All manuals and user guides at all-guides.com

1. General Safety Instructions

2. Summary

3. Performance Features

4. Primary Technical Parameter

5. Structure

6. General Drawing

7. Wiring Diagram

8. Installation of Electric Actuators

9. Debug Description

10. Running Test

11. Maintenance

-1-
All manuals and user guides at all-guides.com

1. General Safety Instructions

Do not open the upper shell when with main power

Check the specification on the nameplate is the same as order specification.

Pls reading the instruction book before using

Pls reset the limit switches when mounting the valve

Do not change the internal wiring

If the power supply is 3 phase, should to check the rotating direction.

2. Summary
"AOX-Q" series electric actuator is used for controlling 0° ~ 270° rotation of the valves and other similar
products, such as butterfly valve, ball valve, damper, flapper valve, cock valve etc. It widely applies to petroleum,
chemical, water treatment, shipping, paper making, power plant, heating, light industry and other industries.
Drived by 380V/220V/110VAC power or 24V/110VDC power, inputs 4-20mA or 0-10VDC control signal,
moves valve to the right position, and achieves to automatic control, maximum output torque is 6000N·M.

3. Performance Features
3. 1. Shell--The shell is made of aluminum alloy, with anodic oxidation treatment and polyester powder coating.
It is strong corrosion-resistant and enclosure IP67,NEMA 4 and 6, IP68 and explosion-proof is optional.

-2-
All manuals and user guides at all-guides.com

3.2. Motor--Asynchronous motor, small, large torque, and small inertia force, F-class insulation rating, with
thermal protection to avoid damaging.

3.3. Manual Structure--The design of handwheel is safe, reliable, labor-saving, small. Declutch to operate by
handwheel if without power, and reset automatically when power on.

3.4. Indicator-- Installs indicator in the center axis and adopts convex mirror design, no cumulate water, more
convenient to observe.

3.5. Space heater-- It is used for controlling temperature to avoid condensing internal of housing and keep dry.

3.6. Limit switch-- Mechanical, electronic double limit. Mechanical limit stopper is adjustable, safe and reliable;
electronic limit switch is controlled by cam. Set position accurately and conveniently, and not affected by
excessive handle.

3.7.Torque Switch-- (Except AOX-Q-005/008/010) Providing overload protection to avoid the damage of valve
and electric actuator when jammed by cutting power automatically.

3.8.Self-locking--Accurate worm and worm gear transfer large torque efficiently , high efficiency, low noise
(max. 50 dB), long life, with self-locking, prevent inversion, as stable and reliable transmission parts, no need to
refuel.

3.9. Anti-off bolt—The bolt attaches to the shell and be not off when remove the shell.

3.10.Installation-- The installation size meets international standard ISO5211 / DIN3337.

3.11. Circuit--Controlling circuit meets the single-phase or three-phase power supply standard, circuit layout is
reasonable and compact, terminals meet various of additional functional requirements effectively.

3.12 The display of valve position—During the opening or closing movement of actuator, the change of valve
position on LCD is displayed with large numbers.

3.13 Adjust the phase sequence automatically—Intelligent actuator check and test the phase sequence for 3 phase
power supply automatically, users no need to consider about the phase sequence.

-3-
All manuals and user guides at all-guides.com

4. Primary Technical Parameter


4.1 AOX-Q series electric actuator technical parameter

Rated Current(A)
Max
Max 60/50Hz Hand
Drive
Output Operating Power wheel Weight
Model Shaft
Torque Time single phase three phases Revolution
Size

