This drawing has been prepared for the use of AECOM's client and may not be used, reproduced

or relied upon by third parties, except as agreed by AECOM and its client, as required by law or for use by governmental reviewing agencies. AECOM accepts no responsibility, and denies any liability whatsoever, to any party that modifies this drawing without AECOM's express written consent. Do not scale this document. All measurements mus
ANSI D 864mm x 559mm
GENERAL NOTES:
1. ALL DIMENSIONS ARE IN METRES, UNLESS NOTED OTHERWISE.
NOTES: 2. THRUST BLOCKS IN ACCORDANCE WITH STANDARD DRAWINGS, MUST STILL BE PROVIDED
1. FIELD FIT GRADING OF FENCED AREA SURFACE TOWARDS ROAD DITCH OR FOR RESTRAINED FITTINGS.
N SPLIT DRAINAGE. LOW POINTS AND PONDING WITHIN FENCED AREA NOT
ACCEPTABLE, MAINTAIN 2% MINIMUM SURFACE SLOPE. 3. THE CONTRACTOR IS RESPONSIBLE FOR THE LOCATION AND PROTECTION OF ALL EXISTING PROJECT
UTILITIES WHETHER SHOWN ON THE DRAWINGS OR NOT.
Community Plan
Approved: _____

4. ALL PROPOSED WATERMAINS 150 TO 300 mm ARE AWWA C-900 DR 18 PVC PIPE. ALL PIPE TO
25.00 HAVE CLASS 'B' BEDDING, UNLESS NOTED OTHERWISE.

5. ALL BOUNDARY VALVE OPERATION MUST BE DONE WITH TOWN OF FORT SMITH
Implementation
1.8 m HIGH GALVANIZED CHAIN LINK FENCE
50 x 50 mm MESH
REPRESENTATIVE PRESENT.
Stage 1
(SEE DETAILS ON DWG C-4032) 6. ALL WATERMAINS SHALL BE TESTED. OPERATING OF BOUNDARY VALVES, FLUSHING AND Fort Smith, NWT
DISINFECTION PROCEDURES ARE TO BE REVIEWED AT THE PRE-CONSTRUCTION MEETING.
Checked: _____

7. CONTRACTOR TO SUPPLY A FILLING AND FLUSHING STRATEGY PLAN TO BE REVIEWED WITH


THE TOWN AND THE CONSULTANT PRIOR TO WATERMAIN ACCEPTANCE TESTING.
ALL SURFACING WITHIN FENCED LIMITS THAT IS NOT PAVED:
CLIENT
8. ALL WATER SERVICES TO BE 20 mm TYPE K COPPER WITH VERTICAL GOOSENECKS OR
150 mm - CRUSHED GRAVEL Q-LINE (COMPOSITE MATERIAL) WATER SERVICE TUBING WITH HORIZONTAL GOOSENECKS.
150 mm - NOMINAL SUBGRADE PREPARATION
9. WATER SERVICES MUST BE A MINIMUM OF 2.00 m FROM MANHOLE SHAFTS, LIGHT POLES,
Salt River First Nation
Designer: _____

CABLES, PEDESTALS, AND TRANSFORMER'S GROUNDING RODS. Fort Smith, NWT X0E 0P0
LIFT STATION No.1 867.872.2986 tel
6.20 10. APPLY APPROVED PVC WATER PIPE JOINT LUBRICANT FOR POTABLE WATER IN
2.40 m DIA CONC BARREL ACCORDANCE WITH MANUFACTURER'S RECOMMENDED APPLICATION PROCEDURES. www.saltriveronline.com
(SEE MECHANICAL AND
INV 196.260 ELECTRICAL DRAWINGS FOR 11. ALL HYDRANTS TO HAVE THE HYDRANT NUMBER PAINTED ON PRIOR TO C.C.C. ALL HYDRANT
INV 196.220 DETAILS) DOMES, NOZZLE CAPS, AND STEAMERS ARE TO BE PAINTED SAFETY YELLOW USING
BENJAMIN MOORE RAPID DRY GLOSS ALKYD ENAMEL OR APPROVED EQUAL. CONSULTANT
Project Management Initials:

MH500

STAGE 1 BDY
R 206.600 12. CLOSE AND STOPPER ALL BOUNDARY VALVES FOR DURATION OF THE PROJECT. AECOM Canada Ltd.

2.00
6.200 m - 250 mm #101, 18817 Stony Plain Road NW
2
62 SAN AT 0.65%
2 - 45° BENDS 6.46 13. ALL SANITARY SEWER ALTERNATIVES: (UNLESS NOTED OTHERWISE) Edmonton, AB T5S 0C2
6.4 20 A) PVC PIPE:
20 INV 196.320 200-375 mm DIA - ASTM D-3034 SDR 35 PVC 780.486.7000 tel 780.486.7070 fax
EOP 450-600 mm DIA - ASTM F-679 SDR 35 PVC www.aecom.com
PIPE BEDDING SHALL BE CLASS B CONFORMING TO ASTM C136 AND ASTM C137.
SPACE ALLOWANCE FOR 14. BACKFLOW PREVENTION DEVICES MUST BE INSTALLED BY LOT OWNERS ON ALL SANITARY REGISTRATION
CONTROLS, GEN-SET AND POWER SERVICES.
21.00

SEE DWG E-5000, E-5002.

