NOTES:

1.EXISTING LIGHTING CIRCUIT BREAKERS FOR LIGHTING


FIXTURES SHALL BE UTILIZED TO FEED THE NEW
LIGHTING FIXTURE AT CONTROL BUILDING REFER TO
DWG. NO. PA-00P109.

2.EXISTING CIRCUIT BREAKERS FEEDING EXISTING FIRE


ALARM CONTROL PANEL AT SWITCHGEAR BUILDING

OF
NO.4804 SHALL BE REPLACE BY THE NEW CIRCUIT
BREAKER (20AT) FOR THE NEW FIRE SUPPRESION

CONSENT
CONTROL PANEL AND MUST BE IDENTIFIED IN RED
NOTE-1 CONTROL ROOM LIGHTING 102
COLOR ON BREAKER HANDLE WITH PERMANENT
128 MECH ROOM LIGHTS NOTE-1
LABEL IN ACCORDANCE TO NEC 760 AND NFPA 72.

144 RACK/EXTENSION ROOM LIGHTS NOTE-1

TTEN
800 RACK/EXTENSION ROOM RECEPTACLES

WRI
THE
THOUT
LEGEND

WI
- SCOPE UNDER J.O. BI-10-00844-0001

NG
DRAWI
FSCP FIRE SUPPRESSION CONTROL PANEL

1586 2903

S
THI
6786

FROMNED
OBTAI
BE
PART,SHALL
SPARE SPARE

SPARE SPARE

SPARE

SPARE SPARE

SPARE SPARE

SPARE 407 CONTROL ROOM LIGHTING, UPS & AIR LOCK NOTE-1

N
I
FULL,OR
SPACE HEATER MCC-0102A

360 NEW FIRE ALARM PANEL (HSSD)

N
I ON
1800 I/O RACK CABINET (EXISTING) MCC BLDG NO.4804 SPARE

REPRODUCTI
1000 K12-FSCP-004 NOTE-2 SPARE

7089 7715 8515 5240 4720 6907

23319 16867

SAUDIARAMCO.NO
DRAWING CONTROL (BI-00179) VD-047942
REMOTE I/O CABINET (EXISTING) MCC BLDG NO.4162
SCOPE OF WORK VE-290771

DRAWING CONTROL (BI-10-00493-0001) VD-688132


SCOPE OF WORK VE-688133
DRAWING CONTROL FOR BI-10-00844-0001 PD-00ADCL
LIGHTING LAYOUT PA-00P109
ELECTRICAL POWER PLAN DA-728700.005

OF
PROPERTY
SOLE
THE
ARE
200 AREA LIGHTING CONTACTOR

N
HEREI
100 TASK LIGHTING FOR ZV-2527

NED
SCALE:

CONTAI
REVISION VALIDATION

THIS REVISION NO. IS COVERED, FOR ALL APPROVAL AND CERTIFICATION

REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

REV.NO. DATE REVISION DESCRIPTION

I
0A3 07/01/21 ISSUED FOR 100% - PP

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
10-00844-0001 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
DRAWING TYPE

ELECTRICAL SCH

NG
PANEL SCHEDULES

DRAWI
EAST/WEST PIPELINE PUMP STATION #9

YANBU SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
K12 P DA-728694 001 0A3
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED HYBRID CADD-01