Gexol
Power Cables
• Single Conductor . . . . . . . . . . . . . . . . . . . . . . . . 2-3
• Two Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
• Three Conductor . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Severe Cold Durability Flame Retardant
Exceeds CSA Cold Bend / Certified to IEC 92-3 (332-3A) • Four Conductor. . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
Cold Impact (-40°C/-35°C) and IEEE 1580
• Five Conductor . . . . . . . . . . . . . . . . . . . . . . . . 10-11
n Best On-Time
• Individually Shielded Pairs . . . . . . . . . . . . . . . 14-15
• Individually Shielded Triads . . . . . . . . . . . . . . 16-17
Delivery Rate*
n Extremely Flexible
Gexol-HF Flame Retardant Low Smoke / Halogen-Free
Power Cables
*Visit www.nexansamercable.com for our • Single Conductor . . . . . . . . . . . . . . . . . . . . . . 18-19
most current on-time delivery rate
• Two Conductor . . . . . . . . . . . . . . . . . . . . . . . . 20-21
• Three Conductor . . . . . . . . . . . . . . . . . . . . . . . 22-23
• Four Conductor. . . . . . . . . . . . . . . . . . . . . . . . 24-25
• Five Conductor . . . . . . . . . . . . . . . . . . . . . . . . 26-27
Control Cable
• Multi-Conductor . . . . . . . . . . . . . . . . . . . . . . . 28-29
Instrumentation Cables
• Individually Shielded Pairs . . . . . . . . . . . . . . . 30-31
• Individually Shielded Triads . . . . . . . . . . . . . . 32-33
Nexans AmerCable believes the information presented throughout this catalog to be reliable and current. All information is subject to change without notice. The information
listed is approximate, and is presented only as a guide for product selection. We make no claims or warranties for the suitability of any product for any particular application.
1
37-104
Gexol®-331HF Fire Resistant
Single Conductor Power Cable • Low Smoke Halogen-Free
Extremely Flexible • 2kV • Rated 90°C
Application
Conductor Designed and constructed for the
Soft annealed flexible demanding environments of offshore
stranded tinned drilling and petroleum facilities located
copper per Insulation/Jacket
IEEE 1580 Table 11.
throughout the world. Primarily used
Fire resistant tape + on critical circuits that must continue
GEXOL®-HF low smoke,
Halogen-Free, flame
to function even in a fire condition.
retardant cross-linked, This product should be used on any
polyolefin insulation circuit dedicated to emergency lighting,
meeting the requirements fire detection/suppression, alarms and
Armor (Optional) for Type LSE or LSX of
IEEE 1580 plus a black
personnel egress.
Basket weave wire
low smoke Halogen-Free
armor per IEEE 1580
flame retardant, polyolefin
Features
and UL 1309/
CSA 245. jacket meeting IEEE 1580. Fire resistant: IEC 60331.
Bronze standard. 2000V/IEC 1000V.
Flame retardant: IEC 332-3 Category A
Tinned copper
available by request. and IEEE 1202.
Sheath (Optional)
A black low smoke
Low smoke and Halogen-Free.
Halogen-Free flame High strand count conductors make this
retardant polyolefin, product more flexible and easier to install
meeting IEEE 1580.
than IEC 60092-350 Series cables.
Severe cold durability: exceeds CSA
cold bend/cold impact (-40˚C/-35˚C).
Suitable for use in Class I, Division 1
and Zone 1 environments
(armored and sheathed).
Optional braid armor of bronze,
aluminum or tinned copper.
Ratings & Approvals
90˚C Temperature Rating
American Bureau of Shipping (ABS)
99-BT5905-X
NRTL Classified to IEEE STD. 1580
Hawke
Transport Canada Gland Types Unarmored Armored & Sheathed
Det Norske Veritas (DNV) Industrial &
(pending) Safe Area (IP68) 121 153-X
Lloyd’s Register of Shipping (LRS) Increased Safety
“EExe” 501/421 501/453/U
(pending) Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1
Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U
“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U
(2 liter or > enclosures)
Zone 1 & 2
Application
Conductor
Soft annealed flexible Designed and constructed for the
Insulation stranded tinned copper demanding environments of offshore
per IEEE 1580 Table 11. drilling and petroleum facilities located
Fire resistant tape +
GEXOL®-HF low smoke throughout the world. Primarily used
Halogen-Free flame on critical circuits that must continue
retardant cross-linked Jacket
polyolefin, meeting the A black low smoke
to function even in a fire condition.
requirements for Halogen-Free flame This product should be used on any
Type LSE or LSX of retardant polyolefin, circuit dedicated to emergency lighting,
IEEE 1580. meeting IEEE 1580. fire detection/suppression, alarms and
Color code: personnel egress.
