Professional Documents
Culture Documents
··FINALDRAWiN~} .. ~L-~J
. . . ·_·
p=H_=I~=.:.N=A=M=E=;==F=P:.=M=C=P=.F=O=RTUNE I.. 9448152~·.I
• HULL NO. S4003
Evac
Sewage treatment plant & Vacuum toilet system
II SPA~_E_P_A_R_T_s_ _ _ _ _ _ _ __
II PIPING
---·
a EVAC REPRESENTATIVES
EVAC i-· Date: 1·6=QeC 20Qi____ _____Q2C~---~~QQ~~=--1
Environment~} S6ititions·Marine·S_ector i OPERATIONANDMAINTENANCE i
"-· ·-----·-·
GENERAL
SAFETY INSTRUCTIONS
--------·------------ -·------------~---··----·-----· ---------------------··
Safety summary
The Evac Vacuum Toilet System receives, treats and discharges sewage waste. Personnel must, at all times,
observe safety regulations while performing maintenance or repairs. Every practical safety feature has been incorporated
into the design and manufacture of this equipment; however, personnel must be aware of the following potential
hazards.
Gas hazards
Putrefaction of organic matter in Vacuum Toilet Systems will produce disagreeable odors and an oxygen deficient
atmosphere. When removing access covers, fresh air from known outside source must be supplied to the surrounding
area. Only after this fresh air has been supplied for the proper tank ventilation should personnel open the tank. Under
no circumstances should any person service a tank without a second person, capable of rendering aid, standing by.
If an extended period of time for the tank repair is anticipated, personnel should utilize the proper respiratory equipment.
Chemical hazards
If some chemicals like disinfection chemicals, foam removing chemicals or pipe cleaning chemicals are used,
manufactures safety regulations must be followed.
Disease hazards
Sewage is a common mode of transmission for parasitic organisms such as bacteria, fungi, protozoa, viruses and
worms. Some of these may be pathogenic, meaning they have the capability of causing serious communicable
diseases. Most diseases associated with sewage result hand-to-mouth transfer of the pathogenic organisms.
Good personal hygiene by those servicing, or in any way coming in contact with the equipment is imperative. After
coming in contact with sewage or any contaminated equipment items, personnel should throughly clean themselves
with a disinfectant soap solution. This precaution is an absolute requirement before eating, drinking or performing
hand-to-mouth functions. Skin abrations, punctures or any other wounds require immediate and proper medical
attention.
Mechanical hazards
Before maintenance is performed on motor driven equipment, the main circuit breaker should be de-energized and
labeled "OUT OF SERVICE". Only authorized maintenance personnel should make repairs to this equipment.
Electrical hazards
The equipment is supplied with voltages that are dangerous and could provide fatal if contacted by personnel. To avoid
electrical shock, remove the electrical power by placing the main circuit breaker in OFF position. Do this before
performing any maintenance on electrical equipment or motors. Personnel should exercise extreme caution when
opening the door although the main circuit breaker is in OFF position. The terminals of incoming power are still alive.
EVAC reserves the right to make alteratioris-10 this specification without priornoUte.
©Copyright EvacOy. A!I rights reserved. 1
EVAC
Environmental Solution~ Marine S~i:tor
-----------·- -·-----·-·-----------·--
EVAC reserves the right ta make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 2
EVAC
Environmental SOiutions Mariiie''SCctOr:;
GENERAL
CHEMICAL RESISTANCE OF MAJOR ELASTOMERS USED IN EVAC COMPONENTS
Chemical Agent ~ NBR EPDM SBR Chemical Agent ~ NBR EPDM SBR
Acetaldehyde 3 4 1 4 Dry chlorine 3 3 3 -
Acetylene 1 1 - 1 Wet chlorine 4 4 4 4
Acetoph~none 3 4 1 4 Dibutyl phthalate 4 4 1 4
Acetone 1 1 1 4 Diethylene glycol 1 1 1 1
Acetic Acid 10% 4 4 3 4 Diethvl sebacate 4 - 2 4
Acetic Acid 50% 4 4 4 3 Dlnitrotoluene - 4 4 4
Acetic Acid 25°/o 4 4 4 4 Dioctyl phthalate 4 4 1 3
Acetic Acid 100% 4 1 1 2 Dioctyl sebacate 4 - 2 3
Boric Acid 10% 1 1 1 1 Epychlorohydrin - - 2 4
Citric Acid 1 1 1 1 Hexane 4 4 4 1
Chloroacetic Acid 3 3 3 3 Ethanol. 1 1 1 2
Chromic Acid 40% 4 4 4 4 Fluorobenzene 4 4 4 4
Formic Acid 3 2 2 2 Formaldehyde 40% 1 1 - 1
Formic Acid - - - 3 Freon 11 2 2 4 1
Phosohoric Acid 60o/o 2 1 1 3 Freon 12 1 1 2 1
Hypochlorous Ac!dc - 1 - 2 Freon 21 3 3 3 3
Ladle Acid 1 1 - 1 Freon 22 1 1 1 1
Maleic Acid 1 - 2 2 Freon 113 3 2 3 3
Naphthenic Acid - - - 1 Freon 114 1 - 1 1
Nitric Acid 10% 2 2 3 3 Glycerine 1 1 1 1
Nitric Acidc 65o/o 4 4 4 4 Silicone wax - - 1 1
PalmiticAcid 3 3 2 1 Hydrogen 1 - 1 1
Salicyclic Acid 1 - 1 3 Calcium Hydroxide 1 1 - 2
Stearic Acid 3 3 2 2 Sodium hypochlorite 10% 2 2 1 2
Sulfuric Acid 10% 1 1 1 3 Milk 2 - 1 1
Sulfuric Acid 20% 1 1 - 1 Mercury 1 1 - 1
Sulfuric Acid 25% 1 1 - 4 Methanol 1 1 1 2
Sulfuric Acid 50% 1 1 - 4 Methyl ethyl ketone 3 3 1 4
Sulfuric Acid 60o/o 1 1 - 4 Naphtha 4 4 4 2
Sulfuric Acid 75%1 4 4 - 4 Nitrobenzene 4 4 1 4
Sulfuric Acid 65% 4 4 3 4 Nitroethane 2 3 2 4
Sulfurous Acid 1 2 2 2 Nitrometane 1 1 2 4
Tannie Acid 1 3 - 2 Nitropropane 3 3 1 4
Tartaric Acid 10% 1 1 2 1 Animal oli (V\lhale·seal) 4 4 2 1
Deionized water 2 1 1 1 Cereal oil 4 4 1 1
Turpentine 4 4 - 4 Coconut oil 3 - 3 -
Acrylonitrite 1 4 2 4 Cod liver oil 4 - 2 1
Ammonia 2 1 1 1 Olive oil 4 3 3 1
Aniline 2 2 2 4 Cotton seed oil 4 4 2 1
Aniline 4 4 1 4 Silicone oil - - 1 1
Asphalt 4 4 4 1 Castor oil 2 1 1 2
ASTM101L 4 3 4 1 Oxygen 3 3 1 1
ASTM20IL 4 4 4 1 Ozone 4 4 1 4
ASTM 30IL 4 4 4 1 Perchloroethylene 4 4 4 3
Benzene 4 4 4 4 Potassium Permannanate 25% 4 - 4 -
Sbdium Bicarbonate 1 1 1 1 Tetraethyllead - - 4 -
Carbon dioxide 1 1 1 1 Propane 4 - 1 2
Butter 4 4 3 1 Soda (sodium hydroxide) 10% 1 1 1 1
Butadene - - - 4 Styrene 4 4 4 4
Uauid Butane 4 4 4 1 Toluene 4 4 4 4
Fuel A (100% lsoctane) 4 3 4 1 Trichloroethylene 4 4 4 4
Fuel B (70% lsoctane, 50o/oToluol) 4 4 4 2 Sulfur 3 3 1 1
Fuel C (50% lsoctane, 50%Toloul) 4 4 4 2
Fuel with methanol or ethanol 4 4 4 3
KeroSene 4 4 - 1
Cyclohexane 4 4 4 1
Cloroacetone - - 1 4 NR= Natural rubber
Chlorobenzene 4 4 4 4 NBR = Nit rile rubber
Chlorofonne 4 4 4 4 EPDM = Ethylene propylene rubber
Choloroprene chlorine 4 4 4 4 SBR =Styrene butadiene rubber
Class:
! NOTE: Check always chemical reisistance of Evac 1 =Very good
components if you are using any of the listed 2= Good
3 =Moderate
chemicals in your sewage system. 4 = Not recommended
EVAC reserves the righttomake alterations to this specification without prior notice.
©Copyright EvacOy. AJ! rights reserved. 3
• 2. EVAC VACUUM TOILETS
.EN!~(W............................................. ·········
E!iiffMl@imi@idf@Rfflil'lll~I
VACUUM TOILET
6544286 EVAC CLASSIC TOILET, WALL MODEL, WHITE (CONTROL MECHANISM ON PORCELAIN)
6543166 WALL PUSI I BUTFOl4 l(IT (OPTIOllAL)
30
Control mechanism on
porcelain
EVAC reserves the right to make alterations lo this specification without priornotice.
©CopyrightEvacOy.Allrightsreserved. 1
EVAC Date: 04 A r 2008 Doc. 001993-2
INSTALLATION
VACUUM TOILET
6544286 EVAC CLASSIC TOILET, WALL MODEL, WHITE, (CONTROL MECHANISM ON PORCELAIN)
6543766 WALL Pl:ISI I Bl:ITION l<IT (OPTIONAL)
Shut-off valve
1/2" MPT
Iii"--- Vacuum
Control mechanism breaker
Seat and cover
Flexible
water hose
Discharge pipe
alignment
tolerance
0
H-+---~9~ to be ±3.0 mm
,__ __ _
_,.-)_--:::._
U-beam
(Not included in EVAC supply)
Fasten the beam to a solid structure.
Recommended service opening for all Classic Minimum service opening for Classic toilets
toilets without USPH and optional place
-~1·
for control mechanism
(Optional place
for control mechanism,
installation hole 048)
230
200 80
0
lO
~
EVAC reserves the rightto make alterations to this specification without priorno!ice.
© Ccpyright Evac Oy. All rights reserved. 1
Date: 04 A r 2008 Doc. 001993-2
INSTALLATION
VACUUM TOILET
6544286 EVAC CLASSIC TOILET, WALL MODEL, WHITE, (CONTROL MECHANISM ON PORCELAIN)
eszi37'C8 YfALL PtJSI I Bl:J"FFeJf l(IT (9P=Fl9tJAL)
Toilet supporting beams ( not Evac supply ) for Evac Classic toilet
U-beam 50x30x2
.--:/
I - /I
v BoltM12, welded
230
0
N
200 N
Lenoth accordino to
the space available
Service area
Bushing
Guiding nut ......... 2 pcs Nut ......................2 pcs Sleeve coupling .... 1 pcs Rubber connector. 1 pcs
Edge strip ........... 1 pcs Bushing ............... 1 pcs Sleeve coupling .... 1 pcs Hose clamp ......... .4 pcs
VACUUM TOILET
6544286 EVAC CLASSIC TOILET, WALL MODEL, WHITE, (CONTROL MECHANISM ON PORCELAIN)
6613766 '•'o'Ab:b Pl:ISI I BIJ+i:gJI l<IT (QP+IQH:01lwJ
Water supply
Shut-off valve
=fl' i ,..,-shut-off valve/vacuum breaker assembly
I
Vacuum breaker I
...J
hoseA~:i:
1
Water connection
Seat and cover
Guiding nuts B
:'""-._
Water valve
Fig.1
! NOTE: Do not use any kind of grease during installation.
Vacuum hoses
Optional place on wall for the control mechanism
Control mechanism
• Remove three vacuum hoses from the control mechanism.
• Remove the control mechanism and replace Covering washer
0~
by the covering washer.
• See recommended hole sizes for the control mechanism
on the wall in the document 001993-2. \
~o
Toilet installation
! NOTE: Check hoses through the toilet service opening in the wall that the hoses run smoothly. The hoses will
not have any kinks.
• Fit the edge strip as shown in figure 1. Place the joint of the strip to the bottom side of the bowl.
• Install the seat and the cover.
• Connect the discharge connection.
! NOTE: Secure with the hose clamp. See installation of the connection pipes in the document 001993-2.
EVAC reserves the rightto make alterations to this specification without prior notice.
©CopyrightEvacOy.Allrightsreserved. 1
EVAC Date: 04 A r 2008 Doc. 002016-2
INSTALLATION
VACUUM TOILET
6544286 EVAC CLASSIC TOILET, WALL MODEL, WHITE, (CONTROL MECHANISM ON PORCELAIN)
&54'l7ii '.'/Abb PY&l I 8Wn:QtJ I<I+ (9P=Fl8PJAI:)
• Connect the shut-off valve/vacuum breaker assembly to the water supply. The shut-off valve must be installed to
the water supply piping's side to ensure the correct flow direction in the vacuum breaker. Note that the vacuum
breaker must be installed vertically as shown.
• Connect the water connection hose A to the shut-off valve/vacuum breaker assembly.
EVAC reserves the rightto make alterations to this specification without prior notice.
@CopyrightEvacOy.Allrigh_tsreserved. 2
Date: 04 A r 2008 Doc. 002025-2
OPERATION AND MAINTENANCE
VACUUM TOILET
6544286 EVAC CLASSIC TOILET, WALL MODEL, WHITE
1
661128? E /AS 81::,SSIS "F91LET, 'A'ALL MO BEL l:JSPI I, '1'/I llTE
Shut-off valve ~
~ Filter (not in USPH model )
v Vacuum breaker
Water hose
Water valve
Flushing nozzle Filter in water valve
///-===--~~
Discharge valve
Operation
The toilet is flushed by pressing the push button. The water valve opens and lets rinsing water flow into the bowl
through the flushing nozzle. After a short delay, the vacuum acts in discharge valve housing and forces the rubber
diaphragm in discharge valve to open. The contents of the bowl is drained to the vacuum sewer by a pressure
difference between the bowl and vacuum sewer.
The flushing cycle in the control mechanism starts the closing cycle. Atmospheric air pulse enters the discharge
valve, which closes. After a short delay, atmospheric air pulse reaches water valve, which closes and lets a certain
level of water at the bottom in the bowl.
After the flushing cycle has stopped, the push button and system will be ready for next flush.
Start-up
• Clean bottom of the bowl inside.
•Check that the mini-check valve and discharge valve are clean and working correctly.
• Check that the water supply hose and the filter of the water valve are not blocked up.
• Check that sufficient vacuum (-30kPa) is available.
• Open the shut-off valve in the water supply piping.
• Press the toilet push button. Pressing the button starts the flushing sequence. The discharge valve opens and the
contents of the bowl are extracted by vacuum. At the same time the bowl is rinsed by water.
•When the discharge valve has been closed, the water level is restored in the bowl by the closing time delay of the
water valve.
EVAC reserves the right to make alterations to this specification without priornotice.
@Copyright EvacOy. All rights reserved. 1
EVAC Date: 04 A r 2008 Doc. 002025-2
OPERATION AND MAINTENANCE
VACUUM TOILET
6544286 EVAC CLASSIC TOILET, WALL MODEL, WHITE
6611287 E'/AS 6LASSIS T81LET, '1'1'ALL MO BEL l:JSPI 1 'a't'f llTE 1
•The seat is easy to clean, with just a few simple directions for you to observe.
• Use a mild soap solution or biological cleaners.
• Seat and hinges should not be left damp, but be dried with a soft cloth.
•When using abrasive, corrosive or chlorine based cleaners for the bowl, avoid contact with the seat and hinges.
Therefore, when cleaning the bowl, make sure that seat and cover are in an upright position until all the cleaner has
been flushed away.
Maintenance Program is based on 20 toilet flushes per day and 20 years operation.
Every year:
• Change Mini-check valve 5959902 if toilet is connected to riser pipe.
• Check operation, push button, seat and cover, rinse pattern, discharge pattern.
• Check possible water and vacuum leakage.
• Clean Filter ( not in USPH models) in water supply.
Every 5 years:
• Change Mini-check valve 5959902 in every toilet.
• Open and clean Water valve filter 5774150.
•Check operation, push button, seat and cover, rinse pattern, discharge pattern.
• Check possible water and vacuum leakage.
•Check Flushing nozzle 6542428 and flushing operation.
Every 10 years:
• Change Mini-check valve 5959902 in every toilet.
• Change Hose diaphragm 6543130 and Sleeve diaphragm 6542990 in discharge valve ..
•Change Water valve diaphragm 5774400.
• Open and clean Water valve filter 5774150.
• Check operation, push button, seat and cover, rinse pattern, discharge pattern.
• Check possible water and vacuum leakage.
• Check flushing operation.
Flushing nozzle
EVAC reserves the right lo make alterations to this specification without priornotice.
©Copyright EvacOy. All rights reserved. 2
EVAC Date: 04 A r 2008 Doc. 002024-1
TROUBLE SHOOTING
VACUUM TOILET
6544286 EVAC CLASSIC TOILET, WALL MODEL, WHITE
6&M287 EVA8 8LASSl8 T01LET, "A'ALL MS BEL l;SPI I, ';\'I llTE
Water supply------j j
~ Shut-offvalve
Water hose
Water valve
Flushing nozzle Filter in water valve
">.J---Control mechanism
Discharge pipe
Cause Remed
• Foreign object in the bowl or • Shut off the problematic branch line
discharge valve vdNe
• Remove foreign object
• Change discharge valve
• Check and if necessary change the
control mechanism
• Blocked porcelain • Clean bowl I clean discharge valve I
• Blocked discharge valve clean vacuum hoses
• Loose I clo ed hoses
• Water shut-off valve closed • Open valve
• No water pressure • Provide water pressure
• Filter full or dirty in water valve • Clean filter
• Flush nozzle clogged • Clean flushing nozzle
• Filter blocked up in water suppl • Clean filter
• Watervalvejammedinopen • Closewatershut-offvalve
position • Clean I change water valve nozzles,
• Bowl clogged or discharge valve not springs, rubbers
operating • Discharge bowl, valve and piping
• Misuse (buckets of water thrown in with normally flushing
the bowl)
• Too low vacuum (less than 30%) to
flush
• No vacuum or low vacuum • Check vacuum level, remove
(less than 30kPa) blockage in piping
• Clogged mini-check valve • Clean I change mini-check valve
• Jammed control mechanism • Change the control mechanism
• Check air filter condition. It should
be place.
