You are on page 1of 120

FOR REVIEW

A 13.02.2023 V.H.QUANG N.V.NAM Y.S. IM FIRST ISSUE


Rev Date Prepared Checked Approved Details of Revision
Owner

VUNG ANG II THERMAL POWER LLC

Owner’s Engineer

TOKYO ELECTRIC POWER SERVICE Co., Ltd.

Contractor

DOOSAN ENERBILITY AND SAMSUNG C&T


JOINT VENTURE

Sub-Supplier

Project
VUNG ANG II THERMAL POWER PROJECT

Title

CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION


SYSTEM

Document No. Identification No. Rev. Page-No.


VA2-YF00-P0CYE-120007 - A 119
CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

RECORD OF REVISION
Rev. Date Page Affected Description of Revision

A 13.02.2023 - FIRST ISSUE

Rev. A Page 1 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

CONTENTS
1. SCOPE ..................................................................................................................................................3

2. GENERAL............................................................................................................................................3

3. CODE AND STANDARDS .................................................................................................................3

4. REFERENCE DOCUMENTS ............................................................................................................4

5. ABBREVIATIONS ..............................................................................................................................8

6. CAUSE AND EFFECT DIAGRAM LIST ......................................................................................10

7. CAUSE AND EFFECT DIAGRAM. ...............................................................................................15

Rev. A Page 2 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

1. SCOPE
This document covers for engineering and performance for fire detection and alarm system of Vung
Ang II Thermal power plant project.

2. GENERAL
The purpose of the fire alarm and detection system is to guarantee a reliable and fault free early warning
system in the event of fire, so that orders for extinguishing the fire can be issued from a central point to
the permanently installed fire extinguishing equipment which is automatically activated.
The system shall be capable of non-interference, not sending false alarm, not being damaged partly or
wholly due to fire prior to sending alarm signals. The system shall be designed according to the
TCVN:5738-2021, NFPA:72-2022 and UL Listed.

3. CODE AND STANDARDS


The fire detection systems shall provide coverage of all the Facility and shall comply with NFPA codes
(or equivalent) in addition to all statutory and local authority requirements including but not limited to
following standards. Even by for items covered the Vietnamese standards, if the NFPA code
requirements is more onerous then the same shall be followed to comply with NFPA codes in addition
to all statutory and local authority requirements. Wherever local standards are preferred in lieu of NFPA
standards, those shall be approved on case by case basis.

 TCVN 5738 -2021: Automatic fire alarm system - technical requirements.

 NFPA 72-2022: National Fire Alarm and Signaling Code.

 UL Listing and FM approval.

Rev. A Page 3 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

4. REFERENCE DOCUMENTS

DOCUMENT NUMBER TITLE


SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128101
ALARM SYSTEM - TURBINE HOUSE
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128152
ALARM SYSTEM - MAIN TRANSFORMER
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128153
ALARM SYSTEM - AUX. TRANSFORMER
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128154
ALARM SYSTEM - EDG DAY TANK
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128102
ALARM SYSTEM - CENTRAL CONTROL BUILDING
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128103
ALARM SYSTEM - H2 GENERATION PLANT
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128105
ALARM SYSTEM - SERVICE GAS SHELTER
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128120
ALARM SYSTEM - CPP REGENERATION FACILITY
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128151
ALARM SYSTEM - AUXILIARY BOILER
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128158
ALARM SYSTEM - CLEAN & DIRTY OIL TANK
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128121
ALARM SYSTEM - FIRE FIGHTING PUMP HOUSE
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128104
ALARM SYSTEM - DANGEROUS GOOD STORE
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128125
ALARM SYSTEM - ADMINISTRATION BUILDING
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128126
ALARM SYSTEM - CANTEEN
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128131
ALARM SYSTEM - CLINIC & FIRE STATION
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128127
ALARM SYSTEM - CAR GARAGE

Rev. A Page 4 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

DOCUMENT NUMBER TITLE


SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128128
ALARM SYSTEM - PRODUCTION SERVICE BUILDING
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128129
ALARM SYSTEM - WORKSHOP
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128130
ALARM SYSTEM - WAREHOUSE
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128132 ALARM SYSTEM - MAIN GATE HOUSE & TRAINING
CENTER
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128133
ALARM SYSTEM - REAR GATE HOUSE
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128116
ALARM SYSTEM - WTB & DEHYDRATOR BUILDING
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128112 ALARM SYSTEM - CHEMICAL DOSING SHELTER FOR
WT SYSTEM
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128117 ALARM SYSTEM - WWT ELECTRICAL & DEHYDRATOR
BUILDING
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128123
ALARM SYSTEM - CHLORINATION BUILDING
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128124 ALARM SYSTEM - ELECTRICAL BUILIDNG FOR CW
AREA
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128108 ALARM SYSTEM - COAL HANDLING ELECTRICAL
BUILDING
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128109 ALARM SYSTEM - HEAVY EQUIPMENT AND COAL
MOBILES GARAGE
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128110
ALARM SYSTEM - COAL STORAGE SHED
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128176
ALARM SYSTEM - COAL TRANSFER TOWER 01

Rev. A Page 5 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

DOCUMENT NUMBER TITLE


SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128177
ALARM SYSTEM - COAL TRANSFER TOWER 02
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128178 ALARM SYSTEM - COAL TRANSFER TOWER 03
(SCREEN HOUSE)
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128179
ALARM SYSTEM - COAL TRANSFER TOWER 04
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128195
ALARM SYSTEM - COAL CONVEYOR TT4 to BOILER
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128192
ALARM SYSTEM - COAL CONVEYOR TT1 to TT2
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128193
ALARM SYSTEM - COAL CONVEYOR TT2 to TT3
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128194
ALARM SYSTEM - COAL CONVEYOR TT3 to TT4
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YD00-P0CYE-128191
ALARM SYSTEM - COAL CONVEYOR JETTY TO TT1
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YU02-P0CYE-128145 ALARM SYSTEM - FLY ASH TRANSPORT AIR
COMPRESSOR SHELTER
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YU02-P0CYE-128147
ALARM SYSTEM - AMMONIA STORAGE SHELTER
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YU02-P1CYE-128156
ALARM SYSTEM - BOILER #1
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YU02-P2CYE-128157
ALARM SYSTEM - BOILER #2
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YU02-P0CYE-128142 ALARM SYSTEM - EP & ASH ELECTRICAL & CONTROL
BUILDING
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YU02-P0CYE-128143
ALARM SYSTEM - FGD ELECTRICAL BUILDING
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YU02-P0CYE-128155
ALARM SYSTEM - LDO STORAGE TANK

Rev. A Page 6 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

DOCUMENT NUMBER TITLE


SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YU02-P0CYE-128159 ALARM SYSTEM - LDO PUMP STAION & FOAM
STATION
SINGLE LINE & LAYOUT FOR FIRE DETECTION AND
VA2-YU02-P0CYE-128160
ALARM SYSTEM - LDO TRUCK UNLOADING STATION
OVERALL BLOCK DIAGRAM FOR FIRE DETECTION
VA2-YU03-P0CYE-120005
AND ALARM SYSTEM
WIRING DIAGRAM FOR FIRE DETECTION AND ALARM
VA2-YV02-P0CYE-120006
SYSTEM
MIMIC BOARD FOR FIRE DETECTION AND ALARM
VA2-YD00-P0CYE-120013
SYSTEM

Rev. A Page 7 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

5. ABBREVIATIONS
ABBREVIATION MEANING
AC Alternate Current
ATEX Atmosphere Explosive
ATS Automatic Transfer Switch
BOM Bill of Material
CCN Customer Change Notice
CCTV Closed Circuit Television
CPU Central Processing Unit
DC Direct Current
EOL End of Line
EPCC Engineering, Procurement, Construction Contractor
Ex Explosion Proof
FAS Fire Alarm System
FACP Fire Alarm Control Panel
FAT Factory Acceptance Test
FOC Fiber Optic Cable
FOPP Fiber Optic Patch Panel
GA General Arrangment
HMI Human Machine Interface
IDC Initiating Device Circuit
IEC International Electrotechnical Commission
I/O Input/Output
IP Ingress Protection
IFAT Integrated Factory Acceptance Test
ISAT Integrated Site Acceptance Test
JB Junction Box
LAN Local Area Network
LCD Liquid Crystal Display
LHD Linear Heat Detector
LED Light Emitting Diode
VA2TP Vung Ang II Thermal Power LLC
MCB Miniatur Circuit Breaker
MCP Manual Call Point

