DRAWINGS NOT TO BE USED FOR CONSTRUCTION UNLESS VERIFICATION SIGNATURE

HAS BEEN ADDED. THE COPYRIGHT OF THIS DRAWING REMAINS WITH NORTHROP
CONSULTING ENGINEERS PTY LTD. ALL SETOUT TO ARCHITECT'S DRAWINGS.
GENERAL CONCRETE CONCRETE CONTINUED CHEMICAL ANCHORS DIMENSIONS TO BE VERIFIED WITH ARCHITECT AND BUILDER BEFORE COMMENCING SHOP

G1 THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH SPECIFICATIONS,


SLAB ON GROUND C1 CARRY OUT ALL CONCRETE WORK IN ACCORDANCE WITH AS3600 AND C20 SITE BENDING OF REINFORCEMENT BARS SHALL BE DONE WITHOUT HEATING CA01. UNLESS NOTED OTHERWISE, CHEMICAL ANCHORS
DRAWINGS OR SITE WORK. NORTHROP ACCEPTS NO RESPONSIBILITY FOR THE
USABILITY, COMPLETENESS OR SCALE OF DRAWINGS TRANSFERRED ELECTRONICALLY.
OTHER CONSULTANTS DRAWINGS AND WRITTEN INSTRUCTIONS AS MAY BE SG1 CAST SLABS ON 0.2mm POLYTHENE MEMBRANE LAID OVER A NOMINAL SAND LEVELING NATSPEC CONCRETE STANDARDS. USING A RE-BENDING TOOL. THE BARS SHALL BE RE-BENT AGAINST A FLAT SPECIFIED IN THESE DRAWINGS REFER TO CHEMSET 801
ISSUED DURING THE COURSE OF THE CONTRACT. LAYER ON FIRM CUT ORIGINAL GROUND OR COMPACTED FILL AS SPECIFIED. C2 CONCRETE PROPERTIES AND COVER TO REINFORCING: SURFACE OR A PIN WITH A DIAMETER NOT LESS THAN THE MINIMUM PIN SIZE CHEMICAL INJECTION ANCHORS.
G2 THE WEATHER PROOFING OF THE BUILDING IS THE ARCHITECTS/BUILDERS SG2 MESH LAPS: PRESCRIBED IN AS3600-2009. CA02. ALTERNATIVE CHEMICAL ANCHORS MAY BE SUBSTITUTED
THE TWO OUTERMOST TRANSVERSE WIRES OF ONE SHEET OF MESH MUST OVERLAP CONCRETE MAX. 56
RESPONSIBILITY. THIS INCLUDES THE SPECIFICATION AND FIXING DETAILS OF COVER C21 SPLICES IN REINFORCEMENT SHALL BE MADE ONLY IN POSITIONS SHOWN ON WITH PRIOR PERMISSION FROM THE SUPERINTENDENT.
THE TWO OUTERMOST TRANSVERSE WIRES OF SHEET BEING LAPPED, AS SHOWN BELOW. ELEMENT STRENGTH DAY DRYING
CLADDINGS, SHEETING AND FLASHING. (mm) THE STRUCTURAL DRAWINGS OR IN POSITIONS OTHERWISE APPROVED IN CA03. MINIMUM EDGE DISTANCE AND SPACING SETOUT OF THE
f'c (MPa) SHRINKAGE
G3 ALL DISCREPANCIES SHALL BE REFERRED TO THE SUPERINTENDENT AND WRITING BY THE STRUCTURAL ENGINEER. LAPS SHALL BE IN ACCORDANCE ANCHORS ARE SPECIFIED ON THESE DRAWINGS. IF THE
RESOLVED BEFORE PROCEEDING WITH THE WORK. BORED PILES 32 50 WITH AS3600 SECTION 13 AND NOT LESS THAN THE DEVELOPMENT LENGTH INSTALLED DISTANCES ARE LESS THAN THAT SPECIFIED
50mm OVERLAP OF END WIRE 1
G4 ALL DIMENSIONS SHOWN SHALL BE VERIFIED BY THE BUILDER ON SITE. SLABS ON GROUND - EXTERNAL 32 TOP 40 BTM 40 FOR EACH BAR. NOTIFY THE SUPERINTENDENT FOR INSTRUCTION.
DRAWINGS SHALL NOT BE SCALED FOR DIMENSIONS. THE RL'S SHOWN ON 650microns C22 FOR LAPS IN MESH, REFER TO SLAB ON GROUND NOTES
- INTERNAL 32 TOP 20BTM 40 CA04. CHEMICAL ANCHORS ARE TO BE STIRCTLY INSTALLED TO
SG3 ALL CONCRETE IS TO BE PLACED USING A VIBRATOR. CURING METHODOLOGY TO BE C23 WELDING OF REINFORCEMENT SHALL NOT BE PERMITTED UNLESS SHOWN ON
THE DRAWINGS ARE APPROXIMATE AND ARE FOR THE SOLE PURPOSE OF MANUFACTURERS INSTALLATION PROCEDURE.
APPROVED IN WRITING BY THE STRUCTURAL ENGINEER PRIOR TO CONCRETE BEING PLACED. MAXIMUM AGGREGATE SIZE = 20mm U.N.O. THE STRUCTURAL DRAWINGS OR APPROVED BY THE STRUCTURAL ENGINEER.
ASSISTING THE STRUCTURAL DOCUMENTATION. THEY ARE NOT BE USED
SLUMP DURING PLACING = 75mm C24 AT EXTERNALLY EXPOSED SURFACES NO METALLIC ITEMS INCLUDING FORM CA05. DIAMETER OF HOLES TO MANUFACTURES SPECIFICATION
FOR CONSTRUCTION PURPOSES. REFER TO ARCHITECTURAL DRAWINGS FOR
EXPOSURE CLASSIFICATION = A1 (INTERNAL WORK) FOR NOMINATED BOLT/BAR DIAMETER. DRILL HOLES USING
CONFIRMATION OF ALL RL'S, ALL LEVELS ARE IN METRES (m) AND
DIMENSIONS ARE IN MILLIMETRES (mm)
FOUNDATIONS = B1 (EXTERNAL WORK)
BOLTS, FORM SPACERS, METALLIC BAR CHAIRS AND TIE WIRE ARE TO BE
PLACED IN THE COVER ZONE. A ROTARY PERCUSSION DRILL. DO NOT CORE DRILL HOLES.
F1 ASSUMED ALLOWABLE BEARING CAPACITY. CA06. CLEAN AND DEGREASE BOLT/BARS PRIOR INSTALLATION.
G5 ALL WORKMANSHIP, TESTING, MATERIALS AND SUPERVISION ARE TO BE IN NO ADMIXTURES SHALL BE USED IN CONCRETE MIX UNLESS APPROVED BY C25 ALL REINFORCEMENT, ANCHOR BOLTS AND OTHER CONCRETE INSERTS
- BORED PILE 700kPa BEARING (VERY LOW STRENGTH ROCK)
ACCORDANCE WITH THESE SPECIFICATIONS, THE OCCUPATIONAL HEALTH STRUCTURAL ENGINEER IN WRITING. SHALL BE WELL SECURED IN POSITION AND INSPECTED BY THE STRUCTURAL CA07. ENSURE CHEMICAL IS ALLOWED TO FULLY CURE IN
F2 A GEOTECHNICAL REPORT HAS BEEN CARRIED OUT, REFER TO REPORT
AND SAFETY ACT 2000 ENFORCED BY THE WORKCOVER AUTHORITY AND C3 CONCRETE PROPERTIES FOR SLABS AND BEAMS SHALL BE VARIED FROM ENGINEER PRIOR TO PLACING CONCRETE. ACCORDANCE WITH MANUFACTURE'S DETAILS PRIOR TO
No. 295165rpt2. THIS REPORT IS FOR INFORMATION ONLY, IT IS NOT A COMPLETE
CURRENT RELEVANT AUSTRALIAN STANDARDS. NORMAL CLASS AS FOLLOWS: C26 HOLD DOWN BOLTS SHALL BE HOT DIPPED GALVANISED. LOADING BOLTS/BARS.
DESCRIPTION OF CONDITIONS AT OR BELOW GROUND LEVEL.
G6 PROPRIETARY ITEMS SPECIFIED SHALL BE INSTALLED IN ACCORDANCE WITH - MINIMUM CEMENT CONTENT 250kg/cu.m. C27 U.N.O, ALL MASONRY ANCHORS INTO CONCRETE SHALL BE RAMSET
F3 THE SLAB AND FOOTINGS HAVE BEEN DESIGNED IN ACCORDANCE WITH AS2870 FOR
THE MANUFACTURER'S WRITTEN INSTRUCTIONS. DO NOT VARY SPECIFIED - PRIOR TO COMMENCEMENT CONCRETE SUPPLIER TO PROVIDE DRYING SHRINKAGE TRUBOLTS (LONGEST VERSION) OR APPROVED EQUIVALENT. BOLTS SHALL BE
PROPRIETARY PRODUCTS WITHOUT WRITTEN APPROVAL FROM THE
CLASS P/M SITE. A SUITABLY QUALIFIED GEOTECHNICAL ENGINEER TO BE CONTACTED
DURING EXCAVATION TO CONFIRM THE SITE CLASSIFICATION.
TEST RESULTS FROM PRODUCTION ASSESSMENT AS EVIDENCE THAT SPECIFIED DRYING GALVANISED WHERE THEY ARE ADJOINING NON FERROUS OR PREPAINTED TESTING REGIME FOR CHEMICAL
STRUCTURAL ENGINEER. SHRINKAGE LIMITS CAN BE ACHIEVED USING NORMAL MIX DESIGN. MEMBERS. PROVIDE STAINLESS STEEL BOLTS FOR ALL EXTERNAL
G7 THESE DRAWINGS AND ISSUED WRITTEN INSTRUCTIONS DURING THE
F4 THE CONTRACTOR SHALL ALLOW TO ENGAGE A QUALIFIED (NPER) GEOTECHNICAL ENGINEER
TO APPROVE THE FOUNDATION MATERIAL. OBTAIN GEOTECHNICAL ENGINEERS APPROVAL
C4 SUBMIT FOR APPROVAL THE FOLLOWING TO THE STRUCTURAL ENGINEER: CONDITIONS, OR WHERE EXPOSED TO THE WEATHER. INJECTION ANCHORS
COURSE OF THE CONTRACT DEPICT THE COMPLETE STRUCTURE. THEY DO - CURING PROCEDURE (PVA MEMBRANES NOT PERMITTED) TR01. HOLD DOWN ANCHORS:
AND SUBMIT CERTIFICATE IN WRITING TO THE STRUCTURAL ENGINEER PRIOR TO - TEST MIN. 1 ANCHOR PER 10% OF COLUMN
NOT DESCRIBE A WORK METHOD. THE ARRANGEMENT, DESIGN AND - STRIPPING PROCEDURE
CONCRETING FOUNDATIONS. BASE PLATES AND 25% OF VERTICAL BRACING
- DETAILS AND LOCATION OF CAST IN SERVICES
INSTALLATION OF TEMPORARY WORKS REMAINS THE RESPONSIBILITY OF
THE CONTRACTOR.
F5 ENSURE STABILITY OF ADJACENT BUILDINGS IS MAINTAINED DURING ALL STAGES OF
CONSTRUCTION.
- CONDUITS, PENETRATIONS AND CONSTRUCTION JOINT LOCATIONS CONCRETE MASONRY BASE PLATES
G8 THE DETERMINATION OF A SAFE WORK METHOD REMAINS THE C5 ALL CONCRETE MIXES SHALL BE DESIGNED BY A RECOGNISED TESTING LAB EXPOSURE CLASSIFICATION: MODERATE (>10km FROM COAST) - SHOULD THERE BE A FAILURE, ALL ANCHORS
F6 DO NOT ALLOW EXCAVATED MATERIAL TO STOCKPILE STAND WITHIN 1500mm OF FOOTING CM1 MASONRY CONSTRUCTION IS TO CONFORM TO AS3700. NEED TO BE TESTED FOR THAT BASE PLATE.
RESPONSIBILITY OF THE CONTRACTOR. ANY ELEMENT WHICH POSES AN AND SUBMITTED FOR REVIEW BY THE STRUCTURAL ENGINEER.
TRENCHES OR PITS. NO EARTH OR DETRITUS IS TO FALL INTO THE FOOTING TRENCHES - MORTAR CLASSIFICATION = M2 TEST LOADING IS AS FOLLOWS:
UNACCEPTABLE LEVEL OF SAFETY RISK TO CONSTRUCT SHALL BE C6 ALL COMPRESSIVE STRENGTH TEST REPORTS SHALL BE SUBMITTED TO
BEFORE OR DURING CONCRETE PLACEMENT. - DURABILITY CLASSIFICATION OF BUILT IN COMPONENTS = R2 - M20 BOLTS-37kN THIS IS BASED ON AN 80% OF
REFERRED TO THE STRUCTURAL ENGINEER. TEMPORARY BRACING AND THE STRUCTURAL ENGINEER FOR REVIEW.
F7 THE UNDERSIDE OF FOUNDATIONS SHALL CONFORM TO THE FOLLOWING REGARDLESS OF - DURABILITY GRADE OF EXTERNAL MASONRY UNITS = PROTECTED ULTIMATE CAPACITY OF THE BOLT. CARE SHOULD
SUPPORT OF STRUCTURE IS THE RESPONSIBILITY OF THE CONTRACTOR AND C7 PROJECT CONTROL TESTING SHALL BE CARRIED OUT ON ALL CONCRETE IN
NOMINATED LEVELS: CM2 THE CHARACTERISTIC UNCONFINED COMPRESSIVE STRENGTH OF THE MASONRY UNITS BE TAKEN NOT TO EXCEED THIS LOAD.
SHALL BE MAINTAINED DURING ALL STAGES OF CONSTRUCTION. ACCORDANCE WITH AS1379. TEST CYLINDERS ARE TO BE KEPT ON SITE.
G9 NOTES ON ANY DRAWING APPLY TO ALL DRAWINGS IN THE SET U.N.O. FOOTING C8 ALL CONCRETE IS TO BE CONTINUOUSLY CURED FOR A MINIMUM PERIOD OF SHALL BE 15MPa OR GREATER.
G10 ALL ARCHITECTURAL FITMENTS SUCH AS GLAZING, PARTITIONS, CEILINGS 10 DAYS AFTER PLACING. CURING TO COMMENCE IMMEDIATELY AFTER FINISHING. CM3 BED UNITS IN FRESHLY PREPARED MORTAR, UNIFORMLY MIXED CEMENT, LIME AND
ETC. SHOULD ALLOW FOR THE SHORT AND LONG TERM MOVEMENT OF TO BE DETERMINED BY ENGINEER SPRAY ON CURING COMPOUNDS TO COMPLY WITH AS3799. SAND IN THE RATIO OF 1:1:6, CONFORMING TO AS3700.
STRUCTURAL ELEMENTS. FOR BEAMS AND SLABS SPANNING LESS THAN 8m (ASSUME 45° FOR TENDER PURPOSES) C9 FOR TENDER PURPOSES ASSUME MINIMUM STRIPPING TIMES AND EXTENT CM4 GROUT FILL FOR BLOCKWORK:
AN ALLOWANCE OF AT LEAST 20mm SHOULD BE MADE (CONSULT SPEC. OR OF BACK PROPPING AS PER AS3610-1995 SECTION 5.0 AND AS PER GENERAL - COMPRESSIVE STRENGTH = N20MPa
STRUCTURAL ENGINEER WHERE SPANS EXCEED 8m). NOTES FOR FORMWORK AND PROPPING. - MAXIMUM AGGREGATE SIZE = 10mm
BASE OF TRENCH OR TOP OF 10MPa
G11 THE BUILDER SHALL PROVIDE CERTIFICATION ON ANY DESIGN AND C10 FORMWORK FINISH CLASSIFICATION TO AS3600: - SLUMP = 225mm
CONCRETE BACKFILL TO TRENCH
CONSTRUCT COMPONENT BY A CHARTERED PROFESSIONAL ENGINEER (NPER). ELEMENT CLASS - MINIMUM PORTLAND CEMENT CONTENT = 300kg/cu.m
G12 THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE LOCATION OF ALL - INGROUND FOOTINGS 5 COMPACT GROUT USING A MECHANICAL VIBRATOR.
SERVICES IN THE VICINITY OF THE WORKS. ANY SERVICES SHOWN ARE - RETAINING WALLS 5 EARTH FACE CM5 CONTROL JOINTS IN UNREINFORCED WALLS SHALL BE PROVIDED IN ACCORDANCE
PROVIDED FOR INFORMATION ONLY. THE CONTRACTOR SHALL CONFIRM THE - RETAINING WALLS 3 EXPOSED FACE WITH THE BCA, BUT GENERALLY AT 5m CENTRES AND 2.5m FROM A CORNER, U.N.O.
LOCATION OF ALL SERVICES PRIOR TO COMMENCING AND SHALL BE FOOTING - COLUMNS 2 REINFORCEMENT IN ACCORDANCE WITH AS1302.