EVAC reserves the right to make alterations to this specificaUon without priornoUce.
Cl Copyright Evac Oy. All rights reserved. 1
Date: 04 A r 2008 Doc. 001995-2
SPARE PARTS
VACUUM TOILET
6544286 EVAC CLASSIC TOILET, WALL MODEL, WHITE, (CONTROL MECHANISM ON PORCELAIN)
8M4'2!3T !!VAC CLASSIC "f61LE"f, ';\"A'.LL MS BEL l:ISPI I, \ 11'1 ll"FE, (68riTROLMESI IAUISM OU POR-BELAIU)
8549?55 \'/ALL Pl:ISI I Bl:ITTQtl l<l:r (QP+IQM 0 L)
~;~
5432728
Seal ""----o Vacuum breaker,
USPH
5431884~
6542432
Seat and cover
with hinges
Shut-off
6543414 VfWe
Filter
5433215
5432548
Connection
5774000
---- Vacuum breaker
5433215
Connection hose
with seals
~-1
hose with
seals
Water valve
(document 6:131 H)
/ •• / · 6542430 v
v'6542428
/. Hose (not in USPH)
Flushing nozzle
• 5481150' 5470214' 6543766
Hose WALL PUSH BUTTON KIT
6542434
Control mechanism Control mechanism_ ~\\\
" ' - - - - - - - - - - i (not included ~ \\\
in wall push button kit) !!!
5736303
Hose
6543768
Hose nipple
\~~"'---.:::J::,5433594
Hose clamp
6543130 6540561
Hose Rubber
diaphragm connection
5433572
J6542990
6542458 Connection
Sleeve hose
Screw
diaphragm
6544235
6543128 6543129 Connection pipe
Discharge valve Outlet pipe with lugs 6543265
INSTALLATION KIT
6542434
CONTROL MECHANISM
EVAC reserves the right to make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 1
EVAC Date: 31 Jul 2008 Doc. 6:131H
SPARE PARTS
VACUUM TOILET
5774000 WATER VALVE
- - - Diaphragm
,___ _ _ _ 5774500
Slider
3752211
0-ring ,I
A _/_)
v-. (' ' " \
Filter
5774100
Solenoid valve
EVAC reserves !he right to make alterations to this specification without prior notice.
©CopyrightEvacOy. All rights reserved. 1
I
Date: 12 Oct 2006 Doc. 001877-1
TECHNICAL DATA
VACUUM TOILET
6543056 EVAC CLASSIC TOILET, FLOOR MODEL, WHITE
Rubber "'....
<D
Bowl elbow90° x
ro
::;:
0
~
\
~
050
50 150
EVAC reserves the rightto make alterations to th ls specification without prior notice.
<OCopyrightEvacOy. All rights reserved. 3
Date: 12 Oct 2006 Doc. 001879-1
INSTALLATION
VACUUM TOILET
6543056 EVAC CLASSIC TOILET, FLOOR MODEL, WHITE
8!t430eT !VAC CLASSle T61LET, FLSOR MB BEL l::fSPI I, '!a'l llTE
Min.120 P/N5610010
Water supply Shut-offvalve Max.100 Cover support
1/2" MPT (not included)
Vacuum breaker
(Not in USPH model) USPH Vacuum breaker
Max. 390 (Only in USPH model)
Flexible water
Push button connection hose
565
380
§;l;.++~fil-t ~
17"7777-'71
•The vacuum breaker air inlet must be installed min.150mm (6") above the overflow point of the toilet.
80
P/N 5433572 20 Discharge pipe alignment tolerance
Straight connection to be± 3.0mm.
Min.120
EVAC reserves the rightto make alterations to this specification without priornotice.
©CopyrightEvacOy. All rights reserved. 13
Date: 12 Oct 2006 Doc. 001879-1
INSTALLATION
VACUUM TOILET
6543056 EVAC CLASSIC TOILET, FLOOR MODEL, WHITE
654985¥ E'l'AS SLASSIS T81LET, FL98R M98EL l:ISPI I, '11/1 lll=i
180
EVAC reserves the rightto make alterations to this specification without prior notice.
©CopyrightEvacOy.Allrightsreserved. 14
Date: 12 Oct 2006 Doc. 001881-1
INSTALLATION
VACUUM TOILET
6543056 EVAC CLASSIC TOILET, FLOOR MODEL, WHITE
6613967 EVAS SLASSIS TOILET, FL98RMOBEL~SPI I, ·,;·111TE
Shut-offvalve
Vacuum breaker~
(Not in USPH models) USPH vacuum breaker
,,,,___ ( Only in USPH model )
EVAC reserves the right to make alterations to this specification without priornotice.
Cl Copyright EvacOy. All rights reserved. 15
Date: 12 Dct 2006 Doc. 001887-1
OPERATION AND MAINTENANCE
VACUUM TOILET
6543056 EVAC CLASSIC TOILET, FLOOR MODEL, WHITE
6613967 E\'AS SLASSIS "'FOILET, FL88R MB BEL ijSPI I, '//I ll'fE
,r----waterhose
~Shut-off valve
Mini-check valve
Discharge valve
Operation
The toilet is flushed by pressing the push button. The water valve opens and lets rtnsing water flow into the bowl
through the flushing ring. After a short delay, the vacuum acts in discharge valve housing and forces the rubber
diaphragm in discharge valve to open. The contents of the bowl is drained to the vacuum sewer by a pressure
difference between the bowl and vacuum sewer.
The flushing cycle in the control mechanism starts the closing cycle. Atmospheric air pulse enters the discharge
valve, which closes. After a short delay, atmospheric air pulse reaches water valve, which closes and lets a certain
level of water at the bottom in the bowl.
After the flushing cycle has stopped, the push button and system will be ready for next flush.
Start-up
•Clean bottom of the bowl inside.
• Check that the mini-check valve and discharge valve are clean and working correctly.
• Check that the water supply hose and the filter of the water valve are not blocked up.
• Check that sufficient vacuum (-30kPa) is available.
• Open the shut-off valve in the water supply piping.
• Press the toilet push button. Pressing the button starts the flushing sequence. The discharge valve opens and the
contents of the bowl are extracted by vacuum.Atthe same time the bowl is rtnsed by water.
•When the discharge valve has been closed, the water level is restored in the bowl by the closing time delay of the
water valve.
VACUUM TOILET
6543056 EVAC CLASSIC TOILET, FLOOR MODEL, WHITE
ii13Qi7 ii'#.O:b QbAG&IQ l'Qlbl:l', FbQQR M98EL '=JSPI I, '•'a'l llTE
•The seat is easy to clean, with just a few simple directions for you to observe.
• Use a mild soap solution or biological cleaners.
• Seat and hinges should not be left damp, but be dried with a soft cloth.
•When using abrasive, corrosive or chlorine based cleaners for the bowl, avoid contact with the seat and hinges.
Therefore, when cleaning the bowl, make sure that seat and cover are in an upright position until all the cleaner has
been flushed away.
Maintenance Program is based on 20 toilet flushes per day and 20 years operation.
Every year:
•Change Mini-check valve 5959902 if toilet is connected to riser pipe.
• Check operation, push button, seat and cover, rinse pattern, discharge pattern.
• Check possible water and vacuum leakage.
• Clean Filter ( not in USPH models ) in water supply.
Every 5 years:
• Change Mini-check valve 5959902 in every toilet.
•Open and clean Water valve filter 5774150.
•Check operation, push button, seat and cover, rinse pattern, discharge pattern.
• Check possible water and vacuum leakage.
• Check Flushing nozzle 6542428 and flushing operation.
Every 10years:
• Change Mini-check valve 5959902 in every toilet.
• Change Membrane 6542455 in the discharge valve.
•Change Water valve diaphragm 5774400.
• Change Membrane 6543231 in the vacuum buffer.
• Open and clean Water valve filter 5774150.
•Check operation, push button, seat and cover, rinse pattern, discharge pattern.
• Check possible water and vacuum leakage.
• Check flushing operation.
Mini-check
valve
EVAC reserves the rightto make alterations to this specification without prior notice.
©Copyrigh!EvacOy.Allrightsreserved. 19
EVAC Date: 12 Oct 2006 Doc. 001888-1
TROUBLE SHOOTING
VACUUM TOILET
6543056 EVAC CLASSIC TOILET, FLOOR MODEL, WHITE
6613967 E'IA6 9LASSl8 T91LET, FL8BR MBBEL tf5f'l I, 'i'il llTE
11-Shut-off valve
~
Flushing ring Filter ( not in USPH model )
Vacuum breaker
Water hose
Control mechanism
Mini-check valve
Discharge valve
Cause Remed
• Foreign object in the bowl or Shut off the problematic branch line
discharge valve valve
Remove foreign object
Change discharge valve
Check and if necessary change the
control mechanism
Blocked porcelain • Clean bowl I clean discharge valve I
Blocked discharge valve clean vacuum hoses
Loose I clo ed hoses
Clean filter
Clean filter
Close water shut-off valve
position • Clean I change water valve nozzles,
• Bowl clogged or discharge valve not springs, rubbers
operating
• Misuse (buckets of water thrown in
the bowl)
• Too low vacuum (less than 30%) to
flush
• No vacuum or low vacuum • Check vacuum level, remove
less than 30kPa) blocka e in i in
• Clogged mini-check valve
• Jammed control mechanism Change the control mechanism
Check air filter condition. It should
be place.
EVAC reserves the rightto make alterations lo this specification without priornotice.
@Copyright EvacOy. All rights reserved. 21
EVAC I Date: 23 Nov 2006 Doc. 001883-2 I
I SPARE PARTS I
VACUUM TOILET
6543056 EVAC CLASSIC TOILET, FLOOR MODEL, WHITE
6543272
6541025 Backplate
Flushing ring (document 001885-1)
with spring and
hose clamp
,,..---i
6542402 ,,. I
Hose clamp ,,. X --...., II
', '> I
/ '--<'
....
I
. /.> I
,,.,,. I
/ I
,,.
~ .......
' ......., ,,......,,...,. ,,. I
;::::. -~ '-'- - - - - 6542434 I
' ~ Control I
mechanism I
i 5433583
5433266 / ' or I Rubber bend
~crew--f
-"-t , L?®
-........_ \
6541024 2644190
Toilet bowl with flushing ring, spring Screw 5825300 5990724 5433594?
and hose clamp Washer Cap nut Hose clamp
6543279
INSTALLATION KIT
EVAC reserves the rightto make alterations to this speciflcation without priornotice.
© CopyrightEvacOy. All rights reserved. 23
Date: 02 Mar 2005 Doc. 6:01022D
SPARE PARTS
VACUUM TOILET
5774002 WATER VALVE, EVAC 90 AND EVAC 900, WALL MODELS AND FLOOR MODELS
- - - Diaphragm
,___ _ _ 5774500
Slider
5522700
Conic spring
5774300
Bottom
3752211
0-ring
5990740 Filter
Screw
5774100
Solenoid valve
EVAC reserves the right to make alterations toth!s specification Without prior notice.
C>Copyright EvacOy. AH tights reserved. 27
• 3. COMBINED SEWAGE TREATMENT PLANT (STP 40C)
TABLE OF DELIVERY CONTENT
'
11 I 12 13 I 14 I 15 I 16 I 17 I 18 I 19 I 20 I 21 I 22 I 23 I 24 I 25 I 26 I 27 I 28
A A
'-- ~
u ______J~~~~~-l-~~~~~~~--1-.--~~~~~~---if-..~~~~~~+--r~~~~~~~~~~~~~~~~~-
B L3L2-~----+--l-~~~~~l--,...~~~~~~t-+.-~~~~~-'--t-l-r-~~~~-++,~~~~~~~~~~~~~~~~ ~
B
-
~
C PE-~__j_-i-l-.~~~--+.-J--1-~~~~~~-l--jf--l-~~~~~~--+-++-~~~~~-j-J-+~~~~~~~~~~~~~~~~~- C
~ ~
~~ t > s '.! .~ 5 l,.;1231:,~, .t, '.~ 1•~1231:,~, ,t, ·~ li~l231:>~t ,~ Ii~~.".,~, ~
~
D
'i-~ ~- :' s ,c_ ----),~,4~.:r,,
001
:-- ::il':J1:::11 :2 ~ ~
002 ,
i---- --)~~,4~.:1,, i-
I-·
s
l':Jl':JI :! ::! :!
003,
1--
s
--\,~,4~.:r,,
1':11'.'11 !.e ~ ~
004,, 1
I-· :::J :J
s
i----- --),.j,.~:1,,
~ 2! ~
E
1...-
1- L·(>l>l>l l l I L·(>l>J>l 1 I I L·i>l>l>I I .b.!i L-J>l>l>IJi ,bJi
1-1 6A 11"1 ID ..., 4-6 3A 11"1 ID >") 6-IOA 2 4 6 11"1 6-IOA 2 4 6 F
F OR 2,5.:.4A 2 4 6 OR 1,6-2.SA 2 4 G OR 2.5-4A OR 2,5-4A
OR 4-6,34 OR 2,5-4A 1-
- OR 0,63-1A
G G
- -
H 1 3 s , \ 3 s 1, ~ s .I 1 3 s H
- K01 1 )_, K02 -, K03 --- K04"_)_j -
J 246 246 246 246 J
~ ~
K K
'--- 4x6mm 2 L-
L L
~ w w w w L-
~ ~ ~ ~
M Xt 1 2 3 XI 7 8 9 Xl 13 14 15 Xl 16 17 16 M
- • - • - • - • - • • •• '•- •- - • - • - • - • - .._ "'-·L ,L-•-•-•-•-•-•-•-•- •-·-·-•-•-•-•-•- - -•-•-•-•-•-•-• •• ••· ' •-•-•-·-·-·- -•-•-•-
~ ~
N N
- L1 L2L3PE /v7'-w"f-. /vJW!-- /vl fl-. /../1 fl'I 1-
T T
THIS DOCUMENT JS THE PROPERTY OF EvAC OY, ANO SHALL NOT SE REPRODUCED NOR SHALL CONTENTS BE Ol\IULGEO IN Atl'f WAY TO UNAUTHORIZED PERSONS WITHOUT THE OWNER'S CONSENT.
-
1
INPUT 440V: -4X - 460Y
K10 E
E F01 - INPUT 46<N: l - 460V
2A 2 4 INPUT 48CN: ... sx - 460V II
r--
G01
F 2.tVOC +
F
@ ™-
- -4X, L, +S::t 12A 24VOC -
-
G 400, 460V TIA 230VAC LI
Al G
- OR 660V, 690V
200VA
TIA 230YAC L2 K1f0 L2
-
H
-
H
~·-18 -
-7-12
2 J
- J
I -
-
K
r--
L
1
n1A
'
2
11
__ ,
4
21
A
i~'."j:'.''.~" F1~1-1--"1412114
w
11
"''i "'
--
B
"'
11
"''i
1A 2
1
1\ 21
3
4
A
11
~
B
11
~
~ -
K
r--
L
-
K12 \ --
-
M Kll
14 24
w
~
14 24
w
~
N N
-
-------------------- - Xl 51 52
~ - ·- -·- - -·- - - -
Xt 53 54
- -·- -·- - -·-·- -·-·- -·-·-·-·-·-·-·-·-----·-·-·- -·---·-·- -·- -·- - - - ---·- - -
p p
._....,
- ~
u v u v
-
,_M@
- R MOS M@
,_ M06 R
-
CHLOR!NA TION ANTIFOAMING
s s
- T
PUMP UNIT PUMP
,___
T
TH!S DOCUl.tENT IS THE PROPERTY Of f>IAC OY, AND SHALL NOT BE REPRODUCED NOR SHALL CONTENTS BE DIVULGED IN ANY WAY TO UNAUTHORIZED PERSONS WITHOUT THE OWNER'S CONSENT•
•
""" EVAC CONTROL PANEL STP 20-125 C, 22220 M
~
"'z
~
w
a;!o
..,w
D
\!!""
::>
~a.<( ,_ Q_""
0
,_ a.""
(.)::; °'
::>
~o. < Ea.<( ~(.)
:c
I[j~
:c
°'Ow;:
~ ~ ci~ :c ;: w '-
~
J I BR I I
\IL.l "Li\ "Li\ "Lil "f
'-
'V \JI-- \f___ \y--- '" --
"jf'~ '"--
"jf'~ i[}- i i[}- I [} i [} I
I
I '--
L so1 114 $02 14 $03 14 $04 114 sos 14 $06 1<4- I LSL BK ~ I LSHBK! LSL !wH l LSL HI
L
'-
5-19
12 1•
5-24
12 14
L -·-
Xl 103
. .J L·-·-
XI 106
. .J
L.--·x,toi L--·x,t1·rt L·-·x1t,·r '--
501- ~ '--- '---
M 506 lJ 2J JJ Fl 18 F128 M
'- MAN 11 11
0 TEST TEST '-
AUTO X X
~
N LINE LINE
l!!l24ll4 N
'-
'-
p
'-
HlO
" @
Hl 1
p
'--
R + YELLOW YELLOW + IR
24VDC 24VOC
'--
PAGE 2 '--
s PAGE 4
s
'- L_
T
T
THIS OOCUMENT JS THE PROPERTY OF DIAC OY, ANO SHALL NOT BE REPRODUCED NOR SHALL CONTENTS SE ciMJLCED IN ANY WAY TO UNAUTHORIZED PERSONS WITHOUT THE OWNER'S CONSENT.
