QIB

LA

GENERAL NOTES
PORTABLE FIRE EXTINGUISHER
ANCHOR BOLT & HOOK AS PER
MANUFACTURERS STANDARDS ALL PORTABLE TYPE FIRE EXTINGUISHERS SHALL BE QCDD APPROVED
AND COMPLY WITH THE REQUIREMENTS OF NFPA 10.

FIRE EXTINGUISHERS SHALL BE CONSPICUOUSLY LOCATED WHERE


FIRE EXTINGUISHER
THEY WILL BE READILY ACCESSIBLE AND IMMEDIATELY AVAILABLE IN
THE EVENT OF FIRE. PREFERABLY THEY SHALL BE LOCATED ALONG
NORMAL PATHS OF TRAVELS, INCLUDING EXITS FROM AREAS
Ø40 FIRE PIPE

1000
EXISTING LINE FIRE EXTINGUISHERS SHALL NOT BE OBSTRUCTED FROM VIEW
MASONRY WALL Key plan
THE CLASSIFICATION OF FIRE EXTINGUISHERS SHALL CONSIST OF A
LETTER THAT INDICATES THE CLASS OF FIRE ON WHICH A FIRE
EXTINGUISHER HAS BEEN FOUND TO BE EFFECTIVE, PRECEDED BY A
RATING NUMBER (CLASS A AND CLASS B ONLY) THAT INDICATES THE
FFL
RELATIVE EXTINGUISHING EFFECTIVENESS

SLAB
THE DISTRIBUTION OF FIRE EXTINGUISHERS SHALL COMPLY WITH THE
PRESCRIBED NFPA-10, AS SHOWN ON THE DRAWINGS AND THE
SPECIFIC REQUIREMENTS OF THE QCDD AUTHORITIES.

Ø40 mm
SCALE.: DETAIL NAME.:
PORTABLE FIRE EXTINGUISHERS SHALL BE MAINTAINED IN A FULLY
N.T.S FIRE EXTINGUISHER DETAIL FOR ALL TYPES CHARGED AND OPERABLE AND KEPT IN THEIR DESIGNATED PLACES
AT ALL TIMES WHEN THEY ARE NOT BEING USED

COLD ABC DRY POWDER FIRE EXTINGUISHER MULTIPURPOSE DRY CHEMICAL


EXTINGUISHERS (CLASS A, CLASS B, AND CLASS C FIRES) THE CAPACITY
OF THE EXTINGUISHER SHALL BE 6KG AND SHALL HAVE A FIRE RATING
ROOM
3 COMP.

OF 21A AND 113B RATING AS SHOWN IN THE DRAWINGS


TABLE
PREP

SINK

Ø25 mm Ø25 mm DP THE DRY POWDER FIRE EXTINGUISHERS SHALL HAVE QCDD APPROVED

* CLASS A FIRES:
FIRES IN ORDINARY COMBUSTIBLE MATERIALS, SUCH AS WOOD, CLOTH,
PAPER RUBBER, AND MANY PLASTICS
MS
HS
FREEZER
UPRIGHT

FIRE BLANKET * CLASS B FIRES:


FIRES IN FLAMMABLE LIQUIDS, COMBUSTIBLE LIQUIDS, PETROLEUM
GREASES, TARS OILS, OIL-BASED PAINTS SOLVENTS, LACQUERS,
overhead ALCOHOLS, AND FLAMMABLE GASES
s/s shelves * CLASS C FIRES:

s/s shelves
overhead
FIRES THAT INVOLVE ENERGIZED ELECTRICAL EQUIPMENT WHERE
THE ELECTRICAL NON-CONDUCTIVITY OF THE EXTINGUISHING MEDIA

1500
FOR KITCHEN HOOD IS OF IMPORTANCE. (WHERE ELECTRICAL EQUIPMENT IS
DE-ENERGIZED, FIRE EXTINGUISHERS FOR CLASS A OR B FIRES CAN
REFRIGERATED MAKELINE

FIRE SUPPRESSION SYSTEM BE USED SAFELY.)