Rev. A Page 8 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

ABBREVIATION MEANING
MCS Manual Call Station
MR Material requisition
NAC Notification Appliance Circuit
NEMA National Electrical Manufacturer’s Association
NFPA National Fire Protection Association
PDU Power Distribution Unit
PE Protective Earth
PKG Package
PVC Poly-Vinyl Chloride
SLC Signaling Line Circuit
SoW Scope of Work
SSS Safety Supervisory System
SUB Substation
UL Underwriter’s Laboratories
UPS Uninterruptible Power Supply
UV Ultraviolet
VLAN Virtual Local Area Network
VDI Vendor Document Index
WP Weatherproof
WSG Workstation Graphics
C&E Cause And Effect Diagram

Rev. A Page 9 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

6. CAUSE AND EFFECT DIAGRAM LIST


No. Document Description Panel KKS No. Page
1 C&E for Main Fire Alarm Control Panel (MFACP). P0CYE02GG001 Page 16
C&E for Local Fire Alarm Control Panel (LFACP-01) at Central
2 P0CYE02GG002 Page 17
Control Building.
C&E for Local Fire Alarm Control Panel (LFACP-01) at
3 P0CYE02GG002 Page 18
Emergency Diesel Generator.
C&E for Local Fire Alarm Control Panel (LFACP-01) at Boiler
4 P0CYE02GG002 Page 19
#1.
C&E for Local Fire Alarm Control Panel (LFACP-01) at Boiler
5 P0CYE02GG002 Page 20
#2.
C&E for Local Fire Alarm Control Panel (LFACP-01) at
6 P0CYE02GG002 Page 21
Turbine House.
C&E for Local Fire Alarm Control Panel (LFACP-02) at
7 P0CYE25GG001 Page 22
Administration Building.
C&E for Local Fire Alarm Control Panel (LFACP-02) at Clinic
8 P0CYE25GG001 Page 23
& Fire Station.
C&E for Local Fire Alarm Control Panel (LFACP-02) at
9 P0CYE25GG001 Page 24
Workshop.
C&E for Local Fire Alarm Control Panel (LFACP-02) at
10 P0CYE25GG001 Page 25
Canteen.
C&E for Local Fire Alarm Control Panel (LFACP-02) at Car
11 P0CYE25GG001 Page 26
Garage.
C&E for Local Fire Alarm Control Panel (LFACP-02) at
12 P0CYE25GG001 Page 27
Warehouse.
C&E for Local Fire Alarm Control Panel (LFACP-02) at Fuel
13 P0CYE25GG001 Page 28
Oil Pump House.
C&E for Local Fire Alarm Control Panel (LFACP-02) at LDO
14 P0CYE25GG001 Page 29
Storage Tanks.
C&E for Local Fire Alarm Control Panel (LFACP-02) at
15 P0CYE25GG001 Page 30
Auxiliary Boiler.
C&E for Local Fire Alarm Control Panel (LFACP-02) at Main
16 P0CYE25GG001 Page 31
gate House & Training.
C&E for Local Fire Alarm Control Panel (LFACP-04) at Fire
17 P0CYE21GG001 Page 32
Fighting Pump House.
C&E for Local Fire Alarm Control Panel (LFACP-04) at
18 P0CYE21GG001 Page 33
Dangerous Goods Store.
C&E for Local Fire Alarm Control Panel (LFACP-04) at Heavy
19 P0CYE21GG001 Page 34
Equipment and Coal Mobiles Garage.
C&E for Local Fire Alarm Control Panel (LFACP-04) at Main
20 P0CYE21GG001 Page 35
Transformer Unit #1.
C&E for Local Fire Alarm Control Panel (LFACP-04) at Aux.
21 P0CYE21GG001 Page 36
Transformer #1A&B.

Rev. A Page 10 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

No. Document Description Panel KKS No. Page


C&E for Local Fire Alarm Control Panel (LFACP-04) at Main
22 P0CYE21GG001 Page 37
Transformer Unit #2.
C&E for Local Fire Alarm Control Panel (LFACP-04) at Aux.
23 P0CYE21GG001 Page 38
Transformer #2A&B.
C&E for Local Fire Alarm Control Panel (LFACP-04) at Dirty
24 P0CYE21GG001 Page 39
Oil Drain & Transfer Lubricating Oil Storage Tank.
C&E for Local Fire Alarm Control Panel (LFACP-04) at
25 P0CYE21GG001 Page 40
Hydrogen Generation Plant.
C&E for Local Fire Alarm Control Panel (LFACP-04) at Service
26 P0CYE21GG001 Page 41
Gas Shelter.
C&E for Local Fire Alarm Control Panel (LFACP-04) at CPP
27 P0CYE21GG001 Page 42
Regeneration Facility.
C&E for Local Fire Alarm Control Panel (LFACP-05) at WWT
28 P0CYE17GG001 Page 43
Electrical & Dehydrator Building.
C&E for Local Fire Alarm Control Panel (LFACP-05) at
29 P0CYE17GG001 Page 44
Chemical Dosing Shelter for WT System.
C&E for Local Fire Alarm Control Panel (LFACP-05) at WTB
30 P0CYE17GG001 Page 45
& Dehydrator Building.
C&E for Local Fire Alarm Control Panel (LFACP-06) at Coal
31 P0CYE08GG001 Page 46
Handling Electrical Building.
C&E for Local Fire Alarm Control Panel (LFACP-06) at
32 P0CYE08GG001 Page 47
Transfer Tower 03 (Coal Screen House).
C&E for Local Fire Alarm Control Panel (LFACP-06) at Gate
33 P0CYE08GG001 Page 48
House Rear.
C&E for Local Fire Alarm Control Panel (LFACP-06) at
34 P0CYE08GG001 Page 49
Transfer Tower 04.
C&E for Local Fire Alarm Control Panel (LFACP-06) at
35 P0CYE08GG001 Page 50
Conveyor Transfer Tower 03 To Tower 04.
C&E for Local Fire Alarm Control Panel (LFACP-06) at As
36 P0CYE08GG001 Page 51
Fired Sampling House.
C&E for Local Fire Alarm Control Panel (LFACP-06) at
37 P0CYE08GG001 Page 52
Ammonia Storage Shelter.
C&E for Local Fire Alarm Control Panel (LFACP-07) at
38 P0CYE24GG001 Page 53
Electrical Building for CW Area.
C&E for Local Fire Alarm Control Panel (LFACP-07) at
39 P0CYE24GG001 Page 54
Chlorination Building.
C&E for Local Fire Alarm Control Panel (LFACP-07) at
40 P0CYE24GG001 Page 55
Cooling Water Pumping Station.
C&E for Local Fire Alarm Control Panel (LFACP-07) at SW
41 P0CYE24GG001 Page 56
Intake Pump Station.
C&E for Local Fire Alarm Control Panel (LFACP-08) at Coal
42 P0CYE76GG001 Page 57
Transfer Tower 01.

