Va2-Yf00-p0cye-120007 Cause and Effect Diagram For Fire Protection System - Rev.a Update 2023.02.13
Va2-Yf00-p0cye-120007 Cause and Effect Diagram For Fire Protection System - Rev.a Update 2023.02.13
Owner’s Engineer
Contractor
Sub-Supplier
Project
VUNG ANG II THERMAL POWER PROJECT
Title
RECORD OF REVISION
Rev. Date Page Affected Description of Revision
CONTENTS
1. SCOPE ..................................................................................................................................................3
2. GENERAL............................................................................................................................................3
5. ABBREVIATIONS ..............................................................................................................................8
1. SCOPE
This document covers for engineering and performance for fire detection and alarm system of Vung
Ang II Thermal power plant project.
2. GENERAL
The purpose of the fire alarm and detection system is to guarantee a reliable and fault free early warning
system in the event of fire, so that orders for extinguishing the fire can be issued from a central point to
the permanently installed fire extinguishing equipment which is automatically activated.
The system shall be capable of non-interference, not sending false alarm, not being damaged partly or
wholly due to fire prior to sending alarm signals. The system shall be designed according to the
TCVN:5738-2021, NFPA:72-2022 and UL Listed.
4. REFERENCE DOCUMENTS
5. ABBREVIATIONS
ABBREVIATION MEANING
AC Alternate Current
ATEX Atmosphere Explosive
ATS Automatic Transfer Switch
BOM Bill of Material
CCN Customer Change Notice
CCTV Closed Circuit Television
CPU Central Processing Unit
DC Direct Current
EOL End of Line
EPCC Engineering, Procurement, Construction Contractor
Ex Explosion Proof
FAS Fire Alarm System
FACP Fire Alarm Control Panel
FAT Factory Acceptance Test
FOC Fiber Optic Cable
FOPP Fiber Optic Patch Panel
GA General Arrangment
HMI Human Machine Interface
IDC Initiating Device Circuit
IEC International Electrotechnical Commission
I/O Input/Output
IP Ingress Protection
IFAT Integrated Factory Acceptance Test
ISAT Integrated Site Acceptance Test
JB Junction Box
LAN Local Area Network
LCD Liquid Crystal Display
LHD Linear Heat Detector
LED Light Emitting Diode
VA2TP Vung Ang II Thermal Power LLC
MCB Miniatur Circuit Breaker
MCP Manual Call Point
ABBREVIATION MEANING
MCS Manual Call Station
MR Material requisition
NAC Notification Appliance Circuit
NEMA National Electrical Manufacturer’s Association
NFPA National Fire Protection Association
PDU Power Distribution Unit
PE Protective Earth
PKG Package
PVC Poly-Vinyl Chloride
SLC Signaling Line Circuit
SoW Scope of Work
SSS Safety Supervisory System
SUB Substation
UL Underwriter’s Laboratories
UPS Uninterruptible Power Supply
UV Ultraviolet
VLAN Virtual Local Area Network
VDI Vendor Document Index
WP Weatherproof
WSG Workstation Graphics
C&E Cause And Effect Diagram
(LAN Cable)
BUILDING
(Hardwire)
P0CYE32GW001
P0CYE31GW001
OUTPUT
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal From Local Fire Alarm Control Panel (LFACP) to DCS
General Note:
- Interface Signal to DCS by Dry-Contact (Hardwire): Details List of signals interface with DCS system by Dry-Contact (Hardwire) will be submitted on other document.
- Interface Signal to DCS by Mobus TCP/IP (LAN Cable): Details List of signals interface with DCS system by Mobus TCP/IP (LAN Cable) will be submited on other document.
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
General Zone/ ROOM
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
General Zone/ Room
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
General Zone/ ROOM
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
General Zone/ ROOM
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
General Zone/ ROOM
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
General Zone/ ROOM
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
SUPERVISED OUTPUTS
FAILURE
DATE
PASS
DESCRIPTION INPUT
-
INPUT
Common Signal
General Note:
Solenoid valve
OUTPUT
P0SGK02GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK02GH102
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK02GH103
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK02GH104
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK02GH105
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK02GH106
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK02GH109
INPUT
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK02GH107
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK02GH108
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK02GH110
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK02GH111
INPUT
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGJ01GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGJ01GH102
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGJ01GH103
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
INPUT
P0SGJ01GH104
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGJ01GH105
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGJ01GH106
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGJ01GH107
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
INPUT
P0SGJ01GH108
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK25GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK25GH102
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK08GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK08GH102
INPUT
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK08GH103
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK08GH104
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK42GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK42GH102
INPUT
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK42GH103
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK42GH104
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK42GH105
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK42GH106
INPUT
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK18GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK18GH102
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK09GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK51GH101
INPUT
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK51GH102
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK23GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK23GH102
INPUT
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK23GH103
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK43GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK43GH102
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK43GH103
INPUT
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK48GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK11GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK11GH102
INPUT
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK11GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK29GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK32GH101
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.
Solenoid valve
OUTPUT
P0SGK03GH101
INPUT
FAILURE
PASS
DATE
DESCRIPTION INPUT
-
INPUT
Input Signal
Discharged Switch X X X X X X X X X
Common Signal
General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.