-
A
A
~
B
B
-G
:::_j
PAGE J
-
G
f- -
H
- H
-
J
- J
r~.'..'.5,
117
r i 1 >-·-,
-
-
K K
I 4 2 I I 4 2 I 1J
f-- !CB- ! !CB-' I E- ~
! PSC ! ! PSA 1 I 510 14 L
-
L 1
L·-·-Xl ~·.J L,_,_ ~·.J
- 114 X1 116S 1 Q 'i1'23'i3
0
-
M M
I xx
- ~J.!~
TEST TEST
LINE LINE N
N
- f--
p p
f- -
R + + R
- s
-24VOC
PACE J
24vtlC
PACE 5
- -
s
- T
-T
TH!S OOCUl.lENT IS THE PROPERTY Of' EVAC DY, AND SHALL NOT BE REPRODUCED NOR Sl-W.L CONTENTS BE DIVULGED IN Aflf WAY TO UNAUTHORIZED PERSONS WITHOUT THE OWNER'S CONSENT.
•
"~' EVAC CONTROL PANEL STP 20-125 C, 22220 M
(I) TAS-POWER OY 3*380-480VAC/690V/230V 50/60Hz /24VDC
R(Y. ALTERATION °'K OiA.NGtO IJIPRO\IEO VACl.W' S1SIDIS CIRCUIT DIAGRAM
OESl~EO
TAN
IOAT(
11.04.05
I
ORAllN
TAN
I
OAT(
11.04.05
I CHECICEO I DATE I
IJIPROVEO DATE
'"'' "'' 1497504 PRO.(C:T
,,.
"'"'· 5461497 I": ( )I REVISION
11 12 I 13 I 14 15 I 16 I 17 I 18 I 19 20 I 21 I 22 I 23 I 24 I 25 I 26 I 27 '
28
A
A
DM8 12/24R EXPANSION UNIT 1 (A02) >---
~
SIEMENS LOGO! 12/24 RC BASIC UNIT 1 ( A01) SIEMENS LOGO!
B
B
>---
~
c c
- - w
L'.l
"':c< -0.
-
"',__u
N
"',__0
z
0
~
z
"'51z
ea.
<
_,
w
G'.;w
_,"' w
>---
D
-D
"'w3' 0 ii: 0. L'.l
u:. uw g,. ;:: "'
:c ::> 0
_,
::> I-
g !!l::> ,
w
w
,w :c ::>
uo.
z=>
<0.
"' :!
:r:~ V>
OJ 0 0. E
E CH 05 06 07 QB
CH 01 02 03 04 >-
~
01:1 I 01:2 02:1 I 02:2 03:1 03:2 04:1 I 04:2 01:1 I 01:2 02:1 I 02:2 03:1 I 03:2 04:11 04:2
F
F
- 2JOVAC I I I I 230VAC
PAGE 6
>-
-
G PAGE 2 G
>--- 24VOC 24VOC
PAGE 4 PAGE 6 H
H
- ~ o~e z
~o~
0
rs ~o~
0
--i 5 >---
"V --· ---·.
23 33
"+:-' ---
23 33 0 <
\F-' ---
23 33
·v,
\ !.., __ - - -
23 33 3-17
31
~ o~e
"V, 23 ' 33
~
+c-E
.o~ 23
1
33
3-18---i
31 J
- J 1
\
" " " "
504 24
K11 --· ---·
\
K12 >-
501 24 34 502 24 34 503 24 34 34
34
" sos 24 34 506
6 24 34 34
-
K
I
501-
SOB 'IJ12J"J~
MAN
0
x
x
- - - '--
TEST
'--
TEST
-
K
- L
AUTO X
U_,!42_4
?- .
13
?- . ' 13
?- ~
13
?-
13 LINE
t_:z ~ -~h t:h LINE
- L
Q04A
-
M
K0~2
A1 A1 Al
KO~
Al
HO~ f0 K1~
Al
K1R.2
Al
N
f-- L2
1 2
KO* ~ 2 1-16
KQR.2
~ 2 1-19 .!.:. 2 1-22
L2
GREEN
-~
24V -
11
ll2-1s 11
ll2-1a
GREEN REO REO
24V -
-
N
~-r:;: 1-14
-r:;: -r:;: -r:;: ~ ~2 p
-
p 3 4 3 3 3
-
"""',....;.---1-14 ...,........-:-1-17 ...,,..........-:-1-19 ..../""':" 1-22 ~,_,,
~2-15
~_µ1-14 §..-1--:': §..-1--:'14: 1-20 ;~1-22
~5-2'
1-17
I]. 147-17 1]. 147-18 ~ 7-19 11, 147-20 I
~S-20 2
~ ~ ~ ~
-s
R
~ ~2 - R
s
I-
T
- T
THIS DOCUl.IENT IS THE PROPERTY OF EVAC OY. ANO SHALL NOT BE REPRODUCED NOR SHALL CONTENTS BE DIVULGEO IN Atff WAY TO UNAUTHORIZEO PERSONS WITHOUT THE OWNER'S CONSENT.
•
""" EVAC CONTROL PANEL STP 20-125 C, 22220 M
REV. M.TERATIOH
'"' I """'" APPROVED
{f) TAS-POWER DY .... ,,,,,., 3*380-480VAC/690V/230V 50/60Hz /24VDC
CIRCUIT DIAGRAM
DESIGNED
TAN
IDATE
11.04.05
DRA'M-1
TAN
DATE
11.04.05
CHECKED IOATt
'"" '"' 1497505
APPROYEO DATE PR0£CT
...., 5461497 I"; ( )I RE..,SION
17 19 20 I 21 I 22 I 23 I 24 I 25 I 26 I 27 I 28
11 I 12 I 13 I 14 I 15 I 16 I I 18 I I
A
A
,__ EXPANSION UNIT 2 (AOJ)
-
SIEMENS LOGO! OMS 12/24R
8
8
I-
w
(/)
-
w a.
c 3 :s_, c
i i~
~ I-
-
-
0 w
"'ct
(/)
w
"'a.
<!
(/)
"l z
o,.
5(.)"'"':s<!
D
I-
E
E 011 012
CH 09 010 -
- 01:1 I 01:2 02:1 I 02:2 03:1 I 03:2 04:1 I 04:2
F
F
,__ -
-
24VOC G
-G PAGE 5 PAGE 7
K13~ 14
11
O~A,24
2l
H
-
F:~j14 ?- ~
23 - H
-
K
J
12
11
14 23
004A 24
- J
K
- F12p:
11
?-~
Q02A 24
-
TEST L
L 23
~
LINE
O(,A~24
- -
M
-
M
N
H1~ ~
RED K1~
Al I-
N
I- 24V - 24V - I-
~7-25 p
-
p
- R
•
-1-23
R
- -
s s
- -
T T
THIS OOCUt.AENT IS THE PROPERTY OF f:VAC OY, ANO SHALL NOT BE REPRODUCED NOR SHALL CONTENTS BE DIVULGED IN Atff WA.Y TO UNAUTHORIZED PERSONS WITHOUT THE OWNER'S CONSENT.
•
•~< EVAC CONTROL PANEL STP 20-125 C, 22220 M
~;
H
~~ r·_x.~1?2 . ., H
- ~§
1 !21 r
a~ K141·"
J ! Q- 11
J
- "~~, L~:~ 12.2_ ..J
K
8~ x1t102
~. ~ K
ir·-·_:~ !~.-.-~1l1.19-·-·-·-·-·-·~
1
'
~--,
~~
L I ~~
!' MONITORING
I
· L
!~
I
- S10 I TEST ! NC CONTACT SYSTEM :
I LINE
M I ~ 0. L·-·-·-·-·-·-·-·-·-·-·-·-•-•j
~~ M
j HOO
($; Al
!s
HO\ HOZ HOJ" H04 H14
-;::; -OVERLOADS
COMMON ALARM
~•
22-17
- -CHLORINATION LOW LEVEL ALARM
-ANTIFOAMING [OW LEVEL ALARM
7-H
R
R
-
s s
-
T
T
THIS DOCUMENT IS THE PROPERTY OF f:<IAC OY. AND SHALL NOT BE REPRODUCED NOR Sl-W.L CONTENTS BE OMJLGED IN Am WAY TO UNAUTHORIZED PERSONS WITHOUT THE OWNER'S CONSENT.
•
"~' EVAC CONTROL PANEL STP 20-125 C, 22220 M
B 3i B
~~~l-.---.---,.-,-)~~--rl-~~-.-J----.---~-rl--~~~~~-+-,.,.+--.-,--,r!+,-,--,-,-,-11---..-rr~rr-,---,c:-r::,-T:l:::l
f- liigNNN
1 '<t'<tV tOl"-1'- O'JO'l01 NNN U11{) tOCO '<t'<t ~~~ ~~ ~~ ~~ ~~ ,....
"' ..-.-.- ..,.,.....,.... NNN 11 11 II ll 11
C ~8
~3\ ....I .-....
I I I JI I I I
.....- I I I I I I ~~ ~~ ,.!_,..!_ ,.!,l")l""l l""lr") l"')!"l l")I"'> r")l"I C
~
i- g .,NVU) .-N l"')'d"l{') <Or-.. OlO'I 0.- Nr")
D
:il-ooo
~ x 8 8 g
-Nr") '<tlOtO l"COO'I o-N
,. . ,... ... u;~ :rii1' co
'::~
000
.... ,. . .-0 0. . . 00
,. . .... ........
,. . ,. . ........
1. ~
D
R ~ ~ R
OW c.!IW
....... ~~ ~~ ~
s o:i!; ei!; s
gt- -1-
1- 5~ ~~ I-
T ~~ ~~ T
THIS DOCUMENT IS THE .PROPERTY Of EVAC r:tf, ANO SHALL NOT BE REPRODUCED NOR SHALL CONTENTS BE DMJLGEO IN ANY WA'f TO Ul-V.UTHORIZEO PERSONS WITHOUT THE OWNER'S CONSENT.
B z
•~ 8 B
" -w" w"
0 <O
~
8 ~
c
Vi
~e
N
......
N
"'......"' "
N' N
<O w
" "
I I I I I I
"" c
1€ "
SI iii
L... w
0 ~ ~
x ... "'
z .. w
D ~
--
<O " co "'
-- ~ s 0
8 D
~
•
§ I I I
w
~
"-
~
w
~
E
-
'
N
' I "'
I
-
' ' ' "' - N
..J E
"w "' i5"
:z 0
~
" ~
F F
- "' "' "'"'· -
G "'
... "'" " "' ~~ G
~
" "-:r: "'"'
" :r:"- " :r: "- -
I I I
H :> :> :> H
-' -' -'
~
-
J J
~
[ l I I I l I I
'-
m~
COMMON
K "' N -
"' N -
ALARM K
~
L
. . - L
L...
PSC PSA ~
M PRESSURE PRESSURE M
SWITCH SWITCH
- ~
CONTROL AlARM
N N
- '-
p
p
L...
-
R
R
~
s s
~
T
T
THIS DOCUMENT lS THE PROPERTY OF EVAC OY, ANO SHALL NOT BE REPRODUCED NOR SHALL CONTENTS BE DIVULGED IN ANY WAY TO UNAUTHORIZED PERSONS WITHOUT THE OWNER'S COKSENT.
•
"~' EVAC CONTROL PANEL STP 20-125 C, 22220 M
1497509
PRO.CCT
..... 5461497 PA9 ( )l ~E~SION
I 16 I 17 I 18 I 19 I 20 I 21 I 22 23 I 24 I 25 I 26 I 27 I 28
11 I 12 I 13 14 I 15
A
A
f-
f-
B
EVAC SANITARY SYSTEM
B
- I I -c
c
f-
D
H15 H12
-D
t--
~ SLUDGE HIGH
-
E
I
H14
ALARM
I H11
LEVEL ALARM
-
E
F
F
COMMON ABOVE -
-
I ALARM
I HIGH LEVEL G
-
G
H13 H10 -
H
H
f-
J
S04 sos
VACUUM
FAILURE/COLLAPSE
S06
BELOW
LOW LEVEL -J
SOI 502 503 ~
t--
K BLOWER 1 DISCHARGE PUMP 1 EJECTOR PUMP 1 EJECTOR PUMP 2 CHLORINATION PUMP ANTIFOAMING PUMP K
t-- MAN 0 AUTO MAN 0 AUTO MAN 0 AUTO MAN 0 AUTO MAN 0 AUTO MAN 0 AUTO t--
L L
- PLATE: 6011 I 8 WHITE -
TEXT: 3.5 BLACK 510 E51
M M
HOO SHUT DOWN RESET
f- EMERGENCY f-
ALARM RESET
N LED TEST STOP N
f-
p
I
POWER ON
I - p
f-
000 - R
- R
s I MAIN SWITCH
I
f-
s
- T
f-
T
THJS DOCUMENT IS THE PROPERTY OF' fVAC r:tf, ANO SHALL NOT BE REPRODUCED NOR SHALL CONTENTS BE DIVULGED IN ANY WAY TO UNAUTHORIZED PERSONS WITHOUT THE OWNER'S CONSENT.
•
""" EVAC CONTROL PANEL STP 20-125 C, 22220 M
I
YACIUI MmtS
I I sc.w:
DESICN(D
JBL
DATE
01.09.06
. ORA~
JBL
DAT(
01.09.06
i CHECKED DATE >.PPIU>VEO DAT(
""
' 1497S10
PROJECT
. """ 5461497 I'"'10 ( )!''"'°"
11 I 12 I 13 I 14 I 15 I 16 I 17 I 18 I 19 I 20 I 21 22 23 I 24 I 25 I 26 I 27 I 28
A
A
f-
CABINET SIZE 500 X 700 X 250 -
B 500
B
I- 442 I-
c 5ic: :;d-; c
I- ~ ~
I-
-
E
- ~
;,., CEII:J[]]IJ
• •
~ G01 001 002 003 004
I-
E
F
I'-
/ F
• ..
Ol
CEEJLEITJ //////////
~v
I-
I-
6,25"
G
I-
[Jfil][E]]J
• • ~ ~ 2 a~
~::. A02 AOJ
c:ICI
..
0 0
I-
G
H
.. .. .. .. .. • 0 0
H
f-
J
OQIJl:]QLJOQD[]QDQQD[]QLJ
® ® ® @ ® ®
0
I'- "'
I'-
v ////////// -
J
-
K
[EQ[J ® 0 I-
K
® ///////////
-
L L
~
PE I"- -
M
I-
~ = B PE
oG:J
'----,
' X1
R '
I-
M
N N
I-
p
2±s 2= 2±s 2±s -p
CABLE GLANDS
I-
1 x PG21
-
R 9 x PG13,5 For Power Supply: O.D. 18.3mm R
4 x PGl 1 For Emc'y Stop: 0.0. 1O.Omm
I-
OR For External Alarm: O.D. 11.2mm I-
s 1 x M32 s
- 9 x M20
4 x Mt6
I-
T T
THIS DOCUMENT IS THE PROPERTY OF £VAC OY, ANO SHALL NOT BE REPRODUCED NOR SHALL CONTENTS BE OlVULGEO IN ANY WAY TO UNAUTHORIZED PERSONS WITHOUT THE OWNER'S CONSENT.
•
"'"' EVAC CONTROL PANEL STP 20-125 C, 22220 M
I I I I
c )I
SCALE
O(SIGN[D
JBL
OATC
01.09.06
' ORA'M( 0.t.TE
01.09.06
CHEOCEO DAT( APPROVED DATE
'" 1497511 PRO.I( CT
'""' 5461497 1·;';
REVISION
EVAC
Environmental S"OlU.tiOils Marine·-seCtor
COMBINED UNITS
8/AC COMBINED SEWAGE TREATMENT PLANTS
The Evac combined sewage treatment plant consists of an integrated vacuum generator and a biological sewage
treatment plant. In the sewage treatment plant an aerobic process of the biopopulation convert organic substances
existing in waste water to carbon dioxide and water without danger of methane gas production.
All waste water, both black water (toilets, urinals, hospital) and grey water (galley, showers ahd sinks) can be treated
in the Evac sewage treatment plants. The treatment plant can operate in all vessels which are sailing in salt, brackish
or fresh water areas.
The sewage treatment plants are fully automatic in normal operation and they require low maintenance. See operation
and maintenance instructions.
The Evac marine sewage treatment plants are designed to fulfill the requirements of IMO MARPOL 73n8 Annex IV
and USCG 33 CFR Part 159 for inspected vessels which specifys discharged waste water from sewage treatment
plants. The effluent quality is as follow:
8005 < 50ppm
Suspended solids < 50 ppm (tested on shore) or 100 ppm (tested aboard ship)
Faecal coliforms < 250 pcs/1 OOml M. P. N.
--·-----------·
EVAC reserves the right to make alterations to this specification without prior notice.
©Copyright EvacOy. AJI rights reserved. 50
EVAC ~=-~~~~~~ 200_~_=:__ __9-'!i<c_ 0G_1Q?)_(:=-~1
:EnvironnieDtal.S.c>i~_#qP~:M~tirte· ~ector l__________________ . !