Black-White
1/0 and larger use Features
insulation with
printed phase I.D.
Fire resistant: IEC 60331.
Flame retardant: IEC 332-3 Category A
and IEEE 1202.
Sheath (Optional) Low smoke and Halogen-Free.
A black, low smoke Armor (Optional)
Halogen-Free flame Basket weave wire armor per High strand count conductors make this
retardant polyolefin, IEEE 1580 and UL 1309/CSA product more flexible and easier to install
meeting IEEE 1580. 245. Bronze standard. than IEC 60092-350 Series cables.
Tinned copper available by
request. Severe cold durability: exceeds CSA
cold bend/cold impact (-40˚C/-35˚C).
Suitable for use in Class I, Division 1
and Zone 1 environments
(armored and sheathed).
Optional braid armor of bronze,
aluminum or tinned copper.
Ratings & Approvals
90˚C Temperature Rating
American Bureau of Shipping (ABS)
99-BT5905-X
NRTL Classified to IEEE STD. 1580
Hawke
Transport Canada Gland Types Unarmored Armored & Sheathed
Det Norske Veritas (DNV) Industrial &
(pending) Safe Area (IP68) 121 153-X
Lloyd’s Register of Shipping (LRS) Increased Safety
“EExe” 501/421 501/453/U
(pending)
Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1
Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U
“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U
(2 liter or > enclosures)
Zone 1 & 2
Conductor
Soft annealed flexible
Application
stranded tinned copper per Designed and constructed for the
IEEE 1580 Table 11.
demanding environments of offshore
Jacket
A black low smoke
drilling and petroleum facilities located
Insulation throughout the world. Primarily used
Halogen-Free flame
Fire resistant tape +
retardant polyolefin, on critical circuits that must continue
GEXOL®-HF low smoke
meeting IEEE 1580. to function even in a fire condition.
Halogen-Free flame
retardant cross-linked This product should be used on any
polyolefin, meeting circuit dedicated to emergency lighting,
the requirements for
Type LSE or LSX of
fire detection/suppression, alarms and
IEEE 1580. personnel egress.
Color code: Features
Black-White-Red
1/0 and larger use Fire resistant: IEC 60331.
insulation with Armor (Optional) Flame retardant: IEC 332-3 Category A
printed phase I.D.
Basket weave wire armor and IEEE 1202.
per IEEE 1580 and UL
Sheath (Optional) 1309/CSA 245. Bronze Low smoke and Halogen-Free.
A black low smoke standard. Tinned copper High strand count conductors make this
available by request.
Halogen-Free flame product more flexible and easier to install
retardant polyolefin,
than IEC 60092-350 Series cables.
meeting IEEE 1580.
An uninsulated
Severe cold durability: exceeds CSA
ground conductor cold bend/cold impact (-40˚C/-35˚C).
may be incorporated
Suitable for use in Class I, Division 1
on a make-to-order
basis. and Zone 1 environments
(armored and sheathed).
Optional braid armor of bronze,
Ratings & Approvals aluminum or tinned copper.
90˚C Temperature Rating
American Bureau of Shipping (ABS)
99-BT5905-X
NRTL Classified to IEEE STD. 1580
Hawke
Transport Canada Gland Types Unarmored Armored & Sheathed
Det Norske Veritas (DNV) Industrial &
(pending) Safe Area (IP68) 121 153-X
Lloyd’s Register of Shipping (LRS) Increased Safety
“EExe” 501/421 501/453/U
(pending)
Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1
Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U
“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U
(2 liter or > enclosures)
Zone 1 & 2
Conductor Application
Soft annealed flexible
stranded tinned copper
Designed and constructed for the
Insulation per IEEE 1580 Table 11. demanding environments of offshore
Fire resistant tape + GEXOL®- drilling and petroleum facilities located
HF low smoke Halogen-Free throughout the world. Primarily used
flame retardant cross-linked Jacket on critical circuits that must continue
polyolefin, meeting A black low smoke
the requirements for to function even in a fire condition.