Rev. A Page 11 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

No. Document Description Panel KKS No. Page


C&E for Local Fire Alarm Control Panel (LFACP-08) at Coal
43 P0CYE76GG001 Page 58
Storage Area #1.
C&E for Local Fire Alarm Control Panel (LFACP-08) at Coal
44 P0CYE76GG001 Page 59
Transfer Tower 02.
C&E for Local Fire Alarm Control Panel (LFACP-08) at Coal
45 P0CYE76GG001 Page 60
Storage Area #2.
C&E for Local Fire Alarm Control Panel (LFACP-08) at Coal
46 P0CYE76GG001 Page 61
Conveyor Transfer Jetty to Transfer Tower 01 (2).
C&E for Local Fire Alarm Control Panel (LFACP-09) at Coal
47 P0CYE48GG001 Page 62
Jetty Control Building.
C&E for Local Fire Alarm Control Panel (LFACP-09) at Coal
48 P0CYE48GG001 Page 63
Conveyor Transfer Jetty to Transfer Tower 01 (1).
C&E for Local Fire Alarm Control Panel (LFACP-10) at ESP &
49 P0CYE42GG001 Page 64
ASH Electrical & Control Building.
C&E for Local Fire Alarm Control Panel (LFACP-10) at FGD
50 P0CYE42GG001 Page 65
Electrical Building.
C&E for Local Fire Alarm Control Panel (LFACP-10) at Fly
51 P0CYE42GG001 Page 66
ASH Transfer Blower Shelter, Compressor.
C&E for Local Fire Alarm Control Panel (LFACP-10) at ASH
52 P0CYE42GG001 Page 67
Slurry Pump Shelter.
C&E for Local Fire Alarm Control Panel (LFACP-10) at CEMS
53 P0CYE42GG001 Page 68
Container.
C&E for Local Fire Alarm Control Panel (LFACP-10) at
54 P0CYE42GG001 Page 69
Electrostatic Precipitator #1 (A&B).
C&E for Local Fire Alarm Control Panel (LFACP-10) at
55 P0CYE42GG001 Page 70
Electrostatic Precipitator #2 (A&B).
C&E for Fire Suppression Panel (FM-200) at Central Control
56 P0SGK02GH101 Page 71
Building - DC&UPS Room.
C&E for Fire Suppression Panel (FM-200) at Central Control
57 P0SGK02GH102 Page 72
Building - Elec. Laboratory Room.
C&E for Fire Suppression Panel (FM-200) at Central Control
58 P0SGK02GH103 Page 73
Building - I&C Inspection Room.
C&E for Fire Suppression Panel (FM-200) at Central Control
59 P0SGK02GH104 Page 74
Building - Battery Room.
C&E for Fire Suppression Panel (FM-200) at Central Control
60 P0SGK02GH105 Page 75
Building - SWGR Room.
C&E for Fire Suppression Panel (FM-200) at Central Control
61 P0SGK02GH106 Page 76
Building - Main Control Room.
C&E for Fire Suppression Panel (FM-200) at Central Control
62 P0SGK02GH109 Page 77
Building - Computer Room.
C&E for Fire Suppression Panel (FM-200) at Central Control
63 P0SGK02GH107 Page 78
Building - Electronic 1 Room.

Rev. A Page 12 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

No. Document Description Panel KKS No. Page


C&E for Fire Suppression Panel (FM-200) at Central Control
64 P0SGK02GH108 Page 79
Building - Electronic 2 Room.
C&E for Fire Suppression Panel (FM-200) at Central Control
65 P0SGK02GH110 Page 80
Building - Communication Room.
C&E for Fire Suppression Panel (FM-200) at Central Control
66 P0SGK02GH111 Page 81
Building - Tariff Room.
C&E for Fire Suppression Panel (CO2) at Turbine House -
67 P0SGJ01GH101 Page 82
Switchgear 1 Room.
C&E for Fire Suppression Panel (CO2) at Turbine House -
68 P0SGJ01GH102 Page 83
Cable Trench Room.
C&E for Fire Suppression Panel (CO2) at Turbine House - MCC
69 P0SGJ01GH103 Page 84
Room (8 - 10).
C&E for Fire Suppression Panel (CO2) at Turbine House - MCC
70 P0SGJ01GH104 Page 85
Room (20 - 22).
C&E for Fire Suppression Panel (CO2) at Turbine House -
71 P0SGJ01GH105 Page 86
Excitation Panel Room (8 - 10).
C&E for Fire Suppression Panel (CO2) at Turbine House -
72 P0SGJ01GH106 Page 87
Excitation Panel Room (20 - 22).
C&E for Fire Suppression Panel (CO2) at Turbine House -
73 P0SGJ01GH107 Page 88
Switchgear 2 Room.
C&E for Fire Suppression Panel (CO2) at Turbine House - Local
74 P0SGJ01GH108 Page 89
Electrical Room.
C&E for Fire Suppression Panel (FM-200) at Administration
75 P0SGK25GH101 Page 90
Building - Server & Telecom Room.
C&E for Fire Suppression Panel (FM-200) at Administration
76 P0SGK25GH102 Page 91
Building - Electrical Room.
C&E for Fire Suppression Panel (FM-200) at Coal Handling
77 P0SGK08GH101 Page 92
Electrical Building - Switchgear Room.
C&E for Fire Suppression Panel (FM-200) at Coal Handling
78 P0SGK08GH102 Page 93
Electrical Building - Control Room.
C&E for Fire Suppression Panel (FM-200) at Coal Handling
79 P0SGK08GH103 Page 94
Electrical Building - Computer Room.
C&E for Fire Suppression Panel (FM-200) at Coal Handling
80 P0SGK08GH104 Page 95
Electrical Building - Battery Room.
C&E for Fire Suppression Panel (FM-200) at ESP & ASH
81 P0SGK42GH101 Page 96
Electrical & Control Building - Battery Room.
C&E for Fire Suppression Panel (FM-200) at ESP & ASH
82 P0SGK42GH102 Page 97
Electrical & Control Building - DC&UPS Room.
C&E for Fire Suppression Panel (FM-200) at ESP & ASH
83 P0SGK42GH103 Page 98
Electrical & Control Building - FASH Control Room.
C&E for Fire Suppression Panel (FM-200) at ESP & ASH
84 P0SGK42GH104 Page 99
Electrical & Control Building - SWGR Room.

Rev. A Page 13 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

No. Document Description Panel KKS No. Page


C&E for Fire Suppression Panel (FM-200) at ESP & ASH
85 P0SGK42GH105 Page 100
Electrical & Control Building - ESP Control Room.
C&E for Fire Suppression Panel (FM-200) at ESP & ASH
86 P0SGK42GH106 Page 101
Electrical & Control Building - ESP SWGR Room.
C&E for Fire Suppression Panel (FM-200) at WWT Electrical &
87 P0SGK18GH101 Page 102
Dehydrator Building - Control & PLC Room.
C&E for Fire Suppression Panel (FM-200) at WWT Electrical &
88 P0SGK18GH102 Page 103
Dehydrator Building - MCC Room.
C&E for Fire Suppression Panel (FM-200) at Heavy Equipment
89 P0SGK09GH101 Page 104
and Coal Mobiles Garage - MCC Room.
C&E for Fire Suppression Panel (FM-200) at Auxiliary Boiler -
90 P0SGK51GH101 Page 105
Server & Telecom Room.
C&E for Fire Suppression Panel (FM-200) at Auxiliary Boiler -
91 P0SGK51GH102 Page 106
Electrical Room.
C&E for Fire Suppression Panel (FM-200) at Chlorination
92 P0SGK23GH101 Page 107
Building - Control Room.
C&E for Fire Suppression Panel (FM-200) at Chlorination
93 P0SGK23GH102 Page 108
Building - TR/RE Room.
C&E for Fire Suppression Panel (FM-200) at Chlorination
94 P0SGK23GH103 Page 109
Building - MCC Room.
C&E for Fire Suppression Panel (FM-200) at FGD Electrical
95 P0SGK43GH101 Page 110
Building - SWGR & Electrical Room.
C&E for Fire Suppression Panel (FM-200) at FGD Electrical
96 P0SGK43GH102 Page 111
Building - Electrical Room.
C&E for Fire Suppression Panel (FM-200) at FGD Electrical
97 P0SGK43GH103 Page 112
Building - Control Room.
C&E for Fire Suppression Panel (FM-200) at Coal Jetty Control
98 P0SGK48GH101 Page 113
Building - Control/Electrical Room.
C&E for Fire Suppression Panel (FM-200) at WTB &
99 P0SGK11GH101 Page 114
Dehydrator Building - Electrical Room.
C&E for Fire Suppression Panel (FM-200) at WTB &
100 P0SGK11GH102 Page 115
Dehydrator Building - Control & PLC Room.
C&E for Fire Suppression Panel (FM-200) at Emergency Diesel
101 P0SGK11GH101 Page 116
Generator - EDG Room.
C&E for Fire Suppression Panel (FM-200) at Workshop - MCC
102 P0SGK29GH101 Page 117
Room.
C&E for Fire Suppression Panel (FM-200) at Main gate House
103 P0SGK32GH101 Page 118
& Training - Control/Electrical Room.
C&E for Fire Suppression Panel (FM-200) at Hydrogen
104 P0SGK03GH101 Page 119
Generation Plant - Local PLC Room.