2% SLOPE

150 mm FM
15. WATER SERVICE OBVERTS TO BE AT MIN 3.65 m DEPTH AT PROPERTY LINE. SANITARY
SERVICE OBVERTS TO BE AT MIN 3.65 m DEPTH AT BOTTOM OF DITCH CROSSING OR
INSULATED IF MINIMUM DEPTH OF COVER CANNOT BE MET.

EOP

8.00
16. ALL MANHOLES ARE STANDARD 1200 mm DIAMETER c/w NF 80 FRAME AND COVER UNLESS

26.990 m - 250 mm SAN AT 0.65%


OTHERWISE NOTED.

17. WHERE SEWER SERVICES ARE REQUIRED TO CONNECT TO MAINS MORE THAN 4.25 m DEEP,
2% SLOPE
ASPHALT PARKING PAD RISERS SHALL BE INSTALLED, c/w 45° BENDS.
- 45 mm - ASPHALT SURFACE COURSE
EOP

- 45 mm - ASPHALT BASE COURSE 18. WATER AND SEWER SERVICES SHALL EXTEND INTO THE LOT(S) 2.0 m.
02 - 180 mm - CRUSHED GRAVEL
6.3 - 150 mm - NORMAL SUBGRADE PREPARATION
20 19. USE 5 DEGREE SWEEP BENDS AND/OR PIPE JOINT DEFLECTIONS TO MAINTAIN CURVED
2 WATERMAIN ALIGNMENTS. SERVICE TAPPING OF BENT PIPES BETWEEN JOINTS IS NOT
6 .30 6.00 PERMITTED.
20
GALVANIZED SLIDING 20. CONSTRUCT 300 mm CLAY CAP ON EXCAVATIONS WITHIN LIFT STATION SITE.
CHAIN LINK FENCE GATE 150 mm FM VALVE

EOP
50 x 50 mm MESH

5.00
(SEE DETAILS ON DWG
C-4032))

2.50
LEGEND:
STAGE 1 BDY PROPOSED EXISTING FUTURE
PROPERTY LINE PROPERTY LINE STAGE 1 BOUNDARY
7.00 m WIDE ASPHALT DRIVEWAY ACCESS
62 LIMIT OF CONSTRUCTION
6.1 (SEE DWG C-4031 FOR DETAILS)

150 mm FM
20
2 SANITARY SEWER (SAN)
6 .16
20
Filename: C:\60646904_SRFN_CONSTR_ENG\20-SHEETS\C\01 DETAILED DESIGN - STAGE 1\60646904-SHT-01-C-5000_RX.DWG

SANITARY FORCEMAIN (FM)


SANITARY MANHOLE MH100
CONTINUATION - REFER TO DWG C-1051

CONTINUATION - REFER TO DWG C-1051


)
YP

600 mm CSP CULV WATERMAIN (WTR)


POLE LOCATION
(T

APPROXIMATE ONLY. REDUCER


m
2% SLOPE

00

TRANSFORMER AND POLE


6.

BY NTPC VALVE
R

HYDRANT
ISSUE/REVISION
23 70 PLUG
6.0 6.0
20 20 SERVICE (SAN AND WTR)
EOP EOP
SERVICE (SAN AND WTR)
(INSULATED SANITARY)
OVERHEAD POWER AND 150 mm FM
ASPHALT PAD DESIGN GRADE .023
TELEPHONE SERVICE TO 06
OH

2 - 45° BENDS AT LIFT STATION 2


LIFT STATION. REFER TO
ROAD E ELECTRICAL DRAWINGS. INV 196.495 0 21/04/30 ISSUED FOR CONSTRUCTION
I/R DATE DESCRIPTION

200 mm SAN 200 mm SAN


MH400 KEY PLAN
Last saved by: DUC.TRUONG(2021-04-29) Last Plotted: 2021-04-29

250 mm WTR 250 mm WTR


0 5.0 10.0
m
1:200
EOP EOP

PROJECT NUMBER
OH
OH OH OH OH
200 mm WTR SERVICE

60646904
200 mm SAN SERVICE

OVERHEAD POWER AND TELEPHONE.


OVERHEAD POWER LINE BY REFER TO DWG E-0002. SHEET TITLE
NTPC.
Lift Station #1
DITCH Site Plan

SHEET NUMBER

C-5000
Printed on ___% Post-Consumer
Recycled Content Paper