N Kg
N·M 90° mm W 110V 220V 380V 440V

AOX-Q-005 50 18/22 Φ20 20 1.10/0.95 0.55/0.54 0.3/0.3 N/A 10 7.5

AOX-Q-008 80 18/22 Φ20 20 1.10/0.95 0.55/0.54 0.3/0.3 N/A 10 7.5

AOX-Q-010 100 18/22 Φ20 20 1.10/0.95 0.55/0.54 0.3/0.3 N/A 10 7.5

AOX-Q-015 150 21/25 Φ22 40 1.65/1.67 0.88/0.84 0.31/0.31 0.30/0.31 11 17.3

AOX-Q-020 200 21/25 Φ22 40 1.67/1.67 0.89/0.85 0.31/0.31 0.30/0.31 11 17.3

AOX-Q-030 300 26/31 Φ35 90 1.85/1.86 0.92/0.92 0.35/0.35 0.34/0.34 13.5 22

AOX-Q-050 500 26/31 Φ35 90 3.60/3.62 1.55/1.58 0.59/0.59 0.58/0.58 13.5 23

AOX-Q-060 600 26/31 Φ35 120 3.65/3.62 1.60/2.20 0.60/0.59 0.59/0.58 13.5 23

AOX-Q-080 800 31/37 Φ45 180 4.10/4.10 2.15/2.20 0.85/0.85 0.79/0.79 16.5 29

AOX-Q-120 1200 31/37 Φ45 180 4.20/4.10 2.35/2.30 0.87/0.87 0.81/0.81 16.5 29

AOX-Q-150 1500 78/93 Φ45 120 3.65/3.62 1.60/2.20 0.60/0.59 0.59/0.58 40.5 77

AOX-Q-200 2000 93/112 Φ45 180 4.10/4.10 2.15/2.20 0.85/0.85 0.79/0.79 49.5 83

AOX-Q-300 3000 93/112 Φ45 180 4.20/4.10 2.35/2.30 0.87/0.87 0.81/0.81 49.5 83

AOX-Q-400 4000 155/185 Φ45 180 4.20/4.10 2.35/2.30 0.87/0.87 0.81/0.81 82.5 83

AOX-Q-500 5000 155/185 Φ45 180 4.20/4.10 2.35/2.30 0.87/0.87 0.81/0.81 82.5 83

AOX-Q-600 6000 155/185 Φ45 180 4.20/4.10 2.35/2.30 0.87/0.87 0.81/0.81 82.5 83

-4-
All manuals and user guides at all-guides.com

4.2 Standard Technical Parameter

Shell Enclosure :IP67,NEMA4, Exd II CT5

Standard:220VAC/1ph
Optional:110VAC/1ph, 380V/440V/3ph,50/60Hz, ±10%
Power
24VDC/110VDC/220VDC

Motor Asynchronous motor

Limit switch 2×Open/ Close, SPDT,250VAC 10A

Auxiliary limit switch 2×Open/ Close, SPDT,250VAC 10A

Torque switch Close/Open, each 1, SPDT,250VAC 10A Except AOX-Q-005/008/010

Travel 90°±10° 0°~270°

.co
Fail safe/
Internal-placed thermal protection, Open 115℃ ±5℃/Close 97℃ ± 5℃
Operating temperature

Indicator Continuous position indicator

Manual operate Declutching mechanism, operate by handwheel


es
Self-locking device Self-locking by worm and worm gear

Mechanical limit 2 × external adjustable stopper

Space heater 30W(110V/220VAC)


uid

Conduit entry 2 × PF 3/4”

Ambient temperature -20℃~+70℃

Lubrication Grease moly(EP type)

Material Steel, Aluminum alloy, Aluminum bronze,Polycarbonate


-g

Ambient humidity Max 90% RH Non-Condensing

Anti-vibration X Y Z 10g,0.2~34 Hz,30 minutes

External coating Dry powder, Epoxy polyester,high anti-corrosion


amll

-5-
All manuals and user guides at all-guides.com

4.3 Option Specification

No. Option scheme Remark

1 Explosion-proof actuator(Exd ⅡCT5) AOX-Q series

2 Water-proof actuator (IP68,10M,250HR) AOX-Q series

3 Potentiometer unit(1K-10K) AOX-Q series

4 Proportion control unit (control signal 4-20mA DC/1-5V/1-10V) AOX-Q series

Local control units (local control open/stop/close optional switch, local/remote


5 AOX-Q series
switch)

6 Travel 120°, 180°,270° AOX-Q series

7 Direct current motor (24VDC) AOX-Q series

Except
8 Torque switch (SPDT× 2 250VAC 10A)
AOX-Q-005/008/010
9 Electric current position sensor (output 4-20mA DC) AOX-Q series

10 Self-reset when power failure AOX-Q series

11 High temperature resistance actuator (-10℃~+100℃) AOX-Q series

12 Low temperature resistance actuator (-40℃~+70℃) AOX-Q series

13 Low speed actuator AOX-Q series

5.Structure
Electric actuators is make up of the following parts

◎ Housing: including shell and base

◎ Drive parts: asynchronous motor

◎ Driving mechanism:double worm and clutch

◎ Ratio control parts:separate with the mechanical parts, easy to debug

◎ Torque switch and limit switch parts

◎ Opening detected and feedback parts.