Rev. A Page 14 of 119


CAUSE AND EFFECT DIAGRAM FOR FIRE PROTECTION SYSTEM
VA2-YF00-P0CYE-120007

7. CAUSE AND EFFECT DIAGRAM.

Rev. A Page 15 of 119


PANEL NAME: MAIN FIRE ALARM CONTROL PANEL (MFACP); KKS NO. : P0CYE02GG001
PANEL'S LOCATION : CENTRAL CONTROL BUILDING
CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: THE WHOLE FACTORY FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: THE WHOLE FACTORY Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer

Interface Signal to DCS by Mobus TCP/IP


MIMIC PANEL AT CENTRAL CONTROL
P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Time Synchronization With Time Server

Time Synchronization With Time Server

Time Synchronization With Time Server

Time Synchronization With Time Server


DESCRIPTION OUTPUT

Interface Signal to DCS by Dry-Contact


Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display

Led Status Show On Mimic Panel

P0CYE02GG001 LOCAL FIRE ALARM PANEL


FUNTIONAL TEST

Interface Signal to DCS


ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer

(LAN Cable)
BUILDING

(Hardwire)
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

Common Signal Fire Alarm System

Any Fire Signal from Fire Alarm System - X X X X X X X X X X X X X X

Any Trouble Signal from Fire Alarm System - X X X X X X X X X X X X X X

Any Supervisory Signal from Fire Alarm System - X X X X X X X X X X X X X X

Common Signal From Local Fire Alarm Control Panel (LFACP) to DCS

Common Fire Alarm Signal from each LFACP P0CYE02GG002, X X X X X X X X X X X X X X X X


P0CYE25GG001,
P0CYE21GG001,
Common Trouble Alarm Signal from each LFACP P0CYE17GG001, X X X X X X X X X X X X X X X
P0CYE08GG001,
P0CYE24GG001,
Common Supervisory Alarm Signal from each LFACP X X X X X X X X X X X X X X X
P0CYE76GG001,
P0CYE48GG001,
Common Discharged Signal from each LFACP P0CYE42GG001 X X X X X X X X X X X X X X X
(Discharged from FM-200, CO2, FOAM, Water Spray, Sprinkler System)

Input From Other System

Time Synchronization Signal From Time Server (SNTP/NTP protocol) - X X X X

General Note:
- Interface Signal to DCS by Dry-Contact (Hardwire): Details List of signals interface with DCS system by Dry-Contact (Hardwire) will be submitted on other document.
- Interface Signal to DCS by Mobus TCP/IP (LAN Cable): Details List of signals interface with DCS system by Mobus TCP/IP (LAN Cable) will be submited on other document.

Rev. A Page 16 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-01); KKS NO. : P0CYE02GG002
PANEL'S LOCATION : CENTRAL CONTROL BUILDING
CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CENTRAL CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE02GG002 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL
DESCRIPTION OUTPUT

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK02GH101 FM-200 2Nd Signal (B) to FSCP

P0SGK02GH102 FM-200 2Nd Signal (B) to FSCP

P0SGK02GH103 FM-200 2Nd Signal (B) to FSCP

P0SGK02GH104 FM-200 2Nd Signal (B) to FSCP

P0SGK02GH105 FM-200 2Nd Signal (B) to FSCP

P0SGK02GH106 FM-200 2Nd Signal (B) to FSCP

P0SGK02GH107 FM-200 2Nd Signal (B) to FSCP

P0SGK02GH108 FM-200 2Nd Signal (B) to FSCP

P0SGK02GH109 FM-200 2Nd Signal (B) to FSCP

P0SGK02GH110 FM-200 2Nd Signal (B) to FSCP

P0SGK02GH111 FM-200 2Nd Signal (B) to FSCP


P0SGK02GH102 FM-200 1St Signal (A) to FSCP

P0SGK02GH103 FM-200 1St Signal (A) to FSCP

P0SGK02GH104 FM-200 1St Signal (A) to FSCP

P0SGK02GH105 FM-200 1St Signal (A) to FSCP

P0SGK02GH106 FM-200 1St Signal (A) to FSCP

P0SGK02GH107 FM-200 1St Signal (A) to FSCP

P0SGK02GH108 FM-200 1St Signal (A) to FSCP

P0SGK02GH109 FM-200 1St Signal (A) to FSCP

P0SGK02GH110 FM-200 1St Signal (A) to FSCP

P0SGK02GH111 FM-200 1St Signal (A) to FSCP


Interface With FM-200 System

P0SGK02GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT
General Zone/ ROOM

Addressable Smoke Detector X X X X X X X X X X X X X X

Addressable Heat Detector X X X X X X X X X X X X X X

Addressable VESDA Detector X X X X X X X X X X X X X X

Addressable Duct Smoke Detector X X X X X X X X X X X X X X

Addressable Manual Call Point X X X X X X X X X X X X X X

Analog Module for Gas Detector X X X X X X X X X X X X X X

Monitor Module for Linear Heat Detector X X X X X X X X X X X X X X

Monitor Module for Pressuare Switch X X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage X X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage X X X X X X X X X X X X X X

Specical Zone/ ROOM

Addressable Smoke Detector at DC & UPS Room - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at DC & UPS Room - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Elec Laborator Room - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Elec Laborator Room - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at I&C Inspection Room - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at I&C Inspection Room - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Battery Room - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Battery Room - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Switchgear Room - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Switchgear Room - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Main Control Room - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Main Control Room - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Computer Room - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Computer Room - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Electronic Room 1 - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Electronic Room 1 - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Electronic Room 2 - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Electronic Room 2 - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Communication Room - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Communication Room - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Tariff Room - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Tariff Room - Group B X X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 17 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-01); KKS NO. : P0CYE02GG002
PANEL'S LOCATION : CENTRAL CONTROL BUILDING
CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: EMERGENCY DIESEL GENERATOR FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE02GG002 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK11GH101 FM-200 2Nd Signal (B) to FSCP


P0SGK11GH101 FM-200 1St Signal (A) to FSCP
Interface Signal Actived to PAS
Interface With Other System

Interface With Other System


Interface With CO2 System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector X X X X X X X X X X X X X X

Addressable Heat Detector X X X X X X X X X X X X X X

Addressable VESDA Detector X X X X X X X X X X X X X X

Addressable Duct Smoke Detector X X X X X X X X X X X X X X

Addressable Manual Call Point X X X X X X X X X X X X X X

Analog Module for Gas Detector X X X X X X X X X X X X X X

Monitor Module for Linear Heat Detector X X X X X X X X X X X X X X

Monitor Module for Pressuare Switch X X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage X X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage X X X X X X X X X X X X X X

Specical Zone/ Room

Addressable Smoke Detector at EDG Room - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at EDG Room - Group B X X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 18 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-01); KKS NO. : P0CYE02GG002
PANEL'S LOCATION : CENTRAL CONTROL BUILDING
CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: BOILER #1 FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE02GG002 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector X X X X X X X X X X X X X X

Addressable Heat Detector X X X X X X X X X X X X X X

Addressable VESDA Detector X X X X X X X X X X X X X X

Addressable Duct Smoke Detector X X X X X X X X X X X X X X

Addressable Manual Call Point X X X X X X X X X X X X X X

Analog Module for Gas Detector X X X X X X X X X X X X X X

Monitor Module for Linear Heat Detector X X X X X X X X X X X X X X

Monitor Module for Pressuare Switch X X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage X X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 19 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-01); KKS NO. : P0CYE02GG002
PANEL'S LOCATION : CENTRAL CONTROL BUILDING
CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: BOILER #2 FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE02GG002 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector X X X X X X X X X X X X X X

Addressable Heat Detector X X X X X X X X X X X X X X

Addressable VESDA Detector X X X X X X X X X X X X X X

Addressable Duct Smoke Detector X X X X X X X X X X X X X X

Addressable Manual Call Point X X X X X X X X X X X X X X

Analog Module for Gas Detector X X X X X X X X X X X X X X

Monitor Module for Linear Heat Detector X X X X X X X X X X X X X X

Monitor Module for Pressuare Switch X X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage X X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 20 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-01); KKS NO. : P0CYE02GG002
PANEL'S LOCATION : CENTRAL CONTROL BUILDING
CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: TURBINE HOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE02GG002 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGJ01GH101 FM-200 2Nd Signal (B) to FSCP

P0SGJ01GH102 FM-200 2Nd Signal (B) to FSCP

P0SGJ01GH103 FM-200 2Nd Signal (B) to FSCP

P0SGJ01GH104 FM-200 2Nd Signal (B) to FSCP

P0SGJ01GH105 FM-200 2Nd Signal (B) to FSCP

P0SGJ01GH106 FM-200 2Nd Signal (B) to FSCP

P0SGJ01GH107 FM-200 2Nd Signal (B) to FSCP

P0SGJ01GH108 FM-200 2Nd Signal (B) to FSCP


P0SGJ01GH102 FM-200 1St Signal (A) to FSCP

P0SGJ01GH103 FM-200 1St Signal (A) to FSCP

P0SGJ01GH104 FM-200 1St Signal (A) to FSCP

P0SGJ01GH105 FM-200 1St Signal (A) to FSCP

P0SGJ01GH106 FM-200 1St Signal (A) to FSCP

P0SGJ01GH107 FM-200 1St Signal (A) to FSCP

P0SGJ01GH108 FM-200 1St Signal (A) to FSCP


P0SGJ01GH101 FM-200 1St Signal (A) to FSCP
Interface Signal Actived to PAS
Interface With Other System