·---·---·---·--··-·---··· ·-·· ·--·---·--··---------
COMBINED UNITS
EVAC COMBINED SEWAGE TREATMENT PLANTS
Ventilation/
Emergency
overflow
Disinfection
Dilution/ chemical
Gravity
dosing
Vacuum inlet
inlet
Sludge return
____ ;y_
_;y_
__y__
Disi1'ldion
Antifoaming · Aeration Aeration Settling chamber
chemical chamber I chamber II chamber
dosing
Treated· water/
Sludge discharge
~
Black sewage water is collected by an integrated Evac vacuum ejector system or by Evac On-line pump system.
Incoming black water must be diluted with technical, grey or sea water. There is a separate dilution/gravity inlet
connection built in chamber I.
All waste water is led to the aeration chamber I by gravity or vacuum. Bacterial growth is stimulated by oxygen of air.
Required air is produced by the air blower(s) and led to aeration chambers I and II via air distributors. The aerobic
treatment process statts in the aeration chamber I and continues in the aeration chamber II. If treated waste water is
coming from a vacuum toilet system, required dilution water must be added into the aeration chamber I.
An activated sludge is separated in the settling chamber by gravity and clarified water floats to the disinfection
chamber. The activated sludge is pumped back to the aeration chamber I by an air driven ejector(s).
-=-
A chlorine based disinfection chemical is added by the dosing pump into the clarified water in the disinfection
chamber to meet IMO's requirements regarding presence of coliform bacterias in treated water. Treated water is_
pumped to sea or ashore by a discharge pump. Disinfection can be also done by UV on special request. Please,
consult Evac.
A mineralized sludge from activation chambers I and II is pumped at given intervals sea;to onsnorefaeilities oTtothe
vessel's sludge storing tank. The discharge pump is equipped with an integrated cutting device to prevent blocking.
EVAC reserves the right to make alterations to this specification Without prior notice.
©Copyright EvacOy. AU rights reserved. 51
EVAC
EnViiOrimenta1 Soiti.Hons M~rine Sec"to'i ·
COMBINED UNITS
STANDARD EVAC STP COMBI, CAPACITY
In the chart a smaller figure is a maximum number of persons for systems where all black (vacuum) and all grey water
is processed (24h/day). A larger figure is for systems where only black water (vacuum) and dilution water is processed
(24h/day). Please, consult always Evac for detailed calculations.
EVACSTP20C
EVACSTP40C
EVACSTP55C
>~i~i:-~~-------·-ii-----------~~~----------------
EVACSTP100C 10.5 4.5
------·-·------··----·-""""'-·-··-···-·..·-··
EVAC reserves the right to make alterations to !his specification without prior notice.
©CopyrightEvacOy. All rights reserved. 52
EVAC r·-oate:-27 Mar2QQ]- Doc. "'1':012140~1
!"·-···-·------------··---··-··-----·----··-·--···--~--··-----~
COMBINED UNITS
STANDARD EVAC STP COMB!, COMPONENTS
-----····----
Vacuum switch
Airvalve,
tankll
~ Airvalve,
tank Ill
Level switch,
Vacuum gauge \ 0
,,_,,,,,-/ tank IV
Dosing
pump set,
(disinfection
Dosing pump set chemical)
(antifoaming
chemical) --..- - -
Level switch,
tank IV
Ejector pump
Shut-off valve,
1
·~_, .~ ~ tanklll
Shut-off valve,
~ Discharge pump
ejector
Shut-off valve,
Shut-off valve,
Shut-off valve, Shut-off valve, tank II
ejector pump
tank I discharge pump
380-620. Adj.
.I FROM
THE PUMP
924 200
Loose flange
DN80PN10
--------
EVAC reserves the right to make alterations to this specification without priornoijce.
©Copyright EvacOy. All rights reserved. 60
EVAC
Enviroruri·~rit~(soiiitiOn~ Marine Sector
COMBINED UNITS
6541200 PUMP TYPE 4/HK 50-F, 3x400/460V 50/60HZ
525 213
Df;lO ~I
G1/4" '. ·'--
~§I
' I
I
0
l()
z
0
~...._,__.... -~1 -
4xM16x45
I 80
I 11~5J
~LqQ..j
G 1/2" 108 150 180
3x460V, 60Hz
•ml 0 so •00 150 200 25o Jlmp g.p.mJ
c 300 [U.S.gpmj
"' 50 100
''° 200
"'' 16 {tts)
0
' ' ' ID 12
" "
3600/min
H
f'll] 28 H
-10 0 l~J
"
@ 1=1
80
20
' I'-
I
'
" '
12 " 50
PSH
• p
'-
' 20
1~4
NPSH 0
[m] 00 10 20 30 50
"' Q[m3thl
Electrical data
Materials Pump casing and interstage casing: Cast iron EN-GJL-250 (GG25)
Impeller: Cast iron EN-GJL-250 (GG25)
Shaft: Stainless steel SIS 2350 (AISI 316Ti)
Impeller nut: Copper alloy UNS 38500
Metal seals: Carbon stainless steel
COMBINED UNITS
5430595 SHUT-OFF VALVE DN50
5430599 SHUT-OFF VALVE DN65
5430593 SHUT-OFF VALVE DN80
0180
P/N 5430599 Shut-off valve DN65
170
080 180
0160
0200
EVAC reseNes the right to make alterations to this specificationwithoul prior notice.
Cl Copyright EvacOy. All rights reserved. 62
Date: .Q§ Au9_~M.._ __ QQ.S._ __j_iJ.:!_027£L.j
TECHNICAL DATA j
COMBINED UNITS
5437598 VACUUM SWITCH R 3/8"
5437587 THREE WAY VALVE R3/8"
------ __119_____ _
30
"'N
[I] -··~
m
~
0
c;;
Connections R 3/8"
Connections R3/8"
EVAC reserves the rig ht to make alterations to this specification without prior notice.
©CopyriQhtEva~Oy.Allrightsreserved. 63
EVAC ~le: 26 Jan 2005 Doc. .! :01 Q~-~.J
··EnVi~O.rir#~'.4~~($6i#~-~dh~:I\1'.~P.~·-:s;;;ct'o-~
··-·--- -------·-------------
L_:i:!=CHNICALDATA l
COMBINED UNITS
5437623 VACUUM GAUGER 1/2"
5437666 THREE WAY VALVE R 1/2"
R 1/2"
Connections R 1/2"
64
EVAC reserves the rightto make alterations to this specification without priornotice.
-----· - - - - - -
©Copyright EvacOy. All rights reserved. 64
Date:06 Jun 2005 Doc. 1:010500 ,
------------------·"···-·-·;
TECHNICAL DATA
------
COMBINED UNITS
70235001 PUMPES120
203 •2
Outlet
m
u
" $
~
u
m
:;,
393 •3
•z
586 •3
Capacity
3x480V, 60Hz
COMBINED UNITS
70302001 AIR BLOWER V12YR
170 R 1 1/2"
female
thread
-
-
0
m
N
@
I
--------ft.<.---'
4x09
dp 3x480 V, 60Hz
(kPo)
30
25
20
15
10
5
0
0 20 40 60 80 100 120
(m'/h)
Tolerance:±5%
Air volume
COMBINED UNITS
6542675 DOSING PUMP SET, CHEMICAL TANK 5 L
6541578 DOSING PUMP SET, CHEMICAL TANK 30 L
............ .,------------··-··-----------
135.5
Metering
Metering
screw -----------
line
' ,.Rapid
'
On/Off - -
vent valve
...___
Suction
200 line
User's Manual
EVAC EMP II
EVAC reserves the rlgtll to makenlteralions lo this specmcation without prior nollce.
QCopyrightEvaeOy.Allrighlo;reseNcd. 14
. ·-· ........ ···-- ······-
EV~~C Dale: 29 Ju! 2005
·-··-----------~····-
Operation
The metering pump in the EVAC EMP JI metering pump is a electronic motor-driven membrane positive-
displacement pumps.
The metering pump is driven by a non-blocking synchronous motor (pos. 1) running at a constant speed.
An eccentric gear moves the diaphragm and thus displaces the metering medium via the pressure valve (pos. 2)
with double ball seal. The suction valve is closed.
The diaphragm is restored by a restoring spring and this causes the metering medium to be sucked into the pump
head via the suction valve (pos. 3). The pressure valve is closed.
The volume delivered can be infinitely adjusted during operation via the stroke adjustment (pos 4). This limits the
restoring movement of the diaphragm.
The pump heads are fitted with a rapid vent valve (pos. 5).
2
4 1: synchronous motor
1 ·1 2: pressure valve
3: suction valve
I I ill111
I
4: lift adjustment(= Pos. 6)
I rl 5: rapid vent valve
·1 1
I
i,
111
I 1
'11
''I
..h ! ... J..._L
.. , __ j
If 1 \:> ____ 6 7
u [------·---]
--~-
1
3
=
ti
GU QQiiQ CID
8
00 0
El& @
Start-up
DANGER: If the metering line can be blocked off, an overflow valve (safety valve) which opens at the maximum
allowed pressure should be installed on the pressure side for safeguarding the metering line and
pump. This can stop the metering line bursting if wrongly operated.
The pressure can rise to 3 times the nominal pressure.
Repairs may only be carried out with plug disconnected from the mains, or when the appliance is off load.
During maintenance and repair work on parts which come into contact with cleaning products, and when replacing
the bindings, the prescribed protective clothing (protective glasses, protective gloves, apron) must be worn
because of the danger of irritation.
Only original spare parts must be used for repairs.
• Push union nut (pas. 12 and pressure piece (pos. 13) over tube
and push onto connecting nipple (pas. 14) as far as stop collar.
• Place 0-ring (pas. 15) into valve groove and tighten swivel nut.
Open vent screw approx. 1 turn and leave open until the metering
medium enters the vent line without bubbles. The close vent screw
and ensure that the metering line is not shut-off at any point.
CAUTION: The metering pump head may contain residual water from
works testing._ 16
Metering capacity
The reproducible metering precision is about +/- 3% at a minimum 30% stroke distance and under constant
conditions.
The characteristics of the pump are such that higher outputs may occur until the operating temperature is reached
(continuous operation at least 2 hours).
Precise metering can be achieved by taking the following points into consideration:
a) All metering capacity informations relates to measurements using water :;it 20'C, with a constant power supply
and warmed-up pump.
b) In order to obtain a high degree of metering precision with free fiow, a pressure maintenance valve (or
metering valve) should be used, in order to produce a constant counterpressure of at least 0.5 bar.
c) If there is pre-pressure on the suction side, the pressure difference between the suction and the pressure
sides should be at least 1 bar. The water column on the metering pump must be protected by an appropriate
valve arrangement.
NOTE: A pressure maintenance valve or metering valve is not a completely reliable blocking element.
WARNING: Only .carry out metering stroke adjustments when the pump is running if the stroke adjustment pump is
not under pressure.
3.5
-=
:c
Q)
2,5
E 2
:J
Ci
>
Ol
c 1.5
·c
Q)
~
Q)
::2 1 bar
2bar-
3bar
<I bar
Sbar
6bar
0,5
~~::---..._:
9bar
0
10bar
-
0 10 20 30 40 50 60 70 ao 90 1(1]
Maintenance
NOTE: Quarterly maintenance interval, shorter intervals if load is greater (e_g_ constant running).
ill. 3
Frequent checking of the membrane is recommended at extreme temperatures and when metering
abrasive materials.
EVAC reserves the right to makealteratlons to this specification v.ithout prior notice.
@Copyrigl1t Evac Oy. All rights reserved. 18
l\C r-··-------------------
Date: 29-:~i~1·2·005·-·~---·-·-- ..Q;C:-3-:0112sA
-;
,
Environn1cntal Solutions M3rinc ScCtor ,[ OPERATIONANDMAINTENANCE i
----~-~------·--------'
Trouble Shooting
DANGER: Before carrying out repair and maintenance work or when metering dangerous substances, always
rinse the metering head, relieve the pressure line and wear protective clothing (protective glasses,
protective gloves and apron).
Electrical repairs may only be carried out by electrical experts (Liability Insurance Association safety
regulations VB G 4 and ZH 1/11) !
DANGER: Opening covers or removing parts, unless possible without using tools, may expose live parts.
Connection points may also be Jive.
Before carrying out a calibration, service, or overhaul and when replacing parts, the device must be disconnected
from all power sources if it needs to be opened:
Metering pump does not work, green - Incorrect voltage - Check power supply
LED not showino
Pump does not suck up despite - Precipitations, sticking - Rinse pump head through
bleeding and max. stroke setting together, drying out of valves suction line, eventually
dismantle and clean or
exchanqe valves
Metering head is leaking, medium is - Metering head is loose - Tighten metering head screw
escaping from leaking connection diagonally
- Diaphranm runtured - Replace diaphraqm
EVAC reserves the ri9hito makealter..itions to this specification without prior noHce.
@Copyright Evac Oy. All rights reserved. 19
EVAC
-······----~----------
Remove cover (pas. 22) from metering head, loosen attachment screws (pas. 17) and remove pump head (pas.
18), unscrew diaphragm (pas. 19), including connecting piece (pas. 20) and back-up ring. Replace intermediate
diaphragm (pas. 21) from ram. When fitting the diaphragm, do not overtighten (by hand, without tools, lightly
tighten). The leak connection of the connecting piece must point downwards. The metering head must be evenly
tightened diagonally.
NOTE: Check metering head screw tightening torque after 24 hours. Tightening torque 3 - 4 Nm.
21
I
I ill. 4
22 17 18
The metering pump is set to nominal pressure at the factory, in accordance with the metering curves. If the stroke
adjustment is to be set by removing the setting button, the basic setting can be determined as follows:
~
ill. 5 1. Switch metering pump on.
2. Place button on 100 % and turn clockwise until adjusting screw is
noticeably tensioned. Because of the eccentric drive, it is only
possible to turn the button in stages with the pump running.
If no resistance is reached, remove button at setting "O" and repeat
stage 2.
,,.
'" .. EiB 3. Then pull button off and put adjusting notch and marking back on
•
scale setting "O" and set desired metering output.
" To determine the metering output accurately the pump should be
\ " 40 so 60
" gauged by litres.
-=
EVAC reserves !he rlgh!to makeal!erations lo this specification without prior nolice.
~-:iCopyrigh! Evi:icOy. All rights reserwd.
20
- ········-··--·------··-·-·---··--·---- -- --
i Dale:29Ju!2005 Doc. 3·Q1125A
i OPERATION AND MAINTENANC_E_i
Environn1cntal Solutions Marine Sector L . .~-~------------·----- -----·
SEWAGIE TREATMENT PLANTS
6542675 DOSING PUMP SET
Dimensions, connections
135,5 2i8
irn:n:rTlTTl,TTTrlTffTTlfTf,>~~~"=='<m#~·<
\
\
II
f!J4,5
!DIOD
618
,--
69,5
=--
© E:l
I
"'
0)
.I . . - . - -·-·-·-· ·-·-·---· -- - .
'"
0)
J,\Y 0
fu
76 19
ill. 6
EVAC reserves the rigt1t to make allemtions to this specirtcation without prior notlce.
t~Copyrighl Evar. Oy. All righL~ mservad. 21
EV/1C
Environrncntal SOiutions Marine Sector
... ·-··-..····----- - - -- ------------·-· --- ·······························-······- . . ....
*
12 7
I
J.
co;=·
16- ~
Descriptiom.(ill. 7)
EVAC reserves the right to make alterations iothis specif1C<1tion without prior notice.
@Copyright Evac Oy. All right-; r,;serv~d. 23
EVAC
Environmental Solutions Marine Sector i TECHNICALDATA
- - - - - - - ''
COMBINED UNITS
70701001 LEVEL SWITCH SSP/3K
0~} G1
rr:-f:3::~:
c
••
"'
mm e
---------·---·-----------·--------~-
EVAC reserves the right to make alterations to this specilicationwilhout priornotice.
©Copyright EvacOy. All rights reserved. 70
EVAC Date: OS Jan 2007 Doc. 1:01125G
-· ·-·-·····-·-----------------·---···--···-·-··-·--···--------- ---
- ---
COMBINED UNITS
6541033 GATE VALVE DN40
5430595 GATE VALVE DN50
5430591 GATEVALVEDN100
6542225 SHUT-OFF VALVE R 11/2"
6541699 SHUT-OFF VALVE R 1"
PIN
Nominal size
A
B
c
D
6542225
R 1 1/2"
70
75
140
94
6541699
R 1"
66
44
63
110 c::::J
'le
Ball valve material Brass Brass A
----------.--·····- ~--------·----·-···--··-------·-··--·--
EVAC reserves the right to make alterations to this specification without prior notice.
- --------------- ··---··-····-·----·---------··-·---·--·-------
©Copyright EvacOy. All rights reserved. 71
EVAC
Environmental Solutions Marine Sector .
. .... ·---------'
COMBINED UNITS
6542288 FLOW METER LH-8SA-HR
:: I
:'!
---t- OUTLET
I
I
~
~
I
I
~
>:
~
(:;
~
~
~
I
I ~
-.;
:'-"•
I
I
~1
~
'
~
" I
I
-·
O>
"" l INLET
LI
7Z 5
! NOTE: Flow meter is an optional component for dilution water control. Please, consult Evac.
·------··---------~--------------------------·--·-----·
EVAC reserves the right to make alterations to this specificationwithout priornotice.
···-----------------··---··------------·--·-----·--·-
©CopyrightEvacOy.Allrightsreserved. 72
EVAC Date: 10 Mar
-·-·-·-··. --·
2005
---- ...··--·---·-··------
Doc. 2:01069C
COMBINED UNITS
STANDARD EVAC STP COMB!