Halogen-Free flame
Type LSE or LSX of retardant polyolefin,
This product should be used on any
IEEE 1580. meeting IEEE 1580. circuit dedicated to emergency lighting,
Color code: fire detection/suppression, alarms and
Black-White-Red-Green
personnel egress.
1/0 and larger use
insulation with Features
printed phase I.D.
Fire resistant: IEC 60331.
Flame retardant: IEC 332-3 Category A
Sheath (Optional) and IEEE 1202.
A black low smoke Armor (Optional)
Halogen-Free flame Low smoke and Halogen-Free.
Basket weave wire armor per
retardant polyolefin, High strand count conductors make this
IEEE 1580 and UL 1309/CSA
meeting IEEE 1580.
245. Bronze standard. Tinned product more flexible and easier to install
copper available by request.
than IEC 60092-350 Series cables.
Severe cold durability: exceeds CSA
cold bend/cold impact (-40˚C/-35˚C).
An uninsulated ground conductor
may be incorporated on a Suitable for use in Class I, Division 1
make-to-order basis. and Zone 1 environments
(armored and sheathed).
Optional braid armor of bronze,
aluminum or tinned copper.
Ratings & Approvals
90˚C Temperature Rating
American Bureau of Shipping (ABS)
99-BT5905-X
NRTL Classified to IEEE STD. 1580
Hawke
Transport Canada Gland Types Unarmored Armored & Sheathed
Det Norske Veritas (DNV) Industrial &
(pending) Safe Area (IP68) 121 153-X
Lloyd’s Register of Shipping (LRS) Increased Safety
“EExe” 501/421 501/453/U
(pending)
Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1
Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U
“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U
(2 liter or > enclosures)
Zone 1 & 2
Conductors Application
Soft annealed flexible
stranded tinned copper per Designed and constructed for the
IEEE 1580 Table 11. Insulation demanding environments of offshore
Fire resistant tape + drilling and petroleum facilities located
GEXOL®-HF low smoke
Halogen-Free flame
throughout the world. Primarily used
retardant cross-linked on critical circuits that must continue
Jacket
polyolefin, meeting to function even in a fire condition.
the requirements for This product should be used on any
A black low smoke Type LSE or LSX of
Halogen-Free flame IEEE 1580. circuit dedicated to emergency lighting,
retardant polyolefin, fire detection/suppression, alarms and
meeting IEEE 1580. Color code: personnel egress.
Black-White-Red-
Green-Orange Features
1/0 and larger use Fire resistant: IEC 60331.
insulation with
printed phase I.D. Flame retardant: IEC 332-3 Category A
Armor (Optional) and IEEE 1202.
Basket weave wire Low smoke and Halogen-Free.
armor per IEEE 1580 and
UL 1309/CSA 245. Bronze Sheath (Optional) High strand count conductors make this
standard. Tinned copper A black low smoke product more flexible and easier to install
available by request. Halogen-Free flame
retardant polyolefin,
than IEC 60092-350 Series cables.
meeting IEEE 1580. Severe cold durability: exceeds CSA
cold bend/cold impact (-40˚C/-35˚C).
Suitable for use in Class I, Division 1
and Zone 1 environments
(armored and sheathed).
Optional braid armor of bronze,
aluminum or tinned copper.
Ratings & Approvals
90˚C Temperature Rating
American Bureau of Shipping (ABS)
99-BT5905-X
NRTL Classified to IEEE STD. 1580
Hawke
Transport Canada Gland Types Unarmored Armored & Sheathed
Det Norske Veritas (DNV) Industrial &
(pending) Safe Area (IP68) 121 153-X
Lloyd’s Register of Shipping (LRS) Increased Safety
“EExe” 501/421 501/453/U
(pending)
Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1
Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U
“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U
GEXOL® is a registered trademark of AmerCable Incorporated. (2 liter or > enclosures)
Zone 1 & 2
Conductors Application
Soft annealed flexible Designed and constructed for the
stranded tinned copper Insulation
per IEEE 1580 Table 11.
demanding environments of offshore
Fire resistant tape + GEXOL®-HF drilling and petroleum facilities located
low smoke Halogen-Free flame
retardant cross-linked polyolefin, throughout the world. Primarily used
Jacket meeting the requirements for on critical circuits that must continue
A black low smoke Type LSE or LSX of IEEE 1580. to function even in a fire condition.