100 min
RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE CAUSED TO SERVICES, AS - LIFT WALLS 2 CM6 CONTROL JOINTS IN REINFORCED WALLS SHALL BE PROVIDED GENERALLY AT 8.0m
WELL AS ANY LOSS INCURRED AS A RESULT OF THE DAMAGE TO ANY - BEAMS AND SLABS 2 CENTRES AND 2.5m FROM A CORNER, U.N.O. PROVIDE REINFORCEMENT IN
SERVICE. - STAIRS 2 ACCORDANCE WITH AS1302.
WHERE PIPE CROSSES A FOOTING, FILL CM7 THE BOTTOM COURSE OF ALL REINFORCED BLOCKWORK SHALL CONSISTS OF
G13 THE STRUCTURAL COMPONENTS DETAILED ON THESE STRUCTURAL - GRANO TREATED SURFACES 2
TO UNDERSIDE OF FOOTING WITH MASS C11 SURFACE FINISHES: E SHAPED BLOCKS TO ENABLE CLEANOUT AND TYING OF STEEL.
DRAWINGS ARE JOB SPECIFIC AND HAVE BEEN DESIGNED IN ACCORDANCE
CONCRETE. WRAP PIPE WITH A 40mm THICK - COLUMNS AND WALLS OFF FORM - FULLY BED FACE SHELLS ONLY. REV DESCRIPTION ISS'D VER'D APP'D DATE
WITH THE RELEVANT AUSTRALIAN STANDARDS AND BUILDING CODE OF
LAYER OF ABLEFLEX OR SIMILAR MATERIAL - FLOOR SLABS (U.N.O.) MACHINE FLOAT - CLEAN OUT ALL CORES AFTER EACH DAY'S LAYING.
AUSTRALIA FOR THE FOLLOWING FIRE RATINGS, WIND LOADS, FLOOR USAGE 1 PROGRESS ISSUE J.H. B.W. 30.06.17
AND EARTHQUAKE LOADS. FOOTING - SLABS TO BE TILED WOOD FLOAT - ENSURE STARTER BARS ARE CORRECTLY LOCATED IN FOOTINGS.
2 ISSUED FOR 95% REVIEW J.H. B.W. 14.07.17
* FRL'S: - STAIRS STEEL TROWEL CM8 ALL MASONRY ANCHORS INTO HOLLOW CONCRETE MASONRY SHALL BE HILTI
HIT-HY20 CHEMICAL INJECTION ANCHORS OR APPROVED EQUIVALENT AND SHALL A ISSUED FOR CONSTRUCTION H.A. R.P. B.W. 21.07.17
- ALL TO BE BY BCA CONSULTANT C12 COMPACT ALL CONCRETE INCLUDING FOOTINGS AND SLABS, USING
WHERE ADDITIONAL EXCAVATION IS REQUIRED MECHANICAL VIBRATORS. BE GALVANISED STEEL FOR EXTERNAL USE. B ISSUED FOR CONSTRUCTION H.A. B.W. 04.09.17
* WIND LOADS: DUE TO UNSATISFACTORY FOUNDATION MATERIAL, C13 PLACE CONCRETE CONTINUOUSLY BETWEEN CONSTRUCTION JOINTS SHOWN CM9 MASONRY TIES SHALL BE GALVANISED, MINIMUM COATING MASS 300g/sq.m
- IMPORTANCE LEVEL = 2.0 POUR 10MPa MASS CONCRETE TO UNDERSIDE OF FOOTING. ON PLAN. DO NOT BREAK OR INTERRUPT SUCCESSIVE POURS SUCH THAT COLD (T3.1 - AS2699.1) PER SIDE AND MEDIUM DUTY CLASSIFICATION U.N.O. FACE FIXED
VERIFIER: R.PRATT

- ANNUAL PROBABILITY OF EXCEEDANCE = 1/500 JOINTS OCCUR. ANY REVISIONS OR ADDITIONS TO CONSTRUCTION JOINTS TIES SHALL BE FIXED USING A SCREW FIXING AND SHALL NOT BE NAILED.
F8 FOOTINGS SHALL BE CENTRALLY LOCATED UNDER WALLS AND COLUMNS UNLESS NOTED ARCHITECT
- REGION = A2 SHOWN ON PLAN REQUIRE APPROVAL FROM THE STRUCTURAL ENGINEER. CM10 THE TOP COURSE OF ALL FREESTANDING HOLLOW BLOCK MASONRY SHALL CONSIST
OTHERWISE ON THE STRUCTURAL DRAWINGS.
- REGIONAL WIND SPEED Vr = 45m/s C14 CONCRETE PROFILES: OF SOLID CAPPING BLOCKS.
- TERRAIN CATEGORY = 3 F9 FOOTINGS SHALL BE EXCAVATED TO THE DETAILED DEPTH AND WIDTH. FOOTINGS SHALL
- BEAM DEPTHS ARE WRITTEN FIRST AND INCLUDE THE SLAB THICKNESS. CM11 PROVIDE SLIDING HORIZONTAL TIES ACROSS JOINTS IN WALLS EQUIVALENT TO
- TERRAIN MULTIPLIER Mz,cat = 0.83 BE INSPECTED AND FILLED WITH CONCRETE AS SOON AS POSSIBLE TO AVOID EITHER BRUNSWICK MFA-3 AT 400 CTS VERTICALLY IN EACH FACE OF THE BLOCKS.
SOFTENING OF THE FOUNDATION MATERIAL OR DRYING OUT BY EXPOSURE. - SIZES OF CONCRETE ELEMENTS DO NOT INCLUDE THICKNESS OF APPLIED FINISHES.
- SHIELDING MULTIPLIER Ms = 1 - NO HOLES, CHASES OR EMBEDMENT OF PIPES OTHER THAN SHOWN IN THE CM12 NON-LOADBEARING WALLS SHALL FINISH 20mm SHORT OF SLAB SOFFIT AND
- TOPOGRAPHIC MULTIPLIER Mt = 1 F10 THE BASE OF ALL PIER HOLES SHALL BE FREE OF WATER AND CLEANED OF LOOSE SHALL BE FASTENED TO THE SOFFIT USING BRUNSWICK MFA - 4 SLIDING TIES
STRUCTURAL DRAWINGS SHALL BE MADE IN CONCRETE MEMBERS WITHOUT
- SITE WIND SPEED = 38m/s MATERIAL OR DEBRIS PRIOR TO PLACEMENT OF CONCRETE. ALLOW TO PROVIDE OR APPROVED EQUIVALENT AT 400mm CENTRES U.N.O.
THE PRIOR WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER.
* FLOOR LIVE LOADS TEMPORARY LINERS AS DEEMED NECESSARY. CM13 LOADBEARING HOLLOW BLOCK WALLS SHALL BE CAPPED WITH M.E.T. GRAPHITE
- PROVIDE DRIP GROOVES AT ALL EXPOSED EDGES, CHAMFERS, DRIP GROOVES,
- GROUND FLOOR = 3kPa GREASED SLIP JOINT OVER TOP COURSE OF BLOCKWORK. CORE FILLED LOAD CLIENT
REGLETS ETC TO BE TO ARCHITECTS DETAILS.
- COMPACTUS AREA
* FLOOR SDL
= 7.5kPa TRENCH BACKFILL AND C15 ALL PENETRATIONS TO HAVE 2-N16 TRIMMER BARS TOP AND BOTTOM TO BEARING WALLS TO BE STEEL TROWELLED LEVEL WITH TWO LAYERS OF ALCOR
OVER.
CATHOLIC EDUCATION OFFICE
FOR THE DIOCESE OF
JOB MANAGER: B.WHITING

EACH FACE U.N.O. EXTEND TRIMMERS 600 BEYOND PENETRATION.


- GROUND FLOOR = 1.0kPa UNDERGROUND SERVICES C16 SETDOWNS OR FALLS IN FLOOR SURFACES ARE NOT PERMITTED UNLESS CM14 WHERE MASONRY ADJOINS STRUCTURAL STEEL OR PASSES A RETURN WALL ON
THE INNER SKIN, INSTALL MEDIUM DUTY TIES AT 400 MAX. CTS. SHOT FIX TIES
WOLLONGONG
* ROOF LIVE LOADS TB1 ALLOW FOR EXCAVATION IN ALL MATERIALS AS FOUND U.N.O. SHOWN ON DRAWINGS. MAINTAIN MINIMUM SLAB THICKNESS SHOWN ON PLAN
- ROOF = 0.25kPa TB2 PRIOR TO COMMENCING EXCAVATION VERIFY LEVELS OF ALL EXISTING WHERE FALLS OCCUR. TO STEELWORK.
* ROOF SDL SERVICES. IF ANY DISCREPANCIES CHECK WITH THE RELEVANT ENGINEER. CM15 ALL STEEL LINTELS SUPPORTING BLOCKWORK ARE TO BE HOT DIPPED GALVANISED.
C17 REINFORCEMENT GRADE AND NOTATION: CM16 MINIMUM COVER TO REINFORCEMENT, FROM THE INSIDE FACE OF THE FACE SHELL,
- ROOF = 0.5kPa TB3 BACKFILL ALL TRENCHES UNDER SLABS, PATHS AND ROADS BELOW
SUBBASE LEVEL WITH ORIGINAL GROUND OR IMPORTED FILL. IS TO BE 5mm (T5.1 AS3700). PROJECT
STRENGTH TO COMPLY
* EARTHQUAKE LOADS: TB4 IMPORTED FILL PROPERTIES: DUCTILITY CM17 NO AIR ENTRAINING AGENTS (BYCOL, ETC) ARE TO BE USED WITHOUT PRIOR MARY IMMACULATE PRIMARY SCHOOL
SYMBOL BAR SHAPE GRADE WITH AUST.
- IMPORTANCE LEVEL =2 CLASS WRITTEN PERMISSION FROM NORTHROP ENGINEERS.
- PASSING 50mm SIEVE - 100% (MPa) STANDARD SCHOOL
- ANNUAL PROBABILITY OF EXCEEDANCE (P) = 1/500 - PASSING 75micron SIEVE - LESS THAN 25% CM18 MATERIALS INCLUDING MORTAR, CONCRETE, GROUT SHALL COMPLY WITH SECTION
- PROBABILITY FACTOR (kp) = 1.0 N DEFORMED RIB BAR 500 NORMAL AS4671 10 OF AS3700. MASONRY UNITS SHALL COMPLY WITH AS4455. WALL TIES SHALL STAGE 2 BLOCK K
- PLASTICITY INDEX - LESS THAN 15%
- HAZARD FACTOR (z) = 0.09 TB5 COMPACT FILL TO 95% MMDD EXCEPT LANDSCAPED AREAS WHICH SHALL R PLAIN ROUND BAR 250 NORMAL AS4671 COMPLY WITH AS2699.
- SITE SUB-SOIL CLASS = Ce BE 85% MMDD. CM19 MASONRY SHALL BE CONSTRUCTED IN ACCORDANCE WITH SECTION 11 OF AS3700.
RECTANGULAR MESH OF
- EARTHQUAKE DESIGN CATEGORY (EDC) =I RL 500 LOW AS4671 CM20 DO NOT CONSTRUCT MASONRY WALLS ON SUSPENDED CONCRETE SLABS UNTIL
TB6 ALLOW FOR 1 SUCCESSFUL COMPACTION TEST PER 20 METRES OF TRENCH DEFORMED RIB BAR
DESIGNED: B.WHITING

G14 THE METHOD OF CONSTRUCTION AND THE MAINTENANCE OF SAFETY SLAB HAS BEEN STRIPPED AND DEPROPPED.
IN THE MIDDLE LAYER.
DURING CONSTRUCTION IS THE RESPONSIBILITY OF THE BUILDER. IF ANY SQUARE MESH OF CM21 GENERAL:
SL 500 LOW AS4671
- PROVIDE 1 LINTEL TO EACH WALL LEAF, DO NOT CUT ON SITE. KEEP
STRUCTURAL ELEMENT PRESENTS DIFFICULTY IN RESPECT TO
CONSTRUCTABILITY OR SAFETY, THE MATTER SHALL BE REFERRED TO THE
CONSTRUCTION PHASE SERVICES DEFORMED RIB BAR
LINTELS 6mm CLEAR OF HEADS AND FRAMES. PACK MORTAR BETWEEN
L-TM TRENCH MESH 500 LOW AS4671
STRUCTURAL ENGINEER FOR RESOLUTION BEFORE PROCEEDING WITH THE - WITNESS POINTS ALL REINFORCING BARS SHALL BE GRADE D500N TO AS4671 AND ALL MESH
THE ANGLE UPSTAND AND SUPPORT MASONRY UNITS.
MINIMUM BEARING EACH END:
Wollongong
WORK. THE DETERMINATION OF A SAFE WORK METHOD REMAINS THE WP1 OBTAIN ENGINEER'S WRITTEN INSPECTION REPORT AT THE FOLLOWING Level 1, 57 Kembla Street, Wollongong, N.S.W. 2500
SHALL BE GRADE 500L TO AS4671 U.N.O. CLASS L REINFORCEMENT SHALL NOT - SPAN < 1800mm = 200mm Ph (02) 4226 3333 Email: southcoast@northrop.com.au
RESPONSIBILITY OF THE BUILDER. WITNESS POINTS: BE USED U.N.O. ALL REINFORCEMENT SHALL BE CERTIFIED BY THE 'AUSTRALIAN - SPAN > 1800mm AND < 3000mm = 400mm ABN 81 094 433 100
G15 NO CHANGES IN ANY STRUCTURAL ELEMENT SHALL BE MADE WITHOUT - PREPARATION OF FOUNDING MATERIAL. CERTIFICATION AUTHORITY FOR REINFORCING STEELS (A.C.R.S)'. PROPPING:
WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER. IF THERE IS A - REINFORCEMENT PRIOR TO CASTING CONCRETE. REINFORCEMENT LABELS: - TO PREVENT DEFLECTION OR EXCESSIVE ROTATION, TEMPORARILY PROP
DISCREPANCY THEN FOR TENDER PURPOSES ALLOW FOR THE MOST - STEEL FRAME INSPECTION PRIOR TO SHEETING.
EXPENSIVE OPTION. NORTHROP ENGINEERS SHALL BE CONTACTED TO N12-300 3N28 SL92 CENTRES AT 200mm PROPRIETARY COLD-FORMED LINTELS UNTIL THE MASONRY REACHES ITS
WP2 GIVE 48 HOURS NOTICE OF INSPECTION. ITS REQUIRED STRENGTH.
CONFIRM PRIOR TO CONSTRUCTION.
DRAWN: H.ABELLA