----------------··--------------------------
Foundation
Evac sewage treatment plants are delivered with a foundation allowing welding or bolting to a vessel's deck or
installation frame. Welding instructions below must be carefully followed. Please, consult EVAC for bolted
installation.
Required maintenance
space 500mm ! NOTE: Installation frame/deck must be
flat and even.
! NOTE: Installation frame/deck must
support tank's bottom frame evenly on
whole frame area. Allowed max. distance
between deck's stiffeners is 800mm.
! NOTE: Piping must be installed so that
there is no stress in flange connections.
3 100 200
L~l:?·~"··~ > o
area is not allowed.
Required maintenance
space 100mm
Required maintenance
space 600mm
EVAC reserves the right to make alterations to this specification without priornotice.
©Copyright EvacOy. All rights reserved. 73
EVAC
Environmental Solutioi:ts Marine Sector
COMBINED UNITS
STANDARD EVAC STP COMB!
Pipings system
The Evac sewage treatment plant can process:
• Black water from vacuum sewage system (Dilution water required)
•Black water from gravity sewage system
• Black water from vacuum sewage system and grey water (Dilution water may be required)
•Black water from gravity sewage system and grey water
Installation and piping arrangement is depending on the vessel's sewage system. Please, consult Evac for sewage
treatment system options and required additional components.
A combined standard sewage treatment unit has the following fiange connections which must be connected to a
vessel's piping system by the yard/Customer:
•Vacuum sewage inlet
•Gravity sewage inlet .
•Dilution water inlet
•Discharge
•Ventilation/Overflow
•Flushing (Only temporary use.)
! NOTE: In custom made treatment plants a number offiange connections may vary. Please, see technical drawings.
Discharge
DN40 PN6
Flushing connection
DN50 PN10
-------~-------·-··-···--···---------
EVAC reserves the right to make alterationstothis specification without prior notice.
©Copyright EvacOy. All rights reserved. 74
EVAC
EnVironmentalc Solutions Marine Sector
COMBINED UNITS
STANDARD EVAC STP COMB!
Dilution water
Because a combined treatment plant is processing black water from vacuum toilet system, dilution water must be
added into incoming sewage. There are several system options to control and monitor dilution water:
•flow meter and pressurized fresh or technical water
•grey water buffer/holding tank and constant flow pump
•grey water buffer/holding tank and dilution water feeding by gravity with flow meter
Screen or Catcher
If there is a risk that a lot of non organic solids obstacles are entering in the treatment plant, a screen or catcher must
be installed before the treatment plant.
Grease separator
Grease is harmful for treatment process. If there is galley water entering to the treatment unit a grease separator must
be installed before treatment plant.
! NOTE: If there is no counter pressure for the discharge pump, a bend piping arrangement must be done with a pipe
loop (goose neck) over tank's water level to prevent siphoning.
Installation principle for vacuum sewage system, dilution by pressurized fresh/technical water
EVAC reserves the rightto make alterations to this specificationwithout prior notice.
©Copyright EvacOy. AH rights reserved. 75
. ·- ·····-- ---- __ --
EVAC
._ ---~.----
COMBINED UNITS
STANDARD EVAC STP COMBI
Ventilation/
Emergency
overflow Disinfection
Dilution/ chemical
Gravity dosing
Vacuum inlet,
\\
inlet·- Sludge return
~-
Vacuum
ejector(s) Aeration
chamber I
_ :!f_ ____ J _
Aeration
chamber II
-
Settling
chamber
Disinfedion
chamber LS
Antifoaming
chemical
dosing
lS
Treated water/
~arge
1.3 Settling
Activated sludge is separated· in the settling chamber by gravity and clarified water flows to the disinfection
chamber. Activated sludge is pumped back to the aeration chamber I by an air driven ejector pump(s).
Airflow for the sludge ejector is adjusted so thatthe sludge return from the chamber Ill is about 1/3 of the pipe section
(See transparent hose above tank). Rest of the air flow produced by the blower(s) is used for aeration and divided
equally between tanks I and II.
Sludge has to be removed frequently from the process to maintain a good biological balance in the sewage treatment
unit. Sludge content in process (in chamber I) must be kept between 1OOml/I and 500 ml/I. Sludge is removed by the
discharge pump.
EVAC reserves the right to make alterations to this specification without priornotice.
©Copyright EvacOy. Al! rights reserved 77
EVAC ;., ......9..~lE'..~~-4 F~-~--:?_9.Q_~----------------9.9_~: . . }~011.Q_~f.- . -i
Environmental Solutions Marine Sector i OPERATION AND MAINTENANCE
'-------· -··----~----------~
COMBINED UNITS
STANDARD EVAC STP COMBI
1. 4 Disinfection
Disinfection chemical (e.g. Sodium hypochlorite (NaCIO), solution, active chlorine 10%) is added to the clarified water
in the disinfection chamber to meet IMO's requirements regarding presence of coliform bacterias in treated water.
Residual chlorine must be kept between 2 ppm and 5 ppm. Residual chlorine can be adjusted by the dosing pump's
settings and/or timer settings. Treated water can be pumped to sea or ashore by the discharge pump.
Following notes must be paid attention to maintain optimal process conditions and effluent quality.
! NOTE: It will take about one month before effective biomass will overtake the process after first start-up or after
maintenance break. During this bacteria breeding period unit is not working as designed.
! NOTE: Never discharge both aeration chambers totaly at same time. Ensure always thatthere is bacterical population
left in either chamber I or chamber II to avoid collapse of the biological process.
! NOTE: Amount of the needed dilution water can be calculated. Needed dilution water is 1 x incoming black water
(vacuum system). The amount of black water in vacuum toilet system is 151/person/day. A total dilution water need
can be calculated:
Dilution water can be fresh, brackish or technical water. Dilution water is added into aeration chamber I.
! NOTE: Dilution is not needed, if vessel's grey water is also processed in the treatment plant.
! NOTE: Some antifoaming chemicals has a very high BOD, value. It is recommended to use antifoaming chemicals
which have low BOD, value.
! NOTE: All substances which might be harmful to the biological process such as large amounts of grease, acids,
alkalines, etc. are not allowed to be led to treatment unit.
COMBINED UNITS
EJECTOR DN80
Operation
The water ejector consists of a jet tube of stainless steel, a check valve and a nozzle of PVC.
The ejector, powered by the EVAC pump, creates vacuum in the piping. Sewage is pumped from the tank throug the
nozzle of the ejector creating a venturi effect whereby air and waste are inducted from the piping, mixed with the
sewage jet and passed into the collecting tank.
When the pump stops, the rubber flap of the check valve is drawn into the closed position by the vacuum, which is
thereby maintained.
Maintenance
The only moving part in the ejector is a rubber flap in the check valve.
Once a year:
• open and clean ejector check valve
EVAC reserves ttie right to make alterationstot11is specification without prior no1ice.
©Copyright EvacOy. AU rights reserved. 79
~· ~~~~ritalSolutionsMarlneSe~ior ;.~~.Q.~~-~~fi?_ri-]~-~~-:.~~:~~.~-~-. .P.g_~.'. ·.---~~~9:~°-~-~-1._J
.......
· l___OP~~!fON AND IVl_~~_!!'NJl.NCE
COMBINED UNITS
PRESSURE SWITCH
3-wayvalve
/
/r \
+ I I
..
••1<""'1
'l[l!UH
l.f•
1n!i!l11
Fig. 1 Knurled
knob
Fig. 2
Operation
. The pressure switch or switche.s and the vacuum gauge should be installed on a separate manifold, to reduce the
chance of impurities entering the switch or gauge (fig. 1). The instrument branch must have 5' slope. Water in the
instrument branch will cause malfunctions.
The switch starts a pump when the vacuum level in the system falls below a preset value. If the vacuum level still
keeps declining, another pump will be started (provided that there is more than one pump in your system). As soon
as the required vacuum level has been reached, the pump(s) will be stopped.
1. Set the stop pressure by turning the knob. As you turn the knob, the indicator on the scale will move. It should be
set between -40kPa and -60kPa (40-60% vacuum). This is the vacuum level at which the pumps will be turned off.
Note that in each system the optimal setting may vary.
2. Set the start pressure by turning the knurled knob, reached by removing the cover of the switch. Turning the knob
will set the starting vacuum level somewhat lower than the "stop"level set by the knob. In effect, whenever the
"stop"level is changed by turning the knob, the starting level will also be changed .
. The plant can be provided with a low level pressure switch for low vacuum alarm. Setthe "off' pressure to -30kPa.
The setting of the switch(es) may vary from system to system depending on the individual requirements.
The vacuum gauge installed, in each system enables you to check that pressure switches are functioning properly.
.Maintenance
Once a year:
• Check the operation of both pressure switch and vacuum gauge.
COMBINED UNITS
STANDARD EVAC STP COMB!, CONTROL PANEL
Control !eds
POWER ON White
BLOWER 1 RUNNING Green
BLOWER 2 RUNNING* Green
DISCHARGE PUMP 1 RUNNING Green
DISCHARGE PUMP 2 RUNNING* Green
EJECTOR PUMP 1 RUNNING Green
EJECTOR PUMP 2 RUNNING* Green
CHLORINATION PUMP RUNNING Green
ANTI FOAMING PUMP RUNNING Green
BELOW LOW LEVEL (Tank IV) Yellow
ABOVE HIGH LEVEL (Tank IV) Yellow
HIGH LEVELALARM (Tank IV) Red
VACUUM FAILURE/COLLAPSE Red
COMMON ALARM Red
SLUDGE ALARM Red
(* If installed)
Blower 2*
Controlled by: Control switch "BLOWER 2" set to "AUTO"
Timer Running time 15min
Pause time 15min
Operation: Starts Contolled by timer, alternates
with blower 1
Stops Contolled by timer
(* If installe_d)
EVAC reserves the right to make alterations to this specification without priornotice.
©Copyright EvacOy. All rights reserved. 82
·----------- ·- ·---·---·-·-.
EVAC !_____ ._Q~_t~_~! Ja!'__?_Q_Q§ --····--·--- Doc;::... ~.:9.1_11_~g
Environmental S6IutionsMarine Sector i OPERATIONANDMAINTENANCE
L_. __________ ----
COMBINED UNITS
STANDARD EVAC STP COMBI, CONTROL PANEL
Discharge pump 1
Controlled by: Control switch "DISCHARGE PUMP 1" set to "AUTO"
Timer Pump starting delay Ss
Timer Pump stopping delay Ss
"HIGH LEVEL SWITCH" LSH
"LOW LEVEL SWITCH" LSL
Operation: Starts Water level above LSH, starting delay Ss,
alternates with discharge pump 2*
Stops Water level below LSL, stopping delay 3s
Discharge pump 2*
Controlled by: Control switch "DISCHARGE PUMP 2" set to "AUTO"
Timer Pump starting delay Ss
Timer Pump stopping delay Ss
"HIGH LEVEL SWITCH" LSH
"LOW LEVEL SWITCH" LSL
Operation: Starts Water level above LSH, starting delay Ss,
alternates with discharge pump 1
Stops Water level below LSL, stopping delay 3s
(' If installed)
Ejector pump 1
Controlled by: Control switch "EJECTOR PUMP 1" set to "AUTO"
Pressure switch PSC, pump starts at -0.35bar, stops at -0.Sbar
Operation: Starts Vacuum level below-0.35bar, alternates with
ejector pump2
Stops Vacuum level -0.Sbar reached
Ejector pump 2•
Controlled by: Control switch "EJECTOR PUMP 2" set to "O"
Pressure switch PSC, pump starts at -0.35bar, stops at-0.Sbar
Operation: Starts Vacuum level below-0.35bar, alternates with
ejector pump1
Stops Vacuum level -0.Sbar reached
(*If installed
If the vacuum level does not reach the presetted value in the presetted time, also the other ejector pump starts. Both
pumps run same time as_long as the presetted vacuun level is reached.
EVAC reserves the rightto make alterations to this specification without prior notice,
©Copyright EvacOy. All rights reserved. 83
. ···----·---·-----·- ·----·---- ---
EVAC i- Dat~:}_!_~-~-~-?..Q.Q9________Q9.S:.:....-~:.Q.~-~-J_6_~-- ....
Environmental Solutions l\farine Sector t_()~E~1:~N AND MAINTENA~C:E__ I
COMBINED UNITS
STANDARD EVAC STP COMBI, CONTROL PANEL
Blower2*
Controlled by: Control switch "BLOWER 2" set to "MAN"
Operation: Starts Control switch set to "MAN"
Stops Control switch set to "O"
(*If installed)
Discharge pump 1
Controlled by: Control switch "DISCHARGE PUMP 1" set to "MAN"
Operation: Starts Control switch set to "MAN"
Stops Control switch set to "O"
Discharge pump 2*
Controlled by: Control switch "DISCHARGE PUMP 2" set to "MAN"
Operation: Starts Control swttch set to "MAN"
Stops Control switch set to "O"
(*If installed)
Ejector pump 1
Controlled by: Control switch "EJECTOR PUMP 1" set to "MAN"
Operation: Starts Control switch set to "MAN"
Stops Control switch set to "O"
Ejector pump 2*
Controlled by: Control switch "EJECTOR PUMP 2" set to "MAN"
Operation: Starts Control switch set to "MAN"
Stops Control switch set to "O"
(* lfinstalled)
Chlorinaton pump
Controlled by: Control switch "CHLORINATION PUMP" set to "MAN"
Operation: Starts Control switch set to "MAN"
Stops Control switch set to "O"
COMBINED UNITS
STANDARD EVAC STP COMB!, CONTROL PANEL
HIGH LEVELALARM
•Water level is over high level switch LSH over presetted time, timer setting 30s.
VACUUM FAILURE/COLLAPSE
•Led is on (vacuum failure), ejector pump has been running over presetted time, timer setting 15min.
•Led is blinking (vacuum collapse), vacuum level below presetted value -0.2bar (Pressure switch alarm) over presetted
time, timer setting 2min.
COMMON ALARM
•Emergency stop, emergency stop pressed down.
•High level alarm, see above.
•Blower overload, circuit breaker tripped.
•Discharge pump overload, circuit breaker tripped.
•Control voltage failure, Circutt breaker tripped.
•Chlorination pump overload, circuit breaker tripped.
• Antifoaming pump overload, circuit breaker tripped.
SLUDGEALARM
Presetted number of discharge times reached, counter setting 200 times.
! NOTE: Evac user manual includes complete electrical drawings and block diagrams. For detailed information,
please consult Evac.
EVAC reserves the right to make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 85
-.----···--- -·. ··-·-·--·
EVAC
--'"'--.---------~
COMBINED UNITS
STANDARD EVAC STP COMBI, CONTROL PANEL
! NOTE: Never let the pump run dry. Mechanical seals may be damaged.
! NOTE: Automatic control logic is by-passed in manual operation mode. Be extreme careful to avoid misuse of the
treatment plant.
! NOTE: The treatment unit is constructed so th<it the aeration chambers I and II are discharged at same time via
"Shut off valve, tank 11" and the minimum required activated sludge volume for the biological process remains automatically
in the aeration chamber I.
! NOTE: Never discharge aeration chamber I below minimum level via "Shut-off valve, tank I" at the same day with the
aeration chamber II. Erysure always that there is a minimum bacterical population left in either chamber I or chamber
II to avoid collapse of the biological process,
! NOTE: Immediately after sludge discharge the effluent might be contaminated by the remaining sludge in the piping
system.
EVAC reserves the righlto make alterations to this specification without priorrmtice.
©Copyright EvacOy. All rights reserve~. 86
... - ... _,__,,_ .. __ ,,. - ...
EVAC
---·---~--
(2)
(i) ~---~--~ ®
T 0
"'
l
SS--
-S3
EVAC reserves the right to make alterations to this specification without priornotice.
©CopyrightEvacOy.Allrightsreserved. 24
EVAC .... q_~-~~-:1.~ Nov,_?_Qg~ . _______QQ~:_..~_:QJ.Q_~Z~------.J
Environmefital Solutions Marine S_eC_tor OPERATION AND MAINTENANCE !
J
2.0 Start up, general
• Follow general safety instructions and be acqu_ainted with a "System description" of the installed system.
•Set power on. LOGO! does not have a power switch. See "System description" and electrical drawings of the
installed system.
•Check that there is present a running program in LOGO!. Normally there is a runnig program loaded in LOGO!
delivered by EVAC and EVAC does not supply programs stored in a separate program module (EEPROM). In case
there is not a program present in LOGO!, please contact EVAC.
Mo 09:00 No Program
06.21.01 Press ESC
>Program ..
PC/Card.
Clock ..
Start
•Use ....,.. or ......_ key and select "Clock". Press "OK" to confirm selection
>Set Clock
S/W Time
•Use ....,.. or ......_ key and select "Set Clock". Press "OK" to confirm selection
··--------··--·-·- · - - - -
EVAC reserves the right to make alterations !othis specification without prior notice.
©Copyright EvacOy. All rights reserved. 25
EVAC _0_3~~_:__?~1';1-~__?.Q.9.?_.. _........ _,. ______ !?.9.~: __?_:_9_!_ 097A
Set Clock
Th 15:30
MM.DD.YY
06.21.01
•Select the day of the week using ,,.- or ....._ key.
•Move the cursor to the next position usfng ..... or ...,. key.
•Change the value using ,,.- or ....._ key.
•Set the correct time. Repeat steps above.
•Set the correct date. Repeat steps above.
•Close your entries, press "OK".
>Set Clock
S/W Time
>Program ..
PC/Card ..
Clock ..
Start
•Use ,,.- key and select "START". Press "OK" to confirm selection. Now the loaded program is running in LOGO!.
When a program is running, a time and date are displayed in status display.
