78.30 19.08 0.913 0.776

Table 12. Wind Velocity Pressure


60
Wind Velocity Pressure, qz (kN/m2)
16

50
15

14
40
13
Height (m)

30 12
11
10
9
20
8

6 7

10 4
3 5
2

1
0
0.4 0.5 0.6 0.7 0.8 0.9 1.0

Wind velocity pressure(kN/m2)

2.2 Wind Load on Cable Trays

Transverse wind loads on the cable tray shall be applied at each bent beam level and calculated as below ;

Design wind force, F = qz x G x Cf x At

where, qz : Wind velocity pressure


G : Gust effect factor, 0.85
Cf : Force coefficient, 2.0 for cable Tray
At : Projected Area = Tray Height x Tray Length

Applied
Cable EL. Max. Cable tray Length qz x G At Applied Joint
Cf Force
Tray (m) height (m) (m) (kN/m2 ) (m2) (EA)
(kN)
W900 113900 0.150 6.000 0.592 2.0 0.900 1.065 1
W600 113900 0.150 6.000 0.592 2.0 0.900 1.065 1
W300 113900 0.150 6.000 0.592 2.0 0.900 1.065 1
Total Sum 3.195

Table 13-3. Wind Load on Cable Trays