- MINIMUM PROPPING PERIOD : 7 DAYS


G16 CONSTRUCTION USING THESE DRAWINGS SHALL NOT COMMENCE UNTIL A
CONSTRUCTION CERTIFICATE HAS BEEN ISSUED AND ONLY IF THE DRAWINGS
TEMPORARY WORKS SPACING (mm)
BAR SIZE (mm)
BAR SIZE (mm)
TYPE OF REINFORCEMENT
BAR SIZE (mm)
DUCTILITY
TW1 THESE DRAWINGS DEPICT THE "PERMANENT" STRUCTURE, TEMPORARY DRAWING TITLE
ARE DESIGNATED " ISSUED FOR CONSTRUCTION". TYPE OF NUMBER OF BARS CLASS
G17 NORTHROP ENGINEERS ACCEPT NO RESPONSIBILITY FOR ANY WORK NOT
WORKS REMAIN THE RESPONSIBILITY OF THE CONTRACTOR.
REINFORCEMENT SQUARE MESH STRUCTURAL DRAWING
TW2 BUILDER MUST ENGAGE NPER QUALIFIED ENGINEER FOR THE DESIGN OF ALL SPECIFICATION NOTES -
INSPECTED OR NOT APPROVED BY THE STRUCTURAL ENGINEER DURING REINFORCEMENT IS REPRESENTED DIAGRAMMATICALLY, AND NOT
TEMPORARY WORKS NECESSARY TO SAFELY ERECT THIS STRUCTURE, AS A C18
CONSTRUCTION
MINIMUM THE FOLLOWING TEMPORARY WORKS REQUIRE ATTENTION: NECESSARILY IN TRUE PROJECTION. BARS SHOWN ARE INDICATIVE ONLY AND SHEET 1
- FORMWORK. LENGTHS MAY VARY. BEAM ELEVATIONS TAKE PRECEDENCE OVER SECTIONS.
- TEMPORARY PROPPING. SLAB PLANS TAKE PRECEDENCE OVER SECTIONS. REFER TO SECTIONS FOR
- NEEDLE BEAMS. EXTRA BARS THAT MAY BE REQUIRED.
- SCAFFOLDING. C19 USE ONLY ALL PLASTIC OR CONCRETE CHAIRS AT EXTERNAL SURFACES. JOB NUMBER DRAWING NUMBER REVISION
TW3 BUILDER MUST CONTACT NORTHROP ENGINEERS IF THEY CONSIDER ANY
PART OF THIS STRUCTURE IS UNSAFE TO ERECT.
FOR CONSTRUCTION 170975 S01 B
DRAWING SHEET SIZE = A1
DRAWINGS NOT TO BE USED FOR CONSTRUCTION UNLESS VERIFICATION SIGNATURE
HAS BEEN ADDED. THE COPYRIGHT OF THIS DRAWING REMAINS WITH NORTHROP

STEELWORK METAL STUD WALLS WORKPLACE HEALTH AND SAFETY CLAY BRICK MASONRY CONSULTING ENGINEERS PTY LTD. ALL SETOUT TO ARCHITECT'S DRAWINGS.
DIMENSIONS TO BE VERIFIED WITH ARCHITECT AND BUILDER BEFORE COMMENCING SHOP
WHS1 THE CONTRACTOR AND ALL SUBCONTRACTORS ARE RESPONSIBLE FOR CONSTRUCTING EXPOSURE CLASSIFICATION: MODERATE (>10km FROM COAST) DRAWINGS OR SITE WORK. NORTHROP ACCEPTS NO RESPONSIBILITY FOR THE
CATEGORY C - ATMOSPHERIC CORROSIVITY MEDIUM SW1 ALL DESIGN, WORKMANSHIP AND MATERIAL TO AS/NZS4600. CB1 MASONRY CONSTRUCTION IS TO CONFORM TO AS3700.
SW2 PROVIDE BRACING IN WALLS AS PER THE PLANS, USING PRYDA 30 X 0.8 THE WORK IN ACCORDANCE WITH THE WORK HEALTH AND SAFETY (WHS) ACT 2011; USABILITY, COMPLETENESS OR SCALE OF DRAWINGS TRANSFERRED ELECTRONICALLY.
S1 FABRICATE AND ERECT STRUCTURAL STEELWORK IN ACCORDANCE WITH AS4100. - MORTAR CLASSIFICATION = M2
GALVANISED STRAP BRACING OR EQUIVALENT FIXED TO THE STUD WALLS, WHS REGULATIONS 2011; RELEVANT CODES OF PRACTICE, AUSTRALIAN STANDARDS AND
S2 FABRICATOR TO INFORM NORTHROP ENGINEERS IF IMPORTED STEEL IS PROPOSED TO BE USED. - DURABILITY CLASSIFICATION OF BUILT IN COMPONENTS = R2
OR NOGGING SECTIONS. FIX STRAP TO EACH STUD BY ONE (1) WAFER HEADED OTHER REGULATORY REQUIREMENTS. THE PRINCIPLE CONTRACTOR MUST INFORM ALL
S3 PROVIDE HOLES, CLEATS AND FIXING FOR TIMBER FRAMING, FINISHES, ETC. SHOWN ON - DURABILITY GRADE OF EXTERNAL MASONRY UNITS = EXPOSURE GRADE
SELF DRILLING METAL SCREW (4.8mm DIAMETER). STAKEHOLDERS, INCLUDING NORTHROP, OF NEW HAZARDS IDENTIFIED IN THE COURSE OF
ARCHITECTURAL DRAWINGS. CB2 THE CHARACTERISTIC UNCONFINED COMPRESSIVE STRENGTH OF THE MASONRY UNITS
PLANNING AND UNDERTAKING THE WORKS.
S4 FABRICATOR SHALL PREPARE SHOP DRAWINGS AND SUBMIT THEM TO THE TOP TRACK 1.15 BMT (MAY BE SLOPING) WHS2 DURING THE DESIGN OF THE STRUCTURE NORTHROP HAS IDENTIFIED RESIDUAL HAZARDS SHALL BE A MINIMUM OF 20 MPa.
BUILDER FOR THEIR APPROVAL. BUILDER SHALL LODGE TWO HARD COPIES OF APPROVED RELATING TO THE DESIGN OF THE STRUCTURAL WORKS THAT WE CONSIDER TO BE CB3 BED UNITS IN FRESHLY PREPARED MORTAR, UNIFORMLY MIXED CEMENT, LIME AND
DRAWINGS TO NORTHROP ENGINEERS PTY LTD FOR APPROVAL PRIOR TO FABRICATION. UNUSUAL OR NON-TYPICAL. HAZARDS WHICH ARE NORMAL WORKPLACE HAZARDS, ARE SAND IN THE RATIO OF 1:1:6, CONFORMING TO AS 3700.
S5 UNLESS NOTED OTHERWISE, USE: DOUBLE STUD TO BE MANAGED BY PERSONS IN CONTROL OF THE WORKPLACE THROUGH A WHS SYSTEM CB4 NO CUTTING, CHASING OR RAKING OF JOINTS IN EXCESS OF 5mm UNLESS AUTHORISED
- 10mm GUSSET, FIN AND END PLATES. OR STEEL COLUMN TO MANAGE THE NORMAL HAZARDS ASSOCIATED WITH CONSTRUCTION, USE AND BY THE STRUCTURAL ENGINEER FOR EVERY LOCATION.
RONDO LIPPED CB5 EXPANSION/CONTRACTION JOINTS SHALL BE PROVIDED IN ACCORDANCE WITH THE
- M20 8.8/S BOLTS. MAINTENANCE OF THE STRUCTURE. THE RESIDUAL HAZARDS IDENTIFIED ON THE NORTHROP
- 6mm CONTINUOUS FILLET WELDS MADE WITH E4818 MILD STEEL ELECTRODES. STUDS SHOWN THUS REQUIREMENTS OF THE BCA, BUT GENERALLY AT A MAXIMUM SPACING OF 5m AND
DRAWINGS ARE NOT AN ENTIRE ASSESSMENT OF HAZARDS, AND DO NOT RELIEVE OTHER
- ALL WELDS SP CATEGORY TO AS1554. PARTIES OR STAKEHOLDERS OF THE THEIR RESPONSIBILITY UNDER THE WHS ACT 2011, 2.5m FROM A CORNER, U.N.O.

45°
- 8.8/TB BOLTS AT BEAM SPLICE LOCATIONS. WHS REGULATIONS 2011, AND THE CODE OF PRACTICE FOR SAFE DESIGN OF STRUCTURES. CB6 MASONRY TIES SHALL BE GALVANISED WITH A MINIMUM COATING MASS OF 470g/sq.m
ADDITIONAL 1-M10 PER SIDE OR GRADE 316 STAINLESS STEEL AND OF MEDIUM DUTY CLASSIFICATION
S6 ALL BOLTS, SCREWS, HOLD DOWN BOLTS, MASONRY ANCHORS SHALL BE
MASONRY ANCHOR BOTTOM TRACK 1.15 BMT U.N.O. AND APPROPRIATE FOR CAVITY WIDTH. ANY FACE FIXED TIE SHALL BE FIXED
HOT DIP GALVANISED TO AS1214 AND AS1650. UNLESS NOTED OTHERWISE ALL BOLTS WHS3 TEMPORARY BRACING AND SUPPORT OF STRUCTURE IS THE RESPONSIBILITY OF THE
100 FROM END STUD USING A SCREW TYPE FIXING AND SHALL NOT BE NAILED. TIES TO STEEL SHALL BE
SHALL BE M20 8.8/S. NO CONNECTION SHALL HAVE LESS THAN 2 BOLTS. ALL BOLTS CONTRACTOR AND SHALL BE MAINTAINED DURING ALL STAGES OF CONSTRUCTION.
GALVANISED 30 x 0.8 U.N.O. STRAP BRACING 1 SIDE OF WALL WHS4 RESIDUAL HAZARDS ARE SHOWN ON THE NORTHROP DRAWINGS. ABBEY TREMOR TIES OR APPROVED EQUIVALENT.
AND WASHERS SHALL BE GALVANISED. ALL HOLES SHALL BE 2mm LARGER THAN THE
WITH TENSIONER TYP. BEND BRACE UNDER OR OVER TRACKS IDENTIFIED BY: CB7 SPACING OF MASONRY TIES:
BOLT DIAMETER UNLESS NOTED OTHERWISE.
S7 ALL STRUCTURAL STEEL TO COMPLY WITH AS1163, AS1594, AS3678, AS3679 PART 1 AND AND FIX AFTER FOLD WITH 2-4.87mm DIA SELF DRILLING S1 - ADJACENT TO WINDOWS AND RETURN WALLS,
PART 2 AS PER SECTION TYPE, WITH MINIMUM YIELD STRESS: METAL SCREWS OR 1-M10 MASONRY ANCHOR TO CONCRETE SLAB - 300mm VERTICAL AND HORIZONTAL.
- HOT ROLLED SECTIONS = 300MPa BRACING DETAIL (NOGGINGS NOT SHOWN). - SOLID MASONRY, 400mm VERTICAL AND HORIZONTAL.
- SQUARE HOLLOW SECTIONS = 350MPa SW3 PROVIDE LIPPED AND GALVANISED WALL STUDS AS FOLLOWS U.N.O. ON DRAWINGS. METAL DECK ROOFING CB8 WHERE
- OTHERWISE, 600mm VERTICAL AND HORIZONTAL.
MASONRY ADJOINS STRUCTURAL STEEL, OR PASSES A RETURN WALL ON
- RECTANGULAR HOLLOW SECTIONS = 350MPa MD1 OBSERVE MANUFACTURERS RECOMMENDATIONS FOR APPROPRIATE NUMBER AND TYPE
THE INNER SKIN PROVIDE MEDIUM DUTY TIES AT 300 MAX. CENTRES. SHOT FIX
- CIRCULAR HOLLOW SECTION = 250MPa WALL TYPE SPACING (mm) MAX. HEIGHT OF ROOF SCREWS.
TIES TO STEELWORK, ENSURE NAILS WILL BE CONCEALED.
- HOT ROLLED PLATE = 250MPa MD2 SHEETS PLACED ADJACENT TO GABLE ENDS ARE TO BE SCREW FIXED AS PER
INTERNAL CB9 LOADBEARING WALLS SHALL BE TOPPED WITH M.E.T. GRAPHITE GREASED SLIP
S8 COLD FORMED SECTIONS TO CONFORM WITH: 600 4200 MANUFACTURERS REQUIREMENTS FOR EAVES.
92.1 x 0.55 BMT JOINT OVER TOP COURSE OF BRICKWORK.
- AS/NZS4600, AS1397 AND AS1595. MD3 WHERE DECKING IS FIXED TO BATTENS, AT EAVES, GABLES AND RIDGES INCREASE
CB10 NON-LOADBEARING WALLS SHALL FINISH 20mm SHORT OF SLAB SOFFIT AND
- MINIMUM YIELD STRESSES: SECTIONS 350MPa. EXTERNAL AND THE BATTEN TO RAFTER FIXINGS TO REFLECT THE EXTRA ROOF DECK FIXINGS. THIS
SHALL BE FASTENED TO THE SLAB SOFFIT USING BRUNSWICK MFA - 4 SLIDING
S9 SURFACE TREATMENT UNLESS NOTED OTHERWISE, FOR 15 YEARS TO FIRST MAINTENANCE: LINED INTERNALLY 600 3400 CAN BE ACHIEVED WITH METAL STRAPS OR BATTEN TIES.
TIES OR APPROVED EQUIVALENT AT 460mm CENTRES.
92.1 x 0.75 BMT
- PROTECTED FROM WEATHER
- EXPOSED TO WEATHER
- AS/NZ2312-ALK2.
- AS/NZ2312-IZS2. EXTERNAL AND NOT
REPAIR OF FIELD WELDS IN HOT DIP GALVANISING CB11 U.N.O. ALL MASONRY ANCHORS INTO CLAY MASONRY SHALL BE HILTI
HIT-HY20 CHEMICAL INJECTION ANCHORS OR APPROVED EQUIVALENT AND ANCHORS
ON EXTERNAL, EXPOSED TO WEATHER PAINTED ELEMENTS, APPLY PRIMER STRIP LINED INTERNALLY 600 2500 HD1 POWER TOOL CLEAN TO AUSTRALIAN STANDARD 1627.2 CLASS 3. REMOVE ALL WELDING
EXPOSED TO WEATHER SHALL BE HOT DIPPED GALVANISED STEEL.
COATING TO ALL CORNERS AND SHARP EDGES. 92.1 x 0.75 BMT 600 3200 SCALE, SLAG AND CORROSION PRODUCTS.
CB12 ALL LINTELS SUPPORTING BRICKWORK ARE TO BE HOT DIP GALVANISED WITH
- BUILT INTO AN EXTERNAL MASONRY WALL - AS/NZ2312-IZS2. 92.1 x 1.15 BMT HD2 DEGREASE AND REMOVE ALL SURFACE CONTAMINANTS.
MINIMUM COATING MASS OF 600g/sq.m.
- IF GALVANISING IS THE FINISHED COATING HOT DIPPED GALVANISING SHALL HD3 APPLY 2 COATS OF "EPOXY ZINC RICH PRIMER" OR APPROVED EQUIVALENT TO A MINIMUM
CB13 NO AIR ENTRAINING AGENTS (BYCOL, ETC) ARE TO BE USED WITHOUT PRIOR
BE IN ACCORDANCE WITH - AS4680. OF 125µm DRY FILM THICKNESS.
WRITTEN PERMISSION FROM NORTHROP ENGINEERS.
S10 FIX CROSS BRACING TO PURLINS AT 3000 MAXIMUM CTS WITH M10 BOLTS OR M6 HOOKS. SW4 PROVIDE NOGGINGS AT 1.6 METRES CTS MAX U.N.0. NOGGING SECTION HD4 OBSERVE GOOD PAINTING PRACTICE WITH RESPECT TO WEATHER AND APPLICATION
CB14 MATERIALS INCLUDING MORTAR, CONCRETE, GROUT SHALL COMPLY WITH SECTION
S11 ALL BURIED STEELWORK TO BE ENCASED IN CONCRETE WITH A MINIMUM COVER OF 50mm SHALL BE 0.75 BMT. NOGGINGS SHALL BE MECHANICALLY FIXED TO STUDS AS CONDITIONS.
10 OF AS3700. MASONRY UNITS SHALL COMPLY WITH AS4455. WALL TIES SHALL
TO STEELWORK. PER MANUFACTURERS SPECIFICATIONS. HD5 STIPPLE EDGES OF THE PAINTED AREA TO ACHIEVE OPTIMUM APPEARANCE OF THE REPAIR.
COMPLY WITH AS2699.
S12 STEELWORK TO BE CONCRETE ENCASED SHALL BE FREE FROM ALL LOOSE RUST, SW5 PROVIDE DOUBLE 1.15mm 'C' CHANNEL STUDS (BOXED) AND 1 EXTRA STUD HD6 ADHERE TO COATING MANUFACTURER'S PRODUCT INSTRUCTIONS.
CB15 MASONRY SHALL BE CONSTRUCTED IN ACCORDANCE WITH SECTION 11 OF AS3700.
LOOSE MILL SCALE, DIRT, OIL, GREASE, ETC. AND REINFORCED WITH F41 FABRIC OR AT SIDES OF OPENING. HD7 IF A CLOSE COLOUR MATCH IS ESSENTIAL, IMMEDIATELY ON COMPLETION, 1 COAT OF ALUMINIUM
CB16 DO NOT CONSTRUCT MASONRY WALLS ON SUSPENDED CONCRETE SLABS UNTIL
EQUIVALENT BLACK IRON WIRE, 3mm DIA. SW6 PROVIDE DOUBLE 1.15mm 'C' CHANNEL STUDS (BOXED) PAINT MAY BE APPLIED OVER GALVANITE FOR APPEARANCE ONLY. OTHERWISE COLOUR
SLAB HAS BEEN STRIPPED AND DEPROPPED.
S13 BOLT SYMBOLS: AT INTERMEDIATE GLAZING SECTIONS: MATCH WILL BE ACHIEVED OVER TIME.
CB17 GENERAL:
- 4.6/S - COMMERCIAL BOLTS OF STRENGTH GRADE 4.6 TO AS/NZS1111, - PROVIDE 1 LINTEL TO EACH WALL LEAF, DO NOT CUT ON SITE. KEEP
SNUG FIT. LINTELS 6mm CLEAR OF HEADS AND FRAMES. PACK MORTAR BETWEEN
DOUBLE BOXED
- 8.8/S - HIGH STRENGTH BOLTS OF STRENGTH GRADE 8.8 TO AS/NZS1254, STUD OR STEEL EARTHWORKS UNDER GROUND SLAB THE ANGLE UPSTAND AND SUPPORT MASONRY UNITS.