Mo 09:00
06.21.01
Mo 09:00
06.21.01
EVAC reserves the right to make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 26
EVAC
t
·~-~P~i~~:-~i]9:Y_:?.QQ~---.:~. ::.=---~-=~-~Q-~~~-j-~gJ.Q~I~.~~J.
Environmental Solutions MarinesecrOr OPERATION AND MAINTENANCE \
------------.-----------·-----·----- .
VACUUM INTERFACE VALVE
PROGRAMMABLE LOGIC LOGO!
>Stop
Set Param
Set Clock
Prg Name
•Use -..... or ....... key and select "Set Clock". Press "OK" to confirm selection
Set Clock
Th 15:30
MM.DD.YY
06.21.01
•Select the day of the week using ..,... or ....... key
• Move the cursor to the next position using ~ or ...,. key.
•Change the value using. -..... or ....... key.
•Set the correct time. Repeai steps above.
•Set the correct date. Repeat steps above.
•Close your entries, press "OK".
>Stop
Set Param
Set Clock
Prg Name
•Press "ESC" to return to time and date display.
Mo 09:00
06.21.01
I> !>
Press )Ii. 1:0., 1.,2. Press• Q:O., 1.
Mo 09:00 123456789 123456789
06.21.01 0123456789 0123456
01234
Press <C Press <C
<I . <I
In RUN mode LOGO! processes the program and reads the status of the inputs and determines the status of the
outputs using your specified program and switches the outputs on or off. Active (state "1 ")inputs and outputs are
displayed in dark backgroud with inverse color.
I:O.,l.,2.- Q:0.,1.
Jl!23456789· 123456719
0123.6789 o:il3456
01234
>Stop
Set Param
Set Clock
Prg Name
•Use ..,.. key and select "Set Param". Press "OK" to confirm selection. LOGO! displays the first parameter. If
parameters cannot be set, you can use ESC to return to the parameter assignment menu.
BOl:T
T = 12:00m
No Param
Ta= 00: OOm Press ESC
• Use ..,.. or ..A.. key and select desired parameter. Press "OK" to edit parameter value.
•Move the cursor to the parameter value to be changed using .._ or ...,. key.
•Use..,.. or ..A.. key to change to parameter value. Press "OK" to confirm parameter value. Press "ESC" if you do
not want to save changes.
EVAC reserves the right to make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 28
EVAC
Environmental Soll1tio~S-Marine Sector OPERATION AND MAINTENANCE
BOl:T
T = r!]l:OOm
vvv lvlove:<l(or,..
OO:OOm Done: OK
>Stop
Set Param
Set Clock
Prg Name
•Press "ESC" to return to the time and date display.
Mo 09:00
06.21.01
Mo 09:00
06.21.01
>Stop
Set Param
Set Clock
Prg Name
•Select "Stop" using ...... or :....._ key.
Stop Prg
>NO
Yes
•Select "Yes" using ~ or ....._ key. Press "OK" to confirm selection. LOGO! returns to the main menu and there
is no acces to input and output displays.
>Program ..
PC/Card ..
Clock.
Start
7 .0 Starting program
>Program ..
PC/Card ..
Clock.
Start
•Use~ key and select "START'. Press "OK" to confirm selection. No the loaded program is running in LOGO!.
When program is running a time and date are displayed in status display.
Mo 09:00
06.21.01
9.0 Loading new program while LOGO! is running (Only for advanced users)
• Remove an old program module (EEPROM) or open module slot cover.
• Insert a new program module (EEPROM) to program module slot.
•Stop a running program. See "Stopping program".
>Program ..
PC/Card ..
Clock ..
Start
•Select "PC/Card" using -~ or ....._ key. Press "OK" lo confirm selection.
EVAC reserves the rightto make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 30
EVAC r_::=g~-~~.:. 2.~ ~.<?.Y.19-Q_~==~~99:~. ~-~~iQ~?~. . . ~:~.
Environmental SolUtioris Marine sector ! OPERATION AND MAINTENANCE I
>PC.,_,.~~
~~~card
Card-<>~~ ~~ = LOGO!
NOTE: Be extremely careful. There is a risk to erase/ove!Write all data in LOGO! or in a program module.
>Program ..
PC/Card ..
Clock.
Start
•Use ~ key and select "START". Press "OK" to confirm selection.
Mo 09:00
06.21.01
EVAC reserves the right to inake alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 31
EVAC r-~::~-Q~t~~ -~ 1- _J_ ~_0 _ ?Q.9=~=--=::.=~~~P_Q~-~--3:0JJi.1_g:_:~_:.. -~
Environmental Solutions.Marine Sector \L _____
OPERATION
-- - - ---
AND MAINTENANCE
---- ------
\
COMBINED UNITS
STANDARD EVAC STP COMB!
Start-up
Transparent hose for
adjusting sludge return· Air valve,
tank Ill
y -- Level
Vacuum switch,
gauge tank IV
Dosing
Dosing pump set,
pump set (disinfection
(antifoaming chemical
chemical)---;::::~~'$ set)
Ejector
pump
Control Level
panel switch,
tank IV
311;!Pr--- Shut-off
valve,
tank IV
Discharge
valve, pump
ejector
Shut-off
valve, Shut-off
ejector Shut-off valve, valve,
pump valve, discharge tank II
tank I pump
•Open valve "Shut-off valve, ejector", "Shut-offvalve(s) ejector pump", "Shut-off valve, tank IV', and the shut-off valves
of the discharge pumps_
• Close valves "Shut-off valve, tank I" and "Shut-off valve, tank II"_
• Check that discharge line is open.
• Open control panel and check all circuit breakers.
•Check that all control switches are set to position "O"_
•Turn main switch to position "1".
• Reset control panel and check control !eds by pressing push button "SHUT DOWN RESET, ALARM RESET, LED
TEST'.
·Check the rotation direction of the pumps and bl6wer(s) by turning control switches to position "MAN". Let the
pumps run only few seconds.
! NOTE: Never let the pump run dry. Mechanical seals may be damaged.
--·····----··-·----------··-·-·------------··-------~----·-·-·--·------- .. ------···-··-·
EVAC reserves the right to make alterations to this specificationwilhout prior notice.
©Copyright EvacOy. All rights reserved. 87
EVAC
Environmental SolutiOns Marine Sector
COMBINED UNITS
STANDARD EVAC STP COMBI
·--------------------
• Fill antifoaming chemical tank and disinfection chemical tank. Prime the dosing pumps. See the operation instruction
of the dosing pump. Adjust the disinfection chemical dosing pump's capacity. See "Disinfection and chlorine
content test" and the operation instruction of the dosing pump.
·Set the control switches of the blower(s), discharge pump(s) and chlorination pump(s) to position "AUTO".
• Fill the treatment unit with fresh water until chamber IV is filled up and discharge pump starts to discharge. The
pump is started by the "High level switch" and stopped by the "Low level switch" in tank IV.
• Check that disinfection chemical dosing pump starts to run after discharge pump has stopped.
·Check that blower(s) starts to run after presetted pause period and stopped after presetted running time.
·Check that air blower(s) has correct direction of rotation.
·Check that sludge returns from settling tank Ill to activation tank I when the air blower(s) is running.
• Adjustairflowtotank Ill so that amount of the sludge return from tank Ill to tank I is about 1/3 of the pipe section (See
transparent hose above tanks). The rest of the air stream must be divided equally between tanks I and II. (Open
manholes and see check bubling in tanks I and IL)
·Set the control switches of the ejector pump(s), antifoaming pump to position "AUTO".
• Check that ejector pump(s) start and ejector(s) create vacuum. Ejector pump(s) will stop when vacuum level reaches
presetted value.
·The sewage treatment unit is now in automatic operation mode.
! NOTE: Effluent quality is within IMO's limits after about one month of the start up.
EVAC reserves the right to make alterations to this specification without priornolice.
©Copyright EvacOy. All rights reserved. 88
EVAC [_ ·-~-[)a~~-.1-~~~-~-~.?_Q9~~==·[)~~:....~~~-~-1.1_ 0B_____]
Environn1ental Solutions Marine Sector L OPERJ\!l_()_N~ND MAINTENANCE_ _J
COMBINED UNITS
EVACSEWAGETREATMENTPLANTS
It is important to keep a sludge content within certain limits Le. a good biological balance for the treatment process in
the sewage treatment unit
! NOTE: When sludge reading excess 600ml / 1.000ml, sludge must be discharged and the treatment unit must be
filled up with fresh water.
! NOTE: Before entering a restricted area or harbour the treatme,nt unit is recommended to discharge to ensure
that there is a maximum storing capacity in the treatment unit. Use "shut-off valve, tank II" for discharging to ensure
that there is always a minimum bacterial population left in chamber I after discharging.
! NOTE: Never discharge aeration chamber I below minimum volume at the same day with the aeration chamber II.
Ensure always that there is always minimum bacterical population in either chamber I or chamber II to avoid
collapse of the biological proces_s.
--------------·-~----------··-·--·----- -----·---·----~------·----···--····-----
EVAC reserves ttie right to make alterations to this specification without priornotice.
©Copyright EvacOy. All rights reserved. 90
EVAC r:. . ~.~~~iD~~jp_QS -~~::·~~------- DOE~ __?.:Q111."8_!~,,...... j
Environmental Solutions Marine Sector I~()_l'_ERATl~N AND MA!_NT~~r.J(;§__
COMBINED UNITS
STANDARD EVAC STP COMBI
Maintenance
Every day
•Observe that the treatment unit is oprating normally and there is no alarms displayed.
• Check that sludge flows through the sludge return hose when the air blower is running.
•Check a smell of the unit. If the unit is smelling, it is most probably that aeration is not working and treatment
process has changed to anaerobic. See "Trouble shooting" of the treatment plant.
Every week
•If the chemical dosing system is in use, check the chlorine content in the effluent water regularly. See "Disinfection
and residual chlorine test".
•Test sludge content in activation chamber I to ensure that mineral sludge content is within acceptable limits. See
"Sludge test and sludge handling" and discharge sludge if needed.
! NOTE: Take a sludge content test at least every week or every time when sludge "SLUDGE ALARM" is displayed.
Reset "SLUDGE ALARM" by pressing control switch S10 "SHUT DOWN RESET, ALARM RESET, LED TEST" for
10s.
Every month
•Check that there is no obstruction in the aeration piping and in the air distributors.
•Check that there is no obstruction in the overflow between the aeration chamber II and the settling chamber.
•Check that there is no obstruction in the overflow be\ween the settling chamber and the disinfection chamber.
•Check that there is no obstruction in the venting line.
•Inspect the tank's external and internal coatings for corrosion. For repairings see additional coating repairing
instructions.
•Check vacuum function.
Every year
•Empty and clean the unit.
! DANGER: Make sure that the unit is well ventilated and there is enough fresh air in the chamber if you have to go
inside to avoid inhaling toxic fumes and suffocation. One person must stay outside of the tank and keep eye on
person who is working inside the unit.
! NOTE: Make sure that the waste water is lead to a proper holding tank (hull tank or collection tank) during shutdown
or maintenance break
··---·-·--····---··---·---·..-- ----~
EVAC reserves Ule right to make alterations to!Jlis specificationwi!hout prior notice.
©Copyright EvacOy. All rights reserved. 89
EVAC i. ~~=Q-~t-~-~ i~~t~~{)_Q§__,__ . . --~- ~9-~~~~~3~:_2-1. !~. .!~. .
Environmerital Sollitions Marine Sector L__OPE~TION AND MAIN_!_~NA..r.1CE__ "
COMBINED UNITS
EVAC SEWAGE TREATMENT PLANTS
Chlorine concentration must be monitored regularly. Residual clorine should be 2-5 ppm in effluent. If chlorine test
shows that residual chlorine is higher than 5 ppm or lower than 2 ppm, adjust chlorine pump's stroking rate. See the
dosing pump's "Operation and maintenance".
Disinfection chemical
Recommended disinfection chemical is sodium hypochlorite (NaCIO), technical quality, concentration 10% active
chlorine.
! NOTE: See disinfection chemical supplier's safety instructions for disinfection chemicals to get detailed information
about handling and storage.
! NOTE: Observe that the chlorine in the dosing tank is active (fresh) and fill it with fresh solution from the store if
needed.
! NOTE: The storage of chlorine solution should be in a dark room, temperature in between 10-15 °C otherwise it will
loose free chlorine. The max.storage time is 180 days at +10°C. The maximum storage time depends on stroring
temperature i.e. the max. storage time is only 50 days at +25°C if redundancy is 50%. See a chart below.
+10°C
170
"•
0
110
~
" 90
Test procedure:
• Fill the sample glass and throw the first "sample" water away immediately. This action will increases test accuracy
significantly.
• Fill the sample glass from the test cock after discharge pump while the discharge pump is running.
·Immerse test paper in effluent.
• Read the residual chlorine by comparing test papers color to the reference color map, For detailed information see
the test kit's instructions.
-----------·----------~ .. ·---·--------------·--·-··-----~-----~-------·--------------------------·-·-·-------·--·--·------------------·--·-·····-·----
EVAC reserves the right to make alterations to this specification without prior notice.
©CopyrightEvacOy.Al!rightsreserved. 91
EVAC 1·oate:oTAUQ-2-oas-·-·-----ooc. 3:01osoc-
1-··--····--·---- --- -·-------·-·-···--·-·-----·-----···
-.
Environmental Solutions-Marine Sector L 0P_1:_RA'.10NAND MAINTENANCE
1. Installation
Install the pump to the base and ensure that no load is transferred
to the pump from the pipework. Use suitable spacers between the
pump and the base when necessary. Follow the instructions of the
manufacturer of motor and make sure that cooling air is provided for
the motor.
Adjust pipework on the suction and pressure side so that the flanges
fit easily together. Make sure that fixing of bolts will not cause any
load to the pump body.
2. Start-up procedure
Clean the holding tank and pipework from any foreign objects. Fill the holding tank to the filling level before starting the
pump. Follow the operation of the pump and check that it starts and stops as per in electric drawings.
3. Operation
4. Maintenance
4/HK 50-F pump is specially' designed to run together with Evac -ejector in heavy duty sewage conditions with
minimal maintenance. The pump is equipped with high quality mechanical seal and electric motor bearings for long
life operation.
Once a year:
Start pump manually and check operation
•no leaks
• smooth n.mning
• vacuum is created
(·recommended: check indicator lamps, valves and vacuum pressure during operation)
----------
5 18 17 7
j
\\ J
I
I I
I
i
~~
'1 \
a" "''1
12 11 13 48 28 27
•Remove the fastening screws situated in between the casing (1) and the interstage casing (3).
• Force complete replacement assembly out of the centering of the pump casing (1) by means of two forcing bolts
against interstage casing (3).
-----------·-----------------··----~----·---------------------·-··------------ ---··-·--···--------·------------
EVAC reserves the right to make alterations to this specification without prjor notice.
©Copyright EvacOy. All rights reserved. 24
EVAC .....P..~!IO!...'. ......Q~...r:.1.~!.-~_Q.Q?. ________________ Qgg_: __ ~:O 1126 B
Environmental Solutions_ Marine· Sector OPERATION AND MAINTENANCE
• Release the fastening bolts of the motor (7) and the interstage casing (3).
• Lift off the interstage casing (3) in alignment along the shaft.
EVAC reserves the righllo make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 26
EVAC ·-. =f?~~.~~~_.:_ Q~::t~~~-~.9_QZ=-~---~-- QQ£~~~~~-!~§-~---··=:
Environmental Solutions Marine Sector OPERATION AND MAINTENANCE
'-.,.,..
•Remove the mechanical seal (17) from the interstage casing (3),
• Clean the high grade steel motor shaft with an ultrafine emery cloth to remove dirt and deposits.
• Check dismantled components for possible damage and renew if necessary.
•Always renew defective mechanical seals as a complete unit
In case of interstage casing (3) has a retaining ring (18) remove it, otherwise skip this stage.
• Remove the retaining ring (18) from the interstage casing (3). NOTE: The retaining ring is not necessary part with
box/bellow type mechanical seal. Always renew defective mechanical seals as a complete unit
-------~--··-- ..· - - - - - - - - - - - - - - - - - - - -
EVAC reserves the right to make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 27
,-- -----------------..--·--------··
EVAC
------
' Date: 09 Mar 2007 Doc. 3:011268
1 ···· ----· - -----·-·-··-·,,·-·--
Environmental Solutions Marine Sector l_ c:l_F>E_RATION AND MAINTENANCE··"
·------ ···-··..-···-·-----------
·Press the counterring of the mechanical seal into the interstage casing (3) (sequence: 0-ring- counterring). Make
sure that no foreign bodies can become deposited on the sliding surface. The 0-ring may be coated with a parting
compound or other suitable lubricant to facilitate fitment. Do not use oil.
• Carefully slide the interstage casing (3) over the motor onto the centring spigot of the motor (7). NOTE: Take care
not to damage the counterring of the mechanical seal on the thread and/or shoulder of the shaft. Make sure that
it is not pressed askew.
---~-·-----------·-··-·------·----·--···-----
EVAC reserves the rightto make alterations to this specification without priornotice.
©Copyright EvacOy. All rightsreserved. 28
EVAC .. =i
1~-~-~~-t~_: .9.~. .M~~iQQz. __~==g~~-~:~~:_9.1I?.§.f.3__
Environmental Solutions Ivlarine Sector I OPERA!ION A~D MAINI~~~~0'_j
·Slide the box/bellow type part over the shoulder of the motor shaft and push it up against the already fitted
counterring. The 0-ring may be coated with a parting compound or other suitable lubricant to facilitate fitment. Do
not use oil.
• When fitment of the mechanical seal is complete, insert the shaft key on the motor shaft.