Halogen-Free flame
retardant polyolefin, Color code: This product should be used on any
meeting IEEE 1580. ICEA K-1, Method 1. For less circuit dedicated to emergency lighting,
than minimum order quantities,
Method 3 may be used.
fire detection/suppression, alarms and
personnel egress.
Colored singles through 37/C.
Black ink printed singles Features
above 37/C.
Fire resistant: IEC 60331.
Sheath (Optional)
Flame retardant: IEC 332-3 Category A
Armor (Optional)
A black low smoke
and IEEE 1202.
Basket weave wire armor
Halogen-Free flame per IEEE 1580 and UL Low smoke and Halogen-Free.
retardant polyolefin, 1309/CSA 245. Bronze
meeting IEEE 1580. standard. Tinned copper High strand count conductors make this
available by request. product more flexible and easier to install
than IEC 60092-350 Series cables.
Severe cold durability: exceeds CSA
cold bend/cold impact (-40˚C/-35˚C).
Suitable for use in Class I, Division 1
and Zone 1 environments
(armored and sheathed).
Optional braid armor of bronze,
Ratings & Approvals aluminum or tinned copper.
90˚C Temperature Rating
American Bureau of Shipping (ABS)
99-BT5905-X
NRTL Classified to IEEE STD. 1580
Hawke
Transport Canada Gland Types Unarmored Armored & Sheathed
Det Norske Veritas (DNV) Industrial &
(pending) Safe Area (IP68) 121 153-X
Lloyd’s Register of Shipping (LRS) Increased Safety
“EExe” 501/421 501/453/U
(pending)
Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1
Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U
“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U
(2 liter or > enclosures)
Zone 1 & 2
Application
Conductor
Smoke, with its toxic and corrosive effects, is
Soft annealed flexible
becoming more clearly recognized as the real
stranded tinned culprit in fire fatalities. And there is increasing
copper per Insulation/Jacket concern about smoke evolution in confined spaces
IEEE 1580 Table 11. or areas of limited egress. Low smoke, Halogen-
GEXOL®-HF low smoke,
Halogen-Free flame Free, Gexol-HF should be used in the living
retardant cross-linked, quarters area to insure safe egress of personnel
polyolefin insulation
meeting the requirements during a fire. Gexol-HF does not produce corrosive
for Type LSE or LSX gases during a fire that might damage expensive
Armor (Optional) of IEEE 1580 plus a electronic equipment, making it ideal for use in
Basket weave wire black low smoke
Halogen-Free flame
control rooms that house
armor per IEEE 1580
and UL 1309/ retardant polyolefin jacket this equipment.
CSA 245. meeting IEEE 1580.
Bronze standard. 2000V/IEC 1000V. Features
Tinned copper Flame retardant: IEC 332-3 Category A
available by request. and IEEE 1202.
Sheath (Optional)
A black low smoke Low smoke and Halogen-Free.
Halogen-Free flame High strand count conductors make this product
retardant polyolefin,
meeting IEEE 1580. more flexible and easier to install
than IEC 60092-350 Series cables.
Severe cold durability: exceeds CSA cold
bend/cold impact (-40˚C/-35˚C).
Suitable for use in Class I, Division 1 and Zone 1
environments (armored and sheathed).
Optional braid armor of bronze, aluminum
or tinned copper.