2800 MAX.
SNUG FIT. COLUMN MINIMUM LINTEL SIZES (AS PER BCA) OR AS FOLLOWS:
- 8.8/TF - HIGH STRENGTH BOLTS OF STRENGTH GRADE 8.8 TO AS/NZS1254, STEEL COLUMN OR
DOUBLE BOXED STUD
(EXISTING FILL RETAINED) - SPAN 0mm TO 900mm = 10mm FLAT BAR.
FULLY TENSIONED FRICTION TYPE (USE LOAD INDICATOR WASHERS). E1. REFER TO THE GEOTECHINCAL ENGINEERS REPORT SPECIFIED IN THE FOUNDATION NOTES. - SPAN 901mm TO 2100mm = 100 x 100 x 10 EA.
- 8.8/TB - HIGH STRENGTH BOLTS OF STRENGTH GRADE 8.8 TO AS/NZS1254, AND 1 EXTRA STUD E2. STRIP SITE OF ALL TOPSOIL, VEGETATION AND DELETERIOUS MATTER TO A - SPAN 2101mm TO 3100mm = 150 x 100 x 10 UA. REV DESCRIPTION ISS'D VER'D APP'D DATE
FULLY TENSIONED BEARING TYPE (USE LOAD INDICATOR WASHERS). AT SIDES OF OPENING MINIMUM DEPTH OF 150mm. PROPPING: 1 PROGRESS ISSUE J.H. B.W. 30.06.17
S14 THE CONTRACTOR SHALL SUPPLY WRITTEN CERTIFICATION TO THE STRUCTURAL 2500 MAX. E3. PROOF ROLL SUBGRADE TO REVEAL SOFT SPOT. SOFT SPOTS TO BE REMOVED AND - TO PREVENT DEFLECTION OR EXCESSIVE ROTATION, TEMPORARILY PROP 2 ISSUED FOR 95% REVIEW J.H. B.W. 14.07.17
ENGINEER PRIOR TO THE ERECTION OF ANY STRUCTURAL STEEL STATING THAT THE HEAD AND SILL MEMBERS BACKFILLED. ALL NATURAL SUBGRADE IS TO BE COMPACTED TO 98% STANDARD PROPRIETARY COLD-FORMED LINTELS UNTIL THE MASONRY REACHES ITS A ISSUED FOR CONSTRUCTION H.A. R.P. B.W. 21.07.17
BOLTS PROPOSED TO BE USED COMPLY WITH AS1252. HIGH STRENGTH BOLTS (8.8) 1. UP TO 1800 SPAN - 92x1.15 'C' CHANNEL STUD COMPACTION IN ACCORDANCE WITH AS1289 PRIOR TO PLACEMENT OF FILL MATERIAL. REQUIRED STRENGTH. IN ACCORDANCE WITH MANUFACTURERS REQUIREMENT.
ARE NOT TO BE WELDED. 2. UP TO 2500 SPAN - 3x92x1.15 'C' CHANNEL STUD E4. THE CONTRACTOR IS TO ENGAGE A QUALIFIED (NPER) GEOTECHINCAL ENGINEER TO - MINIMUM PROPPING PERIOD : 7 DAYS
S15 NO PAINT ON MATING SURFACES WITH TF BOLTING UNLESS APPROVED BY APPROVE THE FOUNDATION MATERIAL. SUBMIT CERTIFICATE IN WRITING TO THE
ENGINEER. PREPARE SURFACES FOR TF CONNECTIONS IN ACCORDANCE WITH SW7 UNLESS NOTED OTHERWISE, STUD WALLS SHALL BE NON LOAD BEARING. CONSULTING ENGINEER PRIOR TO CONCRETE FOUNDATIONS. CONCRETE TESTING
VERIFIER: Approver

SECTION 14.3.6 AF AS4100. ALLOW FOR DEFLECTION OF STUDS WITHIN TOP TRACK AT 20mm. ARCHITECT
E5. WE SUPPORT THE USE OF CONTAMINANT FREE, RECYCLED CONCRETE OR BRICK IN LIEU OF CT1 DEFINITIONS:
S16 BOLTS TO BE INSTALLED WITH ONE HARDENED WASHER UNDER THE SW8 FIX BOTTOM TRACK OF BRACED PANELS TO CONCRETE FLOOR AS PER SW2.
CRUSHED ROCK IN APPROPRIATE CIRCUMSTANCES. - PRODUCTION ASSESSMENT = QUALITY ASSURANCE TESTING CARRIED
FOR ALL OTHER FIXINGS REFER TO MANUFACTURERS SPECIFICATION.
TURNED PART. E6. IMPORTED FILL PROPERTIES: OUT BY THE CONCRETE MANUFACTURER.
SW9 BOTTOM PLATES SHALL BE FIXED TO CONCRETE SLABS USING RAMSET LDU95
S17 TF AND TB BOLTING BY "PART TURN" METHOD WITH LOAD INDICATING WASHERS. - PASSING 50mm SIEVE: 100mm - PROJECT ASSESSMENT = TESTING OF CONCRETE SAMPLES TAKEN
DRIVEPINS WITH GALVANISED 19mm WASHERS AT 900 CTS OR APPROVED
S18 ENSURE ALL BOLTS HAVE SUFFICIENT LENGTH SO THAT AT LEAST ONE FULL THREAD IS - PASS 75 MICRON SIEVE: LESS THAN 75% ONTO SITE AT DISCHARGE POINTS.
EQUIVALENT.
EXPOSED BEYOND THE NUT AFTER TIGHTENING. - PLASTICITY INDEX: LESS THAN 15%, MORE THAN 2% CT2 SUPPLY OF CONCRETE SHALL BE FROM A CONCRETE PLANT THAT CARRIES
SW10 UNLESS NOTED OTHERWISE, LATERALLY RESTRAIN TOP PLATES AT 1800 CTS USING
S19 THE FABRICATION AND ERECTION OF THE STRUCTURAL STEEL WORK METAL STUDS SHOT FIXED TO THE UNDERSIDE OF A SLAB OR SCREW FIXED TO THE OUT PRODUCTION ASSESSMENTS FOR THE COMPRESSIVE STRENGTH AND DRYING
SHALL BE SUPERVISED BY A QUALIFIED PERSON EXPERIENCED IN SUCH SUPERVISION, SHRINKAGE GRADES SPECIFIED FOR THIS PROJECT.
ROOF FRAMING ELEMENTS. SCREW FIX TO TOP PLATE.
IN ORDER TO ENSURE THAT ALL REQUIREMENTS OF THE DESIGN ARE MET. CT3 CONCRETE QUALITY FOR SLABS ON GROUND (UP TO 110mm THICK) SHALL BE CLIENT
S20 ALL MEMBERS SHALL BE SUPPLIED IN SINGLE LENGTHS. SPLICES SHALL ONLY REINFORCEMENT & LAPPING SCHEDULE (UNO) VERIFIED BY PRODUCTION ASSESSMENT.
CATHOLIC EDUCATION OFFICE
CT4 CARRY OUT PROJECT ASSESSMENT FOR REMAINDER OF CONCRETE AS FOLLOWS:
BE PERMITTED IN LOCATIONS SHOWN ON THE STRUCTURAL DRAWINGS. FOR THE DIOCESE OF
PURLINS AND GIRTS L L - CONCRETE SHALL BE SUPPLIED AND TESTED IN ACCORDANCE WITH
JOB MANAGER: B.WHITING

S21 ALL BUTT WELDS SHALL BE COMPLETE PENETRATION BUTT WELDS CATEGORY AS 1379 AND AS1012. WOLLONGONG
BAR LESS THAN 300 CONCRETECAST MORE THAN 300 CONCRETE
SP TO AS1554.1 U.N.O. THE EXTENT ON NON-DESTRUCTIVE WELD EXAMINATION - THE ORGANISATION(S) RESPONSIBLE FOR SAMPLING AND TESTING OF
SHALL BE AS NOTED BELOW UNLESS OTHERWISE NOTED. RADIOGRAPHIC OR BELOW BAR OR VERTICALBAR CAST BELOW BAR CONCRETE TO HAVE RELEVANT 'NATA' LABORATORY REGISTRATION,
ULTRASONIC EXAMINATION SHALL BE TO AS1554.1, AS2177.1 AND AS2207 AS BE INDEPENDENT, AND USE TRAINED,COMPETENT PERSONNEL FOR THE
N12 500 650
APPROPRIATE. ALL BUTT WELDS SHALL BE SUBJECT TO NON-DESTRUCTIVE TAKING OF SAMPLES AND SPECIMENS AND THE PREPARATION OF
EXAMINATION IN ACCORDANCE WITH AS1554.1, AS2177.1 AND AS220. N16 600 800 MATERIALS AND WORK FOR TESTING. PROJECT
THE EXTENT OF TESTING SHALL BE AS FOLLOWS: - SLUMP AT TIME OF POURING TO BE WITHIN THE PERMISSIBLE TOLERANCE
LOAD N20 900 1200 IN AS1379 FOR NOMINAL SLUMP SPECIFIED.
MARY IMMACULATE PRIMARY SCHOOL
VISUAL EXAMINATION IN RADIOGRAPHY OR - AT LEAST 1 SAMPLE FOR EVERY 50cu.m SHALL BE TAKEN AT THE SITE, SCHOOL
WELD VISUAL
ACCORDANCE WITH TABLE ULTRASONICS TO BUT NOT LESS THAN 3 SAMPLES SHALL BE TAKEN PER POUR. FIRST STAGE 2 BLOCK K
CATEGORY SCANNING APPROVED NON-APPROVED L
6.2.2 AS 1554.1 TABLE 6.2.1 AS 1554.1 L L AND LAST BATCH PER DAY TO BE SAMPLED, THE OTHER TAKEN
GP 100 25 NIL PG1 MINIMUM YIELD STRESSES: PROGRESSIVELY DURING THE POUR, RECORDING LOCATION IN POUR
- PURLINS AND GIRTS 450MPa. WHERE SAMPLE WAS TAKEN.
SP 100 50 10 - SURFACE TREATMENT - HOT DIPPED ZINC COATING, AT LEAST 300g/sq.m U.N.O. - IT IS PERMISSIBLE TO REDUCE THE NUMBER OF SAMPLES TO 2 FOR
DESIGNED: B.WHITING

- LAPS, BRIDGING, BRACKETS AND PURLIN BOLTS IN ACCORDANCE WITH POURS OF LESS THAN 30cu.m, AND 1 FOR POURS OF LESS THAN 10cu.m.
THE CONTRACTOR SHALL SUBMIT THE APPROPRIATE TEST CERTIFICATES
MANUFACTURER'S INSTRUCTIONS. L L L L - A SAMPLE CONSISTS OF AT LEAST 3 CYLINDERS. ONE CYLINDER SHALL
TO THE STRUCTURAL ENGINEER PRIOR TO STRUCTURAL CERTIFICATION. BE TESTED AT 7 DAYS. TWO CYLINDERS SHALL BE TESTED AT 28 DAYS.
PG2 UNLESS OTHERWISE DETAILED FABRICATOR SHALL PROVIDE C100 15 TRIMMER PURLINS
S22 GROUT ALL STEEL BASES BY DRY PACKING USING GROUT WHICH IS NON- 7 + 28 DAY TEST RESULTS TO BE SENT IMMEDIATELY TO NORTHROP
ALONG WITH GENERAL PURPOSE BRACKETS TO SUPPORT EDGE OF ROOF SHEETING AT
SHRINK AND HAS A MINIMUM COMPRESSIVE STRENGTH AT 7 DAYS OF 40MPa
ALL HIPS, VALLEYS AND PENETRATIONS. ; PROVIDE 2-N16 TRIMMER BARS x 1200 LONG AT ALL RE-ENTRANT CORNERS. ENGINEERS.
S23 PROVIDE SEAL PLATES TO THE ENDS OF ALL HOLLOW SECTIONS, WITH
PG3 UNLESS OTHERWISE DETAILED, FABRICATOR SHALL ALLOW TO PROVIDE ONE ROW OF ; PROVIDE FALLS & STEPS IN SLAB AS PER ARCH DRAWINGS - IF MORE THAN ONE STRENGTH GRADE IS BEING USED IN A POUR, EACH Wollongong
'BREATHER' HOLES IF MEMBERS ARE TO BE HOT DIP GALVANISED.
BRIDGING FOR PURLINS SPANNING UP TO 4.0m, TWO ROWS FOR PURLINS SPANNING ; CONFIRM SETDOWNS & LOCATIONS WITH ARCH DRAWINGS STRENGTH GRADE SHALL BE CONSIDERED A SEPARATE POUR FOR THE
Level 1, 57 Kembla Street, Wollongong, N.S.W. 2500

;
Ph (02) 4226 3333 Email: southcoast@northrop.com.au
S24 THESE DRAWINGS MAY NOT IDENTIFY ALL SECONDARY STEELWORK ELEMENTS LAP TOP BARS MID-SPAN. LAP BTM BARS AT SUPPORTS. (TYPICAL UNO) PURPOSES OF TESTING. ABN 81 094 433 100
BETWEEN 4.0m AND 8.0m AND THREE ROWS FOR SPANS GREATER THAN 8.0m INSTALLED
THAT ARE REQUIRED FOR SUPPORT, FIXING AND FINISHING OF GLAZING, IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS. ; FABRIC SHALL HAVE A MINIMUM LAP OF TWICE THE WIRE SPACING FOR WIRES - WHERE EARLY STRENGTH IS SPECIFIED TESTING AND TOLERANCE ARE
TO BE IN ACCORDANCE WITH B8.
CLADDING AND LINING. THE TENDERER IS RESPONSIBLE FOR THE INCLUSION OF PG4 PURLIN CLEATS SHALL GENERALLY BE MINIMUM 75 LONG x 8 PLATE U.N.O. WHERE THE IN EACH DIRECTION (TYPICAL UNO)
- WHERE A LIMITING SHRINKAGE LESS THAN 850 x 10^-6 IS SPECIFIED, THE
SUCH STEELWORK ELEMENTS TO THE EXTENT REQUIRED ON THE ARCHITECT'S DISTANCE BETWEEN THE UNDERSIDE OF PURLIN AND THE TOP OF THE BEAM EXCEEDS CONCRETE SHALL BE SAMPLED AND TESTED USING PRODUCTION ASSESSMENT.
DRAWINGS. 150mm THE CLEATS SHALL BE MINIMUM 75 x 6 EA. UP TO A MAXIMUM HEIGHT OF 800mm.
DRAWN: H.ABELLA

S25 FABRICATOR SHALL PROVIDE ALL FIXINGS FOR ARCHITECTURAL ELEMENTS PG5 PURLINS SHALL BE LAPPED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS
WITHOUT WEAKENING STRUCTURAL MEMBERS. UNLESS SHOWN ON THE DRAWINGS.
S26 THE CONTRACTOR SHALL PROVIDE TEMPORARY BRACING AS NECESSARY TO STABILISE DRAWING TITLE
THE STRUCTURE UNTIL PERMANENT BRACING ELEMENTS ARE CONSTRUCTED. STRUCTURAL DRAWING
S27 ERECTION TOLERANCES SHALL COMPLY WITH AS4100. SPECIFICATION NOTES -
SHEET 2