EVAC r_::. :.)2.~~i:_: _ _ _Q_~-·~-~ 2002_.._______ J?..0.~:_j_~Qjj~?_l?_ . . ~1
Enviromnental Soli.J:tions l\farine SeCtOr i OPERATIONANDMAINTENANCE i
L-------------------
··· · - ..
• Push the impeller (2) onto the motor shaft and secure with the impeller nut (13).
•Check the gap between the blade end of impeller (2) and the corresponding face of the casing (1) (check with
depth gauge etc.). The gap must be 0.5- 0.7 mm. If, for example, it is found that the gap is insufficient i.e. the
impeller (2) will run against the casing (1) a second gasket must placed between interstage casing (3) and casing
(1). If, for example, it is found that the impeller clearance is excessive, a shim must be placed behind the impeller
(2) to take up the clearance:
• Excessive clearance will result in considerable loss of capacity of the pump.
•Insert the complete assembly in to the pump casing (1) and bolt it in the position.
•Reconnect the motor electrically. It is essential to observe the type of electrical connection (see motor rating
plate).
•Check rotation direction (see direction of rotation arrow).
•Start up the pump unit (see start-up).
COMBINED UNITS
VACUUM GENERATION
. Pressure switch
,,.,.-.-;::-:.~-
•' .
<:'.·~:..... Vacuum gauge
·:.--
Cause Remedy
EVAC reserves the right lo make alterations to this specificationwithout priOf notice. 9
©Copyright EvacOy. AU rights reserved. 2
EVAC
E~VirOllm,ent:ll SOiutions Marine Sector
COMBINED UNITS
EJECTORDN80
Non-return valve
Sealing surfaces
Flange Flap
Connecting
Bend
-----Plug
Flange
--L~--l:J I I
Nozzle
Cause Remedy
• Sewage plug in the ejector. • Make sure that pump is stopped and shut-
off valve is closed.
• Remove plug and clean out ejector. If this
procedure is unsuccesful, the following
steps should be taken.
• Dismantle flange connections and remove
bend.
• Dismantle flange connections and remove
ejector from tank.
• Dismantle flange connections and remove
connection cone.
• Withdraw non-return valve from ejector.
• Clean sealing surfaces and if necessary
replace rubber flap.
•While the ejector is dismantled, ii is
advisable to check the nozzle and the
inside of the ejector housing for sludge and
impurities.
• R_efit ejector and non-return valve in reverse
order to dismantling, at same lime checking
the condition of all seals and replacing as
necessary.
• Make sure that non-return valve is correctly
positioned.
COMBINED UNITS
EVAC SEWAGE TREATMENT PLANTS, TREATMENT PROCESS
orreplace.
•Too much water enters the plant. •Allowed in peak periods. Try to
reduce peak flow.
·Wrong rotation direction. • Change phases on electrical motor.
• Impeller defect. • Replace impeller.
•Valve in discharge system closed • Check valves in discharge system.
or defect.
• Pump is clogged. • Open and clean pump.
• Discharge pump defect. • Open bypass and repair/replace
discharge pump.
•Too much water enters the plant. •Allowed in peak periods. Try to
reduce peak flow.
~~RiJ~~~~~~r-·~S§cC.reeee.n~i~n~aee~railiti~onncchh:a~mnb~ee.r~c~lo~gmgeedd.:--~.ic~1~ea~n~s~c~r~ee~nand_re_m_o_v_e_d~i~rt-.
•Timer wrongly adjusted. ·Check and adjust timer.
·No power. •Check the electrical system.
·Automatic fuses off. •Check reason for this before
• Motor defect. switching fuses on.
• Impeller defect. • Replace or repair.
• Defect non-return valve and water in • Replace impeller.
air blower. • Repair and replace valve.
--~·- ---·--------·
EVAC reserves the rightto make alterations lo this specificationwithoul priOI" notice.
©Copyright EvacOy. All rights reserved. 94
EVAC
Environmental Solutio·ns ·Marine Sec-1:or TROUBLE SHOOTING
COMBINED UNITS
EVAC SEWAGE TREATMENT PLANTS, TREATMENT PROCESS
------ ------------~-----------
------·······--~~~~-
EVAC reserves the rightto make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 95
EVAC
Envirorimeiltal SOiutiorts Mirine SeciOr
COMBINED UNITS
72008000 EJECTOR DN80, NOZZLE 030
5430571
Ejector bend
2613255
/ Screw(x4)
/
( 5430668
5430816 '
Rubbergasket~ Non-return valve,
complete
5430834 I
Nozzle
5430827 w !
Gasket
5430861
. , .~"-~
Rubber gasket
I
I
__ ) r
5437385~
I
'lo.
Nut(x4)
j(o ~
I ' I -------~
\-·~""'
i
5437385
Nut(x4)~
5430805
I
i
I ~
5450324
Nut (x 8)
2613190
T
Screw (x 8)
5450202
Connecfion
joint
0-ling
72008024
Square gasket
72008030
Square flange
with stud screws
72008010
Ejector body
------·--·---
EVAC reserves Uie right to make aJtera!ionsto th is specification wilh~;rt prior notice.
©Copyright EvacQy. All rights reserved. 96
EVAC ··::.:.g~t~~-?-~:.~.~s=-~92~--·-·····~- _ ooc _.~0391.~~t!~:·~=
Envitonmeni3.I S~luiions Marine Sector SPARE PARTS
COMBINED UNITS
6541200 PUMP 4/HK 50-F, 3x400/460V, 50/GOHZ
6542093 Pump:
7921 0066 Impeller
\~~JJI. -- ------,1 1
I
I
I
I
I
!
_J'
Impeller nut
-- -- --·
-- -- ----
------
6542052
Pump housing Fan cover
----- -- \
------ 6542051 \
-- -- -----
,- ----
-- 6542201
1 Shaft with rotor
I
Anti-friction
bearing, drive side
·-------·-·-·---· --~-~-
EVAC reserves the right to make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 97
EVAC
Envirorunental SolUtions Marine Sector
COMBINED UNITS
70230001 PUMP ES 135/4, 3X400/480V, 50/GOHZ, IMPELLER 0135
r
.
~-
1~ 1 ~
-v-----.-------------
sll'-VJJ
.
~
-
-c- - - -- '
I
I SPARE PART SET FOR PUMPS ES 135/4AND ES 120 INCLUDES PARTS: I
I 0-ring 0-ring Mechanical 0-ring 0-ring I
185x3 80x3 seal 150x3 24x6
L ____ \---\---111't' Mlfis6!fzs-i""-\\-.-. ---""\,
\ \ \ \ '- ~,- ,'":~ ' \
==-=--=--=- . --=-----~
.. l
\ \
'
. \ \
I.
~
~-.
,
'c.:
\
'
·i
'
I
ll==>-1--. " \ \ . ~,-- I\ I
"\\ \ I \, I
-llH!--4n- - iJtte il
I ~22,'. .i\S I
6541984 6541985
6542827 Impeller (ES 120) I I
or
Knife Cutter 6542829 Impeller (ES 135/4) I I
~-~---~---~---~--~---~--J- _jl
I
1
I
6542828
MOTOR (Es 120)
or
EB__j__ I
1
I
m
I
I 6542830 I
I MOTOR (ES 135/4) ~l I I
l ~i?i1:Jft;: MCftS6/1S-l 1 :
: rb :
lI cu :I
I I
:l
I I
' I I
I ~:1
L_~ --.~,.-~.-~-@-Efit2!!:1 ,11e = ·
ruf~~ ~-8 I
l ' "'.' r"Hi::i... 1
L--------------------------------~
! NOTE: Spare parts which includes in spare part set are not sold separately.
EVAC reserves the right to make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 99
EVAC
Environmental SolllriOns Marine Sector
f:~~~~~~M~l~~
'-------~
_____ Q:O-, Bo1<i9iG::~1
- . --C
COMBINED UNITS
70302001 AIR BLOWER V12YR COMPLETE, 3X400/460V, 50/60 HZ
6542730
,Electrical motor
r-------~----------------/--------,
I 65f1709SPAREPARTSET /
I ~ - i
I Gasket for silencer lid , /
1
I
I "- '1._Ld',f---,-
I
/,
I
Muffling material---- - - -
I
(12pcs)
I
I
I
I Spider
I 0-ring --------------
//
I ~ill~~-/
I Bearing
0-ring
L---------------------------------~
! NOTE: Spare parts which include in spare part set are not sold separately.
EVAC reserves the right to make af!eratlons to this specification without priornotice.
@Copyright Evac Oy. All rights reserved. 100
• 4. SPARE PARTS
TABLE OF DELIVERY CONTENT (Spare part)
<Vacuum Toilet>
Item Description Description2 Q'ty
6542990 Sleeve diaphragm 1pc
5959902 Mini check valve 1pc
6542438 Button and button flange for control mechanism 1pc
6542428 Flushing nozzle 1pc
6542430 Water hose 1pc
5774002 Water valve 1pc
"· 5435181 Rubber sleeve 2pcs
x 5435169 Rubber diaphragm 1pc
VS?Fl·i"·'' v
v&;~)~f0
• 5.PIPING
EVAC ~--"()~f~~-~i~:}_~D_]OD_§__~~~~-~-~-~Q:i~~:::.§.~QiQQjQ~:.:.~ :
Environmeilt,al'Solutions Marine Sector [ PIPING
-----------·---------
PIPING
DESIGN AND INSTALLATION
~
1. General system description
2. Pipe materials
3. Pipe sizes I i
4. Pipe connections
5.
6.
7.
Pipe fittings
Brackets
Optimal piping design
I i
6
I
8. Pipe profile, slope and transport pockets 6
9. Branches 8
10. Riser pipes for toilets and interface valves 9
11. Non,return valves 10
12. Shut-off valves 11
13. Inspection openings 12
14. Deck penetrations examples 12
15. Pipe manifold I 13 I
16.
17.
Tank vent pipe
Standard flange for port discharging
I 14 I
14 '1
Enclosure:
.~1. -~~J
Piping (Doc no. 5:01004):
• Tightness requirement
I_ Ti:'~tness test protocol
Existing rules, regulations and standards must be observed. In case of doubt, check with
the manufacturer. Metric units are used throughout the manual. Dimensions are given in
millimetres (mm), unless otherwise stated.
. --·---~~--------------·--- ---
EVAC reserves the rightto make alterations to this specification without prior notice.
©Copyright EvacOy. Afl rigits reserved. 1
EVAC
Environmental Solutions Marine.Sector
PIPING
DESIGN AND INSTALLATION
In vacuum systems sewage transport is done by vacuum (air) instead of water and gravity. Sewage is transported in
"slugs". Optimal "slug" transport is obtained by following these Design and Installation instructions.
System capacity must be dimensioned considering normal daily variations in use and different operation conditions.
System load (fiushings) should be divided evenly between main lines. Ships pitch, a roll and trim shall be considered
in horizontal pipe design to prevent sewage back flow. The best horizontal transport solution is obtained with sloped
pipe, transport pocket at interval of25- 30m and/or non-return valve. Piping shall be designed so that possible clogging
or maintenance is not stopping the whole system. System pipe tightness must be tested, documented and maintained
for good system operation and low energy consumption. Piping shall be accessible and divided in sections for easy
maintenance. ·
Ventilation
Exhaust-air
pipe
Shore
connection
Connection to a
Collecting unit• sewage treatment
plant or holding tank
*) The collecting unit can be based on Evac ejector system, where the collecting tank
is under atmospheric pressure, or on Evac vacuum tank system, or On-line vacuum
generating system.
--~------·-·-·~------- -·--·-·-·-------- - - -
EVAC reserves the right to make alterations to this specificationwithout prior notice.
©Copyright EvacOy. All rights reserved. 2
!·-·oate: -13 Jun 2006 ______ oo~S:o-1·0010·1
EVAC l·--· .. ··-·-·-·-·-·--------···-·--····--·--~-------····--·-------·-1
PIPING
DESIGN AND INSTALLATION
2. Pipe materials
Pipe material must be suitable for sewage transport in vacuum conditions (pressure piping). Fire, corrosion and
maintenance aspects must be considered.
When plastic pipes are used, fire protection regulations must be observed. Note the differences between the different
kinds of plastic materials. HDPE may not be allowed by some authorities.
Check carefully aspects relating to safety and industrial hygiene. Vapours released by PVC solvents are harmful.
Plastic piping does not resist temperatures above 40°C. (Check always with the pipe manufacturer. )
3. Pipe sizes
Number of or Public Minimum cipe size (d x s)
vacuum toilets* Connection HDPE PVC Steel Stainless steel Zinc coated Cu/Ni
toilets in DN d x s (mm) dxs(mm) dxs(mm) d x s (mm) steel d x s (mm)
cabins* d x s <mm)
3 or 1 40 (50) 50x4.6. 50 x 2.4 48.3 x 2.6 50 x 1.0 -53 x 1.5*** 44.5x 1.5
25 or 5 50 63 x 5.8 63x3 60.3 x 2.9 50 x 1.0 -53 x 1.5 57.0 x 2.0
100 or 25 65 (70) 75 x 6.9 75 x 3.6 76.1 x 2.9 75 x 1.0*** -73 x 1.6*** 89.0 x 2.5
Pipe sizing is based on the assumption that 2 - 3 persons are using a cabin toilet per peak hour. For public
toilets up to 15 flushes per hour is estimated.
Heavily used public toilets are recommended to be connected to their own individual pipe connected directly
down to manifold.
• Normally maximum number of toilets in one main line is limited to 50 - 60 toilets for easy maintenance.
"When using zinc coated steel pipes, the recommended riser pipe size is DN40 (42 x 1.5).
EVAC reserves !he rightto make a!teretions to !his speciftcationwithout prior notice.
©Cop)llight EvacOy.All rights reserved. 3
EVAC
Environmental SOlutiOris-Marine SeCtOr PIPING
PIPING
DESIGN AND INSTALLATION
------------------~--------~
4. Pipe connections
Connections have to be tight Joints must be smooth and must not in any way decrease the cross-section area of
the pipe.
HDPEtoHDPE
Mirrorwelding
HOPE-pipes are joined together either by means of mirror welding or with an electric sleeve. In manual mirrorwelding,
the interior of the pipe is chamfered prior to welding. Observe heating temperature, compression time and power, given
by manufacturer of the pipe. Mirror welding is mainly used for prefabricated subassemblies.
PVC to PVC
STEEL!o STEEL
.••
•.
J
--r---------+-,.- -· _L
The steel pipes are joined together either by welding or by flange connection.
PIPING
DESIGN AND INSTALLATION
5. Pipe fittings
Use fittings with large enough curvature radius or use fittings with 45° bends.
Pipe bends located> 3 m from the toilet or interface valve must have large radius or 2 x 45° elbows.
LR (
r>2.5d elbows
Solvent I Weld I
Weld Rubber Seal Thread
.
Toilet and interface valve connections within lenght of max 3 m can be made with short radio us bends.
EVAC reserves the right to make alterations to this speciHcation without prior notice.
©Copyright EvacOy. All righ~ reserved. 5
EVAC i--·--··-··-----··-----------------------··-------1
Date: 13 Jun 2006 Doc. 5:010010 i
PIPING
DESIGN AND INSTALLATION
6. Brackets
In vacuum piping high "slug" speed temporarily creates strong forces at bends and branches. Pipes must be firmly
secured by using brackets and clamps. For plastic pipes use steel brackets with a resilient liner between bracket and
pipe, or plastic clamps. Ensure that pipes will not be damaged by vibration or thermal expansion I contraction. Brackets
or clamps must be fitted at every change of direction. When connecting a riser pipe to an overhead main line, brackets
or clamps must be secured both behind the toilet and atdeckhead. For straight steel pipes, fit bracketsat2.5 m centres
and on plastic pipes at 1.5 m centres, or according to maker" s recommendation.
TT
+ G
Bracket must resist lateral forces.
Vacuum system gives many benefits and flexibility because the system is not depended on gravity.
Downward piping connection is the best for·long term system operation and maintenance although sanitary
equipments (toilets and interface valves) can be connected to riser pipes.
When riser pipes are used, please follow enclosed riser pipe rules in item 1O.
EVAC reserves !he right to make alterations to this specification without priornotice.
©Copyright EvacOy. All rights reserved. 6
EVAC . __Q~~~_:__ Jl..~~n 20_0_£_ ____
DQ.S_ __§~Q1Q.Q_:LQ_ __ j
Environmental Sohitiofls Marine sector PIPING
PIPING
DESIGN AND INSTALLATION
- - =:::::;::~
! NOTE: The combined height L H, + .H2 + .... H" shall not exceed 3 meters.
•---~T=<1m
I~ [: :--><.l~_,_____.1i--
1. ~ ~ Reforming pocket
-
D =outside diameter 40
CIC 25-30 m horizontally.
----~~-·---·· - --~-~--
EVAC reserves the right to make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 7
EVAC
Environmental Solutions Marine SeciOr
PIPING
DESIGN AND INSTALLATION
-
Horizontal pipes
Horizontal pipes shall run either downwards in the direction of the flow or horizontally,neverwith a steady upward
gradient. Trim, roll and pitch of the ship shall be noticed.
Max Ieng ht for a straight horizontal pipe is 25 - 30 m before a pocket, non-return valve or downward piping.
9. Branches
.. -------
EVAC reserves the rightto make alterations to this specificationwithout prior notice.
©Copyright EvacOy. Al! rights reseived. 8
EVAC
Environmental SOIUtions Marine Sector
PIPING
DESIGN AND INSTALLATION
45°
-
!!ilrulr
projection IBranch line
10. Riser pipes for toilets and interface valves
•Typical 2-3 m (one deck height) riser pipe with a toilet or interface valve.