Interface With CO2 System


FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT
General Zone/ Room

Addressable Smoke Detector X X X X X X X X X X X X X X

Addressable Heat Detector X X X X X X X X X X X X X X

Addressable VESDA Detector X X X X X X X X X X X X X X

Addressable Duct Smoke Detector X X X X X X X X X X X X X X

Addressable Manual Call Point X X X X X X X X X X X X X X

Analog Module for Gas Detector X X X X X X X X X X X X X X

Monitor Module for Linear Heat Detector X X X X X X X X X X X X X X

Monitor Module for Pressuare Switch X X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage X X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage X X X X X X X X X X X X X X

Specical Zone/ Room

Addressable Smoke Detector at Switchgear Room 1 - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Switchgear Room 1 - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Cable Trench - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Cable Trench - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Mcc Room (8 - 10) - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Mcc Room (8 - 10) - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Mcc Room (20 - 22) - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Mcc Room (20 - 22) - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Excitation Panel Room (8 - 10) - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Excitation Panel Room (8 - 10) - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Excitation Panel Room (20 - 22) - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Excitation Panel Room (20 - 22) - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Switchgear Room 2 - Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Switchgear Room 2 - Group B X X X X X X X X X X X X X X X

Addressable Smoke Detector at Local Electrical Room- Group A X X X X X X X X X X X X X X X

Addressable Smoke Detector at Local Electrical Room- Group B X X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 21 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-02); KKS NO. : P0CYE25GG001

PANEL'S LOCATION : ADMINISTRATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ADMINISTRATION BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE25GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK25GH101 FM-200 2Nd Signal (B) to FSCP

P0SGK25GH102 FM-200 2Nd Signal (B) to FSCP


P0SGK25GH102 FM-200 1St Signal (A) to FSCP
Interface With FM-200 System

P0SGK25GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X X

Specical Zone/ Room

Addressable Smoke Detector at Server & Telecom Room - Group A - X X X X X X X X X X X X X X X

Addressable Smoke Detector at Server & Telecom Room - Group B - X X X X X X X X X X X X X X X

Addressable Smoke Detector at Electrical Room - Group A - X X X X X X X X X X X X X X X

Addressable Smoke Detector at Electrical Room - Group B - X X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 22 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-02); KKS NO. : P0CYE25GG001

PANEL'S LOCATION : ADMINISTRATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CLINIC & FIRE STATION FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE25GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 23 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-02); KKS NO. : P0CYE25GG001

PANEL'S LOCATION : ADMINISTRATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: WORKSHOP FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE25GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK29GH101 FM-200 2Nd Signal (B) to FSCP


Interface With FM-200 System

P0SGK29GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X X

Specical Zone/ Room

Addressable Smoke Detector at MCC Room - Group A - X X X X X X X X X X X X X X X

Addressable Smoke Detector at MCC Room - Group B - X X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 24 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-02); KKS NO. : P0CYE25GG001

PANEL'S LOCATION : ADMINISTRATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CANTEEN FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE25GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 25 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-02); KKS NO. : P0CYE25GG001

PANEL'S LOCATION : ADMINISTRATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CAR GARAGE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE25GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 26 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-02); KKS NO. : P0CYE25GG001

PANEL'S LOCATION : ADMINISTRATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: WAREHOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE25GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 27 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-02); KKS NO. : P0CYE25GG001

PANEL'S LOCATION : ADMINISTRATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: FUEL OIL PUMP HOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE25GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 28 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-02); KKS NO. : P0CYE25GG001

PANEL'S LOCATION : ADMINISTRATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: LDO STORAGE TANKS FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE25GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 29 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-02); KKS NO. : P0CYE25GG001

PANEL'S LOCATION : ADMINISTRATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: AUXILIARY BOILER FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE25GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK51GH101 FM-200 2Nd Signal (B) to FSCP

P0SGK51GH102 FM-200 2Nd Signal (B) to FSCP


P0SGK51GH102 FM-200 1St Signal (A) to FSCP
Interface With FM-200 System

P0SGK51GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Specical Zone/ Room

Addressable Smoke Detector at SERVER & TELECOM ROOM - Group A - X X X X X X X X X X X X X X

Addressable Smoke Detector at SERVER & TELECOM ROOM - Group B - X X X X X X X X X X X X X X

Addressable Smoke Detector at ELECTRICAL ROOM - Group A - X X X X X X X X X X X X X X

Addressable Smoke Detector at ELECTRICAL ROOM - Group B - X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 30 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-02); KKS NO. : P0CYE25GG001

PANEL'S LOCATION : ADMINISTRATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: MAINGATE HOUSE & TRAINNING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE25GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK25GH101 FM-200 2Nd Signal (B) to FSCP


Interface With FM-200 System

P0SGK25GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Specical Zone/ Room

Addressable Smoke Detector at Control/Electrical Room - Group A - X X X X X X X X X X X X X X

Addressable Smoke Detector at Control/Electrical Room - Group B - X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 31 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-04); KKS NO. : P0CYE21GG001

PANEL'S LOCATION : FIRE FIGHTING PUMP HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: FIRE FIGHTING PUMP HOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE21GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 32 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-04); KKS NO. : P0CYE21GG001

PANEL'S LOCATION : FIRE FIGHTING PUMP HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: DANGEROUS GOODS STORE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE21GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 33 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-04); KKS NO. : P0CYE21GG001

PANEL'S LOCATION : FIRE FIGHTING PUMP HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: HEAVY EQUIPMENT AND COAL MOBILES GARAGE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE21GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK09GH101 FM-200 2Nd Signal (B) to FSCP


Interface With FM-200 System

P0SGK09GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Specical Zone/ Room

Addressable Smoke Detector at MCC Room - Group A - X X X X X X X X X X X X X X

Addressable Smoke Detector at MCC Room - Group B - X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 34 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-04); KKS NO. : P0CYE21GG001

PANEL'S LOCATION : FIRE FIGHTING PUMP HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: MAIN TRANFORMER UNIT #1 FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE21GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 35 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-04); KKS NO. : P0CYE21GG001

PANEL'S LOCATION : FIRE FIGHTING PUMP HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: AUX. TRANSFORMER #1A&B FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE21GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 36 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-04); KKS NO. : P0CYE21GG001

PANEL'S LOCATION : FIRE FIGHTING PUMP HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: MAIN TRANFORMER UNIT #2 FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE21GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 37 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-04); KKS NO. : P0CYE21GG001

PANEL'S LOCATION : FIRE FIGHTING PUMP HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: AUX. TRANSFORMER #2A&B FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE21GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 38 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-04); KKS NO. : P0CYE21GG001

PANEL'S LOCATION : FIRE FIGHTING PUMP HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: DIRTY OIL DRAIN & TRANSFER LUBRICATING OIL STRORAGE TANK FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE21GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 39 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-04); KKS NO. : P0CYE21GG001

PANEL'S LOCATION : FIRE FIGHTING PUMP HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: HYDROGEN GENERATION PLANT FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE21GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK03GH101 FM-200 2Nd Signal (B) to FSCP


Interface With FM-200 System

P0SGK03GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Specical Zone/ Room

Addressable Smoke Detector at Local PLC Room - Group A - X X X X X X X X X X X X X X

Addressable Smoke Detector at Local PLC Room - Group B - X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 40 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-04); KKS NO. : P0CYE21GG001

PANEL'S LOCATION : FIRE FIGHTING PUMP HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: SERVICE GAS SHELTER FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE21GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 41 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-04); KKS NO. : P0CYE21GG001

PANEL'S LOCATION : FIRE FIGHTING PUMP HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CPP REGENERATION FACILITY FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE21GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 42 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-05); KKS NO. : P0CYE17GG001

PANEL'S LOCATION : WWT ELECTRICAL & DEHYDRATOR BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: WWT ELECTRICAL & DEHYDRATOR BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE17GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK18GH101 FM-200 2Nd Signal (B) to FSCP