JOB NUMBER DRAWING NUMBER REVISION

FOR CONSTRUCTION 170975 S02 A


DRAWING SHEET SIZE = A1
DRAWINGS NOT TO BE USED FOR CONSTRUCTION UNLESS VERIFICATION SIGNATURE
HAS BEEN ADDED. THE COPYRIGHT OF THIS DRAWING REMAINS WITH NORTHROP
CONSULTING ENGINEERS PTY LTD. ALL SETOUT TO ARCHITECT'S DRAWINGS.
DIMENSIONS TO BE VERIFIED WITH ARCHITECT AND BUILDER BEFORE COMMENCING SHOP
DRAWINGS OR SITE WORK. NORTHROP ACCEPTS NO RESPONSIBILITY FOR THE
USABILITY, COMPLETENESS OR SCALE OF DRAWINGS TRANSFERRED ELECTRONICALLY.
B0
B1 NOTE:
B2 FOUNDATION SCHEDULE 1. FOR STRUCTURAL SPECIFICATION NOTES REFER TO DWG S01 &
S02
FOR MAIN STRUCTURE GROUND FLOOR AND FOUNDATION PLAN B Z7 MARK SIZE COMMENT(S) 2. FOR TENDER PURPOSES ASSUME AVERAGE PILE LENGTH TO
1100x400D 5-N12 TOP AND BOTTOM, N12-400 TIES BE 1500 LONG (U.N.O)
REFER TO DRAWING S10 GB1 450Wx500D 4N16 TOP & BTM + N12-300 TIES 3. FOUNDATION DESIGN BASED ON ARTICULATED MASONRY BRICK
2 VENEER WALLS, ARTICULATION JOINTS TO BE PROVIDED AT
S55 GB2 1050Wx500D 8N16 TOP & BTM + 2N12-300 TIES
GB3 980W x 500D 8N16 TOP & BTM + 2N12-300 TIES 5000 CTS. MAX.
P1 450 DIA. 300mm SOCKET INTO ROCK 4N16 VERTICAL,
B3 1 R6-240 TIES
S55
B4 P2 600 DIA. 300mm SOCKET INTO ROCK 8N16 VERTICAL,
B5 R6-240 TIES
REFER DRAWING S55 FOR P3 600 DIA. 300mm MIN. SOCKET INTO ROCK AND BASE
/U
EXSITING P3 PIERS. /U P3 1/O EXTERNAL PEDESTRIAN OF PIER TO BE MIN. 1500mm BELOW FINISHED
P4F1/O PF A1 RAMP PLAN AND SECTIONS PAVEMENT LEVEL 8N16 VERTICAL, R6-240
POURED WITH STAGE 1 /U O P TIES
P4 F1/
P P4 450 DIA. 300mm MIN. SOCKET INTO ROCK AND BASE
/O
/U F1 OF PIER TO BE MIN. 1500mm BELOW FINISHED
P3 F1/O
P /U

SF1
P P3 1/O EXTEND PIER REO TO TOP PAVEMENT LEVEL 4N16 VERTICAL, R6-240
PF REO OF SF1 AND COG 300 /U TIES
/U P3 1/O

SF1
P4 SF1 600x400D 4-N16 TOP AND BOTTOM COGGED AT ENDS
PF A0
+ N12-300 TIES

600
/U O /U EXISTING STRUCTURE
P3 F1/ P4 O SF2 1050Wx500D MIN. 8N16 TOP & BTM + N16-300 TIES
P 1/
1

O
BH

1/ 1/
O PF SF3 450x500D MIN. 4-L12TM TOP AND BOTTOM, R6-900 TIES
PF

300
/U O PF
P3 F1/ SF4 450x500D MIN. 3N12 TOP AND BOTTOM, N10-400 TIES
P
SF5 800x600D MIN. 4-N16 TOP AND BOTTOM + N16-300 CLOSED
ALLOW FOR MANUAL TIES. TO CONTINUOUSLY BEAR ON NATURAL
EXCAVATION B MATERIAL OR CONTROLLED FILL WITH MIN.
ALLOWABLE BEARING PRESSURE OF 100kPa

EXISTING STRUCTURE
STEEL COLUMN SCHEDULE
MARK SIZE COMMENT(S)
SOUTHERN VERANDAH FOUNDATION PLAN PF1 200x100x5.0 RHS VERANDAH PORTAL FRAME STEEL COLUMN
SC1 125x125x5.0 SHS STEEL COLUMN
SC2 90x90x5.0 SHS STEEL COLUMN
SC3 200x100x6.0 RHS STEEL COLUMN
SC4 125x125x9.0 SHS STEEL COLUMN

LEGEND
150 DENOTES 150 SLAB THICKNESS U.N.O. N12-250 EW CENTRAL

REV DESCRIPTION ISS'D VER'D APP'D DATE


100 DENOTES SLAB STEP 1 ISSUED FOR 95% REVIEW J.H. B.W. 14.07.17
A ISSUED FOR CONSTRUCTION H.A. R.P. B.W. 21.07.17
B REVISED AS CLOUDED H.A. B.W. 20.10.17
DENOTES PENETRATION/VOID IN SLAB, PROVIDE TRIMMER BARS AS PER DETAIL

BW1/O
VERIFIER: R.PRATT

DENOTES LOAD BEARING BLOCK WALL OVER


ARCHITECT
BW1/U
DENOTES LOAD BEARING BLOCK WALL UNDER

BW1
DENOTES LOAD BEARING BLOCK WALL OVER AND UNDER

O
1/
SC
DENOTES STEEL COLUMN OVER
CLIENT

U
1/
CATHOLIC EDUCATION OFFICE

SC
DENOTES STEEL COLUMN UNDER
FOR THE DIOCESE OF
JOB MANAGER: B.WHITING

WOLLONGONG

1
SC
DENOTES STEEL COLUMN OVER AND UNDER

A DENOTES N12-600, 2500 LONG EXTRA CENTRAL

BH1 PROJECT
DENOTES APPROXIMATE LOCATION OF BORE HOLES.
REFER GEOTECHNICAL REPORT MARY IMMACULATE PRIMARY SCHOOL
SCHOOL
STAGE 2 BLOCK K
B.C.J. DENOTES BRICK WALL CONSTRUCTION JOINT. PROVIDE
10mm ABLEFLEX, SEALANT + BACKING ROD BOTH SIDES,
PROVIDE MEDIUM DUTY STAINLESS STEEL EXTENDIBLE
MASONRY TIES AT 300 CTS.
DESIGNED: B.WHITING

NOTE:
REFER ARCH DRAWINGS
FOR ALL HOBS, RECESSES Wollongong
Level 1, 57 Kembla Street, Wollongong, N.S.W. 2500
& STEPS Ph (02) 4226 3333 Email: southcoast@northrop.com.au
ABN 81 094 433 100

0 1000 2000 3000 4000 5000


DRAWN: H.ABELLA

DRAWING TITLE
STRUCTURAL DRAWING
SOUTHERN VERANDAH
GROUND FLOOR SLAB
AND FOUNDATION PLAN

JOB NUMBER DRAWING NUMBER REVISION

FOR CONSTRUCTION 170975 S11 B


DRAWING SHEET SIZE = A1
DRAWINGS NOT TO BE USED FOR CONSTRUCTION UNLESS VERIFICATION SIGNATURE
HAS BEEN ADDED. THE COPYRIGHT OF THIS DRAWING REMAINS WITH NORTHROP

X0 X1 X1.1 X2 X2.1 X3 STEEL COLUMN SCHEDULE CONSULTING ENGINEERS PTY LTD. ALL SETOUT TO ARCHITECT'S DRAWINGS.
V3 V2 V1.1 DIMENSIONS TO BE VERIFIED WITH ARCHITECT AND BUILDER BEFORE COMMENCING SHOP
MARK SIZE COMMENT(S) DRAWINGS OR SITE WORK. NORTHROP ACCEPTS NO RESPONSIBILITY FOR THE
USABILITY, COMPLETENESS OR SCALE OF DRAWINGS TRANSFERRED ELECTRONICALLY.
PF1 200x100x5.0 RHS VERANDAH PORTAL FRAME STEEL COLUMN
U0 1 NOTE:
K 12 S20
SC1 125x125x5.0 SHS STEEL COLUMN
S26 S31 1. FOR STRUCTURAL SPECIFICATION NOTES REFER TO DWG S01 & S02
ROOF BRACING TO BE SC2 90x90x5.0 SHS STEEL COLUMN
RB1 TYPICAL UNO. 5 V4 E SC3 200x100x6.0 RHS STEEL COLUMN
S30 S25 SC4 125x125x9.0 SHS STEEL COLUMN
A U U U U U U U U U
1/ 1/ 1/ 1/ 1/ 1/ 1/ 1/ 4/
S25 SC VB2 SC SC SC ST3 SC SC SC SC S C
ST1 ST1 U SB8 Y0 ROOF FRAMING SCHEDULE
4/ VB2

SB
S C S B1

7
MARK SIZE COMMENT(S)
VB1

U
1/

8
V1

SB
VB1
U L1 150x100x10 UA + 250x20 PL SHOP WELDED TO VERT LEG

SB1
U SC U

1
1/ 1/

ST
ST
S C 1/ 4/U SC 3/
U OR1 125x125x9.0 SHS FRAMING OUTRIGGER
P1 P1 SC SB U SC
1 1/

ST ST1
4 C PF1 200x100x5.0 RHS SOUTHERN VERANDAH PORTAL FRAME
2/
U SB 4 S
S C
2/
U SB SB
1/
U RB1 2/32x1.2mm 2/32x1.2 STRAP BRACING (PLACED SIDE BY

1
1
SB2

SC

SB1
C

3
0

SB1
150 S SIDE)

SB
2
VB
U
1/ RB2 20mm 20 DIA ROD ROOF BRACING

SB
1/
U
2/
U U ST5 U SC

7
SC SC 2/ 2/ 1/
U SB SB1 200UB25.4
C SC 5

1
SP
ST1 S C L

ST
S Y1 SB2 200PFC
J ST1 U SB 3/
U S26 Z0

1
VB1 2/

ST
C 1 S C SB3 300PFC
S

1
S26

SP
U
C1/ SB
4 SB4 230PFC
S U U

1
2/ 1/

SP
SB5 150PFC
C 4 SC 1/U

5
S SB

300
ST
SC SB6 250UB37.3

SB
SB U Z0.1 SB7 100PFC
4 #-# 5

7
3/

P1
S C SB8 200x100x5.0 RHS
S30
1

U
SP

V5 150
2 4/ BW1 ST1 150x150x5.0 SHS

P4
C

1
ST
S /U
Z0.2

1/U
SB ST2 125x125x5.0 SHS
1800

SB2

BW
1
SP

3
U U S1 ST3 200x200x9.0 SHS
2/

SB
1/
SC SC
ST1 Y2 ST4 89x89x5.0 SHS

1/U
REFER TO S41 FOR U ST5 150x150x9.0 SHS
SB

1
SP

1/

BW
RAINWATER HEAD PLAN BW C
7

U S ST7 125x125x9.0 SHS 125x9 SHS +200x10 PL WELDED TO BASE TO


AND DETAILS C2/ 1/U *-*
4 S Z0.3
SB SB SUPPORT EXTERNAL SKIN OF BRICKWORK
7 5
4 VB1 89x89x5.0 SHS STRUT VERTICAL BRACING LOCATED IN
1

C SB
ST

3
S30 SB U
3/

ST
1 C STUD WALL
S

300
S25
1

SB

VB2 20mm 20 DIA ROD VERTICAL BRACING LOCATED IN


SP

U Y3
1/
7

S C U BRICK VENEER CAVITY


2/

1
1

SP
Z1
ST

A SC 1 10
SB

SC
7

S31
SP

S41 SB
U 5 STEEL PURLIN SCHEDULE
1/
SC U
SB 3/ MARK SIZE COMMENT(S)
2 11 SC
U CP1 C15019 600 CTRS 1 ROW BRIDGING
S31 1/ Z2
1

U SC
ST

B 1/

3
C FP1 FP23019 FASCIA PURLIN
S3
1

SB
SP

S25 S U
180 1/ P1 C20015 AT 1200 CTRS 2 ROWS BRIDGING PER SPAN
0 SC SB4
GUTTER BY OTHERS P4 C15019 AT 900 CTRS 2 ROWS BRIDGING PER SPAN
P1

P5 SZ15019 AT 1200CTRS 2 ROWS BRIDGING PER SPAN


VB U
1 1/
2

C P6 SC15019 AT 1200 CTRS 1 ROW BRIDGING PER SPAN


VB
1

S
ST

U Z2.1
1/ REV DESCRIPTION ISS'D VER'D APP'D DATE
SB
2 SC
1 PROGRESS ISSUE H.A B.W. 16.06.17
WALL SCHEDULE 2 ISSUED FOR 95% REVIEW J.H. B.W. 14.07.17
P4

MARK THICKNESS COMMENT(S) A ISSUED FOR CONSTRUCTION H.A. R.P. B.W. 21.07.17
U
1

BW1 190 N16-400 EW CENTRAL (COREFILLED). INSTALL B ISSUED FOR CONSTRUCTION H.A. B.W. 04.09.17
ST

C1/ SB
1 V0
RB2

S N16-400 STARTERS IN FOUNDATION BEAMS.


+RB1

U
SB4 1/
SC COG 300 AT BOTTOM, LAP 700 INTO WALL
1
VERIFIER: R.PRATT

ST

REINFORCEMENT
6

ARCHITECT
SB

RB2
RB1

P1

RB
1 +RB1 1
U
ST

1/ I
RB2
C
+RB1
H S
6

U
1/
SB

8 SC S26
FOR S26
S31
RB2
1
+RB
REF SOU D Z3

1
FP1
SB

ST
ER TH S25 1
TO E RN F U
V3 CLIENT
U 1/ PROVIDE 10 'T' - PLATE WELDED TO ST1 OR1 TO BE FLUSH TO X3 CATHOLIC EDUCATION OFFICE
DR V S25 U 1/ SC
AW ERA SC
1/ SC 4M20 BOLTS AT 1200 CTS TO SUPPORT FP1. COLUMN FOR THE DIOCESE OF
JOB MANAGER: B.WHITING

ING NDA VB SET PURLINS DOWN 30mm WOLLONGONG


1

2
VB

Z4
FULLY SHOP WELDED V2 TO ALLOW INSTALLATION
S21 H B 1/
U OF GUTTER, REFER ARCH
LOC SC Z0
16
DRAWINGS FOR FURTHER
STEEL ROOF PLAN KL S32 U0 INFORMATION
ST G 14 PROJECT
Z5 V1.1
EEL S25 S32
OR1
MARY IMMACULATE PRIMARY SCHOOL
RO Z0.1
SB3 SB3
SCHOOL
OF SB
3 SB

3
L1/O 5 STAGE 2 BLOCK K

SB

3
PLA

SB
SB3
ST ST4 CP1 Y0
N Z0.2
OR1
VB
4

5
SB SB V1

3
1
SB
Z6 2

SP
5 5

SB
CP1

4
ST
DESIGNED: B.WHITING

ST

P4
4

SB
20 3
SC 15
SPLICE (SP1) S32 S32
SB
5

2
Wollongong

VB
FULLY SHOP

RB1
Level 1, 57 Kembla Street, Wollongong, N.S.W. 2500
SB WELDED
5 RB1 L Ph (02) 4226 3333 Email: southcoast@northrop.com.au
LEGEND S26 Y1
ABN 81 094 433 100

SAFETY IN DESIGN 3
SC
THE FOLLOWING ITEMS HAVE BEEN IDENTIFIED AS RESIDUAL SAFETY RISKS
O

1
0 1000 2000 3000 4000 5000
1/

SP
SC

BUILDING IS UNSTABLE UNTIL SHEAR BLOCK WALLS ARE INSTALLED DENOTES STEEL COLUMN OVER
DRAWN: H.ABELLA

3
CONTRACTOR TO PROVIDE TEMPORARY BRACING TO ENSURE STEEL

SB
U

S1
1/

FRAME CONSTRUCTION STABILITY AND TO ALLOW SHEAR BLOCK


SC

DENOTES STEEL COLUMN UNDER


WALL CONSTRUCTION TO TAKE PLACE FOLLOWING STEEL DRAWING TITLE
INSTALLATION.
LOWER STEEL ROOF PART PLAN STRUCTURAL DRAWING
1
SC

