28 x 4mm² DC FED IN 100mm RF27, TO 1 x 120mm² 4C ALU XLPE FED KEY PLAN

THE INVERTER 1 IN 100mm CL76, TO TIE-IN

+
-
-

-
1.8N 1.9N

+
-

-
1.1.1N 1.1.2N 1.2.1N 1.2.2N 1.3.1N 1.3.2N 1.4.1N 1.4.2N 1.5.1N 1.5.2N 1.6N 1.7N

+

3° 3° 3°

17 17 17 17 17 17 17 17 17 17 17 17 18 18

-
1.1.1P 1.1.2P 1.2.1P 1.2.2P 1.3.1P 1.3.2P 1.4.1P 1.4.2P 1.5.1P 1.5.2P 1.6P 1.7P 1.8P 1.9P

+
28 x 4mm² DC FED IN 100mm RF27, TO WALL PENETRATION 310 450 3° 3° 3°

THE INVERTER 1 NEEDED HERE 600 670

THIS DRAWING

GENERAL NOTES:
EXISTING
PV BOARD 1. SUNGROW SG110CX INVERTER
MINIMUM CLEARANCES (TO INVERTER, WHERE NO
DIMENSION IS SHOWN APPLY BELOW):
509 FLOOR - 450mm
CEILING - 600mm
RIGHT WALL - 400mm
LEFT WALL - 800mm

1400
PVDB INVERTER - 800mm
SG110CX 2.INVERTERS PROTRUDE 310mm.
3.ALL CABLE TRAY EDGES TO BE SMOOTHED
4.LAYOUT DIMENSIONS GIVEN TO RELEVANT
PVDB TOP / SIDE OF INVERTER.
SG110CX
5.WIRE WAY INDICATED, ACTUAL POSITION ON
SITE MAY VARY , DENOTED BY STANDARD WIDTH
6.ALL DIMENSIONS ARE IN mm UNLESS
OTHERWISE INDICATED.
7.UV EXPOSED WIRE MESH TRAYS & LADDERS TO
BE INSTALLED WITH COVERS.
WIREWAY TAKE OFF (RF 27)
1351

TYPE QTY
RF27 100mm + LIDS 3m
RF27 100mm DROPPER 1 OFF

850
RF27 100mm 90° BEND 1 OFF
WIREWAY TAKE OFF (CL)

TYPE STRAIGHT LENGTH

CL76 100mm 90° BEND 3 OFF


CL76 100mm + LIDS 9m
1 x 120mm² 4C ALU XLPE FED 1 x 120mm² 4C ALU XLPE FED CL76 100mm RISER 2 OFF
IN 100mm CL76, SUPPORTED IN 100mm CL76, SUPPORTED
ON 150mm FPA, TO PVDB CL76 150mm FPA 3 OFF
ON 150mm FPA, TO PVDB
CABLE TAKE OFF
SECTION A-A SECTION B-B
Scale: 1:200 Scale: 1:200 TYPE STRAIGHT LENGTH

120mm² 4 CORE XLPE ALU ±7m

28 x 4mm² DC FED IN 150mm RF27, TO


THE INVERTER 1

1 x 120mm² 4C ALU XLPE FED


IN 100mm CL76, SUPPORTED
B

ON 150mm FPA, TO PVDB

SG110CX
600

77
96
670

PVDB

450
A A

1 x 120mm² 4C ALU XLPE FED


IN 100mm CL76, FROM PVDB PROJECT:

TO TIE-IN P0463 - BUILDERS ZAMBISI

ADDRESS:

371 VEDA AVENUE,MONTANA


PRETORIA NORTH,182
DRAWING TITLE:

EXISTING INVERTER LOCATION


PV BOARD TFS - INTERNAL REVIEW
Siya Mamba
REVIEW BY:............................................ DATE: DRAFTSMAN: ENGINEER:
26/01/2023 D. VAN WEZEL S. MAMBA
APPROVED DRAWING NUMBER: REV:
P0463-00-DWG-021 A
APPROVED WITH COMMENTS DRAFTING CHECK: ENGINEER APPROVAL: SCALE:
B

REVISE S.MAMBA P. CAMPANELLA 1:20


11/01/2023 A2
COMMENTS:...........................................
.................................................................

INVERTER LOCATION .................................................................


13/02
CAPE TOWN
4 SILVERWOOD CLOSE | STEENBERG OFFICE PARK | WESTLAKE |
CAPE TOWN | 7945 | SOUTH AFRICA
DATE: .....................SIGN........................ JOHANNESBURG
Scale: 1:200 BUILDING 25 | WOODLANDS OFFICE PARK
20 WOODLANDS DRIVE | WOODLANDS | 2191 | SOUTH AFRICA
CONFIDENTIALITY AND © NOTICE: THIS DOCUMENT IS CONFIDENTIAL AND THE
COPYRIGHT OF REUNERT LTD / TERRA FIRMA SOLUTIONS (PTY) LTD. ANY
A 13/02 ISSUED FOR REVIEW S.M
UN-AUTHORISED PUBLICATION, DISCLOSURE, USE, MODIFICATION OR COPYING IN
REV: DATE: DESCRIPTION: APPROVED: WHOLE OR IN PART IN WHATSOEVER MANNER IS STRICTLY PROHIBITED.

C:\Users\Daniel van Wezel\Terra Firma Solutions\P0463 Builders Zambesi - Documents\4_Drafting\P0463-00-CAD-001.dwg, 2023/02/13 15:15:09, DWG To PDF.pc3