-6-
All manuals and user guides at all-guides.com

6. General Drawing
6.1 AOX-Q-005~120 Appearance and installation dimension

Picture 1 Unit: mm

Model X Y Z ΦA ΦB N-C ΦD N-E ΦF G H

AOX-Q-005 260 161 236 Φ90 Φ70 4-M8 Φ20 140 40

AOX-Q-008 260 161 236 Φ90 Φ70 4-M8 Φ20 140 40

AOX-Q-010 260 161 236 Φ90 Φ70 4-M8 Φ20 140 40

AOX-Q-015 351 227 270 Φ125 Φ102 4-M10 Φ70 4-M8 Φ22 140 45

AOX-Q-020 351 227 270 Φ125 Φ102 4-M10 Φ70 4-M8 Φ22 140 45

AOX-Q-030 367 242 290 Φ150 Φ125 4-M12 Φ102 4-M10 Φ35 140 55

AOX-Q-050 367 242 290 Φ150 Φ125 4-M12 Φ102 4-M10 Φ35 140 55

AOX-Q-060 367 242 290 Φ150 Φ125 4-M12 Φ102 4-M10 Φ35 140 55

AOX-Q-080 410 276 330 Φ180 Φ140 4-M16 Φ140 4-M12 Φ45 140 65

AOX-Q-120 410 276 330 Φ180 Φ140 4-M16 Φ140 4-M12 Φ45 140 65

-7-
All manuals and user guides at all-guides.com

6.1 AOX-Q-150~600 Appearance and installation dimension

Picture 2

Unit:mm

Model X Y Z ΦA ΦB N-C ΦD N-E ΦF G X1 X2

AOX-Q-150 410 276 330 Φ285 Φ165 4-M18 Φ140 4-M16 Φ45 140 454 696

AOX-Q-200 410 276 330 Φ285 Φ165 4-M18 Φ140 4-M16 Φ45 140 454 696

AOX-Q-300 410 276 330 Φ285 Φ165 4-M18 Φ140 4-M16 Φ45 140 454 696

AOX-Q-400 410 276 330 Φ285 Φ165 4-M18 Φ140 4-M16 Φ45 140 454 696

AOX-Q-500 410 276 330 Φ285 Φ165 4-M18 Φ140 4-M16 Φ45 140 454 696

AOX-Q-600 410 276 330 Φ285 Φ165 4-M18 Φ140 4-M16 Φ45 140 454 696

-8-
All manuals and user guides at all-guides.com

7. Wiring Diagram
7.1 AOX-Q-005~010 110/220VAC/50/60Hz,1Ph(on/off model)

Picture 3
7.2 AOX-Q-015~600 110/220VAC/50/60Hz,1Ph(on/off model)

Picture 4

-9-
All manuals and user guides at all-guides.com

7.3 AOX-Q-005~010 110/220VAC/50/60Hz,1Ph (modulating model)

.co
Picture 5
es
7.4 AOX-Q-015~600 110/220VAC/50/60Hz,1Ph (Standard modulating model)
uid
-g
amll

Picture 6

- 10 -
All manuals and user guides at all-guides.com

7.5 AOX-Q-015~600 380V/440V AC/50/60Hz,3Ph (External standard on/off model)

Picture 7

7.6 AOX-Q-015~600 110/220VAC/50/60Hz,1Ph (Intelligent on/off model)

Picture 8

- 11 -
All manuals and user guides at all-guides.com

8、Installation of Electric Actuators


8.1 Installation Sites

8.1.1 Notes for interior installation

◎Pls don’t install non-explosion-proof product to the place with explosive gas

◎When installing in the submerged or outdoor, please inform to us in advance

◎Please reserve space for cable repairing , manual operation.

8.1.2 Notes for outdoor installation

◎In order to avoid rain, direct sunlight and so on, a protective cover or enclosure IP68 is available

◎Please reserve space for cable repairing , manual operation.

8.1.3 Ambient temperature

◎Ambient temperature at -30℃~+60℃;

◎When Ambient temperature is below zero, need to install space heater.

8.1.4 Fluid temperature

When equipped with valve, the heat of the fluid will transfer to the body, then the body temperature will rise.

◎Standard bracket: when the fluid temperature is below +65℃, with standard bracket or without bracket;

◎ Intermediate temperate bracket: when the fluid temperature is over +65 ℃ , with intermediate temperate
bracket;

◎High-temperature bracket:when the fluid temperature is over +180℃, with high-temperature bracket.

8.2 Mounting with Valve

8.2.1Turn valve by hand and check the situation, then turn to full-closed position

8.2.2 The drive shaft is removable and solid before leaving factory (picture 9)

(Note:the size of drive shaft can be machined according to user’s requirement in


square or round)

8.2.3 Before mounting,attention to keep correspondence with the rotate direction


between electric actuator and valve

8.2.4 Fix the bracket on valve

8.2.5Turn electric actuator to full-closed position, fix valve stem and electric actuator drive shaft
Picture 9

by coupling and screws.

8.2.6 Put the electric actuator on bracket, and screw lightly

8.2.7Turn valve by manual to full-closed position and confirm at right situation .

8.2.8Turn electric actuator by manual to confirm non-eccentric, smooth movement, and attention no over travel!