BUILDER TO EXPOSE EXISTING 150PFC PRIOR TO DEMOLITION AND DENOTES STEEL COLUMN OVER AND UNDER STEEL ROOF PLAN
S2 PREPARATION OF SHOP DRAWINGS TO CONFIRM POSITION WITH
STRUCTURAL ENGINEER
1

DENOTES SPLICE PLATE 1. REFER ON DRAWING S33 FOR DETAIL


SP

DETAIL 1
BUILDER TO PROVIDE TEMPORARY PROPPING OF SUMP FRAME #-# DENOTES SC4 CONNECTION TO BW1 REFER DETAIL ON S33 S20
S3 DURING ERECTION OF STEELWORK. PROPPING TO REMAIN UNTIL
*-*
WRITTEN APPROVAL OF STRUCTURAL ENGINEER. DENOTES ST1 CONNECTION TO BLOCKWALL DETAIL ON S33 JOB NUMBER DRAWING NUMBER REVISION
LOWER ROOF ISOMETRIC VIEW
FOR CONSTRUCTION 170975 S20 B
DRAWING SHEET SIZE = A1
DRAWINGS NOT TO BE USED FOR CONSTRUCTION UNLESS VERIFICATION SIGNATURE
HAS BEEN ADDED. THE COPYRIGHT OF THIS DRAWING REMAINS WITH NORTHROP
STEEL COLUMN SCHEDULE CONSULTING ENGINEERS PTY LTD. ALL SETOUT TO ARCHITECT'S DRAWINGS.
DIMENSIONS TO BE VERIFIED WITH ARCHITECT AND BUILDER BEFORE COMMENCING SHOP
MARK SIZE COMMENT(S) DRAWINGS OR SITE WORK. NORTHROP ACCEPTS NO RESPONSIBILITY FOR THE
USABILITY, COMPLETENESS OR SCALE OF DRAWINGS TRANSFERRED ELECTRONICALLY.
PF1 200x100x5.0 RHS VERANDAH PORTAL FRAME STEEL COLUMN
NOTE:
V1.1 SC1 125x125x5.0 SHS STEEL COLUMN
FOR MAIN STRUCTURE STEEL ROOF PLAN SC2 90x90x5.0 SHS STEEL COLUMN
1. FOR STRUCTURAL SPECIFICATION NOTES REFER TO DWG S01 & S02
V2 SC3 200x100x6.0 RHS STEEL COLUMN
REFER TO DRAWING S20 SC4 125x125x9.0 SHS STEEL COLUMN
SB4
EXISTING
SB2
ROOF LINE
ROOF FRAMING SCHEDULE
U
C1/
S MARK SIZE COMMENT(S)
SITE WELD SB3 TO
EXISTING 300 PFC, L1 150x100x10 UA + 250x20 PL SHOP WELDED TO VERT LEG
RB

SB6
OR1 125x125x9.0 SHS FRAMING OUTRIGGER
1

B0 TYP.
10 PL. 2M20
B1 PF1 200x100x5.0 RHS SOUTHERN VERANDAH PORTAL FRAME
SB6

BOLTS.
B2 RB1 2/32x1.2mm 2/32x1.2 STRAP BRACING (PLACED SIDE BY
P6 B3 EXISTING 300 PFC
SIDE)
B4 SB3
EXISTING COLUMN RB2 20mm 20 DIA ROD ROOF BRACING
B5 13 SB1 200UB25.4
RF1
RB1

S32 3 SB8 SB2 200PFC

SB3
RF1 3 3 A1
3 SB3 300PFC
RF1 3 S2
RF1 3 3 U
3 3 3 2/ EXISTING 150 PFC SB4 230PFC
RF1 SC

SB3
RB
3 3 3 P6 1 SB5 150PFC

VB2/U
3 SB6 250UB37.3
EXISTING COLUMN

1
RB
PF1/U
PF1
A P5 SB7 100PFC
SB8

PF1
RB1 U
2/

FP1
S26 1 SB8 200x100x5.0 RHS
RB

PF1
S C
A0 ST1 150x150x5.0 SHS
PF1

RB1 3 ST2 125x125x5.0 SHS


PF1

3 3
FP1

RB1 3 EXISTING STRUCTURE


3 3 3 SB3 ST3 200x200x9.0 SHS
3 3 3 ST4 89x89x5.0 SHS
RF1
3 3 RF1
3 ST5 150x150x9.0 SHS
3 3 RF1 ST7 125x125x9.0 SHS 125x9 SHS +200x10 PL WELDED TO BASE TO
RF1 SUPPORT EXTERNAL SKIN OF BRICKWORK
RF1 VB1 89x89x5.0 SHS STRUT VERTICAL BRACING LOCATED IN
1 STUD WALL
S21
EXISTING STRUCTURE EXISTING VB2 20mm 20 DIA ROD VERTICAL BRACING LOCATED IN
ROOF LINE BRICK VENEER CAVITY

SOUTHERN VERANDAH STEEL ROOF PLAN


STEEL PURLIN SCHEDULE
MARK SIZE COMMENT(S)
CP1 C15019 600 CTRS 1 ROW BRIDGING
FP1 FP23019 FASCIA PURLIN
REFER TO SECTION 13 P1 C20015 AT 1200 CTRS 2 ROWS BRIDGING PER SPAN
B4 ON DRAWING S32 FOR B3 P4 C15019 AT 900 CTRS 2 ROWS BRIDGING PER SPAN
REQUIREMENT OF
P5 SZ15019 AT 1200CTRS 2 ROWS BRIDGING PER SPAN
ADDITIONAL 2
P6 SC15019 AT 1200 CTRS 1 ROW BRIDGING PER SPAN REV DESCRIPTION ISS'D VER'D APP'D DATE
1 50x50x3 SHS MEMBER.
A0 1 ISSUED FOR 95% REVIEW J.H. B.W. 14.07.17
A ISSUED FOR CONSTRUCTION H.A. R.P. B.W. 21.07.17
2 LEGEND
3 3 3 3

O
2

1/
SC
DENOTES STEEL COLUMN OVER
VERIFIER: R.PRATT

ARCHITECT

U
1/
SC
DENOTES STEEL COLUMN UNDER

1
SC
DENOTES STEEL COLUMN OVER AND UNDER
TYPICAL RF1 (FULLY SHOP WELDED)

1
DENOTES SPLICE PLATE 1. REFER ON DRAWING S33 FOR DETAIL

SP
DETAIL 1 #-# DENOTES SC4 CONNECTION TO BW1 REFER DETAIL ON S33 CLIENT
S21 *-* DENOTES ST1 CONNECTION TO BLOCKWALL DETAIL ON S33 CATHOLIC EDUCATION OFFICE
FOR THE DIOCESE OF
JOB MANAGER: B.WHITING

0 500 1000 1500 2000 2500 WOLLONGONG

RF1 - (ROOF FRAMING) SCHEDULE PROJECT


MARK MARK MARY IMMACULATE PRIMARY SCHOOL
200x100x5 RHS + 125x75x2 RHS SCHOOL
1 STITCH WELDED TO TOP OF RHS STAGE 2 BLOCK K
AS REQUIRED
2 50x50x3 SHS
12THK PL TAPERED 200 TO 50mm
DESIGNED: B.WHITING

3 AT 1800 CTS (OUTRIGGERS)

Wollongong
Level 1, 57 Kembla Street, Wollongong, N.S.W. 2500
Ph (02) 4226 3333 Email: southcoast@northrop.com.au
ABN 81 094 433 100

0 1000 2000 3000 4000 5000 PLAN


DRAWN: H.ABELLA

DRAWING TITLE
STRUCTURAL DRAWING
SOUTHERN VERANDAH
STEEL ROOF PLAN

JOB NUMBER DRAWING NUMBER REVISION


SOUTHERN VERANDAH ROOF ISOMETRIC VIEW
FOR CONSTRUCTION 170975 S21 A
DRAWING SHEET SIZE = A1
DRAWINGS NOT TO BE USED FOR CONSTRUCTION UNLESS VERIFICATION SIGNATURE
HAS BEEN ADDED. THE COPYRIGHT OF THIS DRAWING REMAINS WITH NORTHROP
CONSULTING ENGINEERS PTY LTD. ALL SETOUT TO ARCHITECT'S DRAWINGS.
DIMENSIONS TO BE VERIFIED WITH ARCHITECT AND BUILDER BEFORE COMMENCING SHOP
DRAWINGS OR SITE WORK. NORTHROP ACCEPTS NO RESPONSIBILITY FOR THE
USABILITY, COMPLETENESS OR SCALE OF DRAWINGS TRANSFERRED ELECTRONICALLY.
X3 X2.1 X2 X1.1 X1 Y0 Y1 Y2 Y3
X0 NOTE:
1. FOR STRUCTURAL SPECIFICATION NOTES REFER TO DWG S01 & S02
1 2
S30 S30

1 ROOF ROOF

1
SB

SB

SB

1
ST1 ST1

SB
SB8 ST3 ST1

1
ST

1
L1

1
VB

SP

ST
VB2 4 4
OR1 VB2
1 SB SB7 SB
ST4 OR1 ST4 ST4 ST4 ST4 ST4 ST4 ST4 ST4

3
ST7 ST4
5

ST4 ST4 ST4

SC1 ST1
SB
SC4 SB

SC1
2

SC1

SC1

SC1
SC4

SC1
VB

SC1
SC1

SC1

SC1

SC1

SC1

SC1

SC1

SC1
1
VB

VB
2
GROUND FLOOR GROUND FLOOR

ELEVATION A ELEVATION B
S20 S20

V5 V4 V3 V2 V1.1 V1 V0 Z3 Z4 Z5

8
1

ROOF ROOF
ST

S31
SB2
1
ST

1
1

SB
SP

1
SB1

1
1

ST

SB
ST

1
SB2 ST1
4

ST
SB

1
1

ST
VB

6
6

SB

FP T1
SB

SB4

4
SB
S
ST4 ST4 ST4 ST2

4
1
ST1

SB
ST

1
ST5 ST4
SC1

ST4
SC1

SC1

SC1

SC1
SC1
SC1

SC1
SC1
SC1
SC1

VB
1

VB
2
GROUND FLOOR GROUND FLOOR

VB

2
REV DESCRIPTION ISS'D VER'D APP'D DATE
1 PROGRESS ISSUE H.A B.W. 16.06.17
ELEVATION C ELEVATION F 2 ISSUED FOR 95% REVIEW J.H. B.W. 14.07.17
S20 S20 A ISSUED FOR CONSTRUCTION H.A. R.P. B.W. 21.07.17
B ISSUED FOR CONSTRUCTION H.A. B.W. 04.09.17

Z6 Z5 Z4 Z3 Z2.1 Z2 Z1 Z0.3 Z0.2 Z0.1 Z0 Z5 Z4 Z3


VERIFIER: R.PRATT

ARCHITECT
ROOF FRAMING SCHEDULE
MARK SIZE COMMENT(S)
L1 150x100x10 UA + 250x20 PL SHOP WELDED TO VERT LEG
ROOF ROOF
OR1 125x125x9.0 SHS FRAMING OUTRIGGER
PF1 200x100x5.0 RHS SOUTHERN VERANDAH PORTAL FRAME
3 RB1 2/32x1.2mm 2/32x1.2 STRAP BRACING (PLACED SIDE BY
4

5
5

5
1

1
4

SP

SP
SB

SB

SB

SB
SB

SB

SB
SB

SB6 ST1 S30 SIDE)

3
CLIENT

1
SB

ST SB1
ST1

SB
SB3 SB3 SB3 RB2 20mm 20 DIA ROD ROOF BRACING CATHOLIC EDUCATION OFFICE

4
FP1
SB1 200UB25.4 FOR THE DIOCESE OF
JOB MANAGER: B.WHITING

4
ST
SB2 200PFC WOLLONGONG
SC3
SC3

SC3

SC3

SC3

SC1
VB
SC1

SC1
SB3 300PFC

1
GROUND FLOOR GROUND FLOOR SB4 230PFC
SB5 150PFC
SB6 250UB37.3 PROJECT
SB7 100PFC MARY IMMACULATE PRIMARY SCHOOL
SB8 200x100x5.0 RHS SCHOOL
ST1 150x150x5.0 SHS STAGE 2 BLOCK K
ST2 125x125x5.0 SHS
ST3 200x200x9.0 SHS
ELEVATION D ELEVATION G ST4 89x89x5.0 SHS
S20 S20
DESIGNED: B.WHITING

ST5 150x150x9.0 SHS


ST7 125x125x9.0 SHS 125x9 SHS +200x10 PL WELDED TO BASE TO
SUPPORT EXTERNAL SKIN OF BRICKWORK
VB1 89x89x5.0 SHS STRUT VERTICAL BRACING LOCATED IN
STUD WALL Wollongong
ROOF VB2 20mm 20 DIA ROD VERTICAL BRACING LOCATED IN Level 1, 57 Kembla Street, Wollongong, N.S.W. 2500
7

1
SB

SB4 SB Ph (02) 4226 3333 Email: southcoast@northrop.com.au


1

BRICK VENEER CAVITY


SB

ABN 81 094 433 100


1 SB4
1
SB

SB4
4
7

ST
SB

SB4
1

S41
6

SP
7
SB
SB
7

1
SB

SP
7

1000 2000 3000 4000 5000


SB

0
1
SP

LOWER ROOF NOT SHOWN


SC2
DRAWN: H.ABELLA

SC2

ON ELEVATION FOR CLARITY


SC4
SC2
SC1

DRAWING TITLE
GROUND FLOOR STEEL COLUMN SCHEDULE STRUCTURAL DRAWING
MARK SIZE COMMENT(S) STEEL ROOF
PF1 200x100x5.0 RHS VERANDAH PORTAL FRAME STEEL COLUMN ELEVATIONS - SHEET 1
SC1 125x125x5.0 SHS STEEL COLUMN
SC2 90x90x5.0 SHS STEEL COLUMN
SC3 200x100x6.0 RHS STEEL COLUMN
SECTION E SC4 125x125x9.0 SHS STEEL COLUMN
JOB NUMBER DRAWING NUMBER REVISION
S20
FOR CONSTRUCTION 170975 S25 B
DRAWING SHEET SIZE = A1
DRAWINGS NOT TO BE USED FOR CONSTRUCTION UNLESS VERIFICATION SIGNATURE
HAS BEEN ADDED. THE COPYRIGHT OF THIS DRAWING REMAINS WITH NORTHROP
CONSULTING ENGINEERS PTY LTD. ALL SETOUT TO ARCHITECT'S DRAWINGS.
DIMENSIONS TO BE VERIFIED WITH ARCHITECT AND BUILDER BEFORE COMMENCING SHOP
DRAWINGS OR SITE WORK. NORTHROP ACCEPTS NO RESPONSIBILITY FOR THE
USABILITY, COMPLETENESS OR SCALE OF DRAWINGS TRANSFERRED ELECTRONICALLY.
Z6 Z5 Z4 Z3 Z2.1 Z2 Z1 Z0.3 Z0.2 Z0.1 Z0 Y1 Y0
NOTE:
ST4 BEHIND BETWEEN 2 1. FOR STRUCTURAL SPECIFICATION NOTES REFER TO DWG S01 & S02
COLUMNS VB

ROOF ROOF

6
1

1
SB

1
1
SB

SB

SB
SB
ST1 ST1 ST1

ST
ST3 ST1 SB8

SB
SB1

4
VB2 VB

SB
2
1
4 VB2 4 5 3 SB7 VB

4
SB SB SB SB5 SB SB3

3
5

SB
5

5
ST1 ST2 ST2 ST1 ST2

SB
SB
SB

SB
ST2
SB6 4 ST4

4
ST

ST
5
SB

5
VB
SB

SC2
SC2
2

SC1
SC4
SC1

SC1

SC1

SC1

SC1

SC1
SC1
2 VB
VB 2

VB
VB

1
GROUND FLOOR GROUND FLOOR

SECTION H SECTION K
S20 S20

V0 V1 V1.1 V2 V3 V4 V1.1 V2 V3

ROOF ROOF

8
ST

ST 1
1

4
ST1

4
ST

SB
SB1

SB

SB
SB1
VB
SB1

1
2

ST
9 SB1

4
SB7 ST4 ST4
ST B3

SB
1
1

B2

ST
ST

S
1

S31 SB5
ST

ST4
1

V
1
ST

ST4

4
SB
SB4 BEYOND
ST5

3
ST4
1

SB
SC1

VB
ST
SC1

2
SC2

SC2

SC1
SC1

SC1
2
VB
SC1

SC4
SC1

VB

2
2

VB
GROUND FLOOR GROUND FLOOR

REV DESCRIPTION ISS'D VER'D APP'D DATE


SECTION I SECTION L 1 PROGRESS ISSUE H.A B.W. 16.06.17
S20 S20 2 ISSUED FOR 95% REVIEW J.H. B.W. 14.07.17
A ISSUED FOR CONSTRUCTION H.A. R.P. B.W. 21.07.17