P0SGK18GH102 FM-200 2Nd Signal (B) to FSCP


P0SGK18GH102 FM-200 1St Signal (A) to FSCP
Interface With FM-200 System

P0SGK18GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Specical Zone/ Room

Addressable Smoke Detector at Control & PLC Room - Group A - X X X X X X X X X X X X X X

Addressable Smoke Detector at Control & PLC Room - Group B - X X X X X X X X X X X X X X

Addressable Smoke Detector at Electrical Room - Group A - X X X X X X X X X X X X X X

Addressable Smoke Detector at Electrical Room - Group B - X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 43 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-05); KKS NO. : P0CYE17GG001

PANEL'S LOCATION : WWT ELECTRICAL & DEHYDRATOR BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CHEMICAL DOSING SHELTER FOR WT SYSTEM FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE17GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 44 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-05); KKS NO. : P0CYE17GG001

PANEL'S LOCATION : WWT ELECTRICAL & DEHYDRATOR BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: WTB & DEHYDRATOR BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE17GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK11GH101 FM-200 2Nd Signal (B) to FSCP

P0SGK11GH102 FM-200 2Nd Signal (B) to FSCP


P0SGK11GH102 FM-200 1St Signal (A) to FSCP
Interface With FM-200 System

P0SGK11GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Specical Zone/ Room

Addressable Smoke Detector at Electrical Room - Group A - X X X X X X X X X X X X X X

Addressable Smoke Detector at Electrical Room - Group B - X X X X X X X X X X X X X X

Addressable Smoke Detector at Control & PLC Room - Group A - X X X X X X X X X X X X X X

Addressable Smoke Detector at Control & PLC Room - Group B - X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 45 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-06); KKS NO. : P0CYE08GG001
PANEL'S LOCATION : COAL HANDLING ELECTRICAL BUILDING
CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL HANDLING ELECTRICAL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE08GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL
DESCRIPTION OUTPUT

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK08GH101 FM-200 2Nd Signal (B) to FSCP

P0SGK08GH102 FM-200 2Nd Signal (B) to FSCP

P0SGK08GH103 FM-200 2Nd Signal (B) to FSCP

P0SGK08GH104 FM-200 2Nd Signal (B) to FSCP


P0SGK08GH102 FM-200 1St Signal (A) to FSCP

P0SGK08GH103 FM-200 1St Signal (A) to FSCP

P0SGK08GH104 FM-200 1St Signal (A) to FSCP


Interface With FM-200 System

P0SGK08GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT
General Zone/ ROOM

Addressable Smoke Detector X X X X X X X X X X X X X

Addressable Heat Detector X X X X X X X X X X X X X

Addressable VESDA Detector X X X X X X X X X X X X X

Addressable Duct Smoke Detector X X X X X X X X X X X X X

Addressable Manual Call Point X X X X X X X X X X X X X

Analog Module for Gas Detector X X X X X X X X X X X X X

Monitor Module for Linear Heat Detector X X X X X X X X X X X X X

Monitor Module for Pressuare Switch X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage X X X X X X X X X X X X X

Specical Zone/ ROOM

Addressable Smoke Detector at Switchgear Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at Switchgear Room - Group B X X X X X X X X X X X X X X

Addressable Smoke Detector at Control Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at Control Room - Group B X X X X X X X X X X X X X X

Addressable Smoke Detector at Computer Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at Computer Room - Group B X X X X X X X X X X X X X X

Addressable Smoke Detector at Battery Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at Battery Room - Group B X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 46 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-06); KKS NO. : P0CYE08GG001

PANEL'S LOCATION : COAL HANDLING ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: TRANSFER TOWER 03 (COAL SCREEN HOUSE) FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE08GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 47 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-06); KKS NO. : P0CYE08GG001

PANEL'S LOCATION : COAL HANDLING ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: GATE HOUSE REAR FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE08GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 48 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-06); KKS NO. : P0CYE08GG001

PANEL'S LOCATION : COAL HANDLING ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: TRANSFER TOWER 04 FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE08GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 49 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-06); KKS NO. : P0CYE08GG001

PANEL'S LOCATION : COAL HANDLING ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CONVEYOR TRANSFER TOWER 03 TO TOWER 04 FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE08GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 50 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-06); KKS NO. : P0CYE08GG001

PANEL'S LOCATION : COAL HANDLING ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: AS FIRED SAMPLING HOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE08GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 51 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-06); KKS NO. : P0CYE08GG001

PANEL'S LOCATION : COAL HANDLING ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: AMMONIA STORAGE SHELTER FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE08GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 52 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-07); KKS NO. : P0CYE24GG001

PANEL'S LOCATION : ELECTRICAL BUILIDNG FOR CW AREA


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ELECTRICAL BUILIDNG FOR CW AREA FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE24GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


P0CYE02GG001 MAIN ER FIRE ALARM CONTROL PANEL

GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 53 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-07); KKS NO. : P0CYE24GG001
PANEL'S LOCATION : ELECTRICAL BUILIDNG FOR CW AREA
CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CHLORINATION BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE24GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


P0CYE02GG001 MAIN ER FIRE ALARM CONTROL PANEL

GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


DESCRIPTION OUTPUT

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK23GH101 FM-200 2Nd Signal (B) to FSCP

P0SGK23GH102 FM-200 2Nd Signal (B) to FSCP

P0SGK23GH103 FM-200 2Nd Signal (B) to FSCP


P0SGK23GH102 FM-200 1St Signal (A) to FSCP

P0SGK23GH103 FM-200 1St Signal (A) to FSCP


Interface With FM-200 System

P0SGK23GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT
General Zone/ ROOM

Addressable Smoke Detector X X X X X X X X X X X X X

Addressable Heat Detector X X X X X X X X X X X X X

Addressable VESDA Detector X X X X X X X X X X X X X

Addressable Duct Smoke Detector X X X X X X X X X X X X X

Addressable Manual Call Point X X X X X X X X X X X X X

Analog Module for Gas Detector X X X X X X X X X X X X X

Monitor Module for Linear Heat Detector X X X X X X X X X X X X X

Monitor Module for Pressuare Switch X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage X X X X X X X X X X X X X

Specical Zone/ ROOM

Addressable Smoke Detector at Control Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at Control Room - Group B X X X X X X X X X X X X X X

Addressable Smoke Detector at TR/RE Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at TR/RE Room - Group B X X X X X X X X X X X X X X

Addressable Smoke Detector at MCC Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at MCC Room - Group B X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 54 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-07); KKS NO. : P0CYE24GG001

PANEL'S LOCATION : ELECTRICAL BUILIDNG FOR CW AREA


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COOLING WATER PUMPING STATION FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE24GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


P0CYE02GG001 MAIN ER FIRE ALARM CONTROL PANEL

GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 55 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-07); KKS NO. : P0CYE24GG001

PANEL'S LOCATION : ELECTRICAL BUILIDNG FOR CW AREA


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: SW INTAKE PUMP STATION FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE24GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


P0CYE02GG001 MAIN ER FIRE ALARM CONTROL PANEL

GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 56 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-08); KKS NO. : P0CYE76GG001

PANEL'S LOCATION : COAL TRANSFER TOWER 01


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL TRANSFER TOWER 01 FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE76GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 57 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-08); KKS NO. : P0CYE76GG001

PANEL'S LOCATION : COAL TRANSFER TOWER 01


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL STORAGE AREA #1 FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE76GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 58 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-08); KKS NO. : P0CYE76GG001

PANEL'S LOCATION : COAL TRANSFER TOWER 01


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL TRANSFER TOWER 02 FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE76GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 59 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-08); KKS NO. : P0CYE76GG001

PANEL'S LOCATION : COAL TRANSFER TOWER 01


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL STORAGE AREA #2 FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE76GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 60 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-08); KKS NO. : P0CYE76GG001

PANEL'S LOCATION : COAL TRANSFER TOWER 01


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL CONVEYOR TRANSFER JETTY TO TRANSFER TOWER 01 (2) FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE76GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 61 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-09); KKS NO. : P0CYE48GG001

PANEL'S LOCATION : COAL JETTY CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL JETTY CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE48GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK48GH101 FM-200 2Nd Signal (B) to FSCP


Interface With FM-200 System

P0SGK48GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Specical Zone/ Room

Addressable Smoke Detector at Control/Electrical Room - Group A - X X X X X X X X X X X X X X

Addressable Smoke Detector at Control/Electrical Room - Group B - X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 62 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-09); KKS NO. : P0CYE48GG001