Ratings & Approvals
90˚C Temperature Rating
American Bureau of Shipping (ABS)
99-BT5905-X
NRTL Classified to IEEE STD. 1580
Hawke
Transport Canada Gland Types Unarmored Armored & Sheathed
Det Norske Veritas (DNV) Industrial &
(pending) Safe Area (IP68) 121 153-X
Lloyd’s Register of Shipping (LRS) Increased Safety
“EExe” 501/421 501/453/U
(pending)
Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1
Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U
“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U
(2 liter or > enclosures)
Zone 1 & 2
Application
Conductor
Smoke, with its toxic and corrosive effects, is
Soft annealed flexible
stranded tinned copper becoming more clearly recognized as the real
Insulation
per IEEE 1580 Table 11. culprit in fire fatalities. And there is increasing
GEXOL®-HF low smoke
Halogen-Free flame concern about smoke evolution in confined
retardant cross-linked spaces or areas of limited egress. Low smoke,
polyolefin, meeting Jacket Halogen-Free, Gexol-HF should be used in the
the requirements for A black low smoke
Type LSE or LSX Halogen-Free flame
living quarters area to insure safe egress of
of IEEE 1580. retardant polyolefin, personnel during a fire. Gexol-HF does not
IEEE 1580. meeting IEEE 1580. produce corrosive gases during a fire that
Color code: might damage expensive electronic equipment,
Black-White making it ideal for use in control rooms that
1/0 and larger use house this equipment.
insulation with
printed phase I.D. Features
Flame retardant: IEC 332-3 Category A
and IEEE 1202.
Sheath (Optional) Low smoke and Halogen-Free.
A black, low smoke Armor (Optional)
Halogen-Free flame Basket weave wire armor per High strand count conductors make this
retardant polyolefin, IEEE 1580 and UL 1309/CSA product more flexible and easier to install
meeting IEEE 1580. 245. Bronze standard.
than IEC 60092-350 Series cables.
Tinned copper available by
request. Severe cold durability: exceeds CSA cold
bend/cold impact (-40˚C/-35˚C).
Suitable for use in Class I, Division 1 and Zone
1 environments (armored and sheathed).
Optional braid armor of bronze, aluminum
or tinned copper.
Ratings & Approvals
90˚C Temperature Rating
American Bureau of Shipping (ABS)
99-BT5905-X
NRTL Classified to IEEE STD. 1580
Transport Canada Hawke
Gland Types Unarmored Armored & Sheathed
Det Norske Veritas (DNV)
Industrial &
(pending) Safe Area (IP68) 121 153-X
Lloyd’s Register of Shipping (LRS) Increased Safety
“EExe” 501/421 501/453/U
(pending)
Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1
Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U
“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U
(2 liter or > enclosures)
Zone 1 & 2
Conductor
Soft annealed flexible
Application
stranded tinned copper per Smoke, with its toxic and corrosive effects, is
IEEE 1580 Table 11. becoming more clearly recognized as the real
Jacket culprit in fire fatalities. And there is increasing
Insulation A black low smoke concern about smoke evolution in confined
Halogen-Free flame
GEXOL -HF low smoke
®
retardant polyolefin, spaces or areas of limited egress. Low smoke,
Halogen-Free flame Halogen-Free, Gexol-HF should be used in the
meeting IEEE 1580.
retardant cross-linked
polyolefin, meeting living quarters area to insure safe egress of
the requirements for personnel during a fire. Gexol-HF does not
Type LSE or LSX produce corrosive gases during a fire that
of IEEE 1580.
might damage expensive electronic equipment,
IEEE 1580.
making it ideal for use in control rooms that
Color code:
Black-White-Red house this equipment.
1/0 and larger use Features
insulation with Armor (Optional)
printed phase I.D.
Flame retardant: IEC 332-3 Category A
Basket weave wire armor and IEEE 1202.
per IEEE 1580 and UL
Sheath (Optional) 1309/CSA 245. Bronze Low smoke and Halogen-Free.
A black low smoke standard. Tinned copper
available by request.
High strand count conductors make this
Halogen-Free flame
retardant polyolefin, product more flexible and easier to install
meeting IEEE 1580. than IEC 60092-350 Series cables.
An uninsulated Severe cold durability: exceeds CSA cold
ground conductor bend/cold impact (-40˚C/-35˚C).
may be incorporated
on a make-to-order Suitable for use in Class I, Division 1 and Zone
basis. 1 environments (armored and sheathed).
Optional braid armor of bronze, aluminum
or tinned copper.