X1 X1.1 X2
VERIFIER: R.PRATT

X0 ARCHITECT
ROOF FRAMING SCHEDULE
6 MARK SIZE COMMENT(S)
S30
L1 150x100x10 UA + 250x20 PL SHOP WELDED TO VERT LEG
ROOF
OR1 125x125x9.0 SHS FRAMING OUTRIGGER
2

1
SB

SB

SB

ST1 ST1 PF1 200x100x5.0 RHS SOUTHERN VERANDAH PORTAL FRAME


ST5 RB1 2/32x1.2mm 2/32x1.2 STRAP BRACING (PLACED SIDE BY
VB1
SIDE) CLIENT
4

ST4 CATHOLIC EDUCATION OFFICE


ST

RB2 20mm 20 DIA ROD ROOF BRACING


FOR THE DIOCESE OF
SC2

SC2

SB1 200UB25.4
SC2
JOB MANAGER: M.HART

1 WOLLONGONG
SC1

SB2 200PFC
VB
SB3 300PFC
GROUND FLOOR SB4 230PFC
SB5 150PFC
SB6 250UB37.3 PROJECT
SB7 100PFC MARY IMMACULATE PRIMARY SCHOOL
SB8 200x100x5.0 RHS SCHOOL
ST1 150x150x5.0 SHS STAGE 2 BLOCK K
ST2 125x125x5.0 SHS
ST3 200x200x9.0 SHS
SECTION J ST4 89x89x5.0 SHS
S20
DESIGNED: B.WHITING

ST5 150x150x9.0 SHS


ST7 125x125x9.0 SHS 125x9 SHS +200x10 PL WELDED TO BASE TO
SUPPORT EXTERNAL SKIN OF BRICKWORK
EXISTING 150 PFC VB1 89x89x5.0 SHS STRUT VERTICAL BRACING LOCATED IN
STUD WALL Wollongong
EXISTING 300 PFC
17 ROOF
S32 VB2 20mm 20 DIA ROD VERTICAL BRACING LOCATED IN Level 1, 57 Kembla Street, Wollongong, N.S.W. 2500
Ph (02) 4226 3333 Email: southcoast@northrop.com.au
BRICK VENEER CAVITY
P6

ABN 81 094 433 100


P6

P6

B3
SC2 S 6
P
3
SB

SB8 RF1 RF1 RF1 RF1 RF1


0 1000 2000 3000 4000 5000
18
STEEL COLUMN SCHEDULE
DRAWN: H.ABELLA

S32
PF1

PF1

PF1

MARK SIZE COMMENT(S)


PF1

PF1

PF1

GROUND FLOOR DRAWING TITLE


PF1 200x100x5.0 RHS VERANDAH PORTAL FRAME STEEL COLUMN
SC1 125x125x5.0 SHS STEEL COLUMN
STRUCTURAL DRAWING
SC2 90x90x5.0 SHS STEEL COLUMN
STEEL ROOF
SC3 200x100x6.0 RHS STEEL COLUMN
ELEVATIONS - SHEET 2
SC4 125x125x9.0 SHS STEEL COLUMN

JOB NUMBER DRAWING NUMBER REVISION


ELEVATION A
S21
FOR CONSTRUCTION 170975 S26 A
DRAWING SHEET SIZE = A1
DRAWINGS NOT TO BE USED FOR CONSTRUCTION UNLESS VERIFICATION SIGNATURE
HAS BEEN ADDED. THE COPYRIGHT OF THIS DRAWING REMAINS WITH NORTHROP
CONSULTING ENGINEERS PTY LTD. ALL SETOUT TO ARCHITECT'S DRAWINGS.
X0 Y0 DIMENSIONS TO BE VERIFIED WITH ARCHITECT AND BUILDER BEFORE COMMENCING SHOP
75x10mm VERTICAL PLATE 75x10mm VERTICAL Z5 DRAWINGS OR SITE WORK. NORTHROP ACCEPTS NO RESPONSIBILITY FOR THE
AT 2.4M CTS TO FIX LIGHT PLATE AT 2.4M CTS USABILITY, COMPLETENESS OR SCALE OF DRAWINGS TRANSFERRED ELECTRONICALLY.
FULL DEPTH 12mm VERTICAL GAUGE PARAPET FRAMING ENSURE EDGE OF ROOF SHEET NOTE:
TO FIX LIGHT
STIFFENER PLATE. 12 'T' INTO. ALIGN PLATE WITH IS CONNECTED TO ROOF 1. FOR STRUCTURAL SPECIFICATION NOTES REFER TO DWG S01 & S02
GAUGE PARAPET
PLATE WELDED TO STRUT, PURLIN CLEATS. PURLIN MEMBERS ON ALL EDGES TO
FRAMING INTO Y0

1
12mm STIFFENER

ST
2M20 BOLTS MANUFACTURES SPEC. TYP.

P1
CLEATS TO BE FULL DEPTH TYP.

1
SB
CLEATS ST1

CL
2
SB

3
CL

ST
ST1

P1
SB2 SB4

7
CL

SB

P1
12PL SLOTTED PLATE. SB1
12 'T' PLATE 2M20
12PL CLEAT
FULL DEPTH VERTICAL 12mm 2M20 BOLTS
12mm CAP PLATE 2M20 STIFFENER PLATE. 12 'T'
BOLTS. PLATE WELDED TO STRUT 10PL 2M20 BOLTS
2

VB
VB 300 MIN 2M20 BOLTS

1
CL

SC1/BEYOND
SC1

SC2
LC

1
VB
VB

10
0
2

12 'T' PL 2M20
BOLTS
SECTION 4 SECTION 5
ST4 SECTION 3 S20 S20

400 MIN
ST4 (ST1 IN WORST CASE) S25

CL
300 MIN
CL

12 'T' PL 2M20
BOLTS

12 'L' PL
2M20 BOLTS
0
10

VB
1
2
VB

12PL 12 CLEAT
25mm 'L' PLATE TO VB1 X0

LC
CL

2M20 BOLTS. SLOTTED U0


THROUGH COLUMN 25mm
CLEAT WELDED TO BASE
LC

CL
PLATE + SC1
VB

1
VB
75x10mm VERTICAL PLATE AT FULL DEPTH 12mm VERTICAL
2

20mm BASEPLATE 4M20 2.4M CTS TO FIX LIGHT GAUGE STIFFENER PLATE. 12 'T' CONTRACTOR TO PROVIDE ENSURE EDGE OF ROOF IS CONNECTED
CHEMSET 801 ANCHORS. PARAPET FRAMING INTO. ALIGN PLATE WELDED TO STRUT. GUTTER SUPPORT BETWEEN TO ROOF MEMBERS ON ALL EDGES TO
170 EMBEDMENT PLATE WITH PURLIN CLEATS. 2M20 BOLTS SB4 MEMBERS AS REQUIRED. MANUFACTURER'S SPECIFICATIONS TYP.
12 PL CLEAT WHEN NO VB1 CONNECTED MEASUREED BELOW ALL PURLIN CLEATS TO BE FULL REV DESCRIPTION ISS'D VER'D APP'D DATE
TO BRACED COLUMN, ONLY HOBS DEPTH CLEATS

4
1 ISSUED FOR 95% REVIEW J.H. B.W. 14.07.17

SB
4
SC1

2 BOLTS REQUIRED TO BASE

SB
PLATE AS PER THIS WHEN NO VB2 CONNECTED BOX GUTTER TO A ISSUED FOR CONSTRUCTION H.A. R.P. B.W. 21.07.17
10
0 SECTION TO BRACED COLUMN, ONLY ARCH DETAILS B ISSUED FOR CONSTRUCTION H.A. B.W. 04.09.17
20mm BASEPLATE 4M20
2 BOLTS REQUIRED TO
250

CHEMSET 801 ANCHORS.


BASE PLATE AS PER THIS
170 EMBEDMENT ST1 SB1 SB1
SECTION
SC1

MEASURED BELOW ALL GROUND FLOOR GROUND FLOOR


VERIFIER: R.PRATT

SB7

2
SB
HOBS ARCHITECT

12mm CAP PL. 2M20 BOLTS.


ONE BOLT EITHER SIDE OF 65x10 HORIZONTAL
COLUMN. PLATE WELDED TO WEB

VB1 NOT SHOWN


FOR CLARITY VB2 NOT SHOWN CLIENT
FOR CLARITY CATHOLIC EDUCATION OFFICE
FOR THE DIOCESE OF
JOB MANAGER: M.HART

WOLLONGONG

PROJECT
SECTION 1 SECTION 2 SECTION 6 SECTION 7 MARY IMMACULATE PRIMARY SCHOOL
SCHOOL
S25 S25 S26 S20 STAGE 2 BLOCK K
DESIGNED: B.WHITING

VB2 VB2 Wollongong


1

1
SC

SC

Level 1, 57 Kembla Street, Wollongong, N.S.W. 2500


Ph (02) 4226 3333 Email: southcoast@northrop.com.au
ABN 81 094 433 100
1
SC

VB1 0 100 200 300 400 500


DRAWN: H.ABELLA

SLAB EDGE
TYPICAL
VB1

DRAWING TITLE
STRUCTURAL DRAWING
STEEL ROOF DETAILS -
SHEET 1

TYPICAL VERTICAL BRACING (VB1 & VB2) BASEPLATE DETAILS


20mm BASEPLATES
M20 CHEMSET 801 ANCHORS JOB NUMBER DRAWING NUMBER REVISION
170 EMBEDMENT MEASURED BELOW ALL HOBS
20mm GROUT PACK
FOR CONSTRUCTION 170975 S30 B
DRAWING SHEET SIZE = A1
DRAWINGS NOT TO BE USED FOR CONSTRUCTION UNLESS VERIFICATION SIGNATURE
HAS BEEN ADDED. THE COPYRIGHT OF THIS DRAWING REMAINS WITH NORTHROP
Z5 POSITION SB1 AND SB2 V0 CONSULTING ENGINEERS PTY LTD. ALL SETOUT TO ARCHITECT'S DRAWINGS.
CENTRAL OVER DIMENSIONS TO BE VERIFIED WITH ARCHITECT AND BUILDER BEFORE COMMENCING SHOP
75x10mm VERTICAL PLATE AT SUPPORT COLUMN V2 V1.1 DRAWINGS OR SITE WORK. NORTHROP ACCEPTS NO RESPONSIBILITY FOR THE
USABILITY, COMPLETENESS OR SCALE OF DRAWINGS TRANSFERRED ELECTRONICALLY.
2.4M CTS TO FIX LIGHT GAUGE TYPICAL
NOTE:
PARAPET FRAMING INTO. ALIGN 75x10mm VERTICAL PLATE AT
FULL DEPTH 12mm VERTICAL STIFFENER 1. FOR STRUCTURAL SPECIFICATION NOTES REFER TO DWG S01 & S02

1
FULL DEPTH VERTICAL

PF
PLATE WITH PURLIN CLEATS ENSURE EDGE OF ROOF SHEET 2.4M CTS TO FIX LIGHT GAUGE
PLATE BOTH SIDES OF WEB 12 'T'
PURLIN CLEATS TO BE FULL 12mm STIFFENER PLATE. IS CONNECTED TO ROOF
PLATE WELDED TO STRUT. 2M20 PARAPET FRAMING INTO
DEPTH CLEATS 12 'T' PLATE WELDED MEMBERS ON ALL EDGES TO
BOLTS SB1

P1
1
TO STRUT. 2M20 BOLTS

ST
MANUFACTURES SPEC. TYP.

3
ST
1
SB
EXTEND 12PL
4M20 BOLTS
ST1
12 END PL. 4M16 BOLTS SB6
ST4
12mm CAP PLATE INTO FP1, COPE
2M20 BOLTS FLANGES OF SB1 AS
100 12 'L' PLATE. 12 CLEAT
REQ
WELDED TO TOP AND FULL DEPTH VERTICAL 12mm
MIN 20mm VERTICAL COLUMN 2M20 BOLTS STIFFENER PLATE. 12 'T'

VB
CLEARANCE FROM PURLIN PLATE WELDED TO STRUT

2
TO RB2 2M20 BOLTS

TRIANGULAR 10PL FSBW'D

LC
PROVIDE 10mm ABLEFLEX
TO SB1 FLANGE. 20mm PL
BETWEEN BRICKWORK AND
PACKER. 2M20 BOLTS
12 PL STEELWORK TYP.

CL
5
ST

12mm VERTICAL CLEAT

3
2
ST1

SB
WELDED OFF COLUMN.

VB
BOX GUTTER TO
12mm 'T' PLATE ARCH DETAILS
WELDED OFF STRUT. RETURN HOB AROUND
12mm VERTICAL CLEAT

250 MIN
2M20 BOLTS CORNER TO BEAR SB5
WELDED OFF COLUMN,
BRACED BASE PLATE
12mm 'T' PLATE WELDED
ON

SC1
OFF STRUT, 2M20 BOLTS SB5

1
SC1

ST
EMBEDMENT TYP.

GUTTER STOPS EITHER


SIDE OF SB5

DETAIL 8

SC1

SC3
S20

75x10mm VERTICAL
ENSURE EDGE OF ROOF SHEET
IS CONNECTED TO ROOF
V2 PLATE AT 2.4M CTS
TO FIX LIGHT GAUGE
V1.1 DETAIL 9 V1 SECTION 10
MEMBERS ON ALL EDGES TO PARAPET FRAMING S26 S20
INTO REV DESCRIPTION ISS'D VER'D APP'D DATE
MANUFACTURES SPEC. TYP.
1
ST

1 ISSUED FOR 95% REVIEW J.H. B.W. 14.07.17


75x10 VERTICAL PLATE AT A ISSUED FOR CONSTRUCTION H.A. R.P. B.W. 21.07.17
Y0 2400 CTS TO FIX LIGHT GAUGE
PARAPET FRAMING INTO
SB1

75x10mm VERTICAL
ENSURE EDGE OF ROOF SHEET
VERIFIER: R.PRATT

PLATE AT 2.4M CTS


IS CONNECTED TO ROOF ARCHITECT
FULL DEPTH VERTICAL 12mm TO FIX LIGHT
MEMBERS ON ALL EDGES TO

1
ST
STIFFENER PLATE. 12 'T' GAUGE PARAPET
MANUFACTURES SPEC. TYP.
PLATE WELDED TO STRUT, FRAMING INTO
2M20 BOLTS

SB1

P1

8
SB
CLIENT
CATHOLIC EDUCATION OFFICE
FULL DEPTH VERTICAL 12mm
FOR THE DIOCESE OF
STIFFENER PLATE. 12 'T'
JOB MANAGER: M.HART

PLATE WELDED TO STRUT


WOLLONGONG
2M20 BOLTS
3

PROJECT
SB

MARY IMMACULATE PRIMARY SCHOOL


SCHOOL
STAGE 2 BLOCK K
BOX GUTTER TO BOX GUTTER TO
300 MIN

ARCH DETAILS ARCH DETAILS


250x20 PL
DESIGNED: B.WHITING

1
ST

20
L1

3
SB4

SB
SB4
12mm VERTICAL CLEAT Wollongong
WELDED OFF COLUMN Level 1, 57 Kembla Street, Wollongong, N.S.W. 2500
Ph (02) 4226 3333 Email: southcoast@northrop.com.au
1

12mm 'T' PLATE WELDED


ST

ABN 81 094 433 100


OFF STRUT. 2M20 BOLTS SB3 BEYOND

4
ST
0 100 200 300 400 500

1
CP
SC1

1
DRAWN: H.ABELLA

ST

12mm VERTICAL CLEAT


WELDED OFF COLUMN, 12mm
VB2 NOT SHOWN 'T' PLATE WELDED OFF DRAWING TITLE
FOR CLARITY STRUT, 2M20 BOLTS STRUCTURAL DRAWING
REFER SPEC STEEL ROOF DETAILS -
NOTES FOR SHEET 2
LINTELS U.N.O.
SC1