PANEL'S LOCATION : COAL JETTY CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL CONVEYOR TRANSFER JETTY TO TRANSFER TOWER 01 (1) FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE48GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 63 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-10); KKS NO. : P0CYE42GG001
PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING
CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ESP & ASH ELECTRICAL & CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE42GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL
DESCRIPTION OUTPUT

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK42GH101 FM-200 2Nd Signal (B) to FSCP

P0SGK42GH102 FM-200 2Nd Signal (B) to FSCP

P0SGK42GH103 FM-200 2Nd Signal (B) to FSCP

P0SGK42GH104 FM-200 2Nd Signal (B) to FSCP

P0SGK42GH105 FM-200 2Nd Signal (B) to FSCP

P0SGK42GH106 FM-200 2Nd Signal (B) to FSCP


P0SGK42GH102 FM-200 1St Signal (A) to FSCP

P0SGK42GH103 FM-200 1St Signal (A) to FSCP

P0SGK42GH104 FM-200 1St Signal (A) to FSCP

P0SGK42GH105 FM-200 1St Signal (A) to FSCP

P0SGK42GH106 FM-200 1St Signal (A) to FSCP


Interface With FM-200 System

P0SGK42GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT
General Zone/ ROOM

Addressable Smoke Detector X X X X X X X X X X X X X

Addressable Heat Detector X X X X X X X X X X X X X

Addressable VESDA Detector X X X X X X X X X X X X X

Addressable Duct Smoke Detector X X X X X X X X X X X X X

Addressable Manual Call Point X X X X X X X X X X X X X

Analog Module for Gas Detector X X X X X X X X X X X X X

Monitor Module for Linear Heat Detector X X X X X X X X X X X X X

Monitor Module for Pressuare Switch X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage X X X X X X X X X X X X X

Specical Zone/ ROOM

Addressable Smoke Detector at Battery Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at Battery Room - Group B X X X X X X X X X X X X X X

Addressable Smoke Detector at DC&UPS Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at DC&UPS Room - Group B X X X X X X X X X X X X X X

Addressable Smoke Detector at FASH Control Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at FASH Control Room - Group B X X X X X X X X X X X X X X

Addressable Smoke Detector at SWGR Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at SWGR Room - Group B X X X X X X X X X X X X X X

Addressable Smoke Detector at ESP Control Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at ESP Control Room - Group B X X X X X X X X X X X X X X

Addressable Smoke Detector at ESP SWGR Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at ESP SWGR Room - Group B X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 64 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-10); KKS NO. : P0CYE42GG001
PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING
CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: FGD ELECTRICAL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE42GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL
DESCRIPTION OUTPUT

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

P0SGK43GH101 FM-200 2Nd Signal (B) to FSCP

P0SGK43GH102 FM-200 2Nd Signal (B) to FSCP

P0SGK43GH103 FM-200 2Nd Signal (B) to FSCP


P0SGK43GH102 FM-200 1St Signal (A) to FSCP

P0SGK43GH103 FM-200 1St Signal (A) to FSCP


Interface With FM-200 System

P0SGK43GH101 FM-200 1St Signal (A) to FSCP


Interface Signal Actived to PAS
Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT
General Zone/ ROOM

Addressable Smoke Detector X X X X X X X X X X X X X

Addressable Heat Detector X X X X X X X X X X X X X

Addressable VESDA Detector X X X X X X X X X X X X X

Addressable Duct Smoke Detector X X X X X X X X X X X X X

Addressable Manual Call Point X X X X X X X X X X X X X

Analog Module for Gas Detector X X X X X X X X X X X X X

Monitor Module for Linear Heat Detector X X X X X X X X X X X X X

Monitor Module for Pressuare Switch X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage X X X X X X X X X X X X X

Specical Zone/ ROOM

Addressable Smoke Detector at SWGR & Electrical Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at SWGR & Electrical Room - Group B X X X X X X X X X X X X X X

Addressable Smoke Detector at Electrical Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at Electrical Room - Group B X X X X X X X X X X X X X X

Addressable Smoke Detector at Control Room - Group A X X X X X X X X X X X X X X

Addressable Smoke Detector at Control Room - Group B X X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 65 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-10); KKS NO. : P0CYE42GG001

PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: FLY ASH TRANSFER BLOWER SHELTER,COMPRESSOR FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE42GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 66 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-10); KKS NO. : P0CYE42GG001

PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ASH SLURRY PUMP SHELTER FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE42GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 67 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-10); KKS NO. : P0CYE42GG001

PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CEMS CONTAINER FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE42GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 68 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-10); KKS NO. : P0CYE42GG001

PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ELECTROSTATIC PRECIPITATOR #1 (A&B) FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE42GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 69 of 119


PANEL NAME: LOCAL FIRE ALARM CONTROL PANEL (LFACP-10); KKS NO. : P0CYE42GG001

PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ELECTROSTATIC PRECIPITATOR #2 (A&B) FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ALL ZONE/ ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

P0CYE42GG001 LOCAL FIRE ALARM PANEL SUPERVISORY


REPEATER FIRE ALARM CONTROL PANEL

Status Show on Monitor LCD Fire Alarm Panel


GRAPHIC DISPLAY COMPUTER ( GOW )

Event Alarm On Graphic Display Computer


P0CYE02GG001 MAIN FIRE ALARM CONTROL PANEL

Status Show On Monitor Lcd Display

Status Show On Monitor Lcd Display


DESCRIPTION OUTPUT

Interface Signal Shutdown to HVAC


Led Status Show On Mimic Panel

Interface Signal Actived to PAS


Interface With Other System
FUNTIONAL TEST

SUPERVISED OUTPUTS

Fire Alarm Horn & Strobe

Shutdown Signal to ECS


MIMIC PANEL AT CCB
ACCEPTANCE RECORD

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder

Panel Alarm Sounder


Event On Printer
P0CYE32GW001
P0CYE31GW001
OUTPUT

FAILURE

DATE
PASS
DESCRIPTION INPUT

-
INPUT

General Zone/ Room

Addressable Smoke Detector - X X X X X X X X X X X X X

Addressable Heat Detector - X X X X X X X X X X X X X

Addressable Duct Smoke Detector - X X X X X X X X X X X X X

Addressable Manual Call Point - X X X X X X X X X X X X X

Monitor Module for Pressuare Switch - X X X X X X X X X X X X X

Monitor Module for FSCP - Fire Alarm Stage - X X X X X X X X X X X X X

Monitor Module for FSCP - Discharged Stage - X X X X X X X X X X X X X

Common Signal

Any Supervisory Signal - X X X X X X X X X X

Any Trouble Signal - X X X X X X X X X X

General Note:

Rev. A Page 70 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK02GH101

PANEL'S LOCATION : CENTRAL CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CENTRAL CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: DC&UPS ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK02GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 71 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK02GH102

PANEL'S LOCATION : CENTRAL CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CENTRAL CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ELEC. LABORATOR ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK02GH102

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 72 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK02GH103

PANEL'S LOCATION : CENTRAL CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CENTRAL CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: I&C INSPECTION ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK02GH103

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 73 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK02GH104

PANEL'S LOCATION : CENTRAL CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CENTRAL CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: BATTERY ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK02GH104

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 74 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK02GH105

PANEL'S LOCATION : CENTRAL CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CENTRAL CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: SWGR ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK02GH105

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 75 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK02GH106

PANEL'S LOCATION : CENTRAL CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CENTRAL CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: MAIN CONTROL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK02GH106

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 76 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK02GH109

PANEL'S LOCATION : CENTRAL CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CENTRAL CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: COMPUTER ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK02GH109
INPUT

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 77 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK02GH107

PANEL'S LOCATION : CENTRAL CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CENTRAL CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ELECTRONIC 1 ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK02GH107

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 78 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK02GH108

PANEL'S LOCATION : CENTRAL CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CENTRAL CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ELECTRONIC 2 ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK02GH108

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 79 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK02GH110

PANEL'S LOCATION : CENTRAL CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CENTRAL CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: COMMUNICATION ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK02GH110

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 80 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK02GH111

PANEL'S LOCATION : CENTRAL CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CENTRAL CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: TARIFF ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK02GH111
INPUT

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 81 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (CO2); KKS NO. : P0SGJ01GH101

PANEL'S LOCATION : TURBINE HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: TURBINE HOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: SWITCHGEAR 1 ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGJ01GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 82 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (CO2); KKS NO. : P0SGJ01GH102

PANEL'S LOCATION : TURBINE HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: TURBINE HOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: CABLE TRENCH ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGJ01GH102

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 83 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (CO2); KKS NO. : P0SGJ01GH103