~A~91 1
11 Max. pipe lenght is 30 m
from downward pipe Straight riser
DN40 pipe without
riser pipe changes of
N direction
PIPING
DESIGN AND INSTALLATION
• Riser pipe with lift 3 ... 5 m lift is allowed only immediately after a toilet and back flow must be
prevented by a transport pocket and non-return valve.
/ Non-retumvalve
DN50
DN40
Max30mfrom Straight riser pipe
downward pipe
• The diameter of the riser pipe must not be enlarged in the rising part.
NO YES
t
A non-return valve is used where a riser or horizontal part of the piping system might become flooded due to backflow.
If a horizontal collector has connections from both above and below, riser pipes are fitted with non-return valves located
at the highest point of the riser pipe.
Non-return valve
---·-·------------·---------------
EVAC reserves the right lo make alterations tothiS specification without priornotice.
©Copyright EvacOy. AU rights reserved. 10
EVAC ~~Q~_e: 1}_}~~n..?..Qg_~~-~-~~:~-~~~~=-~JiIQQ_1Q.~~~
1
PIPING
DESIGN AND INSTALLATION
A non-return valve shall always be fitted in a toilet connection with a riser pipe exceeding 3 metres.
Non-return valve
>3m
I NOTE: As mentioned in section 10, it is preferable to provide two horizontal collectors. One for connections from
• above, and one for connections from below. The non-return valves may be omitted.
Max30 m from
downward pipe
Shut-off valves should be straight-channel valves (slide, membrane or ball). The valves should be located in such a
way that a malfunction or leakage would not stop the whole system. Valves should generally be installed on each
main pipeline.
If possible, the shut-off valve should be_ located on a vertical part of a pipe. In such position, possible sedimentation
in front of the slide will not cause a stoppage easily.
EVAC reserves the right to make alterations lo this specification without priornotice.
©Copyrigh!EvacOy.Al!rightsreserved. 11
EVAC [~R~_!E}_: _ ~!~_)g~_?_OOB_________ ~:=g__~~: -~-~0.1_ Q_Qi:Q:_·_-_J
Environmental Solutions Marine Sector L__ PIPllll_(>_ __ ----·
PIPING
DESIGN AND INSTALLATION
Inspection openings should be located in such a way that a possible clogging in the piping can be reached at all
points. Maximum distance between openings is 25 - 30 metres_
Locations:
1 . At the end of horizontal pipelines
2. At the upper end of vertical main pipelines
3. At intervals of25 - 30 metres on horizontal pipelines
4. At pockets
5. At 90' bends
1. 2. 3.
5.
-
14. Deck pnetration examples
Vacuum pipe
Seal
Deck Deck
------··-----·----c-cc~·
EVAC reserves the right to make alterations to this specification without prior notice.
©Copyright EvacOy. All rights reserved. 12
EVAC
Environmental SOiutions M~riµC! SeCtor
PIPING
DESIGN AND INSTALLATION
500 500
Plastic pipe
50
!NOTE: Fire-protection rules and rules about watertight compartments shall be observed.
5. 8. DNX 9.
DN65
DN Xis usually equal or one size larger than the incoming mainlines DN Y, however, DN X
is at a minimum DN 65.
PIPING
DESIGN AND INSTALLATION
The smallest recommended diameterfor a collecting tank vent pipe is DN100. Maximum pressure drop allowed for the
tank vent pipe is 10 cm water column.There must not be pockets or horizontal parts in the vent pipe where possible
condensate water might remain and block the airflow. The vent pipe must be routed to a place where smell of sewage
is not disturbing passengers or crew.
210
Pipe dimensions
11 16
ON ·65 80 100
,,==------<'-LL.. '
,..u..,,"""""".,,:
__ E:
-----·--·--------------··-----
El/AC reserves the right to make alterations to this specification without prior notice.
©Copyright EvacOy .All rights reserved. 14
EVAC
Environmentai'Solutiolls Mariile Sector
PIPING
TIGHTNESS REQUIREMENT
As sewage transportation is based on pressure difference, there should be minimum leakage in the vacuum sewage
system. Leakage in the system will lower systems operation performance and gives excess wear and tear for
components. Electric consumption will increase due to the fact that the pumps must run more often to obtain
vacuum. Low vacuum decreases the sewage flow speed in pipes and it will increase the risk of clogging.
Pipe installation design and tightness of a vacuum pipeline must be checked in stages during construction, one
section pipeline at a time. Tightness testing can be done by using pressure air, water or preferably with vacuum.
Pipeline tightness testing is to be done before installation of toilets etc. Toilet connections shall be blocked during the
test by rubber plugs or equal.
During the pipe installation, tightness tests shall be done to eliminate possible leaks in pipe joints etc. When the
sewage piping system is ready with all vacuum· components connected, the test should be run again to check any
possible leakages in toilets, vacuum interface valves etc.
When toilets and other components are connected to the piping, vacuum pressure in the piping system shall stay
between -55 kPa ... -35 kPa for 10-30 minutes without pump starts to guarantee all different operation conditons.
The tightness of the piping system must always be tested. The test procedure and test results must be documented.
(see enclosed test protocol).
PIPING
TIGHTNESS REQUIREMENT
General
All piping must be tightness-tested before toilets, interface valves and vacuum units are connected to the piping
system. Tightness must be checked pipe section by pipe section_ Finally the complete vacuum piping must be
checked.
1. Vacuum Test:
-60 kPa vacuum is created to the pipe, all possible leaks are to be removed until leak is limited to
+2 kPa/h (Le. 2 kPa drop in pressurefr<:>m-60 kPa to-58 kPa during 1 hour)_
Documentation of results
Always document the results (use enclosed test protocol)_
cc_ Yard
Owner
EVAC
16
EVAC
Environmental SoltitionS Marine se<;tor
PIPING
OPERATION AND MAINTENANCE
1. General
2. Pipe cleaning
3. Pipe cleaning examples
----·--·----··-
EVAC reserves the right to make alterations to this speciftcationwithout prior notice.
©Copyright EvacOy. AH rightsreserved. 17
EVAC ..._f2~~e: .9.Z..Q~~-~Q§_----~~YE:. s:D_19..Q5.9_.~-~
-.: ·Eii\ii;onment~1 soiutians M~rirle S'ector PIPING
--·--···-----·- - - - ---·--·····-···--·····-··-·····-·-·---------··
PIPING
OPERATION AND MAINTENANCE
1. General
This document provides information about pipe operation and maintenance and shall be used as advisory only. The
maintenance shall be carried out by qualified and authorized personnel to avoid any risks and misuses. While carrying
out the maintenance, the safety instructions must be followed.
As sewage is an aggressive liquid and can cause corrosion which may lead to leakages in pipes and in system
components, it is recommended thatthe piping should be inspected 2 .. .4 times peryearvisuallythrough cleaning plugs
and flanges.
During inspection, also check the cleaness of the pipe. The risk of built-up deposits is most likely in horizontal pipe
lines, near urinals, in places where ihe sewage flow is slow and in areas, where the temperature is high. lfany serious
deposits or build-ups occur, clean the pipe by the following method: Rinse the piping with a lime-removing agent, e.g.
15-30% phosphoric acid or similar. The agent should be poured into the toilets atthe end of each main branch of the
piping. The acid should be allowed to work for some hours depending on the amount of solid built-ups. Occasionally
a piping treatment may be necessary where toilets and other components are removed and piping plugged and filled
with circulating chemical for 4... 24 hours at regular interval.
! NOTE: Before filling up the piping with chemicals, check pipe tightness by filling the pipes with water. Strong chemicals
may be harmful to the pipes and biological treatment plant.
! HINT: Today's camera technology (camera into vacuum piping) makes it very easy to locate problem section(s) of
piping or how frequently pipe cleaning should be done.
2. Pipe cleaning
Best results will be achieved if regular cleaning procedures are adopted from the very beginning of the vessels delivery
from the yard.
Evac has developed automatic dosing pump set ( P/N 6540390) where cleaning chemical can be fed into the piping
automatically.
By the time; vacuum sewage piping may exhibit signs of build-up deposit.This problem can in most cases be reduced
ortotally eliminated by undertaking relatively simple preventive maintenance measures. It is recommended that ships
experiencing problems with build-up adopt the following maintenance routine:
Pour suitable chemical (see attached list) in each toilet at the end of each vacuum line with a build-up of deposit
problem and flush the toilets.
lnjtially, repeat the procedure every week. Once the problem has been brought under control, repeat the treatment
regularly. ·
! NOTE: If used· excessively, some chemicals may degrade the performance of some biological treatment plants.
Local regulations must be adhered to when handling some of the listed chemicals .
. EVAC reserves the right to make alterations to this specification without prior notice.
. ©Copyright EvacOy. All rightsreserved. 18
EVAC
Environmental Solutioiis Marine Sector
PIPING
OPERATION AND MAINTENANCE
Best results will be achieved when regular cleaning procedures are adopted from the very beginning of the vessels
delivery from the yard.
The build-ups occur most easily in places such as low bends in the horizontal part of the piping, where the sewage has
a possibility to lie still for longer periods of time or where the flow velocity is low. Heat stimulates the build-up of deposits.
.. '=-----~· )
··f~'
\' >- ;\ \>·· Chemical
.
........ .! L__; tank
1. Pipe cleaning is carried out by automatic dosing unit at the end of pipe line approximately once per week.
EVAC reserves lherighltomake~lterationstothisspecificationwithotA°P~~tice. -----------------------·------·---
©CopyrightEvacOy.All rights reserved. . 19
EVAC
Envirollmeiitai Solutici'Os ·Maririe .SeCtor
PIPING
OPERATION AND MAINTENANCE
2. It is recommended to dose chemical into the manifold and collecting unit, to keep the pumps and ejectors valves
free from deposits.
Chemical
Manifold
r--·----
'---•----u----..
! NOTE: ltisrecommendedto use the dosing method regularly. In order toprolongtheneedforusinga more complicated
methods.
1. Estimate the volume of the piping system, to be able to fill the piping with correct amount of chemical for the
treatment.
{\'
\ ,.
\____!
PIPING
OPERATION AND MAINTENANCE
2. Isolate the horizontal branch pipe to be treated from vertical main pipe by means of the shut-of valve.
,,....-,-
'\ ' (-.
l.j
3. Check the piping drawings to be sure that there are no connections to, for instance, the toilets with riser pipes.
Chemical mixture may overilow through the riser toilets.
~-
·:l___.>
.
4. It is always recommended to pressure test the piping with water to ensure that there are no leaks or connections
with overilow possibility before chemicals are fed into the pipe.
I 11\
I I II
;~
'(""\""
'i f'-·
I I I
~ ..../
------·-·-·-·--..,,-~cc----c~--oc--c-.,.·-c--
EVAC reserves the right to make alterations to this specificationwithout prior notice.
-----·-------·---·~-··- ------·------·--------·
©CopyrightEvacOy.Allrightsreserved. 21
EVAC
EilvironmentaI SolutiOns Mariri.e S~ci~r PIPING
PIPING
OPERATION AND MAINTENANCE
5. There can be places in the piping system where a drilled hole has been used to find the location of a pipe blockage.
Occasionally such drill holes may have been plugged inappropriately only to stand vacuum, not pressure or
chemicals. In this case there is a risk the cleaning chemical may penetrate the plugged hole and cause leakage.
Such holes shall be secured properly by ordinary connectors prior the work and pressure tested with water.
A drilled hole
6. To ventilate the piping during chemical filling, open the vacuum piping for instance adjacenttothe chemical feeding.
It is important thatthe open end of the piping system is well ventilated, because chemical cleaning process is creating
toxic gases. Do not have open flames, sparks, or any sources offire in the vicinity of the open end of piping.
'. .
' f :~'.?!H:.nJJti?~+i4'.ik'ii.?J
7. Fill the branch pipe with the cleaning chemical. The reaction between the deposits and the chemical will start
immediately and the "cooking process" begins.
8. During the treatment, the piping can be knocked to remove the deposits from the pipe walls.
10. After the treatment, flush the piping thoroughly with water starting from the toilets nearest the vertical main pipe.
(lftheflushingwill be started from theend of horizontal main pipe, there isa risk thatthe removed deposits will block
the pipe). Occasionally a second treatment may be necessary.
Thereare speciliazed companies to clean sewage pipes by circulating cleaning chemicals through the piping section.
All components are first disconnected from the section pipe to be cleaned. Piping is filled with water to be sure that
there are no leaks. Chemical circulation hoses are connected to the pipe to be cleaned. Chemical is circulated until
the section pipe is clean. More detailed information is available on request.
When using cleaning chemicals always follow manufacturer's instructions for safe use chemical and disposal.
------·--·· - - - - ·
EVAC reserves the right to make alterations to this specification without priornotice.
©Copyright EvacOy. All rights reserved. 22
EVAC i j:Ec-fiNlc.A:i:oi\r.A.- .
Date: 16 Dec 2004 --..D
..... o_c....-... __1__:0_1_1_3__6
.. _s_.___ .. ,:
Environmental Solutions Marine Sec.toe
Chemical Pipes
SS 316 Black steer Galvanized Steel Epoxy coated, CuNiFer
galvanized steel,
type LORO
Hydrochloric Acid 100% _2 3 3 4 3
Hydrochloric Acid 20% 2 3 3 4 3
Phosphoric Acid 2 1 2 2 2
Chlorine 2 2 2 2 2
Scale:
1 =Very good
2 =Good
3= Moderate
4 =Not recommended
- - - - ·-·-·-------..- ·----~---------------------
© Evac Oy 2005
• 7. EVAC REPRESENTATIVES
EVAC COMPANIES AND
MARINE REPRESENTATIVES WORLDWIDE 1
Finland Argentina
Evac Oy (Marine Head Office) Marine Logistics,S.A. Hassler & Associates
Sinimaentie 14 Avenue Alvarez Jonte 6469 12408 Tanager Drive
FIN-02630 Espoo 1408 Buenos Aires Gig Harbor, WA 98332
Finland Argentina Mr. Carl Hassler
Tel.: +358-20 7630 200 Mr. Francisco Agolio Tel.: +1-253-851-3248
Fax: + 358-20 7630 222 Tel.: +54-11-4644 4449 Fax: +1-253-851-3249
evac.marine@evac.zodiac.com Fax: +54-11-4642 2460 earl hassler@msn.com
www.evac.com. www zodiac.com franciscoagolio@marinelogistics.com.ar (British Columbia)
www.marinelogistics.com.ar
China, P.R. EMAR Services
Evac Vacuum Systems Australia 1680 D River Road, PO Box 281
(Shanghai) Co. ltd H.I. Fraser P1y ltd Manotick, Ontario, CN K4M 1A3
Unit F, 24th floor, JiuShi FuXing Mansion 27a Stockdale Rd Mr. Steve Cant
No. 918 Huai Hai Road (M) · O'Connor, WA 6163 Tel.: +1-613-692-1114
SHANGHAI 200020 Australia Fax::+1-613-692-1342
People's Republic of China Mr. Jeff McDonald scant@emarservice.net
Tel.: +86-21-6415 9580 Tel.: +61-8-9314 7877 www.emarservice.com
Fax: +86-21-6415 7550 Fax::+61-8-9314 5933 (Ontario, Quebec, Manitoba,
info.evaccn@evac.zodiac.com jeff@hifraser.com Saskatchewan)
www.hifraser.com
France Chile
Evac E.U.R.L. Bolivia Maquinarias E lnversiones
35/37 Avenue du Gros Chene Maquinarias E lnversiones Tecnicas S.A. (MITSA)
Pare d'Activites des Bellevues Tecnicas S. A. (MITSA) Avda Vicuna Mackenna
BP 50098, ERAGNY Avda Vicuna Mackenna No. 882 - Renaca
F-95613 CERGY-PONTOISE CEDEX No. 882 - Renaca Vina Del Mar, Chile
France Vina Del Mar, Chile Mr. Eduardo De la Iglesia
Tel.: +33-1-3421 9988 Mr. Eduardo De la Iglesia Tel.: +56-32-2834052
Fax: +33-1-3464 3900 Tel.: +56-32-2834 052 Fax: +56-32-2833692
infofr@evac.zodiac.com Fax: +56-32-2833 692 evacequips@mitsachile.com
evacequips@mitsachile.com www.mitsachile.com
USA www.mitsachile.com
Evac North America Inc. Columbia
1260 Turret Drive Brazil Equipment & Systems
ROCKFORD, Illinois 61115-1486 P-VAC Vacuum Parts Engineering (ESE)
USA Rua Luis Otavio No. 2.955 14260 SW 136 St.
Tel.: +1-815-654 8300 Campinas - SP Units 4 & 5
Fax: +1-815-654 8306 13087 - 560 Miami, FL 33186
marine.us@evac.zodiac.com Brazil Mr. Jose Masis
Mr. Pedro Nobrega Tel.: +1-305-378-4101
Tel.: +55-19-3256 3490 Fax: +1-305-378-4121
Fax: +55-19-3256 4661 jotoma 1@earthlink.net
pn1@p-vac.com.br www.equipmentandsystems.com
www.pvac.com.br
Croatia
Canada Baran ltd.
CTH Instruments Ltd. Ratka Petrovica 92
10 Akerley Blvd., Suite 36 51000 RIJEKA
Dartmouth, Nova Scotia, CN B3B 1J4 Croatia
Mr. Arnold Home Tel/Fax::+ 385-51-415 303
Tel.: +1-902-468-6832 Fax:: + 385-51-211 068
Fax: +1-902-468-6833 mate@scor.hr
arnold@cthinst.com
www.cthinst.com
(New Brunswick, Newfoundland, Nova
Scotia, Prince Edward Islands)