Ratings & Approvals
90˚C Temperature Rating
American Bureau of Shipping (ABS)
99-BT5905-X
NRTL Classified to IEEE STD. 1580
Transport Canada Hawke
Gland Types Unarmored Armored & Sheathed
Det Norske Veritas (DNV)
Industrial &
(pending) Safe Area (IP68) 121 153-X
Lloyd’s Register of Shipping (LRS) Increased Safety
“EExe” 501/421 501/453/U
(pending)
Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1
Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U
“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U
(2 liter or > enclosures)
Zone 1 & 2
Conductor Application
Soft annealed flexible
stranded tinned copper
Designed and constructed for the
Insulation per IEEE 1580 Table 11. demanding environments of offshore
Fire resistant tape + GEXOL®- drilling and petroleum facilities located
HF low smoke Halogen-Free throughout the world. Primarily used
flame retardant cross-linked Jacket on critical circuits that must continue
polyolefin, meeting A black low smoke
the requirements for to function even in a fire condition.
Halogen-Free flame
Type LSE or LSX of retardant polyolefin,
This product should be used on any
IEEE 1580. meeting IEEE 1580. circuit dedicated to emergency lighting,
Color code: fire detection/suppression, alarms and
Black-White-Red-Green
personnel egress.
1/0 and larger use
insulation with Features
printed phase I.D.
Fire resistant: IEC 60331.
Flame retardant: IEC 332-3 Category A
Sheath (Optional) and IEEE 1202.
A black low smoke Armor (Optional)
Halogen-Free flame Low smoke and Halogen-Free.
Basket weave wire armor per
retardant polyolefin, High strand count conductors make this
IEEE 1580 and UL 1309/CSA
meeting IEEE 1580.
245. Bronze standard. Tinned product more flexible and easier to install
copper available by request.
than IEC 60092-350 Series cables.
Severe cold durability: exceeds CSA
cold bend/cold impact (-40˚C/-35˚C).
An uninsulated ground conductor
may be incorporated on a Suitable for use in Class I, Division 1
make-to-order basis. and Zone 1 environments
(armored and sheathed).
Optional braid armor of bronze,
aluminum or tinned copper.
Ratings & Approvals
90˚C Temperature Rating
American Bureau of Shipping (ABS)
99-BT5905-X
NRTL Classified to IEEE STD. 1580
Hawke
Transport Canada Gland Types Unarmored Armored & Sheathed
Det Norske Veritas (DNV) Industrial &
(pending) Safe Area (IP68) 121 153-X
Lloyd’s Register of Shipping (LRS) Increased Safety
“EExe” 501/421 501/453/U
(pending)
Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1
Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U
“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U
(2 liter or > enclosures)
Zone 1 & 2
Conductors Application
Soft annealed flexible Smoke, with its toxic and corrosive effects, is
stranded tinned copper per
IEEE 1580 Table 11. Insulation becoming more clearly recognized as the real
GEXOL®-HF low smoke culprit in fire fatalities. And there is increasing
Halogen-Free flame concern about smoke evolution in confined
retardant cross-linked
spaces or areas of limited egress. Low smoke,
polyolefin, meeting
the requirements for Halogen-Free, Gexol-HF should be used in the
Jacket Type LSE or LSX living quarters area to insure safe egress of
A black low smoke of IEEE 1580.
Halogen-Free flame
personnel during a fire. Gexol-HF does not
Color code: produce corrosive gases during a fire that
retardant polyolefin,
Black-White-Red-
meeting IEEE 1580.
Green-Orange
might damage expensive electronic equipment,
making it ideal for use in control rooms that
1/0 and larger use
insulation with house this equipment.
printed phase I.D.
Features
Flame retardant: IEC 332-3 Category A
Armor (Optional) and IEEE 1202.
Basket weave wire
armor per IEEE 1580 and
Low smoke and Halogen-Free.
UL 1309/CSA 245. Bronze Sheath (Optional) High strand count conductors make this
standard. Tinned copper A black low smoke
Halogen-Free flame
product more flexible and easier to install
available by request.
retardant polyolefin, than IEC 60092-350 Series cables.
meeting IEEE 1580. Severe cold durability: exceeds CSA cold
bend/cold impact (-40˚C/-35˚C).
Suitable for use in Class I, Division 1 and Zone
1 environments (armored and sheathed).
Optional braid armor of bronze, aluminum
or tinned copper.