PANEL'S LOCATION : TURBINE HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: TURBINE HOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: MCC ROOM (8 - 10) Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGJ01GH103

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 84 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (CO2); KKS NO. : P0SGJ01GH104

PANEL'S LOCATION : TURBINE HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: TURBINE HOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: MCC ROOM (20 - 22) Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT
INPUT

P0SGJ01GH104

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 85 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (CO2); KKS NO. : P0SGJ01GH105

PANEL'S LOCATION : TURBINE HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: TURBINE HOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: EXCITATION PANEL ROOM (8 - 10) Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGJ01GH105

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 86 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (CO2); KKS NO. : P0SGJ01GH106

PANEL'S LOCATION : TURBINE HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: TURBINE HOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: EXCITATION PANEL ROOM (20 - 22) Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGJ01GH106

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 87 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (CO2); KKS NO. : P0SGJ01GH107

PANEL'S LOCATION : TURBINE HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: TURBINE HOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: SWITCHGEAR 2 ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGJ01GH107

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 88 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (CO2); KKS NO. : P0SGJ01GH108

PANEL'S LOCATION : TURBINE HOUSE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: TURBINE HOUSE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: LOCAL ELECTRICAL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT
INPUT

P0SGJ01GH108

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 89 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK25GH101

PANEL'S LOCATION : ADMINISTRATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ADMINISTRATION BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: SERVER & TELECOM ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK25GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 90 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK25GH102

PANEL'S LOCATION : ADMINISTRATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ADMINISTRATION BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ELECTRICAL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK25GH102

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 91 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK08GH101

PANEL'S LOCATION : COAL HANDLING ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL HANDLING ELECTRICAL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: SWITCHGEAR ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK08GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 92 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK08GH102

PANEL'S LOCATION : COAL HANDLING ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL HANDLING ELECTRICAL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: CONTROL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK08GH102
INPUT

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 93 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK08GH103

PANEL'S LOCATION : COAL HANDLING ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL HANDLING ELECTRICAL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: COMPUTER ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK08GH103

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 94 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK08GH104

PANEL'S LOCATION : COAL HANDLING ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL HANDLING ELECTRICAL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: BATTERY ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK08GH104

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 95 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK42GH101

PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ESP & ASH ELECTRICAL & CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: BATTERY ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK42GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 96 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK42GH102

PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ESP & ASH ELECTRICAL & CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: DC&UPS ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK42GH102
INPUT

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 97 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK42GH103

PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ESP & ASH ELECTRICAL & CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: FASH CONTROL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK42GH103

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 98 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK42GH104

PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ESP & ASH ELECTRICAL & CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: SWGR ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK42GH104

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 99 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK42GH105

PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ESP & ASH ELECTRICAL & CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ESP CONTROL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK42GH105

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 100 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK42GH106

PANEL'S LOCATION : ESP & ASH ELECTRICAL & CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: ESP & ASH ELECTRICAL & CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ESP SWGR ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK42GH106
INPUT

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 101 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK18GH101

PANEL'S LOCATION : WWT ELECTRICAL & DEHYDRATOR BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: WWT ELECTRICAL & DEHYDRATOR BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: CONTROL & PLC ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK18GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 102 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK18GH102

PANEL'S LOCATION : WWT ELECTRICAL & DEHYDRATOR BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: WWT ELECTRICAL & DEHYDRATOR BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: MCC ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK18GH102

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 103 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK09GH101

PANEL'S LOCATION : HEAVY EQUIPMENT AND COAL MOBILES GARAGE


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: HEAVY EQUIPMENT AND COAL MOBILES GARAGE FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: MCC ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK09GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 104 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK51GH101

PANEL'S LOCATION : AUXILIARY BOILER


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: AUXILIARY BOILER FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: SERVER & TELECOM ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK51GH101
INPUT

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 105 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK51GH102

PANEL'S LOCATION : AUXILIARY BOILER


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: AUXILIARY BOILER FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ELECTRICAL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK51GH102

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 106 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK23GH101

PANEL'S LOCATION : CHLORINATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CHLORINATION BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: CONTROL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK23GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 107 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK23GH102

PANEL'S LOCATION : CHLORINATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CHLORINATION BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: TR/RE ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK23GH102
INPUT

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 108 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK23GH103

PANEL'S LOCATION : CHLORINATION BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: CHLORINATION BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: MCC ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK23GH103

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 109 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK43GH101

PANEL'S LOCATION : FGD ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: FGD ELECTRICAL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: SWGR & ELECTRICAL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK43GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 110 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK43GH102

PANEL'S LOCATION : FGD ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: FGD ELECTRICAL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ELECTRICAL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK43GH102

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 111 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK43GH103

PANEL'S LOCATION : FGD ELECTRICAL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: FGD ELECTRICAL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: CONTROL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK43GH103
INPUT

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 112 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK48GH101

PANEL'S LOCATION : COAL JETTY CONTROL BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: COAL JETTY CONTROL BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: CONTROL/ELECTRICAL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK48GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 113 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK11GH101

PANEL'S LOCATION : WTB & DEHYDRATOR BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: WTB & DEHYDRATOR BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: ELECTRICAL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK11GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 114 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK11GH102

PANEL'S LOCATION : WTB & DEHYDRATOR BUILDING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: WTB & DEHYDRATOR BUILDING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: CONTROL & PLC ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK11GH102
INPUT

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 115 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK11GH101

PANEL'S LOCATION : EMERGENCY DIESEL GENERATOR


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: EMERGENCY DIESEL GENERATOR FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: EDG ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK11GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 116 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK29GH101

PANEL'S LOCATION : WORKSHOP


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: WORKSHOP FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: MCC ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK29GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 117 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK32GH101

PANEL'S LOCATION : MAINGATE HOUSE & TRAINNING


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: MAINGATE HOUSE & TRAINNING FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: CONTROL/ELECTRICAL ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK32GH101

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 118 of 119


PANEL NAME: FIRE SUPPRESSION PANEL (FM-200); KKS NO. : P0SGK03GH101

PANEL'S LOCATION : HYDROGEN GENERATION PLANT


CAUSE AND EFFECT DIAGRAM
PROTECT AREA/ BUILDING: HYDROGEN GENERATION PLANT FOR FIRE PROTECTION SYSTEM
PROTECT ZONE/ ROOM: LOCAL PLC ROOM Document No.: VA2-YF00-P0CYE-120007 REV NO.: A UPDATE: 13.02.2023

Active Led on Manual Release and Abort Station


Status Show on Monitor LCD Fire Alarm Panel
FIRE SUPPRESION PANEL (FM-200) SUPERVISORY

Dry-Contact for Common Discharged State


DESCRIPTION OUTPUT

Dry-Contact for Common Fault State

Interface Signal Shutdown to HVAC


Dry-Contact for Common Fire State
Interface with Fire Alarm System
Discharge sonos sounder beacon

Discharge sonos sounder beacon


Do not entry warning sign board

Interface With FM-200 System


FUNTIONAL

Fire sonos sounder beacon


SUPERVISED OUTPUTS
TEST
ACCEPTANCE RECORD

Panel Alarm Sounder

Solenoid valve
OUTPUT

P0SGK03GH101
INPUT

FAILURE
PASS

DATE
DESCRIPTION INPUT

-
INPUT

Input Signal

Manual Release Station X X X X X X X X X X

Discharged Switch X X X X X X X X X

Confirm Actuation 1St Signal (Group A) or


X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Confirm Actuation 1St Signal (Group A) and


X X X X X X X X X
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System

Abort Switch (when Confirm Actuation 1St Signal (Group A) and


X X L
Confirm Actuation 2nd Signal (Group B) From Fire Alarm System)

Supervisory Switch for Cylinders Low Pressure X X X

Common Signal

Any Trouble Signal - X X X

General Note:
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System actived. Delay Timer will be set to 60 seconds and count down. After, if Abort Switch actived.
+ If timer greater than 10 seconds (UL Timer), Delay Timer will be count down from 60 seconds to 10 seconds (UL Timer) and stop.
+ If timer greater than 0 seconds and less than 10 seconds (UL Timer), Delay Timer will be set 10 seconds (UL Timer) and stop.
+ If timer equal to 0 second, Solenoid valve will be actived.
- If Confirm Actuation 1St Signal (Group A) and Confirm Actuation 2nd Signal (Group B) From Fire Alarm System is normal. If Abort Switch actived, Fire Suppresion Panel will have trouble.

Rev. A Page 119 of 119