Note: Decrease hysteresis of the coupling as far as possible.

- 12 -
All manuals and user guides at all-guides.com

8.3 Wire for Power

8.3.1 Remove the metallic plug and insert cables, pls use 3/4” explosion-proof joint in male thread or
explosion-proof flexible tube.

8.3.2 If the joint is mismatch to the actuator, will result in destroying the sealing that can not meet the enclosure
requirement.

8.3.3 Adopt water-proof arrangement when use wire pipe.

8.3.4 Take off shell cover,Press down the metallic dome in the hole of terminal by screwdriver, meanwhile, insert
the leadwire to lateral cavity. And then remove screwdriver.

Picture10 Picture 11

9. Debug Description
9.1 Adjustment of Mechanical Limit

Loosen the mechanical limit stoppers and locknuts, turn handwheel one circle, one side move the clutch
handle in left until occlude, continue to turn the handwheel until the actuator move to the full-close position. Turn
nuts until touch the fan-shaped gear, then turn two circles in anticlockwise direction, tight the locknuts at lastly. It
is the way to set the full-closed position of actuator , the same way to set full-open position.

Picture 12 Picture 13

- 13 -
All manuals and user guides at all-guides.com

9.2 Adjustment of Travel Limit(see picture14)

Move the electric actuator to the full-closed position by manual. And loosen locknut, turn cam (yellow open, red
close) until touch close limit switch (CLS) , then screw locknut. It’s the way to set the full-closed travel limit
position of electric actuator. Full-open position setting is the same way.

Picture 14

9.3 Adjustment of Potentiometer

Potentiometer, as output feedback signal , with 3 terminals, ② connect to


the slide arm of potentiometer. ①connect to the terminal whose resistance

decrease between the slide arm when actuator in opening movement.

③ connect to the terminal whose resistance decrease between the slide arm

when actuator when actuator in closing movement.

(Note: The potentiometer resistance should be not subzero、jump phenomenon.)

Turn valve to the full-open position by manual until limit switch move,
measure with a multimeter , adjust the resistance between ② and ① between 35 Ω ~ 60 Ω .If incorrect,
adjusting by turning the drive gear of potentiometer.

9.4 Adjustment of Over torque Protection Device

At nominal working pressure, adjust limit switch cam until touch switch contact roller. If actual torque to
drive valve over the rating torque, cam axle will rotate in clockwise/anticlockwise direction, and drive the cam to
process over torque movement.

9.5 Adjustment of Indicator Plate

Set valve to full-closed position, loosen screws on glass cover, turn the window glass to aline the indicator
direction mark with indicator hand. And then tight screws

(Note:the indicator plate has been set before leaving factory )

- 14 -
All manuals and user guides at all-guides.com

9.6 Proportion adjustable (PCU) Debug Description

9.6.1Technical parameters

① Input:

—Input signal:4~20mADC; 2~10VDC; 0~5VDC 0~10VDC; 1~5VDC

—Input resistance:250Ω

—Feedback signal:100Ω~10KΩ

② Output:

—Output signal:4~50mADC

—Load resistance: Max 750Ω

—Control output:Relay tip,250VAC,10A(Resistance load)

③ Resolution:Min 1/1000

.co
④ Adjustment of dead zone:0.1%~4.5%

⑤ Working temperature:-10℃~60℃

⑥ Relative humidity:Max 90%(Non-Condensed)

⑦ Position transform precision:±0.5%~±1.5%

⑧ Dielectric Vol.Proof:1500AC /min(Input to output,Power supply to each)


es
⑨ Shock or impact(X,Y,Z):10g

10. Running Test


uid

10.1 Manual Operation

Cut power before manual operation, turn the handwheel one circle, one side move the clutch handle in left
until occlude, continue to turn handwheel to decrease the opening (observe the opening by window glass).

10.2 Electric operation

◎Check the correspondence between the opening of actuator and valve by manual (full-open, full-closed) before
-g

electric operation;

◎Check the wiring,

◎After confirming the above situation, start electric operation


amll

- 15 -
All manuals and user guides at all-guides.com

★NOTE

①Check wiring diagram, power supply, control signal.

②Don’t change the internal wiring.

③If the power supply is 3 phase, check the rotating direction.

④Enable the electric actuator lies in a half on/off position by manual, turn on electricity and input open signal.

⑤If the electric actuator runs to the open direction, the wiring is correct.

⑥If the running direction is opposite, change 2 pieces wiring in 3.

11、Maintenance
Lubrication: Because special Mo-based grease is long life and well resistance, so no need to refuel;

Regular operation: Drive and check the device regularly when valve works infrequently.

★ Note: Debugging description of modulating model, please refer to the specification of the actuator controller