Ratings & Approvals
90˚C Temperature Rating
American Bureau of Shipping (ABS)
99-BT5905-X
NRTL Classified to IEEE STD. 1580
Transport Canada Hawke
Gland Types Unarmored Armored & Sheathed
Det Norske Veritas (DNV)
Industrial &
(pending) Safe Area (IP68) 121 153-X
Lloyd’s Register of Shipping (LRS) Increased Safety
“EExe” 501/421 501/453/U
(pending)
Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1
Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U
“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U
GEXOL® is a registered trademark of AmerCable Incorporated. (2 liter or > enclosures)
Zone 1 & 2
Conductors Application
Soft annealed flexible Smoke, with its toxic and corrosive effects, is
stranded tinned copper Insulation becoming more clearly recognized as the real
per IEEE 1580 Table 11.
GEXOL®-HF low smoke Halogen- culprit in fire fatalities. And there is increasing
Free flame retardant cross-linked concern about smoke evolution in confined
polyolefin, meeting the
Jacket requirements for Type LSE
spaces or areas of limited egress. Low smoke,
A black low smoke or LSX of IEEE 1580. Halogen-Free, Gexol-HF should be used in the
Halogen-Free flame living quarters area to insure safe egress of
retardant polyolefin, Color code:
meeting IEEE 1580. ICEA K-1, Method 1. For less personnel during a fire. Gexol-HF does not
than minimum order quantities, produce corrosive gases during a fire that
Method 3 may be used. might damage expensive electronic equipment,
Colored singles through 37/C. making it ideal for use in control rooms that
Black ink printed singles above house this equipment.
37/C.
Features
Sheath (Optional) Armor (Optional) Flame retardant: IEC 332-3 Category A
A black low smoke Basket weave wire armor and IEEE 1202.
Halogen-Free flame per IEEE 1580 and UL Low smoke and Halogen-Free.
retardant polyolefin, 1309/CSA 245. Bronze
meeting IEEE 1580. standard. Tinned copper High strand count conductors make this
available by request. product more flexible and easier to install
than IEC 60092-350 Series cables.
Severe cold durability: exceeds CSA cold
bend/cold impact (-40˚C/-35˚C).
Suitable for use in Class I, Division 1 and Zone
1 environments (armored and sheathed).
Optional braid armor of bronze, aluminum
or tinned copper.
Ratings & Approvals
90˚C Temperature Rating
American Bureau of Shipping (ABS)
99-BT5905-X
NRTL Classified to IEEE STD. 1580
Transport Canada Hawke
Gland Types Unarmored Armored & Sheathed
Det Norske Veritas (DNV)
Industrial &
(pending) Safe Area (IP68) 121 153-X
Lloyd’s Register of Shipping (LRS) Increased Safety
“EExe” 501/421 501/453/U
(pending)
Explosion Proof 710 753
Class I, Div. 2 Class I, Div. 1
Class I, Zone 2 Class I, Zone 1 & 2
Flameproof 501/421 501/453/U
“EExd” Zone 1 & 2 (2 liter or < enclosures)
ICG 653/U
(2 liter or > enclosures)
Zone 1 & 2
Application
Power Conductors (x3)
A flexible, braid and foil shielded, 2kV power
Soft annealed flexible Ground
stranded tinned copper Conductors (x3) cable specifically engineered for use in variable
per IEEE 1580 Table 11. Soft annealed flexible frequency AC motor drive (VFD) applications
stranded tinned copper where a low smoke halogen-free insulation is
Insulation (2kV) per IEEE 1580 Table 11. required.
GEXOL®-HF low smoke Gexol®-HF insulated
halogen-free flame and sized per UL 1277. Features
n Low Smoke and Halogen-Free.
retardant cross-linked Color: Green
Nexans AmerCable is an ISO 9001 certified cable What can you expect from Nexans
manufacturer that combines leading-edge manufacturing
technology, innovative thinking, and high
AmerCable?
quality service to deliver the finest oil & gas n Fastest Lead Times in the Industry
n On-Time Delivery
cable and engineered cable assemblies
Foil shielded,
Type MC-HL Top Drive power cables
Cables Service engineered for
Loops
use in variable
frequency
AC drive
applications.
Available in several
constructions