REFER TO DWG (KITCHEN HOOD FIRE FIRE BLANKETS:
SUPPRESSION SYSTEM FFL PROVIDE FIRE BLANKETS IN KITCHENS WHERE INDICATED IN THE
DRAWINGS. IT SHOULD BE QCDD APPROVED. FIRE BLANKET SHALL
BE MANUFACTURED FROM 430 GM/SQM GLASS FIBER MATERIAL
SLAB WHICH SHALL WITHSTAND TEMPERATURE UP TO 550°C AND IS RATED
TO BS476 PART4 AND CLASS 1 SURFACE SPREAD OF FLAME TO BS476
PART7. THE SIZE SHALL BE 1.2MX1.2M .
Ø32 mm

SCALE.: DETAIL NAME.:


N.T.S FIRE BLANKET DETAIL
FIRE FIGHTING SYSTEM DESIGN
FB
K

»AUTOMATIC FIRE SUPPRESSION


AREA PROTECTED
FIRE EXTINGUISHERS SCHEDULE · SPRINKLER SYSTEM ----

CUTTING TABLE · PRE-ACTION SYSTEM ----

DOUGH QUANTITY · DELUGE SYSTEM ----


SAUCING HEATING STRIPS · WATER SPRAY FIXED SYSTEM ----
THEATER
ABOVE · FOAM SYSTEM ----
EXTINGUISHER
TYPES DP K FB · CLEAN AGENT SUPPRESSION SYSTEM ----
· FIXED AEROSOL FIRE EXTINGUISHING SYSTEM ----

GROUND FLOOR 2 1 1 · KITCHEN HOOD SUPPRESSION SYSTEM √ KITCHEN HOOD SHOP DRAWING
PEPSI

· OTHERS, SPECIFY ----


DISP

Ø25 mm Ø25 mm
0 ISSUED FOR APPROVAL 16-10-2021 AB OP --
FC »MANUAL FIRE SUPPRESSION REV. DESCRIPTION DATE DWN CHK APP
DP Owner:
PAPA JOHN'S FLOOR AREA (M²)
· PORTABLE FIRE EXTINGUISHER √
UC ICE √
· FIRE BLANKET AL MAJID JAWAD W.L.L
POS
POS

MACHINE MANAGER'S GROUND & MEZZANINE FLOOR 42.5 S.Q.M


TABLE · STANDPIPE AND HOSE SYSTEM Client:

TOTAL BUILT UP AREA = 42.5 S.Q.M 1


- CLASS I - 2 (65mm) HOSE STATION
2

WET STANDPIPE
DRY STANDPIPE
CITY CENTER, QATAR
- CLASS II
Designer:
FIRE FIGHTING DESIGN CRITERIA: 1 inch (25mm) HOSE STATION

TYPE OF OCCUPANCY MERCANTILE OCCUPANCY


JG Interiors
&Design Studio

HAZARD CLASSIFICATION ORDINARY HAZARD (GROUP-02)


Main Contractor
TYPE OF SYSTEM FIRE EXTINGUISHERS

I
Interstar
Trading and Contracting.
Doha, Qatar
I I I LEGENDS DESCRIPTION
Sub. Contractor
DP 6 KG ABC DRY-POWDER, PORTABLE FIRE EXTINGUISHER

K 6 Lit. CLASS-K WET-CHEMICALS, PORTABLE FIRE EXTINGUISHER

FB FIRE BLANKET (1.2mX1.2m)

2HRS 2 HORS FIRE RATED WALL


Drawing Title:
EXISTING UPRIGHT SPRINKLER HEAD

EXISTING FIRE MAIN PIPE PROVIDED BY MALL


FIRE FIGHTING SYSTEM LAYOUT
EXISTING BRANCH FIRE PIPE

THIS IS A CAD DRAWING AND MUST NOT BE ALTERED MANUALLY

Project No. P.04 Drawn By. AB Chacked By. OP


Drawing Number Sht. Scale Dwg. Size Date Revision
07 1 of 1 1:25 A1 16-10-2021 00