SECTION 12
S20 JOB NUMBER DRAWING NUMBER REVISION

DETAIL 11
S20 FOR CONSTRUCTION 170975 S31 A
DRAWING SHEET SIZE = A1
DRAWINGS NOT TO BE USED FOR CONSTRUCTION UNLESS VERIFICATION SIGNATURE
HAS BEEN ADDED. THE COPYRIGHT OF THIS DRAWING REMAINS WITH NORTHROP
ENSURE EDGE OF ROOF SHEET IS CONSULTING ENGINEERS PTY LTD. ALL SETOUT TO ARCHITECT'S DRAWINGS.
A0 A1 CONNECTED TO ROOF MEMBERS DIMENSIONS TO BE VERIFIED WITH ARCHITECT AND BUILDER BEFORE COMMENCING SHOP
100x10PL CLEATS DRAWINGS OR SITE WORK. NORTHROP ACCEPTS NO RESPONSIBILITY FOR THE
1M16 BOLT ON ALL EDGES TO USABILITY, COMPLETENESS OR SCALE OF DRAWINGS TRANSFERRED ELECTRONICALLY.
BOTH SIDES. 2M20
MANUFACTURES SPEC. TYP.
THROUGH BOLTS 4M20 8.8/TB BOLTS
REFER PURLIN 65
CLEAT DETAIL

P5
PAINTED
50x50 SHS 2 2
100 100 80x80x10 PL

1
2

1
P5
RF

RF
1 3
3

3
SB
100
1 50x50 SHS FSBW TYP. MITRE CORNER + FULLY

100
WELD TYPICAL

5
SB
SB3
100 SB5

PF1 MITRE + FSBW TYP. SB5 BEYOND

PF1

PF1
SECTION 13 SECTION 14
S21 S20

V1.1 V2 Z0.1 Z0

FSBW TYP. OR1 FSBW


80x80x10PL TO SC4
TYP.
3

3
SB

SB

SB

SB

3
FSBW TYP.

SB
FSBW TYP

5
SB

5
SB
SB3 SB5 SB3 SB3
SB5 SB5

SC1/BEYOND
8PL
1

ND
SP

SC4/BEYOND
SB5 BEYOND

YO
SB5 BEYOND

BE
195 PURLINS NOT

3/
PURLINS NOT

SB
SHOWN FOR
SHOWN FOR
SC3

CLARITY 12PL 2M20


CLARITY
8.8/TB BOLTS

EXISTING STRUCTURE

SECTION 15 EXISITING 150 PFC EXISTING 300 PFC SECTION 16 REV DESCRIPTION
1 ISSUED FOR 95% REVIEW
ISS'D VER'D APP'D
J.H.
DATE
B.W. 14.07.17
S20 S20 A ISSUED FOR CONSTRUCTION H.A. R.P. B.W. 21.07.17
3
SB

1
FP

10 'T' PLATE 4M20 BOLTS 150


AT 1200 CTS. ALIGN
A0
STIFFENER PLATE WITH 'T'

P6
PLATES

3
VERIFIER: R.PRATT

SB
12 THK TOP PLATE, 2M20 ARCHITECT
BOLTS INTO SB3. PROVIDE

10
STIFFENER AT COLUMN IN SB3
SB8
OFFSET 12mm VB2 CLEAT 2 1

CENTRAL VERTICAL 75mm C SB8


10 THK CLEAT WELDED TO EXISTING STRUCTURE
LIGHT GAUGE STUDS.
10 'T' PLATE 3 CLIENT
SC2, T0 THK 'T' PLATE HORIZONTAL TOP HATS EACH PF1/U
WELDED TO TO SB8 2M20 SIDE TO FRAME OUT WALL 10PL 2M20 CATHOLIC EDUCATION OFFICE
BOLTS SHEETING. TO ARCH DETAILS SITE WELD BOLTS B3 FOR THE DIOCESE OF
JOB MANAGER: B.WHITING

10 PL CLEAT WOLLONGONG
3
BUILDER TO EXPOSE EXISTING
S2 150PFC PRIOR TO DEMOLITION AND
2 1
SHOP DRAWINGS TO CONFIRM
SC2

POSITION WITH STRUCTURAL PROJECT


ENGINEER MARY IMMACULATE PRIMARY SCHOOL
SCHOOL
STAGE 2 BLOCK K
SC2 WELDED TO TOP
OF PORTAL FRAME
1

(PF1).
PF
DESIGNED: B.WHITING

SECTION 17 SECTION 18 DETAIL 19


S26 S26
Wollongong
Level 1, 57 Kembla Street, Wollongong, N.S.W. 2500
Ph (02) 4226 3333 Email: southcoast@northrop.com.au
ABN 81 094 433 100

V2
80x80x10PL OR1 BEYOND
BEHIND
8 PL 0 100 200 300 400 500
3
SB
DRAWN: H.ABELLA

5
SB

SB3 SB3 DRAWING TITLE


SB5 STRUCTURAL DRAWING
STEEL ROOF DETAILS -
SHEET 3
ST4 WELDED
TO SB3 PURLINS NOT
SECTION 20 SHOWN FOR
JOB NUMBER DRAWING NUMBER REVISION
S20 CLARITY

FOR CONSTRUCTION 170975 S32 A


DRAWING SHEET SIZE = A1
DRAWINGS NOT TO BE USED FOR CONSTRUCTION UNLESS VERIFICATION SIGNATURE
PURLIN HAS BEEN ADDED. THE COPYRIGHT OF THIS DRAWING REMAINS WITH NORTHROP
FULL DEPTH 12mm CONSULTING ENGINEERS PTY LTD. ALL SETOUT TO ARCHITECT'S DRAWINGS.
STRUT STIFFENER PLATE DIMENSIONS TO BE VERIFIED WITH ARCHITECT AND BUILDER BEFORE COMMENCING SHOP
STRUT BOTH SIDES DRAWINGS OR SITE WORK. NORTHROP ACCEPTS NO RESPONSIBILITY FOR THE
STRUT
USABILITY, COMPLETENESS OR SCALE OF DRAWINGS TRANSFERRED ELECTRONICALLY.
120
CL
120

CL

CL
25mm 'L' PLATE. SB1/SB6
2M20 BOLTS
12 PLATE, 2M20
12 PLATE, 2M20 10PL 2M20 WELDED
WELDED LUGS
WELDED LUGS LUGS FSBW (TYP) 2x25 END PL. 2M20
STRUT
8.8/TB BOLTS
1

2
VB

50
VB
12PL 4M20 BOLTS
COLUMN

CL

COLUMN
CL

COLUMN
BEAM BEAM
SLOTTED 25mm 12 PL

COLUMN
PLATE CLEAT

CL

50
CL CL

TYPICAL VB1 TO STRUT BRACING TYPICAL VB2 TO STRUT DETAIL TYPICAL STRUT TO COLUMN DETAIL TYPICAL INTERNAL COLUMN SUPPORTING TYPICAL SPLICE DETAIL (SP1)
UB BEAM DETAIL
V3

1
ST
4
SB

SB6
20 MIN

16PL FACE PLATE

100 50
12PL VERT CLEAT 3M16
CHEMSET 801 ANCHORS
AT 100 CTS. 125
200

EMBEDMENT IN VERTICAL

4
ST
SLOTTED HOLES
100

SLAB EDGE
12mm VERTICAL CLEAT

60mm MIN

60mm MIN

60mm MIN
WELDED OFF COLUMN,
12PL WITH 10mm GUSSET S1 12mm 'T' PLATE WELDED
BW1 4M16 CHEMSET 801
OFF STRUT. 2M20 BOLTS
ANCHORS 125 EMBEDMENT

SC1
BW1
S1 SLAB EDGE SLAB EDGE SLAB EDGE
SC4

SHS/RHS BASE PLATE DETAILS TYPICAL STRUT TO COLUMN DETAIL


SC4 CONNECTION TO BLOCK WALL BW1 ST1 CONNECTION TO BLOCKWALL BW1 (NON-BRACED BAY)
16 BASE PLATE (U.N.O.)
(DENOTED ## ON S20) (DENOTED ** ON S20) 2M20 4.6/S CHEMSET 801 ANCHORS, 60mm MIN EDGE DISTANCE.
REV DESCRIPTION ISS'D VER'D APP'D DATE
170 EMBEDMENT DEPTH MEASURED FROM UNDERSIDE OF ALL HOBS
1 ISSUED FOR 95% REVIEW J.H. B.W. 14.07.17
25mm MAX LEVELING GROUT
A ISSUED FOR CONSTRUCTION H.A. R.P. B.W. 21.07.17

10PL, 10 GROUT PROVIDE ADDITIONAL


PACK CAVITY TIES AT MIN.
65 x 65 x 6 EA 200 CROSS CENTRES
VERIFIER: R.PRATT

CLEAT 2M12 PURLIN AT CONNECTION TYP.


ARCHITECT
BOLTS 4M16 CHEMSET
12 CLEAT PLATE 101 ANCHORS
2M12 PURLIN BOLTS 85 EMBEDMENT

50

85
8 CLEAT PLATE
2M12 PURLIN BOLTS 16 DIA. ROD 600
FROM ENDS
50
STRAP BRACE

TO HOLLOW PERFORATED MESH AS


600 MAX

16PL NOMINATED BY ARCHITECT CLIENT


SECTION
350 MAX
200 MAX

CATHOLIC EDUCATION OFFICE


10PL LOCATED AT 50x5 FOR THE DIOCESE OF

30°
JOB MANAGER: B.WHITING

EA AND 50x5 SHS WOLLONGONG


2M12 BOLTS

5
PERPENDICULAR MEMBERS.

ST
5PL CLEAT 1M16 CHEMSET 101
NOTE: ANCHOR. 85 EMBEDMENT
TEK SCREW ALL STRAP
50x5 EA STEEL ANGLE 50x5 SHS PROJECT
BRACES TO EACH PURLIN LOCATE AT EDGES MARY IMMACULATE PRIMARY SCHOOL
AND/OR VERTICAL STUD AND 50x5 SHS AT ROD LINTEL REFER SCHOOL
LOCATIONS SPEC NOTES
TO UB SECTION STAGE 2 BLOCK K

STRAP BRACING TO STRUCTURAL STEEL MEMBERS TYPICAL CANTEEN AWNING SECTION


(TYPICAL TO COLUMNS, STRUTS AND RAFTERS)
DESIGNED: B.WHITING

(3.6M LONG, 0.6M WIDE)


TYPICAL PURLIN CLEAT DETAIL PROVIDE 3x12 GAUGE GALV SELF DRIVING SCREWS (SUPER
(FOR PURLINS UP TO 250mm HIGH) TEKS SERIES 500) TO EACH INDIVIDUAL STRAP BRACE.

Wollongong
Level 1, 57 Kembla Street, Wollongong, N.S.W. 2500
Ph (02) 4226 3333 Email: southcoast@northrop.com.au
ABN 81 094 433 100

0 100 200 300 400 500


DRAWN: H.ABELLA

DRAWING TITLE
STRUCTURAL DRAWING
STEEL ROOF DETAILS
SHEET 4

JOB NUMBER DRAWING NUMBER REVISION

FOR CONSTRUCTION 170975 S33 A


DRAWING SHEET SIZE = A1
DRAWINGS NOT TO BE USED FOR CONSTRUCTION UNLESS VERIFICATION SIGNATURE
HAS BEEN ADDED. THE COPYRIGHT OF THIS DRAWING REMAINS WITH NORTHROP
X0 SAFETY IN DESIGN CONSULTING ENGINEERS PTY LTD. ALL SETOUT TO ARCHITECT'S DRAWINGS.
DIMENSIONS TO BE VERIFIED WITH ARCHITECT AND BUILDER BEFORE COMMENCING SHOP
THE FOLLOWING ITEMS HAVE BEEN IDENTIFIED AS RESIDUAL SAFETY RISKS DRAWINGS OR SITE WORK. NORTHROP ACCEPTS NO RESPONSIBILITY FOR THE
V5 USABILITY, COMPLETENESS OR SCALE OF DRAWINGS TRANSFERRED ELECTRONICALLY.
BUILDING IS UNSTABLE UNTIL SHEAR BLOCK WALLS ARE INSTALLED

SB2
CONTRACTOR TO PROVIDE TEMPORARY BRACING TO ENSURE STEEL NOTE:
BUILDING LINE
BOX GUTTER S1 FRAME CONSTRUCTION STABILITY AND TO ALLOW SHEAR BLOCK 1. FOR STRUCTURAL SPECIFICATION NOTES REFER TO DWG S01 & S02
BELOW.

U
1/
WALL CONSTRUCTION TO TAKE PLACE FOLLOWING STEEL

SC
INSTALLATION.
Y3 SB4 BEHIND
BUILDER TO EXPOSE EXISTING 150PFC PRIOR TO DEMOLITION AND
S2 PREPARATION OF SHOP DRAWINGS TO CONFIRM POSITION WITH
50x10 HORIZONTAL PLATE STRUCTURAL ENGINEER
WELDED TO WEB
4 BUILDER TO PROVIDE TEMPORARY PROPPING OF SUMP FRAME
SB
5mm THICK PLATE
S3 DURING ERECTION OF STEELWORK. PROPPING TO REMAIN UNTIL

7
WRITTEN APPROVAL OF STRUCTURAL ENGINEER.

SB
4
SB
RAINWATER HEAD
PURLINS AND PURLIN
WELDED TO SB4'S
CLEATS NOT SHOWN
FSBW SHOP SPLICE FOR CLARITY. 5mm THICK PLATE
RAINWATER HEAD 5mm THICK PLATE
WELDED TO SB4'S RAINWATER HEAD
BEHIND.

SB
DOWNPIPE

7/U
BUILDING LINE
PFC FABRICATED
FROM PLATE TO 4
FORM CURVE. SB
75x12 FLANGE,
206x8 WEB.
SECTION 1
S25
220 DIA. MAX DOWNPIPE. SP1 REFER TO S33 FOR
REFER HYDRAULIC ENGINEER'S DETAILS
75

DRAWING FOR DETAILS.


MIN

1/U
.

SC
SB
4

REFER ARCHITECT 2 SB U0
FOR SETOUT 2 BOX GUTTER TO ARCH ENSURE EDGE OF ROOF IS CONNECTED
S41
DETAILS, BEYOND. TO ROOF MEMBERS ON ALL EDGES TO
U0 S3 MANUFACTURER'S SPECIFICATIONS TYP.
BUILDING LINE
1 BELOW.
S41 Z5
FSBW SHOP 5mm THICK PLATE
SPLICE. RAINWATER HEAD
END OF BOX WELDED TO SB4'S SB2 SB2
GUTTER
HATCH DENOTES

4
4
RAINWATER HEAD

SB
SB
EXTENT.
50x10 HORIZONTAL PLATE
WELDED TO WEB REV DESCRIPTION ISS'D VER'D APP'D DATE
A ISSUED FOR CONSTRUCTION H.A. B.W. 04.09.17

RAINWATER HEAD DETAILED PLAN 5mm THICK PLATE


RAINWATER HEAD
WELDED TO SB4'S.
DETAIL A
VERIFIER: Approver

S20
ARCHITECT

SECTION 2
S41

CLIENT
CATHOLIC EDUCATION OFFICE
FOR THE DIOCESE OF
JOB MANAGER: B.WHITING

WOLLONGONG
GUTTER BY OTHERS

PROJECT
MARY IMMACULATE PRIMARY SCHOOL
SCHOOL
STAGE 2 BLOCK K
DESIGNED: B.WHITING

Wollongong
Level 1, 57 Kembla Street, Wollongong, N.S.W. 2500
Ph (02) 4226 3333 Email: southcoast@northrop.com.au
ABN 81 094 433 100

0 100 200 300 400 500


DRAWN: H.ABELLA

DRAWING TITLE
STRUCTURAL DRAWING
RAIN WATER HEAD
PLAN AND DETAILS

3D VIEW - RAINWATER HEAD 3D VIEW - RAINWATER HEAD 2 JOB NUMBER DRAWING NUMBER REVISION

FOR CONSTRUCTION 170975 S41 A


DRAWING SHEET SIZE = A1